Rheem Side Inlet Gas Water Heaters User Manual

The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater; and two, for the owner–operator, to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater. This manual also includes a parts list.
It is imperative that all persons who are expected to install, operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations. If you do not understand these instructions or any terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the seller from whom it was purchased. If additional information is required, refer to the section on “If you need service.”
Do not destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol as an indication of Important Safety Information!
California Proposition 65 Warning: This product contains chemicals known to the State of
California to cause cancer, birth defects or other reproductive harm.
AP10046-12 (03/05)
FOR YOUR SAFETY!
—Do not store or use gasoline or other flammable
vapors or liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
—WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
Do not return to your home until authorized by the gas supplier or fire department.
— Improper installation, adjustment, alteration,
service or maintenance can cause injury, property damage or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Use & Care Manual
With Installation Instructions for the Installer
Printed in USA
Water Heaters
Side Inlet Gas
For Manufactured Housing (Mobile Home)
! !
!
!
S
E
D
C
E
R
T
I
I
G
N
D
E
I
F
®
Safety Information
Safety Precautions . . . . . . . 3–6
LP Gas Models . . . . . . . . . . . 5
Installation Instructions
Location . . . . . . . . . . . . . . . . . 7
Installation Methods . . . . . 8-9
Water Connections . . . . . . . 10
Gas Supply. . . . . . . . . . . . . . 13
Leak and Pressure Testing . . 13
Conversion
Instructions . . . . . . . . . . . 24-27
Operating Instructions
Lighting Instructions . . . . . . 16
Water Temperature. . . . . 17, 18
Care and Cleaning
Draining . . . . . . . . . . . . . . . . 19
Burner Inspection . . . . . . . . 20
Extended Shut-Down . . . . . 20
Troubleshooting Tips
Before You Call
For Service . . . . . . . . . . 21, 22
Customer Service
Parts List . . . . . . . . . . . . . . . 23
If You Need Service . . . . . . 28
2
Inside you will find many helpful hints on how to use and maintain your water heater properly. A little preventive care on your part can save you time and money over the life of your water heater.
You’ll find many answers to common problems in the Troubleshooting Guide. If you review the chart of Troubleshooting Tips first, you may not need to call for service.
READ THIS MANUAL
FOR YOUR RECORDS
Write the model and serial numbers here:
#
#
You can find them on a label on the appliance.
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service under the warranty.
Your safety and the safety of others are very important. There are many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. Recognize this symbol as an indication of Important Safety Information! This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER”, “WARNING”, “CAUTION” or “NOTICE”.
These words mean:
DANGER
An imminently hazardous situation that will result in death or serious injury.
WARNING
A potentially hazardous situation that could result in death or serious injury and/or damage to property.
CAUTION
A potentially hazardous situation that may result in minor or moderate injury.
Notice:
Attention is called to observe a specified procedure or maintain a specific condition.
READ THE SAFETY INFORMATION
!
!
!
!
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate this water heater. It may save you time and cost. Pay particular attention to the Safety Instructions. Failure to follow these warnings could result in serious bodily injury or death. Should you have problems understanding the instructions in this manual, or have any questions, STOP, and get help from a qualified service technician, or the local gas utility.
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING.
3
Failure to install the draft hood, vent system and properly vent the water heater to the outdoors as outlined in the Venting Section of the Installation Instructions in this manual can result in unsafe operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, never operate this water heater unless it is properly vented and has an adequate air supply for proper operation. Be sure to inspect the vent system for proper installation at initial start-up; and at least annually thereafter. Refer to the Care and Cleaning section of this manual for more information regarding vent system inspection.
DANGER!
INSTALL THE DRAFT HOOD, VENT SYSTEM AND PROPERLY VENT THE WATER HEATER…
Gasoline, as well as other flammable materials and liquids (adhesives, solvents, etc.), and the vapors they produce are extremely dangerous. DO NOT handle, use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater. Be sure to read and follow the warning label pictured below and other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in property damage, bodily injury or death.
WARNING!
!
DANGER
FLAMMABLES
!
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING.
4
The chart shown above may be used as a guide in determining the proper water temperature for your home.
DANGER: Households with small children, disabled, or elderly persons may require a 120°F. or lower thermostat setting to prevent contact with “HOT” water.
Maximum water temperatures occur just after burner has shut off. To find water temperature being delivered, turn on a hot water faucet and place a thermometer in the water stream and read the thermometer.
The temperature of the water in the heater can be regulated by setting the temperature dial on the front of the gas control (thermostat). To comply with safety regulations the thermostat was set at its lowest
setting before the water heater was shipped from the factory.
The illustration at the left details the approximate water temperature for each mark on the Gas Control (Thermostat) Temperature Dial.
DANGER: Hotter water increases the potential for
Hot Water SCALDS.
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water temperature setting of water heater’s thermostat. Water temperatures above 125°F. can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined on the label pictured below. This label is also located on the water heater.
Notice: Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines . Contact a licensed plumber or the local plumbing authority for further information.
!
DANGER
HOT
BURN
Water temperature over 125°F can cause severe burns instantly or death from scalds.
Children, disabled and elderly are at highest risk of being scalded.
See instruction manual before setting temperature at water heater.
Feel water before bathing or showering.
Temperature limiting valves are available, see manual.
5
LP and natural gas have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or camouflage a gas leak.
DANGER!
LIQUEFIED PETROLEUM (LP - PROPANE OR BUTANE) AND NATURAL GAS MODELS
This water heater is supplied with a thermostatic gas valve that is convertible to LP from natural gas. Be sure to read and carefully follow the Conversion Instructions included in this manual when converting the valve from one type of gas to another.
After conversion, be certain that the gas supplied to the heater is the type that the valve has been converted for (LP for heaters converted to LP use, and natural gas for heaters converted to natural gas use). This water heater will not operate safely if connected to a fuel type other than the one the gas valve is converted for.
LP gas must be used with great caution. It is heavier than air and will collect first in lower areas making it hard to detect at nose level.
Before attempting to light the water heater, make sure to look and smell for gas leaks. Use a soapy solution to check all gas fittings and connections. Bubbling at a connection indicates a leak that must be corrected. When smelling to detect an LP leak, be sure to sniff near the floor also.
Gas detectors are recommended in LP and natural gas applications and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations or customs.
It is recommended that more than one method, such as soapy solution, gas detectors, be used to detect leaks in LP gas applications.
DANGER: If a gas leak is present or
suspected:
Do not attempt to find the cause yourself.
Do not
try to light any appliance.
Do not
touch any electrical switch.
Do not
use any phone in your building.
Leave the house immediately and make sure your family and pets leave also.
Leave the doors open for ventilation and contact the gas supplier, a qualified service agency or the fire department.
Stay away from the house (or building) until the service call has been made, the leak is corrected and a qualified agency has determined the area to be safe.
!
6
Have the installer show you the location of the gas shut-off valve and how to shut it off if necessary. Turn off the manual shut-off valve if the water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to shut off.
Read this manual entirely before installing
or operating the water heater.
Use this appliance only for its intended
purpose as described in this Use and Care Manual.
Be sure your appliance is properly installed
by a qualified technician in accordance with the provided installation instructions.
Do not attempt to repair or replace any part
of your water heater unless it is specifically recommended in this manual. All other servicing should be referred to a qualified technician.
SAFETY PRECAUTIONS
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or strapped to resist falling or horizontal displacement due to earthquake motions. For residential water heaters up to 52 gallon capacity, a brochure with generic earthquake bracing instructions can be obtained from: Office of the State Architect, 400 P Street, Sacramento, CA 95814 or you may call 916-324-5315 or ask a water heater dealer.
However, applicable local codes shall govern installation. For residential water heaters of a capacity greater than 52 gallons, consult the local building jurisdiction for acceptable bracing procedures.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Installing the water heater.
The installation of this water heater must be in accordance with the Manufactured Home Construction and Safety Standard (Title 24, CFR; Part 3280) and the following instructions; instructions supplied with the roof jack assembly, local codes, and utility company requirements governing the installation of water heaters in manufactured homes (mobile homes) and/or in the absence of local codes, the latest edition of The National Fuel Gas Code, ANSI Z223.1.
Location
This water heater must be installed within an enclosure so as to separate the water heater's combustion and venting system from the interior atmosphere of the manufactured home.
All air for combustion must be obtained from the outside atmosphere, and the products of combustion (flue gases) must be discharged directly to the outside atmosphere through the gas vent roof jack assembly. There must not be any door or other opening into the water heater enclosure from the inside of the manufactured home.
Refer to installation methods A, B or C as shown on page 9 of this manual. The water heater enclosure access panel (door) must be in the outside wall of the manufactured home. Any opening for piping must be sealed. Minimum ceiling height within enclosure is 6'6".
Install the water heater with minimum clearance from combustible construction of 0-inch sides and rear; 3 inches from front of control; 12 inches top. If clearances stated on Instruction/Warning label, located on front of heater, differ from the aforementioned clearances, install heater according to the clearances stated on the Instruction/Warning label.
The water heater may be installed on combustible flooring, but not directly on carpeting.
If the water heater must be installed on carpeting, place a wood or metal panel beneath the water heater extending beyond its full width and depth at least 3” in all directions. If the water heater is installed in an alcove or closet, the entire floor must be covered by the panel.
Make certain that the floor underneath the water heater is strong enough to support the weight of the water heater once it is filled with water.
CAUTION: Provisions should be made so that in the event the water heater or one of its fittings were to leak, the resulting flow of water will not cause damage to the manufactured home.
CAUTION: DO NOT subject the water heater to any water distribution system air pressure test. The water heater should either be isolated with valves at the inlet and outlet water connections or disconnected during the test. Failure to properly isolate the water heater during an air pressure test presents a hazard to life and property. With a water pressure test the water heater need not be isolated.
7
WARNING: Combustible
construction refers to adjacent walls and ceilings and should not be confused with combustible or flammable products and materials. Combustible and/or flammable products and materials should never be stored in the vicinity of this or any gas appliance.
8
Installing the water heater.
Installation Methods
Inspect shipment.
Inspect the water
heater for possible shipping damage.
Placement of water heater.
Locate the water heater as desired, make certain the minimum clearances outlined in this manual are observed.
Combustion and ventilation air.
Air for combustion and ventilation must not be supplied from occupied spaces of the mobile home. Select installation method "A", "B" or "C" from page 9. Method B is recommended for cold climates. The air inlet must not be obstructed under any circumstances. Outside air is necessary for proper and safe operation of the water heater.
Method A - Requires a minimum free area of 36 square inches outside fresh air opening in the outside access panel (door). Cut door opening commencing within 12" of the floor. Suggested protection for air opening is 1/4 " (minimum) mesh metal screen.
Method B - Requires the installation of optional Air Inlet (AP11596) and Leg Enclosure (Part No. AE24609C for 30 gallon models, or AE24609D for 40 gallon models).
Method B Installation
After selecting the proper location for the water heater, cut a hole (approx. 3 1/2" dia.) through the floor and bottom sheathing directly below the center of the water heater for installation of the air inlet assembly. Insert air inlet through the hole in the floor (see Method B on page 9) with flanged section on the inside. Secure inlet in position with the four screws supplied. The opening around the Air Inlet Assy. and the bottom sheathing must be sealed to resist the entrance of rodents.
Water heater must be centered directly over air inlet and secured in place with screws provided.
Bottom of the air inlet must be no closer than 12" from ground level.
When mobile home is tightly skirted, an air inlet opening in the skirt must be provided. The opening shall have a minimum free area of at least 9 square inches. If the opening is screened or covered with a louver, the total free area must be at least 9 square inches.
Wrap optional Leg Enclosure (Part No. AE24609C for 30 gallon models, or AE24609D for 40 gallon models) around the legs of the water heater and lock in position with tab. This enclosure will protect the water piping from the cold outside air and directly supply the water heater with air necessary for combustion.
Method C - Requires a minimum free area of 20 square inches outside fresh air opening in the floor(s) directly beneath the water heater. Suggested protection for air opening is 1/4" (minimum) mesh metal screen.
Gas vent roof jack.
The roof jack is not supplied with the water heater as a component part. The roof jack must be Rheem certified for use, and marked as approved by Underwriters Laboratories, Inc. for use on manufactured homes (mobile homes). The installation instructions supplied with each roof jack must be observed to obtain the proper roof jack installation.
Securing the water heater.
Secure the two front legs of the water heater to the floor using the 2 long screws furnished. Attach the bracket (AP11154) to the top pan of the water heater and fasten the bracket to the adjacent walls on each side.
9
Roof Jack
(Not Supplied)
Roof
Ceiling
Floor
Floor
Relief Valve
Opening
"Cold"
Water
Inlet
"Hot"
Water Outlet
Sheet Metal Screws (2 supplied) to Secure Legs to floor
Sheet Metal Screws (2 supplied) to Secure Legs to floor
0" Min.
Clearance (side & rear) 3" Min. from
Front of Control
Secure Draft Hood to Water Heater with TWO Sheet Metal Screws. Secure Roof Jack to Draft Hood with Sheet Metal Screws
SecureStrapping (AP11154) to Water Heater Top Pan and Enclosure Sides with Sheet Metal Screws provided
Minimum Free Area - 36 sq. in. Outside Fresh Air Opening. Cut Door Opening Commencing within 12" of the floor. Suggested Protection Outside Air Opening
1
/4" Mesh (min.) Metal Screen
METHOD A
METHOD C
METHOD B — Recommended for Cold Climates
6'6" Min.
Ceiling
Height
Access Panel (Door)
Opening Required
Access Panel (Door)
Opening Required
Roof Jack
(Not Supplied)
Roof
Ceiling
Floor
Cut Hole Thru Floor
12" Minimum
Ground Level
Center Line of Heater and Air Inlet
Secure Air Inlet to Flooring with Screws provided
Optional Air Inlet (AP11596)
Relief Valve
Opening
"Cold"
Water
Inlet
"Hot"
Water Outlet
Sheet Metal Screws (2 supplied) to Secure Legs to floor
Cut Hole thru Floor(s)
20 Sq. In. Minimum
Equivalent Free Air Opening
1/4" Wire Mesh (Min.) Metal Protection Screen
0" Min.
Clearance (side & rear) 3" Min. from
Front of Control
Secure Draft Hood to Water Heater with TWO Sheet Metal Screws. Secure Roof Jack to Draft Hood with Sheet Metal Screws
Secure Strapping (AP11154) to Water Heater Top Pan and Enclosure Sides with Sheet Metal Screws provided
6'6" Min.
Ceiling
Height
Access Panel (Door)
Opening Required
Optional Leg Enclosure
(Part No. AE24609C for 30 gallon models,
or AE24609D for 40 gallon models).
ROOF JACK — This water heater is certified for use with Rheem Models
AP12119B, AP12118B, AP12118C, AP12118D roof jacks:
Additional information on other Rheem approved and certified roof jacks
may be found at www.r
heem.com
, under
“Library”, scroll down to the Technical Service Bulletins Manufactered Housing Series Section and choose
Bulletin #1504 or by
consulting your distributor.
NOTE: Refer to Section 4, on the reverse side for additional requirements
10
Installing the water heater.
Thermal Expansion
Determine if a check valve exists in the inlet water line. Check with your local water utility company. It may have been installed in the cold water line as a separate back flow preventer, or it may
be part of a pressure reducing valve, water meter or water softener. A check valve located in the cold water inlet line can cause what is referred to as a “closed water system”. A cold water inlet line with no check valve or back flow prevention device is referred to as an “open” water system.
As water is heated, it expands in volume and creates an increase in the pressure within the water system. This action is referred to as “thermal expansion”. In an “open” water system, expanding water which exceeds the capacity of the water heater flows back into the city main where the pressure is easily dissipated.
A “closed water system”, however, prevents the expanding water from flowing back into the main supply line, and the result of “thermal expansion” can create a rapid and dangerous pressure increase in the water heater and system piping. This rapid pressure increase can quickly reach the safety setting of the relief valve, causing it to operate during each heating cycle. Thermal expansion, and the resulting rapid, and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve, and possibly the heater itself. Replacing the relief valve will not correct the problem!
The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve (see illustration below). The expansion tank is designed with an air cushion built in that compresses as the system pressure increases, thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve. Other methods of controlling thermal expansion are also available. Contact your installing contractor, water supplier or plumbing inspector for additional information regarding this subject.
Water Supply Connections
Refer to the illustration on page 11 for suggested typical installation. The installation of unions or flexible copper connectors is recommended on the hot and cold water connections so that the water heater may be easily disconnected for servicing if
necessary. The HOT and COLD water connections are clearly marked and are 3/4” NPT on all models. Install a shut-off valve in the cold water line near the water heater.
IMPORTANT: Do not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the cold water connections on heater. Any heat applied to the cold water supply fittings will permanently damage the connection nipples.
11
Typical Installation
HOT
ALTERNATE SEDIMENT
TRAP LOCATION
Hot Water Outlet
To Fixtures
Roof Jack
Draft Hood
Anode
Flue Baffle
(Underneath)
Temperature and Pressure Relief Valve
Relief Valve Discharge Line to Suitable Drain
Drain Valve
Jacket Door
Thermostat
Sediment Trap
Sediment Trap
Manual Gas
Shut-Off
Ground Joint Union or ANSI Design Certified Semi-Rigid or Flexible
Gas Appliance Connector
To Gas Supply
To Gas Supply
To Cold Water Supply
Vacuum Relief Valve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.
12
Installing the water heater.
WARNING: The tank must be full of water before heater is turned on. The water heater warranty does not cover damage or failure resulting from operation with an empty or partially empty tank.
To Fill the Water Heater
Make certain that drain valve is closed, then open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to allow the air to vent from the water heater and piping.
A steady flow of water from the hot water faucet(s) indicates a full water heater.
Condensation
Condensation can form on the tank when it is first filled with water. Condensation might also occur with a heavy water draw and very cold inlet water temperatures.
Drops of water falling on the burner can produce a sizzling or pinging sound, and the water may also be seen beneath the water heater.
This condition is not unusual, and will disappear after the water becomes heated. If, however, the condensation continues, examine the piping and fittings for possible leaks.
Additional information on this subject may be found at www.rheem.com, under “Library”, scroll down to the Technical Service Bulletins 1400 Series Section and choose Bulletin #1402.
A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must remain in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank. Local codes shall govern the installation of relief valves.
Relief Valve
The pressure rating of the relief valve must not exceed 150 PSI, the maximum working pressure of the water heater as marked on the rating plate.
The BTUH rating of the relief valve must equal or exceed the BTUH input of the water heater as marked on its rating plate.
Position the outlet of the relief valve above a suitable open drain to eliminate potential water damage. Piping used should be of a type approved for hot water distribution.
The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow complete drainage (by gravity) of the relief valve and discharge line.
The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in the discharge line.
13
WARNING: Never use an open flame to test for gas leaks, as bodily injury, property damage or death could result.
Leak Testing
The water heater and its gas connections must be leak tested at normal operating pressures before it is placed in operation.
Turn on the manual gas shut-off valve near the water heater.
Use a soapy water solution to test for leaks at all connections and fittings. Bubbles indicate a gas leak that must be corrected.
The factory connections to the thermostat should also be leak tested after the water heater is placed in operation.
Pressure Testing the Gas Supply System
The water heater and its manual gas shut-off valve must be disconnected
from the gas supply piping system during any high pressure testing of that system at pressures in excess of 1/2 psi (14″ w.c.).
The water heater must be isolated from the gas piping system by closing the manual gas shut-off valve during any pressure testing of the gas supply piping at pressures equal to or less than 1/2 psi (14w.c.).
Gas Supply
Check the markings on the water heater’s rating plate to be certain the type of gas being furnished corresponds to that for which the water heater is built. The water heater can be converted from natural gas to LP or vice versa. See the Conversion Instructions section of this manual.
The branch gas supply line to the water heater should be clean 1/2black steel pipe or other approved gas piping material.
A ground joint union or ANSI design certified semi-rigid or flexible gas appliance connector should be installed in the gas line close to the water heater. A manual gas shut-off valve should be at least 5 ft. above the floor and readily accessible.
Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas. Use compound sparingly on male threads only.
A sediment trap should be installed at the bottom of the gas line.
Do not use excessive force (over 31.5 ft lbs.) in tightening the pipe joint at the thermostat inlet, particularly if teflon pipe compound is used, as the valve body may be damaged.
The inlet gas pressure to the water heater must not exceed 14w.c. for natural or LP gas. For purposes of input adjustment, the minimum inlet gas pressure (with main burner on) is shown on the water heater rating plate. If high or low gas pressures are present, contact your gas supplier for correction.
14
Installing the water heater.
High Altitude
Ratings of gas appliances are based on sea level operation and need not be changed for installations at elevations up to 2,000 feet.
For installations above 2,000 feet, reduce the input per the the National Gas Fuel Code for each 1,00 feet above sea level. Contact the local gas supplier for further information.
WARNING: Failure to install a water heater suitable for the altitude at the location it is intended to serve, can result in improper operation of the appliance resulting in property damage and/or, producing carbon monoxide gas, which could result in personal injury, or death.
For increased energy efficiency, some water heaters have been supplied with two 24” sections of pipe insulation.
Please install the insulation, according to the illustrations above, that best meets your requirements.
R
E
L
I
E
F
V
A
L
V
E
COLD
HOT
Typical vertical piping arrangement
R
E
L
I
E
F
V
A
L
V
E
COLD
HOT
Typical horizontal piping arrangement
Hot and Cold Pipe Insulation Installation
15
Installation Checklist
A. Water Heater Location
B. Water Supply
C. Gas Supply
D. Relief Valve
E. Venting
Water heater securely anchored.
Indoors and protected from freezing
temperatures.
Proper clearance from combustible surfaces
observed and water heater not installed on carpeted floor.
Sufficient fresh air supply for proper
operation of water heater.
Air supply free of corrosive elements and
flammable vapors.
Provisions made to protect area from water
damage.
Sufficient room to service heater.
Combustible materials, such as clothing,
cleaning materials, rags, etc. clear of the base of the heater.
Water heater completely filled with water.
Air purged from water heater and piping.
Water connections tight and free of leaks.
Gas line equipped with shut-off valve, union
and sediment trap.
Approved pipe joint compound used.
Soap and water solution used to check all
connections and fittings for possible gas leak.
Gas Company inspected installation (if
required).
Temperature and Pressure Relief Valve
properly installed and discharge line run beneath mobile home.
Discharge line protected from freezing.
Flue baffle properly hung in top of heater’s
flue.
Gas Vent Roof Jack properly installed.
Lighting the water heater.
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in property damage, bodily injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get help from a qualified person.
17
Safety Precautions
Do turn off manual gas shut-off
valve if water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to shut off.
Do Not turn on water heater unless it is filled with water.
Do Not turn on water heater if cold water supply shut-off valve is closed.
Do Not allow combustible materials such as newspaper, rags or mops to accumulate near water heater.
Do Not store or use gasoline or other flammable vapors and liquids, such as adhesives or paint thinner, in vicinity of this or any other appliance. If such flammables must be used, open doors and windows for ventilation, and all gas burning appliances in the vicinity should be shut off including their pilot lights, to avoid vapors lighting.
NOTICE: Flammable vapors may be drawn by air currents from surrounding areas to the water heater.
If there is any difficulty in understanding or following the Operating Instructions or the Care and Cleaning section, it is recommended that a qualified person or serviceman perform the work.
Operating the water heater.
CAUTION: Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE!! To dissipate such gas and to reduce risk of injury, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the water begins to flow. Do not smoke or use an open flame near the faucet at the time it is open.
DANGER: There is a hot
water scald potential if the thermostat is set too high. Households with small children, disabled, or elderly persons may require a 120°F. or lower thermostat setting to prevent contact with HOT water.
Water Temperature Setting
The temperature of the water in the water heater can be regulated by setting the temperature dial on the front of the thermostat.
Safety and energy conservation are factors to be considered when selecting the water temperature setting of the water heater’s thermostat(s). The lower the temperature setting, the greater the savings in energy and operating costs.
To comply with safety regulations the thermostat was factory set at 120°F. or less where local codes require. This is the recommended starting point.
Water temperatures above 125°F. can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined in this manual and on the label on the water heater. This label is located on the water heater.
Mixing valves for reducing point of use water temperature by mixing hot and cold water in branch water lines are available. Contact a licensed plumber or the local plumbing authority for further information.
The chart below may be used as a guide in determining the proper water temperature for your home.
Operating the water heater.
Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F More than 5 minutes 125°F 11/2to 2 minutes 130°F About 30 seconds 135°F About 10 seconds 140°F Less than 5 seconds 145°F Less than 3 seconds 150°F About 11/2seconds 155°F About 1 second
Table courtesy of Shriners Burn Institute
Water Temperature Setting…
Maximum water temperatures occur just after the burner has shut off. To determine the water temperature, turn on a hot water faucet and place a thermometer in the water stream.
The wide reference mark near WARM on the rim of the temperature dial, represents an approximate water temperature of 120°F.
The long wide reference mark, to the left, represents an approximate water temperature of 130°F.
Each reference mark above or below these points indicates an approximate change of 10°F.
To adjust the temperature, turn the temperature dial to an initial setting of 120°F.
A condition known as “stacking” or “layering” can occur when a series of short and frequent hot water draws are taken.
The hottest temperature water will be at the top of the tank, closest to the outlet pipe delivering hot water to the home.
Stacking can cause this top layer of water to be hotter than the water toward the bottom of the tank near the gas control (thermostat).
Therefore, always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury.
Also, always supervise young children or others who are incapacitated.
The gas control (thermostat) is constructed with a built in safety shut-off device designed to shut off the gas supply to the burner if the pilot flame is extinguished for any reason.
The gas control (thermostat) is also equipped with a single use gas shut off device that will shut off the gas supply to the burner if the water heater exceeds normal operating temperatures. Refer to the (Before You Call For Service) section of this manual, or contact your dealer.
WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
If the water heater has been subjected to fire, flood or physical damage, turn off the manual gas control (shut-off) valve, and do not operate the water heater again until it has been checked by qualified personnel.
W
A
R
M
V
A
C
A
T
I
O
N
H
O
T
18
130°F.
Temperature dial
(Temperatures are approximate)
120°F.
140°F.
150°F.
160°F.
110°F.
100°F.
90°F.
80°F. 70°F.
60°F.
WARNING
READ ALL INSTRUCTIONS BEFORE LIGHTING
O
I
N
T
U
A
C
Y
S
R
E
U
R
S
J
E
A
T
H
N
T
W
O
I
E
A
R
T
D
T
C
E
H
L
N
I
R
E
A
C
R
S
I
S
F
K
O
!
Care and cleaning of the water heater.
Draining the Water Heater
CAUTION: Shut off gas to the water heater at the thermostat gas cock or manual shut-off valve before draining water.
DANGER: Before manually operating the relief valve, make certain no one will be exposed to the hot water released by the valve. The water drained from the tank may be hot enough to present a scald hazard and should be directed to a suitable drain to prevent injury or damage.
In order to drain the water heater, turn off the cold water supply. Open a hot water faucet or lift the handle on the relief valve to admit air to the tank.
Attach a garden hose to the drain valve on the water heater and direct the stream of water to a drain. Open the valve.
Routine Preventative Maintenance
Properly maintained, your water heater will provide years of dependable trouble-free service.
It is suggested that a routine preventative maintenance program be established and followed by the user.
It is further recommended that a periodic inspection of the thermostat, burner, relief valve, internal flue-way and venting system should be made by service personnel qualified in gas appliance repair.
At least once a year, lift and release the lever handle on the temperature pressure relief valve, located near the top of the water heater, to make certain the valve operates freely. Allow several gallons to flush through the discharge line to an open drain.
NOTICE: If the temperature and pressure relief valve on the hot water heater discharges periodically, this may be due to thermal expansion in a closed water system. Contact the water supplier or your plumbing contractor on how to correct this. Do not plug the relief valve outlet.
A water heater’s tank can act as a setting basin for solids suspended in the water. It is therefore not uncommon for hard water deposits to accumulate in the bottom of the tank. It is suggested that a few quarts of water be drained from the water heater’s tank every month to clean the tank of these deposits.
Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe. Strategically located risers in the water pipe system or water hammer arresting devices can be used to minimize the problem.
The anode rod should be removed from the water heater’s tank annually for inspection and replaced when more than 6of core wire is exposed at either end of the rod.
Make sure the cold water supply is turned off before removing anode rod.
Inspect air inlet assembly beneath mobile home (if applicable) to make certain flow of air to the water heater for adequate combustion (proper burner operation) and ventilation is not obstructed.
Housekeeping
To insure sufficient ventilation and combustion air supply, proper clearances must be maintained.
19
DANGER: Before
manually operating the relief valve, make certain no one will be exposed to the danger of coming in contact with the hot water released by the valve. The water may be hot enough to create a scald hazard. The water should be released into a suitable drain to prevent injury or property damage.
DANGER: Failure to perform the recommended Routine Preventative Maintenance can harm the proper operation of this water heater, which can cause carbon monoxide dangers, excessive hot water temperatures and other potentially hazardous conditions.
DANGER: Hotter water increases the potential for Hot Water Scalds.
DANGER: Combustible materials, such as clothing, cleaning materials, or flammable liquids, etc., must not be placed against or next to the water heater.
!
Venting System Inspection
It is recommended the water heater’s internal flue be inspected annually to be certain it is clean by removing the draft hood and flue baffle.
When reinstalling the flue baffle make certain it is hung securely by its hanger at the top of the flue way.
Remove any scale that may have fallen on the burner or floor shield and reinstall the draft hood.
Make certain the draft hood is fastened to the water heater top pan and roof jack vent is properly positioned and securely attached with sheet metal screws.
If after inspection of the vent system you found sooting or deterioration call the local gas utility to correct the problem and clean or replace the flue baffle and venting before resuming operation of the water heater.
Test for spillage at the draft hood relief opening after 5 minutes of burner operation. Use a flame of a match or candle or smoke.
Burner Inspection
Visually inspect the burners annually.
Through the site glass, inspect the pilot burner flame with the main burner off and inspect the main burner while firing.
If any unusual burner operation is noted, the water heater should be shut off until qualified service assistance can be obtained.
For cleaning, remove the burner from the water heater. A vacuum cleaner can be used on the burner and floor shield inside the water heater. The burner can also be cleaned by scrubbing with mild detergent.
CAUTION: For your safety, cleaning of
the main burner should be performed only by qualified service personnel.
21
Before You Call For Service
Troubleshooting Tips Save time and money! Review the charts on the following pages first and you may not need to call for service.
Problem Possible Causes What To Do
Condensation This usually happens when This is normal. After the water in the tank warms
a new water heater is up the condensation will disappear. If, however, the filled for the first time. condition persists, examine the piping and fittings
for possible leaks.
Moisture from the products This is normal and will disappear in time. Excessive of combustion condensing condensation can cause pilot outage. on the tank surface.
An undersized water Use a water heater size that meets the requirements heater will cause of your needs. condensation.
Yellow flame Scale on top of the burner. Shut off the water heater and remove scale. or sooting
Combustion air inlets or Remove lint or debris and inspect air inlet opening flue-way restricted. for restriction.
Not enough combustion or Proper operation of the water heater requires air for ventilation air supplied to combustion and ventilation. See the Combustion and the water heater location. Ventilation Air information in the Locating the water
heater section of this manual.
Unable to light Gas Cock Knob not See the Lighting the water heater section of this the pilot correctly positioned. manual.
Pilot orifice clogged. The pilot should be cleaned or replaced by a qualified
service technician.
Pilot tube pinched or The pilot should be cleaned, repaired or replaced by a clogged. qualified service technician.
Air in gas line. Contact a qualified service technician to purge the air
from the gas line.
Pilot does not stay Loose thermocouple. The connection at the thermostat should be tightened lit when the RED by a qualified service technician. button is released
Thermocouple breakdown. The thermocouple should be replaced by a qualified
service technician.
Safety magnet breakdown. The thermostat should be replaced by a qualified
service technician.
Thermostat’s single The thermostat should be replaced by a qualified use gas shut-off device service technician. has opened.
CAUTION: For your safety DO NOT attempt repair of gas piping, thermostat, burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
22
Before You Call For Service…
Problem Possible Causes What To Do
Rumbling noise Scale and sediment Clean tank.
in tank.
Relief valve Pressure build up This is an unacceptable condition and must be producing popping caused by thermal corrected. Contact the water supplier or plumbing noise or draining expansion to a contractor on how to correct this. Do not plug the
closed system. relief valve outlet.
Not enough or Water usage may have Wait for the water heater to recover after an no hot water exceeded the capacity abnormal demand.
of the water heater.
Low gas pressure. Check gas supply pressure and manifold pressure.
The pilot burner may be out. Check the pilot burner. If necessary, relight using the
instructions in the “Lighting The Water Heater” section of this manual.
The gas control (thermostat) See the “Water Temperature Setting” of The Water may be set too low. Heater section of this manual.
Leaking or open hot Make sure all faucets are closed. water faucets.
Water is too hot The gas control (thermostat) See the “Water Temperature Setting” of The Water
is set too high. Heater section of this manual.
Gas Control (Thermostat) Contact a qualified service technician to replace the Defective. gas control (thermostat).
CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
Replacement Parts.
Instructions For Placing a Parts Order
Address parts orders to the distributor or store from where the heater was purchased.
All parts orders should include:
The model and serial number of the water heater from the rating plate.
Specify type of gas (natural or LP) as marked on the rating plate.
Part description (as noted below) and number of parts desired.
CAUTION: For your safety DO NOT attempt repair of gas piping, thermostat, burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
Conversion instructions—Natural Gas to LP Gas
If your gas supply is LP gas, your water heater can be converted to burn LP gas as follows:
24
WARNING: This conversion kit must be installed by a qualified installer or service technician in accordance with these instructions. Installation must conform with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, ANSI Z223.1. Failure to follow instructions could result in serious injury or property damage. The qualified agency performing this work assumes responsibility for this conversion.
CAUTION: The water heater is factory set to burn natural gas, but can be converted to burn LP gas. Before putting the water heater into operation, verify that the type of gas supplied to your water heater and the type of gas your water heater is set to burn are the same. If they are not, refer to these instructions.
NOTICE: The parts required to make this
conversion are supplied in a small bag attached to the drain valve of the water heater. Should your heater not have this bag attached to the drain valve, a replacement can be obtained. Simply contact the manufacturer at the address below and request a replacement conversion kit.
Customer Service Department
2600 Gunter Park Drive, East Montgomery, AL 36109-1413 Phone: 1-800-432-8373
Turn gas cock knob and manual shut-off valve to the OFF position.
Change main burner regulator setting by unscrewing slotted cap from the gas cock knob; then with a small screwdriver depress and rotate the plunger 90° to align the slot with the
LP
markings. The red disk with the white slot should “pop” up to the top of the bore in the natural gas setting and be at the bottom of the bore in the “LP” setting. Replace the cap.
LP gas
Natural gas
Slotted cap
Slotted plunger of pilot regulator
Change pilot burner regulator setting by unscrewing slotted cap from the front of the control and align the slot with the
LP marking as described in
step 2. Push in and twist bottom of bore for LP, top of bore for natural gas. Replace the cap.
WARNING: Both the main burner and pilot burner gas pressure regulators must be changed as outlined in steps 2 and 3.
Natural Gas to Liquefied Petroleum (LP or Propane) Gas
Gas cock knob
Slotted cap (unscrew to remove)
Slotted plunger of
main regulator
Remove outer jacket door and the inner door.
Inner door
Outer jacket door
Conversion Instructions—Natural Gas to LP Gas
25
Pilot Burner
Gas Cock Knob
Thermocouple
Burner Supply Tube
Pilot Supply Tube
26
Conversion Instructions—LP Gas to Natural Gas
Turn gas cock knob and manual shut-off valve to the OFF position.
Change main burner regulator setting by unscrewing slotted cap from the gas cock knob; then with a small screwdriver depress and rotate the plunger 90° to align the slot with the NAT markings. The red disk with the white slot should “pop” up to the top of the bore in the natural gas setting and be at the bottom of the bore in the “LP” setting. Replace the cap.
Natural gasLP gas
Slotted cap
Slotted plunger of pilot regulator
Change pilot burner regulator setting by unscrewing slotted cap from the front of the control and align the slot with the NAT marking as described in step 2. Push in and twist top of bore for natural gas, bottom of bore for LP. Replace the cap.
WARNING: Both the main burner and pilot burner gas pressure regulators must be changed as outlined in steps 2 and 3.
Remove outer jacket door and the inner door.
Inner door
Outer jacket door
Liquefied Petroleum (LP or Propane) Gas to Natural Gas
Your water heater was factory pre-set to burn natural gas but may have been converted to burn LP gas. If your water heater has been converted to burn LP gas, and your gas supply is now natural gas, your water heater can be converted to burn natural gas as follows:
WARNING: This conversion kit must be installed by a qualified installer or service technician in accordance with these instructions. Installation must conform with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, ANSI Z223.1. Failure to follow instructions could result in serious injury or property damage. The qualified agency performing this work assumes responsibility for this conversion.
CAUTION: The water heater is factory set to burn natural gas, but can be converted to burn LP gas. Before putting the water heater into operation, verify that the type of gas supplied to your water heater and the type of gas your water heater is set to burn are the same. If they are not, refer to these instructions.
NOTICE: The parts required to make this
conversion are supplied in a small bag that should be located in the plastic bag attached to the water heater. If you are unable to locate the cloth bag, a replacement can be obtained. Simply contact the manufacturer at the address below and request a replacement conversion kit.
Customer Service Department
2600 Gunter Park Drive, East Montgomery, AL 36109-1413 Phone: 1-800-432-8373
Gas cock knob
Slotted cap (unscrew to remove)
Slotted plunger of
main regulator
Conversion Instructions—LP Gas to Natural Gas
27
28
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires adjustment, repair, or routine maintenance, it is suggested that you first contact your installer, plumbing contractor or previously agreed upon service agency. In the event the firm has moved, or is unavailable, refer to the telephone directory, commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should then contact the Manufacturer’s National Service Department at the following address:
2600 Gunter Park Drive Montgomery, Alabama 36109-1413 Phone: 1-800-432-8373.
When contacting the manufacturer, the following information will be requested:
a. Model and serial number of the water heater as shown on the rating plate attached
to the front panel of the heater.
b. Address where the water heater is located and physical location. c. Name and address of installer and any service agency who performed service on
the water heater.
d. Date of original installation and dates any service work was performed. e. Details of the problem as you can best describe them. f. List of people, with dates, who have been contacted regarding your problem.
Loading...