RIB,Relay In A Box,Functional Devices PSH550-UPS-BC Data Sheet

POWER
CONTROL
UNINTERRUPTIBLE POWER SUPPLY KIT  BACNET® COMPATIBLE
PSH550-UPS-BC
Enclosed BACnet® Network 550 VA UPS Backup Power Control Center
UPS Output
to protected
device
UPS
SPECIFICATIONS
BOARD AND ENCLOSURE:
Operating Temperature:
Humidity Range:
Indicators:
Main Breaker ON/OFF:
Track Mount:
Approvals: Line Input:
Convenience Receptacles:
-30 to 140° F 5 to 95% (noncondensing) Device Power: Red LED Device Status: Pink LED Network Communication: Green LED Backup Power: Yellow LED USB Status: Blue LED
Switch / Breaker (10 Amp) 12” x 16˝ x 6˝
2.750˝ x 8.000˝ MT212-8N Mounting Track Included UL Listed, UL916, C-UL 120Vac, 10A(max) 120Vac, 10A(max combined)
Information provided over BACnet®
network can be used to schedule
“predictive maintenance” such as UPS
battery replacement, etc.
Line Input
Line
Gnd.
Neut.
RESET
Gnd.
Line
Neut.
OFF
}
UPS plugged into one of two
outlets. Other outlet spare.
To UPS
1 2 3 4 5 6 7 8 9 10
OPEN
B(
EOL
Jumper
Yellow LED =
Backup Power
Red LED = Device Power
Power Input Rating:
25mA @ 120Vac
Network Media:
Twisted Pair 22-24 AWG, shielded recommended (MS/TP) USB A/B (device to UPS, included)
Terminations:
Functional Devices product installed at both ends of the MS/TP network - Use 120 Ohm End of Line Resistors. All other cases follow instructions from the device installed at the end of the MS/TP network.
Polarity:
Network is polarity sensitive.
Baud Rate:
9600, 192000, 38400, 76800, 115200 ( DIP Switch Selectable)
All other combinations=9600 baud
Blue LED = USB Status
Green LED = Network Comm.
Pink LED = Device Status
DIP SWITCHES* BAUD RAT E
8 9 10
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
A(-) REF
+
)
BACnet®
comm.
USB Jack
9600
19200
38400
57600
76800
115200
Shown
With
Cover
Made in USA
Meets
Buy American
of ARRA 2009
Shown Without Cover
Notes:
Circuit breaker for short-circuit protection.
14/3 Line Cord included (3´).
BACnet® Details:
MS/TP Address & Baud Rate must be set prior
to power up via DIP switches.
Device ID will default to 277XXX where XXX is
the MS/TP Address. Examples:
MS/TP Address - 004 Device ID - 277004
MS/TP Address - 121 Device ID - 277121
Device ID can be changed via network
command. Once changed, it will no longer default to 277XXX. (MS/TP Address & Device ID must be unique.)
Devices Instance changed via Object
Identier Property of Device Object.
Status of UPS connection, Battery run time,
line power ,UPS load (VA and %), and battery capacity can be read from BACnet network.
UPS:
Backup Time:
Input:
Output:
Max Load:
Frequency:
Temperature Rating of UPS:
UPS Transfer Time:
Approvals: Kit Weight:
UPS:
550VA 3 Min. @ Full 550 VA Load 15 Min. @ 1/2 Load 120 Vac, 12 Amp 120 Vac, 4.6 Amp 330 Watt 50/60 Hz 32 to 104° F 6ms UL Listed, UL1778
25.22 lbs
Notes:
Average battery life: 3-5 years
depending on the number of discharge cycles and environmental temperature
This model is not designed to notify user
of battery failure.
This model is designed to work
exclusively with Functional Devices Model UPS550
ESTIMATED BACKUP TIME VS. LOAD
60
50
40
30
20
Backup Time (Minutes)
10
0
0 50 100 150 200 250 300 350
Load (Watts)
071217