RIB,Relay In A Box,Functional Devices PSH100A100A Series Data Sheet

POWER
SUPPLIES
AC POWER SUPPLY
PSH100A100A Series
Enclosed Dual 100 VA Power Supplies, 120 to 24 Vac
24 Vac On/O Switch
24 Vac Breaker
120 Vac Convenience Outlet *
24 Vac Breaker
ON OFF
RESET
Com 24 Vac
* Move internal jumper to “HOT”
position if you wish outlets to always be hot otherwise outlets will be switched by main breaker.
Com 24 Vac
120 Vac Convenience Outlet *
10 Amp Main Breaker/Switch
SPECIFICATIONS
Over Current Protection:
Transformer:
Frequency:
24 Vac ON/OFF:
Main Breaker ON/OFF:
Temperature:
Approvals:
Dimensions:
Weight:
24 Vac
ON OFF
On/O Switch
LED Indicator
Two 100 VA Split-Bobbin Circuit Breaker 50/60 Hz On / O Switch & Breaker Switch / Breaker (10 Amp) (Kills power to entire unit: Outlets, Aux. Output, & Transformer)* Total C
ombined Output 9A 40° C Class 2 (UL Approved UL5085-3), UL916, UL508 for -IC models, C-UL,
^ Seismic Certification of Equipment and Components: OSP-0201-10
4.500˝ x 8.625˝ x 4.500˝
8.600 lbs.
Made in USA
Class 2
8.625”
8.250”
ON OFF
RESET
OFF
8.250”
ON OFF
Output Wires:
4.500”
PSH100A100A SERIES SELECTION GUIDE
4.250”
4.500”
Input Wires: “B10˝ Models Only
Model #
PSH100A100A
PSH100A100AN
PSH100A100ANW
PSH100A100AW
PSH100A100AB10*
PSH100A100ANB10*
PSH100A100ANWB10*
PSH100A100AWB10*
Input Power Wires BLK: 120 Vac WHT: Neutral GRN: Ground
Outlet Wires BLK: 120 Vac WHT: Neutral GRN: Ground
“B10˝ Models Only
Auxiliary Output BLU: 120 Vac
120 Vac Outlets
All Other Models
Primary Wires BLK: 120 Vac WHT: Common
“W˝ Models Only
Transformer Output WHT/YEL: 24 Vac WHT/BLU: Common
Aux Output
Wire
Main Breaker on
Input Power
10 Amp Switch / Breaker External Terminal Strip
10 Amp Switch / Breaker External Terminal Strip
10 Amp Switch / Breaker Internal Wires
10 Amp Switch / Breaker Internal Wires
Notes:
All dual models: Model number denotes
location of transformer within enclosure.
PSH100A100A
Left side Right side
Output derating may exceed 20% due to
elevated ambient temperature or heat buildup in device over time.
To order UL508, add “-IC” to end of
model number.
Design is in accordance with ASCE 7-05
Chapter 13: ^
www.oshpd.ca.gov/FDD/Pre-Approval/ OSP-0201-10.pdf
External Terminal Strip
External Terminal Strip
Meets
Buy American
of ARRA 2009
Secondary
Conguration
Internal Wires
Internal Wires
071117