RIB Functional Devices RIBW24B-EN3, RIBW01B-EN3, RIBW208B-EN3, RIBW240B-EN3, RIBW277B-EN3 Applications Manual

...
LRN CLR
902 MHz Wireless Relays Application Manual
Bulletin B1867
RIBWxxxB-EN3
RIBWxxC-EN3
WDWS-EN3 WWS2-EN3
WKC-EN3
WVSCM-EN3 WVSWM-EN3
Getting Started
• Plan where you will mount each receiver and transmitter.
• Avoid transmitting along a length of wall, sharp angles and large obstructions.
• Avoid mounting inside a metal enclosure.
• Typical range is 100’ line of sight.
• All RIBs must be powered during Link.
• RIBWxxxB-EN3 is both a transmitter and a receiver.
• RIBWxxC-EN3 is only a receiver.
• Linking a RIB with another RIB puts the pair in Bi-directional mode.
• PHC Gateway Controller can also link with a RIB and be Bi-directional.
• Relay state at power-up can be set to ON, OFF or LAST STATE (default). (Exception: RIBW24B-EN3 will not save last state when powered from 24Vdc).
• Each Relay can be Linked to up to 30 transmitters of any combination.
902 MHz Model Power Input (Vac) Contact Rating (A) Transmission Source EEP
RIBW24B-EN3 24 ac/dc 20 Dry-Contact A5-30-02
RIBW01B-EN3 120 20 Dry-Contact A5-30-02
RIBW208B-EN3 208 20 Dry-Contact A5-30-02
RIBW240B-EN3 240 20 Dry-Contact A5-30-02
RIBW277B-EN3 277 20 Dry-Contact A5-30-02
RIBW01C-EN3 120 5 NA A5-30-02
RIBW02C-EN3 208-277 5 NA A5-30-02
WDWS-EN3 None NA Contact Closure D5-00-01
WWS2-EN3 None NA Button Press F6-02-02
WKC-EN3 None NA Insert/Remove Card F6-04-01
WVSCM-EN3 None NA Occupancy Detected A5-07-01
WVSWM-EN3 None NA Occupancy Detected A5-07-01
Functional Devices, Inc.’s EnOcean® Manufacturer ID is 0x055.
Compatible Device from other Manufacturers
PHC Gateway Controller EEP A5-38-08
393231L
page 1
Building Automation Applications
Uni-directional Mode: Only one of the RIBs must transmit. Two RIBWxxxB-EN3 or one RIBWxxxB-EN3 and one RIBWxxC-EN3.
LRN CLR LRN CLR
Device Power
Device Power
Dry Contact
• Only one RIB is the transmitter while the other is the receiver.
• Transmitter RIB Dry contact closure will transmit a relay ON command; dry contact open will transmit a relay OFF command.
• Re-transmits dry contact input state every 70-140 seconds.
• Optional modes: Repeater, Alarm (see pages 4)
• When linking a RIB with Version 1.5 firmware (on product label below RIB logo) to a RIB with an earlier version, the Ver. 1.5 must be RIB-1 in this procedure.
Uni-directional Link Procedure
1. Apply power to both RIB’s.
2. Get RIB-1 in Learn mode by pressing the LRN button for ½ second. (LED will blink).
3. On RIB-2 hold LRN button for 3 seconds to transmit a Teach telegram. a. LED on RIB-1 will stay ON for 4 seconds to acknowledge and then transmit a Teach telegram. b. LED on RIB-2 will stay ON for 4 seconds to acknowledge the Teach telegram from RIB-1.
Note: To clear memory, hold CLR button for 3 seconds.
RIBWxxxB-EN3
RIB-1
RIBWxxxB-EN3
or RIBWxxC-EN3
RIB-2
Load
Bi-directional Mode: Two RIBWxxxB- or one RIBWxxB-EN3 and a PHC Gateway Controller
LRN CLR LRN CLR
Relay Output Relay Output
Device Power
RIBWxxxB-EN3
RIBWxxxB-EN3
Device Power
Dry Contact
• Both devices must be able to receive and transmit.
• Dry contact closure will transmit a relay ON command; dry contact open will transmit a relay OFF command.
• RIBWxxB-EN3 Re-transmits dry contact input state every 70-140 seconds.
• Optional modes: Repeater, Alarm (see pages 4)
• When linking a RIB with Version 1.5 firmware (on product label below RIB logo) to a RIB with an earlier version, the Ver. 1.5 must be RIB-1 in this procedure.
Bi-directional Link Procedure
1. Apply power to both RIB’s.
2. Get RIB-1 in Learn mode by pressing the LRN button for ½ second. (LED will blink).
3. On RIB-2, hold LRN button 3 seconds to transmit a Teach telegram. a. LED on RIB-1 will stay ON for 4 seconds to acknowledge and then transmit a Teach telegram. b. LED on RIB-2 will stay ON for 4 seconds to acknowledge the Teach telegram from RIB-1.
Note: To clear memory, hold CLR button for 3 seconds.
RIB-1
RIB-2
Dry Contact
902 MHz Wireless Relays Application Manual B1867
page 2
Lighting Applications
Simple Lighting Control: RIBWxxxB-EN3 or RIBWxxC-EN3 and WWS2-EN3 or WKC-EN3
LRN CLR
WWS2-EN3
(Rocker Switch)
RIBWxxxB-EN3
Org
Blk
Wht or Red
60Hz A/C Power
or RIBWxxC-EN3
or
WKC-EN3
(Keycard Switch)
Yel
Load
WWS2-EN3 Modes WKC-EN3 Mode
A. Rocker Mode
• Relay activates when Rocker ON is pressed; relay deactivates when Rocker OFF is pressed.
• Optional modes: Repeater (see page 4)
Rocker Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and release the button on the switch you are learning three times quickly.
4. LED on RIB will stay ON for 4 seconds indicating telegram reception.
5. To learn another switch, repeat steps 2-4.
B. Momentary Mode
• Relay activates while switch is pressed and deactivates when switch is released.
• Optional modes: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and release the button on the switch you are learning three times quickly.
5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. To learn another switch, repeat steps 2-5.
Momentary Mode
• Relay activates when card is inserted and deactivates when card is removed.
• Optional modes: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Insert and remove the card on the switch you are learning three times quickly.
5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. To learn another switch, repeat steps 2-5.
C. Toggle Mode
• Each press and release of the switch causes the relay to change state.
• Optional modes: Repeater (see page 4)
Toggle Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and release the button on the switch you are learning three times quickly.
6. LED on RIB will stay ON for 4 seconds indicating telegram reception.
7. To learn another switch, repeat steps 2-6.
Occupancy Detection
A. Manual ON–Auto OFF: RIB receiving from both an Occupancy / Vacancy Sensor (WVSWM-EN3 or WVSCM-EN3) and a Wall Switch (WWS2-EN3)
• Relay activates when Rocker ON is pressed. Relay deactivates when Rocker OFF is pressed or 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy / Vacancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Manual ON – Auto OFF Learn Procedure
1. Be sure the Occupancy / Vacancy Sensor is charged
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
7. Press and release rocker switch three times quickly.
8. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
9. To learn another switch, repeat steps 6-8.
Continued on Page 4
902 MHz Wireless Relays Application Manual B1867
page 3
Occupancy Detection
B. Auto On: RIB and an Occupancy / Vacancy Sensor (WVSWM-EN3 or WVSCM-EN3)
• Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy / Vacancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Occupancy / Vacancy Sensor Only Learn Procedure
1. Charge the Occupancy / Vacancy Sensor per instructions.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Repeat steps 3-5 for additional Occupancy / Vacancy Sensors.
Continued from Page 3
Optional Modes
Relay State
• Relay state after power-up can be set to ON, OFF or LAST STATE
• Relay state after power-up is LAST STATE by default.
Setting Relay State to OFF at Power-up:
1. While device is not powered, press and hold the LRN button.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 3 times.
4. Release the LRN button. Relay will always be OFF at power-up.
Setting Relay State to ON at Power-up:
1. While device is not powered, press and hold the CLR button.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 2 times.
4. Release the CLR button. Relay will always be ON at power-up.
Setting Relay State to LAST STATE at Power-up: (Default Mode) **
1. While device is not powered, press and hold the LRN and CLR buttons.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 1 time.
4. Release the LRN and CLR buttons. Relay will return to LAST STATE at power-up.
**NOTE: LAST STATE does not work with RIBW24B-EN3 when powered from 24 Vdc.
Repeater Mode
• Activating Repeater Mode allows relay to repeat signals from other EnOcean devices within range. The relay “hears” the signal and echoes it but will not respond to it unless it has been linked to the transmitting device.
• Relay will allow a signal to be repeated up to two times.
Enabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks twice indicating Repeater Mode is enabled.
Disabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks three times indicating Repeater Mode is disabled.
Alarm Mode
• Activating Alarm Mode requires all learned contact switches, such as WDWS-EN3 or RIBWxxxB-EN3, to transmit a CLOSED telegram before relay will activate. Relay will deactivate if any contact switch transmits an OPEN telegram.
Enabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks twice indicating Alarm Mode is enabled.
Disabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks three times indicating Alarm Mode is disabled.
902 MHz Wireless Relays Application Manual B1867
page 4
Delay Mode
O
O
On
<10s
On
90s 90s 90s
>10s10s
Disabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks three times indicating Delay Mode is disabled.
Wireless
Command
Relay State
• Typically used with Hotel Room Energy Control (see page 5).
• Activating Delay Mode allows the relay to ignore temporary changes in switch states.
• The Delay Mode causes a delay of 10 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also prevents the relay from activating following a deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring window and door contacts that may be briefly opened and then closed. If the contact remains open for longer than 90 seconds the relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks twice indicating Delay Mode is enabled.
Clearing ID’s from Memory
Global Clear (Reset to default settings)
Clears all linked devices, disables optional modes, and turns relay OFF.
Performing Global Clear
1. Press and hold CLR button on RIB for 3 seconds until LED begins slowly blinking. a. Clear Mode will time out and exit in 30 seconds.
Single Device Clear
• Allows the user to Un-link a single transmitter from RIB receiver.
• Maintains all optional mode settings.
Performing Single Device Clear
1. Repeating the Link procedure for a currently Linked device will Un-link that device.
902 MHz Wireless Relays Application Manual B1867
page 5
Energy Saving Applications
RIB with Door/Window Sensor(s) WDWS-EN3
WDWS-EN3
PTAC unit with RIBWxxxB-EN3
in Hotel Room Energy Control Mode
RIBWxxxB-EN3 or RIBWxxC-EN3
in Momentary Mode with Keycard Switch
(Wired through J Box)
WKC-EN3
Keycard Switch
• RIB activates with closed command from WDWS-EN3 and deactivates with open command.
• WDWS-EN3 retransmits contact state every 20-30 minutes.
• Optional modes: Repeater, Alarm, Delay (see pages 4)
WDWS-EN3 Link Procedure
1. Charge the WDWS-EN3 per Instructions provided with unit.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Press and release Link button on WDWS-EN3 to transmit Teach telegram.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. To learn more WDWS-EN3, repeat steps 3-5.
Hotel Room Energy Control RIB with WDWS-EN3 and WKC-EN3
Consult factory.
Other Common Applications
Unidirectional Control with a BAS System
BAS Panel
Wht/Red
DO
Wht/Blu
BAS Controller
Transmitter
In this application the BAS system dry-contact output controls the transmitter and a RIBWxxxB-EN3 or RIBWxxC-EN3 is the receiver.
LRN CLR
RIBWxxxB-EN3 or RIBWxxC-EN3
Org
60Hz A/C Power
Blk
Yel
Wht or Red
Load
902 MHz Wireless Relays Application Manual B1867
page 6
Unidirectional Control with a Thermostat
Thermostat
Power
Device Power
Thermostat
LRN CLR
RIBWxxxB-EN3
Dry Contact Output (Call)
Dry Contact Input
LRN CLR
RIBWxxxB-EN3
or RIBWxxC-EN3
Device Power
Relay Output
Hot Neutral or Other Phase
Heater, A/C,
or Fan
In this application the thermostat dry-contact output controls the transmitter and a RIBWxxxB-EN3 or RIBWxxC-EN3 is the receiver.
Bidirectional Control with a BAS System
BAS Panel
Wht/Red and Wht/Blu
DO
LRN
LRN CLR
RIBWxxxB-EN3
Org
Blk
Wht or Red
60Hz A/C Power
CLR
Yel
BAS Controller
Org
DI
RIBWxxxB-EN3
Yel
Wht/Red Wht/Blu
RIBX Series
(not included)
Load
In this application the BAS system dry-contact output controls the transmitter on a RIBWxxxB-EN3. A second RIBWxxxB-EN3 receives the signal and activates it relay. A current switch detects current flow through the load and closes the dry-contact input on the second RIBWxxxB-EN3. The first RIBWxxxB-EN3 receives the transmission and closes its relay. This contact closure to the BAS system lets the controller know the load status.
902 MHz Wireless Relays Application Manual B1867
page 7
Loading...