UNINTERRUPTIBLE POWER SUPPLY KIT BACNET® COMPATIBLE
PSH550-UPS-BC
Enclosed BACnet® Network 550 VA UPS Backup Power Control Center
UPS Output
to protected
device
UPS
SPECIFICATIONS
BOARD AND ENCLOSURE:
Operating Temperature:
Humidity Range:
Indicators:
Main Breaker ON/OFF:
Dimensions:
Track Mount:
Approvals:
Line Input:
Convenience Receptacles:
-30 to 140° F
5 to 95% (noncondensing)
Device Power: Red LED
Device Status: Pink LED
Network Communication: Green LED
Backup Power: Yellow LED
USB Status: Blue LED
Switch / Breaker (10 Amp)
12” x 16˝ x 6˝
2.750˝ x 8.000˝
MT212-8N Mounting Track Included
UL Listed, UL916, C-UL
120Vac, 10A(max)
120Vac, 10A(max combined)
Information provided over BACnet®
network can be used to schedule
“predictive maintenance” such as UPS
battery replacement, etc.
Line Input
Line
Gnd.
Neut.
RESET
Gnd.
Line
Neut.
OFF
}
UPS plugged into one of two
outlets. Other outlet spare.
To UPS
1 2 3 4 5 6 7 8 9 10
OPEN
B(
EOL
Jumper
Yellow LED =
Backup Power
Red LED = Device Power
Power Input Rating:
25mA @ 120Vac
Network Media:
Twisted Pair 22-24 AWG, shielded recommended (MS/TP)
USB A/B (device to UPS, included)
Terminations:
Functional Devices product installed at both ends of the
MS/TP network - Use 120 Ohm End of Line Resistors. All
other cases follow instructions from the device installed
at the end of the MS/TP network.
Polarity:
Network is polarity sensitive.
Baud Rate:
9600, 192000, 38400, 76800, 115200 ( DIP Switch Selectable)
All other combinations=9600 baud
Blue LED =
USB Status
Green LED = Network Comm.
Pink LED = Device Status
DIP SWITCHES* BAUD RAT E
8 9 10
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
A(-)
REF
+
)
BACnet®
comm.
USB Jack
9600
19200
38400
57600
76800
115200
Shown
With
Cover
Made in USA
Meets
“Buy American”
of ARRA 2009
Shown Without Cover
Notes:
• Circuit breaker for short-circuit protection.
• 14/3 Line Cord included (3´).
BACnet® Details:
• MS/TP Address & Baud Rate must be set prior
to power up via DIP switches.
• Device ID will default to 277XXX where XXX is
the MS/TP Address.
Examples:
MS/TP Address - 004
Device ID - 277004
MS/TP Address - 121
Device ID - 277121
• Device ID can be changed via network
command. Once changed, it will no longer
default to 277XXX. (MS/TP Address & Device
ID must be unique.)
•
Devices Instance changed via Object
Identier Property of Device Object.
• Status of UPS connection, Battery run time,
line power ,UPS load (VA and %), and battery
capacity can be read from BACnet network.
UPS:
Backup Time:
Input:
Output:
Max Load:
Frequency:
Temperature Rating of UPS:
UPS Transfer Time:
Approvals:
Kit Weight:
UPS:
550VA
3 Min. @ Full 550 VA Load
15 Min. @ 1/2 Load
120 Vac, 12 Amp
120 Vac, 4.6 Amp
330 Watt
50/60 Hz
32 to 104° F
6ms
UL Listed, UL1778
25.22 lbs
Notes:
• Average battery life: 3-5 years
depending on the number of discharge
cycles and environmental temperature
• This model is not designed to notify user
of battery failure.
• This model is designed to work
exclusively with Functional Devices
Model UPS550
ESTIMATED BACKUP TIME VS. LOAD
60
50
40
30
20
Backup Time (Minutes)
10
0
0 50 100 150 200 250 300 350
Load (Watts)
071217