PACKAGE AIR CONDITIONERS FEATURING INDUSTRY STANDARD
R410A REFRIGERANT
RLKL-B SERIES 7.5, 10 AND 12.5 TON [26.4, 35.2 AND 44.0 kW]
60 HZ MODELS
Recognize this symbol as an indication of Important Safety Information!
!
DO NOT DESTROY
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE
FOR FUTURE REFERENCE.
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ
THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING
INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION,
ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR
DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE
OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE
AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION
WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF
UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO
ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY
RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE
OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR
DEATH.
CAUTION
!
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22
service equipment or components on R-410A equipment.
WARNING
!
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO
ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT,
STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE,
SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. A GROUNDING LUG IS
PROVIDED IN THE ELECTRIC HEAT ACCESS AREA FOR A GROUND WIRE.
FAILURE TO GROUND THIS UNIT CAN RESULT IN FIRE OR ELECTRICAL
SHOCK CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR
DEATH.
WARNING
!
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS
DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND
EVALUATED FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE
HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.
3
WARNING
!
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE
ATTACHMENT OR USE OF ANY
COMPONENTS, ACCESSORIES OR
DEVICES (OTHER THAN THOSE
AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE
THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY
ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER
AND MAY ALSO ENDANGER LIFE
AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR
INJURY RESULTING FROM THE
USE OF SUCH UNAUTHORIZED
COMPONENTS, ACCESSORIES OR
DEVICES.
II. INTRODUCTION
This booklet contains the installation and operating instructions for your air conditioner.
There are a few precautions that should be taken to derive maximum satisfaction from it.
Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required to
make up the system prior to installation. Give this booklet to the owner and explain its
provisions. The owner should retain this booklet for future reference.
III. CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage,
either shipping or concealed, should be filed immediately with the shipping company.
Check the unit model number, heating size, electrical characteristics, and accessories to
determine if they are correct.
IV. EQUIPMENT PROTECTION FROM THE
IV. ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray,
fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries
are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
1. Avoid having lawn sprinkler heads spray direction on the unit cabinet.
2. In coastal areas, locate the unit on the side of the building away from the waterfront.
3. Shielding provided by a fence or shrubs may give some protection.
Regular maintenance will reduce the buildup of contaminants and help to protect
the unit’s finish.
WARNING
!
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR
DEATH.
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.
2. Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
3. A good liquid cleaner may be used several times a year to remove matter that will
not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings
may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to
contaminants.
V. SPECIFICATIONS
A. GENERAL
The Packaged Air Conditioners are available without heat or with 10, 15, 20, 30, 40 or
50 kW electric heat. Cooling capacities of 7.5, 10 or 12.5 nominal tons of cooling are
available. Units are convertible from horizontal supply and return to bottom supply and
return by relocation of supply and return air access panels. See cover installation detail.
The units are weatherized for mounting outside of the building.
4
The information on the rating plate is in compliance with the FTC and DOE rating for single phase units. The following information is for three phase units which are not covered
under the DOE certification program.
1. The efficiency rating of this unit is a product thermal efficiency rating determined
under continuous operating conditions independent of any installed system.
B. MAJOR COMPONENTS
The typical unit includes a hermetically-sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with thermal expansion valve), a circulation air
blower, a condenser fan, and all necessary internal electrical wiring. The cooling system
of these units are factory-evacuated, charged and performance tested. Refrigerant
amount and type are indicated on rating plate.
C. R-410A REFRIGERANT
All units are factory charged with R-410A refrigerant.
1. Specification of R-410A:
Application: R-410A is not a drop-in replacement for R-22
accommodate its higher pressures. It cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than
R-22. Recovery and recycle equipment, pumps, hoses and the like need to have design
pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig
high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a
service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service
pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never
be done with a mixture of R-410A and air. Leak checking can be performed safely
with nitrogen or a mixture of R-410A and nitrogen.
; equipment designs must
2. Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-
22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for
equipment charging. Post March 1999 cylinders do not have a dip tube and should
be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
3. Evaporator Coil / Expansion Device
The expansion device is specifically designed to operate with R-410A. DO NOT use an
R-22 device. The existing evaporator must be replaced with the factory specified
evaporator specifically designed for R-410A.
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22
service equipment or components on R-410A equipment.
5
FIGURE 1
UNIT DIMENSIONS AND ACCESS LOCATIONS
403⁄16”
[1020.7 mm]
313⁄16”
[96.8 mm]
CONDENSER FANS
POWER
ENTRY
3
1
⁄4” [44.5 mm]
DIA.
FRONT SIDE
5
6
⁄8”
[168.3 mm]
1
⁄8”
4
[104.8 mm]
11
11
⁄16”
[296.9 mm]
COMPRESSOR
ACCESS
FIGURE 2
BASE DIMENSIONS
SUPPLY COVER
(REAR SIDE)
ELECTRICAL
ACCESS
9311⁄16”
[2379.6 mm]
RETURN COVER
BLOWER
ACCESS
COMPRESSOR
ACCESS
SUPPLY
AIR
CONTROL
7
⁄8” [22.2 mm]
583⁄4”
[1492.2 mm]
ENTRY
DIA.
5”
[127 mm]
LEFT SIDE
13
⁄16”
6
[173 mm]
CONDENSER
COIL
(RIGHT SIDE)
ST-A1112-02-00
RETURN
AIR
REAR
SIDE
ST-A1154-03-00
6
FIGURE 3
SUPPLY RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS
25"
[635 mm]
14"
[355.6 mm]
34"
[863.6 mm]
8"
[203.2 mm]
THRU THE BASE ELECTRIC
54"
[1371.6 mm]
23"
[585.5 mm]
UNIT DIMENSIONS
FIGURE 4
BOTTOM VIEW
SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS
RIGHT
SIDE
3
/4”
58
[1492.2 mm]
9311/16”
[2379.4 mm]
88
[2259 mm]
[112.7 mm]
15
/16”
7
4
/16”
1
15
/8”
[384.1 mm]
ST-A1154-04-00
7
/16”
4
[112.7 mm]
1
2
/16”
107/16”
[265.1 mm]
1
2
/8”
[54 mm]
LEFT
SIDE
A0712-02
FRONT
SIDE
3
/8”
2
[60.3 mm]
1
/8”
2
[54 mm]
1
/2”
27
[698.5 mm]
1
/2”
6
[165.1 mm]
7
*26"
[660.4 mm]
12"
[304.8 mm]
44"
[1117.6 mm]
34"
[863.6 mm]
14"
[355.6 mm]
28"
[711.2 mm]
SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATION
SUPPLY DUCT MAY EXTEND UP TO THIS LEVEL
FIGURE 5
REAR VIEW
RIGHT
SIDE
COMPRESSOR
ACCESS
7
/32”
7
[183.3 mm]
LEFT
SIDE
*RECOMMENDED DUCT DIMENSIONS ARE 26”
13
[346 mm]
9311/16”
[2379.6 mm]
5
/8”
7
4
/16”
[112.7 mm]
A0714-03
8
GENERAL DATA - RLKL
NOM. SIZE 7.5, 10 AND 12.5 TON [26.4, 35.2 AND 44.0 kW]
Model RLKL - SeriesB090CLB090CMB090CNB090DL
Cooling performance
Gross Cooling Capacity Btu [kW]87,000 [25.49]87,000 [25.49]87,000 [25.49]87,000 [25.49]
EER/SEER
Nominal CFM/AHRI Rated CFM [L/s]2800/2925 [1321/1380]2800/2925 [1321/1380]2800/2925 [1321/1380]2800/2925 [1321/1380]
AHRI Net Cooling Capacity Btu [kW]84,000 [24.61]84,000 [24.61]84,000 [24.61]84,000 [24.61]
Net Sensible Capacity Btu [kW]64,800 [18.99]64,800 [18.99]64,800 [18.99]64,800 [18.99]
Net Latent Capacity Btu [kW]19,200 [5.63]19,200 [5.63]19,200 [5.63]19,200 [5.63]
IEER
Net System Power kW7.57.57.57.5
Compressor
No./Type1/Scroll1/Scroll1/Scroll1/Scroll
Outdoor Sound Rating (dB)
Outdoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeMicroChannelMicroChannelMicroChannelMicroChannel
MicroChannel Depth in. [mm]1 [25.4]1 [25.4]1 [25.4]1 [25.4]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]1 / 23 [9]1 / 23 [9]1 / 23 [9]1 / 23 [9]
Indoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeRifledRifledRifledRifled
Tube Size in. [mm]0.375 [9.5]0.375 [9.5]0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]2 / 18 [7]2 / 18 [7]2 / 18 [7]2 / 18 [7]
Refrigerant ControlOrificesOrificesOrificesOrifices
Drain Connection No./Size in. [mm]1/1 [25.4]1/1 [25.4]1/1 [25.4]1/1 [25.4]
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter in. [mm]1/24 [609.6]1/24 [609.6]1/24 [609.6]1/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]4500 [2124]4500 [2124]4500 [2124]4500 [2124]
No. Motors/HP1 at 1/2 HP1 at 1/2 HP1 at 1/2 HP1 at 1/2 HP
Motor RPM1075107510751075
Indoor Fan - TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP2232
Motor RPM1725172517251725
Motor Frame Size56565656
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]117.6 [3334]117.6 [3334]117.6 [3334]117.6 [3334]
Weights
GENERAL DATA - RLKL
NOM. SIZE 7.5, 10 AND 12.5 TON [26.4, 35.2 AND 44.0 kW]
Model RLKL - SeriesB090DMB090DNB090YLB090YM
Cooling performance
Gross Cooling Capacity Btu [kW]87,000 [25.49]87,000 [25.49]87,000 [25.49]87,000 [25.49]
EER/SEER
Nominal CFM/AHRI Rated CFM [L/s]2800/2925 [1321/1380]2800/2925 [1321/1380]2800/2925 [1321/1380]2800/2925 [1321/1380]
AHRI Net Cooling Capacity Btu [kW]84,000 [24.61]84,000 [24.61]84,000 [24.61]84,000 [24.61]
Net Sensible Capacity Btu [kW]64,800 [18.99]64,800 [18.99]64,800 [18.99]64,800 [18.99]
Net Latent Capacity Btu [kW]19,200 [5.63]19,200 [5.63]19,200 [5.63]19,200 [5.63]
IEER
Net System Power kW7.57.57.57.5
Compressor
No./Type1/Scroll1/Scroll1/Scroll1/Scroll
Outdoor Sound Rating (dB)
Outdoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeMicroChannelMicroChannelMicroChannelMicroChannel
MicroChannel Depth in. [mm]1 [25.4]1 [25.4]1 [25.4]1 [25.4]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]1 / 23 [9]1 / 23 [9]1 / 23 [9]1 / 23 [9]
Indoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeRifledRifledRifledRifled
Tube Size in. [mm]0.375 [9.5]0.375 [9.5]0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]2 / 18 [7]2 / 18 [7]2 / 18 [7]2 / 18 [7]
Refrigerant ControlOrificesOrificesOrificesOrifices
Drain Connection No./Size in. [mm]1/1 [25.4]1/1 [25.4]1/1 [25.4]1/1 [25.4]
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter in. [mm]1/24 [609.6]1/24 [609.6]1/24 [609.6]1/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]4500 [2124]4500 [2124]4500 [2124]4500 [2124]
No. Motors/HP1 at 1/2 HP1 at 1/2 HP1 at 1/2 HP1 at 1/2 HP
Motor RPM1075107510751075
Indoor Fan - TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP2322
Motor RPM1725172517251725
Motor Frame Size56565656
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]117.6 [3334]117.6 [3334]117.6 [3334]117.6 [3334]
Weights
GENERAL DATA - RLKL
NOM. SIZE 7.5, 10 AND 12.5 TON [26.4, 35.2 AND 44.0 kW]
Model RLKL - SeriesB090YNB120CLB120CMB120DL
Cooling performance
Gross Cooling Capacity Btu [kW]87,000 [25.49]123,000 [36.04]123,000 [36.04]123,000 [36.04]
EER/SEER
Nominal CFM/AHRI Rated CFM [L/s]2800/2925 [1321/1380]4000/3600 [1888/1699]4000/3600 [1888/1699]4000/3600 [1888/1699]
AHRI Net Cooling Capacity Btu [kW]84,000 [24.61]119,000 [34.87]119,000 [34.87]119,000 [34.87]
Net Sensible Capacity Btu [kW]64,800 [18.99]87,200 [25.55]87,200 [25.55]87,200 [25.55]
Net Latent Capacity Btu [kW]19,200 [5.63]31,800 [9.32]31,800 [9.32]31,800 [9.32]
IEER
Net System Power kW7.510.6210.6210.62
Compressor
No./Type1/Scroll1/Scroll1/Scroll1/Scroll
Outdoor Sound Rating (dB)
Outdoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeMicroChannelMicroChannelMicroChannelMicroChannel
MicroChannel Depth in. [mm]1 [25.4]1 [25.4]1 [25.4]1 [25.4]
Face Area sq. ft. [sq. m]13.5 [1.25]27 [2.51]27 [2.51]27 [2.51]
Rows / FPI [FPcm]1 / 23 [9]1 / 23 [9]1 / 23 [9]1 / 23 [9]
Indoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeRifledRifledRifledRifled
Tube Size in. [mm]0.375 [9.5]0.375 [9.5]0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]2 / 18 [7]2 / 22 [9]2 / 22 [9]2 / 22 [9]
Refrigerant ControlOrificesOrificesOrificesOrifices
Drain Connection No./Size in. [mm]1/1 [25.4]1/1 [25.4]1/1 [25.4]1/1 [25.4]
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter in. [mm]1/24 [609.6]2/24 [609.6]2/24 [609.6]2/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]4500 [2124]8400 [3964]8400 [3964]8400 [3964]
No. Motors/HP1 at 1/2 HP1 at 1/3 HP1 at 1/3 HP1 at 1/3 HP
Motor RPM1075107510751075
Indoor Fan - TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP3232
Motor RPM1725172517251725
Motor Frame Size56565656
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]117.6 [3334]203.2 [5761]203.2 [5761]203.2 [5761]
Weights
GENERAL DATA - RLKL
NOM. SIZE 7.5, 10 AND 12.5 TON [26.4, 35.2 AND 44.0 kW]
Model RLKL - SeriesB120DMB120YLB120YMB151CL
Cooling performance
Gross Cooling Capacity Btu [kW]123,000 [36.04]123,000 [36.04]123,000 [36.04]146,000 [42.78]
EER/SEER
Nominal CFM/AHRI Rated CFM [L/s]4000/3600 [1888/1699]4000/3600 [1888/1699]4000/3600 [1888/1699]5000/4225 [2360/1994]
AHRI Net Cooling Capacity Btu [kW]119,000 [34.87]119,000 [34.87]119,000 [34.87]140,000 [41.02]
Net Sensible Capacity Btu [kW]87,200 [25.55]87,200 [25.55]87,200 [25.55]99,500 [29.15]
Net Latent Capacity Btu [kW]31,800 [9.32]31,800 [9.32]31,800 [9.32]40,500 [11.87]
IEER
Net System Power kW10.6210.6210.6212.73
Compressor
No./Type1/Scroll1/Scroll1/Scroll2/Scroll
Outdoor Sound Rating (dB)
Outdoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeMicroChannelMicroChannelMicroChannelMicroChannel
MicroChannel Depth in. [mm]1 [25.4]1 [25.4]1 [25.4]1 [25.4]
Face Area sq. ft. [sq. m]27 [2.51]27 [2.51]27 [2.51]27 [2.51]
Rows / FPI [FPcm]1 / 23 [9]1 / 23 [9]1 / 23 [9]2 / 23 [9]
Indoor Coil - Fin TypeLouveredLouveredLouveredLouvered
Tube TypeRifledRifledRifledRifled
Tube Size in. [mm]0.375 [9.5]0.375 [9.5]0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]13.5 [1.25]13.5 [1.25]13.5 [1.25]13.5 [1.25]
Rows / FPI [FPcm]2 / 22 [9]2 / 22 [9]2 / 22 [9]4 / 15 [6]
Refrigerant ControlOrificesOrificesOrificesTX Valves
Drain Connection No./Size in. [mm]1/1 [25.4]1/1 [25.4]1/1 [25.4]1/1 [25.4]
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter in. [mm]2/24 [609.6]2/24 [609.6]2/24 [609.6]2/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]8400 [3964]8400 [3964]8400 [3964]8000 [3775]
No. Motors/HP1 at 1/3 HP1 at 1/3 HP1 at 1/3 HP2 at 1/2 HP
Motor RPM1075107510751075
Indoor Fan - TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]
Drive TypeBelt/VariableBelt/VariableBelt/VariableBelt (Adjustable)
No. SpeedsSingle
No. Motors1111
Motor HP3233
Motor RPM1725172517251725
Motor Frame Size56565656
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457]
Outdoor Fan - TypePropellerPropellerPropellerPropeller
No. Used/Diameter in. [mm]2/24 [609.6]2/24 [609.6]2/24 [609.6]2/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]8000 [3775]8000 [3775]8000 [3775]8000 [3775]
No. Motors/HP2 at 1/2 HP2 at 1/2 HP2 at 1/2 HP2 at 1/2 HP
Motor RPM1075107510751075
Indoor Fan - TypeFC CentrifugalFC CentrifugalFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]1/15x15 [381x381]
Drive TypeBelt (Adjustable)Belt (Adjustable)Belt (Adjustable)Belt (Adjustable)
No. SpeedsSingleSingleSingleSingle
No. Motors1111
Motor HP5353
Motor RPM1725172517251725
Motor Frame Size1845618456
FurnishedYesYesYesYes
(NO.) Size Recommended in. [mm x mm x mm](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457](6)2x18x18 [51x457x457]