15 AMP PILOT CONTROL RELAYS
RIBU1CW
Enclosed Relay Hi/Low Separation 15 Amp SPDT
with 10-30 Vac/dc/120 Vac Coil
Comm
10-30
Vac/dc
120
Vac
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT nipple
UL Listed, UL916, UL864, C-UL California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
Yes
No
N/O
N/C
Comm
RIBH1CW
Enclosed Relay Hi/Low Separation 15 Amp SPDT
with 10-30 Vac/dc/208-277 Vac Coil
Comm
10-30
Vac/dc
208-277
Vac
Contact Ratings:
15 Amp Resistive @ 150 Vac, 28Vdc
15 Amp Inductive @ 150 Vac
10 Amp Resistive @ 277 Vac
480 VA Pilot Duty @ 240-277 Vac
480 VA Ballast @ 277 Vac
Not rated for Electronic Ballast
600 Watt Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
N/O
N/C
Comm
Made in USA
Meets
“Buy American”
of ARRA 2009
Coil Current:
33 mA @ 10 Vac
35 mA @ 12 Vac
46 mA @ 24 Vac
55 mA @ 30 Vac
13 mA @ 10 Vdc
15 mA @ 12 Vdc
18 mA @ 24 Vdc
20 mA @ 30 Vdc
28 mA @ 120 Vac (RIBU1CW)
39 mA @ 208-277 Vac (RIBH1CW)
Coil Voltage Input:
10-30 Vac/dc ; 120 Vac ; 50-60 Hz (RIBU1CW)
10-30 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBH1CW)
Drop Out = 2.1 Vac / 2.8 Vdc
Pull In = 9 Vac / 10 Vdc
071417