FORM NO. P11-773 REV. 4
Supersedes Form No. P11-773 Rev. 3
PACKAGE
HEAT P
UMP UNITS
*Unit shown with
optional louver
panels installed.
Featuring Industry Standard R-410A Refrigerant
RJNL- 13 SEER HIGH EFFICIENCY SERIES
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
RJNL- 11 EER HIGH EFFICIENCY SERIES
NOMINAL SIZES 6 TONS [21.1 kW]
RJPL- 14 SEER HIGH EFFICIENCY SERIES
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
(14 SEER MODELS ONLY)
13.0

480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
+ Field Installed Only
* = For Canadian Use Only. Uses “P” Fuses for Inductive Circuit.
48
UNITS WITH HEATER KITS—RJNL- SERIES
Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit
Model
No.
RJNL-
A036DK
A042DK
A048DK
A060DK
RXJJ-
Heater Kit
Nominal kW
No Heat — — — 11 15 15
A06D+ 5.6 19.10 6.7 19 20 20
A10D+ 9.6 32.75 11.6 25 25 25
*A11D+* 9.6 32.75 11.6 25 25 25
A12D+ 11.2 38.21 13.5 28 30 30
A15D+ 14.4 49.13 17.3 32 35 35
A20D+ 19.2 65.51 23.1 40 40 40
*A21D+* 19.2 65.51 23.1 40 40 40
No Heat — — — 11 15 15
A06D+ 5.6 19.10 6.7 19 20 20
A10D+
*A11D+* 9.6 32.75 11.6 25 25 25
A12D+ 11.2 38.21 13.5 28 30 30
A15D+ 14.4 49.13 17.3 33 35 35
A20D+ 19.2 65.51 23.1 40 40 40
*A21D+* 19.2 65.51 23.1 40 40 40
No Heat — — — 11 15 15
A06D+ 5.6 19.10 6.7 20 20 20
A10D+
*A11D+* 9.6 32.75 11.6 26 30 30
A12D+ 11.2 38.21 13.5 28 30 30
A15D+ 14.4 49.13 17.3 33 35 35
A20D+ 19.2 65.51 23.1 40 40 40
*A21D+* 19.2 65.51 23.1 40 40 40
No Heat — — — 13 15 20
A06D+ 5.6 19.10 6.7 22 25 25
A10D+ 9.6 32.75 11.6 28 30 30
*A11D+* 9.6 32.75 11.6 28 30 30
A12D+ 11.2 38.21 13.5 30 30 30
A15D+ 14.4 49.13 17.4 35 35 35
A20D+ 19.2 65.51 23.3 43 45 45
*A21D+* 19.2 65.51 23.3 43 45 45
Rated
Heater kW
@ 480 V
9.6
9.6 32.75 11.6 26 30 30
Heater
KBTU/Hr
@ 480 V
32.75 11.6 25
Heater
Amp.
@ 480 V
Unit Min. Ckt.
Ampacity
@ 480 V
Over Current
Protective Device Size
Min./Max.
@ 480 V
25 25
Min./Max.
@ 480 V
Heater Kit
Min. Ckt.
Ampacity
— — 11 15 15
915———
15 15 — — —
15 15 — — —
17 20 — — —
22 25 — — —
30 30 — — —
29 30 — — —
— — 11 15 15
915———
15 15 —
15 15 — — —
17 20 — — —
22 25 — — —
30 30 — — —
29 30 — — —
— — 11 15 15
915———
15 15 — — —
15 15 — — —
17 20 — — —
22 25 — — —
30 30 — — —
29 30 — — —
— — 13 15 20
915———
15 15 — — —
15 15 — — —
17 20 — — —
22 25 — — —
30 30 — — —
30 30 — — —
Heater Kit
Max. Fuse
Size
Heat Pump
Min. Ckt.
Ampacity
@ 480 V
Heat Pump Over Current
Protective Device Size
Min./Max.
@ 480 V
——
Min./Max.
@ 480 V

Old Models
OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL
MEDIUM CABINET (3 TON [11 kW])
21 SERIES
RXPA-CA21 (1)
RXRA-DB21 (2)
RXRX-BBCDB21
RJNLRJPL-
(-)SNC, (-)SND, (-)SNE
(-)RGE, (-)RGF, (-)RGG
(-)PNC, (-)PND
EXTRA LARGE CABINET
(3.5-5 TON [12-18 kW])
23 SERIES
RXPA-CA23 (1)
RXRA-DB23 (2)
RXRX-BBCDB23
(-)SNC, (-)SND, (-)SNE
(-)RGE, (-)RGF,
(-)RGG (4-5 TON [14-18 kW])
(-)PNC, (-)PND, (-)RGH
(3.5, 4 TON [12-14 kW])
LARGE CABINET
(3-3.5 TON [11-12 kW])
22 SERIES
RXPA-CA22 (1)
RXRA-DB22 (2)
RXRX-BBCDB22
(-)RGE, (-)RGF, (-)RGG,
(-)RGH (3 TON [11 kW])
(1) SLOPE TYPE (2) FULL PERIMETER TYPE
RXJ J—A 15 C
Electrical Designation
J = 208-230 V, 1 PH, 60 Hz
C = 208-230 V, 3 PH, 60 Hz
D = 460 V, 3 PH, 60 Hz
Y = 575 V, 3 PH, 60 Hz
Nominal Heater kW
06 = 6 kW 15 = 15 kW
10 = 10 kW 20 = 20 kW
11 = 11 kW * 21 = 21 kW *
12 = 12 kW 24 = 24 kW
* Canadian Models Only
Design Series
A = Initial Design
Accessory Designation
J = Electric Heater
Accessory Classification
J = Package Heat Pump
X = Accessory
R = Trade Name
Field Installed Resistance
Heater Kits
Electric Heater Kits are designed for field
installation using either single-point power
wiring or dual circuit wiring. Low voltage
plugs are provided to allow for quick
connection to the unit. Removing a blockoff panel on the unit allows the heater
elements to be inserted into the supply air
down stream from the indoor coil and
supply air blower.
[ ] Designates Metric Conversions
Model Number Identifier:
67
INTRODUCTIONACCESSORIES—RJNL/RJPL- SERIES