Rheem RPPB User Manual

Page 1
FORM NO. P11-759 REV. 2
Supersedes Form No. P11-759 Rev. 1
RPPB- SERIES
Seven Models
14 SEER with efficiencies ranging up to 14.40 SEER in certain matched systems. Nominal Sizes 1
/2 to 5 Tons
[5.28 kW] to [17.58 kW]
The Rheem®RPPB- Classic Series®Heat Pump Outdoor units can provide year-round heating and cooling comfort for residential, multi-family and light commercial applica­tions. They are designed to operate with Rheem indoor units with cooling and heating capacities certified under the ARI Certification program.
The Rheem RBHK- Air Handler equipped with auxiliary heating elements for supplementary heat was designed especially for use with the RPPB- Heat Pump. Together they provide systems capable of delivering a maximum HSPF (Heating Seasonal Performance Factor) of 8.90 in the heating mode or a maximum standard S.E.E.R. (Seasonal Energy Efficiency Ratio) of 14.40 in the cooling mode.
The following additional features, plus its energy-saving characteristics, make the RPPB- Heat Pump outdoor unit an excellent choice for new construction or upgrading your present system.
Attractive, louvered wrap around jacket protects coil from
weather extremes and yard hazards. Top grille is steel reinforced for extra strength. Cabinet is powder painted for all weather protection.
Four sided outdoor coil design allows compressor opera-
tion with access panel removed.
Air is discharged upward away from bushes and shrubs.
The discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.
Exclusive Combination Grille/Motor Mount secures the
fan motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.
All controls are accessible by removing one service
panel. Removable top grille provides access to the out­door fan motor and outdoor coil.
Compressor compartment offers additional protection
from the elements and reduces operating noise.
Single speed, 8-pole fan motor is designed for low
speed, quieter, energy-saving operation.
Non-cycling reversing valve.
All models meet or exceed a 1000-hour salt spray test
per ASTM B117 Standard Practice for Operating Salt Spray Testing Apparatus.
HEAT PUMPS
*“CERTIFIED UNDER THE
A.R.I. CERTIFICATION
PROGRAM—A.R.I. STANDARD 240-81”
ENER UIDE
Seasonal Energy Efficiency Ratio - SEER
THIS MODEL
14.00
10.0
USES LESS ENERGY
17.0
Page 2
2 Rheem Manufacturing Company
Drawn Painted Base Pan.
Accessories
Low Ambient Control—Allows low temperature operation in the cooling cycle down to 0°F [-17.8°C] outdoor temperature. It is recommended that this control be installed in units to be operated for cooling at outdoor ambient temperatures under 65°F [18°C]. (Model No. RXPZ-C01)
Outdoor Thermostats— RXPT-A01—One outdoor thermostat in box. RXPT-A02—One outdoor thermostat for mounting in box for use with RXPT-A01 or A03. RXPT-A03—One outdoor thermostat with emergency Heat Relay wired and mounted in box. RXPT-A04—Tne outdoor thermostats with emergency Heat Relay wired and mounted in box.
Heat Pump Monitor—Indicates inefficient operation or malfunction of heat pump. (Model No. RXPM-B01)
Thermostats and Subbases—Available through the PROSTOCK
®
Department.
Compressor Time Delay Control—Compressor will remain off for five minutes after power or thermostat interruption, allowing system pressures to equalize. Starting during high pressure conditions can result in shortened compressor life. (Model No. RXMD-B01)
Blower Time Delay Control—RXMD-C02.
Fossil Fuel Kits—RXPF-01
RXPF-02
Engineering Features
RPPB- Series Heat Pump Outdoor Unit
1. Scroll compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.
2. Copper Tube/Aluminum Fin Coils—Both indoor and outdoor coils.
3. Strong, Attractive Cabinet—Constructed of powder painted steel.
Louvered design protects the coil from damage.
4. Internal Check Valve—Provides for more quiet refrigerant metering.
5. Manual Reset High Pressure Control—Deactivates system if
abnormally high pressure occurs.
6. Drawn, Painted Base Pan—For extra corrosion resistance and sound reduction.
7. Hard Start Components—Offer additional starting torque to cover a wide range of voltage and pressure variations.
8. Non-Cycling Reversing Valve—Eliminates discharge noises on each heating cycle.
9. Hot Gas Muffler—Reduces noise in heating cycle.
10. Suction Line Accumulator—Provides protection for the
compressor.
11. Bi-Directional Filter Drier—Provided on all models.
12. Se rvice valves are standard on all models.
13. Refrigerant Metering—TX valves accurately meter refrigerant into
indoor and outdoor coils.
14. Demand Defrost—Provides complete defrost when defrost is required.
Convenience Features
The scroll compressor models, additionally have a 10 year compressor warranty as standard.
All refrigerant connections are on the exterior of the unit, located close to the ground for neat appearing installations.
Coil design permits compressor operation with the access panel removed.
Control box is fully accessible in the upper part of the cabinet, just under the access panel.
Power and control wiring are kept separate.
Every unit is factory charged and tested.
Model Number Identification
R P P B —024
COOLING
CAPACITY
018 = 18,000 BTU/HR [5.28 kW] 024 = 24,000 BTU/HR [7.03 kW] 030 = 30,000 BTU/HR [8.79 kW] 036 = 36,000 BTU/HR [10.55 kW] 042 = 42,000 BTU/HR [12.31 kW] 048 = 48,000 BTU/HR [14.07 kW] 049 = 48,000 BTU/HR [14.07 kW] 060 = 60,000 BTU/HR [17.58 kW] 061 = 60,000 BTU/HR [17.58 kW]
J A Z
RHEEM REMOTE
HEAT PUMP
HIGH
EFFICIENCY
(STANDARD)
DESIGN SERIES
B = SECOND DESIGN
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
VARIATIONS
A = STANDARD
COOLING
CONNECTION
FITTING
Z = SWEAT W/SCROLL
All controls and compressor are accessible
for servicing by removal of the service panel.
[ ] Designates Metric Conversions
Page 3
Rheem Manufacturing Company 3
COPELAND®SCROLL
®
COMPRESSOR
The Copeland scroll compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor technology. The advanced scroll compressor offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The Copeland Scroll also has low start torque, eliminating start problems in the field. And its unique design enables the RPPB- heat pump to perform efficiently, quietly and reliably.
For all season home comfort, performance and energy conservation, choose a Rheem RPPB- Series Heat Pump and RBHK- Series Air Handler.
More than a reverse cycle air conditioner, it’s a specially designed combination Winter/Summer comfort system using a single indoor coil for heating and cooling.
To choose an RBHK- Air Handler designed for use with the RPPB- Heat Pump, refer to the Performance Data Tables and/or the air handler specification sheet.
Rheem Heat Pump System
Page 4
4 Rheem Manufacturing Company
Performance Data ARI Standard Conditions—Single Phase (Scroll Compressor)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by DOE test procedures.
[ ] Designates Metric Conversions
ARI Cooling Performance ARI Heating Performance (70°F [21°C] Indoor)
95°F [35°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
12,750
[3.7]
12,600
[3.7]
13,150
[3.9]
13,450
[3.9]
13,450
[3.9]
13,500
[4.0]
13,100
[3.8]
13,100
[3.8]
13,450
[3.9]
13,500
[4.0]
16,100
[4.7]
15,700
[4.6]
16,700
[4.9]
16,900
[5.0]
16,950
[5.0]
17,000
[5.0]
16,950
[5.0]
16,400
[4.8]
16,400
[4.8]
16,800
[4.9]
17,000
[5.0]
21,250
[6.2]
19,600
[5.7]
22,050
[6.5]
21,700
[6.4]
21,800
[6.4]
21,850
[6.4]
21,800
[6.4]
21,200
[6.2]
Net Latent BTU/H
[kW]
5,750
[1.7]
5,700
[1.7]
5,750
[1.7]
5,950
[1.7]
5,950
[1.7]
5,900
[1.7]
5,700
[1.7]
5,700
[1.7]
5,850
[1.7]
5,900
[1.7]
6,700
[2.0]
6,500
[1.9]
6,700
[2.0]
6,700
[2.0]
6,850
[2.0]
6,800
[2.0]
6,850
[2.0]
6,600
[1.9]
6,600
[1.9]
6,800
[2.0]
6,800
[2.0]
6,950
[2.0]
7,000
[2.1]
6,950
[2.0]
6,900
[2.0]
6,800
[2.0]
6,950
[2.0]
7,000
[2.1]
6,800
[2.0]
EER
SEER
10.65 12.10
10.65 12.20
12.15 14.00
12.45 14.10
12.50 14.10
12.65 14.10
12.10 13.90
12.10 13.95
12.15 14.00
12.25 14.10
10.75 12.40
10.75 12.50
12.10 14.15
12.00 14.00
12.10 14.15
12.25 14.35
12.15 14.25
12.30 14.35
12.30 14.35
12.15 14.20
12.30 14.35
10.80 12.00
10.80 12.10
12.10 14.00
11.60 13.65
11.85 14.00
11.95 14.00
11.90 14.00
12.05 13.90
Indoor
CFM [L/s]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
975
[460]
995
[470] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,025
[484] 1,000
[472]
Outdoor Air
47°F [8.5°C] DB/
43°F [6°C] WB
DOE High Temp.
BTU/H
[kW]
18,700
[5.5]
18,700
[5.5]
18,100
[5.3]
18,100
[5.3]
18,100
[5.3]
18,100
[5.3]
18,200
[5.3]
18,200
[5.3]
18,100
[5.3]
18,100
[5.3]
23,200
[6.8]
23,200
[6.8]
22,600
[6.6]
22,600
[6.6]
22,600
[6.6]
22,600
[6.6]
22,600
[6.6]
22,400
[6.6]
22,400
[6.6]
22,600
[6.6]
22,400
[6.6]
28,400
[8.3]
28,400
[8.3]
27,800
[8.1]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
COP
3.20
3.20
3.44
3.46
3.47
3.49
3.44
3.44
3.44
3.46
3.24
3.24
3.46
3.40
3.42
3.45
3.43
3.48
3.48
3.46
3.48
3.30
3.30
3.46
3.42
3.45
3.47
3.46
3.46
Outdoor Air 17°F [–8.5°C] DB/ 15°F [–9.5°C] WB
DOE Low Temp. BTU/H
[kW]
12,100
[3.5]
12,100
[3.5]
11,500
[3.4]
11,400
[3.3]
11,400
[3.3]
11,300
[3.3]
11,500
[3.4]
11,500
[3.4]
11,500
[3.4]
11,500
[3.4]
14,600
[4.3]
14,600
[4.3]
14,000
[4.1]
14,100
[4.1]
14,100
[4.1]
14,000
[4.1]
14,000
[4.1]
13,900
[4.1]
13,900
[4.1]
14,000
[4.1]
13,900
[4.1]
17,600
[5.2]
17,600
[5.2]
17,300
[5.1]
17,600
[5.2]
17,500
[5.1]
17,400
[5.1]
17,400
[5.1]
17,400
[5.1]
COP
2.30 8.10
2.30 8.20
2.46 8.55
2.44 8.55
2.44 8.55
2.45 8.55
2.44 8.55
2.44 8.55
2.46 8.55
2.46 8.55
2.18 7.55
2.18 7.65
2.32 7.90
2.33 8.00
2.34 8.00
2.36 8.00
2.35 8.00
2.32 7.95
2.32 7.95
2.32 7.95
2.34 7.95
2.26 8.10
2.26 8.40
2.36 8.50
2.32 8.10
2.34 8.40
2.36 8.50
2.35 8.50
2.36 8.50
Outdoor
Unit
RPPB-
018JAZ
024JAZ
030JAZ
Model Numbers
Indoor
Coil and/or
Air Handler
RCHJ-24A1
RCHJ-24A1+RXMD-C02
RCHJ-24A1 (RBHK-17)
RCHJ-24A1 (RGFD-06?MCK?)
RCHJ-24A1 (RGFD-07?MCK?)
RCHJ-24A1 (RGGD-06?MCK?)
RCHJ-24A1 (RGLL-05?BMK?)
RCHJ-24A1 (RGLL-07?BRK?)
RCHJ-24A1 (RGPL-05?BMK?)
RCHJ-24A1 (RGPL-07?BRK?)
RCHJ-24A2
RCHJ-24A2+RXMD-C02
RCHJ-24A2 (RBHK-17)
RCHJ-24A2 (RGFD-06?MCK?)
RCHJ-24A2 (RGFD-07?MCK?)
RCHJ-24A2 (RGGD-06?MCK?)
RCHJ-24A2 (RGGD-07?MCK?)
RCHJ-24A2 (RGLL-05?BMK?)
RCHJ-24A2 (RGLL-07?BRK?)
RCHJ-24A2 (RGPL-05?BMK?)
RCHJ-24A2 (RGPL-07?BRK?)
RCHJ-36A1
RCHJ-36A1+RXMD-C02
RCHJ-36A1 (RBHK-21)
RCHJ-36A1 (RGFD-06?MCK?)
RCHJ-36A1 (RGFD-07?MCK?)
RCHJ-36A1 (RGGD-06?MCK?)
RCHJ-36A1 (RGGD-07?MCK?)
RCHJ-36A1 (RGLL-05?BMK?)
Capacity
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
Total
BTU/H
[kW]
18,300
[5.4]
18,300
[5.4]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
18,800
[5.5]
22,200
[6.5]
22,200
[6.5]
23,000
[6.7]
23,000
[6.7]
23,200
[6.8]
23,200
[6.8]
23,200
[6.8]
23,000
[6.7]
23,000
[6.7]
23,000
[6.7]
23,000
[6.7]
26,600
[7.8]
26,600
[7.8]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
DOE
Region
IV
HSPF
Page 5
Rheem Manufacturing Company 5
Performance Data ARI Standard Conditions—Single Phase (Scroll Compressor) (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by DOE test procedures.
[ ] Designates Metric Conversions
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
21,200
[6.2]
20,800
[6.1]
21,800
[6.4]
21,900
[6.4]
22,050
[6.5]
24,600
[7.2]
23,800
[7.0]
25,200
[7.4]
24,850
[7.3]
24,800
[7.3]
25,050
[7.3]
25,200
[7.4]
25,250
[7.4]
24,900
[7.3]
24,850
[7.3]
25,250
[7.4]
25,250
[7.4]
25,300
[7.4]
24,600
[7.2]
24,600
[7.2]
24,200
[7.1]
24,600
[7.2]
24,600
[7.2]
24,900
[7.3]
25,100
[7.4]
25,350
[7.4]
25,250
[7.4]
25,450
[7.5]
Outdoor
Unit
RPPB-
030JAZ
036JAZ
Model Numbers
Indoor Coil and/or Air Handler
RCHJ-36A1 (RGLL-07?BRK?)
RCHJ-36A1 (RGLL-07?BRQ?)
RCHJ-36A1 (RGPL-05?BMK?)
RCHJ-36A1 (RGPL-07?BRK?)
RCHJ-36A1 (RGPL-07?BRQ?)
RCHJ-36A2
RCHJ-36A2+RXMD-C02
RCHJ-36A2 (RBHK-21)
RCHJ-36A2 (RGFD-06?MCK?)
RCHJ-36A2 (RGFD-07?MCK?)
RCHJ-36A2 (RGFD-09?ZCM?)
RCHJ-36A2 (RGFD-10?ZCM?)
RCHJ-36A2 (RGFD-12?ZCM?)
RCHJ-36A2 (RGGD-06?MCK?)
RCHJ-36A2 (RGGD-07?MCK?)
RCHJ-36A2 (RGGD-09?ZCM?)
RCHJ-36A2 (RGGD-10?ZCM?)
RCHJ-36A2 (RGGD-12?RCM?)
RCHJ-36A2 (RGLL-05?BMK?)
RCHJ-36A2 (RGLL-07?BRK?)
RCHJ-36A2 (RGLL-07?BRQ?)
RCHJ-36A2 (RGLL-10?BRM?)
RCHJ-36A2 (RGLL-12?ARM?)
RCHJ-36A2 (RGPL-05?BMK?)
RCHJ-36A2 (RGPL-07?BRK?)
RCHJ-36A2 (RGPL-07?BRQ?)
RCHJ-36A2 (RGPL-10?BRM?)
RCHJ-36A2 (RGPL-12?ARM?)
Total
Capacity
BTU/H
[kW]
28,000
[8.2]
27,600
[8.1]
27,800
[8.1]
28,000
[8.2]
27,800
[8.1]
33,800
[9.9]
33,800
[9.9]
34,600
[10.1]
34,800
[10.2]
34,600
[10.1]
35,000
[10.3]
35,200
[10.3]
35,200
[10.3]
34,800
[10.2]
34,800
[10.2]
35,200
[10.3]
35,200
[10.3]
35,400
[10.4]
34,400
[10.1]
34,400
[10.1]
34,000
[10.0]
34,400
[10.1]
34,400
[10.1]
34,400
[10.1]
34,600
[10.1]
34,200
[10.0]
34,400
[10.1]
34,600
[10.1]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
Net Latent BTU/H
[kW]
6,800
[2.0]
6,800
[2.0]
6,800
[2.0]
6,900
[2.0]
6,950
[2.0]
10,000
[2.9]
10,000
[2.9]
10,000
[2.9]
9,950
[2.9]
9,800
[2.9]
9,950
[2.9]
10,000
[2.9]
9,950
[2.9]
9,900
[2.9]
9,950
[2.9]
9,950
[2.9]
9,950
[2.9]
10,100
[3.0]
9,800
[2.9]
9,800
[2.9]
9,800
[2.9]
9,800
[2.9]
9,800
[2.9]
9,900
[2.9]
9,900
[2.9]
10,050
[2.9]
9,950
[2.9]
10,150
[3.0]
EER
SEER
12.10 13.95
11.55 13.25
11.90 14.00
12.10 14.10
11.90 14.40
10.90 12.00
10.90 12.10
12.00 14.00
11.20
13.00
11.15 12.95
12.00 14.00
11.90 13.90
12.00 14.00
11.35 13.20
11.25 13.05
12.05 14.10
12.05 14.10
12.15 14.20
11.90 13.95
11.90 13.95
11.30 13.15
11.90 13.90
11.80 13.75
11.30 13.10
11.75 13.70
11.65 14.00
11.70 14.00
12.05 14.10
Indoor
CFM [L/s]
1,000 [472]
1,000 [472]
1,000 [472]
1,000 [472]
1,000 [472]
1,200 [566]
1,200 [566]
1,200 [566]
1,175 [554]
1,200 [566]
1,150 [543]
1,175 [554]
1,225 [578]
1,225 [578]
1,225 [578]
1,175 [554]
1,175 [554]
1,225 [578]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
ARI Heating Performance (70°F [21°C] Indoor)
Outdoor Air
47°F [8.5°C] DB/
43°F [6°C] WB
DOE High Temp. BTU/H
[kW]
28,000
[8.2]
28,200
[8.3]
28,000
[8.2]
28,000
[8.2]
28,000
[8.2]
35,400
[10.4]
35,400
[10.4]
35,800
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
35,800
[10.5]
35,800
[10.5]
36,400
[10.7]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
35,800
[10.5]
36,000
[10.5]
36,000
[10.5]
35,800
[10.5]
COP
3.46
3.38
3.42
3.46
3.44
3.40
3.40
3.58
3.47
3.46
3.62
3.59
3.60
3.50
3.48
3.61
3.61
3.63
3.58
3.58
3.48
3.58
3.56
3.48
3.56
3.54
3.54
3.60
Outdoor Air 17°F [–8.5°C] DB/ 15°F [–9.5°C] WB
DOE Low Temp. BTU/H
[kW]
17,300
[5.1]
17,600
[5.2]
17,500
[5.1]
17,300
[5.1]
17,400
[5.1]
22,200
[6.5]
22,200
[6.5]
22,200
[6.5]
22,800
[6.7]
22,800
[6.7]
22,200
[6.5]
22,200
[6.5]
22,200
[6.5]
22,600
[6.6]
22,600
[6.6]
22,200
[6.5]
22,200
[6.5]
22,200
[6.5]
22,200
[6.5]
22,200
[6.5]
22,600
[6.6]
22,200
[6.5]
22,400
[6.6]
22,400
[6.6]
22,200
[6.5]
22,400
[6.6]
22,400
[6.6]
22,200
[6.5]
COP
2.36 8.50
2.32 8.35
2.34 8.45
2.36 8.50
2.34 8.50
2.40 8.40
2.40 8.50
2.46 8.90
2.39
2.38 8.95
2.48 9.30
2.46 9.20
2.47 9.25
2.40 9.00
2.39 8.95
2.48 9.00
2.48 9.00
2.49 9.00
2.46 8.85
2.46 8.85
2.40 8.65
2.46 8.85
2.44 8.80
2.39 8.80
2.44 8.90
2.44 8.90
2.44 8.90
2.48 8.90
DOE
Region
IV
HSPF
8.95
Page 6
6 Rheem Manufacturing Company
Performance Data ARI Standard Conditions—Single Phase (Scroll Compressor) (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by DOE test procedures.
[ ] Designates Metric Conversions
ARI Cooling Performance
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net Sens. BTU/H
[kW]
29,850
[8.7]
27,900
[8.2]
30,000
[8.8]
29,900
[8.8]
29,800
[8.7]
30,350
[8.9]
30,150
[8.8]
30,150
[8.8]
30,450
[8.9]
28,700
[8.4]
29,200
[8.6]
29,200
[8.6]
30,300
[8.9]
30,200
[8.8]
30,300
[8.9]
34,600
[10.1]
34,600
[10.1]
35,200
[10.3]
34,100
[10.0]
35,200
[10.3]
34,700
[10.2]
34,700
[10.2]
34,700
[10.2]
35,200
[10.3]
Outdoor
Unit
RPPB-
042JAZ
048JAZ
Model Numbers
Indoor Coil and/or Air Handler
RCHJ-48A1
RCHJ-48A1+RXMD-C02
RCHJ-48A1 (RBHK-24)
RCHJ-48A1 (RGFD-09?ZCM?)
RCHJ-48A1 (RGFD-10?ZCM?)
RCHJ-48A1 (RGFD-12?ZCM?)
RCHJ-48A1 (RGGD-09?ZCM?)
RCHJ-48A1 (RGGD-10?ZCM?)
RCHJ-48A1 (RGGD-12?RCM?)
RCHJ-48A1 (RGLL-07?BRQ?)
RCHJ-48A1 (RGLL-10?BRM?)
RCHJ-48A1 (RGLL-12?ARM?)
RCHJ-48A1 (RGPL-07?BRQ?)
RCHJ-48A1 (RGPL-10?BRM?)
RCHJ-48A1 (RGPL-12?ARM?)
RCHJ-51A1
RCHJ-51A1+RXMD-C02
RCHJ-51A1 (RBHK-24)
RCHJ-51A1 (RGLL-07?BRQ?)
RCHJ-51A1 (RGLL-10?BRM?)
RCHJ-51A1 (RGLL-12?ARM?)
RCHJ-51A1 (RGPL-07?BRQ?)
RCHJ-51A1 (RGPL-10?BRM?)
RCHJ-51A1 (RGPL-12?ARM?)
Total
Capacity
BTU/H
[kW]
39,000
[11.4]
39,000
[11.4]
40,500
[11.9]
40,500
[11.9]
40,500
[11.9]
41,000
[12.0]
40,500
[11.9]
40,500
[11.9]
41,000
[12.0]
39,500
[11.6]
40,000
[11.7]
40,000
[11.7]
40,000
[11.7]
40,000
[11.7]
40,000
[11.7]
46,000
[13.5]
46,000
[13.5]
46,500
[13.6]
45,500
[13.3]
46,500
[13.6]
46,000
[13.5]
46,000
[13.5]
46,000
[13.5]
46,500
[13.6]
Net
Latent
BTU/H
[kW]
11,150
[3.3]
11,100
[3.3]
11,000
[3.2]
11,100
[3.3]
11,200
[3.3]
11,150
[3.3]
10,850
[3.2]
10,850
[3.2]
11,050
[3.2]
10,800
[3.2]
10,800
[3.2]
10,800
[3.2]
11,200
[3.3]
11,300
[3.3]
11,200
[3.3]
11,400
[3.3]
11,400
[3.3]
11,300
[3.3]
11,400
[3.3]
11,300
[3.3]
11,300
[3.3]
11,300
[3.3]
11,300
[3.3]
11,300
[3.3]
EER
SEER
10.90 12.00
10.90 12.10
12.10 14.00
11.70 13.25
11.55 13.20
11.75 13.25
11.75 13.25
11.75 13.25
12.00
13.60
11.20 12.85
11.80 13.60
11.85 13.65
11.50 13.20
11.60 13.35
11.90 13.70
11.45 12.00
11.45 12.10
12.25 14.10
10.80 12.35
12.00 13.75
11.55 13.20
11.45 13.10
11.65 13.35
12.00 13.80
Indoor
CFM
[L/s]
1,400 [661]
1,400 [661]
1,400 [661]
1,325 [625]
1,325 [625]
1,475 [696]
1,425 [672]
1,425 [672]
1,450 [684]
1,400 [661]
1,400 [661]
1,400 [661]
1,400 [661]
1,400 [661]
1,400 [661]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
1,600 [755]
ARI Heating Performance (70°F [21°C] Indoor)
Outdoor Air
47°F [8.5°C] DB/
43°F [6°C] WB
DOE High Temp. BTU/H
[kW]
42,500
[12.5]
42,500
[12.5]
41,500
[12.2]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,500
[12.5]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
42,000
[12.3]
47,000
[13.8]
47,000
[13.8]
47,000
[13.8]
48,500
[14.2]
47,000
[13.8]
47,500
[13.9]
47,500
[13.9]
47,500
[13.9]
47,000
[13.8]
COP
3.40
3.40
3.52
3.52
3.49
3.48
3.50
3.50
3.52
3.38
3.48
3.48
3.42
3.44
3.50
3.44
3.44
3.64
3.38
3.60
3.52
3.50
3.54
3.60
Outdoor Air 17°F [–8.5°C] DB/ 15°F [–9.5°C] WB
DOE Low Temp. BTU/H
[kW]
27,200
[8.0]
27,200
[8.0]
26,200
[7.7]
26,600
[7.8]
26,800
[7.9]
26,800
[7.9]
26,800
[7.9]
26,800
[7.9]
26,600
[7.8]
27,000
[7.9]
26,600
[7.8]
26,400
[7.7]
26,800
[7.9]
26,600
[7.8]
26,400
[7.7]
28,400
[8.3]
28,400
[8.3]
29,000
[8.5]
30,400
[8.9]
29,200
[8.6]
29,600
[8.7]
29,800
[8.7]
29,600
[8.7]
29,200
[8.6]
COP
2.28 8.30
2.28 8.40
2.28 8.30
2.29 8.35
2.28 8.25
2.27 8.20
2.28 8.25
2.28 8.25
2.29
2.20 8.25
2.24 8.25
2.26 8.25
2.22 8.35
2.24 8.35
2.26 8.25
2.22 8.10
2.22 8.50
2.38 8.60
2.26 8.20
2.36 8.50
2.32 8.40
2.32 8.35
2.32 8.40
2.36 8.55
DOE
Region
IV
HSPF
8.30
Page 7
Rheem Manufacturing Company 7
Electrical and Physical Data
[ ] Designates Metric Conversions
Performance Data ARI Standard Conditions—Single Phase (Scroll Compressor) (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by DOE test procedures.
ARI Cooling Performance
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
36,150
[10.6]
36,650
[10.7]
36,300
[10.6]
36,400
[10.7]
36,250
[10.6]
36,250
[10.6]
40,400
[11.8]
40,400
[11.8]
42,100
[12.3]
41,100
[12.0]
40,050
[11.7]
40,550
[11.9]
Outdoor
Unit
RPPB-
049JAZ
060JAZ
061JAZ
Model Numbers
Indoor Coil and/or Air Handler
RCQC-4824A
RCQC-4824A (RBHL-25)
RCQC-4824A (RGFD-12?ZCM?)
RCQC-4824A (RGPL-07?BRQ?)
RCQC-4824A (RGPL-10?BRM?)
RCQC-4824A (RGPL-12?ARM?)
RCHJ-61A1
RCHJ-61A1+RXMD-C02
RCHJ-61A1 (RBHK-25)
RCHJ-61A1 (RGPL-12?ARM?)
RCQC-6024A
RCQC-6024A (RBHL-26)
Total
Capacity
BTU/H
[kW]
47,500
[13.9]
48,000
[14.1]
47,500
[13.9]
47,500
[13.9]
47,500
[13.9]
47,500
[13.9]
52,500
[15.4]
52,500
[15.4]
54,000
[15.8]
53,000
[15.5]
52,000
[15.2]
52,500
[15.4]
Net Latent BTU/H
[kW]
11,350
[3.3]
11,350
[3.3]
11,200
[3.3]
11,100
[3.3]
11,250
[3.3]
11,250
[3.3]
12,100
[3.5]
12,100
[3.5]
11,900
[3.5]
11,900
[3.5]
11,950
[3.5]
11,950
[3.5]
EER
SEER
11.50 13.55
12.20 14.25
11.75 13.65
11.95 13.90
11.70 13.60
11.95 13.95
11.30 12.00
11.30
12.10
11.65 13.50
10.65 12.20
10.90 12.85
11.65 13.60
Indoor
CFM [L/s]
1,625 [767]
1,625 [767]
1,650 [779]
1,625 [767]
1,625 [767]
1,575 [743]
1,950 [920]
1,950 [920]
1,950 [920]
1,950 [920]
1,875 [885]
1,875 [885]
ARI Heating Performance (70°F [21°C] Indoor)
Outdoor Air
47°F [8.5°C] DB/
43°F [6°C] WB
DOE High Temp. BTU/H
[kW]
49,000
[14.4]
48,000
[14.1]
49,000
[14.4]
48,500
[14.2]
49,000
[14.4]
48,500
[14.2]
53,500
[15.7]
53,500
[15.7]
53,500
[15.7]
54,500
[16]
55,500
[16.3]
53,500
[15.7]
COP
3.60
3.71
3.65
3.69
3.65
3.71
3.54
3.54
3.60
3.42
3.51
3.65
Outdoor Air 17°F [–8.5°C] DB/ 15°F [–9.5°C] WB
DOE Low Temp. BTU/H
[kW]
31,200
[9.1]
30,000
[8.8]
30,800
[9.0]
30,600
[9.0]
31,000
[9.1]
30,600
[9.0]
32,400
[9.5]
32,400
[9.5]
33,000
[9.7]
34,000
[10.0]
34,800
[10.2]
33,400
[9.8]
COP
2.46 9.30
2.55 9.30
2.49 9.45
2.52 9.50
2.49 9.40
2.53 9.55
2.34 8.40
2.34
2.36 8.70
2.26 8.10
2.50 9.10
2.60 9.25
DOE
Region
IV
HSPF
8.50
ELECTRICAL PHYSICAL
Model
Number
RPPB-
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
018JA 1-60-208-230 9.6/9.6 45 .75 13/13 20/20 20/20 11.0 [1.02] 1 2100 [991] 84 [2381] 160 [72.6] 170 [77.1] 024JA 1-60-208-230 10.9/10.9 54 .75 15/15 20/20 25/25 17.3 [1.60] 1 2200 [1038] 118 [3345] 195 [88.5] 205 [93.0] 030JA 1-60-208-230 12.2/12.2 67 .75 16/16 20/20 25/25 17.3 [1.60] 1 2200 [1038] 124 [3515] 200 [90.7] 210 [95.3] 036JA 1-60-208-230 16.0/16.0 88 1.0 22/22 25/25 35/35 16.8 [1.56] 2 2600 [1227] 195 [5528] 230 [104.3] 240 [108.9] 042JA 1-60-208-230 17.9/17.9 104 1.5 24/24 30/30 40/40 22.4 [2.08] 2 3100 [1463] 234 [6634] 295 [133.8] 305 [138.3] 048JA 1-60-208-230 18.3/18.3 109 1.5 25/25 30/30 40/40 22.4 [2.08] 2 3100 [1463] 281 [7966] 300 [1361] 310 [140.6] 049JA 1-60-208-230 20.0/20.0 109 1.5 27/27 35/35 45/45 22.4 [2.08] 2 3100 [1463] 288 [8165] 300 [136.1] 310 [140.6] 060JA 1-60-208-230 19.9/19.9 137 1.5 27/27 35/35 45/45 22.4 [2.08] 2 3100 [1463] 267 [7569] 305 [138.3] 315 [142.9] 061JA 1-60-208-230 20.2/20.2 137 1.5 27/27 35/35 45/45 22.4 [2.08] 2 3100 [1463] 288 [8165] 305 [138.3] 315 [142.9]
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
Outdoor Coil
No.
2
Rows
]
CFM [L/s]
R22
Oz. [g]
Net
Lbs. [kg]
Weight
Shipping Lbs. [kg]
Page 8
8 Rheem Manufacturing Company
Unit Dimensions
[ ] Designates Metric Conversions
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.
Condenser Coil leaks caused by
factory defects..........................................Five (5) Years
Compressor ..............................................Ten (10) Years
*Any Other Part ..........................................Five (5) Years
*This five year limited warranty is applicable only to single-phase products
installed in residential applications on or after January 1, 2001.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
GENERAL TERMS OF LIMITED WARRANTY
AIR DISCHARGE
ALLOW 600 [1524 mm] CLEARANCE
W
H
AIR INLETS (LOUVERS) ALLOW 120 [305 mm] MIN. CLEARANCE 3 SIDES
Model Number
RPPB-
Height “H”
(Inches) [mm]
018 19 [482.6] 024/030/036 25 [635.0]
Length “L”
(Inches) [mm]
401/2 [1028.7] 275/8 [701.2]
443/8 [1127.1] 311/2 [800.1]
L
1
0
0
0
0
-
A
Width “W”
(Inches) [mm]
042/048/049/060/061 33 [838.2] 443/8 [1127.1] 311/2 [800.1]
ACCESS PANEL
ALLOW 240 [610 mm] ACCESS CLEARANCE
SERVICE FITTINGS
LOW VOLTAGE CONNECTION
7
/80 [22 mm]
HIGH VOLTAGE CONNECTION
11
/320 [34 mm]
1
LIQUID LINE CONNECTION
VAPOR LINE
A-00003
HIGH PRESSURE CONTROL MANUAL RESET (FIELD INSTALLED ACCESSORY)
CONNECTION
7
/80 [73 mm] DIA.
2 ACCESSORY KNOCKOUTS
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 240 [610 mm] CLEARANCE ONE SIDE
Page 9
Rheem Manufacturing Company 9
Heat Pump Refrigerant Line Size Information
NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity.
Additional compressor oil is n
ot required for runs up to 150 feet [45.72 m].
Oil traps in vertical runs are n
ot required for any height up to 125 feet [38.10 m]. See Liquid Line chart for Vertical Separation Requirements and Limitations.
*Adapter to 1
1
/8" [28.58 mm] factory supplied.
[ ] Designates Metric Conversions
System
Capacity
Model
018
024
Line
Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
1/4* [6.35] 25 [7.62] 50 [15.24] 70 [21.34] 25 [7.62] 23 [7.01] 8 [2.44]
5/16 [7.94] 36 [10.97] 42 [12.80] 48 [14.63] 54 [16.46] 0 0 0 0
1/4* [6.35] 25 [7.62] 50 [15.24] 25 [7.62] 23 [7.01]
5/16 [7.94] 24 [7.32] 34 [10.36] 44 [13.41] 54 [16.46] 64 [19.51] 0 0 0 0 0
1/4* [6.35] 25 [7.62] 50 [15.24] 25 [7.62] 23 [7.01]
030
5/16 [7.94] 19 [5.79] 33 [10.06] 47 [14.33] 61 [18.59] 0 0 0 0
3/8 [9.53] 11 [3.35] 15 [4.57]
5/16* [7.94] 25 [7.62] 50 [15.24] 70 [21.34] 25 [7.62] 23 [7.01] 9 [2.74]
036
042
048/049
060/061
*Standard line size NOTES:
This chart is applicable for heat pumps.If the separation height exceeds the table values, increase the outdoor flow-check piston two sizes plus
one size for each additional 10 feet [3.05 m]. Example 1: A 5 ton [17.58 kW] heat pump with a total line length of 100 feet [30.48 m] with a vertical separation of 93 feet [28.35 m] utilizing a vertical separation for 100 feet [30.48 m] run. Separation exceeds table by (93-72) = 21 feet [6.40 m]. Therefore, reduce the indoor coil flow-check piston 2 + 2 = 4 sizes (For example, a #89 piston would reduce to a #85 piston). Increase the outdoor flow-check piston 2 + 2 = 4 sizes (For example, a #56 would increase to a #60).
Do not exceed 120 feet [36.58 m] maximum vertical separation.No changes are required for expansion valve coils.Do not exceed table values for capillary tube coils.Always use the smallest liquid line possible to minimize system charge.For heat pumps with vertical separation: • Route liquid line outside building • Do not insulate liquid line.
Chart may be used to size horizontal runs.
3/8 [9.53] 34 [10.36] 40 [12.19] 46 [14.02] 52 [15.85] 0 0 0 0
5/16* [7.94] 25 [7.62] 50 [15.24] 75 [22.86] 25 [7.62] 23 [7.01] 9 [2.74]
3/8 [9.53] 32 [9.75] 39 [11.89] 46 [14.02] 53 [16.15] 0 0 0 0 3/8* [9.53] 25 [7.62] 44 [13.41] 53 [16.15] 61 [18.59] 70 [21.34] 25 [7.62] 28 [8.53] 19 [5.79] 11 [3.35] 3 [.91] 1/2 [12.7] 37 [11.28] 39 [11.89] 0 0 3/8* [9.53] 25 [7.62] 48 [14.63] 61 [18.59] 72 [21.95] 1/2 [12.7] 35 [10.67] 38 [11.58] 41 [12.50] 0 0 0
3
/8" [9.53 mm] liquid line: Table = 72 feet [21.95 m] maximum
Liquid Line Size
Outdoor Unit Above Indoor Coil
Total Length—Feet [m] Total Length—Feet [m]
Vertical Separation—Feet [m]
Liquid Line Size
Outdoor Unit Below Indoor Coil
Vertical Separation—Feet [m]
25 [7.62] 23 [7.01] 11 [3.35] 3 [.91]
NOTES: This chart is applicable for heat pumps. Heat pumps with any vertical
separation require the use of standard line sizes only, due to the possibility of charge imbalance between heating and cooling modes.
Example 1: A 3 ton [10.55 kW] heat pump with a total line length of 50 feet [15.24 m] can have a maximum vertical separation of 19 feet [5.79 m].
Do not increase line size to
This chart may also be used to size horizontal runs.
Example 2: A 1.5 ton [5.28 kW] heat pump can have a total horizontal line length of 150 feet [45.72 m] when using the No vertical separation allowed.
Do not exceed vertical separation as indicated on the chart.Always use the smallest liquid line possible to minimize system charge.No changes required for flow-check pistons or expansion valve coils.
3
/8" [9.53 mm].
5
/16" [7.94 mm] liquid line size.
0
Unit Vapor Line Connection Size
Vapor Line Run—Feet [m]
Optional
25' [7.62]
Standard Optional
Optional
50' [15.24]
Standard Optional
Optional
100' [30.48]
Standard Optional
Optional
150' [45.72]
Standard Optional
Vapor Line Length/Size versus Capacity Multiplier
3
/4" [19.05 mm] I.D. Sweat
5
/8" [15.88 mm] O.D. Optional
3
/4" [19.05 mm] O.D. Standard
7
/
8" [22.23 mm] O.D. Optional
.98
1.00
1.01
0.96
0.99
1.00
0.93
0.99
1.00 —
0.98
1.00
0.98
1.00
1.01 .96
0.99
1.00
0.93
0.98
0.99
0.97
0.98
1.00
1.01 —
0.99
1.00 —
0.97
0.99
0.95
0.97
7
/8" [22.23 mm] I.D. Sweat
3
/4" [19.05 mm] O.D. Optional
7
/8" [22.23 mm] O.D. Standard
1
1
/
8" [28.58 mm] O.D. Optional
.99
1.00
1.01 .97
0.99
1.01 .93
0.98
1.00
0.97
0.99
1.00
1.01 —
0.99
1.01 —
0.98
1.00 —
0.96
0.99
060/061048/049042036030024RPPB- 018
1
/8" [28.58 mm] I.D. Sweat*
1
7
/8" [22.23 mm] O.D. Optional
1
1
/8" [28.58 mm] O.D. Standard
3
1
/
8" [34.93 mm] O.D. Optional
0.99
1.00
1.01
0.97
1.00
1.01
0.96
0.99
1.00
0.93
0.99
1.00
0.99
1.00
1.01
0.97
0.99
1.01
0.95
0.99
1.00
0.93
0.98
0.99
Page 10
10 Rheem Manufacturing Company
Notes
Page 11
Rheem Manufacturing Company 11
Notes
Page 12
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
RHEEM AIR CONDITIONING DIVISION
5600 Old Greenwood Road, Fort Smith, Arkansas 72908
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 10-05 DC FORM NO. P11-759 REV. 2
Supersedes Form No. P11-759 Rev. 1
Loading...