Rheem RKNL-B090CL22E, RKNL-B073CM15E, RKNL-B090CM22E, RKNL-B090CM15E, RKNL-B090CN22E User Manual

...
FORM NO. R11-855 REV. 1
Air
Package Gas Electric
RKNL-B Series
RKNL-B Series
Rheem Commercial Classic®Series Package Gas Electric Unit
Nominal Sizes 6-12.5 Tons [21.1-44.0 kW] ASHRAE 90.1-2010 Compliant Models
Air
Table of Contents
RKNL-B Series
2
TABLE OF CONTENTS
Unit Features & Benefits ..............................................................................3-7
Model Number Identification ............................................................................8
Options..........................................................................................................9
Selection Procedure ......................................................................................10
General Data
RKNL- Series........................................................................................11-23
General Data Notes ......................................................................................24
Gross Systems Performance Data
RKNL- Series........................................................................................25-27
Indoor Airflow Performance
RKNL- Series........................................................................................28-32
Electrical Data
RKNL- Series........................................................................................33-36
Dimensional Data ....................................................................................37-40
Accessories ............................................................................................41-62
Mechanical Specifications ........................................................................63-69
Wiring Diagrams ......................................................................................70-77
Limited Warranty ..........................................................................................78
Air
Unit Features & Benefits
RKNL-B Series
3
• R-410A HFC refrigerant.
• Complete factory charged, wired and run tested.
• Scroll compressors with internal line break overload and high-pressure protection.
• Single stage compressor on B073 model.
• Dual stage compressor on B090 – B151 models.
• Convertible airflow.
• TXV refrigerant metering system on each circuit (except on B073).
• High Pressure and Low Pressure/Loss of charge protection standard on all models.
• Solid Core liquid line filter drier on each circuit.
• Single slab, single pass designed evaporator and condenser coils facilitate easy cleaning for maintained high efficiencies.
• Cooling operation up to 125 degree F ambient.
• Foil faced insulation encapsulated throughout entire unit minimizes airborne fibers from the air stream.
• Hinged major access door with heavy-duty gasketing, 1/4 turn latches and door retainers.
• Slide Out Indoor fan assembly for added service convenience.
• Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection. G90 galvanized.
• One piece top cover and one piece base pan with drawn supply and return opening for superior water management.
• Forkable base rails for easy handling and lifting.
• Single point electrical and gas connections.
• Internally sloped slide out condensate pan conforms to ASHRAE 62 standards.
• High performance belt drive motor with variable pitch pulleys and quick adjust belt system.
• Permanently lubricated evaporator, condenser and gas heat inducer motors.
• Condenser motors are internally protected, totally enclosed with shaft down design.
• 2 inch filter standard with slide out design.
• Two stage gas valve, direct spark ignition, and induced draft for efficiency and reliability.
• Tubular heat exchange for long life and induced draft for efficiency and reliability.
• Solid state furnace control with on board diagnostics.
• 24 volt control system with resettable circuit breakers.
• Colored and labeled wiring.
• Copper tube/Aluminum Fin coils (12
1
/2 uses MicroChannel
condenser).
• Molded compressor plug.
RKNL-B STANDARD FEATURES INCLUDE:
Air
Unit Features & Benefits
RKNL-B Series
4
Rheem Package equipment is designed from the ground up with the latest features and benefits required to compete in today’s market. The clean design stands alone in the industry and is a testament to the quality, reliability, ease of installation and ser vice ­ability that goes into each unit. Outwardly, the large Rheem Commercial Series™ label ( ) identifies the brand to the customer.
The sheet-metal cabinet ( ) uses nothing less than 18-gauge material for structural components with an underlying coat of G90. To ensure the leak-proof integrity of these units, the design utilizes a one-piece top with a 1/8" drip lip ( ), gasket-protected panels and screws. The Rheem hail guard ( ) (optional) is its trademark, and sets the standard for coil protection in the indus­try. Every Rheem package unit uses the toughest finish in the industry, using electro deposition baked-on enamel tested to withstand a rigorous 1000-hour salt spray test, per ASTM B117.
Anything built to last must start with the right foundation. In this case, the foundation is 14-gauge, commercial-grade, full-perime ­ter base rails ( ), which integrate fork slots and rigging holes to save set-up time on the job site. The base pan is stamped, which forms a 1-1/8" flange around the supply and return opening and has eliminated the worry of water entering the conditioned space ( ). The drainpan ( ) is made of material that resists the growth of harmful bacteria and is sloped for the latest IAQ bene­fits. Furthermore, the drain pan slides out for easy cleaning. The insulation has been placed on the underside of the basepan, removing areas that would allow for potential moisture accumula­tion, which can facilitate growth of harmful bacteria. All insulation is secured with both adhesive and mechanical fasteners, and all edges are hidden.
During development, each unit was tested to U.L. 1995, ANSI
21.47, AHRI 340-370 and other Rheem-required reliability tests. Rheem adheres to stringent IS0 9002 quality procedures, and each unit bears the U.L. and AHRI certification labels located on the unit nameplate ( ). Contractors can rest assured that when a Rheem package unit arrives at the job, it is ready to go with a factory charge and quality checks. Each unit also proudly dis ­plays the “Made in the USA” designation.
Access is granted with 1/4 turn fasteners and hinged access panels. Access to all major compartments is from the front of the unit, including the filter and electrical compartment, blower com­partment, furnace section, and outdoor section. Each panel is permanently embossed with the compartment name (control/filter access, blower access and furnace access).
Electrical and filter compartment access is through a large hinged-access panel. The unit charging chart is located on the inside of the electrical and filter compartment door. Electrical wiring diagrams are found on the control box cover, which allows contractors to move them to more readable locations. To the right of the control box the model and serial number can be found. Having this information on the inside will assure model iden­tification for the life of the product. The production line quality test assurance label is also placed in this location ( ). The two-inch throwaway filters ( ) are easily removed on a tracked system for easy replacement.
1
7
6
5
2
4
3
8
9
10
6
6
9
10
2
8
1
4
3
5
7
Air
Unit Features & Benefits
RKNL-B Series
5
Inside the control box ( ), each elec­trical component is clearly identified with a label that matches the compo­nent to the wire diagram for ease of trouble shooting. All wiring is num­bered on each end of the termination and color-coded to match the wiring diagram. The integrated furnace con­trol, used to control furnace operation, incorporates a flashing LED trouble ­shooting device. Flash codes are clearly outlined on the unit wiring dia­gram. The control transformer has a low voltage circuit breaker that trips if a low voltage electrical short occurs. There is a blower contactor and com­pressor contactor for each compressor.
For added convenience in the field, a factory-installed conve­nience outlet and disconnect ( ) are available. Low and High voltage can enter either from the side or through the base. Low-voltage connections are made through the low-voltage terminal strip. For ease of access, the U.L.-required low voltage barrier can be temporarily removed for low-voltage termination and then reinstalled. The high-voltage connection is terminated at the number 1 compressor contactor. The suggested mounting for the field­installed disconnect is on the exterior side of the electrical control box.
To the right of the electrical and filter compartment are the externally mounted gauge ports, which are per­manently identified by embossed wording that clearly identifies the com­pressor circuit, high pressure connec­tion and low pressure connection ( ). With the gauge ports mounted exter­nally, an accurate diagnostic of system
operation can be performed quickly and easily. Brass caps on the shraeder fitting assure that the gauge parts are leak proof.
The blower compartment is to the right of the gauge ports and can be accessed by 1/4 turn fastener. To allow easy maintenance of the blower assembly, the entire assembly easily slides out by removing two 3/8" screws from the blower retention bracket. The adjustable motor pulley ( ) can easily be adjusted by loosening the bolts on either side of the motor mount. Removing the bolts allows for easy removal of the blower pulley by pushing the blower assembly up to loosen the belt. Once the belt is removed, the motor sheave can be adjusted to the desired number of turns, ranging from 0 to 6 turns open. Where the demands for the job require high static, Rheem has high-static drives available that deliver nominal airflow up to 2" of static. By referring to the airflow performance tables listed in the installation instructions, proper static pressure and CFM requirements can be dialed in. The scroll housing ( ) and blower scroll provide quiet and effi­cient airflow. The blower sheave is secured by an “H” bushing which firmly secures the pulley to the blower shaft for years of trouble-free oper­ation. The “H” bushing allows for easy removal of the blower pulley from the shaft, as opposed to the use of a set screw, which can score the shaft, creating burrs that make blower­pulley removal difficult.
15
14
13
12
11
10
7
13
11
12
14
15
Air
Unit Features & Benefits
RKNL-B Series
6
Also inside the blower compart­ment is the low-ambient control ( ), low-pressure switch ( ), high-pressure switch ( ) and freeze stat refrigerant safety device ( ). The low-ambient control allows for operation of the compressor down to 0 degrees ambient temperature by cycling the outdoor fans on high pres­sure. The high-pressure switch will shut off the compressors if pressures in excess of 610 PSIG are detected, this may occur if the outdoor fan motor fails. The low-pressure switch shuts off the compressors if low pressure is detected due to loss of charge. The freeze stat protects the com­pressor if the evapora tor coil gets too cold (below freezing) due to low airflow. Each factory-installed option is brazed into the appropriate high or low side and wired appropriately. Use of polar­ized plugs and sharder fittings allow for easy field installation.
Inside the blower compartment the interlaced evaporator can also be viewed. The evaporator uses enhanced fin technology for maximum heat transfer. The TXV metering device assures even distribution of refrigerant throughout the evaporator. (Note: the single stage 6 utilizes orifices).
Wiring throughout the unit is neatly bundled and routed. Where wire harnesses go through the condenser bulkhead or blower deck, a molded wire harness assembly ( ) provides an air-tight and water-tight seal, and provides strain relief. Care is also taken to tuck raw edges of insulation behind sheet metal to improve indoor air quality.
The furnace compartment contains the latest furnace technology on the market. The draft inducers ( ) draw the flame from the Rheem exclusive in-shot burners ( ) into the aluminized tubular heat exchanger ( ) for clean, efficient gas heat. Stainless steel heat exchangers can be factory installed for those applications that have high fresh-air requirements, or applications in corrosive environments. Each furnace is equipment with a two-stage gas valve ( ), which provides two stages of gas heat input. The first stage operates at 50% of the second stage (full fire). 81% steady state efficiency is maintained on both first and second stage by staging the multiple inducers to optimize the combustion airflow and maintain a near stioceometric burn at each stage.
The direct spark igniter ( ) assures reliable ignition in the most adverse conditions. This is coupled with remote flame sense ( ) to assure that the flame has carried across the entire length of the burner assembly. Gas supply can be routed from the side or up through the base.
Each furnace has the following safety devices to assure consis­tent and reliable operation after ignition:
• Pressures switches ( ) to assure adequate combustion airflow before ignition.
• Rollout switches ( ) to assure no obstruction or cracks in the heat exchanger.
• A limit device that protects the furnace from over-temperature problems.
16
17
18
19
20
21
22
23
24
25
26
27
28
18
16
24
21
21
26
27
27
25
28
28
22
23
22
17
20
Air
Unit Features & Benefits
RKNL-B Series
7
The compressor compartment houses the heart­beat of the unit. The scroll compressor ( ) is known for its long life, and for reliable, quiet, and efficient operation. The suction and discharge lines are designed with shock loops ( ) to absorb the strain and stress that the starting torque, steady state opera­tion, and shut down cycle impose on the refrigerant tubing. Each compressor and circuit is inde­pendent for built-in redundancy, and each circuit is clearly marked throughout the system. Each unit has two stages of efficient cooling operation, first stage is approximately 50% of second stage. (073 single stage)
Each unit comes standard with filter dryer . The condenser fan motor ( ) can easily be accessed and maintained through the blower compartment. The polarized plug connection allows the motor to be changed quickly and eliminates the need to snake wires through the unit.
The outdoor coil uses the latest enhanced fin design ( ) for the most effective method of heat transfer. The outdoor coil is pro­tected by optional* louvered panels, which allow unobstructed airflow while protecting the unit from both Mother Nature and vandalism.
Each unit is designed for both downflow or horizontal applications ( ) for job configura­tion flexibility. The return air compartment can also contain an economizer ( ). Two models exits, one for downflow applications, and one for horizontal applications. Each unit is pre-wired for the economizer to allow quick plug-in installation. The economizer is also available as a factory-installed option. Power Exhaust is easily field­installed. The economizer, which provides free cooling when outdoor conditions are suitable and also provides fresh air to meet local requirements, comes standard with single enthalpy controls. The controls can be upgraded to dual enthalpy easily in the field. The direct drive actuator combined with gear drive dampers has eliminated the need for linkage adjustment in the field. The economizer control has a minimum position setpoint, an outdoor-air setpoint, a mix-air setpoint, and a CO
2
setpoint. Barometric relief is standard on all economizers. The power exhaust is housed in the barometric relief opening and is easily slipped in with a plug-in assembly. The wire harness to the economizer also has accommodations for a smoke detector.
The Rheem roofcurb ( ) is made for toolless assembly at the jobsite by engag­ing a pin into the hinged corners of adjacent curb sides, which makes the assembly process quick and easy.
31
36
35
34
33
32
30
29
29
32
33
36
35
35
34
30
31
Air
Model Number Identification
RKNL-B Series
8
R K N L B 090 C L 15 E X X X
Economizer Option (See Next Page)
Factory Installed Options (See Next Page)
Ignition System E = Electric
Heating Capacity (MBH) 15 = 150,000 [44.0] 22 = 225,000 [65.9] 25 = 252,000 [73.9]
Drive Package L = Belt Drive M= Belt Drive—High Static N = Belt Drive—High Static
B090 Only
Electrical Designation C = 208-230 V, 3 PH, 60 Hz D = 460 V, 3 PH, 60 Hz Y = 575 V, 3 PH, 60 Hz
Cooling Capacity (BTUH) [kW] 073 = 72,000 [21.10] 090 = 90,000 [26.38] 102 = 102,000 [29.89] 120 = 120,000 [35.17] 151 = 150,000 [43.96]
Future Technical Variations
Design Series L = R410A
Efficiency Designation N = EnergyStar Compliant
Product Classification K = Rooftop—Commercial
Tradebrand R = Rheem Packaged Gas/Electric
[ ] Designates Metric Conversions
Air
Options
RKNL-B Series
9
FACTORY INSTALLED OPTION CODES FOR KNL (6 TO 12.5 TON) [21.1 TO 44.0 kW]
Option Code No Economizer
Single Enthalpy Economizer
w/Barometric Relief and Smoke Detector
A x F
Single Enthalpy Economizer
w/Barometric Relief
x
G x
ECONOMIZER SELECTION FOR KNL (6 TO 12.5 TON) [21.1 TO 44.0 kW]
“x” indicates factory installed option.
Instructions for Factory Installed Option(s) Selection
Note: Three characters following the model number will be utilized to designate a factory-installed option or
combination of options. If no factory option(s) is required, nothing follows the model number.
Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY
INSTALLED OPTION SELECTION TABLE.
Proceed to Step 2.
Step 2. The last option code character is utilized for factory-installed economizers. Choose a character from
the FACTORY INSTALLED ECONOMIZER SELECTION TABLE.
Examples:
RKNL-B120CL22E ............................this unit has no factory installed options.
RKNL-B120CL22EBGA......................this unit is equipped with hail guard and stainless steel heat exchanger.
RKNL-B120CL22EAHA......................this unit is equipped with a non-powered convenience outlet and
service disconnect.
RKNL-B120CL22EAHF ......................this unit is equipped as above and includes an Economizer
with single enthalpy sensor and with barometric relief.
RKNL-B120CL22EAAF ......................this unit is equipped with an Economizer with single enthalpy sensor and
Barometric Relief.
[ ] Designates Metric Conversions
Option Code
AD x AJ AH x AP x BF x x BG x BY x x
CR x x DN x x x
Hail
Guard
Stainless
Steel
Heat Exchanger
x
x
xJB x x x
Non-Powered Convenience
Outlet/Unfused
Service Disconnect
Low Ambient/
Freeze
Stat
Air
Selection Procedure
RKNL-B Series
10
To select an RKNL-B Cooling and Heating unit to meet a job requirement, follow this procedure, with example, using data supplied in this specification sheet.
1. DETERMINE COOLING AND HEATING REQUIREMENTS AND SPECIFIC OPERATING CONDITIONS FROM PLANS AND SPECS.
Example:
Voltage — 208/230V — 3 Phase — 60 Hz Total Cooling Capacity — 106,000 BTUH [31.0 kW] Sensible Cooling Capacity — 082,000 BTUH [24.0 kW] Heating Capacity — 150,000 BTUH [43.9 kW] *Condenser Entering Air — 95°F [35.0 °C] DB *Evaporator Mixed Air Entering —65°F [18.3 °C] WB
78°F [25.6 °C] DB *Indoor Air Flow (vertical) — 3600 CFM [1699 L/s] *External Static Pressure — 0.40 in. WG [.10 kPa]
2. SELECT UNIT TO MEET COOLING REQUIREMENTS.
Since total cooling is within the range of a nominal 10 ton [35.1 kW] unit, enter cooling performance table at 95°F [35.0 °C] DB condenser inlet air. Interpolate between 63°F [17.2 °C] WB and 67°F [19.4 °C] WB to determine total and sensi ble capacity and power input for 65°F [18.3 °C] WB evaporator inlet air at 3750 CFM [1770 L/s] indoor air flow (table basis):
Total Cooling Capacity = 118,900 BTUH [34.82 kW] Sensible Cooling Capacity = 99,950 BTUH [29.27 kW] Power Input (Compressor and Cond. Fans) = 8,950 watts
Use formula in note to determine sensible capacity at 78°F [25.6 °C] DB evaporator entering air:
99,950 + (1.10 x 3,600 x (1 - 0.03) x (78 - 80)) Sensible Cooling Capacity = 92,268 BTUH [27.02 kW]
3. CORRECT CAPACITIES OF STEP 2 FOR ACTUAL AIR FLOW.
Select factors from airflow correction table at 3600 CFM [1699 L/s] and apply to data obtained in step 2 to obtain gross capacity:
Total Capacity = 118,900 x 0.98 = 116,522 BTUH [34.12 kW] Sensible Capacity = 92,268 x 0.95 = 87,655 BTUH [25.67 kW] Power Input = 8,950 x 0.99 = 8,861 Watts
These are Gross Capacities, not corrected for blower motor heat or power.
4. DETERMINE BLOWER SPEED AND WATTS TO MEET SYSTEM DESIGN.
Enter Indoor Blower performance table at 3600 CFM [1699 L/s]. Total ESP (external static pressure) per the spec of 0.40 in. WG [.10 kPa] includes the system duct and grilles. Add from the table ‘Component Air Resistance’, 0.076 in. WG [.02 kPa] for wet coil, 0 in. WG [.00 kPa] for downflow air flow, for a total selection static pressure of 0.476 (0.5) in. WG [.12 kPa], and determine:
RPM = 769 WATTS = 1,576 DRIVE = L (standard 2 H.P. motor)
5. CALCULATE INDOOR BLOWER BTUH HEAT EFFECT FROM MOTOR WATTS, STEP 4.
1,576 x 3.412 = 5,377 BTUH [1.57 kW]
6. CALCULATE NET COOLING CAPACITIES, EQUAL TO GROSS CAPACITY, STEP 3, MINUS INDOOR BLOWER MOTOR HEAT.
Net Total Capacity = 116,522-5,377 =
111,145 BTUH [32.54 kW]
Net Sensible Capacity = 87,655 - 5,377 =
82,278 BTUH [24.09 kW]
7. CALCULATE UNIT INPUT AND JOB EER.
Total Power Input = 8,861 (step 3) + 1,576
(step 4) = 10,437 Watts
EER =
Net Total BTUH [kW] (step 6) =111,145
= 10.65
Power Input, Watts (above) 10,437
8. SELECT UNIT HEATING CAPACITY.
From Physical Data Table read that gas heating output (input rating x efficiency) is:
Heating Capacity = 182,250 BTUH [53.4 kW]
9. CHOOSE MODEL RKNL-B120CL22E
*NOTE: These operating conditions are typical of a commercial
application in a 95°F/79°F [35°C/26°C] design area with indoor design of 76°F [24°C] DB and 50% RH and 10% ventilation air, with the unit roof mounted and centered on the zone it conditions by ducts.
[ ] Designates Metric Conversions
Air
General Data
RKNL-B Series
11
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Model RKNL- Series
B073CL15E B073CM15E B073DL15E B073DM15E
Cooling Performance
1
CONTINUED
Gross Cooling Capacity Btu [kW]
75,000 [21.97] 75,000 [21.97] 75,000 [21.97] 75,000 [21.97]
EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s]
2400/2325 [1133/1097] 2400/2325 [1133/1097] 2400/2325 [1133/1097] 2400/2325 [1133/1097]
AHRI Net Cooling Capacity Btu [kW]
72,000 [21.1] 72,000 [21.1] 72,000 [21.1] 72,000 [21.1]
Net Sensible Capacity Btu [kW]
52,800 [15.47] 52,800 [15.47] 52,800 [15.47] 52,800 [15.47]
Net Latent Capacity Btu [kW]
19,200 [5.63] 19,200 [5.63] 19,200 [5.63] 19,200 [5.63]
IEER
3
11.8 11.8 11.8 11.8
Net System Power kW
6.42 6.42 6.42 6.42
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)
75,000/150,000 [21.97/43.95] 75,000/150,000 [21.97/43.95] 75,000/150,000 [21.97/43.95] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage)
60,750/121,500 [17.8/35.6] 60,750/121,500 [17.8/35.6] 60,750/121,500 [17.8/35.6] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] (1st Stage / 2nd Stage)
30-60 [16.7-33.3] /
30-60 [16.7-33.3]
30-60 [16.7-33.3] /
30-60 [16.7-33.3]
30-60 [16.7-33.3] /
30-60 [16.7-33.3]
30-60 [16.7-33.3] /
30-60 [16.7-33.3] Steady State Efficiency (%) 81 81 81 81
No. Burners
6 6 6 6 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7]
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD
0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m]
13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type
Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/11x12 [279x305] 1/11x12 [279x305] 1/11x12 [279x305] 1/11x12 [279x305] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 1 1/2 1 1/2 1 1/2 1 1/2 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56
Filter—Type
Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Ye s (NO.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
125 [3544] 125 [3544] 125 [3544] 125 [3544]
Weights
Net Weight lbs. [kg] 901 [409] 901 [409] 901 [409] 901 [409] Ship Weight lbs. [kg] 938 [425] 938 [425] 938 [425] 938 [425]
See Page 24 for Notes.
[ ] Designates Metric Conversions
Air
General Data
RKNL-B Series
12
Model RKNL- Series B073YL15E B073YM15E B090CL15E B090CL22E
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
75,000 [21.97] 75,000 [21.97] 93,000 [27.25] 93,000 [27.25]
EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s]
2400/2325 [1133/1097] 2400/2325 [1133/1097] 3000/2775 [1416/1310] 3000/2775 [1416/1310]
AHRI Net Cooling Capacity Btu [kW]
72,000 [21.1] 72,000 [21.1] 90,000 [26.37] 90,000 [26.37]
Net Sensible Capacity Btu [kW]
52,800 [15.47] 52,800 [15.47] 63,100 [18.49] 63,100 [18.49]
Net Latent Capacity Btu [kW]
19,200 [5.63] 19,200 [5.63] 26,900 [7.88] 26,900 [7.88]
IEER
3
11.8 11.8 11.9 11.9
Net System Power kW
6.42 6.42 7.99 7.99
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)
75,000/150,000 [21.97/43.95] 75,000/150,000 [21.97/43.95] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92]
Heating Output Btu [kW] (1st Stage / 2nd Stage)
60,750/121,500 [17.8/35.6] 60,750/121,500 [17.8/35.6] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4]
Temperature Rise Range ˚F [˚C] (1st Stage / 2nd Stage)
30-60 [16.7-33.3] /
30-60 [16.7-33.3]
30-60 [16.7-33.3] /
30-60 [16.7-33.3]
25-55 [13.9/30.6] /
25-55 [13.9/30.6]
40-70 [22.2/38.9] /
40-70 [22.2/38.9] Steady State Efficiency (%) 81 81 81 81
No. Burners
6 6 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.5 [12.7] 0.5 [12.7] 0.75 [19]
Compressor
No./Type 1/Scroll 1/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD
0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m]
13.5 [1.25] 13.5 [1.25] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type
Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/11x12 [279x305] 1/11x12 [279x305] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 1 1/2 1 1/2 2 2 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56
Filter—Type
Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
125 [3544] 125 [3544] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138]
Weights
Net Weight lbs. [kg] 901 [409] 901 [409] 1017 [461] 1053 [478] Ship Weight lbs. [kg] 938 [425] 938 [425] 1054 [478] 1090 [494]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
See Page 24 for Notes.
[ ] Designates Metric Conversions
Air
General Data
RKNL-B Series
13
Model RKNL- Series B090CM15E B090CM22E B090CN15E B090CN22E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310]
AHRI Net Cooling Capacity Btu [kW] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37]
Net Sensible Capacity Btu [kW] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49]
Net System Power kW 7.99 7.99 7.99 7.99
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4]
Temperature Rise Range ˚F [˚C] 25-55 [13.9/30.6] 40-70 [22.2/38.9] 25-55 [13.9/30.6] 40-70 [22.2/38.9]
Net Weight lbs. [kg] 1017 [461] 1053 [478] 1025 [465] 1061 [481]
Steady State Efficiency (%) 81 81 81 81
IEER
3
11.9 11.9 11.9 11.9
No. Burners 6 9 6 9
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19] 0.5 [12.7] 0.75 [19]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Net Latent Capacity Btu [kW] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 2 2 3 3
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138]
Weights
Ship Weight lbs. [kg] 1054 [478] 1090 [494] 1062 [482] 1098 [498]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
See Page 24 for Notes.
[ ] Designates Metric Conversions
Air
General Data
RKNL-B Series
14
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B090DL15E B090DL22E B090DM15E B090DM22E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310]
AHRI Net Cooling Capacity Btu [kW] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37]
Net Sensible Capacity Btu [kW] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49]
Net System Power kW 7.99 7.99 7.99 7.99
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4]
Temperature Rise Range ˚F [˚C] 25-55 [13.9/30.6] 40-70 [22.2/38.9] 25-55 [13.9/30.6] 40-70 [22.2/38.9]
Net Weight lbs. [kg] 1025 [465] 1053 [478] 1017 [461] 1053 [478]
Steady State Efficiency (%) 81 81 81 81
IEER
3
11.9 11.9 11.9 11.9
No. Burners 6 9 6 9
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19] 0.5 [12.7] 0.75 [19]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Net Latent Capacity Btu [kW] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 2 2 2 2
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138]
Weights
Ship Weight lbs. [kg] 1062 [482] 1090 [494] 1054 [478] 1090 [494]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
15
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B090DN15E B090DN22E B090YL22E B090YM22E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] 93,000 [27.25] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310] 3000/2775 [1416/1310]
AHRI Net Cooling Capacity Btu [kW] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37] 90,000 [26.37]
Net Sensible Capacity Btu [kW] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49] 63,100 [18.49]
Net System Power kW 7.99 7.99 7.99 7.99
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 112,500/225,000 [32.96/65.92] 112,500/225,000 [32.96/65.92]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 91,125/182,250 [26.7/53.4] 91,125/182,250 [26.7/53.4]
Temperature Rise Range ˚F [˚C] 25-55 [13.9/30.6] 40-70 [22.2/38.9] 40-70 [22.2/38.9] 40-70 [22.2/38.9]
Net Weight lbs. [kg] 1025 [465] 1061 [481] 1053 [478] 1053 [478]
Steady State Efficiency (%) 81 81 81 81
IEER
3
11.9 11.9 11.9 11.9
No. Burners 6 9 9 9
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19] 0.75 [19] 0.75 [19]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Net Latent Capacity Btu [kW] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88] 26,900 [7.88]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 3 3 2 2
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138] 107.5/110.7 [3048/3138]
Weights
Ship Weight lbs. [kg] 1062 [482] 1098 [498] 1090 [494] 1090 [494]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
16
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B090YN22E B102CL15E B102CL22E B102CM15E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 93,000 [27.25] 101,000 [29.59] 101,000 [29.59] 101,000 [29.59] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3000/2775 [1416/1310] 3200/3200 [1510/1510] 3200/3200 [1510/1510] 3200/3200 [1510/1510]
AHRI Net Cooling Capacity Btu [kW] 90,000 [26.37] 97,000 [28.42] 97,000 [28.42] 97,000 [28.42]
Net Sensible Capacity Btu [kW] 63,100 [18.49] 74,000 [21.68] 74,000 [21.68] 74,000 [21.68]
Net System Power kW 7.99 8.59 8.59 8.59
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 9,113/182,250 [2.67/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] 40-70 [22.2/38.9] 25-55 [13.9/30.6] 40-70 [22.2/38.9] 25-55 [13.9/30.6]
Net Weight lbs. [kg] 1061 [481] 1059 [480] 1095 [497] 1067 [484]
Steady State Efficiency (%) 81 81 81 81
IEER
3
11.9 12 12 12
No. Burners 9 6 9 6
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 1 / 22 [9] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Net Latent Capacity Btu [kW] 26,900 [7.88] 23,000 [6.74] 23,000 [6.74] 23,000 [6.74]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 3 2 2 3
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 107.5/110.7 [3048/3138] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723]
Weights
Ship Weight lbs. [kg] 1098 [498] 1096 [497] 1132 [513] 1104 [501]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
17
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B102CM22E B102DL15E B102DL22E B102DM15E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 101,000 [29.59] 101,000 [29.59] 101,000 [29.59] 101,000 [29.59] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3200/3200 [1510/1510] 3200/3200 [1510/1510] 3200/3200 [1510/1510] 3200/3200 [1510/1510]
AHRI Net Cooling Capacity Btu [kW] 97,000 [28.42] 97,000 [28.42] 97,000 [28.42] 97,000 [28.42]
Net Sensible Capacity Btu [kW] 74,000 [21.68] 74,000 [21.68] 74,000 [21.68] 74,000 [21.68]
Net System Power kW 8.59 8.59 8.59 8.59
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] 40-70 [22.2/38.9] 25-55 [13.9/30.6] 40-70 [22.2/38.9] 25-55 [13.9/30.6]
Net Weight lbs. [kg] 1103 [500] 1059 [480] 1095 [497] 1067 [484]
Steady State Efficiency (%) 81 81 81 81
IEER
3
12 12 12 12
No. Burners 9 6 9 6
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Net Latent Capacity Btu [kW] 23,000 [6.74] 23,000 [6.74] 23,000 [6.74] 23,000 [6.74]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 3 2 2 3
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723]
Weights
Ship Weight lbs. [kg] 1140 [517] 1096 [497] 1132 [513] 1104 [501]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
18
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B102DM22E B102YL22E B102YM22E B120CL15E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 101,000 [29.59] 101,000 [29.59] 101,000 [29.59] 123,000 [36.04] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 3200/3200 [1510/1510] 3200/3200 [1510/1510] 3200/3200 [1510/1510] 4000/3750 [1888/1770]
AHRI Net Cooling Capacity Btu [kW] 97,000 [28.42] 97,000 [28.42] 97,000 [28.42] 118,000 [34.57]
Net Sensible Capacity Btu [kW] 74,000 [21.68] 74,000 [21.68] 74,000 [21.68] 88,800 [26.02]
Net System Power kW 8.59 8.59 8.59 10.49
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 112,500/225,000 [32.96/65.92] 112,500/22,500 [32.96/6.59] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 91,125/182,250 [26.7/53.4] 911,250/182,250 [266.99/53.4] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] 40-70 [22.2/38.9] 40-70 [22.2/38.9] 40-70 [22.2/38.9] 15-45 [8.3/25]
Net Weight lbs. [kg] 1103 [500] 1095 [497] 1103 [500] 1112 [504]
Steady State Efficiency (%) 81 81 81 81
IEER
3
12 12 12 12
No. Burners 9 9 9 6
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.75 [19] 0.75 [19] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 2 / 22 [9]
Net Latent Capacity Btu [kW] 23,000 [6.74] 23,000 [6.74] 23,000 [6.74] 29,200 [8.56]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7] 2 / 18 [7] 3 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 3 2 3 2
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] 154.4/166.6 [4377/4723] 172.8/180.8 [4899/5126]
Weights
Ship Weight lbs. [kg] 1140 [517] 1132 [513] 1140 [517] 1149 [521]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
19
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B120CL22E B120CM15E B120CM22E B120DL15E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 123,000 [36.04] 123,000 [36.04] 123,000 [36.04] 123,000 [36.04] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 4000/3750 [1888/1770] 4000/3750 [1888/1770] 4000/3750 [1888/1770] 4000/3750 [1888/1770]
AHRI Net Cooling Capacity Btu [kW] 118,000 [34.57] 118,000 [34.57] 118,000 [34.57] 118,000 [34.57]
Net Sensible Capacity Btu [kW] 88,800 [26.02] 88,800 [26.02] 88,800 [26.02] 88,800 [26.02]
Net System Power kW 10.49 10.49 10.49 10.49
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] 25-55 [13.9/30.6] 15-45 [8.3/25] 25-55 [13.9/30.6] 15-45 [8.3/25]
Net Weight lbs. [kg] 1148 [521] 1120 [508] 1156 [524] 1112 [504]
Steady State Efficiency (%) 81 81 81 81
IEER
3
12 11.9 11.9 11.9
No. Burners 9 6 9 6
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 29,200 [8.56] 29,200 [8.56] 29,200 [8.56] 29,200 [8.56]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 2 3 3 2
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126]
Weights
Ship Weight lbs. [kg] 1185 [538] 1157 [525] 1193 [541] 1149 [521]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
20
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series B120DL22E B120DM15E B120DM22E B120YL22E
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 123,000 [36.04] 123,000 [36.04] 123,000 [36.04] 123,000 [36.04] EER/SEER
2
11.2/NA 11.2/NA 11.2/NA 11.2/NA
Nominal CFM/AHRI Rated CFM [L/s] 4000/3750 [1888/1770] 4000/3750 [1888/1770] 4000/3750 [1888/1770] 4000/3750 [1888/1770]
AHRI Net Cooling Capacity Btu [kW] 118,000 [34.57] 118,000 [34.57] 118,000 [34.57] 118,000 [34.57]
Net Sensible Capacity Btu [kW] 88,800 [26.02] 88,800 [26.02] 88,800 [26.02] 88,800 [26.02]
Net System Power kW 10.49 10.49 10.49 10.49
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage) 112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 112,500/225,000 [32.96/65.92] 112,500/225,000 [32.96/65.92]
Heating Output Btu [kW] (1st Stage / 2nd Stage) 91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 91,125/182,250 [26.7/53.4] 91,125/182,250 [26.7/53.4]
Temperature Rise Range ˚F [˚C] 25-55 [13.9/30.6] 15-45 [8.3/25] 25-55 [13.9/30.6] 25-55 [13.9/30.6]
Net Weight lbs. [kg] 1148 [521] 1120 [508] 1156 [524] 1148 [521]
Steady State Efficiency (%) 81 81 81 81
IEER
3
11.9 11.9 11.9 11.9
No. Burners 9 6 9 9
No. Stages 2 2 2 2
Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.75 [19]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51]
Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 29,200 [8.56] 29,200 [8.56] 29,200 [8.56] 29,200 [8.56]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25]
Rows / FPI [FPcm] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7]
Refrigerant Control TX Valves TX Valves TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775]
No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP
Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381]
Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
No. Motors 1 1 1 1
Motor HP 2 3 3 2
Motor RPM 1725 1725 1725 1725
Motor Frame Size 56 56 56 56
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes
(No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126] 172.8/180.8 [4899/5126]
Weights
Ship Weight lbs. [kg] 1185 [538] 1157 [525] 1193 [541] 1185 [538]
CONTINUED
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
21
See Page 24 for Notes.
[ ] Designates Metric Conversions
Model RKNL- Series
B120YM22E B151CL15E B151CL25E B151CM15E
Cooling Performance
1
CONTINUED
Gross Cooling Capacity Btu [kW]
123,000 [36.04] 146,000 [42.78] 146,000 [42.78] 146,000 [42.78]
EER/SEER
2
11.2/NA 10.8/NA 10.8/NA 10.8/NA
Nominal CFM/AHRI Rated CFM [L/s]
4000/3750 [1888/1770] 5000/4225 [2360/1994] 5000/4225 [2360/1994] 5000/4225 [2360/1994]
AHRI Net Cooling Capacity Btu [kW]
118,000 [34.57] 140,000 [41.02] 140,000 [41.02] 140,000 [41.02]
Net Sensible Capacity Btu [kW]
88,800 [26.02] 99,500 [29.15] 99,500 [29.15] 99,500 [29.15]
Net Latent Capacity Btu [kW]
29,200 [8.56] 40,500 [11.87] 40,500 [11.87] 40,500 [11.87]
IEER
3
11.9 10.8 10.8 10.8
Net System Power kW
10.49 12.73 12.73 12.73
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)
112,500/225,000 [32.96/65.92] 75,000/150,000 [21.97/43.95] 126,000/252,000 [36.92/73.84] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage)
91,125/182,250 [26.7/53.4] 60,750/121,500 [17.8/35.6] 102,000/204,000 [29.89/59.77] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] (1st Stage / 2nd Stage)
25-55
[13.9/30.6]
15-45 [8.3-25] /
15-45 [8.3-25]
25-55 [13.9-30.6] /
25-55 [13.9-30.6]
15-45 [8.3-25] /
15-45 [8.3-25] Steady State Efficiency (%) 81 81 81 81
No. Burners
9 6 9 6 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled MicroChannel MicroChannel MicroChannel
Tube Size in. [mm] OD
0.375 [9.5] 1 [25.4] 1 [25.4] 1 [25.4]
Face Area sq. ft. [sq. m]
27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 2 / 22 [9] 2 / 23 [9] 2 / 23 [9] 2 / 23 [9]
Indoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 3 / 18 [7] 4 / 15 [6] 4 / 15 [6] 4 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type
Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/2 HP 2 at 1/2 HP 2 at 1/2 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt (Adjustable)/Single Belt (Adjustable)/Single Belt (Adjustable)/Single No. Motors 1 1 1 1 Motor HP 3 3 3 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 184
Filter—Type
Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
172.8/180.8 [4899/5126] 147.2/152 [4173/4309] 147.2/152 [4173/4309] 147.2/152 [4173/4309]
Weights
Net Weight lbs. [kg] 1156 [524] 1266 [574] 1266 [574] 1238 [562] Ship Weight lbs. [kg] 1193 [541] 1303 [591] 1267 [575] 1267 [575]
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
Air
General Data
RKNL-B Series
22
Model RKNL- Series
B151CM25E B151DL15E B151DL25E B151DM15E
Cooling Performance
1
CONTINUED
Gross Cooling Capacity Btu [kW]
146,000 [42.78] 146,000 [42.78] 146,000 [42.78] 146,000 [42.78]
EER/SEER
2
10.8/NA 10.8/NA 10.8/NA 10.8/NA
Nominal CFM/AHRI Rated CFM [L/s]
5000/4225 [2360/1994] 5000/4225 [2360/1994] 5000/4225 [2360/1994] 5000/4225 [2360/1994]
AHRI Net Cooling Capacity Btu [kW]
140,000 [41.02] 140,000 [41.02] 140,000 [41.02] 140,000 [41.02]
Net Sensible Capacity Btu [kW]
99,500 [29.15] 99,500 [29.15] 99,500 [29.15] 99,500 [29.15]
Net Latent Capacity Btu [kW]
40,500 [11.87] 40,500 [11.87] 40,500 [11.87] 40,500 [11.87]
IEER
3
10.8 10.8 10.8 10.8
Net System Power kW
12.73 12.73 12.73 12.73
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)
126,000/252,000 [36.92/73.84] 75,000/150,000 [21.97/43.95] 126,000/252,000 [36.92/73.84] 75,000/150,000 [21.97/43.95]
Heating Output Btu [kW] (1st Stage / 2nd Stage)
102,000/204,000 [29.89/59.77] 60,750/121,500 [17.8/35.6] 102,000/204,000 [29.89/59.77] 60,750/121,500 [17.8/35.6]
Temperature Rise Range ˚F [˚C] (1st Stage / 2nd Stage)
25-55 [13.9-30.6] /
25-55 [13.9-30.6]
15-45 [8.3-25] /
15-45 [8.3-25]
25-55 [13.9-30.6] /
25-55 [13.9-30.6]
15-45 [8.3-25] /
15-45 [8.3-25] Steady State Efficiency (%) 81 81 81 81
No. Burners
9 6 9 6 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19] 0.5 [12.7] 0.75 [19] 0.5 [12.7]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88 88
Outdoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChannel
Tube Size in. [mm] OD
1 [25.4] 1 [25.4] 1 [25.4] 1 [25.4]
Face Area sq. ft. [sq. m]
27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 2 / 23 [9] 2 / 23 [9] 2 / 23 [9] 2 / 23 [9]
Indoor Coil—Fin Type
Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 4 / 15 [6] 4 / 15 [6] 4 / 15 [6] 4 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type
Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/2 HP 2 at 1/2 HP 2 at 1/2 HP 2 at 1/2 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt (Adjustable)/Single Belt (Adjustable)/Single Belt (Adjustable)/Single Belt (Adjustable)/Single No. Motors 1 1 1 1 Motor HP 5 3 3 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 184 56 56 184
Filter—Type
Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Ye s (NO.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
147.2/152 [4173/4309] 147.2/152 [4173/4309] 147.2/152 [4173/4309] 147.2/152 [4173/4309]
Weights
Net Weight lbs. [kg] 1265 [574] 1230 [558] 1266 [574] 1238 [562] Ship Weight lbs. [kg] 1267 [575] 1267 [575] 1267 [575] 1267 [575]
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
See Page 24 for Notes.
[ ] Designates Metric Conversions
Air
General Data
RKNL-B Series
23
Model RKNL- Series
B151DM25E B151YL25E B151YM25E
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
146,000 [42.78] 146,000 [42.78] 146,000 [42.78]
EER/SEER
2
10.8/NA 10.8/NA 10.8/NA
Nominal CFM/AHRI Rated CFM [L/s]
5000/4225 [2360/1994] 5000/4225 [2360/1994] 5000/4225 [2360/1994]
AHRI Net Cooling Capacity Btu [kW]
140,000 [41.02] 140,000 [41.02] 140,000 [41.02]
Net Sensible Capacity Btu [kW]
99,500 [29.15] 99,500 [29.15] 99,500 [29.15]
Net Latent Capacity Btu [kW]
40,500 [11.87] 40,500 [11.87] 40,500 [11.87]
IEER
3
10.8 10.8 10.8
Net System Power kW
12.73 12.73 12.73
Heating Performance (Gas)
4
Heating Input Btu [kW] (1st Stage / 2nd Stage)
126,000/252,000 [36.92/73.84] 126,000/252,000 [36.92/73.84] 126,000/252,000 [36.92/73.84]
Heating Output Btu [kW] (1st Stage / 2nd Stage)
102,000/204,000 [29.89/59.77] 102,000/204,000 [29.89/59.77] 102,000/204,000 [29.89/59.77]
Temperature Rise Range ˚F [˚C] (1st Stage / 2nd Stage)
25-55 [13.9-30.6] /
25-55 [13.9-30.6]
25-55 [13.9-30.6] /
25-55 [13.9-30.6]
25-55 [13.9-30.6] /
25-55 [13.9-30.6] Steady State Efficiency (%) 81 81 81
No. Burners
9 9 9 No. Stages 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19] 0.75 [19] 0.75 [19]
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
5
88 88 88
Outdoor Coil—Fin Type
Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel
Tube Size in. [mm] OD
1 [25.4] 1 [25.4] 1 [25.4]
Face Area sq. ft. [sq. m]
27 [2.51] 27 [2.51] 27 [2.51] Rows / FPI [FPcm] 2 / 23 [9] 2 / 23 [9] 2 / 23 [9]
Indoor Coil—Fin Type
Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 4 / 15 [6] 4 / 15 [6] 4 / 15 [6] Refrigerant Control TX Valves TX Valves TX Valves Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type
Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/2 HP 2 at 1/2 HP 2 at 1/2 HP Motor RPM 1075 1075 1075
Indoor Fan—Type
FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt (Adjustable)/Single Belt (Adjustable)/Single Belt (Adjustable)/Single No. Motors 1 1 1 Motor HP 5 3 5 Motor RPM 1725 1725 1725 Motor Frame Size 184 56 184
Filter—Type
Disposable Disposable Disposable Furnished Yes Yes Yes (NO.) Size Recommended in. [mm x mm x mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
147.2/152 [4173/4309] 147.2/152 [4173/4309] 147.2/152 [4173/4309]
Weights
Net Weight lbs. [kg] 1265 [574] 1266 [574] 1265 [574] Ship Weight lbs. [kg] 1267 [575] 1267 [575] 1267 [575]
NOM. SIZES 6-12.5 TONS [21.1-44.0 kW] ASHRAE 90.1-2007 COMPLIANT MODELS
See Page 24 for Notes.
[ ] Designates Metric Conversions
Air
General Data Notes
RKNL-B Series
24
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 340/360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. IEER is rated in accordance with AHRI Standard 340/360.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.