Rheem RHSL Specification

Rheem Standard Efficiency Air Handler
FORM NO. H11-550
RHSL- Series
PSC Motor Efficiencies up to 15 SEER
• Versatile 4-way convertible design for upflow, downflow, horizontal left and horizontal right applications.
• Sturdy cabinet construction with 1.0 inch [25.4 mm] of foil faced insulation for excellent sound and insulating characteristics.
• Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect.
•1
1
/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between
42
1
/2 to 551/2 inches [1080 to 1410 mm] tall and 22 inches
[559 mm] deep.
• All models meet or exceed 330 to 400 CFM [156 to 189 L/s] per ton at .3 inches [.7 kPa] of external static pressure.
• Enhanced airflow up to .7" external static pressure.
Air
Air Handlers
RHSL Series
Air
Table of Contents
RHSL Series
2
TABLE OF CONTENTS
Engineering Features ......................................................................................3
Model Number Identification ............................................................................4
Dimensional Data............................................................................................5
Airflow Directional Data ..................................................................................6
Airflow Performance Data ..........................................................................7-11
Electrical Data ........................................................................................12-15
Electrical Wiring ............................................................................................16
Accessories ............................................................................................................16
Limited Warranty ..........................................................................................17
Air
Engineering Features
RHSL Series
3
Engineering Features
• The most compact unit design available, all standard heat air handler models only 42
1
/2 to 551/2 inches [1079 to 1409 mm] high.
• Attractive pre-painted cabinet exterior.
• Rugged wall steel cabinet construction, designed for added strength and versatility.
• 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance.
• Four leg blower motor mount.
• Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience.
• Traditional open wire element design for heat applications.
• Field convertible for vertical downflow, horizontal left hand or right hand air supply.
• 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors.
• Indoor coil design provides low air side pressure drop, high performance and extremely compact size.
[ ] Designates Metric Conversions
• Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil.
• Coils are constructed of aluminum fins bonded to internally grooved copper tubing.
• Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils.
• Supply duct flanges provided as standard on air handler cabinet.
• Provisions for field electrical, connections available from either side or top of the air handler cabinet.
• Connection point for high voltage wiring is inside the air han­dler cabinet. Low voltage connection is made on the outside of the air handler cabinet.
• Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 1
1
/2 inch [38 mm] conduit.
• Front refrigerant and drain connections.
Air
Model Number Identification
RHSL Series
4
Available Models at 115V A Voltage
RHSL-HM1817AA RHSL-HM2417AA RHSL-HM3017AA RHSL-HM3617AA RHSL-HM4221AA RHSL-HM4821AA
Available Models at 218V J Voltage
RHSL-HM1817JA RHSL-HM2417JA RHSL-HM3017JA RHSL-HM3617JA RHSL-HM3621JA RHSL-HM4221JA RHSL-HM4821JA RHSL-HM4824JA RHSL-HM6024JA*
RHSL—HM1817JA
Design Variation
A = 1st Design
Voltage
A = 115/1/60 D = 480V-3-60 J = 208/240/1/60
Cabinet Size
17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1200-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM)
Capacity
18 = 18,000 BTU/H [5.27 kW] 24 = 24,000 BTU/H [7.03 kW] 30 = 30,000 BTU/H [8.79 kW] 36 = 36,000 BTU/H [10.55 kW] 42 = 42,000 BTU/H [12.31 kW] 48 = 48,000 BTU/H [14.06 kW] 60 = 60,000 BTU/H [17.58 kW]
HM = A/C or HP, Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration)
Refrigerant
L = R-410A
S = Standard Model (PSC Motor)
Classification
H = Air Handler
Rheem
[ ] Designates Metric Conversions
Available Models at D Voltage
RHSL-HM3617DA RHSL-HM4221DA RHSL-HM4821DA RHSL-HM4824DA RHSL-HM6024DA
Air
Dimensional Data
RHSL Series
5
ELECTRICAL CONNECTIONS
Unit Dimensions
Return Air Opening Dimensions
Model
Size
RHSL
Refrigerant Connections
Sweat (In.) [mm] ID
Unit
Width
“W” In. [mm]
Unit
Height
“H” In. [mm]
Supply
Duct
“A” In. [mm]
Air Flow
CFM (Nom.) [L/s]
Unit Weight/Shipping Weight
(Lbs.) [kg]
Liquid Vapor
Lo Hi
Unit With
Coil (Max. KW)
1817/24173/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
600 [283] 800 [378] 82/96 [37/44]
3017/3617
3
/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
1000 [472] 1200 [566] 92/106 [37/48]
4221/4821
3
/8 [9.53]
7
/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1400 [661] 1600 [755] 150/166 [68/75]
4824
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 501/2 [1282] 231/2 [584] 1600 [755] 162/180 [73/81]
6024
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584] 1800 [850] 181/198 [82/90]
Unit Dimensions & Weights
*Maximum dehumidification airflow.
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
MAY EXIT TOP OR EITHER SIDE
HIGH VOLTAGE CONNECTION
3
/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS.
1
LOW VOLTAGE CONNECTION
5
/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT
7
/8 [22.2 mm],
SUPPLY AIR
[262 mm]
NOTE: 24 CLEARANCE REQUIRED IN FRONT OF
5
/16
10
UNIT FOR FILTER AND COIL MAINTENANCE.
W
A
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION COPPER (SWEAT)
VAPOR LINE CONNECTION COPPER (SWEAT)
HORIZONTAL ADAPTER KIT
VAPOR LINE
CONNECTION
AUXILIARY HORIZONTAL
DRAIN CONNECTION
191/2 [495 mm]
RETURN AIR
OPENING
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
11
/16
21
[551 mm]
515/16
[151 mm]
H
1
4
[105 mm]
Model
Cabinet Size
Return Air
Opening Width
(Inches)
Return Air Opening
Depth/Length
(Inches)
17 157/8 193/4 21 193/8 193/4 24 227/8 193/4
/8
1
3
/16
3
[76 mm]
1
/16[48 mm]
1
1
/8[29 mm]
1
/16
1
[27 mm]
1
[35 mm]
2
[71 mm]
3
/8
13
/16
1
/4
5
[133 mm]
3
5
/8
[136 mm]
PRIMARY DRAIN
CONNECTION
AUXILIARY UPFLOW/DOWNFLOW
DRAIN CONNECTION
LIQUID LINE CONNECTION
VERTICAL DRAIN PAN
Air
Airflow Directional Data
RHSL Series
6
UPFLOW DOWNFLOW
Airflow Directional Data
HORIZONTAL RIGHT HAND AIRFLOW
HORIZONTAL LEFT HAND AIRFLOW
Air
Airflow Performance Data
RHSL Series
7
Airflow Performance
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for
appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows oper­ation within the minimum and maximum limits shown in table
below for both cooling and electric heat operation. For opti­mum blower performance, operate the unit in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C. external static range.
Airflow Operating Limits
[ ] Designates Metric Conversions
Model Cabinet Size 17 17/21
Cooling BTUH x 1,000 Cooling Tons Nominal
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal)
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal)
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,200 BTUH) (360 CFM [170 L/s]/Ton Nominal)
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s]13487 [230]13617 [291]18814 [384]181054 [497]
Maximum Electric Heat Rise °F [°C] 80 [26.7] 63 [17.2] 66 [18.9] 51 [10.6] 49 [9.4] 50 [10] 50 [10]
-018
1.5
675
[319]
600
[283]
540
[255]
-024 2
900
[425]
800
[378]
720
[340]
-030
2.5
1125
[531]
1000 [472]
900
[425]
21
-036 3
1350 [637]
1200 [566]
1080 [510]
-038
3.5
1350 [637]
1200 [566]
1080 [510]
18
1042 [492]
-042
3.5
1575
[743]
1400 [661]
1260 [595]
20
1171 [553]251502 [709]251502 [709]
-048 4
1800
[850]
1600 [755]
1440 [680]
24
-048 4
1800
[850]
1600
[755]
1440
[680]
-060 5
1930
[911]
1800 [850]
1620 [765]
30
1666 [786]
54 [12.2]52 [11.1]
Air
Airflow Performance Data
RHSL Series
8
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—240 Volts
RPM 571
Blower Size/
Motor
HP [W]
# of Speed
626
Motor Speed
from
Factory
687
Manufacturer Recommended Air-Flow Range (Min/Max) CFM
Motor
Speed
736 791
Watts 171 162 157 152 146
10x6
1/5 HP [149]
2 Speed
High
CFM 661 [312] 612 [289] 564 [266]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
837 878
RPM 541 596 657 706 761
915
Watts 180 171 166 161 109
10x6
1/5 HP [149]
2 Speed
High 240V
487/661 CFM [230/312 L/s]
High
CFM 711 [336] 662 [312] 614 [290]
Low
CFM 638 [301] 607 [286] 565 [267] 530 [250]
RPM 812 853 890
487 [230]
Watts 232 216 199
RPM 616 667 715 770 808
Watts 239 230 221 206 205
10x6
1/5 HP [149]
2 Speed
High
CFM 888 [419] 828 [391] 774 [365]
RPM 875 908 958
High 240V
647/888 CFM [305/419 L/s]
Low
CFM 817 [386] 779 [368] 757 [357] 693 [327] 647 [305]
Watts 331 313 301
RPM 646 697 745 800 838
Watts 230 221 212 197 187
10x6
1/5 HP [149]
2 Speed
High
CFM 838 [395] 778 [367] 724 [342]
RPM 900 933 983
High 240V
617/838 CFM [291/395 L/s]
Low
CFM 787 [371] 749 [353] 727 [343] 663 [313] 617 [291]
Watts
320 302 290
RPM 700 754 794 633 870
Watts 344 313 302 309 288
10x8
1/4 HP [186]
2 Speed
High
CFM 1004 [474] 951 [449] 883 [417]
RPM
High 240V
924
517/711 CFM [244/336 L/s]
Low
CFM 668 [315] 637 [301] 595 [281] 560 [264] 517 [244]
953 975
Watts 243 227 210
High 240V
864/1004 CFM
[408/474 L/s]
Low
CFM 1022 [482] 987 [466] 940 [444] 903 [426] 864 [408]
Watts
364 352 344
RPM 750 804 844 883 920
Watts 324 293 282 274 268
10x8
1/4 HP [186]
2 Speed
High
CFM 904 [427] 851 [402] 783 [370]
RPM 949 978 1000
High 240V
814/904 CFM [384/427 L/s]
Low
CFM 972 [459] 937 [442] 890 [420] 853 [403] 814 [384]
Watts
334 322 314
Model
No.
RHSL
-1817
with 13 kW
Heater
-2417
No Heater
-2417
with 13 kW
Heater
-1817
No Heater
-3017
No Heater
-3017
with 18 kW
Heater
-3617/-3621 No Heater
RPM 788 833 872 909 951
Watts 466 462 427 406 395
10x8
1/3 HP [249]
2 Speed
High
CFM 1248 [589] 1194 [563] 1133 [535]
RPM 1008 1028 1042
High 240V
1104/1248 CFM
[521/589 L/s]
Low
CFM 1229 [580] 1201 [567] 1170 [552] 1141 [538] 1104 [521]
Watts 488 475 454
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
240V Airflow Performance Data—RHSL (PSC Motor)
Air
Airflow Performance Data
RHSL Series
240V Airflow Performance Data—RHSL (PSC Motor)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
9
Model
No.
RHSL
-3617/3621 with 18 kW
Heater
-4221
No Heater
-4221
with 20 kW
Heater
-4821/-4824 No Heater
-4821/-4824
with 25 kW
Heater
-6024
No Heater
-6024
with 30 kW
Heater
Motor
Speed
from
Factory
High
240V
High
240V
High
240V
High
240V
High
240V
High
240V
High
240V
Manufacturer Recommended Air-Flow Range
(Min/Max) CFM
1054/1148 CFM
[497/542 L/s]
1241/1537 CFM
[586/725 L/s]
1225/1500 CFM
[553/678 L/s]
1572/1824 CFM
[742/861 L/s]
1225/1500 CFM
[709/814 L/s]
1766/1965 CFM
[833/927 L/s]
1225/1500 CFM
[709/814 L/s]
Blower Size/
Motor
HP [W]
# of Speed
10x8
1/3 HP [249]
2 Speed
10x10
1/2 HP [373]
2 Speed
10x10
1/2 HP [373]
2 Speed
10x10
3/4 HP [559]
2 Speed
10x10
3/4 HP [559]
2 Speed
11x11
3/4 HP [559]
2 Speed
11x11
3/4 HP [559]
2 Speed
Motor
Speed
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 1179 [556] 1151 [543] 1120 [529] 1091 [515] 1054 [497]
RPM 838 883 922 959 1001
Watts 446 442 407 386 375
CFM 1148 [542] 1094 [516] 1033 [487]
RPM 1033 1053 1067
Watts 458 445 424
CFM 1526 [720] 1474 [696] 1427 [673] 1307 [617]
RPM 834
Watts 560 549 535 476 462
CFM 1537 [725] 1418 [669] 1334 [630]
RPM
Watts 860 835 820
CFM 1456 [687] 1404 [663] 1357 [640] 1237 [584] 1171 [553]
RPM 886 906
Watts 542 524 505 468 431
CFM
RPM 1080 1090 1105
Watts 840 800 785
CFM 1741 [822] 1719 [811] 1667 [787] 1628 [768] 1572 [742]
RPM 878 920 950 981 1007
Watts 785 757 707 667 641
CFM 1824 [861] 1767 [834] 1653 [780]
RPM 1102 1112 1121
Watts
CFM 1671 [789] 1649 [778] 1597 [754] 1558 [735] 1502 [709]
RPM 945 965 995 1025 1050
Watts 715 685 650 630 610
CFM 1724 [814] 1667 [787] 1553 [733]
RPM
Watts
CFM 1944 [917] 1912 [902] 1860 [878] 1813 [856] 1766 [833]
RPM 764 803 838 865 889
Watts 779 763 747 729 708
CFM 1965 [927] 1908 [900] 1854 [875]
RPM 943 967 977
Watts
CFM 1844 [870] 1812 [855] 1760 [831] 1713 [808] 1666 [786]
RPM
Watts 745 729 713 696 678
CFM
RPM
Watts 788 766 744
1072 1077
1437 [678] 1318 [622] 1234 [582]
871 830 770
810 780 730
828 799 795
839
PSC CFM [L/s] Air Delivery/RPM/Watts—240 Volts
External Static Pressure—Inches W.C. [kPa]
1241 [586]
870
865 890 913
902
925 959 992
987 1001 1014
948 968
1865 [880] 1808 [853] 1754 [828]
1116
935
1085
1119 1130
Air
Airflow Performance Data
RHSL Series
10
115V/208V/480V Airflow Performance Data—RHSL (PSC Motor)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• All 115V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and
plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap.
Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the
yellow motor wire.
• Replace the cap on the purple motor wire.
• All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below for 3-ton through 4-ton air handlers.
• Unplug the black motor wire off the relay and remove the cap from the red motor wire.
• Plug the red motor wire to the relay and connect the black motor wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and plug in the red motor wire, then cap the black motor wire. There is no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on 480V PSC motors. Connecting red motor wire with yellow motor wire will result in permanent motor damage.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­(Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
Model
No.
RHSL
-1817
No Heater
-1817
with 13 kW
Heater
-2417
No Heater
-2417
with 13 kW
Heater
-3017
No Heater
-3017
with 18 kW
Heater
-3617/-3621 No Heater
Motor
Speed
from
Factory
High
High
High
High
High
High
High
Manufacturer
Recommended Air-Flow Range (Min/Max) CFM
523/705 CFM [247/333 L/s]
487/661 CFM [230/312 L/s]
647/888 CFM [305/419 L/s]
617/838 CFM [291/395 L/s]
864/1004 CFM
[408/474 L/s]
814/904 CFM [384/427 L/s]
1104/1248 CFM
[521/589 L/s]
Blower Size/
Motor
HP [W]
# of Speed
10x6
1/5 HP [149]
2 Speed
10x6
1/5 HP [149]
2 Speed
10x6
1/5 HP [149]
2 Speed
10x6
1/5 HP [149]
2 Speed
10x8
1/4 HP [186]
2 Speed
10x8
1/4 HP [186]
2 Speed
10x8
1/3 HP [249]
2 Speed
Motor
Speed
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 681 [321] 636 [300] 606 [286] 567 [268] 523 [247]
RPM 541 601 670 714 768
Watts 193 181 173 164 157
CFM 705 [333] 650 [307] 599 [283]
RPM 815 861 989
Watts 239 227 204
CFM 651 [307] 606 [286] 576 [272] 537 [253] 493 [233]
RPM 571 631 700 744 798
Watts 184 172 164 155 148
CFM 655 [309] 600 [283] 549 [259]
RPM 840 886 1014
Watts 228 216 193
CFM 875 [413] 806 [380] 787 [371] 739 [349] 682 [322]
RPM 648 700 745 794 827
Watts 259 255 243 234 227
CFM 897 [423] 851 [402] 765 [361]
RPM 906 925 955
Watts 332 318 306
CFM 845 [399] 776 [366] 757 [357] 709 [335] 652 [308]
RPM 678 730 775 824 857
Watts 250 246 234 225 218
CFM 847 [400] 801 [378] 715 [337]
RPM 931 950 980
Watts
CFM 1038 [490] 1010 [477] 976 [461] 925 [437] 883 [417]
RPM 721 771 799 848 880
Watts 325 314 303 290 286
CFM 1015 [479] 963 [454] 890 [420]
RPM 928 955 974
Watts
CFM 988 [466] 960 [453] 926 [437] 875 [413] 833 [393]
RPM 771 821 849 898 930
Watts 305 294 283 270 266
CFM 915 [432] 863 [407] 790 [373]
RPM 953 980 999
Watts
CFM 1201 [567] 1170 [552] 1141 [538] 1104 [521] 1062 [501]
RPM 833 872 909 951 965
Watts 462 427 406 396 385
CFM 1194 [563] 1134 [535] 1078 [509]
RPM 1024 1042 1060
Watts 475 454 417
321 307 295
356 341 329
326 311 299
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/480 Volts
11
115V/208V/480V Airflow Performance Data—RHSL (PSC Motor)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• All 115V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and
plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap.
Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the
yellow motor wire.
• Replace the cap on the purple motor wire.
• All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below for 3-ton through 4-ton air handlers.
• Unplug the black motor wire off the relay and remove the cap from the red motor wire.
• Plug the red motor wire to the relay and connect the black motor wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and plug in the red motor wire, then cap the black motor wire. There is no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on 480V PSC motors. Connecting red motor wire with yellow motor wire will result in permanent motor damage.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater ­(Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
Air
Airflow Performance Data
RHSL Series
Model
No.
RHSL
-3617/3621 with 18 kW
Heater
-4221
No Heater
-4221
with 20 kW
Heater
-4821/-4824 No Heater
-4821/-4824
with 25 kW
Heater
-6024
No Heater
-6024
with 30 kW
Heater
Motor
Speed
from
Factory
High
High
High
High
High
High
High
Manufacturer
Recommended Air-Flow Range (Min/Max) CFM
1054/1148 CFM
[497/542 L/s]
1241/1537 CFM
[580/725 L/s]
1225/1500 CFM
[538/667 L/s]
1512/1824 CFM
[742/801 L/s]
1225/1500 CFM
[695/796 L/s]
1766/1965 CFM
[833/927 L/s]
1225/1500 CFM
[695/796 L/s]
Blower Size/
Motor
HP [W]
# of Speed
10x8
1/3 HP [249]
2 Speed
10x10
1/2 HP [373]
2 Speed
10x10
1/2 HP [373]
2 Speed
10x10
3/4 HP [559]
2 Speed
10x10
3/4 HP [559]
2 Speed
11x11
3/4 HP [559]
2 Speed
11x11
3/4 HP [559]
2 Speed
Motor
Speed
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
High
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 1151 [543] 1120 [529] 1091 [515] 1054 [497] 1012 [478]
RPM 883 922 959 1001 1015
Watts 442 407 386 376 365
CFM 1094 [516] 1034 [488] 978 [462]
RPM 1049 1067 1085
Watts 445 424 387
CFM 1493 [705] 1449 [684] 1363 [643] 1287 [607]
RPM 822
Watts 540 519 506 484 459
CFM 1514 [714] 1411 [666] 1315 [621]
RPM
Watts 710 702 677
CFM 1423 [672] 1379 [651] 1293 [610] 1217 [574] 1141 [538]
RPM 870 882
Watts 514 508 490 461 431
CFM
RPM 1067 1080 1094
Watts 700 678 665
CFM 1711 [807] 1689 [797] 1637 [773] 1598 [754] 1542 [728]
RPM 863 905 935 966 992
Watts 765 737 687 647 621
CFM 1787 [843] 1679 [792] 1575 [743]
RPM 1089 1098 1110
Watts
CFM 1641 [774] 1619 [764] 1567 [739] 1528 [721] 1472 [695]
RPM 930 950 985 1015 1041
Watts 700 660 630 600 580
CFM 1687 [796] 1579 [745] 1475 [696]
RPM
Watts
CFM 1866 [881] 1833 [865] 1806 [852] 1772 [836] 1710 [807]
RPM 764 803 824 856 886
Watts 778 756 733 715 701
CFM 1967 [928] 1916 [904] 1863 [879]
RPM 948 959 991
Watts
CFM 1796 [848] 1763 [832] 1736 [819] 1702 [803] 1640 [774]
RPM
Watts 735 718 705 695 678
CFM
RPM
Watts 818 795 780
1061 1069
1414 [667] 1311 [619] 1215 [573]
695 665 630
670 635 615
850 827 816
828
External Static Pressure—Inches W.C. [kPa]
858
860 878 890
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/480V Volts
1211 [571]
885
925 957 992
989 1005 1020
931 958
1078
1867 [881] 1816 [857] 1763 [832]
1095
1001
1107 1120
Air
Electrical Data
RHSL Series
12
Model
RHLL
Voltage
Application
Phase*
Hertz HP [W] RPM Speeds
Circuit Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
1817
115 1 60
1/5 [149] 1075 2 2.3 3.0 15 2417 1/5 [149] 1075 2 3.8 5.0 15 3017 1/4 [186] 1075 2 4.7 6.0 15 3617 1/3 [249] 1075 2 6.1 8.0 15 4221 1/2 [373] 1075 2 7.9 10.0 15 4821 3/4 [559] 1075 2 8.4 11.0 15
4221 1/2 [373] 1075 2 5.2 7.0 15
3617/5621 1/3 [249] 1075 2 2.5 4.0 15
4821/4824 3/4 [559] 1075 2 5.2 7.0 15
1817
208/240 1 & 3 60
1/5 [149] 1075 2 1.7 3.0 15 2417 1/5 [149] 1075 2 1.7 3.0 15 3017 1/4 [186] 1075 2 2.5 4.0 15
4221 1/3 [249] 1075 2 2.1 3.0 15
3617
480 3 60
1/3 [249] 1075 2 1.4 2.0 15
4821/4824 3/4 [559] 1075 2 2.2 3.0 15
6024 480 3 60 3/4 [559] 1075 2 2.2 3.0 15
6024 208/240 3 60 3/4 [559] 1075 2 5.2 7.0 15
Electrical Data – Blower Motor Only – No Electric Heat
* Blower motors are all single phase motors.
[ ] Designates Metric Conversions
Air
Electrical Data
RHSL Series
13
Air Handler
Model
RHSL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protection
1817/2417
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE 10.8/12.5 1.7 16/18 20/20
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 1.7 24/28 25/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 1.7 35/40 35/40
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 1.7 46/53 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 1.7 59/68 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15./17.4 1.7 21/24 25/25
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 1.7 21/24 25/25
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 1.7 28/31 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 1.7 35/40 35/40
3017/3617
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE
10.8/12.5 2.5 17/19 20/20
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 2.5 25/29 25/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 2.5 36/41 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 2.5 47/54 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 2.5 60/69 602/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 2.5 22/25 25/25
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 2.5 68/79 70/80
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 2.5 25/29 25/30
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 2.5 81/92 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 2.5 29/33 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 2.5 22/25 25/25
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 2.5 29/32 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 2.5 36/41 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 2.5 41/47 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 2.5 48.55 50/60
RXBH-17A07D 7.2 3/60 2-3.6 SINGLE
8.7 1.4 13 15
RXBH-17A10D 9.6 3/60 3-3.2 SINGLE
11.6 1.4 17 20
RXBH-17A15D 14.4 3/60 3-4.8 SINGLE
17.3 1.4 24 25
RXBH-17A18D 17 3/60 3-5.68 SINGLE
20.4 1.4 28 30
3621
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 2.5 25/29 25/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 2.5 36/41 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 2.5 47/54 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 2.5 60/69 602/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 2.5 22/25 25/25
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 2.5 68/79 70/80
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 2.5 25/29 25/30
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 2.5 81/92 90/100
Electrical Data – With Electric Heat
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Air
Electrical Data
RHSL Series
14
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
Air Handler
Model
RHSL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protection
3621
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1 20.5/23.6 2.5 29/33 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 2.5 22/25 25/25
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 2.5 29/32 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 2.5 36/41 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 2.5 41/47 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 2.5 48.55 50/60
RXBH-17A07D 7.2 3/60 2-3.6 SINGLE
8.7 1.4 13 15
RXBH-17A10D 9.6 3/60 3-3.2 SINGLE
11.6 1.4 17 20
RXBH-17A15D 14.4 3/60 3-4.8 SINGLE
17.3 1.4 24 25
RXBH-17A18D 17 3/60 3-5.68 SINGLE
20.4 1.4 28 30
4221/4821
4824
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 5.2 29/32 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 5.2 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 5.2 50/57 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 5.2 72/82 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 5.2 29/32 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 5.2 84/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 5.2 33/36 35/40
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 5.2 93/107 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 5.2 50/57 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J (4-ton only) 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 5.2 115/132 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1
28.8/33.3 5.2 43/49 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 5.2 26/29 30/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 5.2 32/36 35/40
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 5.2 44/50 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-2.84 SINGLE
35.6/41.0 5.2 51/58 60/60
RXBH-1724A18C
4.3/5.7 3/60 3 - 2.84 MULTIPLE CKT 1
17.8/20.5 5.2 29/33 30/35
8.7/11.3 3/60 3 - 2.84 MULTIPLE CKT 2
17.8/20.5 0.0 23/26 25/30
RXBH-24A20C 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 5.2 57/65 60/70
RXBH-24A20C
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1
20.0/23.1 5.2 32/36 35/40
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C (4-ton only) 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 5.2 69/79 70/80
RXBH-24A25C (4-ton only)
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 5.2 38/43 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
RXBH-24A07D 7.2 3/60 2-3.6 SINGLE
8.7 2.2 14 15
RXBH-24A10D 9.6 3/60 3-3.2 SINGLE
11.6 2.2 18 20
RXBH-24A15D 14.4 3/60 3-4.8 SINGLE
17.3 2.2 25 25
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Air
Electrical Data
RHSL Series
15
Air Handler
Model
RHSL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protection
4221/4821/
4824
RXBH-24A18D 17.0 3/60 3-5.68 SINGLE 20.4 2.2 29 30
RXBH-24A20D 19.2 3/60 6-3.2 SINGLE
23.2 2.2 32 35
RXBH-24A25D (4-ton only) 24.0 3/60 6-4.0 SINGLE
28.8 2.2 39 40
6024
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 5.2 29/32 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 5.2 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 5.2 50/57 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 5.2 72/82 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 5.2 29/32 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 5.2 84/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 5.2 33/36 35/40
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 5.2 93/107 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 5.2 50/57 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 5.2 115/132 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1
28.8/33.3 5.2 43/49 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-24A30J 21.6/28.8 1/60 6-4.8 SINGLE
103.8/120 5.2 137/157 150/175
RXBH-24A30J
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1
34.6/40.0 5.2 50/57 50/6
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
7.2/9.6 1/60 2-4.8 MULTPLE CKT 3
34.6/40.0 0.0 44/50 45/50
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 5.2 26/29 30/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 5.2 32/36 35/40
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 5.2 44/50 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-2.84 SINGLE
35.6/41.0 5.2 51/58 60/60
RXBH-1724A18C
6.4/8.5 3/60 3 - 2.84 MULTIPLE CKT 1
17.8/20.5 5.2 29/33 30/35
6.4/8.5 3/60 3 - 2.84 MULTIPLE CKT 2
17.8/20.5 0.0 23/26 25/30
RXBH-24A20C 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 5.2 57/65 60/70
RXBH-24A20C
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1
20.0/23.1 5.2 32/36 35/40
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 5.2 69/79 70/80
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 5.2 38/43 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
RXBH-24A07D 7.2 3/60 2-3.6 SINGLE
8.7 2.2 14 15
RXBH-24A10D 9.6 3/60 3-3.2 SINGLE
11.6 2.2 18 20
RXBH-24A15D 14.4 3/60 3-4.8 SINGLE
17.3 2.2 25 25
RXBH-24A18D 17.0 3/60 3-5.68 SINGLE
20.4 2.2 29 30
RXBH-24A20D 19.2 3/60 6-3.2 SINGLE
23.2 2.2 32 35
RXBH-24A25D 24.0 3/60 6-4.0 SINGLE
28.8 2.2 39 40
RXBH-24A30D 28.8 3/60 6-4.8 SINGLE
34.6 2.2 46 50
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Air
Electrical Wiring
RHSL Series
16
Electrical Wiring
Power Wiring
• Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance.
• Supply wiring must be 75°C minimum copper conductors only.
• See electrical data for product Ampacity rating and Circuit Protector requirement.
Grounding
• This product must be sufficiently grounded in accordance with National Electrical Code (C.E.C. in Canada) and any applicable local ordinance.
• A grounding lug is provided.
RXHF-
Accessories
Auxiliary Horizontal Overflow Pan Accessory RXBM-
Combustible Floor Base RXHB-
Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple three circuit units to a single supply circuit. Kit includes cover and screw for line side terminals.
Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple two circuit units to a single supply circuit. Kit includes cover and screw for line side terminals.
Note: No jumper bar kit is available to convert three phase multiple two circuit units to a single supply circuit.
Auxiliary Electric Heater Kits RXBH- Heater Kits include circuit breakers which meet UL and cUL requirements for service disconnect. See the Electric Heat Electrical Data in this specification sheet for specific Heater Kit Model numbers.
Horizontal Adapter Kit RXHH- This horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit.
Nominal Cooling
Capacity-Tons
Auxiliary Horizontal Overflow Pan
Accessory Model Number
11/2 - 3
RXBM-AC48
31/2 - 5 RXBM-AC61
RXHF-B
B
A
B
A
11/2
[38 mm]
External Filter Base RXHF-
*Accommodates 1" or 2" filter
[ ] Designates Metric Conversions
Model Cabinet Size Filter Size In. [mm]
17 16 x 20 [406 x 508] 21 20 x 20 [508 x 508]
Part Number*
RXHF-17 RXHF-21 RXHF-2424 25 x 20 [635 x 508] 22.70
19.20
15.70
A
25.5
21.0
17.5
B
Model Cabinet Size Part Number*
RXHF-B17 RXHF-B21
Filter Size In. [mm]
RXHF-B24
24
25 x 20 [635 x 508]
17
16 x 20 [406 x 508]
21
20 x 20 [508 x 508]
A
16.90
20.40
25.00
B
20.77
20.77
21.04
External Filter Rack RXHF-B17, B21, B24
*Accommodates 1" filter
Coil Model
Horizontal Adapter Kit
Model Number (10-Pack Qty.)
RXHH-A01 x 10 RXHH-A02 x 10
Horizontal Adapter Kit
Model Number (Single Qty.)
RXHH-A03 x 103617/3621 RXHH-A03
2414 RXHH-A01 2417 RXHH-A02
3821/4821/4824 RXHH-A04 RXHH-A04 x 10
8024 RXHH-A05 RXHH-A05 x 10
Model Cabinet Size
17 21 24
Combustible Floor
Base Model Number
RXHB-17 RXHB-21 RXHB-24
Air
Limited Warranty
RHSL Series
17
GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.
Conditional Parts (Registration Required) ..........Ten (10) Years
*For complete details of the Limited and Conditional Warranties, including
applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
Air
Notes
RHSL Series
18
Air
Notes
RHSL Series
19
The new degree of comfort.
Rheem Heating, Cooling & Water Heating • P.O. Box 17010
Fort Smith, Arkansas 72917 • www.rheem.com
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
PRINTED IN U.S.A 11/12 QG FORM NO. H11-550