FOR UPFLOW AND DOWNFLOW/HORIZONTAL
HIGH EFFICIENCY CONDENSING TWO-STAGE
GAS FURNACES
RGRK, RGRL, AND RGTK SERIES
U.L. recognized fuel gas and CO (carbon monoxide) detectors are recommended in all
applications, and their installation should be in accordance with the manufacturer’s
recommendations and/or local laws, rules, regulations, or customs.
((-)XGY-D02, -D03 OR -D04) – US
((-)XGY-D02A, -D03A, -D04A) – CANADA
DUCT STATIC PRESSURE
______ in. w.c. on heating speed
______ in. w.c. on cooling speed
______ Air temperature rise
CONDENSATE LINE
______ Trap filled with water
______ Vented
______ Sloped toward drain
______ Condensate drain line hoses connected
and clamped
______ Freeze protection (if necessary)
VENTING – DIRECT VENT
______ in. diameter – intake pipe
______ in. diameter – exhaust pipe
______ ft. of pipe – intake air
______ Correct relationship – exhaust to intake
______ Above anticipated snow level
VENTING – NON-DIRECT VENT
______ in. diameter – exhaust pipe
______ ft. of pipe – exhaust
______ no. of elbows
TERMINATION – NON-DIRECT VENT
VERTICAL
______ 12" min. above roof/snow level
HORIZONTAL – STANDARD
______ 12" min. above grade/snow level
HORIZONTAL – ALTERNATE
______ Above anticipated snow level
______ no. of elbows – intake air
______ ft. of pipe – exhaust pipe
______ no. of elbows – exhaust pipe
______ Exhaust Vent Temperature
2
_____________________________ Model Number
_____________________________ Serial Number
_____________________________ Date of Installation
Page 3
IMPORTANT: All manufacturer
products meet current Federal OSHA
Guidelines for safety. California
Proposition 65 warnings are required
for certain products, which are not
covered by the OSHA standards.
California's Proposition 65 requires
arnings for products sold in California
w
that contain, or produce, any of over
600 listed chemicals known to the State
f California to cause cancer or birth
o
defects such as fiberglass insulation,
lead in brass, and combustion products
rom natural gas.
f
All “new equipment” shipped for sale in
California will have labels stating that
the product contains and/or produces
Proposition 65 chemicals. Although we
have not changed our processes,
having the same label on all our
products facilitates manufacturing and
shipping. We cannot always know
“when, or if” products will be sold in the
California market.
You may receive inquiries from
customers about chemicals found in, or
produced by, some of our heating and
air-conditioning equipment, or found in
natural gas used with some of our
products. Listed below are those
chemicals and substances commonly
associated with similar equipment in
our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the
Websites for OSHA (Occupational
Safety and Health Administration), at
www.osha.gov
California's OEHHA (Office of
Environmental Health Hazard
Assessment), at www.oehha.org.
Consumer education is important since
the chemicals and substances on the
list are found in our daily lives. Most
consumers are aware that products
present safety and health risks, when
improperly used, handled and
maintained.
NOTE: A load calculation must be
performed to properly determine the
required furnace BTU size for the
structure. Also, the duct must be properly
designed and installed for proper airflow.
Existing ductwork must be inspected for
proper size and sealed system. Proper
airflow is necessary for both user comfort
and equipment performance.
Before opening the furnace carton and
installation of the furnace, verify the data
tags on the carton and inside the
furnace, match and is what was ordered
from the local distributor. Also, check for
any damage to the furnace before
installation.
IMPORTANT: Proper application,
installation and maintenance of this
furnace and system is a must if
consumers are to receive the full benefits
for which they have paid.
The (-)GRK-, (-)GRL-, (-)GTK- series
furnaces are design-certified by CSA for
use with natural and propane gases as
FIGURE 1
UPFLOW FURNACE COMPONENTS
follows:
1. As non-direct vent central forced air
furnaces taking combustion air from
the installation area or using air
ducted from the outside.
2. As direct vent central forced air
furnaces with all combustion air
supplied directly to the furnace
burners through a special air intake
system outlined in these
instructions.Install this furnace in
accordance with the American
National Standard Z223.1 – latest
edition entitled “National Fuel Gas
Code” (NFPA54) and requirements
or codes of the local utilities or
other authorities having jurisdiction.
This is available from the following:
National Fire Protection
Association, Inc.
Batterymarch Park
Quincy, MA 02269
OWNFLOW/HORIZONTAL FURNACE COMPONENTS
D
AIRFLOW
3
2
CSA-INTERNATIONAL
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
Install units in Canada in accordance
with CSA-B149, local installation
codes and authorities having
jurisdiction. CSA-B149 is available
from:
NOTE: It is our recommendation that
any HVAC equipment which were
subject to flooding be replaced to
avoid any risk of property damage,
personal injury or death. Also, our
position that the immersion by flood
waters compromises any HVAC
products thus voiding this warranty.
15
12
23
22
9
8
ITEM
NO. PART NAME
1CONDENSATE TRAP
2DOOR SWITCH
3JUNCTION BOX
4TRANSFORMER
5PRESSURE SWITCHES
6EXHAUST TRANSITION
7CONNECTOR
8OUTLET AIR PIPE
NOTE: A PARTS BAG IS INCLUDED WITH THE FURNACE. IF A NEW
PARTS BAG NEEDS TO BE ORDERED, USE THE FOLLOWING PART
NUMBERS: AS-100717-01 FOR (-)GRL-45, (-)GRL-60, (-)GRK-75, (-)GRL90 AND (-)GRK-105 AS-100717-02 FOR (-)GRK-120
9SHIPPING PLUG (TO BE REMOVED)
10FLAME SENSOR
11OVERTEMPERATURE SWITCH
12TOP PLATE
13BURNER
14IGNITER
15COMBUSTION AIR INLET
16OPTIONAL AIR INLET (UPFLOW UNITS ONLY)
17OPTIONAL GAS INLET
18GAS VALVE
21
20
19
5
18
10
11
25
19INDUCED DRAFT BLOWER
20CAPACITORS
21BLOWER
22LOW VOLTAGE TERMINAL
23CONTROL MOUNTING PLATE
24FILTER / SOLID METAL BASEPLATE (UPFLOW
UNITS ONLY)
25BURNER COVER PLATE
NOTE: A PARTS BAG IS INCLUDED WITH THE FURNACE. IF A NEW
PARTS BAG NEEDS TO BE ORDERED, USE THE FOLLOWING PART
NUMBERS: AS-100717-03 FOR (-)GTK-60, (-)GTK-75, (-)GTK-90, (-)GTK105 AND (-)GTK-120
7
(DOWNFLOW/HORIZONTAL UNITS ONLY)
6
13
4
AIRFLOW
17
1
14
4
Page 5
IMPORTANT INFORMATION
ABOUT EFFICIENCY AND
INDOOR AIR QUALITY
Central cooling and heating equipment
is only as efficient as the duct system
that carries the cooled or heated air. To
maintain efficiency, comfort and good
indoor air quality, it is important to have
he proper balance between the air
t
being supplied to each room and the air
returning to the cooling and heating
equipment.
Proper balance and sealing of the duct
system improves the efficiency of the
heating and air conditioning system
and improves the indoor air quality of
the home by reducing the amount of
airborne pollutants that enter homes
from spaces where the ductwork and /
or equipment is located. The
manufacturer and the U.S.
Environmental Protection Agency’s
Energy Star Program recommend that
central duct systems be checked by a
qualified contractor for proper balance
and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND DRAW
POLLUTANTS SUCH AS DIRT, DUST,
FUMES AND ODORS INTO THE
HOME CAUSING PROPERTY
DAMAGE. FUMES AND ODORS
FROM TOXIC, VOLATILE OR
FLAMMABLE CHEMICALS, AS WELL
AS AUTOMOBILE EXHAUST AND
CARBON MONOXIDE (CO), CAN BE
DRAWN INTO THE LIVING SPACE
THROUGH LEAKING DUCTS AND
UNBALANCED DUCT SYSTEMS
CAUSING PERSONAL INJURY OR
DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL JOINTS,
SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST BE
SEALED TO LIMIT THE MIGRATION
OF TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE
FROM MIGRATING INTO THE
LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH AS
WATER HEATERS OR BOILERS ALL JOINTS, SEAMS, AND
OPENINGS IN THE EQUIPMENT
AND DUCT MUST ALSO BE
SEALED TO PREVENT
DEPRESSURIZATION OF THE
SPACE AND POSSIBLE
MIGRATION OF COMBUSTION
BYPRODUCTS INCLUDING
CARBON MONOXIDE INTO THE
LIVING SPACE.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITH THE CSA
INTERNATIONAL (CSA)
CERTIFICATION OR THESE
INSTRUCTIONS, CAN RESULT IN
UNSATISFACTORY OPERATION
AND/OR DANGEROUS CONDI-TIONS
AND ARE NOT COVERED BY THE
UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH
RECOGNIZED CODES, IT IS
RECOMMENDED THAT AN
AUXILIARY DRAIN PAN BE
INSTALLED UNDER ALL
EVAPORATOR COILS OR UNITS
CONTAINING EVAPORATOR COILS
THAT ARE LOCATED IN ANY AREA
OF A STRUCTURE WHERE DAMAGE
TO THE BUILDING OR BUILDING
CONTENTS MAY OCCUR AS A
RESULT OF AN OVERFLOW OF THE
COIL DRAIN PAN OR A STOPPAGE
IN THE PRIMARY CONDENSATE
DRAIN PIPING. SEE ACCESSORIES
SECTION OF THESE INSTRUCTIONS
FOR AUXILIARY HORIZONTAL
OVERFLOW PAN INFORMATION
(MODEL (-)XBM).
RECEIVING
Immediately upon receipt, all cartons
and contents should be inspected for
transit damage. Units with damaged
cartons should be opened immediately.
If damage is found, it should be noted
on the delivery papers, and a damage
claim filed with the last carrier.
• After unit has been delivered to job
site, remove carton taking care not to
damage unit.
• Check the unit rating plate for unit
size, electric heat, coil, voltage,
phase, etc. to be sure equipment
matches what is required for the
job specification.
• Read the entire instructions before
starting the installation.
• Some building codes require extra
cabinet insulation and gasketing
when unit is installed in attic
applications.
• If installed in an unconditioned
space, apply caulking around the
power wires, control wires,
refrigerant tubing and condensate
line where they enter the cabinet.
Seal the power wires on the inside
where they exit conduit opening.
Caulking is required to prevent air
leakage into and condensate from
forming inside the unit, control box,
and on electrical controls.
• Install the unit in such a way as to
allow necessary access to the
coil/filter rack and blower/control
compartment.
• Install the unit in a level position to
ensure proper condensate
drainage. Make sure unit is level in
both directions within 1/8”.
• Install the unit in accordance with
any local code which may apply
and the national codes. Latest
editions are available from:
“National Fire Protection
Association, Inc., Batterymarch
Park, Quincy, MA 02269.” These
publications are:
• ANSI/NFPA No. 70-(Latest Edition)
National Electrical Code.
• NFPA90A Installation of Air
Conditioning and Ventilating
Systems.
• NFPA90B Installation of warm air
heating and air conditioning
systems.
• The equipment has been
evaluated in accordance with the
Code of Federal Regulations,
Chapter XX, Part 3280.
5
Page 6
SAFETY INFORMATION
WARNING
!
USE ONLY WITH TYPE OF GAS
APPROVED FOR THIS FURNACE.
REFER TO THE FURNACE RATING
PLATE.
WARNING
!
INSTALL THIS FURNACE ONLY IN
A LOCATION AND POSITION AS
SPECIFIED IN THE LOCATION
REQUIREMENTS AND
CONSIDERATIONS SECTION OF
THESE INSTRUCTIONS. PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR TO THE
FURNACE SPACE AS SPECIFIED
IN THE VENTING SECTION OF
THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE
COMBUSTION AND VENTILATION
AIR TO THE FURNACE SPACE AS
SPECIFIED IN THE COMBUSTION
AND VENTILATION AIR SECTION
OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST
BE DISCHARGED OUTDOORS.
CONNECT THIS FURNACE TO AN
APPROVED VENT SYSTEM ONLY,
AS SPECIFIED IN VENT PIPE
INSTALLATION SECTION OF
THESE INSTRUCTIONS.
WARNING
!
DO NOT OPERATE THE SYSTEM
WITHOUT FILTERS. A PORTION
OF THE DUST ENTRAINED IN THE
AIR MAY TEMPORARILY LODGE IN
THE AIR DUCT RUNS AND AT THE
SUPPLY REGISTERS. ANY
CIRCULATED DUST PARTICLES
WILL BE HEATED AND CHARRED
BY CONTACT WITH THE FURNACE
HEAT EXCHANGER. THIS SOOTY
RESIDUE WILL SOIL CEILINGS,
WALLS, DRAPES, CARPETS AND
OTHER HOUSEHOLD ARTICLES.
SOOT DAMAGE MAY ALSO
RESULT WITH, OR WITHOUT,
FILTERS IN PLACE, WHEN
CERTAIN TYPES OF CANDLES
ARE BURNED, OR CANDLEWICKS
ARE LEFT UNTRIMMED.
WARNING
!
NEVER TEST FOR GAS LEAKS
WITH AN OPEN FLAME. USE A
COMMERCIALLY AVAILABLE
OAP SOLUTION MADE
S
SPECIFICALLY FOR THE
DETECTION OF LEAKS TO CHECK
ALL CONNECTIONS, AS
SPECIFIED IN GAS SUPPLY AND
PIPING SECTION OF THESE
INSTRUCTIONS.
WARNING
!
ALWAYS INSTALL FURNACE TO
OPERATE WITHIN THE
FURNACE'S INTENDED
TEMPERATURE-RISE RANGE
WITH A DUCT SYSTEM WHICH
HAS AN EXTERNAL STATIC
PRESSURE WITHIN THE
ALLOWABLE RANGE, AS
SPECIFIED IN DUCTING SECTION
OF THESE INSTRUCTIONS. SEE
ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED
SO THAT SUPPLY DUCTS CARRY
AIR CIRCULATED BY THE
FURNACE TO AREAS OUTSIDE
THE SPACE CONTAINING THE
FURNACE, THE RETURN AIR
SHALL ALSO BE HANDLED BY
DUCT(S) SEALED TO THE
FURNACE CASING AND
TERMINATING OUTSIDE THE
SPACE CONTAINING THE
FURNACE.
WARNING
!
DO NOT INSTALL THIS FURNACE
IN A MOBILE HOME!! THIS
FURNACE IS NOT APPROVED FOR
INSTALLATION IN A MOBILE
HOME. DOING SO COULD CAUSE
FIRE, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
WARNING
!
HEN THIS FURNACE IS
W
INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE INSTALLED
SO THE BURNERS AND IGNITION
SOURCE ARE LOCATED NO LESS
THAN 18 INCHES ABOVE THE
FLOOR. THIS IS TO REDUCE THE
RISK OF IGNITING FLAMMABLE
VAPORS WHICH MAY
E PRESENT IN A GARAGE.
B
ALSO, THE FURNACE MUST BE
LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY
VEHICLES. FAILURE TO FOLLOW
THESE WARNINGS CAN CAUSE A
FIRE OR EXPLOSION, RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
WARNING
!
THE FURNACE MAY BE USED FOR
HEATING OF BUILDINGS OR
STRUCTURES UNDER
CONSTRUCTION.
INSTALLATION MUST COMPLY
WITH ALL INSTALLATION
INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER
THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO
THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE
AND TEMPERATURE RISE PER
RATING PLATE MARKING;
• MEANS FOR PROVIDING
OUTDOOR AIR REQUIRED FOR
COMBUSTION;
• RETURN AIR TEMPERATURE
MAINTAINED BETWEEN 55°F
(13°C) AND 80°F (27°C); AND
• CLEAN FURNACE, DUCT WORK
AND COMPONENTS UPON
SUBSTANTIAL COMPLETION OF
THE CONSTRUCTION
PROCESS, AND VERIFY
FURNACE OPERATING
CONDITIONS INCLUDING
IGNITION, INPUT RATE,
TEMPERATURE RISE AND
VENTING, ACCORDING TO THE
INSTRUCTIONS AND CODES.
6
Page 7
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND DRAW
POLLUTANTS SUCH AS DIRT, DUST,
FUMES AND ODORS INTO THE
HOME CAUSING PROPERTY
DAMAGE. FUMES AND ODORS
FROM TOXIC, VOLATILE OR
FLAMMABLE CHEMICALS, AS WELL
AS AUTOMOBILE EXHAUST AND
CARBON MONOXIDE (CO), CAN BE
DRAWN INTO THE LIVING SPACE
THROUGH LEAKING DUCTS AND
UNBALANCED DUCT SYSTEMS
CAUSING PERSONAL INJURY OR
DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL JOINTS,
SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST BE
SEALED TO LIMIT THE MIGRATION
OF TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE
FROM MIGRATING INTO THE
LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH AS
WATER HEATERS OR BOILERS ALL JOINTS, SEAMS, AND
OPENINGS IN THE EQUIPMENT
AND DUCT MUST ALSO BE
SEALED TO PREVENT
DEPRESSURIZATION OF THE
SPACE AND POSSIBLE
MIGRATION OF COMBUSTION
BYPRODUCTS INCLUDING
CARBON MONOXIDE INTO THE
LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITH THE CSA
INTERNATIONAL (CSA)
CERTIFICATION OR THESE
INSTRUCTIONS, CAN RESULT IN
UNSATISFACTORY OPERATION
AND/OR DANGEROUS CONDI-TIONS
AND ARE NOT COVERED BY THE
UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED
CODES, IT IS RECOMMENDED THAT
AN AUXILIARY DRAIN PAN BE
INSTALLED UNDER ALL
EVAPORATOR COILS OR UNITS
CONTAINING EVAPORATOR COILS
THAT ARE LOCATED IN ANY AREA
OF A STRUCTURE WHERE DAMAGE
TO THE BUILDING OR BUILDING
CONTENTS MAY OCCUR AS A
RESULT OF AN OVERFLOW OF THE
COIL DRAIN PAN OR A STOPPAGE IN
THE PRIMARY CONDENSATE DRAIN
PIPING. SEE ACCESSORIES
SECTION OF THESE INSTRUCTIONS
FOR AUXILIARY HORIZONTAL
OVERFLOW PAN INFORMATION
(MODEL (-)XBM).
IMPORTANT!
THE COMMONWEALTH OF
MASSACHUSETTS REQUIRES
COMPLIANCE WITH REGULATION
248 CMR 4.00 AND 5.00 FOR
INSTALLATION OF THROUGH-THEWALL VENTED GAS APPLIANCES AS
FOLLOWS:
(a) For all side wall horizontally vented
gas fueled equipment installed in every
dwelling, building or structure used in
whole or in part for residential purposes,
including those owned or operated by
the Commonwealth and where the side
wall exhaust vent termination is less than
seven (7) feet above finished grade in
the area of the venting, including but not
limited to decks and porches, the
following requirements shall be satisfied:
1. INSTALLATION OF CARBON
MONOXIDE DETECTORS. At the time
of installation of the side wall horizontal
vented gas fueled equipment, the
installing plumber or gasfitter shall
observe that a hard wired carbon
monoxide detector with an alarm and
battery back-up is installed on the floor
level where the gas equipment is to be
installed. In addition, the installing
plumber or gasfitter shall observe that a
battery operated or hard wired carbon
monoxide detector with an alarm is
installed on each additional level of the
dwelling, building or structure served by
the side wall horizontal vented gas
fueled equipment. It shall be the
responsibility of the property owner to
secure the services of qualified licensed
professionals for the installation of hard
wired carbon monoxide detectors.
a. In the event that the side wall
horizontally vented gas fueled equipment
is installed in a crawl space or an attic,
the hard wired carbon monoxide detector
with alarm and battery back-up may be
installed on the next adjacent floor level.
b. In the event that the requirements of
this subdivision can not be met at the
time of completion of installation, the
owner shall have a period of thirty (30)
days to comply with the above
requirements; provided, however, that
during said thirty (30) day period, a
battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide
detector as required in accordance with
the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3. SIGNAGE. A metal or plastic
identification plate shall be permanently
mounted to the exterior of the building at
a minimum height of eight (8) feet above
grade directly in line with the exhaust
vent terminal for the horizontally vented
gas fueled heating appliance or
equipment. The sign shall read, in print
size no less than one-half (1/2) inch in
size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local
gas inspector of the side wall
horizontally vented gas fueled
equipment shall not approve the
installation unless, upon inspection,
the inspector observes carbon
monoxide detectors and signage
installed in accordance with the
provisions of 248 CMR 5.08(2)(a) 1
through 4.
(b) EXEMPTIONS: The following
equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10
entitled “Equipment Not Required To
Be Vented” in the most current edition
of NFPA 54 as adopted by the Board;
and
2. Product Approved side wall
horizontally vented gas fueled
equipment installed in a room or
structure separate from the dwelling,
building or structure used in whole or
in part for residential purposes.
(c) MANUFACTURER
REQUIREMENTS – GAS
EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer
of Product Approved side wall
horizontally vented gas equipment
provides a venting system design or
venting system components with the
equipment, the instructions provided
by the manufacturer for installation of
the equipment and the venting
system shall include:
1. Detailed instructions for the
installation of the venting system
design or the venting system
components; and
2. A complete parts list for the venting
system design or venting system.
(d) MANUFACTURER
REQUIREMENTS – GAS
EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the
manufacturer of a Product Approved
side wall horizontally vented gas
fueled equipment does not provide
the parts for venting the flue gases,
but identifies “special venting
systems”, the following requirements
shall be satisfied by the manufacturer:
1. The referenced “special venting
system” instructions shall be included
with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall
be Product Approved by the Board,
and the instructions for that system
shall include a parts list and detailed
installation instructions.
(e) A copy of all installation
instructions for all Product Approved
side wall horizontally vented gas
fueled equipment, all venting
instructions, all parts lists for venting
instructions, and/or all venting design
instructions shall remain with the
appliance or equipment at the
completion of the installation.
7
Page 8
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
. install a parallel duct system
WARNING
!
DO NOT INSTALL THIS FURNACE
IN A MOBILE HOME!! This furnace is
not approved for installation in a
mobile home. Doing so could cause
IRE, PROPERTY DAMAGE,
F
PERSONAL INJURY OR DEATH.
WARNING
!
WHEN THIS FURNACE IS
INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE INSTALLED
SO THE BURNERS AND IGNITION
SOURCE ARE LOCATED NO LESS
THAN 18 INCHES ABOVE THE
FLOOR. THIS IS TO PREVENT
THE RISK OF IGNITING
FLAMMABLE VAPORS WHICH MAY
BE PRESENT IN A GARAGE.
ALSO, THE FURNACE MUST BE
LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY
VEHICLES. FAILURE TO FOLLOW
THESE WARNINGS CAN CAUSE A
FIRE OR EXPLOSION, RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
1. IMPORTANT: If installing the unit
over a finished ceiling or living
area, be certain to install an
auxiliary condensate drain pan
under the entire unit. This
auxiliary drain pan should extend
under any evaporator coil
installed with the furnace and the
open portion of the condensate
drain assembly. See
“Condensate Drain/Neutralizer”
section for more details.
2. IMPORTANT: If using a cooling
evaporator coil with this furnace:
a. be sure the air passes over
the heat exchanger before
passing over the cooling
coil. The cooled air passing
over the warm ambient air
inside the heat exchanger
tubes can cause
condensation inside the tubes
resulting in corrosion and
eventual failure.
b
to divert all the air from the
furnace allowing it to pass
over the cooling coil only. Use
dampers or other means to
prevent chilled air from
passing over the heat
exchanger.
If these are manual dampers, they
must be equipped to prevent heating
or cooling operation unless the
damper is in the full heat or cool
position.
3. IMPORTANT: Install the furnace
level. If it is not level, condensate
cannot drain properly, possibly
causing furnace shut down.
NOTE: These furnaces are approved
for installation in attics, as well as
alcoves, utility rooms, closets and
crawlspaces. Provisions must be
made to prevent freezing of
condensate.
4. IMPORTANT: If this furnace is
installed in a garage, attic and/or
any unconditioned space, install a
self-regulating heat tape around
the condensate trap and along the
entire length of the condensate
drain in the unconditioned space.
When the condensing horizontal
gas furnace is installed in an
unconditioned space where the
temperature would be capable of
reaching close to or below 32°F
FIGURE 3
HORIZONTAL FURNACE W/HEAT TAPE ON CONDENSATE TRAP
DRAIN
PIPE
5. IMPORTANT: If installing in a
0°C), a self-regulating heat tape
(
is required on the condensate
drain, along with an insulation
wrap. The heat tape should meet
the following requirements:
a. The heat tape must be UL
listed.
b. The heat tape must be
installed per the
manufacturer’s instructions for
the entire length of drain pipe
in the unconditioned space.
c. The heat tape should be rated
at 5 or 6 watts per foot at
120V
IMPORTANT: Support this unit
when installed. Since this furnace
is suitable for attic or crawl space
installation, it may be installed on
combustible wood flooring or by
using support brackets.
utility room, be sure the door is
wide enough to:
a. allow the largest part of the
furnace to pass; or
b. allow any other appliance
(such as a water heater)
to pass.
c. allow service clearance
AIRF
LOW
HEAT
TAPE
TRAP
8
I526
Page 9
CAUTION
!
THIS FURNACE IS NOT
APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK,
WITH ACCESS DOORS FACING
UPWARDS OR IN ANY
ORIZONTAL CONFIGURATION.
H
SITE SELECTION
1. Select a site in the building near
he center of the proposed, or
t
existing, duct system.
2. Give consideration to the vent
system piping when selecting the
furnace location. Be sure the
venting system can get from the
furnace to the termination with
minimal length and elbows.
3. Locate the furnace near the
existing gas piping. Or, if running
a new gas line, locate the
furnace to minimize the length
and elbows in the gas piping.
4. Locate the furnace to maintain
proper clearance to combustibles
as shown in the following tables.
WARNING
!
DO NOT LIFT THE UNIT BY THE
HEAT EXCHANGER TUBES. DOING
SO CAN DAMAGE THE HEAT
EXCHANGER ASSEMBLY.
CLEARANCE ACCESSIBILITY
The design of forced air furnaces with
input ratings as listed in the table
under Figure 5 are certified by CSAInternational for the clearances to
combustible materials shown in
inches.
See name/rating plate and clearance
label for specific model number and
learance information.
c
Service clearance of at least 24
inches is recommended in front of
all furnaces.
NOTE: Use recommended 24”
clearance if accessibility clearances
are greater than fire protection
clearances.
WARNING
!
UPFLOW FURNACES ARE DESIGNCERTIFIED FOR INSTALLATION
ON COMBUSTIBLE FLOORS.
NOTE, HOWEVER, THAT
FURNACES MUST NOT BE
INSTALLED DIRECTLY ON
CARPETING, TILE OR OTHER
COMBUSTIBLE MATERIAL OTHER
THAN WOOD FLOORING.
INSTALLATION ON A
COMBUSTIBLE MATERIAL CAN
RESULT IN FIRE, CAUSING
PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
Upflow furnaces are shipped with a
bottom closure panel installed. When
bottom return air is used, remove the
panel by removing the two screws
attaching the panel to the front base
angle. See filter section for details.
WARNING
!
COMBUSTIBLE MATERIAL MUST
NOT BE PLACED ON OR AGAINST
THE FURNACE JACKET. THE AREA
AROUND THE FURNACE MUST BE
KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS
INCLUDING GASOLINE AND
OTHER FLAMMABLE VAPORS AND
LIQUIDS. PLACEMENT OF
COMBUSTIBLE MATERIALS ON,
AGAINST OR AROUND THE
FURNACE JACKET CAN CAUSE AN
EXPLOSION OR FIRE RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
THE HOMEOWNER SHOULD BE
CAUTIONED THAT THE FURNACE
AREA MUST NOT BE USED AS A
BROOM CLOSET OR FOR ANY
OTHER STORAGE PURPOSES.
FIGURE 4
HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS
GAS
PIPE
INTAKE
VENT
ELECTRICAL
CONDUIT
AIRF
LOW
TRAP
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure
7. Allow enough space for proper service maintenance or replacement of the heat exchanger and
blower assembly.
EXHAUST
FAN
I522
9
Page 10
IGURE 5
F
CLEARANCE TO COMBUSTIBLES, UPFLOW UNITS
WGTS
OPTIONAL
RETURN
AIR CUTOUT
(EITHER SIDE)*
I392.DGN
BACKTOP FRONT VENT
2 DIA. KNOCKOUT
ALT. GAS CONNECTION
SIDESIDE
LEFT RIGHTSHIP
/3200012*0111
/3200012*0117
/3200012*0123
/3200012*0145
25
/821513
5
UPFLOW MODELSMINIMUM CLEARANCE (IN.)
/32 15
11
/2 16
1
9
25
25
/2 17
1
/821513
/821513
/8218
5
5
1
/32 15
/32 15
/32 19
11
11
27
/2 16
/2 16
1
1
/3200012*0160
/3200012*0148
/3200012*0152
9
9
25
/2 17
/2 17
1
1
/8218
/8218
/822220
1
1
5
/32 19
/32 19
/32 22
27
27
11
/2 23
1
0417
0617
MODELABCDEF
092119
102119
07A17
07B2119
RETURN
1224
*A service clearance of at least 24 inches is recommended in front of all furnaces.
⁄8
5
AIR
27
AIRFLOW
*BOTH SIDES FOR 1800 CFM
GAS CONNECTION
AIR
SUPPLY
2 DIA.
⁄16
7
26
10
I392
CUTOUT (EITHER SIDE)*
OPTIONAL RETURN AIR
Page 11
IGURE 6
F
CLEARANCE TO COMBUSTIBLES, DOWNFLOW UNITS
WGTS
BACKTOP FRONT VENT
SIDESIDE
LEFT RIGHTSHIP
⁄800012*0117
⁄800012*0123
⁄800012*0148
⁄800012*0152
/3200012*0123
7
7
9
⁄813
⁄813
/2 17
5
5
1
⁄8216
⁄8216
/16218
5
5
3
⁄800012*0160
3
3
7
⁄817
⁄817
⁄820
1
1
5
⁄8223
⁄16220
⁄16220
5
3
3
A103501.DGN
⁄16
13
25
2 DIA.
ALT. GAS CONNECTION
⁄8
3
4
⁄32 15
⁄32 15
⁄32 19
⁄32 19
/32 19
11
11
DOWNFLOW MODELSMINIMUM CLEARANCE (IN.)
MODELABCDEF
27
⁄2 16
⁄2 16
1
1
0617
07A17
07B2119
⁄32 22
27
27
11
⁄2 23
1
092119
102119
1224
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIR
SUPPLY
AIRFLOW
GAS
CONNECTION
2 DIA.
AIR
RETURN
I393
NOTE: IN DOWNFLOW CONFIGURATION, RETURN AIR CUTOUT IS NOT PERMITTED.
11
Page 12
IGURE 7
F
CLEARANCE TO COMBUSTIBLES, HORIZONTAL UNITS
WGTS
A103601.DGN
BACKTOP FRONT VENT
SIDESIDE
LEFT RIGHTSHIP
⁄800012*0117
⁄800012*0123
⁄800012*0123
⁄800012*0148
⁄800012*0152
7
7
3
⁄800012*0160
3
3
7
RETURN AIR
⁄813
⁄813
⁄817
⁄817
⁄817
5
5
1
⁄8216
⁄8216
⁄16220
5
5
3
⁄32 15
⁄32 15
⁄32 19
11
11
HORIZONTAL MODELSMINIMUM CLEARANCE (IN.)
27
⁄2 16
⁄2 16
1
1
⁄820
1
1
5
NOTE: In horizontal configuration, return air cutout is not permitted.
Horizontal left-hand airflow only.
IMPORTANT: This furnace is not approved or recommended for
⁄8223
⁄16220
⁄16220
5
3
3
⁄32 19
⁄32 19
⁄32 22
27
27
11
⁄2 23
1
installation on its back, with access doors facing upwards.
0617
MODELABCDEF
092119
102119
07A17
07B2119
1224
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIRFLOW
⁄16
13
25
GAS
CONNECTION
2 DIA.
2 DIA.
ALT. GAS
DRAIN TRAP LOCATION
⁄8
3
4
CONNECTION
12
AIR
SUPPLY
I520
Page 13
JACKET
DRILL (2)
3/16" DIA.
HOLES
8.000
4.875
1.531
DUCTING
Proper air flow is required for the
correct operation of this furnace.
Too little air flow can cause erratic
operation and can damage the heat
exchanger. The duct system must
carry the correct amount of air for
heating and cooling if summer air
conditioning is used.
Size the ducts according to
acceptable industry standards and
methods. The total static pressure
drop of the air distribution system
should not exceed 0.5" w.c.
WARNING
!
NEVER ALLOW THE PRODUCTS
OF COMBUSTION FROM THE FLUE
TO ENTER THE RETURN AIR
DUCTWORK OR THE CIRCULATED
AIR SUPPLY. ALL RETURN
DUCTWORK MUST BE
ADEQUATELY SEALED AND
SECURED TO THE FURNACE WITH
SHEET METAL SCREWS; AND
JOINTS, TAPED. ALL OTHER DUCT
JOINTS MUST BE SECURED WITH
APPROVED CONNECTIONS AND
SEALED AIRTIGHT. WHEN AN
UPFLOW FURNACE IS MOUNTED
ON A PLATFORM WITH RETURN
THROUGH THE BOTTOM, IT MUST
BE SEALED AIRTIGHT BETWEEN
THE FURNACE AND THE RETURN
AIR PLENUM. THE FLOOR OR
PLATFORM MUST PROVIDE
SOUND PHYSICAL SUPPORT OF
THE FURNACE WITHOUT
SAGGING, CRACKS, OR GAPS,
AROUND THE BASE, PROVIDING A
SEAL BETWEEN THE SUPPORT
AND THE BASE.
FAILURE TO PREVENT PRODUCTS
OF COMBUSTION FROM BEING
CIRCULATED INTO THE LIVING
SPACE CAN CREATE
POTENTIALLY HAZARDOUS
CONDITIONS, INCLUDING
CARBON MONOXIDE POISONING
THAT COULD RESULT IN
PERSONAL INJURY OR DEATH.
DO NOT, UNDER ANY
CIRCUMSTANCES, CONNECT
RETURN OR SUPPLY DUCTWORK
TO OR FROM ANY OTHER HEAT
PRODUCING DEVICE SUCH AS A
FIREPLACE INSERT, STOVE, ETC.
DOING SO MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING,
EXPLOSION, PERSONAL INJURY
OR PROPERTY DAMAGE.
IMPORTANT: Some high efficiency
filters have a greater than normal
resistance to air flow. This can
adversely affect furnace operation.
BE SURE TO CHECK AIR FLOW.
IMPORTANT: When using outside air,
design and adjust the system to maintain
a return air temperature ABOVE 55° F
during the heating season.
NOTE: Return air grilles and warm air
registers must not be obstructed or
closed.
UPFLOW UNITS
. Position the unit to minimize long
1
runs of duct or runs of duct with
many turns and elbows.
2. Open the return air compartment.
WARNING
!
UPFLOW FURNACE: A SOLID METAL
BASE PLATE MUST REMAIN IN THE
FURNACE BOTTOM WHEN USING
SIDE AIR RETURN. FAILURE TO
INSTALL A BASE PLATE COULD
CAUSE THE PRODUCTS OF
COMBUSTION TO CIRCULATE INTO
THE LIVING SPACE AND CREATE
POTENTIALLY HAZARDOUS
CONDITIONS, INCLUDING CARBON
MONOXIDE POISONING OR DEATH.
FOR BOTTOM RETURN, REMOVE
SOLID METAL BASE PLATE.
a. Cut an opening in the side. The
opening should be cut the full
width and height of the knockouts
on the unit. See Figure 8.
FIGURE 8
UPFLOW CUTOUT AND DRILL INFORMATION
NOTE: Where the maximum air flow
is 1800 CFM or more, both sides or 1
side and the bottom must be used for
return air.
3. Connect the return duct or return
air cabinet to the unit. Make the
onnection air tight to prevent
c
entraining combustion gases
from an adjacent fuel-burning
appliance.
4. Be sure to have adequate space
or the unit filter.
f
NOTE: DO NOT take return air
from bathrooms, kitchens,
furnace rooms, garages, utility or
laundry rooms, or cold areas.
NOTE: DO NOT use a rear air
return.
5. If summer air conditioning is
desired, position the indoor coil
on the supply-air side of the unit.
Insure that no air can bypass this
coil.
6. Connect the supply air plenum to
the furnace plenum opening.
IMPORTANT: If a flexible duct
connector must be used, it
MUST
be rated for a minimum
temperature of 250°F
continuous.
.
1313
Page 14
OWNFLOW UNITS
D
1. Position the unit to minimize long
runs of duct or runs of duct with
many turns and elbows.
2. If summer air conditioning is
desired, position the indoor coil
on the supply-air side of the unit.
Insure that no air can bypass this
coil.
3. If installing on a combustible floor
and not using an air conditioning
plenum, install the special non-
combustible floor base. See
Table 1 and Figure 9.
WARNING
!
THE DOWNFLOW FURNACE
DESIGN IS CERTIFIED FOR
INSTALLATION ON A NONCOMBUSTIBLE FLOOR. USE THE
SPECIAL BASE SPECIFIED ON THE
FURNACE CLEARANCE LABEL.
FAILURE TO INSTALL THE
SPECIAL BASE MAY RESULT IN
FIRE, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
THIS SPECIAL BASE IS SHIPPED
FROM THE FACTORY AS AN
ACCESSORY.
4. Connect the furnace to the
supply air plenum.
5. Connect the return air ducting to
the return air opening at the top
of the unit. Make the connection
air tight to prevent entraining
combustion gases from an
adjacent fuel-burning appliance.
NOTE: In downflow
configuration, return air cut out is
not permitted.
6. Be sure to have adequate space
for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace
rooms, garages, utility or laundry
rooms, or cold areas.
HORIZONTAL UNIT
IMPORTANT: THIS FURNACE MAY
ONLY BE INSTALLED SO AS WHEN
ACING THE FRONT OF THE
F
FURNACE, SUPPLY AIR IS
DISCHARGED ON THE LEFT HAND
SIDE.
1. Position the unit to minimize long
uns of duct or runs of duct with
r
many turns and elbows.
2. If summer air conditioning is
desired, position the indoor coil on
the supply air side of the unit.
Insure that no air can bypass this
coil.
3. Connect the furnace to the supply
air plenum.
4. Connect the return air ducting to
the return air opening at the right
end of the unit. Make the
connection air tight to prevent
pulling combustion gases from an
adjacent fuel-burning appliance.
NOTE: In horizontal configuration,
return air cut out is not permitted.
5. Be sure to have adequate space
for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace
rooms, garages, utility or laundry
rooms, or cold areas.
TABLE 1
NON-COMBUSTIBLE FLOOR BASES
Floor BaseSize
No.Cabinet
(-)XGC-B1717
(-)XGC-B2121
(-)XGC-B2424
14
FIGURE 9
NON-COMBUSTIBLE FLOOR BASE
Page 15
VENTING AND COMBUSTION AIR PIPING
EQUIREMENT THAT VENT
GENERAL INFORMATION
WARNING
!
READ AND FOLLOW ALL
INSTRUCTIONS IN THIS SECTION.
FAILURE TO PROPERLY VENT
THIS FURNACE CAN CAUSE
CARBON MONOXIDE POISONING
R AN EXPLOSION OR FIRE,
O
RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY
OR DEATH.
This furnace removes both sensible
and latent heat from the combustion
flue gases. Removal of latent heat
results in condensation of flue gas
water vapor. This condensed water
vapor drains from the secondary heat
exchanger and out of the unit into a
drain trap.
When installed as a non-direct vent
furnace, only exhaust piping is
required and inside combustion air
may be used. Refer to section on
COMBUSTION & VENTILATION AIR
“
FOR FURNACE INSTALLATIONS.”
Direct vent installations require a
dedicated combustion air and venting
system. All air for combustion is taken
from the outside atmosphere and all
combustion products are discharged
to the outdoors.
The combustion air and vent pipe
fittings must conform to American
National Standards Institute (ANSI)
and American Society for Testing
Materials (ASTM) standards
D1785 (Schedule 40 PVC), D2665
(PVC-DWV), D2241 (SDR-21 and
SDR26-26 PVC), D2661 (ABS-DWV)
or F628 (Schedule 40 ABS-DWV).
WARNING
!
IN CANADA, PRODUCTS
CERTIFIED FOR INSTALLATION
AND INTENDED TO BE VENTED
WITH PLASTIC VENT SYSTEMS
(PVC, CPVC) MUST USE VENT
SYSTEMS THAT ARE CERTIFIED
TO THE STANDARD FOR TYPE BH
GAS VENTING SYSTEMS, ULC
S636.
THE COMPONENTS OF THE
CERTIFIED MATERIAL MUST NOT
BE INTERCHANGED WITH OTHER
VENT SYSTEMS OR UNLISTED
PIPE/FITTINGS.
PLASTIC COMPONENTS AND
SPECIFIED PRIMERS AND GLUES
OF THE CERTIFIED SYSTEM MUST
BE FROM A SINGLE SYSTEM
MANUFACTURER AND NOT
INTERMIXED WITH OTHER
SYSTEM MANUFACTURER’S
PARTS.
NOTE: INLET AIR PIPING IS NOT
CONSIDERED TO BE A PART OF
THE “VENTING SYSTEM”. THE
R
ATERIAL BE CERTIFIED TO ULC
M
636 DOES NOT APPLY TO INLET
S
IR PIPING. VENT TERMINATIONS
A
ND CONCENTRIC TERMINATIONS
A
UST BE APPROVED BY THE
M
ANUFACTURER AND CERTIFIED
M
LC-636.
U
MPORTANT: The plastic combustion
I
air and venting components are of
Schedule 40 PVC. If using ABS
piping, ensure that the solvent
cement is compatible for joining PVC
to ABS components or use a
mechanical connection that can
withstand the vent temperatures and
are corrosion resistant.
NOTE: Schedule 40 ABS-DWV pipe
and fittings may be used as an
alternate to PVC pipe for the
combustion air inlet and vent pipes.
NOTE: Cellular core PVC is also
approved for use. It must be schedule
40PVC-DWV cellular pipe for nonpressure applications and
manufactured under ASTM F-891.
NOTE: With the furnace correctly
vented, the inducer will move
approximately 25 cfm per 100,000
Btu’s.
IMPORTANT: No part of the
combustion air and vent pipes may
run under ground.
OVERTEMPERATURE
SAFETY SWITCHES
Furnaces are equipped with safety
switches in the control compartment
to protect against overtemperature
conditions caused by inadequate
combustion air supply. The switches
are located in the burner
compartment. If a switch is tripped it
must be manually reset.
WARNING
!
DO NOT JUMPER THESE
DEVICES! IF ONE OF THESE
SWITCHES SHOULD TRIP, A
QUALIFIED INSTALLER, SERVICE
AGENCY OR THE GAS SUPPLIER
MUST BE CALLED TO CHECK
AND/OR CORRECT FOR
ADEQUATE COMBUSTION AIR
SUPPLY. DO NOT RESET THE
SWITCHES WITHOUT TAKING
CORRECTIVE ACTION TO ASSURE
THAT AN ADEQUATE SUPPLY OF
COMBUSTION AIR IS MAINTAINED
UNDER ALL CONDITIONS OF
OPERATION. FAILURE TO DO SO
CAN RESULT IN CARBON
MONOXIDE POISONING OR
DEATH. IF THIS UNIT IS MOUNTED
IN A CLOSET, THE DOOR MUST BE
CLOSED WHEN MAKING THIS
CHECK.
REPLACE THESE SWITCHES
ONLY WITH THE IDENTICAL
REPLACEMENT PART.
EXISTING VENT SYSTEMS
When the installation of this furnace
replaces an existing furnace that is
removed from a vent system serving
ther appliances, the vent system is
o
likely to be too large to properly vent
the remaining attached appliances.
he following steps should be
T
followed with each appliance
remaining connected to the original
common vent system. Place the
appliance to be tested in operation,
while the other appliances remaining
connected to the common vent
system are not in operation. Test the
operation of each appliance
individually by the following method.
1. Permanently seal any unused
openings in the common venting
system.
2. Visually inspect the venting
system for proper size and
horizontal pitch and determine
that there is no blockage,
restriction, leakage, corrosion or
other deficiencies which could
cause an unsafe condition.
3. If practical, close all building
doors, windows and all doors
between the space where the
appliances remaining connected
to the common venting system
are located.
Turn on clothes dryers and any
appliance not connected to the
common venting system. Turn on
any exhaust fans, such as range
hoods and bathroom exhausts,
so they will operate at maximum
speed. Do not operate a summer
exhaust fan. Close fireplace
dampers.
4. Follow the lighting instructions.
Place the appliance being
inspected into operation. Adjust
the thermostat so the appliance
will operate continuously.
5. Test for spillage at the draft hood
relief opening after 5 minutes of
main burner operation. Use the
flame of a match or candle, or
smoke from a cigarette, cigar
or pipe.
15
Page 16
6. After it has been determined that
each appliance that remains
connected to the common
venting system properly vents
(when tested as outlined above),
return doors, windows, exhaust
fans, fireplace dampers and any
other gas-burning appliance to
their previous conditions of use.
7. If improper venting is observed
during any of the above tests, the
common venting system must be
resized.
When the furnace is installed in the
same space with other gas
appliances such as a water heater, be
sure there is an adequate supply of
ombustion and ventilation air for the
c
other appliances. Do not delete or
reduce the combustion air supply
required by the other gas appliances
in this space. See Z223.1, National
Fuel Gas Code (NFPA54) for
determining the combustion air
requirements for gas appliances. An
unconfined space must have at least
50 cubic feet (volume) for each
1,000 BTUH of the total input of all
appliances in the space. If the open
space containing the appliances is in
a building with tight construction
(contemporary construction), outside
air may still be required for the
appliances to burn and vent properly.
Outside air openings should be sized
the same as for a confined space.
IMPORTANT: Only the current vent
instructions apply. All 90 Plus Gas
Furnaces cannot be common vented.
JOINING PIPE AND
FITTINGS
WARNING
!
PVC SOLVENT CEMENTS AND
PRIMERS ARE HIGHLY
FLAMMABLE. PROVIDE
ADEQUATE VENTILATION AND DO
NOT ASSEMBLE NEAR HEAT
OURCE OR AN OPEN FLAME. DO
S
NOT SMOKE. AVOID SKIN OR EYE
CONTACT. OBSERVE ALL
CAUTIONS AND WARNINGS
PRINTED ON MATERIAL
CONTAINERS. FAILURE TO
FOLLOW THESE GUIDELINES MAY
RESULT IN FIRE, EXPLOSION OR
ASPHYXIATION CAUSING
PERSONAL INJURY OR DEATH.
All pipe, fittings, solvent cement,
primers and procedures must
conform to American National
Standard Institute and American
Society for Testing and Materials
(ANSI/ASTM) standards as shown
below:
CEMENTING JOINTS
Properly seal all joints in the PVC
vent using the following materials and
procedures.
PVC CLEANER-PRIMER AND
PVC MEDIUM-BODY SOLVENT
CEMENT
IMPORTANT: After cutting pipe,
remove all ragged edges and burrs.
This is important to prevent reduction
in pressure drop throughout the
system.
1. Cut pipe end square. Chamfer
edge of pipe. Clean fitting socket
and pipe joint area of all dirt,
grease and moisture.
2. After checking pipe and socket
or proper fit, wipe socket and
f
pipe with cleaner-primer. Apply
a liberal coat of primer to inside
surface of socket and outside of
pipe. Read instructions included
with the primer for proper
application.
3. Apply a thin coat of cement
evenly in the socket. Quickly
apply a heavy coat of cement to
the pipe end and insert pipe into
fitting with a slight twisting
ovement until it bottoms out.
m
NOTE: Cement must be fluid; if
not, recoat.
4. Hold the pipe in the fitting for 30
seconds to prevent the tapered
socket from pushing the pipe out
of the fitting.
5. Wipe all excess cement from the
joint with a rag. Allow 15 minutes
before handling. Cure time varies
according to fit, temperature and
humidity.
NOTE: Stir the solvent cement
frequently while using. Use a natural
bristle brush or the dauber supplied
with the can. The proper brush size is
one inch.
IMPORTANT: For Proper Installation
DO NOT use solvent cement that
has become curdled, lumpy or
thickened.
DO NOT thin. Observe shelf
precautions printed on containers.
For application below 32°F, use only
low-temperature-type solvent
cement.
16
PIPE & FITTING MATERIAL
Schedule 40 PVC (Pipe)D1785
Schedule 40 PVC (Cellular Core Pipe)F891
Schedule 40 PVC (Fittings)D2466
SDR-21PVC (Pipe)D2241
SDR-26 PVC (Pipe)D2241
Schedule 40 ABS Cellular Core DWV (Pipe)F628
Schedule 40 ABS (Pipe)D1527
Schedule 40 ABS (Fittings)D2468
ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings)
PVC-DWV (Drain Waste & Vent)
(Pipe & Fittings)
ASTM
SPECIFICATION
D2661
D2665
Page 17
COMBUSTION AND VENTILATION AIR
NON-DIRECT
erchloroethylene)
FURNACE INSTALLATIONS
WARNING
!
THE FURNACE AND ANY OTHER
UEL-BURNING APPLIANCE MUST
F
BE PROVIDED WITH ENOUGH
FRESH AIR FOR PROPER
COMBUSTION AND VENTILATION
OF THE FLUE GASES. MOST
HOMES WILL REQUIRE THAT
OUTSIDE AIR BE SUPPLIED INTO
THE FURNACE AREA. FAILURE TO
DO SO CAN CAUSE PERSONAL
INJURY OR DEATH FROM
CARBON MONOXIDE POISONING.
Adequate facilities for providing air for
combustion and ventilation must be
provided in accordance with section
5.3, “Air for Combustion and
Ventilation” of the National Fuel Gas
Code, ANSI Z223.1 (latest edition) or
applicable provisions for the local
building codes, and not obstructed so
as to prevent the flow of air to the
furnace.
IMPORTANT: Air for combustion and
ventilation must not come from a
corrosive atmosphere. Any failure
due to corrosive elements in the
atmosphere is excluded from
warranty coverage.
The following types of installation
(but not limited to the following) will
require OUTDOOR AIR for
combustion, due to chemical
exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following substances
in the combustion air supply (but not
limited to the following) will also
require OUTDOOR AIR for
combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
p
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for
lothes dryers
c
• Masonry curing and acid washing
materials
Combustion air must be free of acidforming chemicals such as sulphur,
fluorine and chlorine. These elements
are found in aerosol sprays,
detergents, bleaches, cleaning
solvents, air fresheners, paint and
varnish removers, refrigerants and
many other commercial and
household products. When burned in
a gas flame, vapors from these
products form acid compounds. The
acid compounds increase the dew
point temperature of the flue products
and are highly corrosive after they
condense.
WARNING
!
ALL FURNACE INSTALLATIONS
MUST COMPLY WITH THE
NATIONAL FUEL GAS CODE AND
LOCAL CODES TO PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE
FURNACE. FAILURE TO DO SO
CAN RESULT IN EXPLOSION, FIRE,
PROPERTY DAMAGE, CARBON
MONOXIDE POISONING,
PERSONAL INJURY OR DEATH.
Combustion air requirements are
determined by whether the furnace is
in an open (unconfined) area or in a
confined space such as a closet or
small room.
EXAMPLE 1:
FURNACE LOCATED IN AN
UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at
least 50 cubic feet for each 1,000
BTUH of the total input for allappliances in the space. Here are a
few examples of the room sizes
required for different inputs. The sizes
are based on 8-foot ceilings.
BTUH Minimum Sq. FeetTypical Room Size
InputWith 8' CeilingWith 8' Ceiling
5,00028114' x 20' OR 16' x 18'
4
0,00037515' x 25' OR 19' x 20'
6
5,00046915' x 31' OR 20' x 24'
7
0,00056320’ x 28’ OR 24’ x 24’
9
105,00065720' x 33' OR 26' x 25'
120,00075025' x 30' OR 24' x 32'
If the open space containing the
furnace is in a building with tight
construction, outside air may still be
required for the furnace to operate
and vent properly. Outside air
openings should be sized the same
as for a confined space.
EXAMPLE 2:
FURNACE LOCATED IN A
CONFINED SPACE
A confined space (any space smaller
than shown above as “unconfined”)
must have openings into the space
which are located in accordance with
the requirements set forth in the
following subsections A and B. Size
the openings by how they are
connected to the heated area or to
the outside,
and by the input of all appliances in
the space.
If confined space is within a building
with tight construction, combustion air
must be taken from outdoors or area
freely communicating with the
outdoors.
A. USING INDOOR AIR FOR
COMBUSTION
IMPORTANT: Air should not be
taken from a heated space with a
fireplace, exhaust fan or other
device that may produce a
negative pressure.
If combustion air is taken from the
heated area, the openings must
each have at least 100 square
inches of free area. Each opening
must have at least one square inch
of free area for each 1,000 BTUH
of total input in the space. Here
are some examples of typical
openings required.
BTUHFree Area
17
Page 18
nputEach Opening
I
5,000100 square inches
4
0,000100 square inches
6
5,000100 square inches
7
90,000100 square inches
105,000105 square inches
120,000120 square inches
IGURE 10
F
AIR FROM HEATED SPACE
B. USING OUTDOOR AIR FOR
COMBUSTION
MPORTANT: Do not take air from
I
an attic space that is equipped
with power ventilation.
The confined space must
communicate with the outdoors in
accordance with Methods 1 or 2.
The minimum dimension of air
openings shall not be less than 3
inches. Where ducts are used,
they shall be of the same crosssectional area as the free area of
the openings to which they
connect.
Method 1
Two permanent openings, one
located within 12 inches of the top
and one located within 12 inches
of the bottom of the enclosure,
shall be provided. The openings
shall communicate directly, or by
ducts, with the outdoors or spaces
(crawl or attic) that freely
communicate with the outdoors.
a. Where directly communicating
with the outdoors or where
communicating to the outdoors
AS
G
WATER
HEATER
through vertical ducts as shown in
Figure 11, each opening shall
have a minimum free area of 1
square inch for each 4,000 BTUH
of total appliance input rating in the
enclosure.
BTUHFree AreaRound Pipe
InputEach OpeningSize
45,00011.25 square inches4"
60,00015.00 square inches5"
75,00018.75 square inches5"
90,00022.50 square inches6"
105,00026.25 square inches6"
120,00030.00 square inches6"
b. Where communicating with
URNACE
F
NOTE:
ACH OPENING SHALL
E
HAVE A FREE AREA OF
NOT LESS THAN ONE
QUARE INCH PER 1,000
S
BTU PER H0UR OF THE
TOTAL INPUT RATING OF
LL EQUIPMENT IN THE
A
ENCLOSURE, BUT NOT
LESS THAN 100 SQUARE
NCHES.
I
outdoors through horizontal ducts,
each opening shall have a
minimum free area of 1 square
inch for each 2,000 BTUH of total
input rating of all equipment in the
enclosure (see Figure 12).
Here are some typical sizes:
BTUHFree AreaRound Pipe
InputEach OpeningSize
45,00022.50 square inches6"
60,00030.00 square inches6"
75,00037.50 square inches7"
90,00045.00 square inches8"
105,00052.50 square inches8"
120,00060.00 square inches9"
Method 2 (not shown)
FIGURE 11
AIR FROM ATTIC/CRAWL SPACE
OUTLET AIR
IN ATTIC
MUST BE
ABOVE
INSULATION
1 SQ. INCH PER
4000 BTUH
OUTLET AIR
GAS
WATER
HEATER
18
GABLE
VENT
FURNACE
OPTIONAL1 SQ. INCH PER 4000 BTUH INLET AIR
1 SQ. INCH PER
4000 BTUH INLET AIR
VENTILATED
ATTIC GABLE OR
SOFFIT VENTS
12" MAX.
FIGURE 12
OUTSIDE AIR USING A HORIZONTAL DUCT
OUTLET AIR 1 SQ. INCH
FURNACE
GAS
WATER
HEATER
INLET AIR 1 SQ. INCH
12"
MAX.
PER 2000 BTUH
PER 2000 BTUH
Page 19
One permanent opening, located
within 12 inches of the top of the
enclosure, shall be permitted
where the equipment has
clearances of at least 1 inch from
the sides and back and 6 inches
from the front of the appliance.
The opening shall directly
communicate with the outdoors or
communicate through a vertical or
orizontal duct to the outdoors or
h
spaces (crawl or attic) that freely
communicate with the outdoors,
and shall have a minimum free
area of:
. 1 square inch for each 3,000
a
BTUH of the total input rating of all
equipment located in the enclosure
and
FIGURE 13
COMBUSTION AIR FITTING
TUHFree AreaRound Pipe
B
nputEach OpeningSize
I
5,00015.00 square inches4"
4
0,00016.67 square inches5"
6
5,00025.00 square inches6"
7
90,00030.00 square inches6"
105,00035.00 square inches7"
120,00040.00 square inches7"
b. Not less than the sum of the
areas of all vent connectors in the
confined space.
If unit is installed where there is an
exhaust fan, sufficient ventilation
must be provided to prevent the
exhaust fan from creating a negative
pressure.
Combustion air openings must not be
restricted in any manner.
CONSULT LOCAL CODES FOR
SPECIAL REQUIREMENTS.
CONNECTION TO
FURNACE
IMPORTANT: When indoor
combustion air is used, the inlet air
pening at the furnace must be
o
protected from accidental blockage.
(See Figure 13).
UPFLOW
TTACH DOUBLE ELBOW TO TOP INLET
A
IR OPENING OR 90° ELBOW TO SIDE
A
NLET AIR OPENING TO PREVENT
I
CCIDENTALBLOCKAGE OF INTAKE
A
PENING. PLUG OPENING NOT USED.
O
XHAUST
E
OP
T
OPTION
I337
SIDE
OPTION
2" PVC
OUBLE
D
ELBOW
2" PVC ELBOW
" PVC
DOWNFLOW/HORIZONTAL
2
DOUBLE
ELBOW*
COMBUSTION AIR
*NOTE: WHEN FURNACE IS INSTALLED IN A HORIZONTAL POSITION
ONLY ONE 90° ELBOW IS REQUIRED. INSTALLTHE ELBOW SO THE
OPEN END IS POINTED DOWNWARD.
TTACH DOUBLE ELBOW TO INTAKE AIR
A
OLLAR AND SECURE WITH TWO SHEET
C
ETAL SCREWS TO PREVENT ACCIDENTAL
M
LOCKAGE OF INTAKE AIR OPENING.
B
REDRILL FOR SCREWS.
P
EXHAUST
I336
19
Page 20
VENT PIPE INSTALLATION
NON-DIRECT VENT
INSTALLATION
GUIDELINES
IMPORTANT: Failure to correctly follow
all venting guidelines may result in
rratic furnace operation, freeze-up of
e
combustion air or exhaust air piping or
sooting of the furnace.
ll exhaust piping must be installed in
A
compliance with Part 7, “Venting of
Equipment,” of the latest edition of the
National Fuel Gas Code NPFA54/ ANSI
Z223.1-, local codes or ordinances and
these instructions.
1. Vertical piping is preferred.
2. All horizontal piping must slope
upward a minimum of
foot of run so that condensate drains
toward the furnace.
3. All horizontal runs must be
supported at least every 4 feet. No
sags or dips are permitted.
4. IMPORTANT: Do not common vent
with any other appliance. Do not
install in the same chase or chimney
with a metal or high temperature
plastic pipe from another gas or fuelburning appliance unless the
required minimum clearances to
combustibles are maintained
between the pvc pipe and other
pipes.
5. All vent runs through unconditioned
spaces where below-freezing
temperatures are expected should
be insulated with 1-in. thick,
medium-density, foil-faced
fiberglass. An equivalent “arm-aflex” or “rub-a-tex” insulation may
also be used as long as there is no
heat tape applied to the vent pipe.
For horizontal runs where water may
collect, wrap the vent pipe with selfregulating 3 or 5 watt heat tape. The
heat tape must be U.L. listed and
installed per the manufacturer’s
instructions.
6. The minimum vent pipe length is
5 feet.
7. Extend the exhaust pipe a minimum
of 18” from the cabinet before turning
vent.
8. Vent cannot be ran underground.
FIGURE 14
TEE TERMINAL – FOR STANDARD
HORIZONTAL NON-DIRECT
INSTALLATION
VENT
1
/4 inch per
TABLE 2
UPFLOW UNITS
FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION
PROVIDED FROM INDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
NUMBERS OF ELBOWS
FURNACE
INPUT
45,000
0,000
6
75,000
90,000
05,0003”
1
120,0003”
NOTES:
1. *N.A. - NOT APPLICABLE.
2. MAXIMUM OF 6 ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR
ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS.
3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
4. NO SCREENS MAY BE USED TO COVER EXHAUST.
*A = 17-1/2” CABINET WIDTHB = 21) CABINET WIDTH
PIPE
SIZE
2”
2
3
3
3”
ERMINATION
T
1-23-45-6
Standard605550
Alternate555045
”
”
”
Standard302520
Alternate252015
tandard120120115
S
lternate120120110
A
tandard4540NA
S
Alternate4545NA
Standard908575
Alternate605045
Standard4540NA
lternateNANANA
A
tandard706555
S
lternate403025
A
45° OR 90°
edium / Long Radius ONLY
M
TABLE 3
DOWNFLOW/HORIZONTAL UNITS
FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION
PROVIDED FROM INDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
NUMBERS OF ELBOWS
FURNACE
INPUT
60,000
75,000
90,0003”
105,0003”
120,0003”
NOTES:
1. *N.R. - NOT RECOMMENDED.
2. MAXIMUM OF 6 - 90 DEGREE ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR
ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS.
3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
4. NO SCREENS MAY BE USED TO COVER EXHAUST.
*A = 17-1/2” CABINET WIDTHB = 21” CABINET WIDTH
PIPE
SIZE
2”
3”
3”
TERMINATION
1-23-45-6
Standard403530
Alternate302520
Standard120120120
Alternate110105100
Standard120120120
Alternate1009585
Standard11010595
Alternate504035
Standard656055
Alternate504035
Standard403530
Alternate403530
45° OR 90°
Medium / Long Radius ONLY
20
12"
12" MIN. ABOVE
GRADE OR
SNOW LEVEL
ELEVATED SINGLE PIPE ALTERNATE TEE TERMINATION
See Figure 15. The tee termination may be elevated up to 24 inches above the
wall penetration if required for anticipated snow levels. Use 2 long-sweep, 2-in.
PVC elbows and 2-in. PVC pipe, attaching the tee so it is 12 inches from the wall.
Page 21
TANDARD INSTALLATIONS
S
The single-pipe system requires an
exhaust pipe only. Combustion air may
be taken from the furnace installation
area or ducted to the furnace area from
the outside.
Size the exhaust pipe as specified in
Table 2. This table lists the maximum
allowable length in feet of the exhaust
pipe that may be used for all furnace
inputs as related to the number of
elbows required and the termination.
(See shaded area.)
Vertical through-the-roof installations do
not require a vent termination. Use 2-in.
PVC pipe extending a minimum of 12
inches above the anticipated level of
snow accumulation. See exhaust pipe
requirements, Figure 19. When 3-in.
vent pipe is used from furnace to the
roof, reduce it to 2 inches before
penetrating the roof. A maximum of 18
inches of 2-in. pipe may be used below
the roof. Maximum exposed vent length
above the roof line is 30”. Total 2” vent
length is a maximum of 48”.
Horizontal vent terminations require a
2-in. PVC tee positioned 12 inches from
the outside wall. See exhaust pipe
requirements, Figure 29. When 3-in.
pipe is used from the furnace to the
outside wall, reduce it to 2 inches
before penetrating the wall. A maximum
of 18 inches of 2-in. pipe may be used
inside the wall.
An alternate termination may be used
as shown in Figure 15 to clear
anticipated snow levels. The tee may
be raised up to 24 inches above the
wall penetration. Use two long-sweep
radius bend, 2-in. PVC elbows and a
length of 2-in. PVC pipe so that the
elbows are on 24-in. centers.
NOTE: Extend the exhaust a minimum
of 18" from the furnace top plate before
turning vent.
NON-DIRECT VENT TERMINATION
LOCATION REQUIREMENTS
CAUTION
!
MOISTURE IN THE COMBUSTION
PRODUCTS CONDENSES AS IT
LEAVES THE TERMINATION. THIS
CONDENSATE CAN FREEZE ON
EXTERIOR WALLS, UNDER THE
EAVES, AND ON SURROUNDING
OBJECTS. SOME DISCOLORATION
IS TO BE EXPECTED. HOWEVER,
IMPROPER LOCATION OR
INSTALLATION CAN CAUSE
STRUCTURAL OR EXTERIOR FINISH
DAMAGE TO THE BUILDING.
Non-direct venting location
requirements are slightly different in
some cases than direct venting. Install
a non-direct vent with the following
minimum clearances.
See Figure 16.
1. Locate the bottom of the vent
terminal at least 12 inches above
grade. Increase the 12-in.
minimum to keep the terminal
openings above the level of snow
accumulation, where applicable.
2. The vent shall not terminate over
public walkways or over an area
where condensate or vapor could
create a nuisance or hazard.
3. 4 feet below, 4 feet horizontally
from, or 1 foot above any door,
window soffit, under eave vent or
gravity air inlet to the building.
4. The vent terminal shall have a
minimum horizontal clearance of
4 feet from electric meters, gas
meters, regulators and relief
equipment.
5. 6 feet from an inside corner
formed by two exterior walls –
10 feet is the recommended
distance.
6. Locate it 3 feet above any forced
air inlet located within 10 feet.
Any fresh air or make-up air inlet,
such as for a dryer or furnace
area, is considered a forced air
inlet.
7. Avoid areas where dripping
condensate may cause problems,
such as above planters, patios, or
adjacent to windows where
steam may cause fogging.
FIGURE 15
ALTERNATE HORIZONTAL TERMINATION
FOR NON-DIRECT VENT
INSTALLATIONS
NOT APPLICABLE FOR:
(-)GRL-07EYBGS MODEL
(-)GRL-07EMAES MODEL
(-)GRL-10EZAJS MODEL
OUTSIDE
WALL
In addition to the minimum clearances
listed above, the vent location should
also be governed by the following
guidelines.
. Do not terminate under any kind
1
of patio or deck. If running the
ent under a deck, insulate it to
v
insure no condensate freezes
and blocks the pipe.
2. Do not locate on the side of a
building with prevailing winter
inds. This will help prevent
w
moisture from freezing on walls
and overhangs (under eaves).
3. Do not extend vent directly
through brick or masonry
urfaces. Use a rust-resistant
s
sheet metal or plastic backing
plate behind vent.
4. Do not locate too close to shrubs
as condensate may stunt or kill
them.
5. Minimum vertical clearances of 1
foot are recommended for
overhangs up to 1 foot horizontal.
The vertical clearance should be
increased equally for each
additional increase in horizontal
overhang to a maximum vertical
clearance of 6 feet.
6. Caulk all cracks, seams and
joints within 6 feet horizontally
and above and below vent.
7. Do not terminate in any area that
may allow flue gases to stagnate.
12"
ROM
F
PIPE
24"
MAX.
SUPPORT
STRAP
I198
21
Page 22
IGURE 16
Natural Gas and Propane Installation Code
National Fuel Gas Code
Canadian Installations
US Installations
Canadian Installations
US Installations
F
THER THAN DIRECT VENT TERMINAL CLEARANCES
O
22
Page 23
DIRECT VENT
INSTALLATIONS
WARNING
!
READ AND FOLLOW ALL
INSTRUCTIONS IN THIS SECTION.
FAILURE TO PROPERLY VENT THIS
FURNACE CAN CAUSE CARBON
MONOXIDE POISONING OR AN
EXPLOSION OR FIRE, RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY
OR DEATH.
Direct vent installations require a
dedicated combustion air and venting
system. All air for combustion is taken
from the outside atmosphere and all
combustion products are discharged to
the outdoors. Therefore, no ventilation
orcombustion air openings are
required.
IMPORTANT: The plastic combustion
air and venting components are of
Schedule 40 PVC. If using ABS piping
ensure that the solvent cement is
compatible for joining PVC to ABS
components or use a mechanical
connection that can withstand the vent
temperatures and are corrosion
resistant.
INSTALLATION GUIDELINES
All exhaust piping must be installed in
compliance with Part 7, “Venting of
Equipment,” of the latest edition of the
National Fuel Gas Code NPFA54/
ANSI Z223.1-, local codes or
ordinances and these instructions.
1. Vertical piping is preferred.
2. All horizontal piping must slope
upward a minimum of1/4 inch
per foot of run so that condensate
drains toward the furnace.
3. All horizontal runs must be
supported at least every 4 feet.
No sags or dips are permitted.
4. IMPORTANT: Do not common
vent with any other appliance. Do
not install in the same chase or
chimney with a metal or high
temperature plastic pipe from
another gas or fuel-burning
appliance unless the required
minimum clearances to
combustibles are maintained
between the PVC pipe and other
pipes. Minimum 3 ft. clearance
required between combustion air
inlet and any other exhaust.
5. For horizontal runs where water
may collect, wrap the vent pipe
with self-regulating 3 or 5 watt
heat tape. The heat tape must be
U.L. listed and installed per the
manufacturer’s instructions.
6. The minimum, pipe length is
5 feet for combustion air and
exhaust.
7. Do not install elbows back to
back. Allow at least 15” between
elbows.
Size the exhaust and combustion air
intake pipes as specified in Table 4 or
Table 5. This table lists the maximum
TABLE 4
UPFLOW UNITS FOR DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION
ROVIDED FROM OUTDOORS
P
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE AIR PIPE
UMBER OF ELBOWS
N
5 or 90 Degrees
IPE
FURNACE
INPUT
4
60,000
7
90,0003”
105,0003”
1
NOTES:
P
TERMINATION
IZE
S
5,0002”
5,0003”
20,0003”
1. N.A. - NOT APPLICABLE
2. MAXIMUM OF 6 ELBOWS MAY BE USED. DO NOT COUNT ELBOWS IN ALTERNATE TERMINATION KIT.
MEDIUM OR LONG SWEEP ELBOWS MAY BE USED.
. A 45 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
3
4. CONCENTRIC TERMINATION NO. RXGY-E03/RXGY-E03A IS FOR THRU-THE-ROOF OR THRU-THE-WALL VENTING.
5. USE KITS RXGY-DO2/D02A (2"), RXGY-G02 (2"), OR RXGY-D03/D03A (3") FOR STANDARD OR ALTERNATE
THRU-THE-WALL VENTING.
6. USE KITS RXGY-D04/D04A FOR ALTERNATE VENTING OF 120,000 BTUH UNITS WITH LONG RUNS.
. KIT NUMBERS CONTAINING SUFFIX “A” ARE APPROVED FOR INSTALLATION IN CANADA.
7
8. NO SCREENS MAY BE USED TO COVER COMBUSTION AIR AND EXHAUST.
(A*) = 17
allowable length in feet of the exhaust
and combustion air intake pipes that
may be used for all furnace inputs as
related to the number of elbows
required and the termination (see
shaded area).
NOTE: Extend the exhaust a minimum
of 18" from the furnace top plate
before turning vent.
8. The maximum exposed vent
length (above the roof line) is 30”.
COMBUSTION AIR FOR
DIRECT VENT
INSTALLATIONS
HE COMBUSTION AIR SYSTEM
T
DESIGNED FOR THIS FURNACE
MUST BE USED.
When this furnace is installed as a
direct vent forced air furnace, all
combustion air is supplied directly to
the burner through a special air inlet
system outlined in these instructions.
This system consists of field-supplied
Schedule 40 or 26 SDR-PVC pipe
and one of the following horizontal
vent termination kits: (-)XGYD02/D02A, (-)XGY-D03/D03A,
(-)XGY-D04/D04A, or (-)XGY-E03A.
NOTE: Schedule 40 ABS-DWV pipe
and fittings may be used as an
alternate to PVC pipe for the
combustion air inlet and vent pipes.
The combustion air for this furnace is
supplied directly from the outdoors
through the combustion air inlet
system.
When the furnace is installed in the
same space with other gas
appliances, such as a water heater,
be sure there is an adequate supply
of combustion and ventilation air for
the other appliances. Do not delete or
reduce the combustion air supply
required by the other gas appliances
in this space. See Z223.1, National
Fuel Gas Code (NFPA54) for determining the combustion air
requirements for gas appliances. An
unconfined space must have at least
50 cubic feet (volume) for each
1,000 BTUH of the total input of all
appliances in the space. If the open
space containing the appliances is in
a building with tight construction
(contemporary construction), outside
air may still be required for the
appliances to burn and vent properly.
Outside air openings should be sized
the same as for a confined space.
STANDARD TERMINATIONS
STANDARD VERTICAL
TERMINATIONS
COMBUSTION AIR PIPING
Use two medium-radius sweep
elbows to keep the inlet downward to
prevent entry of rain. See Figure 19
for the proper relationship of
ombustion air to exhaust
c
termination.
STANDARD HORIZONTAL
TERMINATIONS
COMBUSTION AIR PIPING
When 3-in. pipe is used between the
furnace and outside wall, reduce it
to 2 inches before penetrating the
all. Up to 18 inches of 2-in. pipe
w
may be used inside the wall.
The standard horizontal intake air
ermination for all models is a 2-in.
t
PVC coupling with a wind deflector
vane (provided) attached. Cut a
1
2
/4-in. length of 2-in. PVC pipe.
Connect this pipe and another 2-in.
PVC coupling to the coupling at the
wall. The outer coupling must
terminate 4 inches from the wall.
IMPORTANT: To ensure proper
furnace operation, the supplied vane
must be installed in the vertical
position with PVC solvent as shown in
Figure 20, Detail B.
The combustion air inlet terminal
must be located with respect to the
exhaust terminal as shown in Figure
20, Detail C.
IMPORTANT: All furnaces with
horizontal air intakes, except those
using concentric vent kit (-)XGYE03/E03A, must have a drain tee
assembly and trap installed as close
to the furnace as possible. This is to
drain any water that may be in the
combustion air pipe to prevent it from
entering the furnace combustion
chamber.
These parts are included in kits
(-)XGY-D02/D02A (for 2-in. pipe),
(-)XGY-D03/D03A (for 3-in. pipe) and
(-)XGY-D04/D04A (special for the
120,000 BTU furnace installed with
the alternate horizontal termination).
Attach the trap to the bottom of the
tee with PVC solvent. Connect the
other end to a suitable drain, as to the
downstream of a condensate trap on
the furnace.
STANDARD VERTICAL
TERMINATIONS
EXHAUST VENT PIPING
Vertical through-the-roof vent
applications do not require an
exhaust terminal. The exhaust vent
must terminate at least 12 inches
above the combustion intake air
termination. The exhaust vent for
models with inputs of 90,000 through
120,000 BTUH is 2-in. PVC pipe
120,000 BTUH models with
excessively long runs require 2
1
/2”.
Refer to Table 4 for proper
application. This must
be reduced to 1
1
/2“ the last
12 inches for models with inputs of
45,000 through 75,000 BTUH.
ee Figure 19.
S
STANDARD HORIZONTAL
TERMINATIONS
EXHAUST PIPING
For direct vent systems the standard
termination is 2-in. PVC pipe
extending 12 inches from the wall for
furnaces with inputs from 105,000 to
120,000 BTUH. Install a 2-in. coupling
at the outside wall to prevent the
termination from being pushed
inward. When 3-in. pipe is used
between the furnace and outside wall,
reduce to 2 inches before penetrating
the wall. The standard termination is
1
1
/2 -in. PVC pipe extending outward
12 inches from the wall for models
with inputs of 45,000 to 75,000
BTUH. Install a 2-in. to 1
1
/2-in.
coupling at the outside wall to prevent
pushing the termination back into the
wall. See Figure 20, Detail A.
The combustion air and exhaust
terminations must be at least 12
inches above grade and must be
oriented with respect to each other as
shown in Figure 20, Detail B. Refer to
section on alternate venting options
when higher snow levels are
anticipated.
ALTERNATE
TERMINATIONS
ALTERNATE HORIZONTAL DIRECT
VENT TERMINATIONS
(-)XGY-D02/D02A, -D03/D03A AND D04/D04A
The combustion air and exhaust
terminations may be raised a
maximum of 24 inches above the wall
penetration to maintain the required
12 inch clearance above grade or
snow level. See Figure 17. Size the
pipe length according to Table 4 and
Table 5.
Review the following guidelines:
• Size the entire vent system
according to the alternate, not
standard, termination shown in
Table 4 and Table 5.
24
Page 25
• Insulate the entire length of vent
pipe, between the elbow where the
pipe exits the wall and the elbow
where the termination is made, with
closed-cell insulation, such as
a
Arm-a-Flex” or “Rub-a-Tex” with a
“
minimum of 1/2” thickness.
• All elbows installed on the exterior
of the building must be of the long
sweep nature.
• As required for the horizontal piping
ran within the structure, any pipe
ran horizontal outside the structure
must slope upward a minimum of
1/4” per foot run so that condensate
drains toward the furnace.
From the top elbow in the exhaust
pipe, extend a length of PVC pipe
outward so that it terminates exactly
12 inches from the wall. See Figure
17. Reduce the exhaust pipe
extension to is 1
1
⁄2 inch pipe for
45,000 BTUH through 75,000 BTUH
units.
The 45,000 BTUH unit only uses kit
(-)XGY-D02/D02A. The 60,000 BTUH
and 75,000 BTUH downflow only
units may use kits (-)XGY-D02/D02A
or (-)XGY-D03/D03A depending on
pipe lengths and number of elbows.
Use kit (-)XGY-D03/D03A with 90,000
BTUH downflow through 120,000
BTUH units or
upflow 90,000 or
120,000. The (-)XGY-D04/D04A kit
only applies to the 120,000 BTUH unit
using an alternate termination and
excessively long runs. See Table 4.
The following are parts lists for the
(-)XGY-D02/D02A, (-)XGY-D03/D03A
and (-)XGY-D04/D04A alternate
horizontal direct vent termination kits:
(-)XGY-D02/D02A
1. 2-in. tee with reducer assembly
1
2.
⁄2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
1
5. 1
⁄2-in. PVC nipple with coupling
6. PVC strap
7. vent template
(-)XGY-D03/D03A
IGURE 17
F
LTERNATE HORIZONTAL DIRECT VENT TERMINATION
A
EXHAUST VENT
21/2" PVC FOR MODELS WITH 120,000 BTU INPUT
(KIT NO. (-)XGY-D04)
2" PVC FOR MODELS WITH INPUTS OF 90,000 AND
120,000 BTU. REDUCE TO 11/2" FOR MODELS WITH
INPUTS OF 45,000 THRU 75,000 BTU (SEE DETAIL A).
ELBOWS AND RISERS ARE 2" PVC.
SEE DETAIL A
12" FROM
WALL
” MAX.
3
NOTE: 3-1/2”
MAX. WHEN
04 KIT IS
D
SED.
U
4”
EXHAUST / INTAKE RELATIONSHIP
NTAKE
I
24” MAX.
3”
XHAUST
E
DETAIL B
OPTIONAL
INTAKE
4" FROM
WALL
PIPE
SUPPORT
STRAP
OMBUSTION AIR
C
TERMINATION
1. 3-in. tee with reducer assembly
1
2.
⁄2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
(-)XGY-D04/D04A
1
⁄2-in. PVC elbow
1. 2
2. 3" x 2
3. 2
4. 2
5. 2
1
⁄2" PVC bushing
1
⁄2" x 61⁄2" long PVC pipe
1
⁄2" x 16" long PVC pipe
1
⁄2" x 21" long PVC pipe
6. PVC vane
7.
3-in. tee with reducer assembly
8. 6-in. dia.1⁄2-in. PVC trap
9. PVC strap
10. vent template
NOTE: The (-)XGY-D04/D04A kit only
applies to the 120,000 BTUH unit
using an alternate termination and
excessively long runs.
INTAKE VENT
21/2" PVC FOR MODELS WITH
120,000 BTU INPUT.
2" PVC ELBOWS AND RISER
MODELS WITH INPUTS OF 45,000
THRU 105,000 BTU.
SE KIT NO. (-)XGY-D02/D02A WHEN 2"
U
IPE IS USED BETWEEN FURNACE AND
P
UTSIDE WALL. USE KIT NO. (-)XGY-
O
03/D03A WHEN 3" PIPE IS USED.
D
12"
FROM
WALL
-1/2"
1
IPE
P
ANE
V
EXHAUST VENT FOR
DETAIL C
MODELS WITH
NPUT OF 45,000 THRU
I
(-)XGY-D02A
1. 2” Tee assembly w/
connection
1
⁄2” PVC-5” diameter trap
2.
3. Wind deflector vane
4. Vent template
(-)XGY-D03A
1. 3” Tee assembly w/
connection
1
2.
⁄2” PVC-5” diameter trap
3. Wind deflector vane
4. Vent Template
(-)XGY-D04A
1. 3” Tee assembly w/
connection
1
2.
⁄2” PVC-6” diameter trap
3. Wind deflector vane
4. Vent template
DETAIL A
75,000 BTU
1
1
1
I339
⁄2” drain
⁄2” drain
⁄2” drain
25
Page 26
CONCENTRIC
TERMINATIONS
ERTICAL/HORIZONTAL
V
CONCENTRIC VENT
KIT NO. (-)XGY-E03A
This kit is for vertical/horizontal
intake air/vent runs and may be
installed through roofs or sidewalls.
One 5” diameter hole is required for
he installation. See Figure 18 for
t
the general layout. Complete
installation instructions are included
with the kit.
NOTE: The following IPEX brand
concentric termination (System 636)
may be purchased in the field
and
used in place of factory supplied kits:
3” Concentric Kit – Item # 196006
FIGURE 18
ONCENTRIC VENT KIT NO. (-)XGY-E03A
C
SIDEWALL ASSEMBLY
FIELD-SUPPLIED
STRAP
C
B
D
ITEM No.DESCRIPTION
A2.5" PVC PIPE SCHEDULE 40 -- 37.125" LONG
B4" PVC PIPE SCHEDULE 40 -- 24" LONG
C3" x 3" x 4" SPECIAL CONCENTRIC FITTING
D3" x 45° STREET ELBOW (FIELD SUPPLIED)
EPVC RAINCAP
E
A
1" MAXIMUM
ROOF INSTALLATION
A
E
C
NOTE: • Support must be field installed
to secure termination kit to structure.
• No screens may be used to cover
combustion air and exhaust.
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.
B
D
26
Page 27
IGURE 19
F
STANDARD VERTICAL DIRECT VENTING
4
EXHAUST
TERMINATION
ETAIL A
D
5
EXHAUST PIPE
OTES:
N
NCREASE THE 12-IN. MINIMUM
I
1
TO KEEP TERMINAL OPENING ABOVE
ANTICIPATED LEVEL OF SNOW
CCUMULATION WHERE APPLICABLE.
A
HEN 3-IN. DIAM. PIPE IS USED,
W
2
REDUCE TO 2-IN. DIAMETER BEFORE
PENETRATING ROOF. A MAXIMUM
F 18 IN. OF 2-IN. PIPE MAY BE
O
USED BEFORE PASSING
THROUGH ROOF.
SUPPORT VERTICAL PIPE EVERY 6
3
EET.
F
EXHAUST TERMINATION - TERMINATE
4
HE LAST 12 INCHES WITH 2” PVC PIPE
T
ON 90,000 AND 120,000 BTUH MODELS.
REDUCE AND TERMINATE THE LAST 12
NCHES WITH 1
I
THROUGH 75,000 BTUH MODELS. SEE
ETAIL A.
D
30”MAXIMUM EXPOSED VENT LENGTH.
5
THE COMBUSTION AIR PIPE MUST
6
ERMINATE IN THE SAME PRESSURE
T
ZONE AS THE EXHAUST PIPE.
O SCREENS MAY BE USED TO
N
7
COVER COMBUSTION AIR AND
EXHAUST.
1
PVC PIPE ON 45,000
/2”
30” MAX
8” MAX
4
ROOF LINE
3
1
2”
" MAX.
3
SEPARATION
6" MAX.
3
COMBUSTION AIR
IPE
P
12" MIN.
EPARATION
S
12" MIN. ABOVE
OOF LEVEL
R
2
COMBUSTION AIR PIPE
SUPPLY AIR
RETURN AIR
"
EXHAUST
ENT
V
2"
1
IN.
6
"
3
1
COMBUSTION
IR PIPE
A
MAX.
12"
MIN.
2"
1
IN.
M
EXHAUST
ENT
V
OOF LINE
R
M
3
MAX.
12"
MIN.
5
ANTICIPATED
NOW LEVEL
S
COMBUSTION
IR PIPE
A
5
"
3
EXHAUST VENT
0” MAX
3
.
N
I
M
"
12
PITCHED ROOF INSTALLATIONS
AX.
M
ABO
.
ED SN
N
I
M
"
PAT
I
2
C
1
I
T
AN
EVEL
W L
VE
O
5
407
I
FIGURE 20
STANDARD HORIZONTAL DIRECT VENTING
SUPPLY AIR
EXHAUST PIPE
COMBUSTION AIR PIPE
NOTES:
SUPPORT HORIZONTAL PIPE
1
EVERY FOUR FEET.
WHEN 3 IN. PIPE IS USED REDUCE TO 2 IN.
2
BEFORE PENETRATING OUTSIDE WALL.
18 IN. MAXIMUM. 2 IN. DIAMETER PIPE MAY
3
BE USED INSIDE THE WALL.
DETAIL “A”- EXHAUST TERMINATION
4
TERMINATE THE LAST 12 INCHES WITH 2”
PVC PIPE ON 90,000 AND 120,000 BTUH
MODELS. REDUCE AND TERMINATE THE
LAST 12 INCHES WITH 1
45,000 THROUGH 75,000 BTUH MODELS.
INCREASE THE 12 IN. MINIMUM ABOVE
5
GRADE TO KEEP TERMINAL OPENINGS
ABOVE ANTICIPATED LEVELOF SNOW
ACCUMULATION WHERE APPLICABLE.
DETAIL “B”, INSTALL WIND DEFLECTOR
6
VANE IN 2 IN. PVC COUPLING IN VERTICAL
POSITION USING PVC SOLVENT.
THE COMBUSTION AIR TERMINATION MUST
BE IN THE SAME PRESSURE ZONE AS THE
EXHAUST TERMINATION.
THE COMBUSTION AIR PIPE MUST
7
TERMINATE IN THE SAME PRESSURE
ZONE AS THE EXHAUST PIPE.
NO SCREENS MAY BE USED TO COVER
8
COMBUSTION AIR AND EXHAUST.
NO ELBOWS CAN BE INSTALLED AT
9
TERMINATION.
1
/2” PVC PIPE ON
1
2” OR 3” TEE
W/DRAIN TRAP
RETURN AIR
VANE
TRAP
CONNECT
TO DRAIN
2
2” PVC
COUPLING
6
COMBUSTION AIR TERMINATION
DETAIL B
12”
3
12”
4”
12” MIN. ABOVE
GRADE LEVEL
SEE DETAIL B
SEE DETAIL A
4”
5
4”
EXHAUST / INTAKE RELATIONSHIP
4
EXHAUST TERMINATION
DETAIL A
3”
EXHAUST
INTAKE
DETAIL C
OPTIONAL
INTAKE
I407
27
Page 28
LOCATION REQUIREMENTS
HORIZONTAL DIRECT VENTS
CAUTION
!
THE COMBUSTION PRODUCTS
AND MOISTURE IN THE FLUE
GASES WILL CONDENSE AS THEY
LEAVE THE TERMINATION. THE
ONDENSATE CAN FREEZE ON
C
THE EXTERIOR WALL, UNDER THE
EAVES AND ON SURROUNDING
OBJECTS. SOME DISCOLORATION
TO THE EXTERIOR OF THE
BUILDING IS TO BE EXPECTED.
HOWEVER, IMPROPER LOCATION
OR INSTALLATION CAN RESULT IN
STRUCTURAL OR EXTERIOR
FINISH DAMAGE TO THE
BUILDING AND MAY
RECIRCULATE PRODUCTS OF
COMBUSTION INTO THE
COMBUSTION AIR TERMINAL AND
FREEZE.
The vent must be installed with the
following minimum clearances. See
Figures 21 and 22.
1. The bottom of the vent terminal
and the air inlet shall be located
at least 12 inches above grade.
Increase the 12-in. minimum to
keep the terminal openings
above the level of snow
accumulation, where applicable.
2. The vent shall not terminate over
public walkways or over an area
where condensate or vapor could
create a nuisance or hazard.
3. The vent terminal shall be
located at least one foot from any
opening through which flue
gases could enter a building.
4. The vent terminal shall be at
least 3 feet above any forced air
inlet located within 10 feet,
except the combustion air inlet of
a direct vent appliance.
5. The vent terminal shall have a
minimum horizontal clearance of
4 feet from electric meters, gas
meters, regulators and relief
equipment.
6. Locate the furnace combustion
air inlet minimum of 3 feet from
the vent of any other gas or fuel
burning appliance or clothes
dryer to prevent recirculation of
the flue gases into the furnace
combustion air inlet. The only
exception to this requirement is
the case of multiventing two or
more furnaces, which is covered
in the section on multiventing in
these instructions.
In addition to the minimum clearances
listed above, the vent location
should also be governed by the
following guidelines.
. Do not terminate under any kind
1
of patio or deck. If running the
ent under a deck, insulate it to
v
insure no condensate freezes
and blocks the pipe.
2. Do not terminate behind any area
that may allow the flue products
to become stagnant and
ecirculate.
r
3. Do not locate on the side of a
building with prevailing winter
winds. This will help prevent
moisture from freezing on walls
and overhangs (under eaves).
4. Do not extend vent directly
through brick or masonry
surfaces. Use a rust-resistant
sheet metal or plastic backing
plate behind vent.
FIGURE 21
MOISTURE ZONES
5. Do not locate too close to shrubs
as condensate may stunt or
kill them.
6. Minimum vertical clearances of 1
foot are recommended for
overhangs up to 1 foot horizontal.
The vertical clearance should be
ncreased equally for each
i
additional increase in horizontal
overhang to a maximum vertical
clearance of 6 feet.
7. Caulk all cracks, seams and
joints within 6 feet horizontally
nd above and below vent.
a
8. Painted surfaces must be sound
and in good condition with no
cracking, peeling, etc. Painted
surfaces will require
maintenance.
9. Do not expose 3" x 2" reducer/
bushing to outdoor ambient
temperatures.
2 FT. SQ. SHEET METAL PLATE ON BRICK OR
MASONRY SURFACE RECOMMENDED, BUT
NOT REQUIRED BY CODE.
28
Page 29
IGURE 22
Natural Gas and Propane Installation Code
National Fuel Gas Code
Canadian Installations
US Installations
Canadian Installations
US Installations
F
IRECT VENT TERMINAL CLEARANCES≤
D
29
Page 30
FIGURE 23
WO FURNACE VENTING THROUGH ROOF
T
WO-PIPE VENTINGTWO-PIPE VENTING
T
OMBUSTION
C
AIR INTAKE
2”PVC
FIGURE 24
WO FURNACE VENTING THROUGH WALL
T
VE
ABO
N.
I
EVEL
L
M
”
W
2
1
SNO
3" MIN.
24" MAX.
1
3
4" MAX.
2
6
RE
”
0
" MIN.
”
COM
I
M
D
N.
NDE
E
M
COMBUSTION
AIR INTAKE
2”PVC COUPLING
WITH VALVE IN
VERTICALPOSITION
XHAUST VENT
E
CONCENTRIC VENTINGCONCENTRIC VENTING
" MIN.
8
4" MAX.
2
MINIMUM 12”ABOVE AVERAGE
SNOW ACCUMULATION. MAXIMUM
OF 24 IN.ABOVE ROOF.
6” MINIMUM
10” RECOMMENDED
MINIMUM 12”
MAXIMUM 1”
DISTANCE
FROM WALL
ABOVE GRADE
MULTIVENTING
IF VENTING TWO OR MORE
FURNACES NEAR EACH OTHER IS
REQUIRED, EACH FURNACE
MUST BE INDIVIDUALLY VENTED –
NO COMMON VENTING IS
PERMITTED. See Figures 23 and 24
for positioning of the terminations.
When more than two furnaces are to
be vented, there must be at least 4
feet between the first two furnaces
and the third, etc.
30
SEE CONCENTRIC
VENT INSTALLATION
INSTRUCTIONS
8" MIN.
24" MAX.
SEE CONCENTRIC VENT INSTALLATION
INSTRUCTIONS.
Page 31
(-)XGY-G02 Side Wall Vent
EXHAUST
AIR
INTAKE
This termination for horizontal venting
only.
MPORTANT: Do not install on the
I
prevailing winter wind side of the
structure. Observe same clearance
specified for horizontal, standard
termination.
NOTE: Multi-venting-No common
venting.
FIGURE 25
VENT KIT INSTALLATION OPTIONS
NOTE: Install the vent and air intake
piping into the vent plate openings.
Seal all gaps between the pipes and
wall. Be Sure To Use Silicone Sealant
to seal the vent pipe to the vent cap
to permit field disassembly for annual
inspection and cleaning. Also seal all
pipe penetrations in wall. To prevent
possibility of condensate freeze-up or
recirculation, do not install vent kits
one above the other.
NOTE: The vent illustration in Figure
26 can be used for non-direct vent
terminations also.
FIGURE 26
TYPICAL INSTALLATIONS
31
Page 32
CONNECTING TO FURNACE
IMPORTANT: Clean and debur all
pipe cuts. The shavings must not be
allowed to block the exhaust,
combustion air or condensate drain
pipes.
UPFLOW FURNACE
The exhaust pipe connection is a 2-in.
emale PVC pipe fitting extending
f
through the left side of the furnace top
plate. This opening has a protective
cap which should be removed just
prior to installing the exhaust pipe.
When 2-in. pipe is used, connect it
directly to this fitting. When 3-in. pipe
is used, connect a 2 to 3-in. coupling
to this fitting with a short piece of 2-in.
PVC pipe.
The combustion air connection
is at the right side of the top plate.
An alternate combustion air
connection may be made on the right
side of the jacket. This opening has a
plastic cap. A combustion air
connection fitting is supplied with the
furnace and it must be installed in the
furnace by screwing it into the
opening. Make sure the rubber
“O-ring” supplied with the furnace is
used with this fitting. See Figure 27.
DOWNFLOW/HORIZONTAL
FURNACE
The exhaust pipe connection is a 2-in.
female PVC pipe fitting extending
through the right side of the furnace
top cover. This opening has a protective cap which should be removed
just prior to installing the exhaust
pipe. When 3-in. pipe is used,
connect a 2 to 3-in. coupling to this
fitting with a short piece of 2-in. PVC
pipe.
The combustion air connection is a 2in. extruded hole on the left side of
the top plate. When a 2-in. pipe is
used, attach a 2-in. PVC coupling
over this hole with RTV sealant, drill
two pilot holes, and add two sheet
metal screws through the coupling
into the extrusion to secure it in place
before piping. When 3-in. pipe is
used, connect a 2 to 3-in. coupling to
this fitting with a short piece of 2-in.
PVC pipe. See Figure 28.
IGURE 27
F
PFLOW COMBUSTION AIR AND VENT PIPE CONNECTION
U
O”RING
“
TOP PLATE
EXHAUST
VENT CAP/PLUG
EXHAUST
OUTLET AIR PIPE
EXHAUST TRANSITION
CONNECTOR
CONDENSATE TRAP
DRAIN HOSES
(AS SHIPPED FROM
FACTORY)
FIGURE 28
DOWNFLOW/HORIZONTAL COMBUSTION AIR AND VENT PIPE CONNECTION
TOP PLATE
COUPLING
NOTE:
ATTACH COUPLING TO
EXTRUDED COLLAR WITH
TWO SCREWS. PUT BEAD
OF SILICONE AROUND
BASE BEFORE
MOUNTING COUPLING.
COMBUSTION
AIR CHASE
INDUCED DRAFT
BLOWER
COMBUSTION
IR ADAPTER
A
NOTE:
WHEN COMBUSTION AIR IS IN
PTIONAL POSITION SWAP LOCATION
O
OF 2" PVC MALE ADAPTER AND “O”
RING WITH PLUG.
P
AIR POSITION
I
BLOWER
LUG OPT. COMBUSTION
NDUCED DRAFT
329
I
EXHAUST VENT
CAP/PLUG
EXHAUST
PIPE - PVC
EXHAUST
CONNECTOR
EXHAUST
OUTLET AIR PIPE
EXHAUST
TRANSITION
32
a103101
Page 33
CONDENSATE DRAIN/NEUTRALIZER
GENERAL INFORMATION
CAUTION
!
O NOT RUN DRAIN OUTDOORS.
D
FREEZING OF CONDENSATE CAN
CAUSE PROPERTY DAMAGE.
IMPORTANT: Do not connect into a
common drain line with an air conditioner evaporator coil drain. A blocked
or restricted drain line can result in
over-flow of the coil pan and negate the
furnace blocked drain shutoff control.
FILL TRAP ASSEMBLY WITH WATER
BEFORE OPERATING THE
FURNACE. This can be done by
removing the drain hose
from the trap and pouring about a
cup of water into the vent trap. Water
will flow into the house drain when the
trap is full.
If local codes require, install a
condensate neutralizer cartridge in the
drain line. Install cartridge in horizontal
position only. Also install an overflow
line if routing to a floor drain. See
Figure 29.
If no floor drain is available, install a
condensate pump that is resistant to
acidic water. Pumps are available from
your local distributor. If pump used is
not resistant to acidic water, a
condensate neutralizer must be used
ahead of the pump. The condensate
pump must have an auxiliary safety
switch to prevent operation of the
furnace and resulting overflow of
condensate in the event of pump
failure. The safety switch must be wired
through the “R” circuit only (low voltage)
to provide operation in either heating or
cooling modes.
IMPORTANT: If installing the unit over
a finished ceiling or living area, be
certain to install an auxiliary condensate
rain pan under the entire unit
d
xtending out under the condensate
e
ee.
t
IMPORTANT: There are two options
when choosing a height for the
condensate riser:
CONDENSATE OVERFLOW: With a 5
inch riser installed above the tee, a
blocked drain will result in overflow from
the riser.
FURNACE SHUTDOWN: To cause the
furnace to shut down when a blocked
drain is present, install a riser which is a
minimum of 10
13
/16“. If the furnace is
installed in an attic, crawlspace or other
area where freezing temperatures may
occur, the furnace drain can freeze
while shut off for long periods of time.
FIGURE 29
UPFLOW CONDENSATE DRAIN
NOTE:
SEE UPFLOW MODEL
NOTES FOR PIPE
HEIGHT
10
1
3
16
/
Use a solvent cement that is
compatible with PVC material. Cut the
drain hoses to the appropriate length
nd connect to the trap with hose
a
lamps. Tighten the clamps with
c
liers and check for leaks after
p
ttaching.
a
MPORTANT: The inducer drain hose
I
ust slant downward away from
m
nducer. If the hose is not slanted,
i
he inducer will fill with water and
t
ause the pressure switch to open,
c
ausing nuisance failures or
c
ntermittent operation.
i
NOTE: INDUCER
DRAIN HOSE
MUST SLANT
DOWNWARD
AWAY FROM
INDUCER.
UPFLOW MODELS
The condensate drain trap is located in
the blower compartment on the lefthand side of the jacket. A short piece of
1
/2-in. PVC pipe and a1/2-in. tee are
provided. Connect the1/2-in. pipe to the
elbow on the trap and the tee to this
pipe so that the open end is upward.
Run a drain tube from the bottom of the
tee to a floor drain or condensate
pump.
IMPORTANT: The upflow model only
has a new drain system. There is a third
port on the drain trap (marked by a red
cap) for the hose attached to the
induced draft motor. Remove plug in
inducer drain hose and remove cap off
drain trap before connecting inducer
drain hose to drain trap. All three hoses
MUST be attached during operation of
the furnace. Be sure all three hoses are
secured to the drain trap using the hose
clamps provided in the parts bag.
TO FLOOR DRAIN OR CONDENSATE PUMP
NOTE: CONNECT
INDUCER DRAIN HOSE
TO SMALLER PORT ON
CONDENSATE TRAP.
DRAIN LINE
NEUTRALIZER CARTRIDGE (OPTIONAL)
OVERFLOW LINE
(REQUIRED ONLY WHEN
OPTIONAL NEUTRALIZER
CARTRIDGE IS USED.)
CONDENSATE TRAP
CONDENSATE TRAP
I408
33
Page 34
REVERSING THE TRAP
UPFLOW UNITS
The trap may be moved to the right
side for right side drainage. Open the
knockout for the drain on the right
side of the cabinet. Remove the
bracket holding the trap from the left
side. Seal the left side drain hole with
a plug provided in the cloth bag with
the furnace. Position the mounting
racket and trap so that the drain
b
elbow is centered in the hole on
the right. See Figure 30.
1
Drill two
mount the bracket. Mount the trap
and bracket to the right side with the
drain elbow pointing through the
knockout. Connect the
tee as noted above. Route the drain
hoses behind the control box, cut to
the appropriate length, and connect to
the trap with hose clamps. Fill trap
with water.
IMPORTANT: Do not allow any sags
or kinks in the hoses. This prevents
proper condensate flow.
IMPORTANT: Do not connect into
a common drain line with an air
conditioner evaporator coil drain. A
blocked or restricted drain line can
result in overflow of the coil pan and
negate the furnace blocked drain
shutoff control.
DOWNFLOW MODELS
IMPORTANT: There are two options
when choosing a height for the
condensate riser:
CONDENSATE OVERFLOW: With a
3
⁄4 inch riser installed above the tee,
1
a blocked drain will result in overflow
from the riser.
FURNACE SHUTDOWN: To cause
the furnace to shut down when a
blocked drain is present, install a riser
which is a minimum of 5
furnace is installed in an attic,
crawlspace or other area where
freezing temperatures may occur, the
furnace drain can freeze while shut
off for long periods of time. Provisions
must be made to prevent freezing of
condensate.
Use a solvent cement that is
compatible with PVC material.
To convert downflow models to lefthand drain, a kit ((-)XGY-H01) must
be ordered from the distributor. The
kit includes a 24” piece of
PVC pipe, a 2-9/16” length of black
hose, a 2” rubber grommet, a 1-5/8”
plug and instructions. Note the
location of the alternate drain hole as
shown in Figure 32.
To convert to left side drainage,
remove the long molded hose from
the trap. Remove the double-elbow
black molded hose from the trap and
exhaust transition and discard.
Remove the trap from its mounting
/8” holes in the cabinet to
1
/2-in. pipe and
1
⁄2”. If the
1
⁄2” black
IGURE 30
F
PFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
U
PROPER DRAIN SLOPE REQUIRED
(NO KINKS ALLOWED)
SHEETMETAL IFC
MOUNTING PLATE
CONDENSATE TRAP
FIGURE 31
DOWNFLOW CONDENSATE DRAIN
CONDENSATE TRAP
DRAIN LINE
NEUTRALIZER CARTRIDGE
(OPTIONAL)
bracket, rotate it 180 degrees and
mount in place with the drainage elbow
pointing to the left. Reattach the long
black molded hose. Use the 2-9/16”
length of black hose included in the
(-)XGY-H01 kit between the trap and
exhaust transition. Clamp hoses tight
with white nylon clamps.
Remove the plug from the 2” alternate
drain hole (see Figure 32) and replace
it with the 2” rubber grommet supplied
in the (-)XGY- H01 downflow alternate
drain kit. Also, remove the 1-5/8”
grommet supplied in the primary drain
hole and replace it with the 1-5/8”
diameter plug that is also supplied in
the (-)XGY-H01 downflow alternate
drain kit. Both the hole-plug and
grommet must be in place to insure a
good seal in the burner compartment.
TO FLOOR DRAIN OR CONDENSATE PUMP
A length of 1/2” black PVC pipe is
also provided in the (-)XGY-H01
downflow alternate drain kit. Glue
one end of the pipe to the elbow in
the trap. Cut the pipe so that it
extends through the alternate drain
hole in the left side of the cabinet one
inch. Connect the 1/2” PVC tee
(supplied with the furnace) to the
pipe with a 1-3/4” riser. Use the 15/8” plug supplied in the (-)XGY-H01
downflow alternate drain kit to seal
the right side drainage hole.
IMPORTANT: Do not connect into a
common drain line with an air
conditioner evaporator coil drain
located above the furnace. A blocked
or restricted drain line can result in
overflow of the coil pan and negate the
furnace blocked-drain shutoff control.
UT DRAIN HOSES AS
C
EQUIRED
R
ND CONNECT TO
A
NLETS ON TOP
I
F CONDENSATE
O
RAP
T
RAIN
D
XTENSION
E
O FLOOR
T
RAIN
D
NOTE:
DRAIN VENT NEEDS
O BE ABOVE
T
COLLECTOR BOX
DRAIN SPOUT.
MINIMUM HEIGHT
OPEN TOP
VERFLOW LINE
O
(REQUIRED ONLY WHEN
OPTIONAL NEUTRALIZER
ARTRIDGE IS USED.)
C
DRAIN
RISER
TEE
A039407
a103101
34
Page 35
CONDENSATE DRAIN
FOR HORIZONTAL
INSTALLATION
Refer to Figure 33 for Steps 1-4.
This unit is shipped factory ready for
downflow installation. The
condensate trap assembly and drain
hoses require conversion for
horizontal installation. Remove the
existing condensate trap with the unit
in the upright position.
1. Remove the burner compartment
door from the unit.
2. Remove the two screws from the
right side of the furnace jacket
which support the trap mounting
bracket. Remove the two
plastic plugs on either side of the
trap outlet hole and discard.
3. Remove the black molded 90°
hose ➂ from the top of the
existing trap ➀ and furnace
collector box. Cut 1.0 inch from
the long end of the hose. NOTE:
Exception – do not shorten the
90° hose on the 07B furnace!
The 07B has a longer distance
between the collector box and
horizontal drain trap.
4. Remove the double-elbow black
molded hose ➀ from the exhaust
transition ➀. Discard this hose
and the downflow trap.
NOTE: The following steps should
take place with the furnace in the
horizontal position.
Refer to Figure 34 for Steps 6-11.
5. Locate the parts bag in the
burner compartment. Install two
plastic plugs ➅ in the side of the
jacket from bottom side up.
6. Fill the trap assembly ➆ with a
cup of water.
7. Attach the gasket ➇ onto the trap
assembly so that the gasket
holes on the gasket line up with
the holes on the trap assembly.
8. Insert the trap assembly with
gasket up through the existing
hole in the jacket and secure
from inside the jacket. Use two
screws provided. Screw down
into the two “ears” molded into
either side of the trap. Snug the
trap assembly against the
furnace jacket compressing the
gasket slightly to eliminate any
air leaks. Do not
9. Attach the black molded rubber
90° elbow ➈ to the straight spout
on the trap top using a white
nylon clamp ➉. Attach the other
end of the rubber elbow to the
spout ➋ located on the exhaust
transition ➄ using a white nylon
clamp.
10. Attach the 90° end of the molded
hoseto the collector box.
Clamp the hose tight with white
nylon clamp. Then attach the
long end of the molded hose to
B
C
A
D
E
F
G
H
overtighten!
I
J
K
E
L
IGURE 32
F
OWNFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
D
DRAIN
VENT
RAIN
D
XTENSION
E
TEE
DRIPLEG
ALTERNATE
DRAIN HOLE
LOCATED
ERE ON
H
JACKET.
REMOVE
(
BURNERS
PLASTIC PLUG
ND REPLACE
A
MANIFOLD
ITH
W
GROMMET).
TO FLOOR
DRAIN OR
ONDENSATE
C
UMP
P
CONDENSATE TRAP
the 45° elbow molded into the top
of the trap assembly. Clamp the
hose tight with white nylon clamp.
IMPORTANT: Tighten all clamp
connections with a pair of pliers
and check for leaks after
conversion is complete.
11. IMPORTANT: There are two
options when choosing a height for
the condensate riser:
CONDENSATE OVERFLOW: With
3
a 1
⁄4 inch riser installed above the
tee, a blocked drain will result in
UNION
FILLING THE TRAP
FILL THE TRAP ASSEMBLY WITH
WATER BEFORE OPERATING THE
FURNACE. Do this by removing the
drain hose from the trap or from the
connection to the secondary coil.
Pour about a cup of water into the
vent trap. Any excess water flows into
the house drain when the trap is full.
NOTE: Fill the trap assembly with
water every heating season.
overflow from the riser.
FURNACE SHUTDOWN: To
cause the furnace to shut down
when a blocked drain is present,
install a riser which is a minimum
of 51⁄2”. If the furnace is installed in
an attic, crawlspace or other area
where freezing temperatures may
occur, the furnace drain can freeze
while shut off for long periods of
time. Provisions must be made to
prevent freezing of condensate
(see Figure 3).
Use a solvent cement that is
compatible with PVC material.
NOTE: See location requirements and
combustion section for additional
recommendations.
EXISTING
DRAIN HOLE.
PLUG WITH
5/8”PLUG
1
SUPPLIED IN
IT.
K
ROTATE TRAP
180° AND
INSTALLRIGID
IPE FROM
P
ELBOW TO
OPPOSITE
SIDE OF
ACKET AS
J
SHOWN.
35
Page 36
I534
CONDENSATE TRAP CONVERSION FROM DOWNFLOW TO
HORIZONTAL INSTALLATION
FOR HORIZONTAL OPERATION
FIGURE 34
HORIZONTAL POSITION: CONDENSATE TRAP INSTALLATION
36
FIGURE 33
UPRIGHT POSITION: REMOVAL OF EXISTING DOWNFLOW CONDENSATE TRAP
Page 37
GAS SUPPLY AND PIPING
GAS SUPPLY
WARNING
!
THIS FURNACE IS EQUIPPED AT
THE FACTORY FOR USE ON
NATURAL GAS ONLY.
CONVERSION TO LP GAS
REQUIRES A SPECIAL KIT IS
AVAILABLE AT THE DISTRIBUTOR.
FAILURE TO USE THE PROPER
CONVERSION KIT CAN CAUSE
IRE, CARBON MONOXIDE
F
POISONING, EXPLOSION,
PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH. See the
conversion kit index supplied with the
furnace. This index identifies the
proper LP Gas Conversion Kit
required for each particular furnace.
IMPORTANT: Any additions, changes
or conversions required for the
furnace to satisfactorily meet the
application should be made by a
qualified installer, service agency or
the gas supplier, using factoryspecified or approved parts.
IMPORTANT: Connect this furnace
only to gas supplied by a commercial
utility.
IMPORTANT: U.L. or CSA
recognized fuel gas and CO
detector(s) are recommended in all
applications, and their installation
should be in accordance with the
manufacturer’s recommendations
and/or local laws, rules, regulations or
customs.
GAS PIPING
Install the gas piping according to all
local codes and regulations of the
utility company.
If possible, run a separate gas supply
line directly from the meter to the
furnace. Consult the local gas
company for the location of the
manual main shut-off valve. The gas
line and manual gas stop must be
adequate in size to prevent undue
pressure drop and never smaller than
the pipe size to the gas valve on the
furnace. Refer to Table 6 for the
recommended gas pipe size. See
Figure 35 for typical gas pipe
connections.
Install a ground joint union within 3 ft.
of the cabinet to easily remove the
gas valve assembly. Install a manual
gas stop valve in the gas line outside
the furnace casing. The manual gas
stop should be readily accessible to
turn the gas supply on or off. Install a
drip leg in the gas supply line as close
to the furnace as possible. Always
FIGURE 35
AS PIPING INSTALLATION
G
UPFLOW
ROMMET
MANUAL
GAS
STOP
TO 5 FEET
4
ABOVE FLOOR
REQ’D BY
OME
S
UTILITIES.
GROMMET
(IN NORMAL
OSITION)
P
DRIP LEG
U
NION
TOP VIEW OF GAS LINE AND VALVE
IN OPT. POSITION
URNERS
B
AS VALVE
G
G
OTE: WHEN GAS LINE
N
IS IN OPT. POSITION,
SWAP LOCATION OF
ROMMET AND PLUG.
G
OPT. GAS LINE
OSITION
P
PLUG
(IN NORMAL
OSITION)
P
ANIFOLD
M
PRESSURE
TAP
GNITOR
I
MANIFOLD
DOWNFLOW
ROMMET
IGNITOR
G
OTE: WHEN GAS
N
LINE IS IN OPT.
POSITION, SWAP
OCATION OF
L
GROMMET AND
PLUG.
AS VALVE
G
PLUG
(IN NORMAL
POSITION)
MANIFOLD
PRESSURE
TAP
MANIFOLD
I328
ANUAL
M
G
TOP
S
TO 5 FEET ABOVE
4
FLOOR REQ’D BY
SOME UTILITIES.
GROMMET
(IN NORMAL
POSITION)
DRIP LEG
AS
TOP VIEW OF GAS LINE AND VALVE
N OPT. POSITION
I
UNION
BURNERS
HORIZONTAL
MANUALGAS STOP
UNION
DRIP LEG
BURNERS
MANIFOLD
GAS VALVE
I524
IMPORTANT: DO NOT RUN A FLEXIBLE GAS CONNECTOR INSIDE THE
UNIT. Extend the 1/2" black pipe from the gas valve to the outside of the cabinet.
37
Page 38
use a pipe compound resistant to the
action of liquefied petroleum gases on
all threaded connections.
IMPORTANT: When making gas pipe
connections, use a back-up wrench to
prevent any twisting of the main gas
valve and manifold. Do not
overtighten gas valve on pipe.
Any strains on the gas valve can
change the position of the gas orifices
in the burners. This can cause erratic
furnace operation.
IMPORTANT: Do not run a flexible
gas connector inside the furnace. The
as pipe gasket in the cabinet does
g
not seal around a flexible gas line.
If local codes allow the use of a
flexible gas appliance connector,
always use a new listed connector.
Do not use a connector which has
previously serviced another gas
appliance. Massachusetts law
requires that all flexible connectors be
less than 36”.
It is important to have all openings in
the cabinet burner compartment
sealed for proper furnace operation.
IMPORTANT: ENSURE that the
furnace gas valve not be subjected to
high gas line supply pressures.
DISCONNECT the furnace and its
individual manual gas stop from the
gas supply piping during any pressure
testing that exceeds 1/2 PSIG. (3.48
kPa).
TABLE 6
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
apacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
C
ravity of 0.60 (natural gas).
g
ominalLength of Pipe, Feet
N
Iron Pipe
Size, Inches1020304050607080
/213292736356504643
1
3/42781901521301151059690
1
1-1/41,050730590500440400370350
-1/21,6001,100890760670610560530
1
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
equired for the gas input rating of the furnace. By formula:
r
he gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT
T
determined by consulting the local natural gas utility or the LP gas supplier.
520350285245215195180170
as Input of Furnace (BTU/HR)
Cu. Ft. Per Hr. Required=
G
Heating Value of Gas (BTU/FT
3
)
3
may be
)
FIGURE 36
TYPICAL GAS VALVE
GAS VALVE #60-101921-02
AS CONTROL
G
WITCH
S
IGH FIRE
H
ANIFOLD
M
RESSURE
P
DJUSTMENT
A
LOW FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
GAS PRESSURE
Natural gas supply pressure should
be 5" to 10.5" w.c. LP gas supply
pressure should be 11" to 13" w.c.
This pressure must be maintained
with all other gas-fired appliances in
operation.
The minimum gas supply pressure to
the gas valve for proper furnace input
adjustments is 5" w.c. for natural gas,
however 6" to 7" is recommended.
The minimum gas supply pressure is
11" w.c. for LP gas.
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
CAUTION
!
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT)
NEED TO BE CHANGED. SEE THE
SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS”OF THIS BOOK
FOR INSTRUCTIONS.
NEVER PURGE A GAS LINE INTO
INLET
PRESSURE
TAP
THE COMBUSTION CHAMBER.
WARNING
!
NEVER USE MATCHES, FLAME OR
ANY IGNITION SOURCE FOR
CHECKING LEAKAGE. FAILURE TO
ADHERE TO THIS WARNING CAN
CAUSE A FIRE OR EXPLOSION
RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
To check for gas leakage, use an
approved chloride-free soap and water
solution, or other approved method.
GAS VALVE
This furnace has a 24-volt gas valve. It
has ports for measuring supply and
OUTLET
PRESSURE
TAP
manifold gas pressure. The valve
body contains a pressure regulator to
maintain proper manifold gas
pressure.
A control switch is on the valve body.
It can be set to only the “ON” or“OFF”positions. The gas valve is a
slow-opening valve. See Figure 36.
When energized, it takes 6 to 8
seconds to fully open.
38
Page 39
LP CONVERSION
IMPORTANT: LP gas from trucks
used to transport liquid-based
fertilizers can contain chemicals that
will damage the furnace. Verify that
your gas supplier does not use the
same truck to transport materials
other than LP.
For LP conversion, a new gas valve is
required. The new gas valve is
included in the LP kit. The correct LP
orifices should be selected based on
the altitude of the installation (see
chart below). Orifices included in the
kit are for sea level to 2000 ft.
(1.15mm) and 3000 to 4000 ft.
(1.10mm) The LP Gas Valve Kit is
FP19. Orifices for elevations 4000 ft.
and above must be ordered. Refer to
Table 7.
CAUTION
!
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT)
NEED TO BE CHANGED. SEE THE
SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS”OF THIS BOOK
FOR INSTRUCTIONS.
NOTE: Furnace conversion to LP gas
must be performed by a qualified
installer, service agency or the gas
supplier.
To change the gas valve and orifice
spuds for either conversion to LP or for
levation:
e
1. Shut off the manual main gas valve
and remove the gas manifold.
2. Replace the orifice spuds.
3. For LP conversion ONLY, Remove
the gas valve.
4. Reassemble in reverse order. In
LP applications, use the new gas
valve provided in the LP
conversion kit.
5. Attach the notice label alerting the
next service technician that the
furnace has been converted to LP
gas.
6. Turn the gas supply back on and
check for proper operation, leaks
and manifold pressure. See
Figures 37 and 39.
NOTE: Orifices in the kit are sized for a
heating value of 2500 BTU per cubic ft.
for LP.
ORIFICE ORDERING
INFORMATION
Orifice sizes are selected by adding the
2-digit drill size required in the orifice
part number. Drill sizes available are 39
through 64; metric sizes available
1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill
size)
Example 1:
# 60 drill size orifice required
Part # 62-22175-60
Example 2:
1.15mm drill size orifice required
Part # 62-22175-91
NOTE: Do not
TABLE 7
Altitudeburner) 15000Size
0 to 2000 ft.150001.15 mm
2000’-3000’132001.15 mm
3000’-4000’126001.10 mm
4000’-5000’12000#58
5000’-6000’11400#59
6000’-7000’10800#60
7000’-8000’10200#62
8000’-9000’9600#63
9000’-10000’9000#64
plug or drill out orifices.
BTU Input (perOrifice
(factory)
SETTING GAS PRESSURE
The maximum gas supply pressure
to the furnace should be 10.5" w.c.
natural gas, or 13" w.c. LP gas. The
inimum supply gas pressure to the
m
gas valve should be 5" w.c. natural
gas or 11" w.c. LP gas. A properly
calibrated U-Tube manometer is
required for accurate gas pressure
measurements.
CAUTION
!
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT)
NEED TO BE CHANGED. SEE THE
SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS”OF THIS BOOK
FOR INSTRUCTIONS.
Supply Gas Pressure Measure-ment.
A line pressure tap is on the input
side of the gas valve. See Figure 37.
1. With gas shut off to the furnace
at the manual gas stop outside
the unit, remove the input
pressure tap plug.
2. Connect a U-Tube manometer to
the pressure tap.
3. Turn on the gas supply and
operate the furnace and all other
gas-fired units on the same gas
line as the furnace.
4. Note or adjust the line gas
pressure to give:
A. 5" - 10.5" w.c. for natural gas.
B. 11" - 13" w.c. for LP gas.
5. Shut off the gas at the manual
gas stop and remove the
U-Tube manometer.
6. Replace the pressure tap plug
before turning on the gas. Turn
on gas and check for leaks.
If the supply gas line pressure is
above these ranges, install an in-line
gas regulator to the furnace for
natural gas units. With LP gas, have
the LP supplier reduce the line
pressure at the regulator.
If supply gas line pressure is below
these ranges, either remove any
restrictions in the gas supply piping or
enlarge the gas pipe. See Tables 6
and 8. With LP gas, have the LP
supplier adjust the line pressure at
the regulator.
Manifold Gas Pressure Measurement.
Natural gas manifold pressure should
39
Page 40
IGURE 37
F
ANIFOLD PRESSURE TAP
M
ANIFOLD
M
RESSURE
P
TAP
FIGURE 38
TYPICAL GAS VALVE
INLET
PRESSURE TAP
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
LOW FIRE
PRESSURE
MANIFOLD
ADJUSTMENT
OUTLET
PRESSURE
TAP
TABLE 8
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
be 3.5" w.c.; LP gas manifold
pressure should be 10" w.c. Only
small variations on gas pressure
should be made by adjusting the
pressure regulator.
1. With the gas shut off at the
anual gas stop, remove the
m
pressure tap plug in the gas
manifold or the gas valve outlet.
See Figure 37.
2. Connect a U-Tube manometer to
his pressure tap. See Figure 39.
t
3. Turn on the gas supply and
operate the furnace in high heat
mode.
4. Note or adjust the manifold gas
pressure to give:
A. 3.5" w.c. for natural gas high
fire.
B. 10" w.c. for LP gas high fire.
5. To adjust the pressure regulator
for high fire, remove the regulator
cap located on the side of theregulator. See Figure 38.
6. Turn the adjustment screw
clockwise to increase pressure or
counterclockwise to decrease
pressure.
7. Securely replace the regulator
cap for high fire.
8. Operate the furnace in low
speed.
9. Note or adjust the manifold
pressure to give:
A. 1.7" w.c. for natural gas low
fire.
B. 4.8" w.c. for LP gas low fire.
10. To adjust the pressure regulator
for low fire, remove the regulator
cap on the top of the regulator.
See Figure 38.
11. Turn the adjustment screw
clockwise to increase pressure or
counterclockwise to decrease
pressure.
12. Securely replace the regulator
cap for low fire.
13. Verify pressures for high and low
fire operation.
14. Shut off gas at the manual gas
valve and remove the U-Tube
manometer.
15. Replace the manifold pressure
tap plug before turning on gas.
Check for leak.
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
40
Page 41
IGURE 39
F
YPICAL MANIFOLD PRESSURE READING
T
41
Page 42
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT
FUSE BOX OR SERVICE PANEL
BEFORE MAKING ANY ELECTRICAL
CONNECTIONS. FAILURE TO DO SO
CAN CAUSE ELECTRICAL SHOCK
RESULTING IN PERSONAL INJURY
OR DEATH.
NOTE: Electric to furnace must be
supplied by commercial utility. Proper
voltage is 110-125 volts.
WARNING
!
THE CABINET MUST HAVE AN
UNINTERRUPTED GROUND
ACCORDING TO THE LATEST
EDITION OF THE NATIONAL
ELECTRICAL CODE, ANSI/ NFPA70OR IN CANADA, THE CANADIAN
ELECTRICAL CODE, CSA-C221 OR
LOCAL CODES THAT APPLY. DO NOT
USE GAS PIPING AS AN ELECTRICAL
GROUND. A GROUND SCREW IS
PROVIDED IN THE JUNCTION BOX.
FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING IN
PERSONAL INJURY OR DEATH.
WARNING
!
THIS FURNACE IS EQUIPPED WITH A
BLOWER DOOR SAFETY SWITCH.
DO NOT DISABLE THIS SWITCH.
FAILURE TO FOLLOW THIS
WARNING CAN RESULT IN
ELECTRICAL SHOCK, PERSONAL
INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical
components are protected from water
(condensate).
Before proceeding with the electrical
connections, be certain that the voltage,
frequency and phase corresponds to
that specified on the furnace rating
plate. For single furnace application,
maximum over-current protection is 15
amperes.
Use a separate fused branch electrical
circuit containing a properly sized fuse
or circuit breaker. Route this circuit
directly from the main switch box to an
electrical disconnect that is readily
accessible and located within site of the
furnace. Connect from the electrical
disconnect to the junction box on the left
side of the furnace, inside the blower
compartment. For the proper
connection, refer to the appropriate
wiring diagram located on the inside
over of the furnace control box and in
c
these instructions.
NOTE: UPFLOW MODELS ONLY
The electrical junction box may be
moved to the right side if necessary. A
nockout is provided. Seal the opposite
k
hole with plug provided.
NOTE: L1 (hot) and N (neutral) polarity
must be observed when making field
connections to the furnace. The ignition
control may not sense flame if L1 and
Neutral are reversed. When L1 and
Neutral are reversed, a diagnostic code
of 6 blinks followed by a pause and 6
blinks will be displayed on the control
FIGURE 40
LINE VOLTAGE CONNECTIONS
UT ELECTRONIC CONTROLS 1095-201 CONTROL BOARD
board “Status” L.E.D. See Figure 40.
Make all electrical connections in
ccordance with the latest edition of
a
the National Electrical Code
ANSI/NFPA70 and local codes having
jurisdiction.
These may be obtained from:
National
National Fire Protection
Batterymarch Park
Quincy, MA 02269
CSA
CSA - International
178 Rexdale Blvd.
Etobicoke (Toronto), Ontario
Canada M9W, 1R3
Electric Code
Association, Inc.
Standards
42
Page 43
IGURE 41
F
HERMOSTAT WIRING OPTIONS
T
2 HEAT - 1 COOL
HEAT, 1 COOL
1
OPTION A) TIMED STAGING W/1
(
TAGE HEAT T-STAT (AFTER F3507
S
ATE CODE (AUGUST 2007)
D
2 HEAT - 2 COOL
THERMOSTAT
NOTE: Do not use 24 volt control wiring
smaller than No. 18 AWG. (Refer to
Table 9.)
See Figure 41 for thermostat wiring
options.
A single- or two-stage thermostat may be
used, however, a two-stage thermostat is
recommended for optimum performance.
The room thermostat must be compatible
with the integrated furnace control on the
furnace. Generally, all thermostats that
are not of the “current robbing” type are
compatible with the integrated furnace
control being used.
Install the room thermostat in accordance
with the instruction sheet in the box with
the thermostat. Run the thermostat lead
wires inside the control compartment.
Connect the thermostat as shown on the
wiring diagram. Never install the
thermostat on an outside wall or where it
will be influenced by drafts, concealed
hot or cold water pipes, lighting fixtures,
radiation from fireplace, rays of sun,
lamps, television, radios or air streams
from registers. Refer to the instructions
packed with the thermostat for best
anticipator adjustment or selection.
Locate the thermostat approximately five
feet up from the floor.
HEAT ANTICIPATOR SETTINGS
If a current reading taken at the
thermostat is not performed, an initial
setting of .15 amps is recommended.
(OPTION B) 100% HEAT ALWAYS -- NO TIMED STAGING
1 HEAT, 1 COOL
FIELD-INSTALLED OPTIONAL ACCESSORIES
Adjust as needed to improve comfort
level.
ISOLATION RELAY
IMPORTANT: NOT ALL ELECTRONIC
NIGHT SETBACK THERMOSTATS
ARE COMPATIBLE WITH THE
FURNACE CONTROL SYSTEM.
SOME MAY REQUIRE AN ISOLATION
RELAY.
If an isolation relay is needed, install it
as close to the control board as
possible. Use a single-pole, singlethrow relay with a 24 volt operating coil.
The relay contacts should be designed
for 24 volt loads.
Connect one end of the operating coil
to the thermostat “W” terminal.
Connect the other end of the coil to the
“C” terminal on the control board.
➢ Connect a jumper from the coil
terminal connected to the thermostat to
one of the normally open relay
contacts.
➢ Connect the other side of the
normally open relay contacts to the
control board “W” terminal if using a
two stage thermostat. Connect that one
side of the normally open relay
contacts to the control board “W2”
terminal if using a single stage
thermostat.
When the thermostat calls for heat, it
powers the 24 volt operating coil. This
closes the relay contacts and
conducts power from terminal 3 and 4
to terminal “W” on the control board
and starts the furnace ignition
sequence. See Figure 42.
➢ NOTE: Use of an isolation relay
with the two stage furnace is not
normally needed.
ELECTRONIC AIR CLEANER
Electronic air cleaner line voltage
power can be supplied from the screw
terminal “EAC” and a line voltage
neutral screw terminal on the control
board. This will power the electronic
air cleaner whenever the circulating
air blower is in operation.
HUMIDIFIER
Line voltage power can be supplied
from screw terminal “HUM” to a line
voltage neutral screw terminal on the
control board. This will power the
humidifier during a normal heat
sequence after the blower has turned
on.
OTE: Do not use 24 volt control wiring smaller than No. 18.
N
FIGURE 42
ISOLATION RELAY
SOLID COPPER WIRE - AWG
3.0161412
2.5161412
2.0181614
0100150
LOAD - AMPS
5
ENGTH OF RUN - FEET ➀
L
FURNACE TWINNING
INSTALLATIONS
NOTE: Run furnaces as individual
furnaces before trying to twin or when
troubleshooting.
Twinning operation of two furnaces,
installed side-by-side, connected by a
common duct system with main power
supplied by the same source, and
controlled by a common thermostat can
be done with the UT Electronic Controls
1095-204 integrated control boards.
➀ Only twin identical furnaces with
identical control boards.
➁ Furnaces must have same heating
and blower capacity.
➂ Only bottom returns can be used.
(Upflow models only)
➃ No more than two furnaces (a pair)
can share the same supply and
return.
NOTE: Duct system must be adequate
to provide correct airflow to each
furnace for supply and return.
IMPORTANT: Twinning furnaces must
operate off the same phase of power.
ST-A0804-01
It should be noted that both blowers will
run simultaneously when there is a call
for heating, cooling or fan.
The status LED will display blink code 5
if twinning is not set up properly (refer to
Troubleshooting diagram in the back of
this manual).
IMPORTANT: Only two furnaces on a
single thermostat.
UT ELECTRONIC CONTROLS
1095-201 or 204
TWO-STAGE TWINNING OPERATION
USING A SINGLE-STAGE
THERMOSTAT
A two-stage thermostat will give the
most optimum performance. The
furnace (when twinned) can operate
using a single-stage thermostat.
OPTION A: To run both units together
as a single-stage furnace with NO
staging (100% high heat always) wire
the two furnaces together as shown in
Figure 43.
Both controls must have jumper P6 in
the “TWIN” position (see Figure 48).
Both controls must have jumper P7 in
the “5” or “7” position (see Figure 48).
OPTION B: Both controls must have
jumper P6 in the “TWIN” position (see
Figure 48).
Both controls must have jumper P7 in
the “5” or “7” position (see Figure 48).
For the first fire or twelve minutes of
operation, the furnace will run at low
fire. If the thermostat does not satisfy
in fire or twelve minutes, the furnaces
will automatically switch to high fire
and will run on high fire until the
thermostat is satisfied. See Figure 43
for the wiring diagram for this
configuration.
TWO-STAGE OPERATION
(See Figure 45)
a. Control board "ONE" is on
furnace connected to the
thermostat.
b. The 24 VAC supply to both
control boards must be in
phase with each other.
c. Connect the "C," "W1," “W2,”
“Y,” and "TWIN" terminals to
counterparts on each control.
d. Both control boards must have
jumper P6 in the “TWIN”
position (see Figure 48).
Both controls must have
jumper P7 in the “NONE”
position (see Figure 48).
44
Page 45
IGURE 43
F
T Electronic Controls 1095-201 IFC, TWINNING CONNECTION -- SINGLE STAGE OPERATION
U
45
Page 46
IGURE 44
F
UT ELECTRONIC CONTROLS 1095-202 CONTROL BOARD, TWINNING CONNECTION -- TWO-STAGE OPERATION
46
Page 47
FIGURE 45
UT ELECTRONIC CONTROLS 1095-202 CONTROL BOARD, TWINNING CONNECTION -- TWO-STAGE OPERATION
47
Page 48
0+ HIGH ALTITUDE
9
INSTRUCTIONS
NATURAL GAS
!
CAUTION
INSTALLATION OF THIS FURNACE AT
ALTITUDES ABOVE 2000 FT (610 m)
SHALL BE IN ACCORDANCE WITH
OCAL CODES, OR IN THE ABSENCE
L
OF LOCAL CODES, THE NATIONAL
FUEL GAS CODE, ANSI Z223.1/NFPA
54 OR NATIONAL STANDARD OF
CANADA, NATURAL GAS AND
PROPANE INSTALLATION CODE,
CAN B149.1.
INSTALLATION OF THIS APPLIANCE
AT OR ABOVE 5000 FT (1525 m)
SHALL BE MADE IN ACCORDANCE
WITH THE LISTED HIGH ALTITUDE
CONVERSION KIT AVAILABLE WITH
THIS FURNACE.
!
CAUTION
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT) NEED
TO BE CHANGED. THE FOLLOWING
EXAMPLES SHOW HOW TO
DETERMINE IF AN ORIFICE CHANGE
WILL BE NECESSARY AND HOW TO
DETERMINE THE NEW ORIFICE SIZE.
IN CANADA, AS AN ALTERNATE TO
SIZING THE BURNER ORIFICE, THE
MANIFOLD GAS PRESSURE MAY BE
ADJUSTED. THIS METHOD IS
COVERED LATER IN THIS SECTION.
THIS METHOD OF ADJUSTING
MANIFOLD PRESSURE MAY ONLY
BE USED IN CANADIAN
INSTALLATIONS.
34" 90 Plus furnaces installed at high
elevations require the installation of a
high altitude kit for proper operation. The
high altitude kit consists of a high
altitude pressure switch that replaces
the pressure switch attached to the
induced draft blower.
IGH ALTITUDE KIT
H
Installer must make necessary burner
orifice and pressure switch changes as
indicated in the table below:
(-)GRK/(-)GRL PRESSURE SWITCH CHANGES
IGH ALTITUDESET POINTSET POINT
H
INPUT
45,000RXGY-F18-1.08NO CHANGE
0,000RXGY-F18-1.08NO CHANGE
6
75,000 (N)N/ANO CHANGE NO CHANGE
5,000 (W)RXGY-F18-1.08NO CHANGE
7
0,000RXGY-F20-1.15NO CHANGE
9
105,000N/ANO CHANGE NO CHANGE
20,000RXGY-F21-0.50-0.30
1
IT NO.HIGH FIRELOW FIRE
K
Alternately, furnaces can be ordered
from the factory already converted for
high altitude elevations. The factory
option for high altitude elevations
would be ordered as a 278 option
(example; a 105k BTU upflow furnace
which is factory converted for high
altitude elevations would have the
model number (-)GRK-10EZAJS278
These factory converted furnaces
come with a pressure switch for highaltitude elevations already attached.
Also, different burner orifices are
installed at the factory which are one
drill size smaller (#51 DMS) than
standard (-)GRK gas furnaces (#50
(-)GTK PRESSURE SWITCH CHANGES
INPUT
60,000RXGY-F29-1.0-0.8
5,000 (N)RXGY-F30-0.8-0.6
7
75,000 (W)RXGY-F30-0.8-.06
0,000RXGY-F31-0.9-.06
9
105,000RXGY-F32-0.7-.04
20,000RXGY-F33-0.4-0.3
1
ITHIGH FIRELOW FIRE
K
IGH ALTITUDE
H
NOTE: Orifices are no longer supplied
with kit.
The pressure switch must be installed
at elevations above 5000 ft. Elevations
above 2000 ft. require the furnace to be
de-rated 4% per thousand feet.
The necessary high altitude kits to use
with (-)GRK/(-)GRL & (-)GTK furnace
models are listed below:
DMS). The smaller orifice is installed
to accommodate for average heating
values expected in most high altitude
areas and a required 4% per
thousand feet reduction in input as
specified by the National Fuel GasCode (NFGC). Specific orifices
should always be recalculated for all
high altitude installations as outlined
below. Orifices should be changed, if
necessary, based on gas heating
value and elevation.
NOTE: Factory installed orifices are
calculated and sized based on a sea
level Natural Gas heating value of
1075 BTU per cubic ft. Regional
reduced heating values may nullify
the need to change orifices except at
extreme altitudes.
NOTE: 278 Option Code is available on
(-)GRK/(-)GRL models only.
sizing using the National Fuel Gas
Code Appendix F. For a simplified
estimation of orifice size based on
heating value and elevation, use
Tables 8 and 10, however
calculations are the best method.
Example: 900 BTU/ft
3
Regional
Natural Gas Heating Value
I / H = Q
15000 / 900 = 16.68 ft
3
/hr
I = Sea Level input (per burner):
15000
H = Sea Level Heating Value: 900
Q = 16.68 ft3Natural Gas per hour.
From Table F.1 of National Fuel GasCode Handbook, 2002 (3.5” w.c.
column)
Orifice required at Sea Level: #48
From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation
(4% de-rate per thousand ft.): #50
Orifice required at 8000 ft. elevation
(4% de-rate per thousand ft.): #51
TABLE 10
Natural Gas Orifice Drill Size (4% per 1000 ft. De-Rate)
IMPORTANT: 90 Plus Models only. Do not use this chart for any 80 Plus Models.
Burner Input (per burner) 15,000 BTU @ Sea Level
Annual Avg. Heat
Value (btu per ft
Sea level 2000 to 3000 to 4000 to 5000 to 6000 to 7000 to 8000 to
3
)
to 1999 ft 2999 ft3999 ft4999 ft5999 ft5999 ft7999 ft8999 ft
850
900
burner capacity by the Cubic Foot value for the Heat Value. Once you have either the Cubic Foot Value or the Heat Value you can estimate the Sea
NOTE:
Heat Value at Sea Level, for the location of the installation, is available from the Natural Gas Supplier to that site. Orifices for all altitudes are based
All calculations are performed by using the first three columns of information only. Before beginning any calculations, determine the
individual burner Btu size and heating value at Sea Level for the installation site. Each value shown in the Heat Value column is per
burner at 3.5" W.C.
on Sea Level values.
Divide the individual burner capacity (15,000 for 90 plus) by the Heat Value for the site to determine the Cubic Foot value at Sea Level, or divide
these two points on the chart above.
Level orifice for the site. To select the corresponding high altitude orifice, locate the site elevation on the chart above and the orifice required at Sea
Level from your calculation in the first column. The correct high altitude orifice that must be installed in each individual burner is the intersection of
49
Page 50
TABLE 12
IMPORTANT: 90+ MODELS ONLY. DO NOT USE THIS CHART
OR ANY 80 PLUS MODELS.
F
P GAS ORIFICE DRILL SIZE (4% PER 1000 FT DE-RATE)
L
AltitudeInput (per burner) 15000Orifice Size
0 to 2000 ft150001.15 mm (factory)
2001 to 3000132001.15 mm
3001 to 4000126001.10 mm*
4001 to 500012000#58*
5001 to 600011400#59**
6001 to 700010800#60**
7001 to 800010200#62**
8001 to 90009600#63**
9001 to 10000 9000#64**
** : -GRL-07 and -GRL-10 models use 1.15mm orifice
** : -GRL-07 model uses 1.15mm orifice
** : -GRL-10 model uses 1.10mm orifice
Example: 1050 BTU/ft3Regional Natural
Gas Heating Value
I / H = Q
15000 / 1050 = 14.63 ft.
3
I = Sea Level input (per burner): 15000
H = Sea Level Heating Value: 1050
Q = 14.28 ft.
3
Natural Gas per hour.
From Table F.1 of National Fuel GasCode Handbook, 2002 (3.5” w.c. column)
Orifice required at Sea Level: #50
From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4%
de-rate per thousand ft.): #51
Orifice required at 8000 ft. elevation (4%
de-rate per thousand ft.): #52
LP GAS AT HIGH ALTITUDE
ELEVATIONS
LP Gas is a manufactured gas that has
consistent heating value across most
regions.
The NFGC guidelines are used with the
following exception:
The recommended LP Gas high altitude
orifice selections differ slightly in that the
NFGC LP orifice chart, as they are not
accurate for Rheem products. The
National Fuel Gas Code LP orifices are
based on an 11" of water column
pressure at the orifice, which differs from
Rheem products that use 10" of water
column at the orifice. This difference
requires a deviation from the NFGC
orifice size recommendations. The Sea
Level input should still be reduced by 4%
per thousand ft. and the orifice size must
be selected based on the reduced input
selection shown in Table 12.
ALTERNATE METHOD FOR
CANADIAN
HIGH-
ALTITUDE DERATE
In Canada, unless an orifice change
is specifically mandated by local
codes, an alternate method of altitude
deration through a reduction in
manifold pressure is acceptable as
escribed in Table 13.
d
The information in Table 13 is based
on a heating value of 1000 BTU per
cubic feet of natural gas, and 2500
BTU per cubic feet of LP gas.
IMPORTANT: Actual input rates must
be measured on-site with manifold
pressure adjustment to ensure that an
actual 10% reduction in input rate is
ORIFICE ORDERING
INFORMATION
IMPORTANT: Do not plug or drill out
orifices.
Orifice sizes are selected by adding the
2-digit drill size required in the orifice
part number. Drill sizes available are 39
through 64; metric sizes available
1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill
size)
Example 1:
#60 drill size orifice required
Part # 62-22175-60
Example 2:
1.15mm drill size orifice required
Part # 62-22175-91
TABLE 13
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE
IMPORTANT: 90+ MODELS ONLY. DO NOT USE THIS CHART FOR ANY 80 PLUS MODELS.
NATURAL GASLP GAS
ORIFICE
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
45,000
60,000
75,000
90,000
105,000
120,000
40,500
54,000
67,500
81,000
94,500
108,000
OUTPUT
40,500
54,000
67,500
81,000
94,500
108,000
36,450
48,600
60,750
72,900
85,050
97,200
FIGURE 46
MANIFOLD PRESSURE-CHANGE LABEL
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
MANIFOLD
SIZE
PRESSURE
#50
3.5” W.C.
#51
3.0” W.C.
BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT
INPUT RATING FOR INSTALLATION AT ALTITUDES
achieved.
Once this field adjustment has been
made, the label shown in Figure 46
must be affixed in a conspicuous
location on the front of the furnace
cabinet:
NOTE: This label is supplied in the
information packet shipped with each
furnace.
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
45,000
60,000
75,000
90,000
105,000
120,000
40,500
54,000
67,500
81,000
94,500
108,000
OUTPUT
40,500
54,000
67,500
81,000
94,500
108,000
36,450
48,600
60,750
72,900
85,050
97,200
ORIFICE
SIZE
1.15mm
1.10mm
MANIFOLD
PRESSURE
10” W.C.
7.6” W.C.
50
LA PRESSION DU DISTRIBUTEUR D’ALIMENTATION
DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D’OBTENIR LA BONNE PUISSANCE D’ENTRÉE POUR
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
D’ALTITUDE.
92-24399-01-01
Page 51
START-UP PROCEDURES
A gas furnace’s firing rate, temperature
rise and operation should be checked
after installation. During this process we
recommend that doors and windows be
opened, smoke alarms disabled
temporarily, as furnaces may have
some residual smoke and odor upon
initial operation through the first heating
cycle. We do all we can to control our
manufacturing processes, but it is
possible to have this issue on certain
sizes and models on occasion. Failure
to follow this caution could result in a
nuisance smoke (fire call) or other
smoke or odor complaint from the
customer.
DIRECT SPARK IGNITION
LIGHTING INSTRUCTIONS
This appliance is equipped with a direct
spark ignition device. This device lights
the main burners each time the room
thermostat (closes) calls for heat. See
lighting instructions on the furnace.
During initial start-up, it is not unusual
for odor or smoke to come out of any
room registers. It is recommended to
ensure proper ventilation by opening
windows and doors, before initial firing.
The furnace has a negative pressure
switch that is a safety during a call for
heat. The induced draft blower must pull
a negative pressure on the heat
exchanger to close the negative
pressure switch. The induced draft
blower must maintain at least the
negative pressure switch set point for
the furnace to operate. If the induced
draft blower fails to close or maintain the
closing of the negative pressure switch,
a “no heat call” would result.
WARNING
!
TO START FURNACE
1. BE SURE THAT THE MANUAL GAS
STOP HAS BEEN IN THE “OFF”
POSITION FOR AT LEAST FIVE
MINUTES. DO NOT ATTEMPT TO
MANUALLY LIGHT THE MAIN
BURNERS. FAILURE TO FOLLOW
THIS WARNING CAN CAUSE A
FIRE OR AN EXPLOSION
RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
2. Set the room thermostat to the lowest
setting.
3. Remove furnace panel.
4. Turn the gas control knob to the “ON”
position, or set the gas control switch
to the “ON” position.
5. Securely replace furnace panel.
6. Turn on the manual gas stop and the
electrical power.
7. Set the room thermostat to “Heat” and
adjust to desired room temperature.
8. Complete installation checklist.
WARNING
!
SHOULD OVERHEATING OCCUR OR
THE GAS SUPPLY FAIL TO SHUT
OFF, SHUT OFF THE MANUAL GAS
STOP TO THE APPLIANCE BEFORE
SHUTTING OFF THE ELECTRICAL
SUPPLY. FAILURE TO DO SO CAN
CAUSE AN EXPLOSION OR FIRE
RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
IGNITOR PLACEMENT,
ALIGNMENT & LOCATION
Ignition failure may be a result of
improper ignitor alignment caused during
a service call or other work done to the
furnace in the field. When performing any
work on the burner, heat exchanger, etc.,
the technician must check alignment of
the spark ignitor. Misalignment of the
ignitor could cause a failure to light or
rough ignition. The correct ignitor
alignment is shown in Figure 47.
Sequence of operation with a single
stage heat thermostat
NOTE: Single-stage operation is
determined by the position of the jumper
at position P7 of the control board.
Options are 5 minutes between first and
second stage or 12 minutes between
first and second stage (see Figure 48).
Do not leave jumper at P7 in the
“NONE” position when using a single-
stage thermostat with the timed
staging feature. If the jumper is left
on “NONE”, the furnace will never
reach high heat (100% heat).
For single-stage operation, “W” from
the thermostat must be connected to
“W” on the furnace control.
See the section of this book titled
“Electrical Wiring – Thermostat” for a
wiring diagram showing how to
connect a thermostat (see Figure
41).
a. Connect the “W” terminal on the
thermostat to the “W” terminal on
the IFC. Do not connect any wire
to “W” on IFC when using a singlestage thermostat.
b. When there is a call for heat, the
“R” and “W2” contacts close and
the IFC runs a self check routine to
verify that both of the pressure
switch contacts are open. The limit
switch contacts are constantly
monitored.
c. The induced draft motor starts on
high until the low and high
pressure switch contacts close (a
maximum of 60 seconds), and
then runs for a 30-second prepurge. After the 30-second prepurge, the spark ignitor energizes
and the high stage of the gas valve
opens, lighting the burners.
d. After the gas valve energizes, the
remote flame sensor must prove
ignition for one second using the
process of flame rectification. If the
burners do not light or flame is not
sensed, the system goes through
another ignition sequence. It does
this up to 4 times.
e. The IBM starts on low speed 20
seconds after the burners light and
flame is sensed. The induced draft
motor and gas valve switch to low
speed. The furnace operates on
low fire for 12 minutes and then, if
the thermostat is not satisfied,
shifts to high fire, causing the draft
inducer to go to high speed, the
FIGURE 47
UPFLOW OPTIMUM IGNITOR LOCATION
DOWNFLOW/HORIZONTAL OPTIMUM IGNITOR LOCATION
51
Page 52
gas valve to 100% and the main
blower goes to high-fire heating
speed.
f. When the thermostat cycle ends, the
gas valve de-energizes, and the
burners go out.
g. The draft inducer will continue
running for a 10 second post purge.
h. The main blower will run for for the
user-defined blower-off delay (this
timing is field adjustable, for 90, 120
150, or 180 seconds at Jumper P6 on
the furnace control board). See Figure
48 for switch settings.
Sequence if the system doesn’t light or
doesn’t sense flame:
a. If flame is not sensed within 8
seconds after the gas valve energizes,
the valve and the ignitor are deenergized. The induced draft motor
will, stop momentarily, and then restart
to check PS operation.
b. The ignition process goes through
three more tries.
c. If there is no ignition after the fourth
trial, the furnace goes into soft lockout
for one hour.
d. The sequence repeats after a one
hour delay and continues repeating
until ignition is successful or the call
for heat is terminated.
e. To reset the lockout, break power
either at the thermostat or at the unit
disconnect switch for 30 seconds. The
furnace will then go through another
set of trials for ignition.
f. If flame is established and maintained
during the trial for ignition period and
flame is lost, the gas valve is deenergized, the draft inducer stops after
a 10-second post-purge. The blower
motor runs at the high-fire or low-fire
heating speed (depending on state
when flame was lost) until it completes
the blower-off delay.
When the blower-off delay is over, the
control initiates another ignition trial
period by starting the inducer for the
pre-purge. The control will recycle up
to 5 flame losses (4 re-cycles) within a
single call for heat before going into
lockout.
TO SHUT DOWN FURNACE
1. Set the room thermostat to its lowest
setting.
2. Shut off the gas to main burners by
setting the gas control switch to the
“OFF” position, or by turning the
manual gas stop closed.
Sequence of operation with two
stage thermostat
See the section of this book titled
“Electrical Wiring - Thermostat” for a
wiring diagram showing how to connect
a thermostat.
Connect W1 on thermostat to W on IFC.
Connect W2 on thermostat to W2 on
IFC.
Call for 1st stage heat
a. R and W thermostat contacts close
and the IFC runs a self check routine.
After the IFC verifies that both sets of
pressure switch contacts are open,
the induced draft motor starts on high
until both pressure switch contacts
close (a maximum of 60 seconds).
b. After a 30 second pre-purge the spark
igniter energizes and the gas valve
(high stage) opens, lighting the
burners.
c. After the burners light, the remote
flame sensor must prove ignition. If the
burners do not light or flame cannot be
proven, the system goes through
another ignition sequence. It does this
up to 4 times.
d. Twenty seconds after flame sense,
the main blower energizes on low
speed, the gas valve drops to low fire,
and the inducer drops to low speed.
The furnace continues to run on low
until the call for heat is satisfied or the
second-stage contacts close. If the
first-stage call for heat is satisfied the
gas valve de-energizes and the
induced draft motor continues running
for a 10 second post purge time. The
main blower runs for the user-defined
blower-off delay (this timing is field
adjustable at Jumper P6). See Figure
48 for switch settings.
Call for 2nd stage heat after 1st stage
R and W2 thermostat contacts close,
calling for 2-stage heat. The induced
draft motor then switches to high
speed and the high pressure switch
contacts will close. The gas valve
switches to high fire and the main
blower switches to high-fire heating
speed.
2nd stage heat satisfied, 1st stage
heat still required.
R and W2 thermostat contacts open (W1
to R remains closed). The induced draft
motor switches to low speed, the main
blower motor switches to low-fire heating
speed and the gas valve changes to low.
The furnace continues to run in this mode
until the first-stage heat call is satisfied.
The system will shut down as noted in
“d,” under first-stage call for heat.
Call for second-stage heat with no other
existing heat call present.
a-c. Same operation as call for first-stage
heat
FIGURE 48
TWO-STAGE, 80 PLUS IFC JUMPER SELECTIONS
d.Main blower starts on high speed
20 seconds after gas valve
energizes. The furnace continues
to run on high until the W2
contacts open. If W2 and W1
open at the same time (both high
& low stages are satisfied), the
gas valve de-energizes and the
inducer continues to run for a 10second post-purge. The main
blower runs for the user selected
blower-off delay. See Figure 48
for switch settings.
NOTE: Under certain conditions the
furnace may alternate between low
and high fire continuously. This
operation is based on demand from
the thermostat and is controlled by
the thermostat. This operation is
normal and can be expected at times
to maintain optimum comfort.
SETTING BLOWER TIMING
The UT ELECTRONIC CONTROLS
IFC has four quick connect terminals
for connecting the motor speed
leads. These are:
1. FAN SPEED/LOW — motor runs
on this speed when the
thermostat is in the “FAN ON”
position or when in low-fire
heating speed heat.
4. HEAT/COOL — connect desired
speed when high heating and
cooling speed are the same.
High fire and low fire blower timing
are the same.
IMPORTANT: Do not connect any
motor speeds to “HEAT” or “COOL” if
you use the “HEAT/COOL” terminal.
52
Page 53
DJUSTING OR CHECKING
A
URNACE INPUT
F
A properly calibrated manometer or
gauge is required for accurate gas
pressure readings.
ATURAL GAS
N
1. When adjusting the furnace input,
he high fire input should be
t
checked. The high fire manifold
pressure should be 3.5’ W.C.
Follow these steps to be sure the
furnace is high fire mode:
. With a single stage thermostat, the
a
furnace runs for 12 minutes on low
fire before shifting to high fire. To
be certain that it is on high fire,
jump terminals “W” and “W2” on
the control board in the blower
compartment.
b. With a two stage thermostat, set
the thermostat to its highest setting
to keep the furnace operating in the
high fire mode.
2. To adjust high fire manifold
pressure, remove the adjustment
cover screw on the outlet end of
the gas valve and turn the
adjustment screw clockwise to
increase the pressure and
counterclockwise to reduce the
pressure. Replace the cover screw
securely. See Figure 38.
3. The low fire manifold pressure
should be 1.7” W.C. As mentioned
above, the furnace remains in the
low fire mode for 12 minutes upon
a heat call with a single stage
thermostat. With a two stage
thermostat, disconnect the
thermostat lead to the “W2”
terminal on the IFC and the furnace
will remain in the low fire mode. To
adjust the pressure, remove the
regulator cover, on top of the valve,
and adjust as noted under Step 2,
above. After the adjustment
replace the screw cover securely.
NOTE: Use a 3/32” allen wrench or
small-blade screwdriver for making
the pressure adjustment.
TABLE 14
METER TIME
ETER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES
M
INPUTSIZE
BTU/HRCU. FT.MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
45,000TEN1201320135014403320
60,000TEN901001024110250
75,000TEN71280819848200
0,000TEN60640707201640
9
05,000TEN510540606201420
1
20,000TEN430505105301230
1
METER
ONE112120123128320
ONE054101316230
ONE04404805005320
ONE036040042044140
O
O
ormula: Input BTU/HR =
F
LP GAS
On furnaces using LP gas, the LP gas
supply pressure must be set between
11.0" and 13.0" W.C. by means of the
tank or branch supply regulators. Set
the furnace manifold pressure at 10"
W.C. on high fire and 4.8" W.C. on
low fire at the gas control valve. For
elevations up to 8,000 feet, rating
plate inputs apply. For high altitudes
(elevations 5,000 ft. and over), the
orifice spud must be changed.
QUIPPED FOR NATURAL OR LP GAS
E
EATING VALUE OF GAS BTU PER CU. FT.
H
001000104011002500 (LP)
9
NE031034036038126
NE027030031033115
eating Value of Gas (BTU/FT
H
Time in Seconds (for 1 cu. ft.) of Gas
3
x 3600 x correction factor
)
SETTING INPUT RATE
The furnace is shipped from the
factory with #50 orifices. With -278
option code, furnaces will be shipped
with #51 orifice for elevations of 5000
ft. They are sized for natural gas
having a heating value of 1075
BTU/cu. ft. and a specific gravity of
.60.
Since heating values vary geographically, the manifold pressure
and/or gas orifice size may need to
be changed to adjust the furnace to
its nameplate input. Consult the local
gas utility to obtain the yearly average
heating value and orifice size required
to fire each individual burner at
15,000 BTU/HR.
Proper input is important to prevent
over firing of the furnace beyond its
design-rated input. NEVER SET
INPUT ABOVE THAT SHOWN ON
THE RATING PLATE.
To check furnace input:
1. Make certain that all other gas
appliances are shut off, with the
exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the
time required to burn one cubic foot
of gas. See Table 14.
53
Page 54
AIR FLOW
The importance of proper air flow over the
heat exchanger cannot be over
mphasized.
e
CAUTION
!
IT IS IMPORTANT THAT EACH DUCT
SYSTEM BE SIZED AND INSTALLED
FOR THE SPECIFIC APPLICATION BY
PROPERLY APPLYING THE
APPROPRIATE INDUSTRY ACCEPTED
TANDARD. IF LESS THAN MINIMUM
S
STANDARDS ARE APPLIED, THE
EQUIPMENT USER COULD EXPECT
TO EXPERIENCE HIGHER UTILITY
BILLS, MAJOR COMPONENT FAILURE,
VARYING DEGREES OF AIR NOISE OR
OTHER UNSATISFACTORY ISSUES,
OVER WHICH THE EQUIPMENT
MANUFACTURER HAS NO CONTROL.
TEMPERATURE RISE CHECK
To determine if the air flow is correct,
make a temperature rise check.
1. Insert a thermometer in the supply
air duct as close to the furnace as
possible yet out of a direct line from
the heat exchanger. See Figure 49.
2. Insert a thermometer in the return air
duct as close to the furnace as
possible.
3. Operate the furnace. High fire and
low fire heating modes have the
same temperature rise range.
4. When the thermometer in the supply
air duct stops rising (approximately
five minutes), subtract the return air
temperature from the supply air
temperature. The difference is the
temperature rise.
5. Compare the measured temperature
rise to the approved temperature rise
range listed on the furnace name
plate. See Figure 50.
If the measured temperature rise is above
the approved range, the air flow is too
low. More air must be moved by speeding
up the blower, by removing restrictions in
the duct system, or by adding more
supply or return air duct. If the measured
temperature rise is below the approved
range, the air flow is too much. Use lower
speed tap on the multi-speed blower.
RISE RANGE IS 40 TO 70 DEGREES,
THE MOST IDEAL RISE WOULD BE
55 DEGREES (THE MIDDLE OF THE
RISE RANGE). IN ALL
PPLICATIONS, THE INSTALLER
A
UST ADJUST THE TEMPERATURE
M
RISE TO THIS "MIDDLE" POINT AS
CLOSELY AS POSSIBLE. ALSO, THE
TEMPERATURE RISE SHOULD
NEVER BE ABOVE OR FALL BELOW
THE STATED RANGE. DOING SO
COULD CAUSE DAMAGE TO THE
HEAT EXCHANGER OR
INTERMITTENT OPERATION WHICH
OULD CAUSE INJURY OR DEATH
C
AND WILL VOID THE
MANUFACTURER'S WARRANTY FOR
THIS PRODUCT.
FIGURE 50
TYPICAL FURNACE NAME PLATE
AIR CONDITIONING DIVISION
FORT SMITH, ARKANSAS
IGURE 49
F
TEMPERATURE RISE MEASUREMENT
WARNING
!
THE MEASURED TEMPERATURE RISE
SHOULD BE AS CLOSE TO THE
MIDDLE OF THE STATED RANGE AS
POSSIBLE. FOR EXAMPLE, IF THE
54
Page 55
GAS FURNACE (DIRECT
DRIVE) INSTRUCTIONS
FOR CHANGING BLOWER
SPEED
WARNING
!
DISCONNECT THE ELECTRICAL
UPPLY TO THE FURNACE
S
BEFORE ATTEMPTING TO
CHANGE THE BLOWER SPEED.
FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING
IN PERSONAL INJURY OR DEATH.
The blower motor is wired for blower
speeds required for normal operation
as shown.
If additional blower speed taps are
available (leads connected to “M1”
and “M2” on the IFC), speeds may be
changed if necessary to fit
requirements of the particular
installation. Reconnect the unused
motor leads to “M1” or “M2” on the
Integrated Furnace Control Board
(IFC). Check motor lead color for
speed designation.
Heating speeds should not be
reduced where it could cause the
furnace air temperature to rise to
exceed the maximum outlet air
temperature specified for the unit.
IMPORTANT: Any combination of
motor taps to the IFC can be used
provided the temperature rise is
within the specified range when in
high or low heat and that there is
enough airflow in the cooling mode.
When changing the motor tap
speeds, the temperature rise must be
checked on both heat speeds and
temperature drop in cooling must be
checked again after the change is
made to ensure that the temperatures
are within the required specified
ranges.
55
Page 56
TABLE 15
90 PLUS AIR FLOW PERFORMANCE
FM @ ESP
MODELBLOWER/
MOTOR HP.1.2.3.4.5.6.7
(-)GRL-0411 X 7 /
1
⁄
2
PEED
S
PFLOW MODELS
U
LOW805780760720685645605
M-LO920885850810775730690
*
-HI11401110108510451010950890
M
HIGH1360132012801235119511401080
-)GRL-07(A)11 X 7 /
(
1
⁄
2
OW780745710675640595555
L
-LO880850825785750702655
M
*M-HI109010501010970925875825
HIGH1300125512101160111010551005
(-)GRL-0611 X 7 /
1
⁄
2
LOW770740710675645605570
*M-LO880845815790760715670
-HI10601025990960925880835
M
IGH126012151175113511001040985
H
(-)GRL-07(B)12 X 7 /
(-)GRL-09**12 X 11 /
3
⁄
4
3
⁄
4
LOW110510951080105010301010990
M-LO1290127512601220119511701140
*
-HI1480143514151390137013001255
M
IGH1705166516151570154014751400
H
LOW1235121011851150112010751035
-LO1490146514401405137513151255
M
*M-HI1720167016201600158015201460
HIGH2100205020001955191018251745
A = 17
B = 21" Cabinet Size
NOTE: CFM valves represent furnace-only airflow ratings.
**Where the maximum air flow is above 1800 CFM, we recommend both sides or 1 side and bottom to be used to maximize air flow.
C
56
Page 57
I528
HORIZONTAL
I413
MAINTENANCE
WARNING
!
THESE INSTRUCTIONS ARE
NTENDED AS AN AID TO
I
QUALIFIED SERVICE PERSONNEL
FOR PROPER INSTALLATION,
ADJUSTMENT AND OPERATION
OF THIS UNIT. READ THESE
NSTRUCTIONS THOROUGHLY
I
BEFORE ATTEMPTING
INSTALLATION OR OPERATION.
FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN
IMPROPER INSTALLATION,
ADJUSTMENT, SERVICE OR
MAINTENANCE, POSSIBLY
RESULTING IN FIRE, ELECTRICAL
TABLE 16
ILTER SIZES
F
UPFLOW FILTER SIZES
URNACEINPUTBOTTOMSIDE
F
IDTHMBTUHSIZESIZE
W
1
45, 60, 75A15
7
/2"
1
21"75B, 90, 10519
1
4
2
/2"
FURNACEINPUT
IDTHMBTUH
W
1
7
1
/2"
21"75B, 90, 10512" X 20"2
1
24
/2"12014" X 20"2
12022
DOWNFLOW/HORIZONTAL FILTER SIZES
60, 75A12" X 20"2
3
X 25"15
/4"
1
/4" X 25"153/4" X 25"1
3
X 25"15
/4"
3
/4"
3
/4"
IZE
S
SHOCK, CARBON MONOXIDE
POISONING, EXPLOSION,
PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
QUANTITY
X 25"1
X 25"1
UANTITY
Q
FIGURE 51
ILTER LOCATIONS
F
DOWNFLOW
AIRFLOW
HORIZONTAL
57
Page 58
IGURE 52
FILTER AND ROD ASSEMBLY
FILTERSUPPORTANGLE
FILTER
FILTER ROD
JACKET
I332
JACKET
DRILL (2)
3
/16" DIA.
HOLES
8.000
4.875
1.531
CUT-OUT AND DRILL DETAIL
JACKET
JACKET
ANGLE
FILTER RODSUPPORTANGLE
FILTER SUPPORTANGLE(SEE ANGLE DETAIL)
ATTACH WITH
SHEET METAL
SCREWS (2 REQÕD)
ANGLE DETAIL
ROD & FILTER SUPPORT ANGLE ASSEMBLY
F
BOTTOM PANEL REMOVAL
ILTER LOCATION
F
JACKET ASSEMBLY
REMOVE
SOLID BOTTOM
CREW
S
(2) REQ’D.
SOLID BOTTOM REMOVAL
UPFLOW BOTTOM RETURN
NOTE:
ACK FLANGE OF SOLID BOTTOM FITS
B
UNDERNEATH JACKET. SIDES AND FRONT
FLANGES FIT OVER FLANGES ON JACKET.
AIRFLOW
FILTER
ACKET ASSEMBLY
J
FILTER & ROD LOCATION
ILTER
F
ROD
UPFLOW SIDE RETURN
SOLID
BOTTOM
NOTE: Use both side returns for 1800 CFM or more.
58
AIRFLOW
FILTER SUPPORT
ANGLE
(SEE ANGLE DETAIL)
AE-61883-01
FILTER ROD
SUPPORT
ANGLE
AE-60520-01
SOLID
BOTTOM
FILTER ROD
SUPPORT
ANGLE
AE-60520-01
FILTER
SUPPORT
ANGLE
AE-61883-01
SOLID
BOTTOM
FILTER
FILTER
ROD
45-24095-01
Page 59
WARNING
!
DISCONNECT MAIN ELECTRICAL
POWER TO THE UNIT BEFORE
ATTEMPTING ANY MAINTENANCE.
AILURE TO DO SO CAN CAUSE
F
ELECTRICAL SHOCK RESULTING IN
PERSONAL INJURY OR DEATH.
FILTER MAINTENANCE
Have your qualified installer, service
gency or the gas supplier instruct you
a
on how to access your filters for
regular maintenance.
FILTERS
Filter application and placement are
critical to airflow, which may affect the
heating and cooling system
performance. Reduced airflow can
shorten the life of the system’s major
components, such as motor, limits, heat
exchanger, evaporator coil or
compressor. Consequently, we
recommend that the return air duct
system have only one filter location.
The most common location will be
inside the furnace or a filter base. For
systems with a return air filter grille or
multiple filter grilles, can have a filter
installed at each of the return air
openings. Your HVAC professional can
show you where they have installed the
filter(s).
If high efficiency filters or electronic air
cleaners are used in the system, it is
important that the airflow is not reduced
to maximize system performance and
life. Always verify that the system’s
airflow is not impaired by the filtering
system that has been installed, by
performing a temperature rise and
temperature drop test.
Keep the filter(s) clean at all times.
Vacuum dirt from filter, wash with
detergent and water, air dry thoroughly
and reinstall.
DO NOT DOUBLE FILTER THE
RETURN AIR DUCT SYSTEM. DO
NOT FILTER THE SUPPLY AIR DUCT
SYSTEM.
NOTE: Some filters must be resized to
fit certain units and applications. See
Table 16 and Figures 51 & 52.
1. 21” - 75,000(B), 90,000 & 105,000
BTUH units require removal of a
3.5-in. segment of filter and frame
to get the proper width for a side
filter.
2. 24.5” - 120,000 BTUH unit requires
removal of a 7" segment of filter
and frame to get the proper width
for a side filter.
CAUTION
!
DO NOT OPERATE THE SYSTEM
WITHOUT FILTERS. A PORTION OF
THE DUST ENTRAINED IN THE AIR
MAY TEMPORARILY LODGE IN THE
AIR DUCT RUNS AND AT THE
SUPPLY REGISTERS. ANY
RECIRCULATED DUST PARTICLES
WILL BE HEATED AND CHARRED BY
CONTACT WITH THE FURNACE
HEAT EXCHANGER. THIS RESIDUE
WILL SOIL CEILINGS, WALLS,
DRAPES, CARPETS AND OTHER
HOUSEHOLD ARTICLES AND MAY
RESULT IN UNPLEASANT ODORS.
LUBRICATION
IMPORTANT: DO NOT attempt to
lubricate the bearings on the blower
motor or the induced draft blower
otor. Addition of lubricants can reduce
m
the motor life and void the warranty.
The blower motor and induced draft
blower motor are permanently
lubricated by the manufacturer and do
not require further attention.
The blower motor and induced draft
blower motor must be cleaned
periodically by a qualified installer,
service agency, or the gas supplier to
prevent the possibility of overheating
due to an accumulation of dust and dirt
on the windings or on the motor
exterior. And, as suggested elsewhere
in these instructions, the air filters
should be kept clean. Dirty filters can
restrict airflow. The motor depends
upon sufficient air flowing across and
through it to keep from overheating.
SYSTEM OPERATION
INFORMATION
Advise The Customer
1. Keep the air filters clean. The
heating system will operate better,
more efficiently and more
economically.
2. Arrange the furniture and drapes
so that the supply air registers and
the return air grilles are
unobstructed.
3. Close doors and windows. This will
reduce the heating load on the
system.
4. Avoid excessive use of kitchen
exhaust fans.
5. Do not permit the heat generated
by television, lamps or radios to
influence the thermostat operation.
6. Except for the mounting platform,
keep all combustible articles 3 feet
from the furnace and vent system.
7. IMPORTANT: Replace all blower
doors and compartment covers
after servicing the furnace. Do not
operate the unit without all panels
and doors securely in place.
8. Explain proper operation of the
system.
ANNUAL INSPECTION
• The furnace should operate for many
years without excessive scale buildup in the flue passageways. However,
it is recommended that a qualified
installer, service agency, or the gas
supplier annually inspect the flue
passageways, the vent system and
the main burners for continued safe
operation. Pay particular attention to
deterioration from corrosion or other
sources.
• IMPORTANT: It is recommended
that at the beginning and at
approximately half way through the
heating season, a visual inspection
e made of the main burner flames
b
for the desired flame appearance by
a qualified installer, service agency
or the gas supplier. If the flames are
distorted and/or there is evidence of
back pressure, check the vent and
inlet air system for blockage. If there
is carbon and scale in the heat
exchanger tubes, the heat
exchanger assembly should be
replaced.
WARNING
!
HOLES IN THE VENT PIPE OR
HEAT EXCHANGER CAN CAUSE
TOXIC FUMES TO ENTER THE
HOME, RESULTING IN CARBON
MONOXIDE POISONING OR
DEATH. THE VENT PIPE OR HEAT
EXCHANGER MUST BE REPLACED
IF THEY LEAK.
• IMPORTANT: It is recommended
that at the beginning of the heating
season, the flame sensor be
cleaned with steel wool by a
qualified installer, service agency or
the gas supplier.
• IMPORTANT: It is recommended
that at the beginning of the heating
season, the condensate trap be
inspected for debris or blockage and
be filled with water. A blocked
condensate trap can cause water to
back up into the primary heat
exchanger and lead to nuisance
tripping of the overtemperature
switches.
• IMPORTANT: It is recommended
that at the beginning of the heating
season, the condensate neutralizer
if used be replaced by a qualified
installer, service agency or the gas
supplier.
• IMPORTANT: It is recommended
that an annual inspection and
cleaning of all furnace markings be
made to assure legibility. Attach a
replacement marking, which can be
obtained through the distributor, if
any are found to be illegible or
missing.
TROUBLESHOOTING
Refer to Figure 53.
WIRING DIAGRAM
Figure 54 is a complete wiring
diagram for the furnace.
59
Page 60
IGURE 53
o
r
I
F
C n
o
t
p
r
o
p
e
r
l
y
g
r
o
u
n
d
e
d
.
F
ROUBLESHOOTING CHART
T
Go To
Next Page
60
Page 61
IGURE 53
F
TROUBLESHOOTING CHART (CONTINUED)
61
Page 62
FIGURE 54
IRING DIAGRAM
W
62
Page 63
63
Page 64
64CM 0510
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.