Rheem RP13, RP14 Installation Manual

WARNING:
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT, AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE, OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
R-410A HEAT PUMP OUTDOOR UNITS
INSTALLATION INSTRUCTIONS
RP13 (13 SEER) RP14 (14 SEER) AND RP15 (15 SEER)
Do not destroy this manual. Please read carefully and keep in a safe place for future reference by a serviceman.
[ ] indicates metric conversions.
92-105074-04-03 (8/15)
Printed in USA
CONTENTS
Important
Safety Information ............................................. 3
General Information ........................................4-7
Checking Product Received ........................................4
Application ...................................................................4
Electrical and Physical Data ..................................... 5-6
Specifications ...............................................................7
Contents
Proper Installation ........................................................7
Installation .................................................... 8-19
Choosing a Location ......................................8-10
Operational Issues........................................................8
Corrosive Environment .................................................8
For Units With
Space Limitations .........................................................9
Customer Satisfaction Issues ......................................9
Unit Mounting ............................................................... 9
Factory-Preferred
Tie-Down Method.........................................................9
Snow Depth Table ......................................................10
Tools and Refrigerant .......................................11
Tools Required for Installing and
Servicing R-410A Models ..........................................11
Specifications of R-410A ...........................................11
Quick-Reference
Guide for R-410A .......................................................11
Replacement Units ...........................................12
Indoor Coil ........................................................12
Location ...................................................................... 12
Interconnecting Tubing ................................ 12-26
Refrigerant Level Adjustment .....................................12
Maximum Length of Lines ..........................................12
Outdoor Unit Installed
Above or Below Indoor Coil ................................. 13-26
Tubing Installation ......................................................24
Tubing Connections ...................................................25
Leak Testing ...............................................................26
Wiring .........................................................27-28
Control Wiring ............................................................27
Conventional 24 VAC
Thermostat Control Wiring .........................................27
Typical Thermostat Wiring Diagrams .........................27
Power Wiring .............................................................. 28
Grounding ................................................................... 28
Start-Up ......................................................29-33
Start-Up ......................................................................29
Checking Airflow ........................................................29
Evacuation Procedure ............................................... 30
Final Leak Testing .......................................................30
Checking
Refrigerant Charge ...................................... 31-33
Charging Units
With R-410A Refrigerant ............................................31
Confirm ID Airflow
and Coils Are Clean ...................................................31
Measurement Device Setup .......................................31
Charging by Weight ....................................................31
Gross Charging by Pressures ....................................32
Final Charge by Subcooling .......................................32
Finishing Up Installation ............................................. 33
Components and Controls ............................... 34
Compressor
Crankcase Heat (CCH) ......................................34
Hard-Start Components ....................................34
High- and Low-Pressure
Controls (HPC and LPC) ....................................34
Demand Defrost ................................................... 35-36
Accessories ..................................................... 37
Remote Outdoor
Temperature Model ....................................................37
Low Ambient Control (LAC) ...................................... 37
Diagnostics ................................................ 38-40
Cooling Mechanical
Checks Flowchart ..................................................... 38
Heating Mechanical
Checks Flowchart ..................................................... 39
Defrost Mechanical
Checks Flowchart ..................................................... 40
General Troubleshooting Chart ...... ...........................41
Service Analyzer Charts ....................................... 42-46
Cooling/Heating Tips .............................................................47
Wiring Diagrams ........................................ 48-50
2
IMPORTANT SAFETY INFORMATION
WARNINGS:
These instructions are intended as an aid to
qualified, licensed service personnel for proper installation, adjustment, and operation of this unit. Read these instructions thoroughly before
attempting installation or operation. Failure to
follow these instructions may result in improper installation, adjustment, service, or maintenance possibly resulting in fire, electrical shock, property damage, personal injury, or death.
• The unit must be permanently grounded. Failure to do so can cause electrical shock resulting in severe personal injury or death.
• Turn off electric power at the fuse box or service panel before making any electrical connections.
• Complete the ground connection before making line voltage connections. Failure to do so can result in electrical shock, severe personal injury, or death.
• Disconnect all power to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
• Never assume the unit is properly wired and/or grounded. Always test the unit cabinet with a noncontact voltage detector available at most electrical supply houses or home centers before removing access panels or coming into contact with the unit cabinet.
• Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death.
The top of the scroll compressor shell is hot.
Touching the compressor top may result in serious personal injury.
The manufacturer’s warranty does not cover
any damage or defect to the unit caused by the attachment or use of any components, accessories, or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with
the heat pump. You should be aware that the
use of unauthorized components, accessories, or devices may adversely affect the operation of the heat pump and may also endanger life and property. The manufacturer disclaims any
responsibility for such loss or injury resulting from the use of such unauthorized components, accessories, or devices.
CAUTIONS:
R-410A systems operate at approximately 60%
higher pressures (1.6 times) than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment. Use appropriate care when using this refrigerant. Failure to exercise care may result in equipment damage or personal injury.
Only match this outdoor unit with a matched indoor
coil or air handler approved for use with this outdoor unit per the unit manufacturer’s specification sheet. The use of unmatched coils or air handler will likely result in a charge imbalance between the cooling and heating modes which can cause unsatisfactory operation including a high-pressure switch lockout condition.
Only use indoor coils approved for use on R-410A
systems. An R-22 coil will have a TXV or fixed restrictor device that is not designed to operate properly in an R-410A system and will result in serious operational issues. The R-22 coil could also contain mineral oil which is incompatible with the POE oil used in R-410A systems and could result in reliability issues with the compressor and TXVs.
When coil is installed over a finished ceiling and/or
living area, it is required that a secondary sheet metal condensate pan be constructed and installed under the entire unit. Failure to do so can result in property damage.
The compressor has an internal overload protector.
Under some conditions, it can take up to 2 hours for this overload to reset. Make sure overload has had time to reset before condemning the compressor.
UNIT MAY START SUDDENLY AND WITHOUT
WARNING. A flashing red light on the heat pump/ defrost control indicates a call for unit operation is present at the heat pump/defrost control. The heat pump/defrost control will attempt to start unit after the anti-short cycle time expires, when a high or low pressure control automatically resets, or when the heat pump/defrost control exits the lockout mode as the temperature rises above 5°F.
Safety
3
GENERAL INFORMATION
WARNING:
Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions and can cause the related warranty not to apply.
The RP series of heat pumps are designed to operate with standard 24 VAC thermostats and air handlers or gas furnaces.
This installation instruction manual contains complete instructions for installation and setup using conventional 24 VAC controls. Please refer to the manufacturer’s specification sheets for complete performance data, thermostat, and accessory listings.
The information contained in this manual has been prepared to assist in the proper installation, operation, and maintenance of the air conditioning system.
General Information
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Homeowner should retain this manual for future reference.
To achieve optimum efficiency and capacity, the matching indoor cooling coils listed in the manufacturer’s specification sheet must be used for this model heat pump.
Checking Product Received
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check model number, electrical characteristics, and accessories to determine if they are correct. Check system components (indoor coil, outdoor unit, air handler/furnace, etc.) to make sure they are properly matched.
Application
Before specifying any heat pump equipment, a survey of the structure and a heat loss and heat gain calculation must be made. A heat loss calculation involves identifying all surfaces and openings that lose heat to the surrounding air and quantifying that heat loss. A cooling heat gain calculation makes similar measurements and determines the amount of heat needed to be removed. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal. These factors must be considered before selecting a heat pump system to provide year-round comfort. The Air Conditioning Contractors of America (ACCA) J Manual method of load calculation is one recognized procedure for determining the heating and cooling load.
After the proper equipment combination has been selected, satisfying both sensible and latent requirements, the system must be properly installed. Only then can the unit provide the comfort it was designed to provide.
There are several factors that installers must consider.
Outdoor unit location
Indoor unit blower speed and airflow
Proper equipment evacuation
Supply and return air duct design and sizing
Refrigerant charge
System air balancing
Diffuser and return air grille location and sizing
Electrical and Physical Data
RP13
ELECTRICAL PHYSICAL
Fan
Model
Number
RP1336AC1NA 208-230 3 60 10.4 73.0 0.60 14 20/20 20/20 14.82 [1.38] 1 3333 [1573] 111 [3146] 171 [77.6] 184 [83.5]
RP1342AC1NA 208-230 3 60 13.5 88.0 1.00 18 25/25 30/30 14.82 [1.38] 1 2933 [1384] 201 [91.2] 208 [94.3]
RP1348AC1NA 208-230 3 60 13.7 83.1 1.20 19 25/25 30/30 19.76 [1.84] 1 4055 [1913]
RP1360AC1NA 208-230 3 60 15.9 110.0 1.00 21 25/25 35/35 24.23 [2.25] 1 4780 [2255]
RP1336AD1NA 460 3 60 5.8 38.0 0.50 8 15/15 15/15 14.82 [1.38] 1 3333 [1573]
RP1342AD1NA 460
RP1348AD1NA 460
RP1360AD1NA 460
Voltage
Phase
3 60 6.0 44.0
3 60
3 60
Rated Load
Freq
6.2 41.0 0.60
7.1 52.0 0.50
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Amperes
0.50
Motor
Full
Load
(FLA)
Minimum
Circuit
Ampacity
Amperes
8
9
10
Fuse or HACR
Circuit Breaker
Minimum
Amperes
15/15
15/15
15/15
Maximum
Amperes
14.82 [1.38]1 2933 [1384]
15/15
15/15
19.76 [1.84]
15/15
24.23 [2.25]
4
Face Area
Sq. Ft .
[m
Outdoor Coil WeightCompressor
No.
Rows
2
]
CFM [L/s]
1
4055 [1913]
1
4780 [2255]
Refrig .
Per
Circuit
(oz.)
[g]
155 [4394]
143 [4054]
232 [6577]
111 [3146]
155 [4394]
143 [4054]
232 [65717]
Net Lbs. [kg]
227 [103.0] 234 [106.1]
262 [118.8] 269 [122.0]
171 [77.6] 178 [80.7]
201 [91.2]
227 [103.0]
262 [118.8]
Shipping Lbs. [kg]
208 [94.3]
234 [106.1]
269 [122.0]
GENERAL INFORMATION
Model
Number
Voltage
Phase
Freq
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan
Motor
Full
Load
Amperes
(FLA)
Minimum
Circuit Ampacity Amperes
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft .
[m
2
]
No.
Rows
CFM [L/s]
Refrig .
Per
Circuit
(oz.)
[g]
Net Lbs. [kg]
Shipping Lbs. [kg]
Fuse or HACR
Circuit Breaker
Outdoor Coil WeightCompressor
ELECTRICAL PHYSICAL
RP1518AJ1NA 208-230 1 60 9/ 9 48.0 0.70 12 15/15 20/20 9.06 [0.84] 1 2411 [1137] 97 [2750] 149 [67.6] 156 [70.8]
RP1524AJ1NA 208-230 1 60 10.3/10.3 61.6 0.70 14 20/20 20/20 11.14 [1.03] 1 2478 [1169] 88 [2495] 152 [68.9] 159 [72.1]
RP1530AJ1NA 208-230 1 60 14.1/14.1 73.0 1.00 19 25/25 30/30 17.29 [1.61] 1 3852 [1817] 122 [3459] 191 [86.6] 198 [89.8]
15.4/15.4
83.9 2.80
22
30/30
35/35 19.76 [1.84]
3121 [1472] 118 [3345]
199 [90.3]
206 [93.4]
RP1542AJ1NA
208-230 1 60
17.9/17.9
112.0 1.00
24
30/30 40/40
19.76 [1.84]
1
3815 [1800] 139 [3941]
221 [100.2] 228 [103.4]
RP1548AJ1NA
18.5/18.5
124.0 2.80
26 35/35 40/40 24.23 [2.25]
4379 [2066] 188 [5330]
257 [116.6]
264 [119.7]
RP1560AJ1NA
208-230 1 60
23.7/23.7
152.5
1.00
31
40/40
50/50 28.26 [2.62]
1
3654 [1724] 212 [6010]
278 [126.1] 285 [129.3]
RP1536AJ1NA
208-230 1 60
208-230 1 60
1
1
RP1536AC1NA 208-230 3 60 1
10.4
73.0 2.80
16
20/20
25/25
19.76 [1.84]
3121 [1472] 124 [3515] 199 [90.3]
206 [93.4]
208-230 3 60 1 RP1542AC1NA
13.5
88.0
1.00 18
25/25 30/30 19.76 [1.84] 3815 [1800]
145 [4110]
221 [100.2] 228 [103.4]
RP1548AC1NA
208-230 3 60
13.8
83.11 2.80
21
25/25 30/30 24.23 [2.25]
4379 [2066] 194 [5500]
257 [116.6] 264 [119.7]
RP1560AC1NA
208-230 3 60
15.9
110.0
1 1.00 21
25/25 35/35
28.26 [2.62]
3654 [1724] 223 [6321]
278 [126.1] 285 [129.3]
RP1518BJ1NA
208-230 1 60
9/9
47.5
1 0.70 12
15/15 20/20
9.06 [0.84]
2411 [1137] 99 [2806]
149 [67.6] 156 [70.8]
RP1524BJ1NA 208-230 1 60 10.9/10.9 62.9 0.70 15 20/20 25/25 11.14 [1.03] 1 2478 [169] 105 [2977] 152 [68.9] 159 [72.1]
RP1530BJ1NA 208-230 1 60 12.8/12.8 67.8 1.00 18 25/25 25/25 17.29 [1.61] 1 3852 [1817] 116 [3288] 191 [86.6] 198 [89.8]
Electrical and Physical Data
RP14
ELECTRICAL PHYSICAL
Fan
Model
Number
RP1418AJ1NA 208-230 1 60 9/9 48.0 0.70 12 15/15 20/20 9.06 [0.84] 1 2411 [1137] 97 [2750] 151 [68.5] 158 [71.7] RP1418FJ1NA 208-230 1 60 9/9 47.5 0.70 12 15/15 20/20 9.06 [0.84] 1 2411 [1137] 99 [2806] 149 [67.6] 156 [70.8] RP1424AJ1NA 208-230 1 60 10.3/10.3 61.6 0.70 14 20/20 20/20 9.06 [0.84] 1 2411 [1137] 89 [2523] 146 [66.2] 153 [69.4] RP1424FJ1NA 208-230 1 60 10.9/10.9 62.9 0.70 15 20/20 25/25 11.14 [1.03] 1 2478 [169] 105 [2977] 152 [68.9] 159 [72.1] RP1430AJ1NA 208-230 1 60 14.1/14.1 73.0 0.70 19 25/25 30/30 11.14 [1.03] 1 2535 [1196] 106 [3005] 155 [70.3] 162 [73.5] RP1430FJ1NA 208-230 1 60 12.8/12.8 67.8 1.00 18 25/25 25/25 17.29 [1.61] 1 3852 [1817] 116 [3288] 191 [86.6] 198 [89.8] RP1436AJ1NA 208-230 1 60 16.7/16.7 79.0 0.60 22 30/30 35/35 14.82 [1.38] 1 3333 [1573] 111 [3146] 177 [80.3] 184 [83.5] RP1436FJ1NA 208-230 1 60 15.4/15.4 83.9 2.80 22 30/30 35/35 19.76 [1.84] 1 3121 [1472] 118 [3345] 199 [90.3] 206 [93.4] RP1442AJ1NA 208-230 1 60 17.9/17.9 112.0 0.90 24 30/30 40/40 14.82 [1.38] 1 2933 [1384] 155 [4394] 201 [91.2] 208 [94.3] RP1442FJ1NA 208-230 1 60 17.9/17.9 112.0 1.00 24 30/30 40/40 19.76 [1.84] 1 3815 [1800] 139 [3941] 221 [100.2] 228 [103.4] RP1448AJ1NA 208-230 1 60 21.8/21.8 117.0 1.20 29 35/35 50/50 19.76 [1.82] 1 4055 [1913] 143 [4054] 227 [103.0] 234 [106.1] RP1448FJ1NA 208-230 1 60 18.5/18.5 124.0 2.80 26 35/35 40/40 24.23 [2.25] 1 4379 [2066] 188 [5330] 257 [116.6] 264 [119.7] RP1460AJ1NA 208-230 1 60 23.7/23.7 152.5 1.00 31 40/40 50/50 24.23 [2.25] 1 4780 [2255] 232 [6577] 262 [118.8] 269 [122.0] RP1460FJ1NA 208-230 1 60 23.7/23.7 152.5 1.00 31 40/40 50/50 28.26 [2.62] 1 3654 [1724] 212 [6010] 278 [126.1] 285 [129.3] RP1436AC1NA 208-230 3 60 10.4 73.0 0.60 14 20/20 20/20 14.82 [1.38] 1 3333 [1573] 111 [3146] 177 [80.3] 184 [83.5] RP1436FC1NA 208-230 3 60 10.4 73.0 2.80 16 20/20 25/25 19.76 [1.84] 1 3121 [1472] 124 [3515] 199 [90.3] 206 [93.4] RP1442AC1NA 208-230 3 60 13.5 88.0 1.00 18 25/25 30/30 14.82 [1.38] 1 2933 [1384] 155 [4394] 201 [91.2] 208 [94.3] RP1442FC1NA 208-230 3 60 13.5 88.0 1.00 18 25/25 30/30 19.76 [1.84] 1 3815 [1800] 145 [4110] 221 [100.2] 228 [103.4] RP1448AC1NA 208-230 3 60 13.7 83.1 1.20 19 25/25 30/30 19.76 [1.84] 1 4055 [1913] 143 [4054] 227 [103.0] 234 [106.1] RP1448FC1NA 208-230 3 60 13.8 83.1 2.80 21 25/25 30/30 24.23 [2.25] 1 4379 [2066] 194 [5500] 257 [116.6] 264 [119.7] RP1460AC1NA 208-230 3 60 15.9 110.0 1.00 21 25/25 35/35 24.23 [2.25] 1 4780 [2255] 232 [6577] 262 [118.8] 269 [122.0] RP1460FC1NA 208-230 3 60 15.9 110.0 1.00 21 25/25 35/35 28.26 [2.62] 1 3654 [1724] 223 [6321] 278 [126.1] 285 [129.3] RP1436AD1NA 460 3 60 5.8 38.0 0.50 8 15/15 15/15 14.82 [1.38] 1 3333 [1573] 111 [3146] 177 [80.3] 184 [83.5] RP1442AD1NA 460 3 60 6.0 44.0 0.50 8 15/15 15/15 14.82 [1.38] 1 2933 [1384] 155 [4394] 201 [91.2] 208 [94.3] RP1448AD1NA 460 3 60 6.2 41.0 0.60 9 15/15 15/15 19.76 [1.84] 1 4055 [1913] 143 [4054] 227 [103.0] 234 [106.1]
RP1460AD1NA 460 3 60 7.1 52.0 0.50 10 15/15 15/15 24.23 [2.25] 1 4780 [2255] 232 [6577] 262 [118.8] 269 [122.0]
Voltage
Phase
Freq
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Amperes
Minimum
Motor
(FLA)
Circuit
Full
Load
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft .
[m
Outdoor Coil WeightCompressor
No.
Rows
2
]
CFM [L/s]
Refrig .
Per
Circuit
(oz.)
[g]
Net Lbs. [kg]
Shipping Lbs. [kg]
General Information
RP15
5
“L”
“W”
“H”
A
I
R
D
I
S
C
H
A
R
G
E
ALLOW 60” [1524mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152mm] Min. OF CLEARANCE ALL SIDES
12” [305mm] RECCOMMENDED
SERVICE PANELS/
INLET CONNECTIONS / HIGH & LOW
VOLTAGE ACCESS
ALLOW 24” [ 610 mm] OF CLEARANCE
ST-A1226-02-00
GENERAL INFORMATION
R P 14 24 A J 1 N A
General Information
MINOR SERIES
Z
CONTROLS C - COMMUNICATING N - NON-COMMUNICATING
TYPE 1 - SINGLE STAGE P - PISTON
VOLTAGE J = 1 PH, 208-230/60 C = 3 PH, 208-230/60 D = 3 PH, 460/60
A = NATIONAL HEAT PUMP F = DUAL FUEL HEAT PUMP
CAPACITY 18 = 18000 BTU/HR [5.28 kW] 24 = 24000 BTU/HR [7.03 kW] 30 = 30000 BTU/HR [8.79 kW] 36 = 36000 BTU/HR [10.55 kW] 42 = 42000 BTU/HR [12.31 kW] 48 = 48000 BTU/HR [14.07 kW] 60 = 60000 BTU/HR [17.58 kW]
6
13 SEER 14 SEER 15 SEER
HEAT PUMP
BRAND
ALLOW 60" [1524mm] OF
CLEARANCE
AIR INLET LOUVERS ALLOW 6" [152 mm] OF CLEARANCE ALL SIDES 12" [305 mm] RECOMMENDED
SERVICE PANELS/ INLET CONNECTIONS / HIGH & LOW VOLTAGE ACCESS ALLOW 24" [610 mm] OF CLEARANCE
Specifi cations
GENERAL INFORMATION
DIMENSIONAL DATA
Height “H” inches (mm)
Length “L” inches (mm)
Width “W” inches (mm)
Height “H” inches (mm)
Length “L” inches (mm)
Width “W” inches (mm)
Height “H” inches (mm) Length “L” inches (mm)
Width “W” inches (mm)
RP13
RP14
RP15
36, 42 6048
27 (686) 39 (991)35 (889)
33.75 (857) 35.75 (908)33.75 (857)
33.75 (857)
18A, 24A, 30A
18F, 24F
25 (635) 31 (787) 39 (991) 45 (1143)35 (889)
29.75 (756) 33.75 (857) 35.75 (908) 35.75 (908)33.75 (857)
29.75 (756)
18, 24 30 36, 42 48 60 25 (635) 31 (787) 35 (889) 39 (991) 45 (1143)
29.75 (756) 33.75 (857) 33.75 (857) 35.75 (908) 35.75 (908)
29.75 (756) 33.75 (857) 33.75 (857) 35.75 (908) 35.75 (908)
33.75 (857)
35.75 (908)33.75 (857)
30F 48F, 60A 60F
36A, 42A
27 (686)
33.75 (857)
33.75 (857)
36F, 42F
48A
35.75 (908) 35.75 (908)33.75 (857)
General Information
Proper Installation
Proper sizing and installation of this equipment is critical to achieve optimal performance. Use the information in this Installation Instruction Manual and reference the applicable manufacturer’s specification sheet when installing this product.
IMPORTANT: This product has been
designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate indoor components. However, proper refrigerant charge and proper airflow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and airflow instructions. Failure to confirm proper charge
and airflow may reduce energy efficiency and shorten equipment life.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
• INDOOR THERMOSTAT
7
INSTALLATION
Choosing a Location
Location
IMPORTANT:
national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor heat pump.
Consult local and
NOTICE: These units must be installed
outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect performance or operation.
Operational Issues
IMPORTANT: Locate the unit
in a manner that will not prevent, impair, or compromise the performance of other equipment installed in proximity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, and exhaust and inlet openings. In the absence of national codes or manufacturers’ recommendations, local code recommendations and requirements will take precedence.
• Refrigerant piping and wiring should be properly sized and kept as short as possible to avoid capacity losses and increased operating costs.
• Locate the unit where water runoff will not create a problem with the equipment. Position the unit away from the drip edge of the roof whenever possible. Units are weatherized, but can be affected by the following:
• Water pouring into the unit from the junction of rooflines, without protective guttering. Large volumes of water entering the heat pump while in operation can impact fan blade or motor life, and coil damage may occur to a heat pump if moisture cannot drain from the unit under freezing conditions.
• Freezing moisture or sleeting conditions can cause the cabinet to ice-over prematurely and prevent heat pump operation, requiring backup heat, which generally results in less economical operation.
• Closely follow the clearance recommendations on page 8.
• 24" [61.0 cm] to the service panel access
• 60" [152.4 cm] above heat pump fan discharge (unit top) to prevent recirculation
• 6" [15.2 cm] to heat pump coil grille air inlets with 12" [30.5 cm] minimum recommended
Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life.
Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
• Avoid having lawn sprinkler heads spray directly on the unit cabinet.
• In coastal areas, locate the unit on the side of the building away from the waterfront.
• Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
• Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the base pan.
WARNING: Disconnect all power
to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
Regular maintenance will reduce the buildup of contaminants and help to protect the unit’s finish.
• Frequent washing of the cabinet, fan blade, and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
• Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
• A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
8
INSTALLATION
SERVICE PANELS/
INLET CONNECTIONS
/ HIGH & LOW
VOLTAGE ACCESS
ALLOW 24” [610 mm] OF
CLEARANCE
ALLOW 60” [1524 mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152 mm] Min. OF
CLEARANCE ALL SIDES
12” [305 mm] RECOMMENDED
ST-A1226-04-00
6" MIN. (152 mm) FOR 1.5 & 2 TON 9" MIN. (229 mm) FOR 2.5-5 TON 24" MIN. (610 mm)
ST-A1226-03-00
ELEVATE ABOVE
ANTICIPATE HIGH
SNOW FALL
DO NOT BLOCK
OPENINGS
IN BASE PAN
BASE PAD
(CONCRETE OR OTHER SUITABLE
MATERIAL)
Choosing a Location (cont.)
For Units With Space Limitations
In the event that a space limitation exists, we will permit the following clearances:
Single-Unit Applications: Clearances below 6" [15.2 cm] will reduce unit capacity and efficiency. Do not reduce the 60" [152.4 cm] discharge or the 24" [61.0 cm] service clearances.
Multiple-Unit Applications: When multiple condenser grille sides are aligned, a 6" [15.2 cm] clearance is recommended for 1.5 and 2 ton models and 9" [22.9 cm] for 2.5 ton to 5 ton models. Two combined clearances below the minimum will reduce capacity and efficiency. Do not reduce the 60" [152.4 cm] discharge or 24" [61.0 cm] service clearances.
Location
• If elevating a unit on a flat roof, use 4" x 4" [10.2 cm x 10.2 cm] or equivalent stringers positioned to distribute unit weight evenly and prevent noise and vibration.
• Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup and coil damage. Mount the unit high enough to be above the average accumulated area snowfall. See “Ground Snow Depth” chart on page 10 for representative snow depths.
NOTICE: Do not block drain openings on
bottom of unit.
• If unit must be elevated because of anticipated snowfall, secure unit and elevating stand such that unit and/or stand will not tip over or fall off. Keep in mind that someone may try to climb on unit.
Customer Satisfaction Issues
• The heat pump should be located away from the living, sleeping, and recreational spaces of the owner and those spaces on adjoining property.
• To prevent noise transmission, the mounting pad for the outdoor unit should not be connected to the structure and should be located a sufficient distance above grade to prevent ground water from entering the unit.
Unit Mounting
WARNING: Secure an elevated unit
and its elevating stand in order to prevent tipping. Failure to do so may result in severe personal injury or death.
Elevation of Unit
If elevating the heat pump, either on a flat roof or on a slab, observe the following guidelines.
Factory-Preferred Tie-Down Method for High Wind or Seismic Loads
IMPORTANT: The manufacturer-
approved/recommended method is a guide to securing equipment for wind and seismic loads. Other methods might provide the same result, but the manufacturer method is the only one endorsed by the manufacturer for securing equipment where wind or earthquake damage can occur. Additional information is available in the PTS (Product Technical Support) section of the manufacturer’s Web sites Rheemote.net, MyRheem.com, or MyRuud.com and can be found as a listing under each outdoor model. If you do not have access to this site, your distributor can offer assistance.
9
INSTALLATION
Choosing a Location (cont.)
Location
ALABAMA INDIANA MINNESOTA NEW MEXICO PENNSYLVANIA VIRGINIA
Huntsville 7 Evansville 12 Duluth 64 Albuquerque 4 Allentown 23 Dulles Airport 19
ARIZONA
Flagstaff 48 Indianapolis 21
Prescott 3 South Bend 44 Rochester 50
Winslow 7
ARKANSAS
Ft. Smith 5 Des Moines 22 Jackson 3 Buffalo 42 Williamsport 20
Little Rock 6 Dubuque 38 MISSOURI
CALIFORNIA
Blue Canyon 25 Waterloo 36 Kansas City 18 Rochester 38
Mt. Shasta 69
COLORADO
Alamosa 15 Dodge City 12
Colorado Springs 14 Goodland 14 Billings 17 Cape Hattaras 5 Aberdeen 42
Denver 15 Topeka 19 Glasgow 17 Charlotte 10 Huron 43 Beckley 51
Grand Junction 16 Wichita 11 Great Falls 16 Greensboro 11 Rapid City 14 Charleston 20
Pueblo 7
CONNECTICUT
Bridgeport 23 Lexington 12 Kalispell 53 Winston-Salem 17 Bristol 8
Hartford 29 Louisville 11 Missoula 23
New Haven 15
DELAWARE
Wilmington 13 Portland 62 Lincoln 20 Williston 25 Nashville 8 Milwaukee 32
GEORGIA MARYLAND
Athens 5 Baltimore 17 North Platte 15 Akron-Canton 15 Abilene 6 Casper 10
Macon 8
IDAHO
Boise 6 Nantucket 18 Valentine 22 Dayton 11 El Paso 5 Sheridan 25
Lewiston 9 Worcester 35
0 Pocatello 7
ILLINOIS
Chicago O’Hare 18 Detroit City 9 Reno 11
Chicago 22 Detroit Airport 17 Winnemucca 6 Oklahoma City 5 Wichita Falls 5
Moline 17
Peoria 16 Flint 28 Concord 66
Rockford 25 Grand Rapids 37
Springfi eld 23 Houghton Lake 56 Atlantic City 11 Eugene 17 Wendover 3
NOTICE:
10
Local records and experience must be considered when establishing the unit installation height. There is a 2% probability that the ground snow depth shown in this table will be exceeded annually. Drifts have not been considered. This data represents 184 National Weather Service locations at which measurements are made and assumes a nationwide snow density of 12 lb./ft.
Fort Wayne 17 International Falls 43 Clayton 10 Erie 19 Lynchburg 16
IOWA
Burlington 17
Sioux City 33 Columbia 21
KANSAS
Concordia 23 Springfi eld 14
KENTUCKY
Covington 12 Helena 18 Wilmington 9
MAINE NEBRASKA
Caribou 100 Grand Island 30 Fargo 34 Memphis 5 Madison 32
MASSACHUSETTS
Boston 30 Scottsbluff 11 Columbus 10 Dallas 3 Lander 20
MICHIGAN
Alpena 53 Ely 9 Youngstown 12 Midland 2
Detroit – Willow Run
Lansing 42 Newark 15 Medford 8
Marquette 53 Pendleton 11 Burlington 37
Muskegon 43 Portland 10
Sault Ste. Marie 80 Salem 7
GROUND SNOW DEPTH – INCHES
Minneapolis/St. Paul
St. Cloud 53 Albany 25 Pittsburgh 22 Richmond 12
MISSISSIPPI
St. Louis 16 Syracuse 35 Columbia 12 Spokane 41
MONTANA
Havre 24 Raleigh-Durham 10 Sioux Falls 38 Elkins 21
Norfolk 29
Omaha 20 Cleveland 16 Amarillo 10 Cheyenne 15
NEVADA
Elko 20 Toledo Express 8 Lubbock 10
NEW HAMPSHIRE
21
NEW JERSEY
50 Roswell 8 Harrisburg 23 National Airport 18
NEW YORK
Binghamton 35 Scranton 16 Roanoke 17
NYC – Kennedy Airport 18
NYC – LaGuardia Airport 18
NORTH CAROLINA
Asheville 12
NORTH DAKOTA
Bismarck 25 Knoxville 8 La Crosse 32
OHIO TEXAS WYOMING
Mansfi eld 17 Fort Worth 6
OKLAHOMA
Tulsa 8
OREGON
Burns City 24 Salt Lake City 8
Philadelphia 16 Norfolk 9
WASHINGTON
RHODE ISLAND
Providence 21 Quillayute 24
SOUTH CAROLINA
Greenville 4 Stampede Pass 51
SOUTH DAKOTA
TENNESSEE
Chattanooga 6 Green Bay 36
San Antonio 3
UTAH
Milford 16
VERMONT
Olympia 24
Seattle-Tacoma 14
Yakima 25
WEST VIRGINIA
Huntington 15
WISCONSIN
3
Tools and Refrigerant
Ambient and Tube
Thermometers
Manifold
Gauge
Set
Brazing
Rods
Torch Nitrogen
Reclaimer
Recovery Cylinders
Allen Wrench
Crescent Wrench
INSTALLATION
Tools Required for Installing and Servicing R-410A Models
Manifold Sets: – Up to 800 PSIG High-Side – Up to 250 PSIG Low-Side – 550 PSIG Low-Side Retard Manifold Hoses: – Service Pressure Rating of 800 PSIG Recovery Cylinders: – 400 PSIG Pressure Rating – Dept. of Transportation 4BA400 or BW400
CAUTION: R-410A systems operate
at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
Specifications of R-410A
Application: R-410A is not a drop-in replacement for R-22. Equipment designs must
accommodate its higher pressures. It cannot be retrofitted into R-22 heat pumps.
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F [-52.7°C] and its saturation pressure at 77°F [25°C] is 224.5 psig.
Composition: R-410A is a near-azeotropic mixture of 50% by weight difluoromethane (HFC-
32) and 50% by weight pentafluoroethane (HFC-
125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps,
hoses, and the like must have design pressure ratings appropriate for R-410A. Manifold sets
need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating, DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, a mixture of R-410A and air can become combustible. R-410A and air should
never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak-checking can
be performed safely with nitrogen or a mixture of R-410A and nitrogen.
Quick-Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are light rose in color.
• R-410A, as with other HFCs, is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil used in R-410A systems.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post-March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A factory-approved biflow liquid line filter drier is shipped with every unit and must be installed in the liquid line at the time of installation. Only manufacturer-approved liquid line filter driers can be used. These are Sporlan (CW083S) and Alco (80K083S) driers. These filter driers are rated for minimum working pressure of 600 psig. The filter drier will only have adequate moisture-holding capacity if the system is properly evacuated.
• Desiccant (drying agent) must be compatible for POE oils and R-410A refrigerant.
Tools
11
INSTALLATION
Replacement Units
Tubing
To prevent failure of a new unit, the existing line set must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier must be installed and refrigerant tubing must be properly sized. Test the oil for acid. If positive, a suction line filter drier is mandatory.
Indoor Coil
CAUTION: Only use evaporators
approved for use on R-410A systems that are specifically matched with the outdoor unit per the manufacturer’s specification sheets. Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant, forming two different liquids and decreasing oil return to the compressor. This can result in compressor failure.
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not
responsible for the performance and operation of a mismatched system or for a match listed with another manufacturer’s coil.
NOTICE: All outdoor units must be
installed with a matched TXV indoor coil. Refer to manufacturer’s outdoor unit specification sheet for approved indoor coils.
IMPORTANT: When replacing an
R-22 unit with an R-410A unit, either replace the line set or ensure that residual mineral oil is drained from existing lines including oil trapped in low spots.
The thermostatic expansion valve in the matching coil is specifically designed to operate with R-410A. DO NOT use an R-22 TXV or
evaporator. The existing evaporator must be replaced with the factory-specified TXV evaporator specifically designed for R-410A.
Location
Do not install the indoor coil in the return duct system of a gas or oil furnace. Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched toward the drain connection.
CAUTION: When coil is installed
over a finished ceiling and/or living area, it is required that a secondary condensate pan be installed under entire unit. Failure to do so can result in property damage.
12
Interconnecting Tubing
The purpose of this section is to specify the best construction/sizing practices for installing interconnection tubing between the indoor and outdoor unit.
Refrigerant Level Adjustment
All units are factory-charged with R-410A refrigerant to cover 15 feet of standard size interconnecting liquid and vapor lines with a required field installed filter drier. Adjustment of charge may be necessary even if the application has exactly 15 feet of line set due to other installation variables such as pressure drop, vertical lift, and indoor coil size. For different lengths, adjust the charge as indicated below.
• 1/4" ± .3 oz./foot [6.4 mm ± 8.5 g/.30 m]
• 5/16" ± .4 oz./foot [7.9 mm ± 11.3 g/.30 m]
• 3/8" ± .6 oz./foot [9.5 mm ± 17.0 g/.30 m]
• 1/2" ± 1.2 oz./foot [12.7 mm ± 34.0 g/.30 m]
• 6 oz. required factory supplied field-installed
filter drier.
Charge Adjustment = (Line Set (oz./ft.) x Total Length) – Factory Charge for Line Set
Example: A three ton heat pump unit with factory
installed 3/8” liquid service valve requires 75 ft. of line set with a liquid line diameter of 1/2”.
Factory Charge for Line Set = 15 ft. x .6 oz. = 9 oz. Charge Adjustment = (1.2 oz. x 75 ft.) – 9 oz. =
+ 81 oz.
Interconnecting Tubing (cont.)
INSTALLATION
Interconnecting Tubing and Fitting Losses
Refrigerant tubing is measured in terms of actual length and equivalent length. Actual length is used for refrigerant charge applications. Equivalent length takes into account pressure losses from
Equivalent Length for Fings ()
90° Short
Line Size
(in)
3/8 1.3 0.8 0.3 6 4 0.4 6 1/2 1.4 0.9 0.4 9 5 0.6 6 5/8 1.5 1 0.5 12 6 0.8 6 3/4 1.9 1.3 0.6 14 7 0.9 6 7/8 2.3 1.5 0.7 15 8 1 6
1-1/8 2.7 1.8 0.9 22 12 1.5 6
Radius
Elbow
90° Long
Radius Elbow
45°
Elbow
Liquid Line Selection
The purpose of the liquid line is to transport warm sub-cooled liquid refrigerant from the outdoor unit to the indoor unit. It is important not to allow the refrigerant to fl ash any superheated vapor prior to the expansion device of the indoor coil. The ashing of refrigerant can occur for the following reasons:
• Low refrigerant charge
• Improperly selected liquid line size
• Absorption of heat prior to expansion device
• Excessive vertical rise between the condenser and evaporator
Table 2 lists the equivalent length per 25’ of liquid line at various diameters up to 300’. The total pres-
tubing length, fi ttings, vertical separation, acces- sories, and fi lter dryers. The table below references diff erent commonly used equivalent lengths.
Table 1
Solenoid
Valve
sure drop allowed for the liquid line is 50 PSI. The procedure for selecting the proper liquid line is as follows:
• Measure the total amount of vertical rise
• Measure the total amount of liquid line needed
• Add all of the equivalent lengths associated with any fi ttings or accessories using the table above.
• Add the total length and fi tting pressure drop. This will equal your total equivalent length.
• Round-down the total equivalent length to the closest value in Table 2.
• Reference Table 2 to verify the rounded-down value of the calculated equivalent length is com­patible with the required vertical rise and diam­eter of liquid line.
Check
Valve
Site
Glass
Filter Dryer
Tubing
Note: Elevaon is defined as the
highest point of the line set to the
lowest
13
INSTALLATION
Interconnecting Tubing (cont.)
Example: A 3-Ton heat pump unit is installed 50’
below the ID unit, requires a 75’ of 1/2” diameter liquid line, and 4 90° LR elbows.
• Fitting Equivalent Length (ft.) = 4 x .9 = 3.6’
• Total Equivalent Length (ft.) = 75’ + 3.6’ = 78.6’
• Rounded-down value (ft.) = 75’
Liquid Line
R-410A System
Capacity
Model
(Exerpt from Table 2, page 17)
Size
Connection
Size (Inch I.D.) [mm]
37 3/8" [9.53]
Liquid Line
Size (Inch
O.D.) [mm]
1/4 [6.35] 25 [7.62]
5/16 [7.94] 25 [7.62] 50 [15.24] 60 [18.29] 45 [13.72] 35 [10.67] 20 [6.1] 5 [1.52]
3/8 [9.53] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 80 [24.38] 75 [22.86] 70 [21.34] 65 [19.81] 60 [18.29] 55 [16.76] 50 [15.24] 45 [13.72]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38]
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 90 [27.43] 90 [27.43] 90 [27.43]
25 [7.62] 50 [ 15.24] 75 [22.86] 100 [30.48] 125 [45. 72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
Long Line Set Applications
Long line set applications are defi ned as applica- tions that require accessories or alternate construc­tion methods. The following are special consider­ations that need to be addressed when installing a long line set application:
• Additional refrigerant charge
• Fitting losses and maximum equivalent length
Tubing
considerations
• Refrigerant migration during the off cycle
• Oil return to the compressor
• Capacity losses
• System oil level adjustment
Table 2 is used to determine if the application is
considered to have a long line set. The region of
the chart that is shaded grey is considered to be a long line set application.
Oil Level Adjustments for Long Line Set Applications
Additional oil will need to be added for long line set applications. (Ref. Table 2). Below is the equation for the oil level adjustment and the compressor name plate oil charge for the diff erent od units.
Oil to be Added = [(Charge Adjustment + OD Unit Name Plate Charge (oz.)) x (0.022) – [(0.10) x (Compressor Name Plate Oil Charge (oz.))]
Example: An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjust­ment = 52.4 oz., Name Plate Charge = 107 oz., Name Plate Oil Charge = 25 oz., Oil to be Added = ((52.4 oz. +107 oz.) x .022) – (.10 x 25 oz.) = 1.0 oz.
This application is acceptable because the 50’ vertical rise is less than the maximum rise of 75’ for this application. The application is also considered to have a long line set. Reference the long line set section of the I&O for detail.
Liquid Line S i z e
Elevation (Above or Below) Indoor Coil
Total
Maximum
RP1436AC ZP31K5E-T5F-13R 42 N RP1442AC ZP36K5E-TF5-13R 42 Y RP1448AC ZP42K5E-TF5-13R 42 N RP1460AC ZP49K6E-TF5-130 42 Y RP1436AD ZP31K5E-TFD-13R 42 N RP1442AD ZP36K5E-TFD-13R 42 Y RP1448AD ZP42K5E-TFD-13R 42 Y RP1460AD ZP49K6E-TFD-130 42 Y RP1418AJ ZP16K5E-PFV-13R 21 N RP1430AJ ZP25K5E-PFV-13R 25 N RP1436AJ ZP31K5E-PFV-13R 21 N RP1442AJ ZP21K6E-PFV-130 21 N RP1442AJ ZP36K5E-PFV-13R 42 N RP1448AJ ZP42K5E-PFV-13R 42 Y RP1460AJ ZP49K6E-PFV-130 42 N RP1436FC ZP31K6E-TF5-130 21 N RP1442FC ZP36K5E-TF5-13R 42 N RP1448FC ZP40K6E-TF5-130 42 Y RP1460FC ZP49K6E-TF5-130 42 Y RP1418FJ ZP14K6E-PFV-130 21 N RP1424FJ ZP20K6E-PFV-130 21 N RP1430FJ ZP24K6E-PFV-130 25 N RP1436FJ ZP31K6E-PFV-130 21 N RP1442FJ ZP36K5E-PFV-13R 42 N RP1448FJ ZP40K6E-PFV-130 42 N RP1460FJ ZP49K6E-PFV-130 42 Y
Length - Feet [ m ]
Equivalent
Vertic al S eparation - Feet [m]
OD Model
RP1336AC RP1342AC RP1348AC RP1360AC RP1336AD RP1342AD RP1348AD RP1360AD
OD Model
N/R N/R N/R N/R N/R
Compressor
ZP31K5E-TF5-13R 42 ZP36K5E-TF5-13R 42
ZP42K5E-TF5-13R ZP49K6E-TF5-130 ZP31K5E-TFD-13R ZP36K5E-TFD-13R ZP42K5E-TFD-13R ZP49K6E-TFD-130
Compressor
Name Plate Oil
Charge (oz)
42
42 42
42 42 42
Name Plate Oil
Charge (oz)
Factory
Installed
CCH
Factory
Installed
CCH
N Y N Y N Y Y Y
14
Interconnecting Tubing (cont.)
INSTALLATION
OD Model
RP1518AJ
RP1518BJ
RP1524AJ
RP1524BJ
RP1530AJ
RP1530BJ
RP1536AJ
RP1542AJ
RP1548AJ
RP1560AJ
RP1536AC
RP1542AC
RP1548AC
RP1560AC
Compressor
ZP16K5E-PFV-13R 21
ZP14K6E-PFV-130 21
ZP21K5E-PFV-13R 21
ZP20K6E-PFV-130 21
ZP25K5E-PFV-13R
ZP24K6E-PFV-130
ZP31K6E-PFV-130 21
ZP36K5E-PFV-13R
ZP40K6E-PFV-130 42
ZP49K6E-PFV-130
ZP31K6E-TF5-130
ZP36K5E-TF5-13R
ZP40K6E-TF5-130
ZP49K6E-TF5-130
Name Plate Oil
Charge (oz)
25
25
42
42
21
42
42
42
Factory
Installed
CCH
N
N
N
N
N
N
N
N
N
Y
N
N
Y
Y
Suction Line Selection
Purpose of the suction line is to return superheated vapor to the condensing unit from the evaporator. Proper suction line sizing is important because it plays an important role in returning oil to the com­pressor to prevent potential damage to the bear­ings, valves, and scroll sets. Also, an improperly sized suction line can dramatically reduce capacity
and performance of the system. The procedure for selecting the proper suction line is as follows:
• The total amount of suction line needed
• Add all of the equivalent lengths associated with any fi ttings or accessories using the table on previous page.
• Add the total length and fi tting pressure drop. This will equal your total equivalent length.
• Reference Table 2 to verify that the calculated equivalent length falls within the compatibility region of the chart.
• Verify Table 3 to verify the capacity diff erence is compatible with the application.
Refrigerant Migration During Off Cycle
Long line set applications can require a consider­able amount of additional refrigerant. This addition­al refrigerant needs to be managed throughout the entire ambient operating envelope that the system will go through during its life cycle. Off -Cycle mi- gration is where excess refrigerant condenses and migrates to the lowest part of the system. Exces­sive build-up of refrigerant at the compressor will result in poor reliability and noisy operation during startup. This section demonstrates the required accessories and unit confi guration for diff erent ap- plications.
Tubing
OUTDOOR UNIT LEVEL OR NEAR LEVEL TO INDOOR SECTION LINE SET
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH LIMITATIONS
IDEALLY, LINE SET SLOPES AWAY
FROM OUTDOOR. VERIFY
SUB-COOLING PRIOR TO
THROTTLEING DEVICE, INSULATED
LIQUID LINE.
ST-A1219-01-01
15
INSTALLATION
Interconnecting Tubing (cont.)
Tubing
For applications that are considered to have a long line set with the outdoor unit and indoor unit on the same level the following is required:
• TXV or EEV on the indoor unit
• Start components may be required depending upon quality of voltage (consistantly <200vac at outdoor unit)
Crankcase heater (Some models have factory in­stalled CCH's. Refer to tables on pages 14 and 15.)
OUTDOOR UNIT BELOW INDOOR SECTION LINE SET
INSULATE
LIQUID AND
SUCTION LINE
• Insulated liquid and suction line
• Vapor line should slope toward the indoor unit
• Follow the proper line sizing, equivalent length, charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify at least 5°F sub-cooling at the ID unit prior to throttling device
ROUTE REFIGERANT LINES EVEN WITH TOP OF
COIL OR INSTALL INVERTED TRAP .
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH
LIMITATIONS
For applications that are considered to have a long line set with the outdoor unit below the indoor unit the following is required:
• TXV or EEV at the IDunit
• Crankcase heater (Some models have factory installed CCH's. Refer to tables on pages 14 and 15.)
• Start components may be required depending upon quality of voltage (consistantly <200vac at OD unit)
• Refrigerant lines should be routed even with the top of the ID coil or an inverted trap is to be ap-
16
ST-A1219-02-02
Figure 4
plied (refer to fi gure 4).
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length, charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Measure pressure at the liquid line service valve and prior to expansion device. Verify that it is not greater than 50 PSI
• For elevations greater that 25’ can expect a lower sub-cooling
Interconnecting Tubing (cont.)
OUTDOOR UNIT ABOVE INDOOR SECTION LINE SET
INSULATE LIQUID AND
SUCTION LINE
INSTALLATION
REFERENCE TABLE 2
FOR ELEVATION
LIMITATIONS
Tubing
VERIFY
SUB-COOLING
PRIOR TO
THROTTLING
DEVICE
For applications that are considered to have a long line set with the outdoor unit above the indoor unit the following is required:
• TXV at the indoor unit
• Crankcase heater (Some models have factory installed CCH's. Refer to tables on pages 14 and
15.)
• Start components maybe required depending upon quality of voltage (consistantly <200 vac at outdoor unit)
TXV OR EEV AT INDOOR
EVAPORATOR
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length, charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify at least 5°F sub-cooling at the ID unit prior to throttling device
17
Loading...
+ 39 hidden pages