Rheem RH-EVR Series, Rheem S-SS Series Installation, Operation And Maintenance Manual

Page: 1 / 8
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Commercial Electric Water Heater
Model : Rheem RH-EVR/S-SS Series
Installation and service must be
performed by
Qualified Service Personnel Only.
This manual supplies information for the installation, operation and servicing of the appliance. It is strongly recommended that this manual be reviewed completely before proceeding with an installation. Upon receiving equipment, check for signs of shipping damage. Pay particular attention to parts accompanying the water heater, which may show signs of being hit or otherwise being mishandled. Verify total number of pieces shown on packing slip with those actually received. In case there is damage or a shortage, immediately notify carrier.
INSTALLATION PROCEDURE
LOCATION OF UNIT
1. Locate the appliance so that if water
connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the unit. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this unit, or any of its components.
2. Insure that the appliance is located near
an acceptable drain so that the vessel can be properly drained when performing service or maintenance. The drain must also provide adequate drainage in the event of leakage the tank or related piping. The drain must prevent water
damage to the adjacent area and lower floors of the structure.
3. The appliance must be installed so that
the electrical components are protected from water (dripping, spraying, etc.) during appliance operation and service (replacing of fuses, elements, etc.)
4. The appliance must be installed on a level
floor. Shim the base as necessary if leveling is required.
5. The floor on which the appliance is
installed must be capable of supporting the total weight of the water heater when completely filled with water. Combustible floor locations may be used. Maintain required clearances from combustible surfaces.
6. The appliance must not be installed on
carpet.
7. The appliance must be installed indoors
where it is protected from exposure to wind, rain and weather.
8. Locate the appliance as close as possible
to the point of major hot water usage, the water piping and branch electrical circuit wiring.
9. Insulate water piping to control heat loss
and possible condensation.
10. The appliance must be located in an area
that is not subject to freezing. The ambient temperature of the space where the appliance is installed must not go below 32° F (0° C) or above 104° F (40° C).
11. The water heater is not intended for space
heating applications.
Page: 2 / 8
Minimum Clearences Between Water Heater and Surrounding Surfaces
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the electrical components, water pipe connections, piping and other auxiliary equipment, as well as the appliance.
WATER CONNECTIONS
Inlet and Outlet Connections
For ease of service, install unions on the cold water inlet and hot water outlet of the water heater. The cold water inlet connection is located on the lower right side of the water heater. A manual shutoff valve should be installed upstream on the cold water source as an isolation device. The hot water outlet connection is located on the top center of the water heater. A manual shutoff valve should be installed downstream on the hot water outlet source as an isolation device in case the water heater must be disconnected from the system.
STORAGE TANK
This appliance uses AISI 304L quality stainless steel tank to store the heated water for use. The storage tank is constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements. The volume capacity of storage tank is approximately 1000 liters (265 gal). Please refer to the attached mechanical general arrangement dimensional drawing of storage tank. The tank is furnished with threaded connections for cold water inlet, hot water outlet, recirculation, a relief valve and a drain connection. The storage tank has a hand hole for ease of inspection, cleanout and service. An optional manhole may be specified for greater ease of inspection. A magnesium anode(s) is standard to help prevent dissipation of the tank material by electrolytic action.
JACKET ASSEMBLY
Outer Jacket – The outer jacket assembly is constructed from steel, galvanized on both sides. The galvanized surface is specially prepared and phosphate coated to allow application of electrostatic paint process. This coating process insures a long life from the jacket assembly. The storage tank is insulated by rock wool material covered by outer jacket.
Page: 3 / 8
RELIEF VALVE
This water heater is supplied with a temperature and pressure relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV. The relief valve(s) is installed in the horizontal position and mounted in the tapping provided in the storage tank. No valve is to be placed between the relief valve and the water heater. To prevent water damage, the discharge from the relief valve must be piped to a suitable floor drain for disposal when relief occurs. No reducing couplings or other restrictions shall be installed in the discharge line. The discharge line shall allow complete drainage of the valve and line. Relief valves should be manually operated at least once a year. A relief valve that fails to completely reseat and continues to discharge water must be immediately replaced with a new, properly sized, temperature and pressure relief valve.
CAUTION: Avoid contact with hot
discharge water. Insure that no one is in front of or around the relief valve discharge line. Make sure that the extremely hot water manually discharged from the relief valve will not cause bodily injury or property damage.
CAUTION:L EXPANSION OF WATER
THERMAL EXPANSION OF WATER
A relief valve that discharges periodically may be due to thermal expansion in a closed system. A water heater installed in a closed system, such as one with a backflow preventer or check valve installed in the cold water supply, shall be provided with means to control expansion. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT plug or cap the relief valve.
ELECTRICAL CONNECTIONS
All installation procedures involving electric power connection should only be performed by a trained, certified electrician.
WARNING: WATER HEATER IS EQUIPPED
FOR OPERATION ON ONE VOLTAGE ONLY. Check the rating plate on the front of the
control panel access for the correct voltage and phase. DO NOT use this water heater with any other voltage other than the voltage specified on the rating plate. Failure to use the correct voltage can cause problems that can result in death, serious bodily injury or property damage.
CAUTION: THE SUPPLY VOLTAGE OF THE
WATER HEATER IS 415VAC, 3 PHASE, 60 HZ. DO NOT CONNECT THE WATER HEATER TO AN IMPROPER SOURCE OF ELECTRICITY!
1. Use copper conductors only. All wiring
between the appliance and field installed devices shall be made with copper wire suitable for at least 75° C (167° F) temperature rating.
2. The factory internal wiring is attached to a
terminal block inside the unit. The branch circuit is connected to the terminal block through an opening provided on the side of the water heater electrical access panel.
3. Line voltage wire exterior to the appliance
must be enclosed in approved conduit or approved metal clad cable.
4. To avoid serious damage, DO NOT energize
the appliance until the system is full of water. Ensure that all air is removed from the
storage tank and piping before beginning initial operation. Operation of a water heater without a completely filled tank may result in serious damage to the appliance and heating element burn out.
5. The water heater should be connected with a
separate grounded branch circuit with over current protection and disconnect switch. The water heater should be grounded in accordance with national and local codes. A ground terminal is provided for ground connection only.
Page: 4 / 8
6. Provide the appliance with proper overload
protection in the branch circuit. It is suggested that the electrician size the branch circuit at 125 percent of the heater ampere rating and further increase wire size as necessary to compensate for voltage drop in long runs. Branch circuit voltage drop should not exceed 3% at the heater.
7. Voltage applied to the heater should not vary
more than +5% to -10% of the model and rating plate marking for satisfactory operation.
8. A wiring diagram is provided with the water
heater for the electricians use.
LOW WATER CUTOFF
This water heater is equipped with an electronic low water cut-off installed at the factory. This low water cut-off device uses a water level sensing probe located above the heating element installed in the highest point in the storage tank. If the internal water level drops below this point, the low water cut-off will shut down operation of the heating elements. The electronic low water cut-off has an LED located on its casing. This LED will be illuminated and the control circuit will be completed between the common and normally open contacts on the relay unit when the sensing probe is below the water level in the storage tank. The operation of a low water cutoff should be inspected every six months. For details refer to electrical control circuit drawing attached to this manuel.
STANDARD EQUIPMENT
Your commercial electric water heater is equipped with the following as standard equipment.
Low watt density immersion heating
elements with an stainless steel sheath. Each heating element has 18 KW power and two elements are grouped so the group power is 36 KW. There are 4 groups of elements making the total input power 144 KW.
Internal fusing of all elements in a
maximum of 48 amp increments provides additional safety.
Electrostatic paint coated galvanized steel
outer jacket and electrical control panel are provided.
Electrical control panel is provided with a
hinged door and key lock.
An AISI 304L stainless steel tank
constructed to ASME specifications and provided with magnesium anode(s).
ASME rated temperature and pressure
relief valve provided by factory to ensure safe heater operation.
Terminal block connections are installed
by the factory for safe easy wiring connection.
Manual reset high water temperature limit
control.
Surface mounted mechanical thermostats
for each heater group. Max temperature setting 162°F (72 °C)
3 year limited warranty provides
protection against failure of tanks due to defects in material and workmanship in commercial application.
Four groups of heating elements are
controlled by four regulating thermostats as one thermostat for each group.
Time relays are provided to turn on the
heater groups in sequence with a user defined time delay between each group.
Manual on-off switches for each heater
group with pilot lights.
Page: 5 / 8
MECHANICAL THERMOSTATS
Temperature regulating thermostat
High Limit thermostat with manual reset
This water heater uses mechanical surface mounted thermostats to activate magnetic contactors allowing current to flow to the immersion heating elements. The standard control system uses one immersion thermostat for each 36kW of electric heating power in a water heater.
TEMPERATURE REGULATING
THERMOSTATS
This water heater has an adjustable thermostat to control water temperature. The thermostat is factory pre-set at approximately 125° F (51.7° C) or less. Households with small children or invalids may require a 120° F (48.9° C) or lower temperature setting to reduce risk of scald injury. Remember, no water heating system will provide exact temperatures at all times. Allow a few days of operation at the setting to determine the correct temperature setting consistent with your needs.
WATER TEMPERATURE SETTINGS
1. Turn “OFF” the electrical power to the
water heater.
2. Open the thermostat cover on the tank.
3. Adjust each thermostat to the
desired temperature setting by turning the adjusting knob from hot to very hot position to increase the temperature. When the knob is at very hot position the adjusted temperature is max. 72 ° C. Each thermostat will be factory pre-set to approximately 125° F (51.7° C) or less as shipped.
4. Close the thermostat cover.
5. Turn “ON” the electrical power to the
water heater.
WARNING:
HAZARD OF ELECTRICAL SHOCK – Before opening the electrical access panel to adjust the thermostat make sure the electrical supply to the water heater is
turned “OFF”.
HIGH WATER TEMPERATURE
LIMIT CONTROL
The unit is equipped with a fixed setting, manual reset high water temperature limit control. The water heater temperature limit control has a fixed limit setting of 180° F (82 ° C). If water temperature exceeds the limit set point, the limit will break the control circuit and shut down the unit. The limit control can only be reset after the water temperature has cooled below the set point of the limit. The high water temperature limit control is mounted on the surface of the tank, above the heating element installed at the highest point in the tank. The high limit control is reset by pushing the red reset button on the control. Operation of the limit control usually indicates a major problem with the thermostat, contactors or heating elements. Do not continue to push the reset multiple times. The source of the problem
Loading...
+ 10 hidden pages