Rheem RGRK SERIES, RGRL SERIES, RGTK SERIES Installation Instructions Manual

INSTALLATION INSTRUCTIONS
FOR UPFLOW AND DOWNFLOW/HORIZONTAL HIGH EFFICIENCY CONDENSING TWO-STAGE GAS FURNACES
RGRK, RGRL, AND RGTK SERIES
U.L. recognized fuel gas and CO (carbon monoxide) detectors are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
92-24161-36-22
SUPERSEDES 92-24161-36-21
INSTALLATION CHECK LIST
REFER TO INSTALLATION INSTRUCTIONS
TERMINATIONS – DIRECT VENT
AS SUPPLY
G
______ Adequate pipe size
_____ Correct supply pressure (during furnace operation)
_
______ Manifold pressure
______ No gas leaks
_____ L.P. Kit Number (if applicable)
_
ELECTRICAL
______ 115 V.A.C. supply (Single Circuit)
______ Polarity observed
______ Furnace properly grounded
______ Adequate wire size
FURNACE INSTALLATION
______ Adequate clearance to combustibles
______ Adequate clearance for service (at front)
VERTICAL
______ Intake – 12" min. above roof/snow level
______ Correct relationship – exhaust to intake
HORIZONTAL/VERTICAL – CONCENTRIC ((-)XGY-E03A)
______ Intake – 12" min. above roof/snow level
______ Intake “Y” rotated above center
______ Exhaust sloped toward furnace
HORIZONTAL – STANDARD ((-)XGY-D02, -D03) – US
((-)XGY-D02A, (-)XGY-D03A) – CANADA
______ Correct relationship – exhaust to intake
______ 12" min. above grade/snow level
HORIZONTAL – ALTERNATE
((-)XGY-D02, -D03 OR -D04) – US ((-)XGY-D02A, -D03A, -D04A) – CANADA
DUCT STATIC PRESSURE
______ in. w.c. on heating speed
______ in. w.c. on cooling speed
______ Air temperature rise
CONDENSATE LINE
______ Trap filled with water
______ Vented
______ Sloped toward drain
______ Condensate drain line hoses connected
and clamped
______ Freeze protection (if necessary)
VENTING – DIRECT VENT
______ in. diameter – intake pipe
______ in. diameter – exhaust pipe
______ ft. of pipe – intake air
______ Correct relationship – exhaust to intake
______ Above anticipated snow level
VENTING – NON-DIRECT VENT
______ in. diameter – exhaust pipe
______ ft. of pipe – exhaust
______ no. of elbows
TERMINATION – NON-DIRECT VENT
VERTICAL
______ 12" min. above roof/snow level
HORIZONTAL – STANDARD
______ 12" min. above grade/snow level
HORIZONTAL – ALTERNATE
______ Above anticipated snow level
______ no. of elbows – intake air
______ ft. of pipe – exhaust pipe
______ no. of elbows – exhaust pipe
______ Exhaust Vent Temperature
2
_____________________________ Model Number
_____________________________ Serial Number
_____________________________ Date of Installation
IMPORTANT: All manufacturer products meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California's Proposition 65 requires
arnings for products sold in California
w that contain, or produce, any of over 600 listed chemicals known to the State
f California to cause cancer or birth
o defects such as fiberglass insulation, lead in brass, and combustion products
rom natural gas.
f
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the Websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov California's OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and maintained.
and the State of
CONTENTS
afety Precautions ...................................................................................................1
S
nstallation Check List ..............................................................................................2
I
eneral Information..................................................................................................4
G
afety Information ....................................................................................................6
S
ocation Requirements and Considerations ............................................................8
L
ucting ...................................................................................................................13
D
enting and Combustion Air Piping .......................................................................15
V
ombustion and Ventilation Air ..............................................................................17
C
ent Pipe Installation..............................................................................................20
V
Condensate Drain/Neutralizer................................................................................33
Gas Supply and Piping...........................................................................................37
Electrical Wiring......................................................................................................42
Accessories............................................................................................................43
Furnace Twinning...................................................................................................44
High Altitude Installations.......................................................................................48
Start-Up Procedures...............................................................................................51
Air Flow...................................................................................................................54
Maintenance...........................................................................................................57
Troubleshooting......................................................................................................59
Wiring Diagram.......................................................................................................62
3
GENERAL INFORMATION
NOTE: A load calculation must be performed to properly determine the required furnace BTU size for the structure. Also, the duct must be properly designed and installed for proper airflow. Existing ductwork must be inspected for proper size and sealed system. Proper airflow is necessary for both user comfort and equipment performance.
Before opening the furnace carton and installation of the furnace, verify the data tags on the carton and inside the furnace, match and is what was ordered from the local distributor. Also, check for any damage to the furnace before installation.
IMPORTANT: Proper application, installation and maintenance of this furnace and system is a must if consumers are to receive the full benefits for which they have paid.
The (-)GRK-, (-)GRL-, (-)GTK- series furnaces are design-certified by CSA for use with natural and propane gases as
FIGURE 1
UPFLOW FURNACE COMPONENTS
follows:
1. As non-direct vent central forced air furnaces taking combustion air from the installation area or using air ducted from the outside.
2. As direct vent central forced air furnaces with all combustion air supplied directly to the furnace burners through a special air intake system outlined in these instructions.Install this furnace in accordance with the American National Standard Z223.1 – latest edition entitled “National Fuel Gas Code” (NFPA54) and requirements or codes of the local utilities or other authorities having jurisdiction. This is available from the following:
National Fire Protection
Association, Inc. Batterymarch Park Quincy, MA 02269
OWNFLOW/HORIZONTAL FURNACE COMPONENTS
D
AIRFLOW
3
2
CSA-INTERNATIONAL 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
Install units in Canada in accordance with CSA-B149, local installation codes and authorities having jurisdiction. CSA-B149 is available from:
CSA-INTERNATIONAL 178 Rexdale Blvd. Toronto, Ontario Canada M9W, 1R3
NOTE: It is our recommendation that any HVAC equipment which were subject to flooding be replaced to avoid any risk of property damage, personal injury or death. Also, our position that the immersion by flood waters compromises any HVAC products thus voiding this warranty.
15
12
23
22
9
8
ITEM NO. PART NAME 1 CONDENSATE TRAP 2 DOOR SWITCH 3 JUNCTION BOX 4 TRANSFORMER 5 PRESSURE SWITCHES 6 EXHAUST TRANSITION 7 CONNECTOR 8 OUTLET AIR PIPE
NOTE: A PARTS BAG IS INCLUDED WITH THE FURNACE. IF A NEW PARTS BAG NEEDS TO BE ORDERED, USE THE FOLLOWING PART NUMBERS: AS-100717-01 FOR (-)GRL-45, (-)GRL-60, (-)GRK-75, (-)GRL­90 AND (-)GRK-105 AS-100717-02 FOR (-)GRK-120
9 SHIPPING PLUG (TO BE REMOVED) 10 FLAME SENSOR 11 OVERTEMPERATURE SWITCH 12 TOP PLATE 13 BURNER 14 IGNITER 15 COMBUSTION AIR INLET 16 OPTIONAL AIR INLET (UPFLOW UNITS ONLY) 17 OPTIONAL GAS INLET 18 GAS VALVE
21
20
19
5
18
10
11
25
19 INDUCED DRAFT BLOWER 20 CAPACITORS 21 BLOWER 22 LOW VOLTAGE TERMINAL 23 CONTROL MOUNTING PLATE 24 FILTER / SOLID METAL BASEPLATE (UPFLOW UNITS ONLY) 25 BURNER COVER PLATE
NOTE: A PARTS BAG IS INCLUDED WITH THE FURNACE. IF A NEW PARTS BAG NEEDS TO BE ORDERED, USE THE FOLLOWING PART NUMBERS: AS-100717-03 FOR (-)GTK-60, (-)GTK-75, (-)GTK-90, (-)GTK­105 AND (-)GTK-120
7
(DOWNFLOW/HORIZONTAL UNITS ONLY)
6
13
4
AIRFLOW
17
1
14
4
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have
he proper balance between the air
t being supplied to each room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING. SEE ACCESSORIES SECTION OF THESE INSTRUCTIONS FOR AUXILIARY HORIZONTAL OVERFLOW PAN INFORMATION (MODEL (-)XBM).
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment
matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is required to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in a level position to ensure proper condensate drainage. Make sure unit is level in both directions within 1/8”.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
5
SAFETY INFORMATION
WARNING
!
USE ONLY WITH TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS FURNACE TO AN APPROVED VENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
WARNING
!
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY CIRCULATED DUST PARTICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAMAGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE
OAP SOLUTION MADE
S SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
WARNING
!
ALWAYS INSTALL FURNACE TO OPERATE WITHIN THE FURNACE'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO AREAS OUTSIDE THE SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE FURNACE.
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
HEN THIS FURNACE IS
W INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR. THIS IS TO REDUCE THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY
E PRESENT IN A GARAGE.
B ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
THE FURNACE MAY BE USED FOR HEATING OF BUILDINGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKING;
• MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND 80°F (27°C); AND
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERATURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS AND CODES.
6
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING. SEE ACCESSORIES SECTION OF THESE INSTRUCTIONS FOR AUXILIARY HORIZONTAL OVERFLOW PAN INFORMATION (MODEL (-)XBM).
IMPORTANT!
THE COMMONWEALTH OF MASSACHUSETTS REQUIRES COMPLIANCE WITH REGULATION 248 CMR 4.00 AND 5.00 FOR INSTALLATION OF THROUGH-THE­WALL VENTED GAS APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time
of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide
detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local
gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
7
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
. install a parallel duct system
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! This furnace is
not approved for installation in a mobile home. Doing so could cause
IRE, PROPERTY DAMAGE,
F PERSONAL INJURY OR DEATH.
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR. THIS IS TO PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. IMPORTANT: If installing the unit
over a finished ceiling or living area, be certain to install an auxiliary condensate drain pan under the entire unit. This auxiliary drain pan should extend under any evaporator coil installed with the furnace and the open portion of the condensate drain assembly. See “Condensate Drain/Neutralizer” section for more details.
2. IMPORTANT: If using a cooling
evaporator coil with this furnace:
a. be sure the air passes over
the heat exchanger before passing over the cooling coil. The cooled air passing over the warm ambient air inside the heat exchanger tubes can cause condensation inside the tubes resulting in corrosion and eventual failure.
b
to divert all the air from the furnace allowing it to pass over the cooling coil only. Use dampers or other means to prevent chilled air from passing over the heat exchanger.
If these are manual dampers, they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position.
3. IMPORTANT: Install the furnace
level. If it is not level, condensate cannot drain properly, possibly causing furnace shut down.
NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces. Provisions must be made to prevent freezing of condensate.
4. IMPORTANT: If this furnace is
installed in a garage, attic and/or any unconditioned space, install a self-regulating heat tape around the condensate trap and along the entire length of the condensate drain in the unconditioned space. When the condensing horizontal gas furnace is installed in an unconditioned space where the temperature would be capable of reaching close to or below 32°F
FIGURE 3
HORIZONTAL FURNACE W/HEAT TAPE ON CONDENSATE TRAP
DRAIN PIPE
5. IMPORTANT: If installing in a
0°C), a self-regulating heat tape
( is required on the condensate drain, along with an insulation wrap. The heat tape should meet the following requirements:
a. The heat tape must be UL
listed.
b. The heat tape must be
installed per the manufacturer’s instructions for the entire length of drain pipe in the unconditioned space.
c. The heat tape should be rated
at 5 or 6 watts per foot at 120V
IMPORTANT: Support this unit when installed. Since this furnace is suitable for attic or crawl space installation, it may be installed on combustible wood flooring or by using support brackets.
utility room, be sure the door is wide enough to:
a. allow the largest part of the
furnace to pass; or
b. allow any other appliance
(such as a water heater) to pass.
c. allow service clearance
AIRF
LOW
HEAT TAPE
TRAP
8
I526
CAUTION
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS FACING UPWARDS OR IN ANY
ORIZONTAL CONFIGURATION.
H
SITE SELECTION
1. Select a site in the building near he center of the proposed, or
t existing, duct system.
2. Give consideration to the vent
system piping when selecting the furnace location. Be sure the venting system can get from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the
existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas piping.
4. Locate the furnace to maintain
proper clearance to combustibles as shown in the following tables.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES. DOING SO CAN DAMAGE THE HEAT EXCHANGER ASSEMBLY.
CLEARANCE ­ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the table under Figure 5 are certified by CSA­International for the clearances to combustible materials shown in inches.
See name/rating plate and clearance label for specific model number and
learance information.
c
Service clearance of at least 24 inches is recommended in front of all furnaces.
NOTE: Use recommended 24” clearance if accessibility clearances are greater than fire protection clearances.
WARNING
!
UPFLOW FURNACES ARE DESIGN­CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. NOTE, HOWEVER, THAT FURNACES MUST NOT BE INSTALLED DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Upflow furnaces are shipped with a bottom closure panel installed. When bottom return air is used, remove the panel by removing the two screws attaching the panel to the front base angle. See filter section for details.
WARNING
!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES.
FIGURE 4
HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS
GAS PIPE
INTAKE VENT
ELECTRICAL CONDUIT
AIRF
LOW
TRAP
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure
7. Allow enough space for proper service maintenance or replacement of the heat exchanger and blower assembly.
EXHAUST FAN
I522
9
IGURE 5
F
CLEARANCE TO COMBUSTIBLES, UPFLOW UNITS
WGTS
OPTIONAL
RETURN
AIR CUTOUT
(EITHER SIDE)*
I392.DGN
BACK TOP FRONT VENT
2 DIA. KNOCKOUT
ALT. GAS CONNECTION
SIDE SIDE
LEFT RIGHT SHIP
/32 0 0 0 1 2* 0 111
/32 0 0 0 1 2* 0 117
/32 0 0 0 1 2* 0 123
/32 0 0 0 1 2* 0 145
25
/8 2 15 13
5
UPFLOW MODELS MINIMUM CLEARANCE (IN.)
/32 15
11
/2 16
1
9
25
25
/2 17
1
/8 2 15 13
/8 2 15 13
/8 2 18
5
5
1
/32 15
/32 15
/32 19
11
11
27
/2 16
/2 16
1
1
/32 0 0 0 1 2* 0 160
/32 0 0 0 1 2* 0 148
/32 0 0 0 1 2* 0 152
9
9
25
/2 17
/2 17
1
1
/8 2 18
/8 2 18
/8 2 22 20
1
1
5
/32 19
/32 19
/32 22
27
27
11
/2 23
1
04 17
06 17
MODEL A B C D E F
09 21 19
10 21 19
07A 17
07B 21 19
RETURN
12 24
*A service clearance of at least 24 inches is recommended in front of all furnaces.
8
5
AIR
27
AIRFLOW
*BOTH SIDES FOR 1800 CFM
GAS CONNECTION
AIR
SUPPLY
2 DIA.
16
7
26
10
I392
CUTOUT (EITHER SIDE)*
OPTIONAL RETURN AIR
IGURE 6
F
CLEARANCE TO COMBUSTIBLES, DOWNFLOW UNITS
WGTS
BACK TOP FRONT VENT
SIDE SIDE
LEFT RIGHT SHIP
8 0 0 0 1 2* 0 117
8 0 0 0 1 2* 0 123
8 0 0 0 1 2* 0 148
8 0 0 0 1 2* 0 152
/32 0 0 0 1 2* 0 123
7
7
9
8 13
8 13
/2 17
5
5
1
8 2 16
8 2 16
/16 2 18
5
5
3
8 0 0 0 1 2* 0 160
3
3
7
8 17
8 17
8 20
1
1
5
8 2 23
16 2 20
16 2 20
5
3
3
A103501.DGN
16
13
25
2 DIA.
ALT. GAS CONNECTION
8
3
4
32 15
32 15
32 19
32 19
/32 19
11
11
DOWNFLOW MODELS MINIMUM CLEARANCE (IN.)
MODEL A B C D E F
27
2 16
2 16
1
1
06 17
07A 17
07B 21 19
32 22
27
27
11
2 23
1
09 21 19
10 21 19
12 24
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIR
SUPPLY
AIRFLOW
GAS
CONNECTION
2 DIA.
AIR
RETURN
I393
NOTE: IN DOWNFLOW CONFIGURATION, RETURN AIR CUTOUT IS NOT PERMITTED.
11
IGURE 7
F
CLEARANCE TO COMBUSTIBLES, HORIZONTAL UNITS
WGTS
A103601.DGN
BACK TOP FRONT VENT
SIDE SIDE
LEFT RIGHT SHIP
8 0 0 0 1 2* 0 117
8 0 0 0 1 2* 0 123
8 0 0 0 1 2* 0 123
8 0 0 0 1 2* 0 148
8 0 0 0 1 2* 0 152
7
7
3
8 0 0 0 1 2* 0 160
3
3
7
RETURN AIR
8 13
8 13
8 17
8 17
8 17
5
5
1
8 2 16
8 2 16
16 2 20
5
5
3
32 15
32 15
32 19
11
11
HORIZONTAL MODELS MINIMUM CLEARANCE (IN.)
27
2 16
2 16
1
1
8 20
1
1
5
NOTE: In horizontal configuration, return air cutout is not permitted.
Horizontal left-hand airflow only.
IMPORTANT: This furnace is not approved or recommended for
8 2 23
16 2 20
16 2 20
5
3
3
32 19
32 19
32 22
27
27
11
2 23
1
installation on its back, with access doors facing upwards.
06 17
MODEL A B C D E F
09 21 19
10 21 19
07A 17
07B 21 19
12 24
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIRFLOW
16
13
25
GAS
CONNECTION
2 DIA.
2 DIA.
ALT. GAS
DRAIN TRAP LOCATION
8
3
4
CONNECTION
12
AIR
SUPPLY
I520
JACKET
DRILL (2) 3/16" DIA. HOLES
8.000
4.875
1.531
DUCTING
Proper air flow is required for the correct operation of this furnace. Too little air flow can cause erratic operation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling if summer air conditioning is used.
Size the ducts according to acceptable industry standards and methods. The total static pressure drop of the air distribution system should not exceed 0.5" w.c.
WARNING
!
NEVER ALLOW THE PRODUCTS OF COMBUSTION FROM THE FLUE TO ENTER THE RETURN AIR DUCTWORK OR THE CIRCULATED AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS; AND JOINTS, TAPED. ALL OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS AND SEALED AIRTIGHT. WHEN AN UPFLOW FURNACE IS MOUNTED ON A PLATFORM WITH RETURN THROUGH THE BOTTOM, IT MUST BE SEALED AIRTIGHT BETWEEN THE FURNACE AND THE RETURN AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT OF THE FURNACE WITHOUT SAGGING, CRACKS, OR GAPS, AROUND THE BASE, PROVIDING A SEAL BETWEEN THE SUPPORT AND THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCULATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR SUPPLY DUCTWORK TO OR FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR PROPERTY DAMAGE.
IMPORTANT: Some high efficiency
filters have a greater than normal resistance to air flow. This can adversely affect furnace operation. BE SURE TO CHECK AIR FLOW.
IMPORTANT: When using outside air, design and adjust the system to maintain a return air temperature ABOVE 55° F during the heating season.
NOTE: Return air grilles and warm air registers must not be obstructed or closed.
UPFLOW UNITS
. Position the unit to minimize long
1
runs of duct or runs of duct with many turns and elbows.
2. Open the return air compartment.
WARNING
!
UPFLOW FURNACE: A SOLID METAL BASE PLATE MUST REMAIN IN THE FURNACE BOTTOM WHEN USING SIDE AIR RETURN. FAILURE TO INSTALL A BASE PLATE COULD CAUSE THE PRODUCTS OF COMBUSTION TO CIRCULATE INTO THE LIVING SPACE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH. FOR BOTTOM RETURN, REMOVE SOLID METAL BASE PLATE.
a. Cut an opening in the side. The
opening should be cut the full width and height of the knockouts on the unit. See Figure 8.
FIGURE 8
UPFLOW CUTOUT AND DRILL INFORMATION
NOTE: Where the maximum air flow
is 1800 CFM or more, both sides or 1 side and the bottom must be used for return air.
3. Connect the return duct or return air cabinet to the unit. Make the
onnection air tight to prevent
c entraining combustion gases from an adjacent fuel-burning appliance.
4. Be sure to have adequate space
or the unit filter.
f
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
NOTE: DO NOT use a rear air return.
5. If summer air conditioning is desired, position the indoor coil on the supply-air side of the unit. Insure that no air can bypass this coil.
6. Connect the supply air plenum to the furnace plenum opening.
IMPORTANT: If a flexible duct connector must be used, it MUST
be rated for a minimum temperature of 250°F continuous.
.
1313
OWNFLOW UNITS
D
1. Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2. If summer air conditioning is desired, position the indoor coil on the supply-air side of the unit. Insure that no air can bypass this coil.
3. If installing on a combustible floor
and not using an air conditioning plenum, install the special non-
combustible floor base. See Table 1 and Figure 9.
WARNING
!
THE DOWNFLOW FURNACE DESIGN IS CERTIFIED FOR INSTALLATION ON A NON­COMBUSTIBLE FLOOR. USE THE SPECIAL BASE SPECIFIED ON THE FURNACE CLEARANCE LABEL. FAILURE TO INSTALL THE SPECIAL BASE MAY RESULT IN FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THIS SPECIAL BASE IS SHIPPED FROM THE FACTORY AS AN ACCESSORY.
4. Connect the furnace to the supply air plenum.
5. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining combustion gases from an adjacent fuel-burning appliance.
NOTE: In downflow configuration, return air cut out is not permitted.
6. Be sure to have adequate space
for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
HORIZONTAL UNIT
IMPORTANT: THIS FURNACE MAY ONLY BE INSTALLED SO AS WHEN
ACING THE FRONT OF THE
F FURNACE, SUPPLY AIR IS DISCHARGED ON THE LEFT HAND SIDE.
1. Position the unit to minimize long uns of duct or runs of duct with
r many turns and elbows.
2. If summer air conditioning is
desired, position the indoor coil on the supply air side of the unit. Insure that no air can bypass this coil.
3. Connect the furnace to the supply
air plenum.
4. Connect the return air ducting to
the return air opening at the right end of the unit. Make the connection air tight to prevent pulling combustion gases from an adjacent fuel-burning appliance.
NOTE: In horizontal configuration, return air cut out is not permitted.
5. Be sure to have adequate space
for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
TABLE 1
NON-COMBUSTIBLE FLOOR BASES
Floor Base Size
No. Cabinet
(-)XGC-B17 17
(-)XGC-B21 21
(-)XGC-B24 24
14
FIGURE 9
NON-COMBUSTIBLE FLOOR BASE
VENTING AND COMBUSTION AIR PIPING
EQUIREMENT THAT VENT
GENERAL INFORMATION
WARNING
!
READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING
R AN EXPLOSION OR FIRE,
O RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
This furnace removes both sensible and latent heat from the combustion flue gases. Removal of latent heat results in condensation of flue gas water vapor. This condensed water vapor drains from the secondary heat exchanger and out of the unit into a drain trap.
When installed as a non-direct vent furnace, only exhaust piping is required and inside combustion air may be used. Refer to section on
COMBUSTION & VENTILATION AIR
“ FOR FURNACE INSTALLATIONS.”
Direct vent installations require a dedicated combustion air and venting system. All air for combustion is taken from the outside atmosphere and all combustion products are discharged to the outdoors.
The combustion air and vent pipe fittings must conform to American National Standards Institute (ANSI) and American Society for Testing Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), D2241 (SDR-21 and SDR26-26 PVC), D2661 (ABS-DWV) or F628 (Schedule 40 ABS-DWV).
WARNING
!
IN CANADA, PRODUCTS CERTIFIED FOR INSTALLATION AND INTENDED TO BE VENTED WITH PLASTIC VENT SYSTEMS (PVC, CPVC) MUST USE VENT SYSTEMS THAT ARE CERTIFIED TO THE STANDARD FOR TYPE BH GAS VENTING SYSTEMS, ULC S636.
THE COMPONENTS OF THE CERTIFIED MATERIAL MUST NOT BE INTERCHANGED WITH OTHER VENT SYSTEMS OR UNLISTED PIPE/FITTINGS.
PLASTIC COMPONENTS AND SPECIFIED PRIMERS AND GLUES OF THE CERTIFIED SYSTEM MUST BE FROM A SINGLE SYSTEM MANUFACTURER AND NOT INTERMIXED WITH OTHER SYSTEM MANUFACTURER’S PARTS.
NOTE: INLET AIR PIPING IS NOT CONSIDERED TO BE A PART OF THE “VENTING SYSTEM”. THE
R
ATERIAL BE CERTIFIED TO ULC
M
636 DOES NOT APPLY TO INLET
S
IR PIPING. VENT TERMINATIONS
A
ND CONCENTRIC TERMINATIONS
A
UST BE APPROVED BY THE
M
ANUFACTURER AND CERTIFIED
M
LC-636.
U
MPORTANT: The plastic combustion
I
air and venting components are of Schedule 40 PVC. If using ABS piping, ensure that the solvent cement is compatible for joining PVC to ABS components or use a mechanical connection that can withstand the vent temperatures and are corrosion resistant.
NOTE: Schedule 40 ABS-DWV pipe and fittings may be used as an alternate to PVC pipe for the combustion air inlet and vent pipes.
NOTE: Cellular core PVC is also approved for use. It must be schedule 40PVC-DWV cellular pipe for non­pressure applications and manufactured under ASTM F-891.
NOTE: With the furnace correctly vented, the inducer will move approximately 25 cfm per 100,000 Btu’s.
IMPORTANT: No part of the combustion air and vent pipes may run under ground.
OVERTEMPERATURE SAFETY SWITCHES
Furnaces are equipped with safety switches in the control compartment to protect against overtemperature conditions caused by inadequate combustion air supply. The switches are located in the burner compartment. If a switch is tripped it must be manually reset.
WARNING
!
DO NOT JUMPER THESE DEVICES! IF ONE OF THESE SWITCHES SHOULD TRIP, A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER MUST BE CALLED TO CHECK AND/OR CORRECT FOR ADEQUATE COMBUSTION AIR SUPPLY. DO NOT RESET THE SWITCHES WITHOUT TAKING CORRECTIVE ACTION TO ASSURE THAT AN ADEQUATE SUPPLY OF COMBUSTION AIR IS MAINTAINED UNDER ALL CONDITIONS OF OPERATION. FAILURE TO DO SO CAN RESULT IN CARBON MONOXIDE POISONING OR DEATH. IF THIS UNIT IS MOUNTED IN A CLOSET, THE DOOR MUST BE CLOSED WHEN MAKING THIS CHECK.
REPLACE THESE SWITCHES ONLY WITH THE IDENTICAL REPLACEMENT PART.
EXISTING VENT SYSTEMS
When the installation of this furnace replaces an existing furnace that is removed from a vent system serving
ther appliances, the vent system is
o likely to be too large to properly vent the remaining attached appliances.
he following steps should be
T followed with each appliance remaining connected to the original common vent system. Place the appliance to be tested in operation, while the other appliances remaining connected to the common vent system are not in operation. Test the operation of each appliance individually by the following method.
1. Permanently seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage, restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. If practical, close all building doors, windows and all doors between the space where the appliances remaining connected to the common venting system are located. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
15
6. After it has been determined that each appliance that remains connected to the common venting system properly vents (when tested as outlined above), return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the common venting system must be resized.
When the furnace is installed in the same space with other gas appliances such as a water heater, be sure there is an adequate supply of
ombustion and ventilation air for the
c other appliances. Do not delete or reduce the combustion air supply required by the other gas appliances in this space. See Z223.1, National Fuel Gas Code (NFPA54) for determining the combustion air requirements for gas appliances. An unconfined space must have at least 50 cubic feet (volume) for each 1,000 BTUH of the total input of all appliances in the space. If the open space containing the appliances is in a building with tight construction (contemporary construction), outside air may still be required for the appliances to burn and vent properly. Outside air openings should be sized the same as for a confined space.
IMPORTANT: Only the current vent instructions apply. All 90 Plus Gas Furnaces cannot be common vented.
JOINING PIPE AND FITTINGS
WARNING
!
PVC SOLVENT CEMENTS AND PRIMERS ARE HIGHLY FLAMMABLE. PROVIDE ADEQUATE VENTILATION AND DO NOT ASSEMBLE NEAR HEAT
OURCE OR AN OPEN FLAME. DO
S NOT SMOKE. AVOID SKIN OR EYE CONTACT. OBSERVE ALL CAUTIONS AND WARNINGS PRINTED ON MATERIAL CONTAINERS. FAILURE TO FOLLOW THESE GUIDELINES MAY RESULT IN FIRE, EXPLOSION OR ASPHYXIATION CAUSING PERSONAL INJURY OR DEATH.
All pipe, fittings, solvent cement, primers and procedures must conform to American National Standard Institute and American Society for Testing and Materials (ANSI/ASTM) standards as shown below:
CEMENTING JOINTS
Properly seal all joints in the PVC vent using the following materials and procedures.
PVC CLEANER-PRIMER AND PVC MEDIUM-BODY SOLVENT CEMENT
IMPORTANT: After cutting pipe,
remove all ragged edges and burrs. This is important to prevent reduction in pressure drop throughout the system.
1. Cut pipe end square. Chamfer edge of pipe. Clean fitting socket and pipe joint area of all dirt, grease and moisture.
2. After checking pipe and socket
or proper fit, wipe socket and
f pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe. Read instructions included with the primer for proper application.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting
ovement until it bottoms out.
m NOTE: Cement must be fluid; if
not, recoat.
4. Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity.
NOTE: Stir the solvent cement frequently while using. Use a natural bristle brush or the dauber supplied with the can. The proper brush size is one inch.
IMPORTANT: For Proper Installation
DO NOT use solvent cement that has become curdled, lumpy or thickened.
DO NOT thin. Observe shelf precautions printed on containers.
For application below 32°F, use only low-temperature-type solvent cement.
16
PIPE & FITTING MATERIAL
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
SDR-21PVC (Pipe) D2241
SDR-26 PVC (Pipe) D2241
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent) (Pipe & Fittings)
ASTM
SPECIFICATION
D2661
D2665
COMBUSTION AND VENTILATION AIR
NON-DIRECT
erchloroethylene)
FURNACE INSTALLATIONS
WARNING
!
THE FURNACE AND ANY OTHER
UEL-BURNING APPLIANCE MUST
F BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE PERSONAL INJURY OR DEATH FROM CARBON MONOXIDE POISONING.
Adequate facilities for providing air for combustion and ventilation must be provided in accordance with section
5.3, “Air for Combustion and Ventilation” of the National Fuel Gas Code, ANSI Z223.1 (latest edition) or applicable provisions for the local building codes, and not obstructed so as to prevent the flow of air to the furnace.
IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation (but not limited to the following) will require OUTDOOR AIR for combustion, due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air supply (but not limited to the following) will also require OUTDOOR AIR for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
p
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for
lothes dryers
c
• Masonry curing and acid washing materials
Combustion air must be free of acid­forming chemicals such as sulphur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrigerants and many other commercial and household products. When burned in a gas flame, vapors from these products form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they condense.
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY DAMAGE, CARBON MONOXIDE POISONING, PERSONAL INJURY OR DEATH.
Combustion air requirements are determined by whether the furnace is in an open (unconfined) area or in a confined space such as a closet or small room.
EXAMPLE 1: FURNACE LOCATED IN AN UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of the total input for all appliances in the space. Here are a few examples of the room sizes required for different inputs. The sizes are based on 8-foot ceilings.
BTUH Minimum Sq. Feet Typical Room Size
Input With 8' Ceiling With 8' Ceiling
5,000 281 14' x 20' OR 16' x 18'
4
0,000 375 15' x 25' OR 19' x 20'
6
5,000 469 15' x 31' OR 20' x 24'
7
0,000 563 20’ x 28’ OR 24’ x 24’
9
105,000 657 20' x 33' OR 26' x 25'
120,000 750 25' x 30' OR 24' x 32'
If the open space containing the furnace is in a building with tight construction, outside air may still be required for the furnace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
EXAMPLE 2: FURNACE LOCATED IN A CONFINED SPACE
A confined space (any space smaller than shown above as “unconfined”) must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and B. Size the openings by how they are connected to the heated area or to the outside, and by the input of all appliances in the space.
If confined space is within a building with tight construction, combustion air must be taken from outdoors or area freely communicating with the outdoors.
A. USING INDOOR AIR FOR
COMBUSTION
IMPORTANT: Air should not be taken from a heated space with a fireplace, exhaust fan or other device that may produce a negative pressure.
If combustion air is taken from the heated area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 BTUH of total input in the space. Here are some examples of typical openings required.
BTUH Free Area
17
nput Each Opening
I
5,000 100 square inches
4
0,000 100 square inches
6
5,000 100 square inches
7
90,000 100 square inches
105,000 105 square inches
120,000 120 square inches
IGURE 10
F
AIR FROM HEATED SPACE
B. USING OUTDOOR AIR FOR
COMBUSTION
MPORTANT: Do not take air from
I
an attic space that is equipped with power ventilation.
The confined space must communicate with the outdoors in accordance with Methods 1 or 2. The minimum dimension of air openings shall not be less than 3 inches. Where ducts are used, they shall be of the same cross­sectional area as the free area of the openings to which they connect.
Method 1 Two permanent openings, one located within 12 inches of the top and one located within 12 inches of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating with the outdoors or where communicating to the outdoors
AS
G
WATER
HEATER
through vertical ducts as shown in Figure 11, each opening shall have a minimum free area of 1 square inch for each 4,000 BTUH of total appliance input rating in the enclosure.
BTUH Free Area Round Pipe
Input Each Opening Size
45,000 11.25 square inches 4"
60,000 15.00 square inches 5"
75,000 18.75 square inches 5"
90,000 22.50 square inches 6"
105,000 26.25 square inches 6"
120,000 30.00 square inches 6"
b. Where communicating with
URNACE
F
NOTE:
ACH OPENING SHALL
E HAVE A FREE AREA OF NOT LESS THAN ONE
QUARE INCH PER 1,000
S BTU PER H0UR OF THE TOTAL INPUT RATING OF
LL EQUIPMENT IN THE
A ENCLOSURE, BUT NOT LESS THAN 100 SQUARE
NCHES.
I
outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch for each 2,000 BTUH of total input rating of all equipment in the enclosure (see Figure 12).
Here are some typical sizes:
BTUH Free Area Round Pipe
Input Each Opening Size
45,000 22.50 square inches 6"
60,000 30.00 square inches 6"
75,000 37.50 square inches 7"
90,000 45.00 square inches 8"
105,000 52.50 square inches 8"
120,000 60.00 square inches 9"
Method 2 (not shown)
FIGURE 11
AIR FROM ATTIC/CRAWL SPACE
OUTLET AIR IN ATTIC MUST BE ABOVE INSULATION
1 SQ. INCH PER
4000 BTUH
OUTLET AIR
GAS
WATER
HEATER
18
GABLE
VENT
FURNACE
OPTIONAL1 SQ. INCH PER 4000 BTUH INLET AIR
1 SQ. INCH PER 4000 BTUH INLET AIR
VENTILATED ATTIC GABLE OR SOFFIT VENTS
12" MAX.
FIGURE 12
OUTSIDE AIR USING A HORIZONTAL DUCT
OUTLET AIR 1 SQ. INCH
FURNACE
GAS
WATER
HEATER
INLET AIR 1 SQ. INCH
12"
MAX.
PER 2000 BTUH
PER 2000 BTUH
One permanent opening, located within 12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall directly communicate with the outdoors or communicate through a vertical or
orizontal duct to the outdoors or
h spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:
. 1 square inch for each 3,000
a BTUH of the total input rating of all equipment located in the enclosure and
FIGURE 13
COMBUSTION AIR FITTING
TUH Free Area Round Pipe
B
nput Each Opening Size
I
5,000 15.00 square inches 4"
4
0,000 16.67 square inches 5"
6
5,000 25.00 square inches 6"
7
90,000 30.00 square inches 6"
105,000 35.00 square inches 7"
120,000 40.00 square inches 7"
b. Not less than the sum of the areas of all vent connectors in the confined space.
If unit is installed where there is an exhaust fan, sufficient ventilation must be provided to prevent the exhaust fan from creating a negative pressure.
Combustion air openings must not be restricted in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
CONNECTION TO FURNACE
IMPORTANT: When indoor combustion air is used, the inlet air
pening at the furnace must be
o protected from accidental blockage. (See Figure 13).
UPFLOW
TTACH DOUBLE ELBOW TO TOP INLET
A
IR OPENING OR 90° ELBOW TO SIDE
A
NLET AIR OPENING TO PREVENT
I
CCIDENTALBLOCKAGE OF INTAKE
A
PENING. PLUG OPENING NOT USED.
O
XHAUST
E
OP
T OPTION
I337
SIDE OPTION
2" PVC
OUBLE
D ELBOW
2" PVC ELBOW
" PVC
DOWNFLOW/HORIZONTAL
2 DOUBLE ELBOW*
COMBUSTION AIR
*NOTE: WHEN FURNACE IS INSTALLED IN A HORIZONTAL POSITION ONLY ONE 90° ELBOW IS REQUIRED. INSTALLTHE ELBOW SO THE OPEN END IS POINTED DOWNWARD.
TTACH DOUBLE ELBOW TO INTAKE AIR
A
OLLAR AND SECURE WITH TWO SHEET
C
ETAL SCREWS TO PREVENT ACCIDENTAL
M
LOCKAGE OF INTAKE AIR OPENING.
B
REDRILL FOR SCREWS.
P
EXHAUST
I336
19
VENT PIPE INSTALLATION
NON-DIRECT VENT INSTALLATION
GUIDELINES
IMPORTANT: Failure to correctly follow all venting guidelines may result in
rratic furnace operation, freeze-up of
e combustion air or exhaust air piping or sooting of the furnace.
ll exhaust piping must be installed in
A compliance with Part 7, “Venting of Equipment,” of the latest edition of the National Fuel Gas Code NPFA54/ ANSI Z223.1-, local codes or ordinances and these instructions.
1. Vertical piping is preferred.
2. All horizontal piping must slope upward a minimum of foot of run so that condensate drains toward the furnace.
3. All horizontal runs must be supported at least every 4 feet. No sags or dips are permitted.
4. IMPORTANT: Do not common vent with any other appliance. Do not install in the same chase or chimney with a metal or high temperature plastic pipe from another gas or fuel­burning appliance unless the required minimum clearances to combustibles are maintained between the pvc pipe and other pipes.
5. All vent runs through unconditioned spaces where below-freezing temperatures are expected should be insulated with 1-in. thick, medium-density, foil-faced fiberglass. An equivalent “arm-a­flex” or “rub-a-tex” insulation may also be used as long as there is no heat tape applied to the vent pipe. For horizontal runs where water may collect, wrap the vent pipe with self­regulating 3 or 5 watt heat tape. The heat tape must be U.L. listed and installed per the manufacturer’s instructions.
6. The minimum vent pipe length is 5 feet.
7. Extend the exhaust pipe a minimum of 18” from the cabinet before turning vent.
8. Vent cannot be ran underground.
FIGURE 14
TEE TERMINAL – FOR STANDARD HORIZONTAL NON-DIRECT INSTALLATION
VENT
1
/4 inch per
TABLE 2 UPFLOW UNITS
FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM INDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
NUMBERS OF ELBOWS
FURNACE
INPUT
45,000
0,000
6
75,000
90,000
05,000 3”
1
120,000 3”
NOTES:
1. *N.A. - NOT APPLICABLE.
2. MAXIMUM OF 6 ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS.
3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
4. NO SCREENS MAY BE USED TO COVER EXHAUST.
*A = 17-1/2” CABINET WIDTH B = 21) CABINET WIDTH
PIPE SIZE
2”
2
3
3
3”
ERMINATION
T
1-2 3-4 5-6
Standard 60 55 50
Alternate 55 50 45
Standard 30 25 20
Alternate 25 20 15
tandard 120 120 115
S
lternate 120 120 110
A
tandard 45 40 NA
S
Alternate 45 45 NA
Standard 90 85 75
Alternate 60 50 45
Standard 45 40 NA
lternate NA NA NA
A
tandard 70 65 55
S
lternate 40 30 25
A
45° OR 90°
edium / Long Radius ONLY
M
TABLE 3 DOWNFLOW/HORIZONTAL UNITS
FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM INDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
NUMBERS OF ELBOWS
FURNACE
INPUT
60,000
75,000
90,000 3”
105,000 3”
120,000 3”
NOTES:
1. *N.R. - NOT RECOMMENDED.
2. MAXIMUM OF 6 - 90 DEGREE ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS.
3. A 45 OR 22.5 DEGREE ELBOW IS CONSIDERED ONE ELBOW.
4. NO SCREENS MAY BE USED TO COVER EXHAUST.
*A = 17-1/2” CABINET WIDTH B = 21” CABINET WIDTH
PIPE SIZE
2”
3”
3”
TERMINATION
1-2 3-4 5-6
Standard 40 35 30
Alternate 30 25 20
Standard 120 120 120
Alternate 110 105 100
Standard 120 120 120
Alternate 100 95 85
Standard 110 105 95
Alternate 50 40 35
Standard 65 60 55
Alternate 50 40 35
Standard 40 35 30
Alternate 40 35 30
45° OR 90°
Medium / Long Radius ONLY
20
12"
12" MIN. ABOVE
GRADE OR
SNOW LEVEL
ELEVATED SINGLE PIPE ALTERNATE TEE TERMINATION
See Figure 15. The tee termination may be elevated up to 24 inches above the wall penetration if required for anticipated snow levels. Use 2 long-sweep, 2-in. PVC elbows and 2-in. PVC pipe, attaching the tee so it is 12 inches from the wall.
Loading...
+ 44 hidden pages