Rheem RXRX-AL01, RXRX-AL02 Installation Manual

INSTALLATION INSTRUCTIONS

LOCKOUT PROTECTION MODULE KIT

RXRX-AL01

7.5, 10.0-TON

 

 

RXRX-AL02 12.5, 15.0 & 20-TON

 

 

GAS, ELECTRIC & SELF-CONTAINED PACKAGED UNIT

! Recognize this symbol as an indication of Important Safety Information!

 

 

 

 

 

 

Parts List

RXRX-AL01

 

RXRX-AL02

 

 

Description

Part Number

Quantity

Part Number

Quantity

 

WIRE NUT

45-18058-01

1

45-18058-01

2

 

 

 

 

 

 

 

ANTI CYCLE DELAY CONTROL

47-104319-01

1

AS-104325-01

1

 

 

 

 

 

 

 

HIGH PRESSURE CONTROL

47-102290-01

1

47-102290-01

2

 

 

 

 

 

 

 

SCREW-SHEET METAL 6-20 X 3/4

63-22153-0ϳ

4

63-22153-07

4

 

 

 

 

 

 

 

WIRE TIE

64-17606-01

1

64-17606-01

1

 

 

 

 

 

 

 

ADAPTER TEE

83-21457-02

1

83-21457-02

2

 

 

 

 

 

 

 

INSTALLATION INSTRUCTIONS

92-104323-01

1

92-104323-01

1

 

 

 

 

 

 

 

WIRING DIAGRAM

90-104329-01

1

90-104329-02

1

 

 

 

 

 

 

 

WIRE HARNESS

AS-104330-01

1

AS-104330-03

1

 

 

 

 

 

 

 

WIRE HARNESS

AS-104330-02

1

AS-104330-04

1

 

 

 

 

 

 

 

! WARNING

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS KIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION, ADJUSTMENT, OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

! WARNING

BEFORE BEGINNING ANY MODIFICATION, BE SURE MAIN DISCONNECT SWITCH IS IN THE “OFF” POSITION. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. TAG DISCONNECT WITH A SUITABLE WARNING LABEL.

TOOLS/SUPPLIES REQUIRED

a.1/4” nut driver.

b.wire cutters/stripper.

c.handheld voltmeter/ohmmeter.

d.electrical tape.

e.9/16” open end wrench

f.7/16” open end wrench

g.power drill.

GAS, ELECTRIC AND SELF-CONTAINED UNITS RXRX-AL01 INSTALLATION 7.5 AND 10.0-TON

1. HIGH PRESSURE SWITCH INSTALLATION

a.Shut off power to unit (see warning above).

b.Remove blower compartment access panel.

c.Remove brass cap from Schrader valve located on liquid line (see Figure 1) that is normally used for the low ambient control accessory. If a low ambient control accessory is already installed, it must be removed first.

d.Using the 9/16” open end wrench, assemble the High Pressure Control to the Adapter Fitting that does not have a valve core. Always “backup” the fitting when tightening using the 7/16” open end wrench. Attach pressure control/adapter fitting onto liquid line access fitting and torque to 8-10 ft./lbs. (see Figure 1) using the same wrenches and technique.

e.If a low ambient control accessory is used, install it next using the same torque settings.

92-104323-01-01

SUPERSEDES 92-104323-01-00

Rheem RXRX-AL01, RXRX-AL02 Installation Manual

FIGURE 1

(Note: 7.5 and 10 ton models will have one liquid line)

2. SWITCH ELECTRICAL CONNECTIONS

a.Route wires on the new auto-reset refrigerant high pressure switch toward the unit control box by placing them across the wire trough over the indoor coil. The indoor top panel may need to be partially lifted by removing fasteners to complete this step. The two-pin connector (Plug 22) on Figure 4 must be visible in the control box of the unit when finished.

b.Remove the existing manual reset refrigerant high pressure switch from the electrical circuit by cutting the wire leads to the original switch and connecting the wire leads still in the circuit together with a wire nut. DANGER: The remaining steps must be completed to provide overpressure protection!!!

c.Use electrical tape over the wirenut to secure and provide moisture protection.

d.Secure loose wires with wire tie.

e.Replace blower compartment access cover.

3.ANTI-CYCLE DELAY CONTROL INSTALLATION

a.Shut off power to unit (see warning above).

b.Remove control box access panel.

c.Remove control box cover.

d.Remove control shelf (see Figure 2).

e.Drill holes (see Figure 2) and install new control board on control shelf with included fasteners.

f.Reinstall control shelf.

FIGURE 2

2

4. CONTROL WIRING CONNECTIONS

a.Using the wire harnesses provided with the kit, make the electrical connections as shown on the wiring diagram.

1.Remove the yellow 24 volt wire from the compressor contactor coil (CC1) and attach it to the input “Y” on the AntiCycle Delay Control.

2.Connect the purple wire from PL8 to CC1 coil where the yellow wire was removed in the previous step (see Figure 4).

b.Replace control box cover.

c.Paste included Anti-Cycle Delay Control wiring diagram on control box cover near the unit wiring diagram.

d.Replace control box access panel.

e.Restore power to unit and check for proper operation.

GAS, ELECTRIC AND SELF-CONTAINED UNITS RXRX-AL02 INSTALLATION 12.5-TON

1.INSTALLATION OF HIGH PRESSURE SWITCHES

a.Shut off power to unit (see warning above).

b.Remove blower compartment access panel.

c.Remove brass cap from Schrader valve located on refrigerant circuit #1 liquid line (see Figure 1) that is normally used for the low ambient control accessory. If the low ambient control is already installed, it must be removed first.

d.Using the 9/16” open end wrench, assemble the High Pressure Control to the Adapter Fitting that does not have a valve core. Always “backup” the fitting when tightening using the 7/16” open end wrench. Attach pressure control/adapter fitting onto liquid line access fitting and torque to 8-10 ft./lbs. (see Figure 1) using the same wrenches and technique.

e.If a low ambient control accessory is used, install it next using the same torque settings.

f.Repeat steps “c” through “e” above for refrigerant circuit #2 liquid line.

2. SWITCH ELECTRICAL CONNECTIONS

a.Route wires on the new auto-reset refrigerant high pressure switches toward the unit control box by placing them across the wire trough over the indoor coil. The indoor top panel may need to be partially lifted by removing fasteners to complete this step. The two-pin connectors (Plug 22 & Plug 23) on Figure 5 must be visible in the control box of the unit when finished.

b.Remove the existing manual reset refrigerant high pressure switches from the electrical circuit by first cutting the wire leads for refrigerant circuit #1 and connecting the wire leads still in the circuit together with a wire nut. Repeat for refrigerant circuit #2. DANGER: The remaining steps must be completed to provide overpressure protection!!!

c.Use electrical tape over the wire nuts to secure and provide moisture protection.

d.Secure loose wires with wire tie.

e.Replace blower compartment access cover.

3.ANTI-CYCLE DELAY CONTROL INSTALLATION

a.Shut off power to unit (see warning above).

b.Remove control box access panel.

c.Remove control box cover.

d.Remove control shelf (see Figure 2).

e.Remove control boards from control board assembly without disturbing attached wiring.

f.Discard sheet metal base from control board assembly.

g.Drill holes (see Figure 2) and install two new control boards on control shelf with included fasteners.

h.Reinstall control shelf.

4. CONTROL WIRING CONNECTIONS

a.Using the wire harnesses provided with the kit, make the electrical connections as shown on the wiring diagram.

1.Remove the yellow 24 volt wire from the compressor contactor coil (CC1) and attach it to the input “Y” on the AntiCycle Delay Control.

2.Connect the purple wire from PL8 to CC1 coil where the yellow wire was removed in the previous step (see ACD1 on Figure 5). The orange 24 volt wire that originally went to the compressor contactor (CC2) is now the input “Y” to the second stage Anti-Cycle Delay Control (ACD2) board.

b.Verify Plug 20 & Plug 22 are connected to the refrigerant high pressure switch on refrigerant circuit #1.

c.Verify Plug 21 & Plug 23 are connected to the refrigerant high pressure switch on refrigerant circuit #2.

d.Replace control box cover.

e.Paste included Anti-Cycle Delay Control wiring diagram on control box cover near the unit wiring diagram.

f.Replace control box access panel.

g.Restore power to unit and check for proper operation.

GAS, ELECTRIC AND

SELF-CONTAINED UNITS

RXRX-AL02 INSTALLATION

15.0 AND 20.0-TON

1. HIGH PRESSURE SWITCH INSTALLATION

a.Shut off power to unit (see warning above).

b.Open blower compartment access door.

c.Remove brass cap from Schrader valve located on refrigerant circuit #1 liquid line (see Figure 1) that is normally used for the low ambient control accessory. If the low ambient control is already installed, it must be removed first.

d.Using the 9/16” open end wrench, assemble the High Pressure Control to the Adapter Fitting that does not have a valve core. Always “backup” the fitting when tightening using the 7/16” open end wrench. Attach pressure control/adapter fitting onto liquid line access fitting and torque to 8-10 ft./lbs. (see Figure 1) using the same wrenches and technique.

e.If a low ambient control accessory is used, install it next using the same torque settings.

f.Repeat steps “c” through “e” above for refrigerant circuit #2 liquid line.

3

Loading...
+ 5 hidden pages