Tankless Technical Bulletin
Vertical Venting - Zero Clearance - Demand Pumps
Vertical Venting
In the past, we required to have a horizontal offset and a form of condensation collector (in-line 
or condensate tee) for any of our Tankless water heater installations terminated with vertical vent 
conguration. Effective with this notice Rheem will allow a straight vertical vent run off the top of 
the water heater provided that a vertical condensate collector, as designed by the appropriate vent 
manufacturer, is installed as close to the tankless water heater as possible. All other considerations, 
clearances, and installation requirements as outlined in the Use and Care Manual must be met. 
See our Tankless Application Drawing RTG11171 and RTG11172 for information and suggested 
components.
Zero Clearance DV Venting
Previously, Rheem has required a one (1) inch clearance around concentric vent piping to 
combustible surfaces for our tankless water heaters. Through testing we have certied that a clearance 
of zero (0) inches is acceptable to combustible and non-combustible surfaces. Effective with this notice 
a clearance of zero (0) inches to combustible and non-combustible surfaces for our Direct Vent (DV) 
concentric venting for our RTG-66 and RTG-53 Series Direct Vent water heaters is acceptable.
Demand Pump Systems
While we have allowed return circulation with our tankless products, we have in turn reduced the 
warranty of those products in installations where water is re-circulated through the tankless unit. These 
types of applications typically include hot water on demand plumbing system composed of a return 
circulation loop and a high ow pump. These types of systems can put undo stress on a tankless water 
Typical 66DV
Vertical Installation
In keeping with its policy of continuous progress 
and product improvement, Rheem reserves the 
right to make changes without notice.
heater and dramatically shorten the life expectancy of the unit, thus we reduce the applicable warranty 
under those conditions. 
In consideration of these types of applications, and seeing more and more tankless water heaters 
being installed under these circumstances, it is our recommendation that only a Demand Pump System 
be used. This is a pump system that works via a push button or motion detector that will activate a 
small high ow pump for a short duration to bring hot water from the tankless unit to the desired xture 
location. These pumps typically include some circuitry to limit the amount of operation time, not a timer, 
and have an integrated thermostat that will shut off the pump when the hot water reaches the xture. 
There are several different brands and manufactures of such systems, the use of these systems with 
a Rheem Tankless Water Heater will not impact or affect the warranty. A system that uses a timer to 
control the operation is NOT considered a demand pump. Any other recirculation system, continuous, 
timer, thermostatic, domestic heat, or any application where the water is re-circulated through the 
tankless water heater, will reduce the warranty of the Rheem Tankless Water Heater to 3-Years on the 
heat exchanger and parts.
See our Tankless Application Drawing RTG11154 for information.