RIB,Relay In A Box,Functional Devices RIB12P, RIB12P30 Data Sheet

RELAYS
20 / 30 AMP POWER CONTROL RELAYS
RIB12P
Enclosed Relay 20 Amp DPDT with 12 Vac/dc Coil
Wht/Yel
12 Vac/dc
Wht/Yel
12 Vac/dc
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) DPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms LED On = Activated
2.30˝ x 3.20˝ x 1.80˝ with .50˝ NPT Nipple (RIB12P)
2.30˝ x 3.20˝ x 1.80˝ with .75˝ NPT Nipple (RIB12P30) 16˝, 600V Rated
Wires:
UL Listed, UL60947, C-UL UL Accepted for Use in Plenum, NEMA 1 Yes No
Blu N/C
Yel
Comm
Org
N/O
Gry N/C
Prp
Comm
Brn N/O
RIB12P30
Enclosed Relay 30 Amp DPDT with 12 Vac/dc Coil
Wht/Yel
12 Vac/dc
Wht/Yel
12 Vac/dc
Contact Ratings: (RIB12P)
20 Amp Resistive @ 300 Vac 20 Amp Resistive @ 28 Vdc 15 Amp Resistive @ 600 Vac 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
770 VA Pilot Duty @ 120 Vac 1158 VA Pilot Duty @ 240 Vac 1109 VA Pilot Duty @ 277 Vac 1640 VA Pilot Duty @ 480 Vac Heavy Pilot Duty @ 600 Vac 3 HP @ 480-600 Vac 2 HP @ 240-277 Vac 1 HP @ 120 Vac
Blu N/C
Yel
Comm
Org
N/O
Gry N/C
Prp
Comm
Brn N/O
Contact Ratings: (RIB12P30)
30 Amp Resistive @ 300 Vac 25 Amp Resistive @ 28 Vdc 15 Amp Resistive @ 600 Vac 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
770 VA Pilot Duty @ 120 Vac 1158 VA Pilot Duty @ 240 Vac 1110 VA Pilot Duty @ 277 Vac 1640 VA Pilot Duty @ 480 Vac Heavy Pilot Duty @ 600 Vac 3 HP @ 480-600 Vac 2 HP @ 240-277 Vac 1 HP @ 120 Vac
Made in USA
Meets
Buy American
of ARRA 2009
Coil Current:
115 mA @ 10 Vac 180 mA @ 12 Vac 79 mA @ 11 Vdc 90 mA @ 12 Vdc 115 mA @ 15 Vdc
Coil Voltage Input:
12 Vac/dc ; 50-60 Hz Drop Out = 4.5 Vac / 4.8 Vdc Pull In = 9.7 Vac / 11 Vdc
071417