10 AMP TRACK MOUNT CONTROL RELAY
RIBMN2401D
2.75˝ Track Mount Relay 10 Amp DPDT with
24 Vac/dc/120 Vac Coil
N/O
120 Vac
Comm
Made in USA
Meets
“Buy American”
of ARRA 2009
24 Vac/dc
Comm
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Track Mount:
Approvals:
Gold Flash:
Override Switch:
N/C
N/O
Comm
N/C
One (1) DPDT Continuous Duty Coil
10 million c
ycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
8ms
LED On = Activated
1.700˝ x 2.750˝ x 1.750˝
2.750˝, See MT212 Series on page 152
MT212 Mounting Track Sold Separately
UL Listed, UL916, UL864, C-UL
California State Fire Marshal
No
No
Contact Ratings:
10 Amp Resistive @ 30 Vdc
10 Amp General Use @ 277 Vac
1/2 HP @ 120/240 Vac (N/O)
1/3 HP @ 120/240 Vac (N/C)
B300 Pilot Duty
120 Vac 30A Make 3A Break (360 VA)
240 Vac 15 A Make 1.5A Break (360 VA)
208 Vac 17.3A Make 1.73A Break (360 VA)
277 Vac 13A Make 1.3A Break (360 VA)
24 Vac 30A Make 5A Break (120VA) 5A Max
Coil Current:
36 mA @ 30Vdc
24 mA @ 18 Vac
32 mA @ 24 Vac
40 mA @ 30 Vac
31 mA @ 120 Vac
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz
Drop Out = 3 Vac / 3.8 Vdc
Pull In = 18 Vac / 20 Vdc
071417