DRY CONTACT INPUT TRACK MOUNT RELAYS
RIBM013PNDC
4.00˝ Track Mount Relay 30 Amp 3PDT, Class 2
Dry Contact Input, 120 Vac Power Input
N/C
N/O
DRY CONTACT
POWER INPUT
120 Vac
Neutral
INPUT
CONTROL
CIRCUIT
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Power Status:
Dimensions:
Track Mount:
Approvals:
Gold Flash:
Override Switch:
Comm
N/C
N/O
Comm
N/C
N/O
Comm
One (1) 3PDT Continuous Duty Coil 10
million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
Red LED On = Activated
Green LED On = Activated
2.875˝ x 4.000˝ x 1.750˝
4.000˝, See MT4 Series on page 152
MT4 Mounting Track Sold Separately
UL Component Recognized, UL916 CUL
No
No
Contact Ratings:
30 Amp Resistive @ 300 Vac
30 Amp Resistive @ 28 Vdc
15 Amp Resistive @ 600 Vac
7.5 HP @ 480 Vac, 3 Phase
5 HP @ 240 Vac, 3 Phase
3 HP @ 480-600 Vac, 1 Phase
2 HP @ 240/277 Vac, 1 Phase
1 HP @ 120 Vac, 1Phase
20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
Heavy Pilot Duty
770 VA @ 120 Vac, 1 Phase
1158 VA @ 240 Vac, 1 Phase
1109 VA @ 277 Vac, 1 Phase
1640 VA @ 480 Vac, 1 Phase
1466 VA @ 240 Vac, 3 Phase
2122 VA @ 480 Vac, 3 Phase
Made in USA
Meets
“Buy American”
of ARRA 2009
Power Input:
95 mA @ 120 Vac
Notes:
• Dry Contact Input Operation:
Close dry contact to activate relay.
071417