Rheem RKNN, RKPN, RKQN Installation Manual

ISO 9001:2008
INSTALLATION INSTRUCTIONS
Package Gas Electric Featuring Industry Standard R-410A Refrigerant
RKNN 13 SEER (3-5 TONS) SERIES RKPN 14 SEER (3-5 TONS) SERIES RKQN 15 SEER (3-5 TONS) SERIES
ONLY)
92-23577-129-04
SUPERSEDES 92-23577-129-03
I.TABLE OF CONTENTS
I. Table of Contents ..................................................................................................2
II. Introduction............................................................................................................3
III. Checking Product Received ..................................................................................3
IV. Specifications.........................................................................................................3
A. General .............................................................................................................3
B. Major Components............................................................................................3
C.R-410A Refrigerant...........................................................................................3
1. Specifications of R-410A...............................................................................3
2. Quick Reference Guide for R-410A ..............................................................4
3. Evaporator Coil/TXV .....................................................................................4
4. Tools Required for Installing and Servicing R-410A Models.........................4
V. Safety Information..................................................................................................4
VI. Unit Dimensions.....................................................................................................5
VII. Installation..............................................................................................................7
A. General .............................................................................................................7
1. Pre-Installation Check..................................................................................7
2. Location Considerations...............................................................................7
B. Outside Installation............................................................................................8
C.Attaching Exhaust and Combustion Air Inlet Hoods .........................................9
D.Cover Panel Installation/Conversion Procedure ...............................................9
E. Clearances........................................................................................................9
F. Rooftop Installation .........................................................................................10
G.Ductwork .........................................................................................................10
H.Return Air........................................................................................................11
VIII. Gas Supply, Condensate Drain and Piping.........................................................13
A. Gas Connection ..............................................................................................13
B. LP Conversion.................................................................................................14
C.NOx Models ....................................................................................................14
D.Adjusting or Checking Furnace Input..............................................................15
E. Condensate Drain ...........................................................................................16
IX. Wiring...................................................................................................................16
A. Power Supply..................................................................................................16
B. Hook Up ..........................................................................................................18
C.Internal Wiring.................................................................................................18
D.Thermostat......................................................................................................18
X. Furnace Section Controls and Ignition System....................................................19
Normal Furnace Operating Sequence.................................................................19
Operating Instructions .........................................................................................20
Burners................................................................................................................21
Manual Reset Overtemperature Control..............................................................21
Pressure Switch...................................................................................................21
Limit Control ........................................................................................................21
XI. System Operating Information.............................................................................21
Advise the Customer...........................................................................................21
Furnace Section Maintenance.............................................................................22
Lubrication...........................................................................................................23
Cooling Section Maintenance..............................................................................23
Replacement Parts..............................................................................................24
Troubleshooting...................................................................................................24
Wiring Diagrams..................................................................................................24
Charging..............................................................................................................24
Blower Motor Speed Taps...................................................................................24
XII. General Data..................................................................................................27-66
XIII. Units with ECM Blower Motors
(RKQN-A060CV & DV Units Only)..................................................................67
XIV. Miscellaneous......................................................................................................71
Electrical and Physical Data...........................................................................70-79
Airflow Performance.......................................................................................80-89
Wiring Diagrams...........................................................................................90-103
Charge Chart.....................................................................................................104
Troubleshooting..........................................................................................105-107
2
Recognize this symbol as an
!
indication of Important Safety Information!
WARNING
!
THE MANUFACTURER’S WAR­RANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPER­ATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFAC­TURER DISCLAIMS ANY RESPON­SIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
INSTALL THIS UNIT ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDER­ATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADE­QUATE COMBUSTION AND VEN­TILATION AIR TO THE UNIT SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUS­TION AND VENTILATION AIR TO THE UNIT SPACE AS SPECIFIED IN THE COMBUSTION AND VENTI­LATION AIR SECTION OF THESE INSTRUCTIONS.
II. INTRODUCTION
This booklet contains the installation and operating instructions for your combination gas heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference.
III. CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. IMPORTANT: Check the unit model number, heating size, electrical characteristics, and accessories to determine if they are correct.
IV. SPECIFICATIONS
A. GENERAL
The Combination Gas Heating/Electric Cooling Rooftop is available in 80,000, 100,000, 120,000 and 135,000 BTU/Hr. heating inputs and cooling capacities of 3, 3 nominal tons of cooling. Units are convertible from bottom supply and return to side sup­ply and return by relocation of supply and return air access panels. See cover installa­tion detail.
The units are weatherized for mounting outside of the building.
WARNING
!
UNITS ARE NOT DESIGN CERTIFIED TO BE INSTALLED INSIDE THE STRUC­TURE. DOING SO CAN CAUSE INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE AND CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
The information on the rating plate is in compliance with the FTC and DOE rating for sin­gle phase units. The following information is for three phase units which are not covered under the DOE certification program.
1. The energy consumption of the ignition system used with this unit is 9 watts.
2. The efficiency rating of this unit is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed refrigerating system (consisting of a scroll com­pressor, condenser coil, evaporator coil with thermostatic expansion valve), a circulation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assem­bly, combustion air motor and fan, and all necessary internal electrical wiring. The cool­ing system of these units is factory-evacuated, charged with R-410A refrigerant and per­formance tested. Refrigerant amount and type are indicated on rating plate.
C. R410A REFRIGERANT
All units are factory charged with R-410A refrigerant.
1
2, 4, and 5
1. Specification of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-
22. Recovery and recycle equipment, pumps, hoses and the like need to have design
pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply
3
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be performed safely
with nitrogen or a mixture of R-410A and nitrogen.
2. Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-
22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R­410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils and R-410A
3. Evaporator Coil / TXV
The thermostatic expansion valve is specifically designed to operate with R-410A. DO NOT use an R-22 TXV. The existing evaporator must be replaced with the factory specified TXV evaporator specifically designed for R-410A.
4. Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
V. SAFETY INFORMATION
WARNING
!
USE ONLY WITH TYPE OF GAS APPROVED FOR THIS UNIT. REFER TO THE UNIT RATING PLATE.
4
VI. UNIT DIMENSIONS
FOR CLEARANCES SEE FIGURE 7.
IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIREC­TIONS TO ALLOW WATER TO DRAIN FROM THE CONDENSER SEC­TION AND CONDENSATE PAN.
FIGURE 1
BOTTOM VIEW
FIGURE 2
CABINET DIMENSIONS AND ACCESS LOCATIONS
I316
I281
5
FIGURE 3
CABINET DIMENSIONS AND ACCESS LOCATIONS
FIGURE 4
SUPPLY AND RETURN DIMENSIONS
I282
I288
6
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFI­CALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNEC­TIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
WARNING
!
ALWAYS INSTALL UNIT TO OPER­ATE WITHIN THE UNIT'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SEC­TION OF THESE INSTRUCTIONS. SEE ALSO UNIT RATING PLATE.
WARNING
!
WHEN A UNIT IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE UNIT TO AREAS OUTSIDE THE SPACE CON­TAINING THE UNIT, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE UNIT CASING AND TERMINATING OUT­SIDE THE SPACE CONTAINING THE UNIT.
VII.INSTALLATION
A. GENERAL
Install this unit in accordance with The American National Standard Z223.1-latest edition booklet entitled “National Fuel Gas Code,” and the requirements or codes of the local utility or other authority having jurisdiction.
Additional helpful publications available from the “National Fire Protection Association” are: NFPA-90A - Installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B - Warm Air Heating and Air Conditioning Systems 1984.
These publications are available from: National Fire Protection Association, Inc.
1 Batterymarch Park Quincy, MA 02169-7471 www.nfpa.org
1. PRE-INSTALLATION CHECK-POINTS — Before attempting any installation, care­fully consider the following points:
Structural strength of supporting members
(Rooftop Installation) Clearances and provision for servicing Power supply and wiring Gas supply and piping Air duct connections and sizing Drain facilities and connections Location for minimum noise and
vibration - away from bedroom
windows
2. LOCATION CONSIDERATIONS The metal parts of this unit may be subject to rust or deterioration in adverse envi-
ronmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petrole­um refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment location and exposure.
1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.
2. In coastal areas locate the unit on the side of the building away from the water­front.
3. Shielding by a fence or shrubs may give some protection.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULT ING IN PER­SONAL INJURY OR DEATH. REGULAR MAINTENANCE WILL REDUCE THE BUILDUP OF CONTAMINANTS AND HELP TO PROTECT THE UNIT’S FINISH.
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
2. Regular cleaning and waxing of the cabinet with a good automobile polish will pro­vide some protection.
3. A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be ver­ified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
7
WARNING
!
THIS UNIT MAY BE USED TO HEAT THE BUILDING OR STRUC­TURE DURING CONSTRUCTION IF THE FOLLOWING INSTALLATION REQUIREMENTS ARE MET. INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RAT­ING PLATE MARKING;
• MEANS OF PROVIDING OUT­DOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND 80°F (27°C); AND
• INSTALLATION OF EXHAUST AND COMBUSTION AIR INLET HOODS COMPLETED;
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUB­STANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPER­ATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEM­PERATURE RISE AND VENTING, ACCORDING TO THE INSTRUC­TIONS.
FIGURE 5
OUTSIDE SLAB INSTALLATION. CLOSET DISTRIBUTION SYSTEM. SLAB FLOOR CONSTRUCTION.
B. OUTSIDE SLAB INSTALLATION
WARNING
!
THESE UNITS ARE DESIGNED CERTIFIED FOR OUTDOOR INSTALLATION ONLY. INSTALLATION INSIDE ANY PART OF A STRUCTURE CAN RESULT IN INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE. INSTALLATION INSIDE CAN ALSO CAUSE RECIRCULATION OF FLUE PROD­UCTS INTO THE CONDITIONED SPACE RESULTING IN PERSONAL INJURY OR DEATH.
I298
(Typical outdoor slab installation is shown in Figure 5.)
1. Select a location where external water drainage cannot collect around unit.
2. Provide a level slab sufficiently high enough above grade to prevent surface water from entering the unit
3. The location of the unit should be such as to provide proper access for inspection and servicing as shown in Figure 7.
4. Locate unit where operating sounds will not disturb owner or neighbors.
5. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
6. Where snowfall is anticipated, the height of the unit above the ground level must be considered. Mount unit high enough to be above anticipated maximum area snowfall
and to allow combustion air to enter the combustion air inlet.
7. Select an area which will keep the areas of the vent, air intake, and A/C condenser
fins free and clear of obstructions such as weeds, shrubs, vines, snow, etc. Inform the user accordingly.
8. Remove compressor shipping supports (if so equipped) after installation.
8
C. ATTACHING EXHAUST AND COMBUSTION AIR INLET HOODS
IMPORTANT: Do not operate this unit without the exhaust/combustion air inlet hood properly installed. This hood is shipped in a carton in the blower compartment inside the unit and must be attached when the unit is installed. See Figure 3.
To attach exhaust/combustion air inlet hood:
1. Remove screws securing blower access panel and remove access panel. For location of blower access panel, see Figure 2.
2. Remove exhaust/combustion air inlet hood from the carton, located inside the blower compartment.
3. Attach blower access panel.
4. Attach the combustion air inlet/exhaust hood with screws. Reference Figure 3 for proper location. Screws are in carton with the hood.
5. Vent the unit using the flue exhaust hood, as supplied from the factory, without alteration or addition.
D. COVER PANEL INSTALLATION/CONVERSION PROCEDURE
DOWNFLOW TO HORIZONTAL
1. Remove the screws and covers from the outside of the supply and return sections.
2. Install the covers in the bottom supply and return openings with the painted side up. See Figure 6. Use the existing gasket to seal the covers.
3. Secure the supply cover to the base of the unit with 1 screw, engaging prepunched tab in unit base.
4. Secure the return cover to the base of the unit with screws engaging prepunched holes in the unit base.
This unit is provided with 2 - 25X 16X 1disposable filters. When replacing filters, ensure they are inserted fully to the back to prevent bypass.
Recommended
Clearance
48 A - Front 18 B - Condenser Coil 12* C - Duct Side 36 D - Evaporator End 60 E - Above
*Without Economizer. 57 With Economizer
Location
FIGURE 6
COVER GASKET DETAIL FOR UNITS SHIPPED FOR DOWNFLOW APPLICATION BEING CONVERTED TO HORIZONTAL
E. CLEARANCES
The following minimum clearances must be observed for proper unit performance and serviceability. Reference Figure 7.
NOTE: Supply duct may be installed with “0’ inch clearance to combustible materials, provided 1minimum Fiberglass insulation is applied either inside or on the outside of the duct.
I631
9
FIGURE 7
CLEARANCES
I297
F. ROOFTOP INSTALLATION
1. Before locating the unit on the roof, make sure that the roof structure is adequate to support the weight involved. (See Electrical & Physical Tables in this manual.) THIS
IS VERY IMPORTANT AND THE INSTALLER’S RESPONSIBILITY.
2. For rigging and roofcurb details, see Figures 8, 9, 10 and 11.
3. The location of the unit on the roof should be such as to provide proper access for inspection and servicing.
4. Remove compressor shipping supports (if so equipped) after installation.
IMPORTANT: If unit will not be put into service immediately, block off supply and return air openings to prevent excessive condensation.
G. DUCTWORK
The installing contractor should fabricate ductwork in accordance with local codes. Use industry manuals as a guide when sizing and designing the duct system. Contact Air Conditioning Contractors of America, 2800 Shirlington Road, Suite 300, Arlington, VA 22206, http://www.acca.org.
WARNING
!
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING DEVICE SUCH AS FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY, PROP­ERTY DAMAGE OR DEATH.
10
FIGURE 8
FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTING SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL.
I299
Place the unit as close to the conditioned space as possible allowing clearances as indi­cated. Run ducts as directly as possible to supply and return outlets. Use of non-flam­mable weatherproof flexible connectors on both supply and return connections at unit to reduce noise transmission is recommended.
On ductwork exposed to outside temperature and humidity, use a minimum of 2of insulation and a vapor barrier. Distribution system in attic, furred space or crawl space should be insulated with at least 2of insulation. cient for ductwork inside the air conditioned space.
Provide balancing dampers for each branch duct in the supply system. Properly support ductwork from the structure.
IMPORTANT: In the event that the return air ducts must be run through an “unconfined” space containing other fuel burning equipment, it is imperative that the user/homeowner must be informed against future changes in construction which might change this to a “confined space.” Also, caution the user/homeowner against any future installation of additional equipment (such as power ventilators, clothes dryers, etc., within the existing unconfined and/or confined space which might create a negative pressure within the vicinity of other solid, liquid, or gas fueled appliances.
1
2 to 1 thick insulation is usually suffi-
H. RETURN AIR
WARNING
!
NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTS TO ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED. ALL OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS AND SEALED AIRTIGHT.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCU­LATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
11
ROOFTOP UNI
COUNTER FLASHING*
GASKET
NAILER STRIP
DUCT*
INSULATION*
CANT STRIP*
ROOF FE INSULATI
ROOF DE
TURAL
RETURN DUCT*
SUPPLY DUCT*
NAILING STRIP
INSULATION PANELS (2) SUPPLIED
GASKET (FULL PERIMETER AND ON DIVIDERS, MUST BE ABOVE DUCT AND INSULATION PANEL FLANGES.)
HOLD DOWN BRACKET TYP. (4) PLCS.
UNIT
FIGURE 9
LIFTING DETAIL
B
FIGURE 10
ROOFCURB
SPREADER BAR
A
38.25
5/8SHACKLE
(EACH CORNER)
CORNER WEIGHTS BY PERCENTAGE
ABCD
22% 27% 23% 28%
LIFTING BEAM
CABLE OR CHAIN
C.G.
25.75
C
D
I296
FIGURE 11
ROOFCURB
ROOFTOP UNIT
SUPPLY
RETURN
ST-A0801-19-01
GASKET
NAILER STRIP
DUCT*
ROOFCURB
ROOF STRUCTURAL MEMBER*
*BY CONTRACTOR
COUNTER FLASHING*
INSULATION*
CANT STRIP*
ROOF FELT*
INSULATION*
ROOF DECK*
ST-A0801-19-01
12
VIII. GAS SUPPLY, CONDENSATE DRAIN AND
VIII. PIPING
A. GAS CONNECTION
IMPORTANT: Connect this unit only to gas supplied by a commercial utility.
1. Install gas piping in accordance with local codes and regulations of the local utility company. In the absence of local codes, the installation must conform to the specifi­cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.
NOTE: The use of flexible gas connectors is not permitted. If local codes allow the use of a corrugated stainless steel flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.
NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be a T-handle gas cock.
2. Connect the gas line to the gas pipe inlet opening provided into the 1/2inlet valve. See Figure 5 or 8 for typical piping.
3. Size the gas line to the furnace adequate enough to prevent undue pressure drop and never less than 1/2nominal pipe size.
4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possi­ble.
5. Install an outside ground joint union to connect the gas supply to the control assem­bly at the burner tray.
6. Gas valves have been factory installed. Install a manual gas valve where local codes specify a shut-off valve outside the unit casing. (See Figure 12.)
7. Make sure piping is tight. A pipe compound resistant to the action of liquefied
petroleum gases must be used at all threaded pipe connections.
8. IMPORTANT: any additions, changes or conversions required for the furnace to sat­isfactorily meet the application should be made by a qualified installer, service agency or the gas supplier, using factory-specified or approved parts. In the com­monwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
IMPORTANT: Disconnect the furnace and its individual shutoff valve from the gas sup­ply piping during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch gauge or isolate the system from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of this gas sup­ply system at pressures equal to or less than 1/2 PSIG.
TO CHECK FOR GAS LEAKS, USE A SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD. DO NOT USE AN OPEN FLAME.
FIGURE 12
SUGGESTED GAS PIPING
ROOF OR GROUND LEVEL INSTALLATION
FROM GAS METER
MANUAL GAS SHUT-OFF VALVE
Factory supplied grommet must be utilized.
*
UNIT GAS SUPPLY CONNECTION
WARNING
!
CHECK FOR LEAKS. THE USE OF AN OPEN FLAME CAN RESULT IN FIRE, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
IMPORTANT: Check the rating plate to make certain the appliance is equipped to burn the type of gas supplied. Care should be taken after installation of this equipment that the gas control valve not be subjected to high gas supply line pressure.
TABLE 1
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Nominal
Iron Pipe
*
Size,
Inches
1
2 132 92 73 63 56 50 46 43
3
4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 11⁄4 1,050 730 590 500 440 400 370 350 11⁄2 1,600 1,100 890 760 670 610 560 530
10 20 30 40 50 60 70 80
Equivalent Length of Pipe, Feet
13
In making gas connections, avoid strains as they may cause noise and damage the con­trols. A backup wrench is required to be used on the valve to avoid damage.
The capacities of gas pipe of different diameters and lengths in cu. ft. per hr. with pres­sure drop of 0.3 in. and specific gravity of 0.60 (natural gas) are shown in Table 1.
After determining the pipe length, select the pipe size which will provide the minimum cubic feet per hour re quired for the gas input rating of the furnace. By formula:
Gas Input of Furnace
Cu. Ft. Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT
(BTU/HR) Heating Value of Gas
3
(BTU/FT
3
) may be determined by consulting the local natural gas utility or the
)
L.P. gas supplier.
B. LP CONVERSION
WARNING
!
FACTORY FOR USE ON NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES A SPECIAL KIT SUPPLIED BY THE DISTRIBUTOR OR MANUFACTUR­ER. MAILING ADDRESSES ARE LISTED ON THE FURNACE RATING PLATE, PARTS LIST AND WARRANTY. FAILURE TO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSON­AL INJURY, PROPERTY DAMAGE OR DEATH.
Convert the valve to use liquefied petroleum (LP) gas by replacing the pressure regulator spring with the conversion kit spring. This LP kit spring allows the regulator to maintain the proper manifold pressure for LP gas. The correct burner LP orifices are included in the kit. See Figure 13.
IMPORTANT: To remove the gas valve, remove the four screws securing the manifold pipe to the burner tray. Remove the manifold pipe with gas valve attached. See Figure 14.
NOTE: Order the correct LP conversion kit from the furnace manufacturer. See Conversion Kit Index shipped with unit for proper LP kit number. Furnace conver­sion to LP gas must be performed by a qualified technician.
C. NOx MODELS
When converting units equipped with NOx inserts to LP gas, the stainless steel screen mesh inserts in the entrance of the tubular exchangers are not required to meet SCAQMD NOx emission levels. These inserts and 1/8diameter retaining rod should be carefully removed before firing this furnace on LP gas. IMPORTANT: This furnace is not designed to operate on LP gas with the NOx inserts in place.
Step by step instructions on removing the NOx inserts and retaining rod are included in the Conversion Kit Installation Instructions.
TABLE 2
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal Iron Pipe Size, Inches
1/2 3/4
1-1/4 1-1/2
Example (LP): Input BTU requirement of unit, 150,000
10 20 30 40 50 60 70 80 90 100 125 150
275 189 152 129 114 103 96 89 83 78 69 63 567 393 315 267 237 217 196 182 173 162 146 132
1,071 732 590 504 448 409 378 346 322 307 275 252
1
2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
2
Equivalent length of pipe, 60 ft. = 3/4IPS required.
Length of Pipe, Feet
14
FIGURE 13
FIGURE 14
MANIFOLD PIPE
D. ADJUSTING OR CHECKING FURNACE INPUT
– Natural Gas Line Pressure 5- 10.5W.C. – LP Gas Line Pressure 11- 13W.C.
– Natural Gas Manifold Pressure 3.5 W.C – LP Gas Manifold Pressure - 10W.C.
Supply and manifold pressure taps are located on the gas valve body 1/8N.P.T. and on the manifold.
Use a properly calibrated manometer gauge for accurate gas pressure readings. Only small variations in the gas flow should be made by means of the pressure regulator
adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10W.C. at the gas con­trol valve.
To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace
the regulator cap securely.
Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices. To change orifice spuds, shut off the manual main gas valve and remove the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings apply. For high altitudes (elevations over 2,000 ft.), see conversion kit index 92-21519-XX for derating and orifice spud sizes.
Check of input is important to prevent over-firing of the furnace beyond its design­rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate.
Heating Value of Gas
Cu. Ft. Per Hr. Required =
Start the furnace and measure the time required to burn one cubic foot of gas. Prior to checking the furnace input, make certain that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS): The main burner orifices in your furnace and in these kits are sized for the nameplate input and intended for installations at elevations up to 2,000 feet in the USA or Canada, or for ele­vations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated at the factory. For elevations above 2,000 feet (610 meters) IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1,000 feet (305 meters) above sea level.
(BTU/Cu. Ft.) x 3600 Time in Seconds
(for 1 Cu. Ft.) of Gas
15
TABLE 3
INPUT
BTU/HR
40,000
60,000
80,000
100,000
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
METER
SIZE
CU. FT.
ONE 1 21 1 30 1 34 1 39 3 45
ONE 0 54 101316230
ONE 0 41 0 45 0 47 0 50 1 53
ONE 0 33 0 36 0 38 0 40 1 30
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
TEN 13 30 15 0 15 36 16 30 37 30
TEN 9010 0 10 24 11 0 25 0
TEN 6 45 7 30 7 48 8 15 18 45
TEN 5 24 60615 6 36 15 0
OR LP GAS
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
NOTICE: DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD IS UNLAWFUL IN CANADA (REFER TO CAN/CGA 2.17). UNITS INSTALLED IN ALTITUDES GREATER THAN 2,000 FEET (610 METERS) MUST BE SHIPPED FROM THE FACTORY OR FROM A FACTORY AUTHORIZED CONVERSION STATION WITH THE HEATING INPUT DERATED BY 10% SO AS TO OPERATE PROPERLY IN ALTITUDES FROM 2,000 - 4,500 FEET (610 - 1,373 METERS).
E.CONDENSATE DRAIN
The condensate drain connection of the evaporator is threaded 3/4nominal P.V.C. pipe. IMPORTANT: Install a condensate trap to ensure proper condensate drainage. See Figure 15.
FIGURE 15 CONDENSATE DRAIN
DO NOT OVERTIGHTEN DRAIN FITTING
IX. WIRING
A. POWER SUPPLY
WARNING
!
TURN OFF THE MAIN ELECTRICAL POWER AT THE BRANCH CIRCUIT DIS­CONNECT CLOSEST TO THE UNIT BEFORE ATTEMPTING ANY WIRING. FAIL­URE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
1. All wiring should be made in accordance with the National Electrical Code. Consult the local power company to determine the availability of sufficient power to operate the unit. Check the voltage at power supply to make sure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT. Install a branch circuit disconnect near the rooftop, in accordance with the N.E.C., C.E.C. or local codes. A bracket is provided with the unit for mounting of the disconnect. See Figure 16.
2. It is important that proper electrical power is available at the unit. Voltage should not vary more than 10% from that stamped on the unit nameplate. On three phase units, phases must be balanced within 3%.
3. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined from Table 3 using the circuit ampacity found on the unit rating plate. Use the smallest wire size allowable in Table 4 from the unit dis­connect to unit.
NOTE: A bracket is provided with the unit for mounting the branch circuit disconnect to the unit. This is the recommended location for the disconnect. See Figure 16.
4. For through the base wiring entry reference Figure 17.All fittings and conduit are field supplied for this application. Reference the chart with Figure 17for proper hole and conduit size.
16
FIGURE 16
RECOMMENDED BRANCH CIRCUIT DISCONNECT LOCATION
TABLE 4
BRANCH CIRCUIT COPPER WIRE SIZE (Based on 1% Voltage Drop)*
BRANCH CIRCUIT DISCONNECT
MOUNTING SHOWN
FOR 4 & 5 TON
MOUNTING FOR 3-TON
200 64443322 150 86644433 100 10 8866644
50 14 12 10 10 8866
15 20 25 30 35 40 45 50
BRANCH CIRCUIT AMPACITY
SUPPLY WIRE
LENGTH-FEET
*Taken from National Electric Code
TO POWER
TO THERMOSTAT
I317A
NOTES:
1. Wire size based on 60°C rated wire insulation and 30°C Ambient Temp. (86°F).
2. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.
When installed, the unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70, if an external electrical source is utilized.
IMPORTANT: THIS UNIT IS AP PROVED FOR USE WITH COPPER CONDUCTORS
CONNECTED TO UNIT CONTACTOR.
ONLY WARRANTY MAY BE JEOPARDIZED IF ALUMINUM WIRE IS CONNECTED TO
UNIT CONTACTOR. Special instructions apply for power wiring with aluminum conductors: Warranty
is void if connections are not made per instructions.
Attach a length (6or more) of recommended size copper wire to the unit contactor ter­minals L1 and L3 for single phase, L1, L2 and L3 for three phase.
Select the equivalent aluminum wire size from the tabulation below: Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for copper-
aluminum splices. Please exercise the following instructions very carefully to obtain a positive and lasting connection:
1. Strip insulation from aluminum conductor.
2. Coat the stripped end of the aluminum wire with the recommended inhibitor, and wire brush the aluminum surface through inhibitor. INHIBITORS: Brundy-Pentex “A”; Alcoa-No. 2EJC; T & B-KPOR Shield.
3. Clean and recoat aluminum conductor with inhibitor.
4. Make the splice using the above listed wire nuts or split bolt connectors.
5. Coat the entire connection with inhibitor and wrap with electrical insulating tape.
TABLE 5
AWG Copper AWG Aluminum Connector Type and Size
Wire Size Wire Size (or equivalent)
#12 #10 T & B Wire Nut PT2 #10 # 8 T & B Wire Nut PT3 # 8 # 6 Sherman Split Bolt TSP6 # 6 # 4 Sherman Split Bolt TSP4 # 4 # 2 Sherman Split Bolt TSP2
17
FIGURE 17
FIGURE 18
TYPICAL THERMOSTAT WIRING
I658
WIRE SIZE, AWG
14
CONDUIT SIZE
HOLE SIZE
NOTES: 1. DETERMINE REQUIRED WIRE SIZE FROM MINIMUM CIRCUIT AMPACITY SHOWN IN INSTALLATION & OPERATING INSTRUCTION.
2. BOTTOM POWER ENTRY WILL NOT ACCOMMODATE WIRE LARGER THAN #2 AWG (SHADED AREA).
1/2 7/8
12
1/2 7/8
10
1/2 7/8
8
3/4
1-31/32
6
1
1-23/64
4
1
1-23/64
3
1-1/4
1-23/32
2
1-1/4
1-23/32
1
1-1/2
1-31/32
0
1-1/2
1-31/32
2-15/32
00
2
000
2
2-15/32
B. HOOK-UP
To wire unit, refer to the following hook-up diagram. Refer to Figures 3 and 17 for location of wiring entrances. Wiring to be done in the field between the unit and devices not attached to the unit, or
between separate devices which are field installed and located, shall conform with the temperature limitation for Type T wire [63°F rise (35°C)] when installed in accordance with the manufacturer’s instructions.
C. INTERNAL WIRING
IMPORTANT: Some single phase units are equipped with a single pole contactor. Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor.
Some models are equipped with electronically commutated blower motors which are constantly energized, unless the main unit disconnect is in the off position.
A diagram of the internal wiring of this unit is located under the electrical box cover and this manual. If any of the original wire as supplied with the appliance must be replaced, the wire gauge and insulation must be same as original wiring.
Transformer is factory wired for 230 volts on 208/230 volt models and must be changed for 208 volt applications. See unit wiring diagram for 208 volt wiring.
D. THERMOSTAT
The room thermostat must be compatible with the spark ignition control on the unit. Generally, all thermostats that are not of the “current robbing” type are compatible with the integrated furnace control. The low voltage wiring should be sized as shown in Table
6. Install the room thermostat in accordance with the instruction sheet packed in the box
with the thermostat. Run the thermostat lead wires inside the compressor access panel compartment and connect to low voltage terminals as shown on the wiring diagram. Never install the thermostat on an outside wall or where it will be influenced by drafts, concealed hot or cold water pipes or ducts, lighting fixtures, radiation from fireplace, sun
18
TABLE 6
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.
3.0 16 14 12 10 10 10
2.5 16 14 12 12 12 10
2.0 18 16 14 12 12 10
Amps
Thermostat Load -
(1) The total wire length is the distance from the furnace to the thermo­stat and back to the furnace.
NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18 AWG.
50 100 150 200 250 300
Length of Run – Feet (1)
rays, lamps, televisions, radios or air streams from registers. Refer to instructions packed with the thermostat for “heater” selection or adjustment.
The following are the recommended thermostats available through the manufacturer to be used:
W/O Economizer W/Economizer
(-)HC-TST101GESS (-)HC-TST103UNMS
(-)HC-TST103UNMS (-)HC-TST203UNMS
(-)HC-TST201GESS (-)HC-TST302UNMS
(-)HC-TST203UNMS (-)HC-TST303UNMS
(-)HC-TST301GESS (-)HC-TST304UNMS (-)HC-TST302UNMS (-)HC-TST303UNMS
(-)HC-TST304UNMS
X. FURNACE SECTION CONTROLS AND
IGNITION SYSTEM
NORMAL FURNACE OPERATING SEQUENCE
This unit is equipped with an integrated direct spark ignition control.
1. The thermostat calls for heat.
2. The control board will run a self check to verify that the limit control and manual reset overtemperature control are closed and that the pressure switch is open.
3. Upon closure of the pressure switch, the control board energizes the induced draft blower for a 15 second prepurge.
4. After the 15 second prepurge, the gas valve opens and the spark is initiated for 7 sec­ond trial for ignition.
5. Burners ignite and flame sensor proves all burners have lit.
6. The circulating air blower is energized after 30 seconds.
7. The control board enters a normal operation loop in which all safety controls are moni­tored continuously.
8. Thermostat is satisfied and opens.
9. The gas valve is de-energized and closes, shutting down the burner flame.
10. The control board will de-energize the inducer after a five second post purge.
11. The circulating air blower is de-energized after 90 seconds. The integrated control is a three ignition system. After a total of three cycles without sensing main burner flame, the system goes into a
100% lockout mode. After one hour, the ignition control repeats the prepurge and ignition cycles for 3 tries and then go into 100% lockout mode again. It continues this sequence of cycles and lockout each hour until ignition is successful or power is interrupted. During the lockout mode, neither the ignitor or gas valve will be energized until the system is reset by turning the thermostat to the “OFF” position or interrupting the electrical power to the unit for 3 seconds or longer. The induced draft blower and main burner will shut off when the thermostat is satisfied.
The circulating air blower will start and run on the heating speed if the thermostat fan switch is in the “ON” position.
The integrated furnace control is equipped with diagnostic LED. The LED is lit continuously when there is power to the control, with or without a call for heat. If the LED is not lit, there
19
is either no power to the control or there is an internal component failure within the control, and the control should be replaced.
If the control detects the following failures, the LED will flash on for approximately 1/4 sec­ond, then off for 3/4 second for designated failure detections.
1 Flash: Failed to detect flame within the three tries for ignition. 2 Flash: Pressure switch or induced draft blower problem detected. 3 Flash: High limit or auxiliary limit open. 4 Flash: Flame sensed and gas valve not energized or flame sensed with no “W” signal. 5 Flash: Overtemperature switch open.
OPERATING INSTRUCTIONS
This appliance is equipped with integrated furnace control. This device lights the main burners each time the room thermostat (closes) calls for heat. See operating instructions on the back of the furnace/controls access panel.
WARNING
!
DO NOT ATTEMPT TO MANUALLY LIGHT THIS FURNACE WITH A MATCH OR ANY OPEN FLAME. ATTEMPTING TO DO SO CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TO START THE FURNACE
1. STOP! Read the safety information on the Operating Instructions label located on this appliance.
WARNING
!
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
2. Set the thermostat to its lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance does not have a pilot. It is equipped with an ignition device which auto­matically lights the burner. Do NOT
5. Remove control door/access panel.
6. Move switch to the “OFF” position.
7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP!
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas suppli­er’s instructions.
• If you cannot reach your gas supplier, call the fire department.
If you don’t smell gas, go to the next step.
8. Move “OFF” position to “ON” position.
9. Replace the control door.
10. Turn on all electric power to the appliance.
11. Set the thermostat to the desired setting.
12. If the appliance will not operate, follow the instructions below on how to shut down the furnace.
WARNING
!
THE SPARK IGNITOR AND IGNITION LEAD FROM THE IGNITION CONTROL ARE HIGH VOLTAGE. KEEP HANDS OR TOOLS AWAY TO PREVENT ELECTRICAL SHOCK. SHUT OFF ELECTRICAL POWER BEFORE SERVICING ANY OF THE CONTROLS. FAILURE TO ADHERE TO THIS WARNING CAN RESULT IN PER­SONAL INJURY OR DEATH.
try to light the burner by hand.
20
The initial start-up on a new installation may require the control system to be energized for some time until air has bled through the system and fuel gas is available at the burners.
TO SHUT DOWN FURNACE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control door.
4. Move switch to the “OFF” position.
5. Replace control door.
WARNING
!
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, SHUT OFF THE MANUAL GAS VALVE TO THE APPLIANCE BEFORE SHUTTING OFF THE ELECTRICAL SUPPLY. FAILURE TO DO SO CAN RESULT IN AN EXPLOSION OR FIRE CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH!
BURNERS
Burners for these units have been designed so that field adjustment is not required. Burners are tray-mounted and accessible for easy cleaning when required.
MANUAL RESET OVERTEMPERATURE CONTROL
Two manual reset overtemperature controls (one on 80,000 BTUH) are located on the burner shield. These devices senses blockage in the heat exchanger or insufficient com­bustion air. This shuts off the main burners if excessive temperatures occur in the burner compartment.
Operation of this control indicates an abnormal condition. Therefore, the unit should be examined by a qualified installer, service agency, or the gas supplier before being placed back into operation.
WARNING
!
DO NOT JUMPER THIS DEVICE! DO NOT reset the over temperature control with­out taking corrective action to assure that an adequate supply of combustion air is maintained under all conditions of operation. Failure to do so can result in carbon monoxide poisoning or death. Replace this control only with the identi­cal replacement part.
PRESSURE SWITCH
This furnace has a pressure switch for sensing a blocked exhaust or a failed induced draft blower. It is normally open and closes when the induced draft blower starts, indicating air flow through the combustion chamber.
LIMIT CONTROL
The supply air high temperature limit cut-off is set at the factory and cannot be adjusted. It is calibrated to prevent the air temperature leaving the furnace from exceeding the maxi­mum outlet air temperature.
WARNING
!
DO NOT JUMPER THIS DEVICE! DOING SO CAN CAUSE A FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
IMPORTANT: Replace this control only with the identical replacement part.
XI. SYSTEM OPERATING INFORMATION
ADVISE THE CUSTOMER
1. Change the air filters regularly. The heating system operates better, more efficiently and more economically.
2. Arrange the furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
3. Close doors and windows. This reduces the heating and cooling load on the system.
4. Avoid excessive use of exhaust fans.
5. Do not permit the heat generated by television, lamps or radios to influence the ther­mostat operation.
6. Except for the mounting platform, keep all combustible articles three feet from the unit and exhaust system.
21
7. IMPORTANT: Replace all blower doors and compartment cover after servicing the
unit. Do not operate the unit without all panels and doors securely in place.
8. Do not allow snow or other debris to accumulate in the vicinity of the appliance.
FURNACE SECTION MAINTENANCE
The unit’s furnace should operate for many years without excessive scale build-up in flue passageways; however, it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the exhaust system and the burners for continued safe operation, paying particular attention to deterioration from corrosion or other sources.
If during inspection the flue passageways and exhaust system are determined to require cleaning, the following procedures should be followed (by a qualified installer, service
agency, or gas supplier):
1. Turn off the electrical power to the unit and set the thermostat to the lowest tem­perature.
2. Shut off the gas supply to the unit either at the meter or at manual valve in the supply piping.
WARNING
!
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
3. Remove the furnace controls access panel and the control box cover.
4. Disconnect the gas supply piping from the gas valve.
5. Disconnect the wiring to the induced draft blower motor, gas valve, flame sensor, and flame roll-out control, and ignitor cable. Mark all wires disconnected for proper reconnection.
6. Remove the screws (4) connecting the burner tray to the heat exchanger mounting panel.
7. Remove the burner tray and the manifold assembly from the unit.
8. Remove the screws (5) connecting the induced draft blower to the collector box and screws (18) connecting the collector box to the heat exchanger center panel. Remove the induced draft blower and the collector box from the unit.
9. Remove the screws (3) connecting the divider plate to the heat exchanger center panel.
10. Remove the turbulators from inside the heat exchangers by inserting the blade of a screwdriver under the locking tabs. Pop the tabs out of the expanded grooves of the heat exchanger. Slide the turbulators out of the heat exchangers.
11. Direct a water hose into the outlet of the heat exchanger top. Flush the inside of each heat exchanger tube with water. Blow out each tube with air to remove excessive moisture.
12. Reassemble (steps 1 through 10 in reverse order). Be careful not to strip out the
screw holes used to mount the collector box and inducer blower. Replace induc­er blower gasket and collector box gasket with factory replacements if dam­aged.
22
WARNING
!
HOLES IN THE EXHAUST TRANSITION OR HEAT EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME. THE EXHAUST TRANSITION OR HEAT EXCHANGER MUST BE REPLACED IF THEY HAVE HOLES OR CRACKS IN THEM. FAILURE TO DO SO CAN CAUSE CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
The manufacturer recommends that a qualified installer, service agency or the gas suppli­er visually inspect the burner flames for the desired flame appearance at the beginning of the heating season and approximately midway in heating season.
The manufacturer also recommends that a qualified installer, service agency or the gas supplier clean the flame sensor with steel wool at the beginning of the heating season.
WARNING
!
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPT­ING MAINTENANCE. FAILURE TO DO SO MAY RESULT IN ELECTRICAL SHOCK OR SEVERE PERSONAL INJURY OR DEATH.
LUBRICATION
IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the warranty.
The blower motor and induced draft blower motor are prelubricated by the manufacturer and do not require further attention.
A qualified installer, service agency or the gas supplier must periodically clean the motors to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. And, as suggested elsewhere in these instruc­tions, the air filters should be kept clean because dirty filters can restrict air flow and the motor depends upon sufficient air flowing across and through it to prevent overheating.
COOLING SECTION MAINTENANCE
WARNING
!
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPT­ING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
It is recommended that at the beginning of each cooling season a qualified installer or service agency inspect and clean the cooling section of this unit. The following areas should be addressed: evaporator coil. condenser coil, condenser fan motor and venturi area.
To inspect the evaporator coil:
1. Remove the filter access panel and the blower/evaporator coil access panel. Remove the filters.
WARNING
!
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE UNIT. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
2. Shine a flashlight on the evaporator coil (both sides) and inspect for accumulation of lint, insulation, etc.
3. If coil requires cleaning, follow the steps shown below.
Cleaning Evaporator Coil
1. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
2. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solu­tion. Rinse the coil thoroughly with water. IMPORTANT: Do not pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
3. Inspect the drain pan and condensate drain at the same time the evaporator coil is checked. Clean the drain pan by flushing with water and removing any matters of obstructions which may be present.
4. Go to next section for cleaning the condenser coil.
Cleaning Condenser Coil, Condenser Fan, Circulation Air Blower and Venturi
1. Remove the compressor access panel. Disconnect the wires to the condenser fan motor in the control box (see wiring diagram). Remove the wires from the opening in the bottom of the control box.
2. Remove the screws securing the condenser top panel and remove the panel with condenser fan motor and grille attached.
3. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
4. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solu-
use excessive water
23
tion. Rinse the coil thoroughly with water. IMPORTANT: Do not pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
5. The venturi should also be inspected for items of obstruction such as collections of grass, dirt or spider webs. Remove any that are present.
6. Inspect the circulating air blower wheel and motor for accumulation of lint, dirt or other obstruction and clean it necessary. Inspect the blower motor mounts and the blower housing for loose mounts or other damage. Repair or replace if necessary.
Re-assembly
1. Place the condenser top panel back on the unit and replace all screws.
2. Run the fan motor wires through the hole in the bottom of the control box. Reconnect fan motor wires per the wiring diagram attached to the back of the cover.
3. Replace the filter and blower/evaporator coil access panels.
4. Replace the control box cover and controls access panel.
5. Restore electrical power to the unit and check for proper operation, especially the condenser fan motor.
use excessive water
REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
TROUBLESHOOTING
Refer to Troubleshooting Chart included in this manual.
WIRING DIAGRAMS
Refer to the appropriate wiring diagram included in this manual.
CHARGING
Refer to the appropriate charge chart included in this manual.
BLOWER MOTOR SPEED TAPS
After determining necessary CFM and speed tap data from the Airflow Performance Data, follow the steps below to change speeds.
1. Remove the blower access panel.
2. Reference Figure 19 for location of the speed tap block on the blower.
3. Remove the furnace control access panel.
4. Remove the control box cover. See Figure 20 for location of the integrated furnace control board.
5. Reference Figure 21 for the proper location of the red and black wires on the speed tap block and on the furnace integrated control board to obtain the speed tap you have chosen.
6. After adjusting the wires accordingly, attach the control box cover, furnace control access panel and the blower access panel to the unit.
24
FIGURE 19
SPEED TAP BLOCK
FIGURE 21
INTEGRATED FURNACE CONTROL
FIGURE 20
25
FIGURE 21 (Continued)
26
XII. GENERAL DATA - RKNN MODELS
!"#$%&%'(%&)
Model RKNN- Series A036CK08 A036CK12 A036CL08 A036CL12
Cooling Performance
1
Continued ->
Gross Cooling Capacity Btu [kW] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61]
EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13
Nominal CFM/AHRI Rated CFM [L/s] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] AHRI Net Cooling Capacity Btu [kW] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] Net Sensible Capacity Btu [kW] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] Net Latent Capacity Btu [kW] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] Net System Power kW 2.93 2.93 2.93 2.93
Heating Performance (Gas)
4
Heating Input Btu [kW] 80,000 [23.44] 120,000 [35.16] 80,000 [23.44] 120,000 [35.16] Heating Output Btu [kW] 64,800 [18.99] 97,200 [28.48] 64,800 [18.99] 97,200 [28.48] Temperature Rise Range ºF [ºC] 30-60 [16.7-33.3] 50-80 [27.8-44.4] 30-60 [16.7-33.3] 50-80 [27.8-44.4] AFUE % 80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 4 6 4 6 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 0.7 [18] 0.7 [18] 0.7 [18] 0.7 [18] Face Area sq. ft. [sq. m] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] Rows / FPI [FPcm] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 1 [25] 1 [25] 1 [25] 1 [25] Face Area sq. ft. [sq. m] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3680 [1737] 3680 [1737] 3680 [1737] 3680 [1737] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] Drive Type Direct Direct Belt (Adjustable) Belt (Adjustable) No. Speeds Multiple Multiple Single Single No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1075 1075 1725 1725 Motor Frame Size 48 48 48 48 Filter - Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
Refrigerant Charge Oz. [g] 54 [1531] 54 [1531] 54 [1531] 54 [1531] Weights
Net Weight lbs. [kg] 507 [230] 517 [235] 525 [238] 517 [235] Ship Weight lbs. [kg] 514 [233] 525 [238] 532 [241] 525 [238]
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Continued ->
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci­ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
27
GENERAL DATA - RKNN MODELS
!"#$%*%'(%&)
Model RKNN- Series A036CM08 A036CM12 A036DK08 A036DK12
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61]
EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13
Nominal CFM/AHRI Rated CFM [L/s] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] AHRI Net Cooling Capacity Btu [kW] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] Net Sensible Capacity Btu [kW] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] Net Latent Capacity Btu [kW] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] Net System Power kW 2.93 2.93 2.93 2.93
Heating Performance (Gas)
4
Heating Input Btu [kW] 80,000 [23.44] 120,000 [35.16] 80,000 [23.44] 120,000 [35.16] Heating Output Btu [kW] 64,800 [18.99] 97,200 [28.48] 64,800 [18.99] 97,200 [28.48] Temperature Rise Range ºF [ºC] 30-60 [16.7-33.3] 50-80 [27.8-44.4] 30-60 [16.7-33.3] 50-80 [27.8-44.4] AFUE % 80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 4 6 4 6 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 0.7 [18] 0.7 [18] 0.7 [18] 0.7 [18] Face Area sq. ft. [sq. m] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] Rows / FPI [FPcm] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 1 [25] 1 [25] 1 [25] 1 [25] Face Area sq. ft. [sq. m] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3680 [1737] 3680 [1737] 3680 [1737] 3680 [1737] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] Drive Type Belt (Adjustable) Belt (Adjustable) Direct Direct No. Speeds Single Single Multiple Multiple No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1725 1725 1075 1075 Motor Frame Size 48 48 48 48 Filter - Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
Refrigerant Charge Oz. [g] 54 [1531] 54 [1531] 54 [1531] 54 [1531] Weights
Net Weight lbs. [kg] 525 [238] 517 [235] 507 [230] 517 [235] Ship Weight lbs. [kg] 532 [241] 525 [238] 514 [233] 525 [238]
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Continued ->
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci­ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
28
GENERAL DATA - RKNN MODELS
!"#$%+%'(%&)
Model RKNN- Series A036DL08 A036DL12 A036DM08 A036DM12
Cooling Performance
1
Continued ->
Gross Cooling Capacity Btu [kW] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61]
EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13
Nominal CFM/AHRI Rated CFM [L/s] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] AHRI Net Cooling Capacity Btu [kW] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] Net Sensible Capacity Btu [kW] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] Net Latent Capacity Btu [kW] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] Net System Power kW 2.93 2.93 2.93 2.93
Heating Performance (Gas)
4
Heating Input Btu [kW] 80,000 [23.44] 120,000 [35.16] 80,000 [23.44] 120,000 [35.16] Heating Output Btu [kW] 64,800 [18.99] 97,200 [28.48] 64,800 [18.99] 97,200 [28.48] Temperature Rise Range ºF [ºC] 30-60 [16.7-33.3] 50-80 [27.8-44.4] 30-60 [16.7-33.3] 50-80 [27.8-44.4] AFUE % 80 80 80 80 Steady State Efficiency (%) 81 81 81 81 No. Burners 4 6 4 6 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 0.7 [18] 0.7 [18] 0.7 [18] 0.7 [18] Face Area sq. ft. [sq. m] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] Rows / FPI [FPcm] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 1 [25] 1 [25] 1 [25] 1 [25] Face Area sq. ft. [sq. m] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3680 [1737] 3680 [1737] 3680 [1737] 3680 [1737] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] Drive Type Belt (Adjustable) Belt (Adjustable) Belt (Adjustable) Belt (Adjustable) No. Speeds Single Single Single Single No. Motors 1 1 1 1 Motor HP 1/2 1/2 1/2 1/2 Motor RPM 1725 1725 1725 1725 Motor Frame Size 48 48 48 48 Filter - Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
Refrigerant Charge Oz. [g] 54 [1531] 54 [1531] 54 [1531] 54 [1531] Weights
Net Weight lbs. [kg] 525 [238] 517 [235] 525 [238] 517 [235] Ship Weight lbs. [kg] 532 [241] 525 [238] 532 [241] 525 [238]
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Continued ->
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci­ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
29
GENERAL DATA - RKNN MODELS
!"#$%)%'(%&)
Model RKNN- Series A036JK08 A036JK12 A036YL12 A036YM12
Cooling Performance
1
Continued ->
Gross Cooling Capacity Btu [kW] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61] 36,200 [10.61]
EER/SEER
2
11.5/13 11.5/13 11.5/13 11.5/13
Nominal CFM/AHRI Rated CFM [L/s] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] 1200/1250 [566/590] AHRI Net Cooling Capacity Btu [kW] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] 34,600 [10.14] Net Sensible Capacity Btu [kW] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] 25,300 [7.41] Net Latent Capacity Btu [kW] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] 9,300 [2.72] Net System Power kW 2.93 2.93 2.93 2.93
Heating Performance (Gas)
4
Heating Input Btu [kW] 80,000 [23.44] 120,000 [35.16] 120,000 [35.16] 120,000 [35.16] Heating Output Btu [kW] 64,000 [18.17] 96,000 [27.54] 97,200 [28.48] 97,200 [28.48] Temperature Rise Range ºF [ºC] 30-60 [16.7-33.3] 50-80 [27.8-44.4] 50-80 [27.8-44.4] 50-80 [27.8-44.4] AFUE % 80 80 80 80 Steady State Efficiency (%) 80 80 81 81 No. Burners 4 6 6 6 No. Stages 1 1 1 1 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
78 78 78 78
Outdoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 0.7 [18] 0.7 [18] 0.7 [18] 0.7 [18] Face Area sq. ft. [sq. m] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] 13.9 [1.29] Rows / FPI [FPcm] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] 1 / 23 [9] Indoor Coil - Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel MicroChannel Depth in. [mm] 1 [25] 1 [25] 1 [25] 1 [25] Face Area sq. ft. [sq. m] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] 4.8 [0.45] Rows / FPI [FPcm] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] 1 / 20 [8] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] 1/0.75 [19.05] Outdoor Fan - Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 3680 [1737] 3680 [1737] 3680 [1737] 3680 [1737] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] 1/10x10 [254x254] Drive Type Direct Direct Belt (Adjustable) Belt (Adjustable) No. Speeds Multiple Multiple Single Single No. Motors 1 1 1 1 Motor HP 1/2 1/2 3/4 3/4 Motor RPM 1075 1075 1725 1725 Motor Frame Size 48 48 56 56 Filter - Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
(1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635] (1)1x16x25 [25x406x635]
Refrigerant Charge Oz. [g] 54 [1531] 54 [1531] 54 [1531] 54 [1531] Weights
Net Weight lbs. [kg] 507 [230] 517 [235] 517 [235] 517 [235] Ship Weight lbs. [kg] 514 [233] 525 [238] 525 [238] 525 [238]
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Continued ->
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci­ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
30
Loading...
+ 78 hidden pages