Water
Commercial Gas
Tankless Water Heaters
Rheem Commercial Condensing Tankless Water Heaters
Commercial Tankless Models Commercial Tankless Models with Manifold Control
RTGH-C95DVL
Rheem Model Number
Operation / Installation Forced Combustion / Indoor Only Forced Combustion / Outdoor Only
Minimum/Maximum Gas Rate (Input) 11,000 / 199,000
Approved Gas Types Natural Gas Liquid Propane Natural Gas Liquid Propane
Thermal Efficiency 96% 95%
Dimensions (Inches) Height: 27-1/2 / Width: 18-1/2 / Depth: 9-3/4 / Weight: 82 Lbs.
Electrical
– Appliance (120 VAC/60 Hz)
– Temperature Controler 12 V DC
Ignition System Direct Ignition
Hot Water Capacity
– Min Flow Rate (Gpm) 0.4
– Minimum Activation Flow Rate 0.26
– Maximum Flow Rate 9.5
Temperature
– Factory Default Range 100°-120°F
– Optional Range 85°-185°F
Temperature (without Remote) 120°F
Freeze Protection To (Ambient Temp.) -30°F
Service Connections
– Gas Supply 3/4" (19mm) MNPT
– Cold Water Inlet 3/4" (19mm) MNPT
– Hot Water Outlet 3/4" (19mm) MNPT
Controller UMC-117
Controller Cable 18 AWG
RTGH-C95XL
RTGH-C95DVLN /
RTGH-CM95DVLN
RTGH-CM95DVL
RTGH-C95DVLP /
RTGH-CM95DVLP
LEED Points = 2
RTGH-C95XLN /
RTGH-CM95XLN
RTGH-CM95XL
RTGH-C95XLP /
RTGH-CM95XLP
Chart continued on reverse
INTEGRATED HOME COMFOR
PRINTED IN U.S.A. 06/17 WP FORM NO. TK-601RH

Water
Commercial Gas
Tankless Water Heaters
Rheem Commercial Condensing Tankless Water Heaters Continued
Rheem Model Number
RTGH-C95DVLN /
RTGH-CM95DVLN
Safety Devices
Clearances Combustible and
Noncombustable
– Top of Heater 12" (30cm)
– Front of Heater 12" (30cm)
– Sides of Heater 0.5" (1.3cm)
– Back of Heater 0"
– Bottom of Heater 12" (30cm)
– From Vent Pipe 0"
Min/Max Gas Supply Pressure
4" wc (1.0kPa) / 10.5" wc
(2.6kPa)
Min/Max Water Supply Pressure 14 psi (97kPa) / 150 psi (1035kPa)
NOx Complies with South Coast Air Quality Management District 14 ng/J or 20 ppm NOx emission levels
Venting
Centrotherm PPs (polypropelene solid) N/A
PVC (Schedule 40, ASTM D-1785) N/A
CPVC (Schedule 40, ASTM) N/A
ABS (Schedule 40, ASTM D-2661) N/A
Common Venting
Centrotherm PPs
(polypropelene solid)
Power Venting (Room Air Intake) Individual or Common Vent Individual N/A
Warranty 5 Year Heat Exchanger / 5 Year Parts / 1 Year Labor
RTGH-C95DVLP /
RTGH-CM95DVLP
RTGH-C95XLN /
RTGH-CM95XLN
*24 inches (610mm) reccomended for service
8" wc (2.0kPa) / 13" wc
4" wc (1.0kPa) / 10.5" wc
(3.2kPa)
N/A N/A
(2.6kPa)
RTGH-C95XLP /
RTGH-CM95XLP
8" wc (2.0kPa) / 13" wc
(3.2kPa)
51/2
1
/4”
Maximum Common Vent Length
Number
of Units
2 100 100
3 100 100 100
4 100 100 100
27 1/2”
Indoor
Direct
Vent
27 1/2”
Outdoor
5 100 100 100
6 82 82 82
7 55 55 55
8 43 43 43
To Determine Equivalent Vent Lengths, Add:
87 Degree Elbow 5.0' (1.5m)
4 1/4”
7 1/2”
18 1/2”
2 1/2”2 3/4”
2 3/4”
1
/2”
3
6 3/4”
3
9
18 1/2”
1
/4”
3
1
/2”
3
7 1/2”
3
9
/4”
3
2
2 1/2”
2 3/4”
6 3/4”
/4”
/4”
4 1/4”
1
/4”
3
45 Degree Elbow 2.5' (0.8m)
Tankless Multi-Unit Flow Rates
Total System BTU
Manifold
based on
QTY
199,900 Btu per Unit
1 199,900 9.5 8.4 7.5 6.3 5.4 4.9 4.7 4.2 3.8 3.4 3.1 2.7
2 399,800 19.0 16.7 15.0 12.5 10.7 9.8 9.4 8.4 7.5 6.8 6.3 5.4
3 599,700 28.5 25.1 22.5 18.8 16.1 14.6 14.1 12.5 11.3 10.2 9.4 8.1
4 799,600 38.0 33.4 30.1 25.1 21.5 19.5 18.8 16.7 15.0 13.7 12.5 10.7
5 999,500 47.5 41.8 37.6 31.3 26.8 24.4 23.5 20.9 18.8 17.1 15.7 13.4
6 1,199,400 57.0 50.1 45.1 37.6 32.2 29.3 28.2 25.1 22.5 20.5 18.8 16.1
7 1,399,300 66.5 58.5 52.6 43.8 37.6 34.2 32.9 29.2 26.3 23.9 21.9 18.8
8 1,599,200 76.0 66.8 60.1 50.1 42.9 39.0 37.6 33.4 30.1 27.3 25.1 21.5
9 1,799,100 85.5 75.2 67.6 56.4 48.3 43.9 42.3 37.6 33.8 30.7 28.2 24.2
10 1,999,000 95.0 83.5 75.2 62.6 53.7 48.8 47.0 41.8 37.6 34.2 31.3 26.8
11 2,198,900 104.5 91.9 82.7 68.9 59.1 53.7 51.7 45.9 41.3 37.6 34.4 29.5
12 2,398,800 114.0 100.2 90.2 75.2 64.4 58.6 56.4 50.1 45.1 41.0 37.6 32.2
13 2,598,700 123.5 108.6 97.7 81.4 69.8 63.4 61.1 54.3 48.9 44.4 40.7 34.9
14 2,798,600 133.0 116.9 105.2 87.7 75.2 68.3 65.8 58.5 52.6 47.8 43.8 37.6
15 2,998,500 142.5 125.3 112.7 94.0 80.5 73.2 70.5 62.6 56.4 51.2 47.0 40.3
16 3,198,400 152.0 133.6 120.3 100.2 85.9 78.1 75.2 66.8 60.1 54.7 50.1 42.9
17 3,398,300 161.5 142.0 127.8 106.5 91.3 83.0 79.9 71.0 63.9 58.1 53.2 45.6
18 3,598,200 171.0 150.3 135.3 112.7 96.6 87.9 84.6 75.2 67.6 61.5 56.4 48.3
19 3,798,100 180.5 158.7 142.8 119.0 102.0 92.7 89.3 79.3 71.4 64.9 59.5 51.0
20 3,998,000 190.0 167.0 150.3 125.3 107.4 97.6 94.0 83.5 75.2 68.3 62.6 53.7
35 45 50 60 70 77 80 90 100 110 120 140
Total System Gallons Per Minute (GPM) - Per Temperature Rise (∆T)
MAXIMUM VENT LENGTH (EQ. FT.)
Direct Vent Power Vent (Room Air)
Air Intake Exhaust Air Intake Exhaust
100
N/A
• The vent termination does not count as part of the
straight pipe equivalent when determining the total
8" Common Vent
vent length.
• The system may be vented horizontally through a
wall or vertically through the roof.
• Header kits have already been counted and do not
need to be added.
Maximum Single Unit Vent Length (intake/outlet):
NUMBER
OF 90°
ELBOWS
0 or 1 5.0 ft. (1.5 m) 38.0 ft. (11.6 m) 94.0 ft. (28.6 m)
(ULC-S636 pipe must be used for Canada.)
MAX. LENGTH
OF 2"
STRAIGHT PIPE
MAX. LENGTH
OF 3"
STRAIGHT PIPE
MAX. LENGTH
OF 4"
STRAIGHT PIPE
2 3.5 ft. (1.0 m) 36.5 ft. (11.1 m) 88.0 ft. (26.8 m)
3 2.0 ft. (0.6 m) 35.0 ft. (10.6 m) 82.0 ft. (25.0 m)
4 N/A 33.5 ft. (10.2 m) 76.0 ft. (23.2 m)
5 N/A 32.0 ft. (9.8 m) 70.0 ft. (21.3 m)
6 N/A 30.5 ft. (9.3 m) 64.0 ft. (19.5 m)
Rheem Water Heating • 1115 Northmeadow Parkway, Suite 100
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1
Roswell, Georgia 30076 • www.rheem.com
INTEGRATED HOME COMFOR
Brampton, Ontario L6Y 0P5 • www.rheem.com
PRINTED IN U.S.A. 06/17 WP FORM NO. TK-601RH
2

Water
Commercial Tankless Water Heaters
Suggested Specifications Sheet
Suggested Specifications
RTGH-C95DVLN, RTGH-C95DVLP, RTGH-C95XLN, or RTGH-C95XLP
The fully modulating, on-demand, condensing gas fired tankless water heater(s) shall be Rheem models RTGH-C95DVLN,
RTGH-C95DVLP, RTGH-C95XLN, or RTGH-C95XLP, having an input rating of 11,000 Btu/h through 199,000 Btu/h and available
in NG or LP. The heater(s) shall have ¾ in. male NPT water and gas connections. The heater(s) shall have a minimum flow rate
of 0.26 GPM and an activation rate of 0.40 GPM. An integrated condensate neutralizer will be included with every unit. The inlet
gas supply pressures shall be 4.0 in. WC (min.) up to 10.5 in. WC (max) for NG and 8.0 in. WC (min.) up to 13 in. WC (max.) for
LP. The heater(s) shall be factory s upplied with a manual gas shutoff valve, a pressure relief valve, 2 water service valves and a
temperature remote, RTG20006, that can be installed up to 195 ft. from the heater using 18 gauge ( minimum) control wire. The
temperature remote shall provide diagnostic information, fault history, and heater set temperature with a minimum set water
temperature of 85°F and maximum set water temperature of 185°F. The heater(s) shall operate using 120 V / 60 Hz power source.
The heater(s) will incorporate a factory installed power cord (indoor models only).
The indoor heater(s) shall be vented with 2", 3" or 4" diameter PVC schedule 40, CPVC schedule 40, CentroTherm PPs or ABS
(U. S. only) with a length not to exceed 5 ft. (equivalent) for 2", 38 ft. (equivalent) for 3" vent or 94 ft. (equivalent) for 4" vent,
terminating horizontally or vertically. The intake pipe may use material such as PVC, ABS, PP, or aluminum and cannot exceed 5
ft. (equivalent) for 2", 38 ft. (equivalent) for 3" vent or 94 ft. (equivalent) for 4" vent. For single vent applications the heater can use
room make up air. RTGH-C95DVLN or RTGH-CM95DVLN can be common vented with up to 8 units in-line with an 8" diameter
trunk line. The outdoor heater(s) shall be constructed with an integral exhaust vent on the front of the heater.
The water heater(s) shall use a copper, fin tube primary heat exchanger. The secondary heat exchanger shall be constructed from
stainless steel 316L. The heater(s) shall be controlled by an on-board solid-state printed circuit board which uses the following
factory installed components: thermistors to monitor water inlet and outlet temperatures and heat exchanger temperature; a flow
sensor to measure flow rate; flame rods to monitor flame is on or off and if oxygen level is appropriate. The heater shall include inline fusing for electrical surge protection, an electronic igniter coil, aluminized stainless steel burners, Guardian OFW overheat film
wrap, heat exchanger thermistor and outlet thermistor to work as high limit switch, modulating gas valve, an ambient thermistor
and freeze protection to -30°F.
The heaters can manifold controls to EZ-Link up to 2 heaters to provide additional capacity. The EZ-Link controls shall be built
onto the on-board solid-state printed circuit board and does not require external controls. The heaters can use a MIC-6 controller,
RTG20213A, to manifold 2-6 heaters or a MIC-185 controller, RTG20126A & RTG20126B, to manifold 2-20 heaters. The EZ-Link,
MIC-6, or MIC-185 controls shall modulate the system for the most efficient performance and rotate the initial heater for balanced
duty/cycle operation. The heater(s) shall be CSA approved for sale in the United States and Canada, ENERGY STAR
with a Thermal Efficiency of 96% for Indoor and 95% for Outdoor units, meets the energy efficiency requirements of the U.S.
Department of Energy and ASHRAE 90.1-2007, and complies with Ultra-Low NOx emissions of 14 ng/J or 20 ppm.
®
qualified
Suggested Specifications
RTGH-CM95DVLN, RTGH-CM95DVLP, RTGH-CM95XLN, or RTGH-CM95XLP
The fully modulating, on-demand, condensing gas fired tankless water heater(s) shall be Rheem models RTGH-CM95DVLN,
RTGH-CM95DVLP, RTGH-CM95XLN, or RTGH-CM95XLP
Same as non-manifold ready (see above) until 4th paragraph
The manifold ready heaters can manifold controls to EZ-link up to 20 heaters to provide additional capacity. Each manifold ready
heater shall include a factory installed control module and the control cable shall be included with the units. The heaters controls
shall modulate the system for the most efficient performance and rotate the initial heater for balanced duty/cycle operation. The
heater(s) shall be CSA approved for sale in the United States and Canada, ENERGY STAR
Efficiency of 96% for Indoor and 95% for Outdoor units, meets the energy efficiency requirements of the U. S. Department of
Energy and ASHRAE 90.1-2007, and complies with Ultra-Low NOx emissions of 14 ng/J or 20 ppm.
®
qualified with a minimum Thermal