90 PLUS GAS FURNACE
INSTALLATION INSTRUCTIONS
HONEYWELL VALVE
ELECTRIC IGNITION RXGJ-FP33
BEFORE INSTALLING THIS KIT, CHECK CONVERSION KIT INDEX TO BE
SURE YOU HAVE THE RIGHT KIT FOR THE FURNACE MODEL YOU ARE CONVERTING.
PARTS LIST
DESCRIPTION PART NUMBER FP33
Installation Instructions 92-104443-01 1
Conversion Label 92-18153-05 1
Conversion Kit #396221-2 (Honeywell) 60-22513-03 1
Orifice - Burner (1.10 mm) 62-22175-90 8
!
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR
PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOR OUGHLY BEFORE ATTEMPTING ANY MAINTENANCE OR OPERATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE
RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
FOR CANADIAN INSTALLATIONS, THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S
AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS
OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
IMPORTANT: DAMAGE TO THE PRODUCT RESULTING
FROM FAILURE TO FOLLOW INSTRUCTIONS OR USE OF
UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE
MANUFACTURER’S PRODUCT WARRANTY COVERAGE.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET:
The main burner orifices in this kit are sized for nameplate
input and intended for installations at elevations up to 2,000
feet only. For elevations above 2,000 feet, the burner orifices
must be sized as shown in Chart 5 in Conversion Kit Index 9221519-69.
In USA: All gas piping must comply with the latest NFPA 54
National Fuel Gas Code and all state and local codes. All electrical wiring must comply with the latest NFPA 70, National
Electrical Code and all state and local codes.
In Canada: All gas piping must comply with the latest CAN1B149-1 & 2 installation codes for gas burning appliances and all
provincial and local codes, Part 1– CSA Standard C22.1 and all
provincial and local codes.
FIGURE 1
DIRECT SPARK IGNITION LOCATION
DIRECT
SPARK
IGNITOR
MAIN
BURNER
ORIFICE
SUPERSEDES 92-104443-01-00
92-104443-01-01
KIT INSTALLATION (SEE ILLUSTRATION)
1. Disconnect the gas line at the union ahead of the combination gas valve.
2. Remove burners from assembly.
A. To Change Burner Orifice
Remove each burner orifice from the manifold. See
Figure 1. Refer to Table 1 and verify the correct burner
orifice size required. Open the burner orifice envelope
marked with the orifice drill size required and install in the
burner when the unit is converted to LP gas.
B. Convert Gas Valve to LP Gas (See Figure 2)
See Honeywell envelope kit #396221-2 for proper LP regulator spring and instructions. If unsure of which spring is
correct for the valve you are converting refer to Figure 3.
Manifold gas pressure must be adjusted to 10ⴖ W.C. after
valve conversion to LP gas with furnace in operation and
proper gas supply pressure (see rating plate). The gas
supply line pressure should be between 11ⴖ and 14ⴖ W.C.
at the appliance.
FIGURE 2
CONVERTING HONEYWELL VR8215 CONTROLS FROM NATURAL GAS
TO L.P. GAS OPERATION
NOTE: Use a pipe compound resistant to the action of the lique-
fied petroleum gases at all threaded pipe connections.
3. Place the conversion label adjacent to the rating plate.
4. Turn on gas supply and electrical supply.
DO NOT REMOVE OR DEFACE ORIGINAL RATING PLATE.
5. Check unit thoroughly for gas leaks — with soap and water —
not with a flame.
6. Follow lighting instructions to put furnace into operation.
7. Operate thermostat to check unit operation for ignition and
extinction characteristics.
COMPLETING CONVERSION
1. Using a ballpoint indelible pen, record the following informa tion on label 92-18153-05 provided in this kit.
a. Date of conversion.
b. Installer’s name, address and telephone number.
c. Burner orifice size.
2. Place completed conversion label next to the rating plate.
3. Install the burner compartment access door.
FIGURE 3
HONEYWELL REGULATOR SPRINGS (ACTUAL SIZE)
2 CM 0313