Rheem RXGJ-FP33 Installation Manual

90 PLUS GAS FURNACE
INSTALLATION INSTRUCTIONS
HONEYWELL VALVE
ELECTRIC IGNITION RXGJ-FP33
BEFORE INSTALLING THIS KIT, CHECK CONVERSION KIT INDEX TO BE
SURE YOU HAVE THE RIGHT KIT FOR THE FURNACE MODEL YOU ARE CONVERTING.
PARTS LIST
DESCRIPTION PART NUMBER FP33
!
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOR ­ OUGHLY BEFORE ATTEMPTING ANY MAINTENANCE OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FOR CANADIAN INSTALLATIONS, THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE WITH REQUIREMENTS OF THE MANUFACTURER, PROVIN­CIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
IMPORTANT: DAMAGE TO THE PRODUCT RESULTING FROM FAILURE TO FOLLOW INSTRUCTIONS OR USE OF UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S PRODUCT WARRANTY COVERAGE.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET:
The main burner orifices in this kit are sized for nameplate input and intended for installations at elevations up to 2,000 feet only. For elevations above 2,000 feet, the burner orifices must be sized as shown in Chart 5 in Conversion Kit Index 92­21519-69.
In USA: All gas piping must comply with the latest NFPA 54 National Fuel Gas Code and all state and local codes. All elec­trical wiring must comply with the latest NFPA 70, National Electrical Code and all state and local codes.
In Canada: All gas piping must comply with the latest CAN1­B149-1 & 2 installation codes for gas burning appliances and all provincial and local codes, Part 1– CSA Standard C22.1 and all provincial and local codes.
FIGURE 1
DIRECT SPARK IGNITION LOCATION
DIRECT SPARK IGNITOR
MAIN BURNER ORIFICE
SUPERSEDES 92-104443-01-00
92-104443-01-01
KIT INSTALLATION (SEE ILLUSTRATION)
1. Disconnect the gas line at the union ahead of the combina­tion gas valve.
2. Remove burners from assembly.
A. To Change Burner Orifice
Remove each burner orifice from the manifold. See Figure 1. Refer to Table 1 and verify the correct burner orifice size required. Open the burner orifice envelope marked with the orifice drill size required and install in the burner when the unit is converted to LP gas.
B. Convert Gas Valve to LP Gas (See Figure 2)
See Honeywell envelope kit #396221-2 for proper LP reg­ulator spring and instructions. If unsure of which spring is correct for the valve you are converting refer to Figure 3.
Manifold gas pressure must be adjusted to 10W.C. after valve conversion to LP gas with furnace in operation and proper gas supply pressure (see rating plate). The gas supply line pressure should be between 11and 14W.C. at the appliance.
FIGURE 2
CONVERTING HONEYWELL VR8215 CONTROLS FROM NATURAL GAS TO L.P. GAS OPERATION
NOTE: Use a pipe compound resistant to the action of the lique-
fied petroleum gases at all threaded pipe connections.
3. Place the conversion label adjacent to the rating plate.
4. Turn on gas supply and electrical supply.
DO NOT REMOVE OR DEFACE ORIGINAL RATING PLATE.
5. Check unit thoroughly for gas leaks — with soap and water — not with a flame.
6. Follow lighting instructions to put furnace into operation.
7. Operate thermostat to check unit operation for ignition and extinction characteristics.
COMPLETING CONVERSION
1. Using a ballpoint indelible pen, record the following informa ­ tion on label 92-18153-05 provided in this kit.
a. Date of conversion. b. Installer’s name, address and telephone number. c. Burner orifice size.
2. Place completed conversion label next to the rating plate.
3. Install the burner compartment access door.
FIGURE 3
HONEYWELL REGULATOR SPRINGS (ACTUAL SIZE)
2 CM 0313
Loading...