Rheem RGPE series, RGLE series Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISON­ING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PROPOSITION 65 WARNING: THIS PRODUCT CONTAINS CHEMICALS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
— Do not store or use gasoline or other flammable vapors and liquids, or other combustible materials
in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— DO NOT RELY ON SMELL ALONE TO DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT
BE ABLE TO SMELL FUEL GASES.
• U.L. recognized fuel gas and CO detectors are recommended in all applications, and their installa­tion should be in accordance with the manufacturer’s recommendations and/or local laws, rules regulations, or customs.
— Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
ISO 9001:2008
FOR RGPE UPFLOW, HORIZONTAL, RGLE DOWNFLOW 2 STAGE, 80+ GAS FURNACES
COMMUNICATING
THERMOSTATS
INSTALLATION
SEE PAGE 84
This Memory Card must be removed (broken away) from the furnace control when the control is replaced. The card must be inserted into the connector at J15 of the replacement con­trol. Failure to retain this memory card with the furnace when replacing the furnace control could result in no operation when the furnace control is replaced.
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN 2 OR MORE DIFFERENT FURNACES. DOING SO COULD RESULT IN UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DUR­ING HEATING (AND OTHER MODES) OR A LOSS OF HEAT.
SUPERSEDES 92-24161-77-01
92-24161-77-02
Page 2
IMPORTANT: All Manufacturer products
meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain prod­ucts, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facili­tates manufacturing and shipping. We cannot always know “when, or if” prod­ucts will be sold in the California market.
You may receive inquiries from cus­tomers about chemicals found in, or pro­duced by, some of our heating and air­conditioning equipment, or found in nat­ural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene More details are available at the
Websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov
and the State of California's OEHHA(Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most con­sumers are aware that products present safety and health risks, when improperly used, handled and maintained.
Installation Instructions are updated on a regular basis. This is done as product changes occur or if new information becomes available. In this publication, an arrow denotes changes from the previous edition or additional new mater­ial.
IMPORTANT: To insure proper installa­tion and operation of this product, com­pletely read all instructions prior to attempting to assemble, install, operate, maintain or repair this product. Upon unpacking of the furnace, inspect all parts for damage prior to installation and start-up.
TABLE OF CONTENTS
SAFETY INFORMATION..........................................................................................................................................3
INSTALLATION CHECK LIST...................................................................................................................................5
GENERAL INFORMATION.......................................................................................................................................6
IMPORTANTINFORMATION ABOUT EFFICIENCYANDINDOORAIR QUALITY...................................6
RECEIVING.....................................................................................................................................................7
LOCATION REQUIREMENTSANDCONSIDERATIONS.......................................................................................7
LOCATION.......................................................................................................................................................7
CLEARANCE-ACCESSIBILITY....................................................................................................................10
SITE SELECTION.........................................................................................................................................10
DUCTING......................................................................................................................................................10
COMBUSTIONAND VENTILATION AIR ...............................................................................................................12
COMBUSTIONAIR REQUIREMENTS........................................................................................................12
VENTING.................................................................................................................................................................16
GENERAL INFORMATION...........................................................................................................................16
DRAFTINDUCER.........................................................................................................................................16
FURNACE CATEGORY INFORMATION.....................................................................................................16
IMPORTANTAPPLICATIONNOTES...........................................................................................................16
B-1 VERTICALVENTING.............................................................................................................................17
SPECIAL VENT SYSTEMS..........................................................................................................................17
POWERVENT SYSTEMS...........................................................................................................................18
EXISTING VENT SYSTEMS........................................................................................................................18
GAS SUPPLYAND PIPING....................................................................................................................................19
GAS SUPPLY................................................................................................................................................19
GAS PIPING..................................................................................................................................................19
GAS PRESSURE..........................................................................................................................................20
LP CONVERSION.........................................................................................................................................20
SETTING GAS PRESSURE.........................................................................................................................21
ADJUSTING OR CHECKINGFURNACE INPUT.......................................................................................22
ELECTRICALWIRING............................................................................................................................................23
ELECTRICALCHECKS........................................................................................................................24
ACCESSORIES.......................................................................................................................................................25
FIELDINSTALLEDOPTIONACCESSORIES............................................................................................25
OTHERACCESSORIES AVAILABLE..........................................................................................................27
RXGW-B01 CHIMNEYADAPTER...............................................................................................................27
TYPICAL WIRING FOR SELECTACCESSORIESFOR COMMUNICATING RESIDENTIAL
SYSTEMS............................................................................................................................................27
80+ HIGH ALTITUDE INSTRUCTIONS.......................................................................................................29
LP GAS..........................................................................................................................................................29
ORIFICE ORDERING INFORMATION........................................................................................................29
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE......................................................29
AIRFLOW.................................................................................................................................................................31
INTEGRATED FURNACE CONTROL...................................................................................................................33
24 VAC THERMOSTAT INPUTS..................................................................................................................33
SPECIAL CONFIGURATION–COMMUNICATINGTHERMOSTATW/NON-COMM. CONDENSER......34
24 VAC FROM TRANSFORMERCONNECTIONS....................................................................................34
FUSE.............................................................................................................................................................34
115 VAC TERMINALS...................................................................................................................................34
INDUCED DRAFTMOTOROUTPUT.........................................................................................................34
NEUTRALTERMINALS................................................................................................................................35
ELECTRONICAIR CLEANER OUTPUT.....................................................................................................35
HUMIDIFIEROUTPUT.................................................................................................................................35
15-PIN MATE-N-LOK CONNECTOR...........................................................................................................35
COMMUNICATING ECM MOTOR COMMUNICATIONS CONNECTION.................................................36
SPARK IGNITIONTRANSFORMER...........................................................................................................37
R-J11 CONNECTOR.....................................................................................................................................37
COMMUNICATIONS NETWORK CONNECTION......................................................................................37
COMMUNICATIONS L.E.D.’S......................................................................................................................37
LEARNBUTTON...........................................................................................................................................38
MEMORY CARD CONNECTOR..................................................................................................................38
MEMORY CARD...........................................................................................................................................38
REPLACINGTHE FURNACE CONTROL...................................................................................................41
DIPSWITCHES.............................................................................................................................................44
SW1...............................................................................................................................................................44
SW2...............................................................................................................................................................46
FURNACE OPERATION USINGNON-COMMUNICATING SIINGLE-STAGE AND TWO-STAGE
THERMOSTATS......................................................................................................................................46
SW3-1AND SW3-2.......................................................................................................................................47
BIAS / TERMINATION ..................................................................................................................................48
DUALSEVEN-SEGMENT DIAGNOSTICDISPLAY ...................................................................................48
FAULT CODE BUFFER................................................................................................................................48
CLEARING DIAGNOSTICFAULT CODES FROM THE BUFFER.............................................................48
COMMUNICATING SYSTEMS....................................................................................................................49
START-UP PROCEDURES....................................................................................................................................57
IGNITOR PLACEMENT, ALIGNMENT& LOCATION.................................................................................57
TO START THE FURNACE..........................................................................................................................57
TO SHUT DOWN THE FURNACE..............................................................................................................57
SEQUENCE OF OPERATION.....................................................................................................................57
ADJUSTING OR CHECKINGFURNACE INPUT.......................................................................................59
MAINTENANCE.......................................................................................................................................................60
FILTERS ........................................................................................................................................................60
SYSTEM OPERATION INFORMATION......................................................................................................62
ANNUAL INSPECTION................................................................................................................................62
LUBRICATION...............................................................................................................................................62
REPLACEMENTPARTS..............................................................................................................................62
NOx MODELS...............................................................................................................................................62
TROUBLESHOOTING............................................................................................................................62-63
WIRING DIAGRAM.......................................................................................................................................79
THERMOSTATS......................................................................................................................................................80
NON-COMMUNICATINGTHERMOSTATS.................................................................................................80
SEQUENCE OF OPERATION.....................................................................................................................80
COMMUNICATING THERMOSTATS.....................................................................................................................84
2
Page 3
SAFETY INFORMATION
IMPORTANT!
THE COMMONWEALTH OF MASSA­CHUSETTS REQUIRES COMPLIANCE WITH REGULATION 248 CMR 4.00 AND 5.00 FOR INSTALLATION OF THROUGH-THE-WALL VENTED GAS APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the follow­ing requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.At the time of
installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the respon­sibility of the property owner to secure the services of qualified licensed profes­sionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizon­tally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above require­ments; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide
detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identifi­cation plate shall be permanently mount­ed to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equip­ment. The sign shall read, in print size no less than one-half (1/2) inch in size,
“GASVENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas
inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes car­bon monoxide detectors and signage installed in accordance with the provi­sions of 248 CMR 5.08(2)(a) 1 through
4. (b) EXEMPTIONS: The following equip-
ment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizon­tally vented gas fueled equipment installed in a room or structure sepa­rate from the dwelling, building or struc­ture used in whole or in part for resi­dential purposes.
(c) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installa­tion of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satis­fied by the manufacturer:
1. The referenced “special venting sys­tem” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installa­tion instructions.
(e) A copy of all installation instructions for all ProductApproved side wall hori­zontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the com­pletion of the installation.
WARNING
!
INSTALLTHIS FURNACE ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDER­ATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADE­QUATE COMBUSTION AND VENTI­LATION AIR TOTHE FURNACE SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUS­TION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECI­FIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS FURNACE TO AN APPROVEDVENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFI­CALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNEC­TIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE TION INSTRUCTIONS.
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS FACING UPWARDS, OR WITH SUPPLY AIR DISCHARGING TO THE RIGHT­HAND SIDE WHEN FACING THE FRONT OF THE FURNACE. SEE FIGURES 6 AND 7 FOR PROPER INSTALLATION OF HORIZONTAL MODELS.
WARNING
!
DO NOT INSTALLTHIS FURNACE IN A MOBILE HOME!! THIS FUR­NACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PER­SONAL INJURY OR DEATH.
WARNING
!
USE ONLYWITH TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
3
Page 4
WARNING
!
WHENTHIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE,IT MUST BE INSTALLED SO THE BURN­ERS AND IGNITION SOURCE ARE LOCATED NO LESSTHAN 18 INCH­ES ABOVETHE FLOOR.THIS ISTO REDUCETHE RISK OF IGNITING FLAMMABLEVAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO,THE FURNACE MUST BE LOCATED OR PROTECTEDTO AVOID PHYSICAL DAMAGE BY VEHI­CLES. FAILURETO FOLLOWTHESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
USE OF THIS FURNACE IS ALLOWED DURING CONSTRUCTION IF THE FOLLOWINGTEMPORARY INSTALLATION REQUIREMENTS ARE MET. INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPERVENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RAT­ING PLATE MARKING;
• MEANS FOR PROVIDING OUT­DOOR AIR REQUIRED FOR COM­BUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND 80°F (27°C); AND;
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUB­STANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPERATING CONDITIONS INCLUDING IGNI­TION, INPUT RATE,TEMPERA­TURE RISE AND VENTING, ACCORDINGTOTHE INSTRUC­TIONS.
WARNING
!
DO NOT JUMPER OR OTHERWISE BYPASS OVERTEMPERATURE OR ANY OTHER LIMITS OR SWITCHES ONTHE FURNACE. IF ONE OF THESE LIMITS OR SWITCHES SHOULDTRIP OR OPEN,THE USER ISTO BE INSTRUCTEDTO CALL A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER. FOR MANUALLY RESETABLE SWITCHES,THE USER IS FURTHER INSTRUCTEDTO NEVER RESETTHE SWITCH, BUTTO CALL A QUALIFIED TECHNICIAN. MANUAL RESET SWITCHES MAY REQUIRE FURTHER CORRECTIVE ACTIONS. FAILURETO FOLLOWTHIS WARNING COULD RESULT IN CARBON MONOXIDE POISONING, SERIOUS INJURY OR DEATH. IFTHE UNIT IS INSTALLED IN A CLOSET,THE DOOR MUST BE CLOSEDWHEN MAKINGTHIS CHECK. INSTALLERS ANDTECHNI­CIANS ARE INSTRUCTEDTO REPLACE ANY LIMIT OR SAFETY SWITCH/DEVICE ONLY WITH IDENTI­CAL REPLACEMENT PARTS.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTOTHE HOME CAUSING PROPERTY DAM­AGE. FUMES AND ODORS FROM TOXIC,VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMO­BILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTOTHE LIVING SPACETHROUGH LEAKING DUCTS AND UNBAL­ANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 5).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS INTHE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTOTHE LIV­ING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CAR­BON MONOXIDE INTOTHE LIVING SPACE.
WARNING
!
ALWAYS INSTALL FURNACE TO OPERATE WITHIN THE FUR­NACE'S INTENDED TEMPERA­TURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTER­NAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FUR­NACETO AREAS OUTSIDE THE SPACE CONTAINING THE FUR­NACE,THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CAS­ING AND TERMINATING OUTSIDE THE SPACE CONTAININGTHE FURNACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITHTHE CSA INTERNATIONAL (CSA) CERTIFI­CATION OR THESE INSTRUC­TIONS, CAN RESULT IN UNSATIS­FACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOG­NIZED CODES, IT IS RECOM­MENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPO­RATOR COILS THAT ARE LOCAT­ED IN ANY AREA OF A STRUC­TURE WHERE DAMAGETOTHE BUILDING OR BUILDING CON­TENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING. SEE ACCES­SORIES SECTION OF THESE INSTRUCTIONS FOR AUXILIARY HORIZONTAL OVERFLOW PAN INFORMATION (MODEL RXBM).
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN 2 OR MORE DIFFERENT FURNACES. DOING SO COULD RESULT IN UNEX­PECTED OPERATION – INCLUD­ING INADEQUATE AIRFLOW DUR­ING HEATING (AND OTHER MODES OR A LOSS OF HEAT).
4
Page 5
Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction is some­times caused by an improper installation. By completing this checklist, the problem may be found and corrected. Make copies of the checklist and complete one for every Low Profile Furnace service call for your records.
INSTALLATION CHECKLIST
(Refer to this manual for specifics.) GAS SUPPLY
Adequate pipe size No gas leaks Proper supply and manifold gas pressure (check with an accurate U-tube manometer with the furnace and all other
gas appliances operating.)
ELECTRICAL
Correct thermostat and subbase Thermostat model Subbase model Correct thermostat mode and setting Correct line supply voltage Correct power supply polarity is required with electronic ignition Correct furnace ground to electrical panel DC microamp (A) flame signal (hot surface ignition units) Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals “Y” “C” - not with wire nuts
VENTING
Correct vent pipe diameter and length (according to CSA tables) Vent connection size Correct venting material (according to CSA tables) Correct lining for masonry chimneys Adequate clearance from combustibles Proper negative pressure reading in the vent Vent pipe secured to induced draft blower housing
COMBUSTION AIR
Proper source of combustion air Optional attic combustion air pull Correct combustion air opening size Non-attic combustion air pull
FURNACE INSTALLATION
Adequate clearance from combustibles Adequate clearance for service Proper air temperature rise (See furnace rating plate) External static pressure inches w.c. Correct filter(s) Correct cooling coil or accessories (if equipped) Adequate supply and return air ducting ReturnAir Duct Size SupplyAir Duct Size Air ducts sealed to prevent leakage
5
Page 6
GENERAL INFORMATION
The RGPE/RGLE series furnaces are design certified by CSA for use with nat­ural and propane gasesas follows:
As a CategoryI furnace, it may be vented vertically with type B-1 vent pipe and alsomay be common vent­ed as described in these instructions.
This furnace should be installed in accor­dancewith the American National Standard Z223.1 - latest edition booklet entitled “National Fuel Gas Code” (NFPA
54) (in Canada, CSAB149.1 and .2 Installation Codes for gas burning appli­ances), and the requirements or codes of the localutility or other authorityhaving jurisdiction including local plumbing or wastewater codes.
The NationalAppliance Energy ConservationAct (NAECA) of 1987 states that any gas furnace manufac­turedafter January 1, 1992, must have a minimumAnnual Fuel Utilization Efficiency (AFUE) of 78%.The higher the AFUE percentage the more usableheat energy the consumer gets for every dol­lar of fuel purchased.This is similarto the EPA's minimum gas mileage require­ment for automobiles. It gives the con­sumera relativelyeasy way to make direct efficiency comparisons between differentfurnace brands and styles.
A high AFUE value, which translates into a low operating cost, is not the only con­cern thatconsumers have. Theyalso want a furnace with a reasonable installed cost. They want a furnace that provides them with comfort – their main concern.And they expecta furnace with exceptional reliability and longevity.
Gas furnace manufacturers are always striving to provide consumers with the best furnace value. The Low Profile Furnace addresses all those consumer needs. It gives exceptionalefficiency with a low installationcost. It delivers the comfort the customer wants along with the reliability they expect.
The key to all these customer benefits is the furnace's heat exchanger.The mate­rialsused to construct the furnace in gen­eral and the heatexchanger in particular make it a rugged,long lasting unit. The unique heat exchanger design provides the customer with a furnace only 34 inch­es high.This gives the consumer a unit easily installed in almost every location that accepts all customary accessories.
With the introduction of higherefficiency furnaces, special attention mustbe paid to the venting system.Only listed venting systems may be used as stated in the installation instructions and the National
Fuel Gas Code, ANSI Z223.1 (NFPA 54), or the Canadian CAN/CGA B149.1 and B149.2 InstallationCodes for Gas Burning Appliances.Sincefurnace tech-
nology and ventingrequirements are changing, awarenessof local, state, and federal codes and industry changes is imperative.
NOTE: Always perform a proper heat loss calculation beforespecifying the fur­nace size. This ensures that the furnace is sized to adequately, economically, heat the building and provide the correct air­flow for yourapplication.
IMPORTANT:PROPERAPPLICATION, INSTALLATION AND MAINTENANCE OF THIS FURNACE ISA MUST IF CONSUMERSARE TO RECEIVE THE FULLBENEFITS FOR WHICH THEY HAVE PAID.
Additionalhelpful publications available from the “NationalFire Protection Association” are: NFPA-90A– Installation ofAir Conditioning and Ventilating Systems 1985 or latestedition.NFPA­90B – WarmAir Heating and Air Conditioning Systems 1984.
Thesepublications are availablefrom:
National Fire Protection Association,
Inc. Batterymarch Park Quincy, MA 02269
CSA-INTERNATIONAL 178 Rexdale Blvd. Etobicoke (Toronto), Ontario Canada M9W, 1R3
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment.
FIGURE 1
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program rec­ommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST,FUMES AND ODORS INTOTHE HOME CAUSING PROP­ERTY DAMAGE. FUMES AND ODORS FROM TOXIC,VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOX­IDE (CO), CAN BE DRAWN INTO THE LIVING SPACETHROUGH LEAKING DUCTS AND UNBAL­ANCED DUCT SYSTEMS CAUS­ING PERSONAL INJURY OR DEATH (SEE FIGURE 1).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOX­IDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH
6
Page 7
AS WATER HEATERS OR BOILERS
- ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CAR­BON MONOXIDE INTOTHE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITHTHE CSA INTERNATIONAL (CSA) CERTIFICA­TION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COV­ERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDEDTHAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORA­TOR COILS OR UNITS CONTAINING EVAPORATOR COILS OR GAS FUR­NACES USED WITH EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGETO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOP­PAGE IN THE PRIMARY CONDEN­SATE DRAIN PIPING.
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applica­tions.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is required to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in a level position to ensure proper condensate drainage. Make sure unit is level in both directions within 1/8”.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPANo. 70-(Latest Edition) National Electrical Code.
• NFPA90AInstallation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning sys­tems.
• The equipment has been evaluat­ed in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
1. NOTE: This furnace is shipped with heat exchanger support brackets installed under the back of the heat exchanger.These may be removed before installation, but it is not required.
LOCATION
!
WARNING
THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DO NOT INSTALLTHIS FUR­NACE IN A MOBILE HOME. INSTALLATION IN A MOBILE HOME COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
2. IMPORTANT: This furnace is not approved or recommended for instal­lation on its back, with access doors facing upwards.
3. This furnace is suitable for installa­tion in buildings constructed on-site. This heating unit should be central­ized with respect to the heat distribu­tion system as much as practicable.
4. NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces.
5. IMPORTANT: Support this unit when
installed.Forattic or crawl space installation, horizontal furnaces may be installed on combustible wood flooring or by using support brackets. See Figure 2.
FIGURE 2
HORIZONTAL FURNACE INSTALLEDW/SUPPORT BRACKETS
EXHAUST VENT
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure 3. Allow enough space for proper service maintenance or replacement of the heat exchanger and blower assembly.
6. IMPORTANT: If installing in a util-
ity room, be sure the door is wide enough to:
a. allow the largest part of the fur­b. allow any other appliance
nace to pass; or (such as a water heater) to
pass.
ST-A0799-01
7
Page 8
FIGURE 3
UPFLOW/HORIZONTAL DIMENSIONS
Ship.
/32
19
15
REDUCED CLEARANCE (IN.)
Back Top Front Vent
Left Right
A B C D E F
20
/16
1
28
May be 1with type B vent.
May require 3to 4or 3or 5adapter.
May be 0with type B vent.
/2 0 3 0 1 3 6 105 lbs.
/2 0 3 0 1 3 6 115 lbs.
/2 0 0 0 1 3 6 120 lbs.
1
/8 15 2
3
/32 12
11
/2 16
1
/2 0 0 0 1 3 6 140 lbs.
1
1
1
/2 2
1
/8 15 2
/8 18
/8 22 2
3
1
7
/32 12
/32 14
/32 15
11
27
11
/2 16
/2 23
1
1
D
/16
9
/32
19
B
A
/16
7
24
5
ALTERNATE
GAS CONNECTION
/4
3
/8 DIA.
1
/8
5
26
/8 DIA.
7
/8 DIA.
7
OPTIONAL RETURN AIR CUTOUT
/2
1
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
23
11
/8
3
14
/32
11
RIGHT SIDE
24
34
FRONT
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
/4
1
1
BOTTOM
TOP
RGPE Side Side Wgts.
Model
05 17
07(A) 17
/32
17
23
AIR
RETURN
/2
1
24
AIR
SUPPLY
25.406
12 24
07(B),10 21 19
/32
19
SIGHT
GLASS
*Both sides for 1800 CFM or above.
AIRFLOW
/32
11
E
/16
C
13
26
/8
5
26
GAS CONNECTION
F
24
/8
3
14
/2
1
11
LOW VOLTAGE
ELECTRICAL CONNECTION
OPTIONAL RETURN AIR CUTOUT
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
LEFT SIDE
IMPORTANT: This furnace is not approved or recommended for
installation on its back, with access doors facing upwards.
8
Page 9
FIGURE 4
DOWNFLOW DIMENSIONS
Ship.
Back Top Front Vent
REDUCED CLEARANCE (IN.)
/8
5
/8
1
20
/16
1
28
May be 1with type B vent.
May require 3to 4or 3or 5adapter.
May be 0with type B vent.
/8
5
26
/8 DIA.
/8 DIA.
7
7
/16
7
24
/8 DIA.
5
1
D
Left Right
A B C D E
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
Model
DOWNFLOW MODELS
RGLE Side Side Wgts.
/16
3
/8
/8 0 0 0 1 3 6 140 lbs.
/8 0 3 0 1 3 6 105 lbs.
/8 0 0 0 1 3 6 120 lbs.
5
1
5
3
20
/8
3
6
23
/8 23
/8 16
/8 20
1
7
5
/32 12
/32 13
/32 15
11
27
11
/2 16
/2 23
1
1
12 24
07(A) 17
07(B),10 21 19
/4
3
19
/8
5
R.A.
B
A
/8
5
/4
3
SIGHT
34
GLASS
AIRFLOW
S.A.
AIR
E
SUPPLY
/8
3
23
/8
3
20
/16
3
6
TOP BOTTOM
AIR
RETURN
1
/2
24
/8
5
26
C
LOW VOLTAGE
/16
13
26
GAS CONNECTION
ELECTRIC CONNECTION
NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.
COMBUSTIBLE FLOOR BASE REQUIRED IF FURNACE IS NOT INSTALLED ON COIL BOX.
9
Page 10
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the tables on the following pages are certified by CSA for the clearances to combustible materials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches is recommended in front of all furnaces.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST TAKE PRECEDENCE OVER FIRE PROTEC­TION CLEARANCES.
!
WARNING
UPFLOW AND HORIZONTAL FURNACES MUST NOT BE INSTALLED DIRECTLY ON CARPET­ING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE CAUSING PROPER­TY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
A gas-fired furnace for installation in a residential garage must be installed so that the burner(s) and the ignition source are located not less than 18” above the floor and the furnace is locat­ed or protected to avoid physical dam­age by vehicles.
!
WARNING
DOWNFLOW UNIT DESIGN IS CERTI­FIED FOR INSTALLATION ON NON­COMBUSTIBLE FLOOR. A SPECIAL COMBUSTIBLE FLOOR SUB-BASE, FIGURE 5, IS REQUIRED WHEN INSTALLING ON A COMBUSTIBLE FLOOR. FAILURETO INSTALLTHE SUB-BASE MAY RESULT IN FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.THIS SPECIAL BASE IS OFFERED AS AN ACCES­SORY FROM THE FACTORY. SEE THE CLEARANCE LABEL LOCATED INSIDE THE FURNACE FOR THE APPROPRIATE MODEL NUMBER.
THE SPECIAL BASE IS NOT REQUIRED WHEN THE FURNACE IS INSTALLED ON TOP OF AN AIR CONDITIONING PLENUM.
SITE SELECTION
1. Select a site in the building near the center of the proposed, or existing, duct system.
2. Give consideration to the vent sys­tem piping when selecting the fur­nace location. Be sure the venting system can travel from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas pip­ing.
4. Locate the furnace to maintain prop­er clearance to combustibles as shown in Figures 3 and 4.
!
CAUTION
WHEN COILS ARE INSTALLED ABOVE A FINISHED CEILING OR LIVING AREA, IT IS RECOMMENDED THAT AN AUXILIARY SHEET METAL CONDENSATE DRAIN PAN BE FAB­RICATED AND INSTALLED UNDER ENTIRE UNIT. FAILURETO DO SO CAN RESULT IN PROPERTY DAM­AGE. RUN CONDENSATETO A LOCATION WHERE IT IS NOTICE­ABLE.
!
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET OR WITHIN THE SPECIFIED CLEARANCES OF THE VENT PIPE. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COM­BUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMA­BLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUNDTHE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.THE FURNACE OWNER SHOULD BE CAUTIONED THATTHE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PUR­POSES.
DUCTING
Proper air flow is required for the correct operation of this furnace. Too little air flow can cause erratic oper­ation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling. Position the unit to minimize long runs or runs with many turns and elbows.
Size and install the ducts according to acceptable industry standards and methods. The total static pres­sure drop (including evaporator coil, if used) of the entire system should not exceed 0.8” w.c. adequate space for unit filter. NOTE: Airflow external static pressure mea­surements do not include filter or coil.
IMPORTANT: Some high efficiency filters have a greater than normal resistance to air flow.This can adversely affect furnace operation. BE SURE TO CHECK AIR FLOW if using any filter other than the facto­ry-provided filter.
NOTE: DO NOT take return air from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
IMPORTANT: Return air tempera- ture must be above 55°F during the heating season.
!
WARNING
NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTSTO ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED.WHEN A FURNACE IS MOUNTED ON A PLATFORM,WITH RETURN THROUGHTHE BOTTOM, IT MUST BE SEALED AIRTIGHT BETWEEN THE FURNACE AND THE RETURN AIR PLENUM. THE RETURN AIR PLENUM MUST BE PERMANENT­LY ENCLOSED. NEVER USE A DOOR AS A PART OF THE RETURN AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT OF THE FURNACE, WITHOUT SAGGING, CRACKS, GAPS, ETC., AROUND THE BASE AS TO PROVIDE A SEAL BETWEEN THE SUPPORT AND THE BASE.
Be sure to have
10
Page 11
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIR­CULATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZ­ARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUM­STANCES, CONNECT RETURN OR SUPPLY DUCTWORK TO OR FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLO­SION, PERSONAL INJURY OR PROP­ERTY DAMAGE.
!
WARNING
BLOWER AND BURNERS MUST NEVER BE OPERATEDWITHOUT THE BLOWER DOOR IN PLACE.THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTOTHE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
UPFLOW UNITS
1. Set furnace in place and connect the return duct or return air cabinet to unit. Make the connection air-tight to prevent entraining combustion gases from any adjacent fuel-burning appli­ances. Unit return air may be con­nected on the sides or bottom of the return air compartment.
a. Openings in the side must be cut
out the full width of the knockouts on the unit. If using side return air,
THE BOTTOM base plate must be installed.
NOTE: Where the maximum airflow
is 1800 CFM or more, both sides or the bottom must be used for return air.
b. If using bottom return air, place fur-
nace over return air plenum and seal furnace bottom to return air plenum.
!
WARNING
A SOLID METAL BASE PLATE, (SEE TABLE 1) MUST BE IN PLACE WHEN THE FURNACE IS INSTALLED WITH SIDE AIR RETURN DUCTS. FAILURE TO INSTALL A BASE PLATE COULD CAUSE PRODUCTS OF COMBUS­TION TO BE CIRCULATED INTO THE LIVING SPACE AND CREATE POTEN­TIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH.
TABLE 1
FURNACE BASE BASE
WIDTH PLATE NO. PLATE SIZE
1
17
/2 RXGB-D17 151/8x 239/16
21” RXGB-D21 18
1
24
/2 RXGB-D24 255/8” x 239/16
5
/8” x 239/16
2. If summer air conditioning is desired, position the indoor coil on the supply air side of the furnace. Insure that no air can bypass this coil.
3. Connect the supply air plenum to the furnace plenum opening, or indoor coil.
NOTE: The RGLE has louvers to cool the inducer motor bearings.
DOWNFLOW UNITS
!
WARNING
THE DOWNFLOW FURNACE DESIGN IS CERTIFIED FOR INSTALLATION ON A NON-COMBUSTIBLE FLOOR. IF INSTALLED ON A COMBUSTIBLE FLOOR, USE THE SPECIAL BASE SPECIFIED ON THE FURNACE CLEARANCE LABEL. FAILURETO INSTALLTHE SPECIAL BASE MAY RESULT IN FIRE, PROPERTY DAM­AGE, PERSONAL INJURY OR DEATH.THIS SPECIAL BASE IS SHIPPED FROM THE FACTORY AS AN ACCESSORY.
FIGURE 5
COMBUSTIBLE FLOOR BASE (RXGC-B17, -B21, -B24)
1. Position the unit over the supply air plenum and connect.
a. If installing on a combustible
floor and not using an evapo- rator coil box, install the spe­cial combustible floor base. See Figure 5.
b. If summer air conditioning is
desired, position the indoor coil on the supply air side. Insure that no air can bypass this coil.
2. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining com­bustion gases from an adjacent fuel-burning appliance.
HORIZONTAL UNITS
1. Unit can be mounted left or right side airflow configuration.
2. Position the unit on adequate supports or by using support brackets (see Figure 2) and con­nect supply plenum and return.
3. If summer air conditioning is desired, position the indoor coil on the supply air side of the unit. Insure that no air can bypass this coil.
4. Secure the four angle brackets shipped with the unit to the return air opening. See Figure 6. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining com­bustion gases from an adjacent fuel-burning appliance.
NOTE: Do not block furnace access with support rods. Maintain clear­ances recommended in Figure 3. Allow enough space for proper ser­vice maintenance or replacement of the heat exchanger and blower assembly.
11
Page 12
FIGURE 6
HORIZONTAL RETURN AIR DUCT (LEFT-HAND AIRFLOW POSITION SHOWN)
AIRFLOW
RETURN
REAR VIEW
FOUR ANGLE BRACKETS ARE SHIPPED WITH EACH UNIT THAT CAN BE USED TO SECURE THE RETURN AIR DUCT TO A HORIZONTAL UNIT.
COMBUSTION AND VENTILATION AIR
IMPORTANT: This is not a direct vent furnace. Review venting instructions before installing.
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry
rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following sub­stances in the combustion air supply may also require OUTDOOR AIR for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for
clothes dryers
• Masonry acid washing materials
!
WARNING
THIS FURNACE AND ANY OTHER FUEL-BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUS­TION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRETHAT OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAILURETO DO SO CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING.
Adequate facilities for providing air for combustion and ventilation must be provided in accordance with section
5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI, Z223.1 latest edition or CSA B149.1 and .2 or, applicable provisions for the local building codes, and not obstructed so as to prevent the flow of air to the furnace.
COMBUSTION AIR REQUIRE­MENTS
IMPORTANT: Air for combustion and ventilation must not come from a corro­sive atmosphere. Any failure due to cor­rosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation may require OUTDOOR AIR for combustion, due to chemical exposures:
FIGURE 7
AIR FROM HEATED SPACE
12
Page 13
Combustion air must be free of acid forming chemicals; such as sulphur, flu­orine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresh­eners, paint and varnish removers, refrigerants and many other commercial and household products. Vapors from these products when burned in a gas flame form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they con­dense.
!
WARNING
ALL FURNACE INSTALLATIONS MUST COMPLYWITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN CREATE HAZ­ARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH FROM SMOKE, FIRE OR CARBON MONOXIDE.
Combustion air requirements are deter­mined by whether the furnace is in an open (unconfined) area or in a confined space such as a closet or small room. See Figures 7 and 8.
EXAMPLE 1. FURNACE LOCATED IN AN UNCON­FINED SPACE
Using indoor air for combustion.
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of the total input for all appli ances
in the space. Here are a few
-
examples of the room sizes required for different inputs. The sizes are based on 8 foot ceilings.
BTUH Minimum Sq. Feet Typical Room Size
Input With 8' Ceiling With 8' Ceiling
50,000 312 14*x24* or 18*x18*
75,000 469 15*x31* or 20*x24* 100,000 625 20*x31* or 25*x25* 125,000 833 23*x34* or 26*x30*
If the open space containing the fur­nace is in a building with tight construc­tion (contemporary construction), out­side air may still be required for the fur­nace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
FIGURE 8
AIR FROM ATTIC/CRAWL SPACE
EXAMPLE 2. FURNACE LOCATED IN A CONFINED SPACE
A confined space (any space smaller than shown above as “unconfined”) must have openings into the space which are located in accordance with the requirements set forth in the follow­ing subsections A and B. Size the open­ings by how they are connected to the heated area or to the outside, and by the input of all appliances in the space.
If confined space is within a building with tight construction, combustion air must be taken from outdoors or area freely communicating with the outdoors.
A. USING INDOOR AIR FOR COM-
BUSTION, ALL OF THE MODELS
IMPORTANT: Air should not be taken from a heated space with a fireplace, exhaust fan or other device that may produce a negative pressure.
If combustion air is taken from the heat-
ed area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 Btuh of total input in the space. Here are some examples of typical openings required.
Btuh Free Area
Input Each Opening
100,000 100 Square Inches
AIR INTAKE PIPE CONNECTION (RGPE UPFLOW/HORIZONTAL ONLY)
A double-elbow may be installed to top inlet air opening, BUT IS NOT REQUIRED.This will help to prevent accidental blockage of the intake opening. Reference Figure 9 for proper elbow diame­ter.
NOTE: Inlet is specifically designed
to prevent material from being pulled into furnace. If elbows are not used, the intake opening must be kept clean and free of debris.
It is also acceptable to run the condensate drain (or refrigerant) line access over the air intake hole as long as a 1" minimum clearance is maintained.
B. USING OUTDOOR AIR FOR
COMBUSTION, ALL OF THE MODELS
IMPORTANT: Never take com- bustion air from an attic space that is equipped with power ventilation.
The confined space must com­municate with the outdoors according to Methods 1 and 2. The minimum air opening dimen­sion shall not be less than 3 inch­es. When using ducts, they shall be of the same cross-sectional area as the free area of the open­ings to which they connect.
13
Page 14
FIGURE 9
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET AIR OPENING TO PREVENT ACCIDENTALBLOCKAGE OF INTAKE OPENING. THIS IS NOT A REQUIREMENT. (SEE PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED BUT MAY NOT PREVENT DEBRIS FROM BEING DROPPED INTO THE FURNACE.
EXHAUST
PVC DOUBLE ELBOW
6" MININUM CLEARANCE
#8 SCREWS
6" MIN.
GROUND OR SHELF SURFACE
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
METALFLUE PIPE ONLY
#8 SCREWS
B: Method 1 Provide two permanent openings,
one located within 12 inches of the top and one located within 12 inches of the bottom of the enclosure. Each opening shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating
with the outdoors or where com­municating to the outdoors through VERTICAL DUCTS, each opening shall have a minimum free area of 1 square inch for each 4000 BTUH of total appli­ance input rating in the enclosure. Here are typical duct sizes:
VERTICAL OUTDOOR AIR OPENING DIMENSIONS
BTUH Free Area Round
Input Each Opening Pipe Size
50,000 12.50 sq. inches 4
75,000 18.75 sq. inches 5 100,000 25.00 sq. inches 6 125,000 31.25 sq. inches 7
b. Where communicating with out-
doors through HORIZONTAL DUCTS, each opening shall have a minimum free area of 1 square inch for each 2000 BTUH of total input rating for all equipment in the enclosure. Here are typical duct sizes:
HORIZONTAL OUTDOOR AIR OPENING DIMENSIONS
BTUH Free Area Round
Input Each Opening Pipe Size
50,000 25.00 sq. inches 6
75,000 37.50 sq. inches 7 100,000 50.00 sq. inches 8 125,000 62.50 sq. inches 9
B: Method 2 One permanent opening, located within
12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall directly communicate with the out­doors or communicate through a verti­cal or horizontal duct to the outdoors or spaces (crawl or attic) that freely com­municate with the outdoors and have a minimum free area of:
a. One square inch for each 3000
BTUH of the total input rating of all equipment located in the enclosure, AND
b. Not less than the sum of the
areas of all vent connectors in the confined space.
IMPORTANT: If the furnace is in a location with an exhaust fan, there must be sufficient ventilation to pre­vent the exhaust fan from creating a negative pressure in the room.
Combustion air openings must NOT BE RESTRICTED in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
14
Page 15
B: Method 3, RGPE only For the optimum in quiet operation, attic
air may be brought directly to the fur­nace.
IMPORTANT: In applications using Method 3 for combustion air, the attic must be ventilated by gable or soffit vents. See Figure 8.
It is not required to provide any per­manent openings as described in Method 1
!
or Method 2.
CAUTION
COMBUSTION AIR INTAKES CAN­NOT BE TERMINATED OUTSIDE. DOING SO CAN CAUSE IMPROPER
FIGURE 10
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
OPERATION OF THE FURNACE
If attic combustion air is used, the inlet air opening at the furnace must be pro­tected from accidental blockage. Install a 90° elbow pointing horizontally at the top of inlet air pipe. See Figure 11 (maximum of 2, 22
1
2°, 45° or 90°
elbows, allowed).
NOTE: Maximum length of pipe that may be used for combustion air is 10 feet with two elbows. Lengths of more than 10 feet can result in nui­sance pressure switch trips.
FIGURE 11
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH A 90° ELBOW TO TOP INLET AIR OPENING TO PREVENT ACCIDENTALBLOCKAGE OF INTAKE OPENING.
PVC ELBOW
EXHAUST
ATTIC SPACE
METALFLUE PIPE ONLY
INDOOR SPACE
10 FT. MAX.
!
CAUTION
12" MIN. FROM TOP OF INSULATION
INCLUDING HORIZONTALDIRECTION
#8 SCREW
INSULATION
6" MINIMUM CLEARANCE
PVC COUPLER
USE OF SHEET METAL AIR INTAKE PIPE INSTEAD OF PVC MAY RESULT IN NOISE ISSUES.
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
#8 SCREWS
15
Page 16
VENTING
GENERAL INFORMATION
The furnace must be vented in accor­dance with these instructions, National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA­B149.1 & .2 and requirements or codes of the local utility or other authority hav­ing jurisdiction.
!
WARNING
DEVICES ATTACHED TOTHE FLUE OR VENT FOR THE PURPOSE OF REDUCING HEAT LOSS UP THE CHIMNEY HAVE NOT BEEN TESTED AND HAVE NOT BEEN INCLUDED IN THE DESIGN CERTIFICATION OF THIS FURNACE. WE, THE MANUFAC­TURER, CANNOT AND WILL NOT BE RESPONSIBLE FOR INJURY OR DAMAGE CAUSED BYTHE USE OF SUCH UNTESTED AND/OR UNCER­TIFIED DEVICES, ACCESSORIES OR COMPONENTS.
DRAFT INDUCER
!
WARNING
VENT PIPE ATTACHING HOLES MUST BE PREDRILLED IN THE DRAFT INDUCER COLLAR TO PRE­VENT DAMAGINGTHE INDUCER. DRILL 1/8DIAMETER HOLES THROUGHTHE VENT PIPE AND COLLAR AND USE #8 SCREWS TO ATTACH. SEE FIGURE 12. FAILURE TO FOLLOWTHIS WARNING CAN CAUSE RECIRCULATION OF FLUE PRODUCTS CAUSING CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
FIGURE 12
ATTACHINGTO DRAFT INDUCER COLLAR
FURNACE CATEGORY INFORMATION
This furnace is shipped as a Category I type induced draft furnace. A Category I furnace operates with a nonpositive vent pressure and has a vent gas tem­perature at least 140°F above the dew point of the vent gases. A Category I type may be a draft hood equipped fur­nace or have a fan assisted combustion system (induced draft). The inducer is used to pull flue products through the combustion chamber and as they leave the furnace, most of the energy has been dissipated. The buoyant effect of the flue gases provides venting to the outdoors.
During the off cycle, the inducer is off and there is very little flow through the vent, cooling the vent. During the on cycle there is no dilution airflow, as with a draft hood type furnace. Although the vent heats up rapidly without dilution air, the flue products contain more water vapor, which results in a higher dew point temperature. It is most important that you follow the guide­lines in these instructions to prevent the possible formation of condensation in the venting system.
As a Category I furnace it may be vent­ed vertically with type B-1 vent pipe and also may be common vented, as described in these instructions.
A0991-01
IMPORTANT APPLICTION NOTES
When the furnace is used as a replacement, the existing vent sys­tem should be inspected to assure that there are no obstructions, block­age, or any signs of corrosion and is properly sized for use with this fur­nace.
NOTE: When the vent table permits more than one diameter of pipe for a connector or vent, the smallest per­mitted diameter must be used.
Vent pipe may be type “B-1,” either rigid or suitable flexible construction that carries a u.l. listing.
Common venting is allowed with vertical B-1 vent systems, and lined masonry chimneys. Follow the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2 for proper installation practices.
NOTE: Follow combustion air instructions as outlined in this manu­al.
Single wall vent connectors to “B-1 vent or masonry chimneys” may be used under the guidelines of the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
The entire length of the vent con­nector shall be readily accessible for inspection, cleaning and replacement.
16
Page 17
“B-1” VERTICAL VENTING
Type “B-1” vents must be installed in accordance with the terms of their list­ings and the vent manufacturer’s instructions.
“B-1” vents must be supported and spaced in accordance with their listings and the manufacturer’s instructions. All vents must be supported to maintain their minimum clearances from com­bustible material.
VERTICAL VENTING
Categorized
Input Size Required
50K 3
75K *4 100K *4 125K *5
*NOTE: All furnaces have a 3” vent connec­tion as shipped from the factory. A 3” to 4” or 3” to 5” vent transition is required on all but the 50,000 BTUH models when vertically vented or common vented with metal vent pipes. THE VENT TRANSITION CONNEC-
TION MUST BE MADE ATTHE FURNACE VENT EXIT. It must originate with an adapter
if required, at the furnace flue collar and ter­minate either in a listed cap or roof assem­bly. When common venting, the vent con­nector size may differ from the above diame­ters depending on application. See ANSI Z21.47-1993/CSA-2.3-M93 or latest edition tables.
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed cap or listed roof assembly. Gas vents 12 inches in size or smaller with listed caps shall be permitted to be terminated in accordance with Figure 13, provided they are at least 8 feet from a vertical wall or similar obstruction. All other gas vents shall terminate not less than 2 feet above the highest point where they pass through the roof and at least 2 feet higher than any portion of a building within 10 feet.
2. A type B-1 gas vent shall terminate at least 5 feet in vertical height above the highest connected equipment draft hood or flue collar.
3. Must rise
1
/4” per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or dips. Supports at 4 foot intervals and at all elbows are recommended.
4. The vent connector must be mechan­ically fastened to the outlet collar of the furnace with at least (2) sheet metal screws except vent connectors that are B-1 material. These shall be assembled in accordance with the manufacturer’s instructions. See Figure 12.
Furnace Vent
FIGURE 13
TYPICAL VENTING WITH “B-1”VENT
5. Any angle greater than 45 degrees from the vertical is considered hori­zontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft-hood equipped appliances shall not be greater than 75 percent of the verti­cal height of the vent.
NOTE: Refer to the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
Single appliance venting of a fan assist­ed furnace into a tile-lined masonry chimney is prohibited. The chimney must be lined with either Type B vent or with a listed, single wall, metal lining system. Reference National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2. See Figure 14 for typical B-1 vent chase.
!
WARNING
DO NOT CONNECT THIS FUR­NACETO A CHIMNEY USED TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD TO IMPROPER FUNC­TIONING OF THE UNIT, AND DUE TO SOOTING,THE POSSIBILITY OF FIRE RESULTING IN PROPER­TY DAMAGE, PERSONAL INJURY OR DEATH.
SPECIAL VENT SYSTEMS (SVS)
IMPORTANT: It is THE FURNACE MANUFACTURER’s position now that new pipe used in a category III vent application, including Selkirk’s Selvent™ II HTPV product, should cease immediately.
installations of any HTPV
17
Page 18
POWER VENT SYSTEMS
When vertical venting is not possible, the only acceptable method for horizon­tal venting is with the use of Tjernlund model GPAK-1TR or Field Controls models SWG-4R power venter. Type B vent pipe and fittings must be used. Common venting is not permitted
All application and installation instructions supplied with the power venter must be followed.
Please address all questions regarding power venter installation, agency list­ings and furnace model compatibility to:
Tjernlund Products, Inc. (800) 255-4208 or (612) 426-2993
Field Controls L.L.C. (800) 742-8368 or (919) 522-0214
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: CHIMNEY ADAPTER IS CERTIFIED FOR USE ON UPFLOW (RGPE) ONLY.
This appliance is CSA certified for use with RXGW-B01 Chimney Adapter. Refer to Kit Installation Instructions 92-101682-01.
EXISTING VENT SYSTEMS
IMPORTANT RETROFIT VENTING INSTRUCTIONS
If this furnace is a replacement installa­tion, ALWAYS INSPECT the existing vent system to be sure there are no obstructions, blockages, or signs of cor­rosion.
When the existing furnace is removed from a venting system serving other appliances, the venting is likely to be too large to properly vent the remaining attached appliances.
The following steps shall be followed with each appliance that remains con­nected to the common venting system, while the other appliances that remain connected to the common venting sys­tems are not in operation.
NOTE:When the vent table permits more than one diameter of pipe for a connector or vent, the smallest per­mitted diameter must be used.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no block­age, restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all build­ing doors, windows and all doors between the space where the appli­ances remaining connected to the common venting system are located.
Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6. After it has been determined that each appliance that remains con­nected to the common venting system properly vents (when test­ed as outlined above) return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the common venting system must be resized. Refer to National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
FIGURE 14
DEDICATED VENTING THROUGH CHIMNEY WITH “B-1”VENT
18
Page 19
GAS SUPPLY AND PIPING
GAS SUPPLY
!
WARNING
THIS FURNACE IS EQUIPPED ATTHE FACTORY FOR USE ON NATURAL GAS ONLY. CONVERSIONTO LP GAS REQUIRES A SPECIAL KIT AVAIL­ABLE FROMTHE DISTRIBUTOR. FAILURETO USE THE PROPER CON­VERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
See the conversion kit index supplied with the furnace.This index identifies the proper LP Gas Conversion Kit required for each particular furnace.
IMPORTANT: Any additions, changes or
conversions required for the furnace to satisfactorily meet the application should be made by a qualified installer, service agency or the gas supplier, using facto­ry-specified or approved parts. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appro­priate fuel.
IMPORTANT: Connect this furnace only to gas supplied by a commercial utility.
IMPORTANT: A U.L. recognized fuel gas and CO detector(s) are recom­mended in all applications, and their installation should be in accor­dance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
FIGURE 15
GAS PIPING INSTALLATION
MANUAL GAS VALVE
(IN CLOSED POSITION)
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
GAS PIPE INSTALLATION
UPFLOW & DOWNFLOW
UNION
HORIZONTAL
MANUAL GAS VALVE (IN CLOSED POSITION)
FLAME SENSOR
BURNERS
BURNERS
FLAME SENSOR
DUCT
UNION
GAS VALVE
MANIFOLD
DIRECT SPARK IGNITOR
GAS PIPING (SEE FIGURE 15)
Install the gas piping according to all local codes, state codes and regulations of the utility company, whichever holds jurisdiction.
If possible, run a separate gas supply line directly from the meter to the fur­nace. Consult the local gas company for the location of the manual main shut-off valve.The gas line and manual gas
valve must be adequate in size to prevent undue pressure drop and never smaller than the pipe size to the combination gas valve on the fur­nace. Refer to Table 2 for the recom-
mended pipe size for natural gas and Table 3 for LP gas pipe sizes.
IMPORTANT: It is permissible to run flexible gas connector inside the unit to a piece of black pipe. If local codes
DIRECT SPARK IGNITOR
allow the use of a flexible gas appliance connector, always use a new listed con­nector. Do not use a connector which has previously serviced another gas appliance.Massachusetts law limits flex­ible gas connectors to a maximum of 36”.
Install a ground joint union outside the cabinet to easily remove the con­trol valve assembly. Install a manual shut-off valve in the gas line outside the cabinet. The valve should be readi-
ly accessible to turn the gas supply on or off. Install a drip leg in the gas supply line as close to the furnace as possible. Always use a pipe compound resistant to the action of liquefied petroleum gases on all threaded connections.
MANIFOLD
GAS VALVE
IMPORTANT: When making gas pipe connections, use a back-up wrench to prevent any twisting of the control assembly and gas valve.Do not overtighten the connection.
Any strains on the gas valve can change the position of the gas ori­fices in the burners. This can cause erratic furnace operation.
IMPORTANT: ENSURE that the fur- nace gas control valve not be sub­jected to high gas line supply pres­sures.
DISCONNECT the furnace and its individual shut-off valve from the gas supply piping during any pressure
testing that exceeds 1/2 PSIG (14” W.C.) (3.48 kPa).
19
Page 20
GAS PRESSURE
IMPORTANT: Natural gas supply pres­sure should operate between 5" to
10.5w.c. LP gas supply pressure should be 11to 13w.c. This pressure
must be maintained with all other gas-fired appliances in operation.
NOTE: Do not exceed a gas pressure of 13” w.c.
WARNING
!
ELEVATIONS ABOVE 2000 FT REQUIRETHATTHE FURNACE INPUT RATING BE ADJUSTED ANDTHAT THE SIZE OFTHE BURNER ORI­FICES BE RE-CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE.THE BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED.SEE THE SECTION TITLED“HIGH ALTITUDE INSTALLA­TIONS” OF THIS BOOK FOR INSTRUCTIONS.
WARNING
!
NEVER PURGE A GAS LINE INTO THE COMBUSTION CHAMBER. NEVER USE MATCHES, FLAME OR ANY IGNITION SOURCE FOR CHECKING LEAKAGE.FAILURETO FOLLOWTHIS WARNING CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
To check for gas leakage, use an approved chloride-free soap and water solution, or other approved method.
LP CONVERSION
NOTE: For installation, see specific LP kit installation instructions. Orifice must be ordered for the correct elevation.
NOTE:Order the correct LP conversion kit from the local distributor. Furnace conversion to LP gas must be per­formed by a qualified technician.
More information found in the high alti­tude and orifice section.
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas, remove the NOx insert assemblies. Steps for removal are listed below:
1. Turn off all electrical power and the gas supply to the furnace.
2. Remove the burner door from the furnace.
3. Remove the igniter assembly –
handle with care.
4. Remove the two screws attach­ing the NOx insert retainer brackets to the center panel. Pull the retainer rod.
5. Put the two screws back into the holes in the center panel.
6. Re-install the igniter and burner assemblies.
7. Replace burner door.
8. Turn on electrical power and gas supply to the unit.
NOTE:Some NOx models may have one less NOx insert.
20
Page 21
SETTING GAS PRESSURE
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure). (Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal Length of Pipe, Feet Iron Pipe Size, Inches 10 20 30 40 50 60 70 80 90100125 150
1/2 275 189 152 129 114 103 96 89 83 78 69 63 3/4 567 393315 267 237 217 196 182 173 162 146 132
11,071 732 590504 448 409 378 346 322 307 275 252 1-1/4 2,205 1,496 1,212 1,039913 834 771 724 677 630567 511 1-1/2 3,307 2,299 1,858 1,559 1,417 1,275 1,1811,086 1,023 976 866
787
2 6,221 4,331 3,465 2,9922,646 2,394 2,205 2,047 1,9211,811 1,606 1,496
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
The maximum gas supply pressure to the furnace should be 10.5w.c. natur­al gas, or 13w.c. LP gas. The mini­mum supply gas pressure to the gas valve should be 5" w.c. natural gas or 11" w.c. LP gas. A properly calibrated manometer is required for accurate gas pressure measurements.
Supply Gas Pressure Measurement.
A line pressure tap is on the inlet side of the gas valve.
1. With gas shut off to the furnace at the manual gas valve outside the unit, remove the input pressure tap plug.
2. Connect a U-Tube manometer to the pressure tap.
3. Turn on the gas supply and oper­ate the furnace and all other gas­fired units on the same gas line as the furnace.
4. Adjust the line gas pressure to supply:
A. 5” - 10.5” w.c. for natural gas. B. 11” - 13” w.c. for LP gas.
5. Shut off the gas at the manual gas valve and remove the U-Tube manometer.
6. Replace the pressure tap plug.
7. Turn gas on, and check for leaks.
NATURAL GAS:
If the supply gas line pressure is above the operating range, install an in-line gas regulator to the furnace. If supply gas line pressure is below the operat­ing range, either remove any restric­tions in the gas supply piping or enlarge the gas pipe. See Table 2.
LP GAS:
If the supply gas line pressure is above the operating range, have the LP sup­plier reduce the line pressure at the regulator. If supply gas line pressure is below operating range, have the LP supplier adjust the line pressure at the regulator. See Table 3.
NOTE: Depending on the amount of LP vapor and the outdoor ambient tem­perature, the LP storage tank may require supplemental heat to maintain proper pressure levels. Ensure LP stor­age tank does not drop below 15% capacity during heating season.
FIGURE 16
TYPICAL HOSE CONNECTION TO LINE PRESSURETAP
TABLE 2
NATURALGAS PIPE CAPACITYTABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of 0.60 (natural gas).
Nominal Length of Pipe, Feet Iron Pipe
Size, Inches 10 20 30 40 50 60 70 80
1/2 132 92 73 63 56 50 46 43 3/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 1-1/4 1,050 730 590 500 440 400 370 350 1-1/2 1,600 1,100 890 760 670 610 560 530
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be determined by consulting the local natural gas utility or the LP gas supplier.
Gas Input of Furnace (BTU/HR) Heating Value of Gas (BTU/FT3)
TABLE 3
LP GAS PIPE CAPACITYTABLE (CU.FT./HR.)
21
Page 22
ADJUSTING OR CHECKING FURNACE INPUT
NATURAL GAS:
The maximum gas supply pressure to the furnace should be 10.5” W.C. for natural gas. The minimum gas supply pressure for purposes of input adjust­ment to the furnace should be 5” W.C.
A properly calibrated manometer or gauge is required for accurate gas pressure readings.
1. When adjusting the furnace input, the high fire input should be checked. The high fire manifold pres­sure should be 3.5' W.C. Follow these steps to be sure the furnace is high fire mode:
a. With a single stage thermostat,
the furnace runs for 12 minutes on low fire before shifting to high fire. To be certain that it is on high fire, jump terminals “W” and “W2” on the control board in the blower compartment.
b. With a two stage thermostat, set
the thermostat to its highest set­ting to keep the furnace operating in the high fire mode.
2. To adust high fire manifold pressure, remove the adjustment cover screw on the outlet end of the gas valve and turn the adjustment screw clock­wise to increase the pressure and counterclockwise to reduce the pres­sure. Replace the cover screw securely.
3. The low fire manifold pressure should be 1.7" W.C. As mentioned above, the furnace remains in the low fire mode for 12 minutes upon a heat call with a single stage thermo­stat. With a two stage thermostat, disconnect the thermostat lead to the “W2” terminal on the control board and the furnace will remain in the low fire mode. To adjust the pressure, remove the regulator cover, on top of the valve, and adjust as noted under Step 2, above. After the adjustment replace the screw cover securely.
NOTE: Use a 3/32allen wrench for
making the pressure adjustment.
LP GAS:
Furnaces for use on LP gas, the LP gas supply pressure must be set between
11.0” and 13.0” W.C. by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas control valve. For elevations up to 7,000 feet, rating plate input ratings apply. For high alti­tudes (elevations 7,000 and over) and for any necessary major changes in the gas flow rate the orifice spud must be changed.
TO CHANGE ORIFICE SPUDS:
1. Shut off the manual main gas valve and remove the gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for leaks.
5. Check for proper operation and set to proper manifold pressure.
TABLE 4
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS
INPUT
BTU/HR
50,000
75,000
100,000
125,000
150,000
Input BTU/HR =
METER
CU. FT.
SIZE
ONE 15112 1 15 1 18 3 20 TEN 10 50 12 00 12 30 13 12 30 00
ONE 0 44 0 48 0 50 0 53 20 TEN 7 12 80819 8 48 20 0
ONE 0 33 0 36 0 38 0 40 1 30 TEN 5 24 60615 6 36 15 0
ONE 0 26 0 29 0 30 0 32 1 12 TEN 4 19 4 48 50517 12 0
ONE 0 31 0 24 0 25 0 26 10 TEN 3 36 40410 4 20 10 0
Heating Value of Gas (BTU/Ft3) x 3600 x correction factor Time in Seconds (for 1 cu.ft.) of Gas
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
Check of input is important to pre­vent over firing of the furnace beyond its design-rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE.
TO CHECK FURNACE INPUT:
1. Make certain that all other gas appliances are shut off, with the exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the time required to burn one cubic foot of gas.
4. Use Table 4 to determine input rate.
22
Page 23
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRI­CAL CONNECTIONS. FAILURETO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSON­AL INJURY OR DEATH.
WARNING
!
THE CABINET MUST HAVE AN UNINTERRUPTED GROUND ACCORDINGTO THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, ANSI/ NFPA70-, OR IN CANADA,THE CANADIAN ELECTRICAL CODE, CSA-C22.1 OR LOCAL CODES THAT APPLY. A GROUND SCREW IS PROVIDED IN THE JUNCTION BOX. FAILURE TO PROPERLY CONNECTTHE GROUNDWIRE CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSON­AL INJURY OR DEATH.
ate wiring diagramlocated on the inside cover of the furnacecontrol box and in these instructions.
NOTE:The electrical junction box may be moved to the right sideif necessary. A knockout is provided.Seal the opposite holewith plugprovided.
WARNING
!
L1TERMINAL AND NEUTRALTERMI­NAL POLARITY MUST BE OBSERVED WHENMAKINGFIELD CONNECTIONS TOTHE FURNACE. FAILURETO DO SOWILL EXPOSE LIVEWIRING IN THE BLOWER COMPARTMENTWHEN THE DOOR IS REMOVED.TOUCHING THESE LIVE CIRCUITS COULD RESULT IN PERMANENT INJURY OR DEATH FROMELECTRICALSHOCK.
FIGURE 17
JUNCTION BOX LOCATION
UPFLOW/HORIZONTAL
Make all electrical connections in accordance with the latest edition of the National Electrical Code ANSI/NFPA70 – or in Canada, the Canadian Electrical Code Part 1­CSA Standard C22.1 and local codes having jurisdiction.
These may be obtained from: National Fire Protection
Association, Inc. Batterymarch Park Quincy, MA 02269
Canadian StandardsAssociation 178 Rexdale Boulevard Rexdale, Ontario, Canada M9W 1R3
WARNING
!
THIS FURNACE IS EQUIPPED WITH A BLOWER DOOR SAFETY SWITCH. DO NOT DISABLETHIS SWITCH. FAILURETO FOLLOW THISWARNING CAN RESULT IN ELECTRICAL SHOCK, PERSON­AL INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical compo­nents are protected from water.
A grounding wire is provided to connect to the incoming grounding wire from line power. The furnace must be perma­nently grounded in accordance with all national and local codes.
Before proceeding with the electrical connections, be certain that the service panel voltage, frequency and phase cor­responds to that specified on the fur­nace rating plate. Maximum over-current protection is 15 amperes.
Use a separate,fused branch electrical circuitcontaininga properly sizedfuse or circuitbreaker. Connect this circuitdirectly fromthe main switchbox to an electrical disconnect that is readily accessible and locatedwithin arm’s reach (2 ft.)of the furnace. Connect fromthe electrical dis­connectto the junction boxon the left sideof the furnace, inside the blower compartment. See Figure 17.For the proper connection,refer to the appropri-
DOWNFLOW
23
Page 24
ELECTRICAL CHECKS
Line Power Check
The furnace must have a nominal 115 volt power supply for proper opera­tion. If there is not a consistent power supply, contact a licensed electrician to correct the problem.
1. With the blower compartment door off, manually hold the push button door switch in.
2. Call for heat at the thermostat.
3. With the unit operating, use a volt­meter to measure the voltage from any 120 VAC terminal to any neu­tral connection.
4. The voltage should be a nominal 115 volts (acceptable 105­120VAC).
This test should be made with the unit in full operation.
Polarity Check
If line & neutral are reversed, a fault code (26) will be displayed at the fur­nace seven segment display (SSD) and at the communicating thermostat active fault display screen (communi­cating systems only).
Proper line voltage polarity, or phas­ing, is a must for this furnace to oper­ate. Use a volt meter to make this check.
1. With the blower compartment door off, manually hold the push button door switch in.
2. Use a voltmeter to measure the voltage from any 120 VAC terminal to any bare metal ground on the furnace.
3. The voltage should be a nominal 115 volts (acceptable 105­120VAC).
4. Use a voltmeter to measure the voltage from any neutral terminal to the bare metal ground on the furnace.
5. The voltage should be less than
1.0 VAC.
6. If the voltage from any 120 VAC terminal to ground is less than 1.0 VAC volts and the voltage from a neutral to ground is a nominal 115 volts, the polarity is reversed.
7. To correct the problem, either reverse the hot and neutral wires to the furnace or have a licensed electrician check the building wiring.
ControlVoltage Check
1. With the blower compartment door off, manually hold the push button door switch in.
2. Call for heat at the thermostat. (Does not include communicating thermostats.)
3. With the unit operating, use a volt­meter to measure the voltage from control voltage terminal “W” to ter­minal “C” on the furnacecontrol board.
4. The voltage should be a nominal 24 volts (Acceptable 18-30 VAC).
This test should be made with the unit
in full operation.
24
Page 25
ACCESSORIES
FIELD-INSTALLED OPTION ACCESSORIES
TWINNING: Most installations of (-)GPE/ (-)GLE furnaces cannot be twinned. However, a few exceptions exist for installations with some commercial evaporator coils. Consult the installation instructions of the coil to see if the fur­nace(s) can be twinned. If so, a twinning kit will be required and the part number for the kit can be found in the installation instructions for the coil.
ELECTRONIC AIR CLEANER
Line voltage power is supplied from the screw terminal “EAC”, see Figure 18, and a line voltageneutral screw terminal on the control board. This will power the electronic air cleaner whenever the blower is operating and delivering the recommended minimum CFM. The 50 and 75 KBTU models, which are capa­ble of a maximum delivery of 1200 CFM, will operate the electronic air cleaner at 500 CFM and above. The 100 and 120 KBTU models, which are capable of a maximum delivery of 2000 CFM, will operate the electronic air cleaner at 800 CFM and above. These limits are set to prevent excessive production of ozone at the lower airflows of the furnaceand are based on average requirements of commercially available electronic air cleaners. Continuous fan speeds are selectable and some lower fan speeds may not deliver enough airflow to operate an electronic air cleaner. The IFC deter­mines the minimum airflow necessary to operate an electronic air cleaner and will not turn on the electronic air cleaner unless the airflow is high enough for the EAC.
FIGURE 18
EAC AND HUMIDIFIER TERMINALS ON FUR­NACE CONTROL (IFC)
HUMIDIFICATION AND DEHUMIDIFI­CATION
HUMIDIFIER – The humidifier contacts (labeled “HUM OUT”) are “dry” contacts on the I.F.C. This means that the termi­nals are connected directly to the con­tacts of a board-mounted relay. The coil of the relay is controlled by the microprocessor of the IFC. The coil is engaged roughly any time the heat speed blower is engaged and (1) 24VAC is present on the thermostat ter­minal of the IFC labeled “HUM STAT” or (2) a communicating thermostat with humidification and dehumidification capability is installed with call for humidification present.
FIGURE 19
WIRING FOR OPTIONAL HUMIDIFICATION (AND DEHUMIDIFICATION WITH COMMUNICATING THERMOSTAT) WITH OPTIONAL HUMIDIFIER AND NO HUMIDISTAT (HUMIDIFICATION ACTIVE DURING ANY HEAT CALL) (FOR USE WITH COMMUNICATING AND NON-COMMUNICATING THERMOSTATS)
FIGURE 20
WIRING FOR OPTIONAL DEHUMIDIFICATIONWITH HUMIDIFICATION (WITH OPTIONAL HUMIDISTAT AND HUMIDIFIER) NOTE: CAN BE USED WITH COMMUNICATING OR NON-COMMUNICATING SYSTEMS
An optional 24VAC humidistat can be installed as shown in Figures 19 thru 54 (II thru IV). With the optional humidistat, two separate conditions must be met before humidification can begin 1). There must be a call for heat and the blower must be engaged and 2.) The humidistat must determine that there is a need for humidification.
Note: Dipswitch SW2-1 (labeled “ODD”) enables (“ON”) or disables (“OFF”) dehumidification operation. However, it has no affect on humidi­fication operation. If this switch is set to the “ON” position and no humidistat is installed, the cooling
25
Page 26
FIGURE 21
WIRING FOR OPTIONAL DEHUMIDIFICATION OPERATION AND HUMIDIFICATION WITH OPTIONAL HUMIDIFIER (HUMIDIFIER WITH INTERNAL POWER SUPPLY) (FOR USE WITH NON-COMMUNICATINGTHERMOSTATS)
FIGURE 22
HUMIDISTAT USEDTO CONTROL DEHUMIDIFICATION IN COOLING ONLY (NO HUMIDIFIER) (FOR USE WITH NON-COMMUNICATINGTHERMOSTATS)
airflow will be permanently reduced by approximately 15% giving less than optimal performance and possibly caus­ing problems. It is not recommended to leave this switch in the “ON” position without a humidistat installed.
Control of dehumidification in cooling and/or humidification in heating can be done with a variety of methods depend­ing on whether there is a communicat­ing thermostat or a humidistat available and depending on the type of operation desired.
With systems configured with communi­cating thermostats and condensers, dehumidification is controlled by the condenser and is not affected by the position of dipswitch SW2-1 or the volt­age (or lack of voltage) at the thermo­stat terminal labeled “HUM STAT”.
To determine which wiring diagram and method to use, select from the following configurations:
A. HUMIDIFICATION CONTROL ONLY
WITH NO DEHUMIDIFICATION (REQUIRES OPTIONAL HUMIDIFI­ER).
A1. WITH COMMUNICATING
THERMOSTAT Humidifier control is included with the (-)HC-TST412MDMS (modulating, non-communicat­ing) and (-)HC-TST550CMMS (full-color communicating) model thermostats. However, it is not included with the (-)HC­TST501CMMS model commu­nicating thermostat. The latter thermostat should not be used if humidification control is required. To wire the furnace for humidification control using the former thermostat, refer to the wiring diagram in Figure 19(I). Be sure not
to install the
jumper between “R” and “HUM
STAT” on the furnace con­trol. Installing this jumper will operate the humidifier any time there is a heat call. Without the jumper, the humidification call from the thermostat must be active and a heat call must be pre­sent with the blower running.
A2. WITH NON-COMMUNICAT-
ING THERMOSTAT A2-1 CONTINOUS HUMID-
IFIER OPERATION DURING HEATING. For continuous humid­ifier operation during heating, refer to Figure 19 (I) and make sure to install the jumper between the thermostat termi­nals labeled “R” and “HUM STAT”. A sepa­rate humidistat is not required for this con­figuration and the humidifier will turn on whenever there is a call for heat and the blower is running.
A2-2 CONTROLED
HUMIDIFIER OPERA­TION USING A HUMIDISTAT (REQUIRES OPTION­AL HUMIDISTAT). Controlled humidifica­tion can be accom­plished using a humidistat as shown in Figures 20 (II) or 21 (III). These figures show installation of a humidifier with exter­nal and internal power supplies respectively. Dehumidification oper­ation will be disabled if the dipswitch SW2-1 is in the “OFF” posi­tion. If this switch is in the “ON” position, dehumidification con­trol will be active.
B. DEHUMIDIFICATION CONTROL
WITH NO HUMIDIFICATION B1. For communicating ther-
mostats listed with this fur­nace, dehumidification is controlled automatically when selected at the ther­mostat and additional wiring is not necessary. The actual airflow demand (reduced for dehumidification) is request­ed of the furnace by the condenser.
26
Page 27
B2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES OPTIONAL HUMIDISTAT).
Control of dehumidification only (no humidification) can be accomplished by installing an optional humidistat as shown in Figure 22 (IV). The dipswitch SW2-1 must be set to the “ON” position. If this switch is not turned “ON”, dehumidification operation will not take place. Further, if this switch is “ON” and no humidistat is installed, airflow in cooling will be perma­nently reduced by approximate­ly 15%.
C. HUMIDIFICATION AND DEHUMIFI-
CATION CONTROL (REQUIRES OPTIONAL HUMIDIFI­ER).
C1. WITH COMMUNICATING
THERMOSTAT
Humidifier control is included with the (-)HC-TST412MDMS (modulating, non-communicat­ing) and (-)HC-TST550CMMS (full-color communicating) model thermostats. However, it is not included with the (-)HC­TST501CMMS model commu­nicating thermostat. Do not purchase the latter thermostat if humidification control is required. To wire the furnace for humidification and dehumidi­fication control using the former thermostat, refer to the wiring diagram in Figure 19 (I). Be sure not between “R” and “HUM STAT” on the furnace control. Installing this jumper will oper­ate the humidifier any time
to install the jumper
THERMOSTAT AND ACCESSORIES FOR THERMOSTAT
Programmable Communicating:
(-)HC-TST501CMMS
Full-Color, Programmable Communicating:
(-)HC-TST550CMMS
Remote Sensor:
(For Thermostats Above Only)
F1451378
Thermostat Wall Plate ForThermostat HC-TST501CMMS Above Only:
F61-2600
there is a heat call and dehu­midification will never take place when in cooling. Without the jumper, a humidification call from the thermostat must be active and a heat call must be present with the blower running for the “HUM OUT” relay con­tacts to close.
C2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES OPTIONAL HUMIDISTAT.)
For non-communicating ther­mostats, an optional humidistat must be installed. Controlled humidification and dehumidifi­cation can be accomplished using a humidistat as shown in Figures 20 (II) or 21 (III). These figures show installation of a humidifier with external and internal power supplies respec­tively. Dehumidification opera­tion will be disabled if the dip­switch SW2-1 is in the “OFF” position. If this switch is in the “ON” position, dehumidification control will be active.
OTHER ACCESSORIES AVAILABLE
FOSSIL FUEL KIT (non-communicat-
ing systems only)
Use of a heat pump with the two stage furnace requires a heat pump thermostat used in conjunction with the fossil fuel kit. For proper operation use the follow­ing procedures:
a. With the RXPF-F01 kit, connectthe
thermostat “E” terminal, one side of the plenum switch, and the black wire from the fossil fuel kit to “W2” on the IFC.
b. For the RXPF-F02 kit, connect
“W” on the fossil fuel kit interface wiring board to “W2” on the IFC.
Regardless of which fossil fuel kit is used, when activated, the two stage furnace follows the sequence of operation for a single stage thermo­stat.
IMPORTANT: ALWAYS FOLLOW THE MANUFACTURER’S FOSSIL FUEL KIT INSTRUCTIONS.
TWINNING: Most installations of (-)GPE and (-)GLE furnaces cannot be twinned. However, a few excep­tions exist for installations with some commercial evaporator coils. Consult the installation instructions of the coil to see if the furnace can be twinned. If so, a twinning kit will be required and the part number for the kit can be found in the installation instruc­tions for the coil.
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: Chimney adapter is certified for use on upflow only.
This appliance is CSA certified for use with RXGW-B01 chimney adapter. Refer to kit installation instructions 92-101682-01.
TYPICAL WIRING FOR SELECT ACCESSORIES FOR COMMUNICATING RESIDENTIAL SYSTEMS
The Rheem Serial Communicating (CC2) system allows accessories to be connected to shut down the sys­tem in the event of a fault. Typical devices that can be connected are the drain overflow switch, smoke detector and freeze protection switch. There are two methods of connecting the switch to the system depending on the device configura­tion normally closed or normally open. The blower can run during a fault or the blower can shut off dur­ing a fault depending on how the system is connected. Please refer to local and/or state codes for installing these devices. The following opera­tion applies only when BOTH the condenser and thermostat are serial communicating devices. If the con­denser is non-communicating (tradi­tional, legacy 24VAC controlled) this diagram is not valid.
27
Page 28
METHOD BLOWER
ACTIVATION
CONTACTS WIRING CONFIGURATION
NORMALLY
OPEN
When 24 VAC is applied to Y1 at the furnace control in a communicating system a SYSTEM BUSY message appears on the thermostat. When the SYSTEM BUSY message appears the outdoor unit will shut down and the indoor unit will continue to run at first stage cooling airflow.
A
BLOWER
RUNS
(Y1)
NORMALLY
CLOSED
If the device does not have normally open contacts an additional relay must be used for proper system operation.
NORMALLY
OPEN
When the device is connected to Y2 and a fault occurs the blower will shut down. The Y2 input can still be used with normally open or normally closed contacts.
B
BLOWER
DOES NOT
RUN
(Y2)
NORMALLY
CLOSED
If the device does not have normally open contacts an additional relay must be used for proper system operation.
OPERATION WITH SELECTED ACCESSORIES
28
Page 29
80+ HIGH ALTITUDE
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT INPUT RATING FOR INSTALLATION AT ALTITUDES
BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION
DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
D'ALTITUDE.
92-24399-01-01
INSTRUCTIONS (TABLE 13)
!
CAUTION
INSTALLATION OFTHIS FURNACE AT ALTITUDES ABOVE 2000 FT (610 m) SHALL BE IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES,THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54 OR NATIONAL STAN­DARD OF CANADA, NATURAL GAS AND PROPANE INSTALLATION CODE, CAN B149.1.
Furnaces can be ordered from the fac­tory already converted for high altitude elevations. The factory option for high altitude elevations would be ordered as a 278 option (example: a 75k BTU upflow furnace which is factory convert­ed for high altitude elevations would have the model number (-)GPE­07EAMKR). These factory converted furnaces come with pressure switches for high-altitude elevations already attached. Also, different burner orifices are installed at the factory which are one drill size smaller (#43 DMS) than standard (-)GPE/(-)GLE gas furnaces (#42 DMS). The smaller orifice is installed to accommodate for average heating values expected in most high altitude areas and a required 4% per thousand feet reduction in input as specified by the National Fuel Gas Code (NFGC). Specific orifices should always
be recalculated for all high alti­tude installations as outlined below. Orifices should be changed, if neces­sary, based on gas heating value and elevation.
34" 80 Plus furnaces installed above 2,000 ft. require the furnace to be de­rated 4% per thousand feet.
IMPORTANT: Factory installed orifices are calculated and sized based on a sea level Natural Gas heating value of 1075 BTU per cubic ft.
NOTE:Orifices are available through your local distributor.
Reference Tables 11, 12 and 13 for appropriate orifice sizing.
NOTE:Keep any parts removed during LP conversion procedure stored with the product literature for future use.
The following are examples of orifice sizing using the National Fuel Gas Code Appendix F:
Example: 900 BTU/ft Natural Gas Heating Value
I/H = Q 25000 / 900 = 27.78 ft
I = Sea Level input (per burner): 25000 H = Sea Level Heating Value: 900 Q = 27.78 ft
3
Natural Gas per hour.
From Table F.1 of National Fuel Gas Code Handbook, 2002 (3.5w.c. col- umn).
Orifice required at Seal Level: #40 From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4% de-rate per thousand ft): #42
3
Regional
3
Orifice required at 8000 ft. elevation (4% de-rate per thousand ft.): #44
TABLE 11
LP GAS
Example: 1050 BTU/ft3 Regional Natural Gas Heating Value
I / H = Q 25000 / 1050 = 23.81ft
3
I = Sea Level input (per burner): 25000 H = Sea Level Heating Value: 1050 Q = 23.81 ft
3
Natural Gas per hour.
From Table F.1 of Natural Fuel Gas Code Handbook, 2002 (3.5w.c. col- umn).
Orifice required at Sea Level: #43 From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4% de-rate per thousand ft.): #45
Orifice required at 8000 ft elevation (4% de-rate per thousand ft): #47
LP GAS (TABLE 11)
LP Gas is a manufactured gas that has consistent heating value across most regions.
The NFGC guidelines are used with the following exception:
The recommended LP Gas high altitude orifice selections differ slightly in that the NFGC LP orifice chart, as they are not accurate for Rheem products. The National Fuel Gas Code LP orifices are based on an 11" of water column pres­sure at the orifice, which differs from products that use 10" of water column at the orifice. This difference requires a deviation from the NFGC orifice size recommendations. The Sea Level input
Altitude burner) 25000 Size
0 to 2000 ft. 25000 #54 2000-3000 24000 #54 3000-4000 23000 #54 4000-5000 22000 #54 5000-6000 21000 #54 6000-7000 20000 #54 7000-8000 19000 #55 8000-9000 18000 #55
9000-10000 17000 #55
sand ft. and the orifice size must be selected based on the reduced input in Table 11.
ORIFICE ORDERING INFORMATION
Orifice sizes are selected by adding the 2-digit drill size required in the orifice part number. Drill sizes avail­able are 39 through 64; metric sizes available 1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill size)
Example 1: # 60 drill size orifice required Part # 62-22175-60
Example 2:
1.15mm drill size orifice required Part # 62-22175-91
should still be reduced by 4% per thou-
TABLE 12
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE
NATURAL GAS LP GAS
ORIFICE
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
50,000
75,000 100,000 125,000 150,000
45,000
67,500
90,000 112,500 135,000
OUTPUT
40,000 60,000
80,000 100,000 120,000
36,000
54,000
72,000
90,000 108,000
SIZE
#42
#42
MANIFOLD
PRESSURE
3.5” W.C.
2.9” W.C.
ALTITUDE
0’ - 2000’
2001’ - 4500’
FIGURE 23
MANIFOLD PRESSURE-CHANGE LABEL
INPUT
50,000
75,000 100,000 125,000 150,000
45,000
67,500
90,000 112,500 135,000
Input (per Orifice
ORIFICE
OUTPUT
40,000 60,000
80,000 100,000 120,000
36,000
54,000
72,000
90,000 108,000
SIZE
#54
#54
MANIFOLD PRESSURE
10” W.C.
8.1” W.C.
29
Page 30
NATURALGAS QUICK REFERENCE CHART FOR ORIFICE SELECTION, AT 3.5" W.C.AND APPROXIMATE FINAL FIRING RATES
ELEVATION CHART (NFG recommended orifice based on 4% derate for each 1000 foot of elevation, based on the intersection of the
Heat
80 Plus
Cubic
Sea Level
orifice required at Sea Level and the elevation required below)
Value at
Foot at
0-999 1000-1999 2000-2999 3000-3999 4000-4999 5000-5999 6000-6999 7000-7999 8000-8999 9000-9999
25,000
3.5" W.C.
25,000 24,000 23,000 22,000 21,000 20,000 19,000 18,000 17,000 16,000
30
TABLE 13
37 30.63 816 37 37 38 39 39 40 41 42 42 43
38 29.25 855 38 38 39 40 41 41 42 42 43 43
39 28.2 887 39 39 40 41 41 42 42 43 43 44
40 27.03 925 40 40 41 42 42 42 43 43 44 44
41 25.98 962 41 41 42 42 42 43 43 44 44 45
Size
Orifice
80 Plus Models with 25,000 Btu's per Burner
SUPPLEMENTAL ORIFICE SIZE CHART
Sea Level
42 24.95 1002 42 42 42 43 43 43 44 44 45 46
43 22.39 1117 43 43 44 44 44 45 45 46 47 47
44 21.01 1190 44 44 45 45 45 46 47 47 48 48
Final Firing Rate per Burner
NOTE:
All calculations are performed by using the first three columns of information only. Before beginning any calculations, determine the individual burner Btu size
and heating value at Sea Level for the installation site. Each value shown in the Heat Value column is per burner at 3.5" W.C.
Heat Value at Sea Level, for the location of the installation, is available from the Natural Gas Supplier to that site. Orifices for all altitudes are based on Sea Level values.
Divide the individual burner capacity (25,000 for 80 plus) by the Heat Value for the site to determine the Cubic Foot value at Sea Level, or divide burner capacity by the
Cubic Foot value for the Heat Value. Once you have either the Cubic Foot Value or the Heat Value you can estimate the Sea Level orifice for the site. To select the corre-
sponding high altitude orifice, locate the site elevation on the chart above and the orifice required at Sea Level from your calculation in the first column. The correct high
altitude orifice that must be installed in each individual burner is the intersection of these two points on the chart above.
Page 31
ALTERNATE METHOD FOR CANADIAN
HIGH-ALTITUDE
DERATE
In Canada, unless an orifice change is specifically mandated by local codes, an alternate method of altitude deration through a reduction in manifold pressure is acceptable as described in Table 12. This information is based on a heating value of 1000 BTU per cubic feet of nat­ural gas, and 2500 BTU per cubic feet of LP gas.
IMPORTANT: Actual input rates must be measured onsite with manifold pres­sure adjustment to ensure that an actual 10% reduction in input rate is achieved.
Once this field adjustment has been made, the label shown in Figure 23 must be affixed in a conspicuous loca­tion on the front of the furnace cabinet.
NOTE: This label is supplied in the information packet shipped with each furnace.
AIR FLOW
The importance of proper air flow over the heat exchanger cannot be over emphasized.
!
CAUTION
IT IS IMPORTANT THAT EACH DUCT SYSTEM BE SIZED AND INSTALLED FORTHE SPECIFIC APPLICATION BY PROPERLY APPLYINGTHE APPRO­PRIATE INDUSTRY ACCEPTED STAN­DARD. IF LESS THAN MINIMUM STANDARDS ARE APPLIED,THE EQUIPMENT USER COULD EXPECT TO EXPERIENCE HIGHER UTILITY BILLS,MAJOR COMPONENT FAIL­URE,VARYING DEGREES OF AIR NOISE OR OTHER UNSATISFACTORY ISSUES,OVERWHICHTHE MANU­FACTURER HAS NO CONTROL.
One of the most common causes of heat exchanger failure is overheating due to low air flow.An air flow table is located inside the blower door and on the follow­ing pages.
FIGURE 24
TEMPERATURE RISE MEASUREMENT
FIGURE 25
TYPICAL FURNACE NAME PLATE
AIR CONDITIONING DIVISION
FORT SMITH, ARKANSAS
ZONING SYSTEMS
The manufacturer does not currently provide or support zoning.However, zoning systems can be installed with the system as long as the zoning equipment manufacturers specificationsand instal­lation instructions are met and followed.
The preferred zoning method is to use a “bypass” system which is properly installed for maximum efficiency. In these systems, excess air is routed back through the system to be used again – this is opposed to a “dump” system in which excess air is routed to a zone where it is expected that the extra heat or cooling would be least noticed.
If installed as a “bypass” system, the installation must have an optional freeze stat installed to preventthe coil from icing with excess bypass cooling. Also, if the zoning equipment manufacturerpro­vides a limit switch (usually provided by
31
Page 32
the zoning manufacturer), this limit must be installed in the system to prevent the furnace from overheating.
TEMPERATURE RISE CHECK
To determineif the air flow is correct, make a temperature rise check.
1. Insert a thermometer in the supply air duct as close to the furnace as possible yet out of a direct line from the heat exchanger. See Figure 24.
2. Insert a thermometer in the return air duct as close to the furnace as possible.
3. Operate the furnace.
4. When the thermometer in the sup­ply air duct stops rising (approxi­mately five minutes), subtract the return air temperature from the sup­ply air temperature. The difference is the temperature rise.
5. Compare the measured tempera­ture rise to the approved tempera­ture rise range listed on the furnace name plate. See product specifica­tion sheet and nameplate located on furnace.
If the measured temperature rise is above the approved range, either the air flow is too low or the manifold pressure needs to be adjusted. More air must be moved by speeding up the blower, by removing restrictions in the duct system, or by adding more supply or return air duct. If the measured temperature rise is below the approved range, either the air flow is too much or the manifold pres­sure needs to be adjusted. Use lower speed tap on the multi-speed blower.
IMPORTANT: The measured tempera­ture rise should be in the middle of the range. See product specification sheet and name plate located on furnace.
IMPORTANT: Some high-efficiency fil­ters have a greater than normal resis­tance to airflow. This can adversely affect furnace operation.BE SURETO CHECK AIRFLOW if using any filter other than factory-provided filter.
32
Page 33
INTEGRATED FURNACE CONTROL (I.F.C.)
(all must be on)
FIGURE 26
TWO-STAGE CLIMATE-TALK COMMUNICATING FURNACE CONTROL (RHEEM # 62-102784-01)
24 VACTHERMOSTAT (TSTAT) INPUTS (J4 & J6)
24 VACTHERMOSTAT (TSTAT) INPUTS (J4 & J6)
These connections are used with any traditional 24VAC one-stage or two­stage thermostat. Fully communicating thermostats must be connected to the COMM NETWORK CONNECTION (see section titled
SSYYSSTTEEMMSS
details).
CCOOMMMMUUNNIICCAATTIINNGG
of this document for
22,, YY11,, YY22,, GG,, CC aanndd RR
WW11,, WW traditional nearly all HVAC equipment. Installation of the thermostat to these connections is straight-forward and simple.
thermostat inputs used in
are the
HHUUMM SSTTAATT to connect the output of a humidistat to the furnace control to control humidification and/or dehumidifica­tion. Optional equipment is required for these features. Please see the section titled
DEHUMIDIFICATION
ment for more details.
– T
his terminal is used
HUMIDIFICTION AND
of this docu-
33
Page 34
SPECIAL CONFIGURATION – COMMUNICATING THERMOSTAT AND FURNACE WITH A NON­COMMUNICATING CONDENSER
YY11 aanndd YY22 used to connect directly to a non-com­municating condenser when a commu­nicating thermostat is installed to the furnace but a non-communicating con­denser is installed in the system. While the optimum configuration is with a communicating condenser connected to the network, there may be installa­tions where this is not desired. In these cases, the thermostat will be communicating with the furnace control and the furnace control will energize the condenser as necessary (the addi­tional relays have been added to the furnace control to allow this operation).
The thermostat connections labeled “Y1” and “Y2” on the I.F.C. are normally
iinnppuuttss
the blower when they are energized. However, in this configuration, these (normally) inputs become energize the condenser when a cooling call has been sent from the communi­cating thermostat.
– These terminals may be
to the furnace control to turn on
oouuttppuuttss
to
When this configuration is desired, use the wiring diagram in Figure 27 to con­nect the thermostat and condenser to the furnace control. For single stage condensers, a jumper must be installed between Y1 & Y2 at the furnace con­trol.
NOTE: A heat pump condenser cannot be installed with this configuration. There is no control for the reversing valve.
24 VAC FROM TRANSFORMER (XFORMER) CONNECTIONS
These inputs are used to connect 24VAC from the furnace transformer to the furnace control (I.F.C.).
FUSE (F1)
A three-amp automotive-style (ATC blade type) fuse is supplied on-board the furnace control. This fuse should provide protection from short-circuits on the control board and associated 24 VAC wiring.
115 VAC TERMINALS
These terminals supply 115 VAC to the furnace control from the input at the junction box of the furnace. Additionally, spare terminals are pro­vided for use with electronic air cleaners and other accessories as needed (Check the voltage rating of your equipment.)
INDUCED DRAFT MOTOR (INDUCER) OUTPUT (J2)
This four-pin Mate-n-Lok style con­nector is black in color and provides power to both the high and low speed inducer outputs. This con­nector on the IFC has female sock­ets so that it can not be confused with the four-pin connector used for motor control (which has male pins).
For troubleshooting purposes, follow the wiring diagram and troubleshoot­ing flowchart supplied in this manual and on the inside of the furnace blower door. Additionally, the pin designations for the connector are specified below:
FIGURE 27
WIRING DIAGRAM – SPECIAL CONFIGURATION: COMMUNICATING THERMOSTAT AND FURNACE WITH NON-COMMUNICATING CONDENSER
34
Page 35
PPiinn 11
to Inducer High Speed Output. PPiinn 22 PPiinn 33 PPiinn 44
Inducer Low Speed Output
to
not used.
is
Neutral.
to
NEUTRAL TERMINALS
These terminals connect 115VAC neu­tral to the furnace control from the input at the junction box of the furnace. Additionally, spare terminals are provid­ed for use with electronic air cleaners, humidifiers and other accessories as needed (Check the voltage rating of your equipment.)
ELECTRONIC AIR CLEANER (E.A.C.) OUTPUT (J8)
This output is used to energize an elec­tronic air cleaner. The output will pro­vide 1.0 amp at 115 VAC. This output is energized any time the blower motor is above 40% of maximum airflow capaci­ty. Airflow below this value is not con­sidered to be enough for a typical elec­tronic air cleaner to perform properly.
For 1/2HP motors – Electronic air clean­er is energized any time the blower is above 480 CFM (1200 CFM x 0.4)
For 1 HP motors - Electronic air cleaner is energized any time the blower is above 800 CFM (2000 CFM x 0.4)
HUMIDIFIER OUTPUT (J8)
These outputs (two) are connected to the contacts of a control-mounted relay. In this sense, they are what are called “dry” contacts. That is, they provide no voltage, they are only used to close a circuit. The contacts can be used to close either a 24VAC or 115VAC circuit either with a maximum of 1 amp cur­rent. Details about the humidifier out­puts and wiring diagrams can be found in the section titled
AND DEHUMIDIFICATION
ument.
HUMIDIFICATION
of this doc-
15-PIN MATE-N-LOK CONNEC­TOR (J1) (see Fig 28)
The 15-pin Mate-n-Lok style connector provides connections for a variety of inputs and outputs to the furnace con­trol. For modulating furnaces with a solenoid-controlled modulating gas valve (HG or HH Fuel Codes) the 15­pin connector provides power and con­trol signals to the gas valve. Also, the flame sense, pressure switches sense and limits sense (Main Limit, MRLC and HALC) are connected to the I.F.C. through this connector. Reference the wiring diagram for the furnace printed in this document or on the inside of the
furnace blower door for pin assign­ments for troubleshooting.
For troubleshooting purposes, follow the wiring diagram and troubleshoot­ing flowchart supplied in this manual and on the inside of the furnace blower door. Additionally, the pin designations for the connector are specified below:
PPiinn 11
to F
lame Sense rod.
PPiinn 22
to
Overtemp Limit (MRLC)
Sense PPiinn 33 PPiinn 44
PPiinn 55
PPiinn 66
PPiinn 77 PPiinn 88
PPiinn 99
PPiinn 11
PPiinn 1111 PPiinn 11
PPiinn 11 PPiinn 11 PPiinn 11
Main Limit (LC) Sense
to
24 VAC to Limit Sense
to
Circuits
VAC out to Auxiliary Limit
24
(HALC- Heat
Control)
1st stage gas valve solenoid
valve main
2nd stage gas valve solenoid
Low Pressure Switch
to
sense.
High Pressure Switch
to
sense.
00
to Low and High Pressure
Switch 2
to Aux Input sense
22
to Ground on furnace cabi-
net
33
not used on this control
44
not used on this control
55
gas valve 24VAC common
Assisted Limit
solenoid 24VAC.
4VAC
35
Page 36
FIGURE 28
15-PIN CONNECTOR; J1 WITH PIN DESIGNATIONS
COMMUNICATING ECM MOTOR COMMUNICATIONS (CONTROL) CONNECTION (J10) (see Fig 28)
This connector sends and receives messages to and from the blower motor through a single peer-to-peer network. The blower motor does not communi­cate on the same communications buss as the furnace, condenser and thermo­stat. Further, a different communica­tions protocol is used.
For troubleshooting purposes, follow the wiring diagram and troubleshooting flowchart supplied in this manual and on the inside of the furnace blower door. Additionally, the pin designations for the connector are specified below:
PPiinn 11
to com
motor PPiinn 22
motor PPiinn 33
motor PPiinn 44
motor
municating blower
connector Pin 1 (+V)
to communicating blower
connector Pin 2 (TX)
to communicating blower
connector Pin 3 (RX)
to communicating blower
connector Pin 4 (C)
36
Page 37
FIGURE 29
FOUR-PIN MOTOR CONTROL CONNECTION; J10 WITH PIN ASSIGNMENTS.
SPARK IGNITION TRANS­FORMER (XFORMER) (T1)
The spark ignition transformer resides on the furnace control (older genera­tions of the modulating furnace have the spark transformer mounted to a separate ignition control). The trans­former provides spark energy at approximately 60 hz frequency and a minimum of 12KV. The transformer can be seen in Figure 29.
R-J11 CONNECTOR (J-11)
WARNING
!
DO NOT CONNECT A TELEPHONE OR PHONE LINE TO THE CONNEC­TOR (JACK) AT POSITION J-11. DOING SO COULD CAUSE IRREPRABLE DAMAGE TO EITHER THE FURNACE CONTROL (I.F.C.) OR THE TELEPHONE (OR TELEPHONE LINE) OR BOTH.
This connector is used to program the furnace control at the factory. It can also be used to connect a field service diagnostic tool. Unfortunately, this tool was not available at the time of this publication but should be available in the future. Otherwise, this connection is not to be used in the field. It should never be connected to a telephone line or a telephone. Doing so could dam­age the furnace control or the tele­phone (or telephone lines) or both.
COMMUNICATIONS NETWORK CONNECTION
These connections are used when installing a communicating thermostat specified for use with this furnace. Further, normally, thermostat connec­tions will not be made at the 24 V Thermostat Inputs when using a com­municating thermostat. (Except under one special circumstance where a com-
municating thermostat and non-com­municating condenser are used. See Figure 27 and the section of this document titled SPECIAL CON-
FIGURATION – COMMUNICATING THERMOSTAT AND FURNACE WITH A NON-COMMUNICATING CONDENSER.)
The terminal labeled “1” on the fur­nace control connects directly to the terminal labeled “1” on the thermo­stat and “1” on the condenser. The remaining connections follow the same pattern.
Follow the wiring diagram in Figure 27 for connections of the communi­cations network.
COMMUNICATIONS L.E.D.’s (Light Emitting Diodes)
Note: The “RX” and “STAT” L.E.D.’s will not operate unless a communicating thermostat is
37
Page 38
installed. These L.E.D.’s will not ener­gize if a traditional 24V thermostat only is used to control the furnace.
“RX” (Green) L.E.D. – This L.E.D. indi-
cates that communications is being sensed to or from (i.e.: the network is trying to communicate) other components (e.g. a condenser) on the network. This L.E.D. will blink ran­domly any time a message is received by the furnace control. If no blinking is seen within five minutes, it can be assumed that there is not valid commu­nications established. Check wiring to make sure that all points are connected properly.
Further, if this L.E.D. is on continuously, it is an indication that mis-wiring has occurred. Most probably, connections “1” and “2” are reversed. Double-check the wiring and make sure that the wire connected to pin “1” on the condenser is the same wire connected to pin “1” on the thermostat and the furnace control. The same follows for the wires to pins “2”, “R” and “C”.
“STAT”
(STATUS) (Red) L.E.D.
L.E.D. blinks ON, ¾ second OFF) upon power-up.
twice slowly (¼ second
something
on
This
LEARN BUTTON
Pressing the learn button for two sec­onds will cause the green “RX” L.E.D. to blink rapidly (for a short period) to indi­cate an attempt at communications. If the L.E.D. does not blink, communica­tions can not be established. The prob­lem may be that the wires at the J9 con­nector “1” and “2” on the I.F.C. may be reversed. Check to make sure that wiring is from “1” on the IFC leads to “1” on the thermostat and condenser (if pre­sent) and the same follows for connec­tions “2”, “R” and “C”.
MEMORY CARD CONNECTOR (J15)
This connector is used to insert a mem­ory card.
MEMORY CARD
A memory card is defined as an elec­tronic card that carries a copy of the fur­nace shared data.
RULES FOR WRITING, DISTRIBU­TION AND ARBITRATION OF MULTI­PLE COPIES OF FURNACE SHARED DATA FOR COMMUNICATING-CAPA­BLE FURNACES
Furnace shared data data specific to a given furnace that is critical for proper furnace opera­tion. More specifically, it is data which defines the operation of the furnace and is unique to a given fur­nace platform and model. The most critical of these data are the coeffi­cients that control the blower opera­tion (i.e. define the blower speed­torque operation). Because of this, each furnace control is programmed with furnace shared data for that model furnace only. The furnace shared data from any given furnace can NOT be transferred to another furnace for any reason. Doing so can adversely affect operation of the furnace. Further, if no furnace shared data is present, the furnace will not operate in any mode and a fault will be displayed.
Valid Furnace Shared Data as furnace shared data for the fur­nace series in question with the cor­rect motor horsepower. However, it is impossible for the furnace control to determine if the furnace shared data is matched to the furnace input BTU’s if the motor horsepower is cor­rect. This means, for example, fur­nace shared data for a 120KBTU upflow furnace could be installed and recognized as valid furnace shared data in a 90KBTU downflow furnace. VALID FURNACE SHARED DATA simply means that there is no motor horsepower conflict and that the fur­nace shared data is for the series of furnace in question. VALID FUR­NACE SHARED DATA is data that will be used by the furnace control with no fault reported. VALID FUR­NACE SHARED DATA may not nec­essarily mean that the furnace shared data is correct for the furnace in question. The input BTU’s could still be incorrect and this is why it is important to never exchange memory cards from one furnace to another.
Furnace shared data is programmed into the furnace control microproces­sor and attached memory card at the factory. The attached memory card cannot be programmed in the field
is defined as
is defined
but furnace shared data inside the furnace IFC microprocessor may be written or rewritten in the field through the network depending on the circumstances.
WARNING
!
DO NOT REPLACE THE FURNACE CONTROL OR MEMORY CARD OF THE FURNACE WITH A FURNACE CONTROL OR MEMORY CARD OF ANOTHER FURNACE OR ANOTH­ER COMPONENT (E.G.: A MEMO­RY CARD FROM A CONDENSER OR AIR HANDLER). THE WRONG FURNACE CONTROL OR MEMO­RY CARD MAY SPECIFY PARA­METERS WHICH WILL MAKE THE FURNACE RUN AT UNDESIRED CONDITIONS INCLUDING (BUT NOT NECESSARILY LIMITED TO) REDUCED AIRFLOW DURING HEATING CAUSING EXCESSIVE UNDESIRED OPERATION OF THE MAIN LIMIT CONTROL. FUR­THER, THE MEMORY CARD IS SPECIFIC TO THE MODEL NUM­BER AND BTU INPUT RATING FOR A SPECIFIC FURNACE AND THIS INFORMATION SHOULD NOT BE TRANSPORTED FROM ONE FURNACE (OR COMPO­NENT) TO ANOTHER.
The memory card is the default memory location to be used first when there is any conflict. If the
memory card has been replaced with a card that has data for another furnace, the furnace will assume the identity of the “other” furnace. In all cases, the memory card has the final say about the data to use. It is only when the memory card is not present, is corrupt or specifies a motor larger or smaller than what is found in the furnace that the furnace control will use the data stored in the microprocessor (a mirror of the most recent memory card with blow­er size matching that found in the furnace). The hierarchy of data to be used in the event of a lost card or conflict is listed in order of impor­tance below.
AATTTTAACCHHEEDD
1. An
physically connected to the fur­nace control and almost appears to be part of the furnace control itself. A photo is shown in Figure 30 and is how the furnace control with memory card is shipped from the factory.
memory card is
38
Page 39
FIGURE 30
AN ATTACHED MEMORY CARD
IINNSSEERRTTEEDD
2. An
memory card is one that has been inserted into connector J15 of the furnace control and is shown in the photo in Figure 31 below. A memory card will not be inserted in this connector from the factory and the connector is designed only to be used to install a memory card to a replacement furnace control in the field.
Replacement IFC’s (furnace controls) from ProStock do NOT contain any furnace shared data and, as such,
FIGURE 31
IINNSSEERRTTEEDD
AN FURNACE CONTROL BELOW. REPLACEMENT FURNACE CONTROLS FROM PROSTOCK WILL INCLUDE THIS ATTACHED CARD (BELOW) EXCEPT WITHOUT THE ELECTRONIC COMPO­NENTS WHICH ARE SHOWN HERE SURFACE-MOUNTED TO THE CARD.
MEMORY CARD. NOTE THAT A BLANK CARD IS STILL SEEN ATTACHED TO THE
will not operate the furnace until fur­nace shared data is loaded in the field either via the original memory card or via redundant copies stored on various components in a commu­nicating network (the latter applies only to installations configured as communicating systems and NOT to so-called legacy (24VAC) controlled systems).
When the furnace control is replaced, the original memory card must be broken away from the origi-
nal furnace control (IFC) and retained with the furnace. When the new IFC is installed, the origi­nal memory card will be inserted into connector J15 of the IFC to impart the critical furnace shared data to the replacement control. Note that in this circumstance there will be essentially two fur­nace shared data cards; one attached to the furnace control and one inserted into connector J15. However, the attached card has no furnace shared data as replacement controls ordered from ProStock will not contain any furnace shared data on the mem­ory card or in the microprocessor and memory cards cannot be written (or rewritten) in the field.
nnoo mmeemmoorryy ccaarrdd pprreesseenntt
1. If a. Furnace shared data from the
“network” is used. Furnace network shared data is defined as a redundant copy (or copies) of the critical furnace shared data stored at various places and components on the communicating network.
The “network” can be defined as follows:
I. The “network” can be the
furnace control itself if it was programmed at the fac­tory and the memory card has been removed for some reason.
II. The “network” can be a fur-
nace control which has had a valid card previously (either attached or inserted) and removed for some rea­son.
III. The “network” can be a fur-
nace control attached to a communicating condenser and/or thermostat which has copies of the furnace shared data that can be retrieved by the furnace control.
IV. A furnace control sent as a
replacement part will have no furnace shared data either in the microprocessor or on the memory card. The replacement control does not include a valid memory card. The furnace shared data can be added by:
1.Inserting a valid memory card (e.g. the original memory card sent with the original furnace con-
, –
39
Page 40
trol or a valid replacement memory card ordered from ProStock.
or
2.by attaching the furnace con­trol to a communicating net­work (e.g. a condenser and thermostat) which was previ­ously connected to (and operating with) a valid fur­nace control with valid fur­nace shared data.
Regardless, the memory card of a replacement control can­not be programmed or repro­grammed in the field with fur­nace shared data and will always remain blank. In fact, this card does not even con­tain the electronic compo­nents necessary to turn it into a valid memory card.
V. Replacement memory cards
with the appropriate furnace shared data for any given model can be ordered from Pro-Stock. In the event that the original memory card is lost, the original furnace control has been replaced and there is no furnace shared data on the net­work (or the furnace is not part of a communicating network (i.e.: is not connected to a com­municating condenser and ther­mostat)), the replacement memory card must be ordered and installed into the connector at J15 to give the furnace valid furnace shared data. The fur­nace will not operate properly without the correct furnace shared data. When no furnace shared data is present (either at the memory card or on the net­work) a “d1” (NO SHARED DATA) fault code will be dis­played at both the thermostat active fault screen and at the furnace control (I.F.C.) seven­segment displays. Also, the homeowner will be alerted via the communicating thermostat with either a CHECK SYSTEM or CHECK FURNACE error message displayed on the main screen.
If the original memory card is lost, it should be replaced even if there is valid furnace shared data on the network. The valid furnace shared data on the net­work should only be considered as a backup to the memory card.
b. If valid furnace shared data is
available from the network and no memory card is present, a “d4” (MEM CARD INVALID) fault is displayed at the communicating thermostat active fault screen and at the furnace seven-segment dis­plays when in standby mode only (see fault code priority list). The homeowner is not alerted (level 1 fault).
c. If no furnace shared data is pre-
sent on the network and a memo­ry card is either not present or the shared data on the memory card is not valid, a “d1” (NO SHARED DATA) fault is displayed at both the communicating thermostat active fault screen and at the fur­nace seven-segment displays provided a higher priority fault code is not also present (in which case the higher priority fault is displayed) (see fault code priority list). The homeowner is alerted via the communicating thermostat (level 2 fault).
d. If furnace shared data from the
memory card is not valid or is not present and shared data from network can be used, the appro­priate fault (d4, d5, d6, d7 or d8 – see fault codes in this manual) is displayed at the communicating thermostat active fault screen and at the furnace seven-segment dis­plays during standby mode only. The homeowner is not alerted (level 1 fault).
oonnee mmeemmoorryy ccaarrdd pprreesseenntt
2. If (attached to IFC the IFC), furnace shared data from the memory card (if valid) will be used to write (or re-write) the net­work furnace shared data and fur­nace shared data from card will be used. If the data on that card is not valid,:
a. If furnace shared data on the
memory card
I. is corrupt or invalid (“d4” –
MEM CARD INVALID”),
and/or
II. is for another component or
different furnace series (“d5” – CARD-HARD CNFLCT),
and/or
III. does not match the horsepow-
er of the attached motor (“d6”­BLWR HP CNFLCT),
and/or
IV. does not support the motor
manufacturer of the motor pre­sent (“d7” - BLWR MFG CNFLCT),
oorr
inserted in J15 of
and/or
V. is from an older furnace
and is missing critical newer furnace shared data (“d8” - OLD SHARED DATA),
furnace shared data from the network (if valid) is used to control the furnace (see description of “network” under “If
pprreesseenntt
Furnace shared data on the network will not be written or re-written from the mem­ory card. If the furnace shared data on the network is valid, the appropriate fault for the memory card will be displayed at the active fault screen of the communicating thermostat and at the furnace seven­segment displays when in standby mode only (see fault code priority list). The homeowner will not be alerted (level 1 fault).
b. If neither the furnace shared
data on the memory card is valid nor the furnace shared data on the network is valid, the fault code status is elevat­ed. The homeowner is alerted via the communicating thermo­stat (level 2 fault) and the fault code DATA) is displayed at the com­municating thermostat active fault screen and at the furnace seven-segment displays pro­vided a higher priority fault is not also present (in which case the higher priority fault is displayed) (see fault code pri­ority list).
c. If no furnace shared data is
available on either the memory card or the network, the fault code “d1” (NO SHARED DATA) is displayed at the com­municating thermostat active fault screen and at the furnace seven-segment displays pro­vided a higher priority fault is not also present (in which case the higher priority fault is displayed) (see fault code pri­ority list). The homeowner is alerted via the communicating thermostat (level 2 fault). Furnace shared data on the network will not be written or re-written from the memory card.
nnoo mmeemmoorryy ccaarrdd
(item 1 above)).
d1
(NO VALID SHARED
40
Page 41
ttwwoo mmeemmoorryy ccaarrddss pprreesseenntt
3. If (attached to IFC of IFC), the memory card inserted into J15 “wins” and its furnace shared data is used and written to the net­work (if valid) unless:
a. If no furnace shared data is pre-
sent on the memory card inserted in J15, the furnace shared data from the attached memory card is used and the rules for
rryy ccaarrdd pprreesseenntt
above) are used. A fault code is not displayed anywhere unless warranted for the attached memo­ry card per the rules outlined for
aanndd
inserted in J15
(outlined in 2
oonnee mmeemmoo--
oonnee mmeemmoorryy ccaarrdd pprreesseenntt
Furnace shared data is not written to the network unless the furnace shared data on the attached mem­ory card is valid.
b. If furnace shared data on the
memory card inserted in J15 is corrupt (“d4” – MEM CARD INVALID), the furnace shared data from the attached memory card is used and the rules for
rryy ccaarrdd pprreesseenntt
above) are used. A fault code is not displayed anywhere unless warranted for the attached memo­ry card per the rules outlined for
oonnee mmeemmoo--
(outlined in 2
oonnee mmeemmoorryy ccaarrdd pprreesseenntt
Furnace shared data is not written to the network unless the furnace shared data on the attached mem­ory card is valid.
c. If furnace shared data on the
inserted memory card is a motor mismatch (“d6” - BLWR HP CNFLCT), the furnace shared data from the attached memory card is used and the rules for
rryy ccaarrdd pprreesseenntt
above) are used. A fault code is not displayed anywhere unless warranted for the attached memo­ry card per the rules outlined for
oonnee mmeemmoo--
(outlined in 2
oonnee mmeemmoorryy ccaarrdd pprreesseenntt
Furnace shared data is not written to the network unless the furnace shared data on the attached mem­ory card is valid.
.
.
.
d. If furnace shared data on the
inserted memory card does not support the motor manufacturer of the motor present (“d7” - BLWR MFG CNFLCT), the furnace shared data from the attached memory card is used and the rules for
sseenntt
used. A fault code is not dis­played anywhere unless warrant­ed for the attached memory card per the rules outlined for
mmeemmoorryy ccaarrdd pprreesseenntt
shared data is not written to the network unless the furnace shared data on the attached memory card is valid.
e. If furnace shared data on the
inserted memory card is from an older furnace and is missing criti­cal newer furnace shared data (“d8” – OLD SHARED DATA), the furnace shared data from the attached memory card is used and the rules for
ccaarrdd pprreesseenntt
above) are used. A fault code is not displayed anywhere unless warranted for the attached memo­ry card per the rules outlined for
oonnee mmeemmoorryy ccaarrdd pprreesseenntt
Furnace shared data is not writ­ten to the network unless the fur­nace shared data on the attached memory card is valid.
4. Furnace shared data is never written to any memory card (attached or inserted) in the field. There is no way to write to a memory card in the field. If a new memory card is need­ed, it must be ordered from Pro­Stock parts replacements.
oonnee mmeemmoorryy ccaarrdd pprree--
(outlined in 2 above) are
oonnee
. Furnace
oonnee mmeemmoorryy
(outlined in 2
.
REPLACING THE FURNACE CONTROL
In the event that the furnace control must be replaced, the memory card must be broken away (detached) from the original furnace control and retained with the furnace. A plastic tether with a note wrapped around the tether is used to remind the technician not to remove the card from the furnace. The card can be broken away easily by putting pres­sure on the control board at dip­switch bank SW-3 with the left hand and pulling forward on the upper right-hand corner of the card with the furnace control still in place on the control board mounting plate (see Figure 32). The card will break free from the furnace control. Use this card to insert into the memory card connector labeled J15 of the replacement control board. Failure to save and connect the memory card properly to the replacement control may result in no operation or undesired operation of the furnace.
When replacing the furnace control, be sure to match the dipswitch set­tings of the original control on the replacement.
DO NOT CUT THE PLASTIC WIRE TIE USED AS A TETHER TO THE ATTACHED, BREAK-AWAY MEMO­RY CARD. DOING SO WILL DEFEAT THE PURPOSE OF RETAINING THE MEMORY CARD – WHICH COULD LEAD TO A LOSS OF CRITICAL DATA NECES­SARY TO OPERATE THE FUR NACE. THE CARD MUST STAY WITH THE FURNACE – EVEN WHEN THE FURNACE CONTROL (IFC) MUST BE REPLACED.
NEVER USE A CONTROL BOARD TAKEN FROM ANOTHER FUR­NACE AS A REPLACEMENT CON TROL FOR THIS FURNACE. FURNACE CONTROLS TAKEN FROM OTHER FURNACES MAY CONTAMINATE THE NETWORK WITH THE WRONG SHARED DATA WHICH CAN ONLY BE FIXED BY REPLACING THE MEMORY CARD WITH THE ORIGINAL MEMORY CARD FROM YOUR FURNACE OR A REPLACEMENT MEMORY CARD DESIGNED FOR YOUR FURNACE.
-
-
41
Page 42
FIGURE 32
REMOVE THE MEMORY CARD WHEN REPLACING THE FURNACE CONTROL. THIS PHOTO SHOWS THE CORRECT WAY TO REMOVE THE MEMO­RY CARD. DO NOT CUT THE TETHER.
For communicatinig systems as a final confirmation of the correct shared data the model number should be verified by checking the furnace user menu under the sub menu titled “Unit Info.” Make sure that the model number displayed in the menu matches the model number on the rating label. (NOTE: Wild cards will be shown in parenthesis. Example: RGFLE/F)-06(E/N)MCKS.)
42
Page 43
FIGURE 33
ON A REPLACEMENT FURNACE CONTROL THE ORIGINAL MEMORY CARD FROM THE ORIGINAL FURNACE CONTROL SHOULD BE INSERTED INTO CONNECTOR J11 OF THE REPLACEMENT CONTROL. DOING THIS WILL GIVE THE REPLACEMENT CONTROL ITS IDENTITY. NOTE THAT THERE WILL BE TWO MEMORY CARDS – THE ORIGINAL (INSERTED INTO J11) AND THE REPLACEMENT (STILL ATTACHED TO THE REPLACE­MENT FURNACE CONTROL).
TETHER S ECURING ORIGINAL MEMORY C ARD TO F URNACE – DO
NOT CUT THIS TETHER OR REMOVE THE ORIGINAL MEMORY CARD FROM THE FURNACE WHEN REPLACING THE FURNACE CONTROL (I.F.C.)
43
Page 44
DIPSWITCHES
TIMED HEAT STAGING
NORMAL NO STAGING
TIMED STAGING
*
(-)GPE-05(-)BMKR (-)GPE-07(-)BRQR (-)GPE-10(-)BRMR (-)GLE-05(-)BMKR (-)GLE-07(-)BRQR (-)GLE-10(-)BRMR (-)GPE-07(-)AMKR (-)GPE-12(-)ARMR (-)GLE-07(-)AMKR (-)GLE-12(-)ARMR
1200 CFM 1600 CFM 2000 CFM
1000 CFM 1400 CFM 1600 CFM
800 CFM 1200 CFM 1400 CFM
600 CFM 1000 CFM 1200 CFM
NNOOTTEE:: does not recognize switch setting changes while energized.
The integrated furnace control
SW1
SW1-1 AND SW1-2 – COOLING AIR­FLOW SELECT – These dipswitches
are used to select the appropriate cool­ing airflow based on the amount required. The switch settings do not affect cooling airflow when installed with a fully communicating condenser. In that case, the condenser supplies the information for cooling airflow which is preset at the factory and not adjustable.
FIGURE 34
DIPSWITCH BANK SW1
For non-communicating systems or communicating systems with a non­communicating condenser (see section titled SPECIAL CONFIGURATION –
COMMUNICATING THERMOSTAT AND FURNACE WITH A NON-COM­MUNICATING CONDENSER of this
document), the target cooling airflow will be determined by the adjustments of SW1-1 and SW1-2. Furnaces with ½ HP motors will have a maximum tar­get airflow setting of 1200 CFM. Furnace with 1 HP motors will have a maximum target airflow setting of 2000 CFM. The airflow achieved may be less than the target if the static pres­sure across the furnace is over 0.6” wc. Consult the cooling equipment instruc­tions and documents for target airflow and adjust accordingly.
Cooling airflow for non-communicat­ing systems can be adjusted approximately +/- 10% by using the cool trim adjustment dipswitches; SW1-5 and SW1-6. See Figure 34.
Cooling airflow for non-communicat­ing systems is also affected by the settings of dipswitch position SW2-6. This switch will determine the appro­priate amount of airflow to be used for the low stage (1
st
stage) of cool­ing. See the tables in Figure 35. More information can be found in the section titled SW2 (SW2-6).
Consult the tables in Figures 34, 35 and 36 for target airflow settings and adjustments based on the positions of the dipswitches SW1-1, SW1-2, SW1-5, SW1-6 and SW2-6.
44
Page 45
FIGURE 35
ON OFF OFF 1200 CFM 600 CFM 1200 CFM 3 Ton A/C ON OFF ON 1000 CFM 500 CFM 1000 CFM 2.5 Ton ON ON OFF 800 CFM 400 CFM 800 CFM 2 Ton A/C
ON ON ON 600 CFM 300 CFM 600 CFM OFF OFF OFF 1200 CFM 900 CFM 1200 CFM 3 Ton A/C OFF OFF ON 1000 CFM 750 CFM 1000 CFM 2.5 Ton OFF ON OFF 800 CFM 600 CFM 800 CFM 2 Ton A/C OFF ON ON 600 CFM 450 CFM 600 CFM
FURNACE COOLING AIRFLOW RATES, GPE-05, GPE-07(-)A, GLE-05 & GLE-07(-)A (1200 CFM Max) motor settings
(applies only to systems configured with non-communicating condenser).
SW1, Pos. 2 SW1, Pos. 1
Y2 Single
stage
Y1 Low 2
stage
Y1+Y2 High 2
stage
Notes
Low Airflow = approx. 50% of High-Stage Cooling (Could be used with condensers with two
compressors.)
HIGH SEER (16+) Premium
Cooling airflow (SW2, Position 4 is
OFF)
SW2, Pos. 4
ON OFF OFF
2000 CFM 1000 CFM 2000 CFM 5 Ton A/C
ON OFF ON
1600 CFM 800 CFM 1600 CFM 4 Ton A/C
ON ON OFF
1400 CFM 700 CFM 1400 CFM 3.5 Ton
ON ON ON
1200 CFM 600 CFM 1200 CFM 3 Ton
OFF OFF OFF
2000 CFM 1400 CFM 1800 CFM 5 Ton A/C
OFF OFF ON
1600 CFM 1200 CFM 1600 CFM 4 Ton A/C
OFF ON OFF
1275 CFM 1050 CFM 1400 CFM
3.5 Ton
OFF ON ON
1200 CFM 900 CFM 1200 CFM 3 Ton
Low Airflow = approx. 50% of
High-Stage (Could be
used with condensers with two
compressors.)
HIGH SEER (16+) Premium
Cooling airflow (SW2, Position 4 is
OFF)
SW2, Pos. 4
FURNACE COOLING AIRFLOW RATES, GPE-10, GPE-12, GLE-10 & GLE-12 (2000 CFM Max) motor settings
(applies only to systems configured with non-communicating condenser).
SW1, Pos. 2 SW1, Pos. 1
Y2 Single
stage
Y1 Low 2
stage
Y1+Y2 High 2
stage
Notes
ON OFF OFF 1200 CFM 600 CFM 1200 CFM 3 Ton A/C ON OFF ON 1000 CFM 500 CFM 1000 CFM 2.5 Ton ON ON OFF 800 CFM 400 CFM 800 CFM 2 Ton A/C
ON ON ON 600 CFM 300 CFM 600 CFM OFF OFF OFF 1200 CFM 900 CFM 1200 CFM 3 Ton A/C OFF OFF ON 1000 CFM 750 CFM 1000 CFM 2.5 Ton OFF ON OFF 800 CFM 600 CFM 800 CFM 2 Ton A/C OFF ON ON 600 CFM 450 CFM 600 CFM
FURNACE COOLING AIRFLOW RATES, GPE-05, GPE-07(-)A, GLE-05 & GLE-07(-)A (1200 CFM Max) motor settings
(applies only to systems configured with non-communicating condenser).
SW1, Pos. 2 SW1, Pos. 1
Y2 Single
stage
Y1 Low 2
stage
Y1+Y2 High 2
stage
Notes
Low Airflow = approx. 50% of High-Stage Cooling (Could be used with condensers with two
compressors.)
HIGH SEER (16+) Premium
Cooling airflow (SW2, Position 4 is
OFF)
SW2, Pos. 4
SW2, Pos. 4 SW1, Pos. 2 SW1, Pos. 1
Y2 Single
Stage
Y1 Low 2
Stage
Y1+Y2 High 2
Stage
ON OFF OFF 1600 CFM 800 CFM 1600 CFM 4 Ton A/C ON OFF ON 1400 CFM 700 CFM 1400 CFM 3.5 Ton A/C ON ON OFF 1200 CFM 600 CFM 1200 CFM 3 Ton A/C
ON ON ON 1000 CFM 500 CFM 1000 CFM 2.5 Ton A/C OFF OFF OFF 1600 CFM 1200 CFM 1600 CFM 4 Ton A/C OFF OFF ON 1400 CFM 1050 CFM 1400 CFM 3.5 Ton A/C OFFONOFF 1200 CFM 900 CFM 1200 CFM 3 Ton A/C OFF ON ON 1000 CFM 750 CFM 1000 CFM 2.5 Ton A/C
FURNACE COOLING AIRFLOW RATES, GPE-07(-)B & GLE-07(-)B (1600 CFM MAX) motor settings
Notes
Low Airflow = approx. 50% of Hi
g
h-Sta
ge
(
Could be used with condensers with tw
o
compressors).
HIGH SEER (16+) Premium Cooling
airflow (SW2, Position 4 is OFF)
(applies only to systems configured with non-communicating condenser)
COOLING AIRFLOW SELECTIONS FOR NON-COMMUNICATING CONDENSERS
SW1-3 TIMED HEAT STAGING – This
switch permits the user to select between no timed staging (i.e. a two stage thermostat is connected) or timed staging with a single-stage thermostat. With the selection “ON,” the furnace will stage up to 100% heat after 12 minutes with a heat call on W1 only. This means that a 1-stage thermostat can be used to simulate 2-stage heating operation.
SW1-4 FAN SPEED SELECT – This dipswitch is used to select the continu­ous fan speed when the furnace is con­figured with a non-communicating ther­mostat.
“OFF”
1
2 HP MOTORS = Approx. 600 CFM
3
4 HP MOTORS = Approx. 800 CFM 1 HP MOTORS = Approx. 1000 CFM “ON”
1
2 HP MOTORS = Approx. 1200 CFM
3
4 HP MOTORS = Approx. 1600 CFM 1 HP MOTORS = Approx. 2000 CFM
SW1-5 AND SW1-6 – COOLING AND HEAT-PUMP AIRFLOW ADJUSTMENT – These dipswitches
are used to adjust the cooling and heat-pump airflow for non-communi­cating systems slightly based on the user’s preference.
SW1-5 = “OFF”, SW1-6 = “OFF” – No adjustment.
SW1-5 = “ON”, SW1-6 = “OFF” – +10% adjustment.
SW1-5 = “OFF”, SW1-6 = “ON” –
-10% adjustment. SW1-5 = “ON”, SW1-6 = “ON” –
No adjustment.
45
Page 46
FIGURE 36
BLOWER OFF DELAY
OFF/OFF
HIGH HEAT = 80 SEC.
LOW HEAT = 110 SEC.
LOW COOL = 0 SEC.
HIGH COOL = 30 SEC.
ON/OFF
HIGH HEAT = 60 SEC.
LOW HEAT = 80 SEC.
LOW COOL = 0 SEC.
HIGH COOL = 0 SEC.
OFF/ON
HIGH HEAT = 120 SEC.
LOW HEAT = 150 SEC.
LOW COOL = 0 SEC.
HIGH COOL = 20 SEC.
ON/ON HIGH HEAT - 180 SEC. LOW HEAT = 180 SEC.
HIGH COOL = 0 SEC.
LOW COOL = 150 SEC.
USE GUIDE: A, B, C, D WILL INDICATE HEATING BLOWER OFF DELAYS IN “SETUP” USER MENU.
A
B
C
A
D
DIPSWITCH BANK SW2 TEST MODE SELECT
ST-A1117-02
SSwwiittcchh ((SSWW22--11)) CCaallll VVoollttaaggee aatt HHUUMM AAccttiioonn ON COOL 24 Normal Cool (c or C)
ON COOL 0 Dehum Cool (cd or Cd) ON Heat 24 Hum Contacts Closed. ON Heat 0 Hum Contacts Open. OFF COOL 24 Normal Cool (c or C) OFF COOL 0 Normal Cool (c or C) OFF Heat 24 Hum Contacts Closed. OFF Heat 0 Hum Contacts Open.
SW2
SW2-1 = ODD “ON” or “OFF” select. This switch will ignore the input from the 24 volt terminal labeled “HUM STAT” during cooling when in the “OFF” posi­tion. However, the “HUM STAT” input is always read in the heating mode to turn on and off the humidifier relay.
When in the “ON” position, the dehumid­ification feature will become active and it will be necessary to install a humidistat to the “HUM STAT” terminal as dis­cussed and shown in wiring diagrams in the section of this manual titled “
HUMIDIFICATION AND DEHUMIDIFI-
CATION
” of this document. Failure to install a humidistat to the “HUM STAT” terminal with dipswitch SW2-1 in the “ON” position will cause the cooling speed airflow to be reduced to the dehumidification speed..
46
SW2-2 and SW2-3 – BLOWER OFF DELAYS
Blower off delays in both heating and cooling are set with these two dip­switches. The selections are as follows (SW2-2/SW2-3):
OFF/OFF(default) = high heat = 80, low heat = 110 sec., Low Cool = 0 sec, High Cool - 30 sec.
ON/OFF = high heat = 60, low heat = 80 sec., Low Cool = 0 sec., High Cool = 0 sec.
ON/ON = highheat = 180, low heat = 180 sec., Low Cool = 0 sec., High Cool = 50 sec.
FURNACE OPERATION USING NON-COMMUNI­CATING SINGLE-STAGE, AND TWO-STAGE THER­MOSTATS (CONSULT THE SECTION OF THIS DOCUMENT TITLED NON-COMMUNICATING THERMOSTATS FOR WIRING DIAGRAMS)
The furnace is capable of operating with a single-stage or a two-stage thermostat as well as the modulating thermostat or fully communicating thermostat specified for use with the furnace. Fully communicating ther­mostat functions and operations are explained in detail in the sections of this manual titled COMMUNICAT-
ING SYSTEMS and THER­MOSTATS (under the sub-section titled COMMUNICATING THER­MOSTATS).
Based on the dipswitch settings of SW1-3, the furnace will operate with either single-stage or two-stage ther­mostats.
See the section of this document titled THERMOSTATS (under the sub-section titled NON-COMMUNI- CATING THERMOSTATS) for infor­mation on how to wire the ther­mostats for each of the configura­tions below.
Page 47
In non-communicating systems, the
Low
Adjustment
Mid-Rise
1st Hi
Adjustment
2nd Hi
Adjustment
Low
Adjustment
Mid-Rise
1st Hi
Adjustment
2nd Hi
Adjustment
B- SW3-1,2 =
ON/OFF
A- SW3-1,2 =
OFF/OFF
C- SW3-1,2 =
OFF/ON
D- SW3-1,2 =
ON/ON
B- SW3-1,2 =
ON/OFF
A- SW3-1,2 =
OFF/OFF
C- SW3-1,2 =
OFF/ON
D- SW3-1,2 =
ON/ON
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
Approx.
Temp Rise
(-)GPE-05(-)BMKR 20°-50°F
27°F 35°F 43°F 45°F
25°-55°F
32°F 40°F 48°F 55°F
(-)GPE-07(-)AMKR 20°-50°F
27°F 35°F 43°F 50°F
30°-60°F
37°F 45°F 53°F 56°F
(-)GPE-07(-)BRQR 20°-50°F
27°F 35°F 43°F 50°F
25°-55°F
32°F 40°F 48°F 55°F
(-)GPE-10(-)BRMR 25°-55°F
32°F 40°F 48°F 55°F
30°-60°F
37°F 45°F 53°F 60°F
(-)GPE-12(-)ARMR 30°-60°F
37°F 45°F 53°F 60°F
35°-65°F
42°F 50°F 58°F 65°F
(-)GLE-07(-)AMK
R
20°-50°F 30°F 35°F 45°F 50°F 30°-60°F 37°F 45°F 53°F 60°F
(-)GLE-07(-)BRQ
R
20°-50°F 27°F 35°F 43°F 50°F 25°-55°F 32°F 40°F 48°F 55°F
(-)GLE-10(-)BRM
R
25°-55°F 32°F 40°F 48°F 55°F 30°-60°F 37°F 45°F 53°F 60°F
(-)GLE-12(-)ARM
R
30°-60°F 37°F 45°F 53°F 60°F 35°-65°F 42°F 50°F 58°F 58°F
UPFLOWDOWNFLW
High Fire
Model
Low Fire
Published
Low Temp
Rise Range
Published High Temp Rise Range
heating cycle is always initiated by a 24 volt signal on W1. When the controller senses 24 volts on W1, the following sequence occurs:
TWO-STAGE FUNCTION SW1-3 = OFF:
After the blower on-delay period, the fur­nace will respond to the thermostat demand by adjusting the gas valve pressure and blower heating speeds to the “W” signal values. “W1” only = low gas valve pressure and blower heating speed. “W2” = high gas valve pressure and blower heating speed.
SINGLE-STAGE FUNCTION (“W” sig­nal only) :
(Single-stage function only applies when switch SW1 is on and a single-stage thermostat is installed as shown in Figure 48.)
After the blower on-delay period, the fur­nace will respond to the thermostat demand by altering the gas valve pres­sure and blower speed as follows:
PPhhaassee 11::
0 to 7 minutes = Low of fur­nace capacity (gas valve output and blower speed)
PPhhaassee 22:: nace ca
After 7 minutes = 100% of fur-
pacity (gas valve output and
blower speed)
NNOOTTEE:: any ph
If the call for heat ends during
ase, the furnace will terminate immediately at the firing rate of that phase.
SSWW22--44 leave dip
- For most cooling operation, switch SW2-4 in the “OFF”
position. This will enable the furnace operation with most two-stage, non­communicating cooling equipment. Actual SEER values will vary and depend on the equipment combination. Consult the specifications sheets and installation instructions of the cooling equipment purchased for a listing of the SEER ratings for a specific combina­tion.
Placing SW2-4 in the “ON” position will establish the low (Y1) cooling airflow at ½ of the max cool (Y2) airflow. This setting will be useful with cooling sys­tems where two compressors are used to control two cooling stages (one com­pressor for first stage and two com­pressors for second stage).
SW3-1 and SW3-2
HEATING AIRFLOW ADJUSTMENTS The furnace is shipped from the factory
with low and high fire heating airflows. These are set from the factory to let the furnace operate at the mid-point of the temperature rise range. The tempera­ture may vary slightly due to furnace input and voltage variations.
The airflow can be slightly adjusted to the homeowner’s taste. This is done with dipswitches SW3-1 and SW3-2 of the furnace control board. There is one adjustment below nom­inal (heat rise is less than nominal – air is warmer). Some models do not have all three adjustments. Figure 37 shows the approximate heat rise based on the adjustments of dip­switch SW3-1 and SW3-2.
WARNING
!
IT IS THE INSTALLER’S RESPON­SIBILITY TO VERIFY THAT THE TEMPERATURE RISE DOES NOT EXCEED THE PUBLISHED RISE RANGE OF THE FURNACE. THE RISE RANGE MUST ALWAYS BE CHECKED AT BOTH
LOW AND HIGH FIRE BEFORE LEAVING THE JOBSITE. IF THE TEMPERA­TURE IS OUTSIDE THE SPECI­FIED RANGE, AN ADJUSTMENT TO THESE DIPSWITCHES MUST BE MADE TO CORRECT THE HEAT RISE.
FIGURE 37
HEAT RISE ADJUST – DIPSWITCHES SW3-1 AND SW3-2
47
Page 48
SW4
FIGURE 38
DIPSWITCH BANK SW4 TERMINATION AND BIAS SELECTIONS
ST-A1117-04
BIAS / TERMINATION
These dipswitches will not be used for first generation controls. They are designed to be used for future genera­tions of ClimateTalk which may support multiple networks. llaattiioonnss,, aallll tthhrreeee ooff tthhee ddiippsswwiittcchheess iinn bbaannkk SSWW44 mmuusstt bbee iinn tthhee OONN ppoossii-- ttiioonn.. IIff nnoott,, tthhee ssyysstteemm mmaayy nnoott bbee aabbllee ttoo ccoommmmuunniiccaattee..
FFoorr ccuurrrreenntt iinnssttaall
--
DUAL SEVEN-SEGMENT DIAGNOSTIC DISPLAY
The dual seven-segment diagnostic dis­play will either display the status of the system (e.g. “H” for Heat) or a diagnos­tic error code in the event of an active fault. Fault and status codes and their meanings can be determined from Table
16. For detailed information for each fault code refer to the TROU­BLESHOOTING section of this manual. For communicating systems, the fault code and a description can be found in the thermostat “Active Fault” display area. (See the section of this document titled “ACTIVE FAULT DISPLAY” under COMMUNICATING SYSTEMS for more information).
The rightmost decimal on the display will blink one time for every 100 CFM of expected airflow whenever the blower is operating. If the value is actually less than 50 CFM above any increment of 100, the value will be rounded to the lesser 100 value and the lesser value will be displayed. For example, if the actual CFM is 1049, the decimal will blink ten times. If the actual CFM value is 1051, the decimal will blink eleven times. For better resolution, a service tool or communicating thermostat is required and the expected CFM can be determined within a resolution of 10 CFM. (See the section of this manual titled “USER MENUS” under “STATUS 1” or “STATUS 2” submenu “BLOWER CFM”).
FAULT CODE BUFFER
Upon power reset, the last five fault codes from the furnace will be dis­played on the seven-segment display. These will be displayed in chronological order from newest (displayed first) to oldest (displayed last).
For communicating systems, the fault code buffer can also be read at the communicating thermostat inside the furnace User Menus. The most recent six fault codes are stored. Also dis­played is the number of days since each fault code was recorded.
NOTE: The following fault codes will not be stored back-to-back in the fault buffer. These will only be stored in the buffer if the previous fault stored was a different fault. 82, 11, 45, 46 & 57.
CLEARING DIAGNOSTIC FAULT CODES FROM THE BUFFER
To clear the fault codes in the fault buffer, the dipswitch at position SW3-2 can be used. Turn the switch off, on, off, on or quickly within 30 seconds to reset the fault codes. When this is done, the right-most seven-segment dis­play will energize the upper and lower horizontal segments for four seconds as confirmation that the fault codes have been cleared from the buffer. Be sure to return the switch to the original position after clearing the faults.
Faults can also be cleared at the furnace User menu under the Fault Hist selection. The seven-segment displays will again operate as described above.
Either procedure will clear the fault codes in the fault buffer displayed at the dual seven-segment displays on the I.F.C. And at the Fault History user menu on communicating ther­mostats.
on, off, on, off
48
Page 49
TABLE 16
LIST OF FAULT CODES AND NORMAL OPERATION CODES
NOTE: To clear current fault codes in the furnace control buffer, turn dipswitch SW3-3 on, off, on, off,
or off, on, off, on within 30 seconds. The right-most seven-segment display will energize the upper and lower horizontal members for four seconds as confirmation that the faults have been cleared. Be sure to return the dispswitch (SW3-3) to its original position after clearing the faults. The fault buffer can also be cleared at the user menu under “FAULT HIST” in the sub-menu titled “CLEAR FAULT HISTORY”.
Either procedure will clear the fault codes in the buffer displayed at the dual seven-segment displays on the I.F.C. AND
NOTE: The following fault codes will not be stored back-to-back in the fault buffer. These will only be stored in the buffer if the previous fault stored was a different fault. 82, 11, 45, 46 & 57.
at the Fault History user menu on communicating thermostats.
COMMUNICATING SYSTEMS
The modulating furnace is capable of communicating with a thermostat and condenser to improve cooling and heat-pump airflow, displaying active faults and active furnace information at the thermostat and improved diagnostics and trou­bleshooting.
WIRING A FURNACE FOR COM­MUNICATIONS.
Maximum wire lengths and notes about wiring communicating sys­tems are noted below.
MAXIMUM COMMUNICATING WIRE LENGTHS (1, 2, R & C)
Max Wire Length – Thermostat to Furnace = 100 FT @ 18 AWG*
Max Wire Length – Furnace to Condenser = 125 FT @ 18 AWG*
Notes:
1. When using twisted pairs, be
sure the wires connected to pins labeled “1” (recommended wire color = green) and “2” (recom­mended wire color = yellow) are a twisted pair.
2. Wires may be solid or stranded..
3. *Wire gage smaller than 18 AWG
is not approved or recommended for this application.
4. When using existing wire from a
previous installation, be sure to trim the tip of the wire back past the insulation and strip a small amount of insulation from the wire to expose clean new copper for the communicating connec­tions. Fresh copper must be exposed when making the com­municating connections or com­munications may not be properly established.
Figure 39 is the wiring diagram for connecting the furnace to an approved ClimateTalk communicat­ing thermostat and approved Rheem or Ruud communicating condenser.
The only approved configuration is to install dedicated wires directly from the furnace to the thermostat and a separate set of dedicated wires directly from the furnace to the condenser. Note: The only approved configuration requires that four dedicated wires (1, 2, R and C) be installed from the furnace to the condenser.
49
Page 50
FIGURE 39
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
ST-A-1114-01
STARTUP FOR SYSTEMS CON­FIGURED WITH COMMUNICA­TIONS
WARNING
!
INSTALLATION OF LINE VOLTAGE AND GAS MUST BE PERFORMED ACCORDING TO INSTRUCTIONS WRITTEN IN THIS MANUAL. FAIL­URE TO DO SO COULD RESULT IN INJURY OR DEATH.
When the furnace is configured for communications, the components on the network (i.e. furnace, thermostat and condenser) must establish com­munications before engaging a heat (or other) thermostat demand. The procedure for establishing communi­cations is automatic and is described below. Once communica­tions is established, the start-up pro­cedure will be the same as the gen­eral start-up instructions described in the section of this manual titled
SSTTAARRTT--UUPP PPRROOCCEEDDUURREESS
.
Once the communicating wiring is properly installed and the furnace is connected to line voltage, the sys­tem can be turned on. The thermo­stat will display the following text:
“SEARCHING”
is displayed several times for sever­al seconds. Next, the text
“FURNACE FOUND”
and
“AIR CONDITIONER FOUND”
or
“HEAT PUMP FOUND”
(depending on which is installed in the system) will be displayed. The process can take several minutes (up to a maximum of 30) to com­plete. If these messages are not displayed within 30 minutes after energizing the system, communica­tions can not be established. There are many reasons why communica­tions may not be established – including improper settings of the “TERM” and “BIAS” switches (see BIAS / TERMINATION) and improp­er wiring (see WIRING A FURNACE FOR COMMUNICATIONS above).
The order in which these messages will be displayed will depend on which components are energized first. The order listed here assumes that the furnace and condenser are energized at the same time. If not, the order of display will be in the order that the components are turned on.
50
Page 51
When the system has found all neces­sary components, the text area of the communicating thermostat will go blank. This is an indicator that the system is operating properly. Proceed by engag­ing a typical thermostat call to determine if operation is correct as described in the section of this book titled START UP PROCEDURES” to test heating, cooling and fan operation and to make neces­sary adjustments.
NOTE: When a communicating con­denser is installed with the system, a capital “C” will be displayed at the fur­nace seven-segment display for both low & high cooling stages.
CONTINUOUS FAN OPERATION IN
CCOOMMMMUUNNIICCAATTIINNGG MMOODDEE Cont
inuous fan operation will always
depend o
n the selection (Hi, Med, Low) made at the communicating thermostat for the continuous fan speed (see instal­lation instructions for the thermostat). However, during the first few operations of continuous fan, the blower speed will be limited to a maximum of 600 CFM for
1
2 HP motors (75KBTU), 700 CFM for
3
4 HP (75KBTU (wide) and 50 KBTU) and 1000 CFM for 1 HP motors (100KBTU). This will continue until the high cooling call information is provided from the condenser. Once the max cool­ing CFM value has been transmitted by the condenser (condenser must reach high stage – in heat pump or cooling), the continuous fan will then have a max­imum CFM value equal to the max cool­ing airflow from the condenser. The Hi, Med and Low selections for continuous fan will be based on max CFM of the condenser with Hi continuous fan speed equal to the high speed CFM of the cooling/HP condenser.
NOTE: When default values are reset in the furnace “SETUP” user menu, the continuous fan CFM will be restored to factory default (Max = 600 CFM for
1
2 HP, 700 CFM for 3⁄4 HP and 1200 CFM for 1 HP). These values will again be used to calculate continuous fan airflow until a cooling call has been established and a communicating condenser sends a fan demand to the furnace control.
ACTIVE FAULT CODES WITH COM­MUNICATING SYSTEMS
Two levels of fault codes exist: (1) Non­critical and (2) Critical. In general a non-critical fault permits all (or nearly all) operations to proceed and a critical fault prevents all (or nearly all) opera­tions from proceeding. Detailed expla­nations are given for each fault code and how to diagnose and troubleshoot problems by fault code displayed in the “TROUBLSHOOTING” section of this manual.
Active faults of either level will be dis­played at the thermostat in the “ACTIVE FAULT” area of the thermo­stat. To enter the furnace “ACTIVE FAULT” area using a communicating thermostat, see the installation and operation instructions for that thermo­stat.
FURNACE USER MENUS NOTICE:
ALL TEMPERATURE VALUES DISPLAYED IN USER MENUS ARE DISPLAYED IN DEGREES FAHRENHEIT AT ALL TIMES. THIS IS TRUE EVEN IF THE THERMOSTAT IS SELECTED TO CELCIUS (C.). USER MENUS CAN NOT DISPLAY TEMPERA­TURES IN CELCIUS.
Systems configured for communica­tions will have some advantages over traditional control (24VAC ther­mostats) systems. One advantage is that a variety of information that can be useful for configuring the furnace/ system and diagnostic/troubleshoot ­ing information can be displayed at the thermostat.
The bulk of this information can be found inside the user menus. The procedure for entering (and exiting) the user menus will vary depending on the thermostat or service tool that is used. To enter, navigate or exit the furnace “USER MENU”s using a communicating thermostat, see the installation and operation instruc­tions for that thermostat.
Navigating the user menus is straight-forward. The menu follows the logic tree shown in Figure 40 (a & b).
NOTE: There may be a delay of several seconds when accessing he user menus or sub-menus. This is normal.
51
Page 52
FIGURE 40a
HIGH LOW
LO HEAT HIGH HEAT
LO HEAT HRS
LO HEAT CYCLES
HI HEAT HRS
HI HEAT CYCLES
BLOWER HOURS
BLOWER CYCLES
MENU TREE
NOTE: There may be a delay of several seconds when accessing user menus or submenus. This is normal.
The thermostat menus give active infor­mation for various parameters and per­mit some installation options to be selected.
Note: Supply Air (SA) and Return Air (RA) temperature readings may not be accurate in standby mode. These should only be read and used when the blower is running in heat, cool or other modes.
“STATUS 1” menu – This menu gives information about the status of certain furnace components and features.
NEXT PAGE
1. MAIN LIMIT – Indicates the state of the main limit – either opened or closed. The normal state is closed. An open limit can be an indicator of excessive static pressure in the ventilation duct.
2. MRLC INPUT
of the Manual Reset Limit Control (MRLC) – either opened or closed. The normal state is closed. These switches are sometimes referred to as “Roll-Out” controls or limits. When one or more of these limits has opened, a flame has rolled into
– Indicates the state
the vestibule. This event should rarely (if ever) happen but can be an indicator that the exhaust flue is blocked.
3. HALC INPUT
– Indicates the state of the Heat Assisted Limit Control (HALC) – either opened or closed. The normal state is closed. This limit switch is only present on downflow/horizontal models and can often be an indicator that the main blower has stopped turning unexpect­edly when opened.
52
Page 53
FIGURE 40b
1 STG.
OFF
ON
A
B
C
D
BLOWER OFF DELAY
OFF ON
A
B
C
D
HIGH HEAT HRS
LOW HEAT HRS
LOW HEAT CYCLES
HIGH HEAT CYCLES
BLOWER HOURS
TOTAL DAYS PWRD
HEAT ADJ
A B C D
A
B C D
BLOWER OFF DELAY
LOW HIGH
MENU TREE – CONTINUED
NOTE: There may be a delay of several seconds when accessing user menus or submenus. This is normal.
4. IDM OUTPUT
of the Induced Draft Motor (IDM) – OFF, HI or LO. The indication is the state at which the furnace con­trol expects the motor to be. If the indication is HI or LO and the motor is not turning, a number of prob­lems could be the cause – including a non-functioning blower relay on the furnace control or a non func­tioning inducer.
5. FURN LO PR SW
state of the Low Pressure Control (LPC) (also known as low pressure switch) – either OPEN or CLOSED.
– Indicates the state
– Indicates the
6. FURN HI PR SW – Indicates the state of the High Pressure Control (HPC) (also known as high pres­sure switch) – either OPEN or CLOSED.
7. GAS VLV
– Indicates the firing rate of the gas valve. This value can be low or high depending on the ther­mostat demand.
8. GAS VLV RELAY
state of the gas valve relay –either ON or OFF. ON indicates that the main gas valve solenoid is engaged. Any time the indication is
– Indicates the
ON, flame should be present.
9. FLAME
ence of a flame. The possibili­ties are “OFF”, “MARGINAL”, “GOOD” and “UNEXPECTED”. A marginal flame can be an indi­cator that the flame sense rod needs to be cleaned. “UNEX­PECTED” flame is a serious condition and must be dealt with immediately by a professional, licensed HVAC technician.
10. BLOWER CFM
CFM that the furnace control
– Indicates the pres-
– Indicates the
53
Page 54
requests from the blower motor. This value may vary somewhat from the actual values, but it should be very close. The value can also be tracked through the blinking decimal point on the seven segment dis­plays at the furnace control (although with not as much resolu­tion).
“STATUS 2” menu – This menu also gives information about the status of certain furnace components and fea­tures.
11.. MMOODDEE
aa.. MMOODD HHEEAATT bb.. AACC cc.. FFAANN OONNLLYY
dd.. HHPP
2. MO
3. MOTOR RPM
4. MAXIMUM CFM
5. BLOWER CFM
6. TEMP DIFF
a. If the Supply Air Sensor (S.A.S.)
b. If the S.A.S. is not
– Indicates the current state of operation of the furnace. The possibilities are listed below:
t operation
Hea
Air
conditioning operation.
operation.
Heat-pump operation.
TOR MFGR – Indicates the manufacturer of the main air-circu­lating blower motor. At the time of this publication there are two possi­bilities; GenteQ (formerly GE) for Regal Beloit (formerly GE) and EMERSON.
of the main circulating air blower.
maximum CFM that the main circu­lating air blower can deliver.
put of airflow in CFM of the main cir­culating air blower.
ence between the outlet duct and inlet duct air temperatures. This menu item may not be accurate when the Air Circulating Blower (ACB) is not turning.
When the outlet air (supply) temper­ature is greater than the inlet air (return) temperature, the thermostat will display the text “RISE” with the temperature value. Conversely, when the outlet air (supply) temper­ature is less than the inlet air (return) temperature, the thermostat will display the text “DROP” with the temperature value.
This temperature is displayed in degrees F and can not to Celsius units. A few other differ­ent conditions that apply to this menu item are:
turned on (see “SUPPLY
is not AIR SENS” in “SETUP” menu below) and a sensor is not attached (or not sensed), NA will be displayed in the “TEMP DIFF” selection.
“SUPPLY AIR SENS” in “SETUP”
Continuous fan
– Indicates the RPM
– Indicates the
– Indicates the out-
* – Indicates the differ-
be changed
turned on (see
menu below) and a sensor is attached, a valid temperature will be displayed in the “TEMP DIFF” selection.
c. If the S.A.S. is
“SUPPLY AIR SENS” in “SETUP” menu below) and a sensor is perature will be displayed in the “TEMP DIFF” selection.
d. If the S.A.S. is
“SUPPLY AIR SENS” in “SETUP” menu below) and a sensor is not sensed), the text “FLT” (for FauLT) is displayed in the “TEMP DIFF” selection
*ALL TEMPERATURES WITHIN THE USER MENUS CAN BE DIS­PLAYED ONLY IN FAHRENHEIT VALUES
Note: Supply Air (SA) and Return Air (RA) temperature readings may not be accurate in standby mode. These should only be read and used when the blower is running in heat, cool or other modes.
7. RETURN TEMP
temperature of the return air in the return air duct. This menu item may not be accurate when the Air Circulating Blower (ACB) is not turning. This value is sensed at the furnace control (IFC) and not at an external sensor attached to the control. If the temperature can not be sensed for some reason, the text “FLT” will be displayed. This temperature is displayed in degrees F and can not Celsius units
*ALL TEMPERATURES CAN BE DISPLAYED ONLY IN FAHREN­HEIT VALUES
Note: Supply Air (SA) and Return Air (RA) temperature readings may not be accurate in standby mode. These should only be read and used when the blower is running in heat, cool or other modes.
8. SUPPLY TEMP
temperature of the supply air in the supply air duct. This menu item may not be accurate when the Air Circulating Blower (ACB) is not turning. This value is sensed at an external sensor attached to the control. This temperature is dis­played in degrees F and can not changed to Celsius units. A few different conditions that apply to this menu item are:
a. If the Supply Air Sensor (S.A.S.)
turned on (see “SUPPLY
is not AIR SENS” in “SETUP” menu below) and a sensor is not attached (or not sensed), NA will be displayed in the “SUPPLY TEMP” selection.
turned on (see
attached, a valid tem-
turned on (see
attached (or not
* – Indicates the
be changed to
* – Indicates the
b. If the S.A.S. is not turned on
(see “SUPPLY AIR SENS” in “SETUP” menu below) and a sensor is temperature will be displayed in the “SUPPLY TEMP” selec­tion.
c. If the S.A.S. is
“SUPPLY AIR SENS” in “SETUP” menu below) and a sensor is temperature will be displayed in the “SUPPLY TEMP” selec­tion.
d. If the S.A.S. is
“SUPPLY AIR SENS” in “SETUP” menu below) and a sensor is not sensed), the text “FLT” (for FauLT) is displayed in the “SUPPLY TEMP” selection.
*ALL TEMPERATURES CAN BE DISPLAYED ONLY IN FAHRENHEIT VALUES
Note: Supply Air (SA) and Return Air (RA) temperature readings may not be accurate in standby mode. These should only be read and used when the blower is running in heat, cool or other modes.
9. HUM OUTPUT
the humidifier output is turned on.
“2 WK HIST” menu – This menu gives information about the number of cycles and the amount of time spent in various modes of operation over the last 14 days.
NOTE: For both 2 WK & LIFE HIST, the value saved prior to power loss may not include information from the last hour of operation. This is because the information is only stored once every hour.
1. LO HT HRS
number of hours of operation of low gas heat in the last 14 days.
22.. LLOO HHTT CCYYCCLLSS number of cycles of operation of low gas heat in the last 14 days.
33.. HHII HHTT HHRRSS ber of hours of operation of high gas heat in the last 14 days.
44.. HHII HHTT CCYYCCLLSS number of cycles of operation of
be
high gas heat in the last 14 days.
55.. BBLLOOWWEERR HHRRSS number of hours of continuous fan operation in the last 14 days.
66.. BBLLOOWWEERR CCYYCCLLSS the number of cycles of opera­tion (i.e.: the number of times it turned on and off) of the contin­uous fan operation in the last 14 days.
attached, a valid
attached, a valid
attached (or not
– Indicates when
– Indicates the
– Indicates the
– Indicates the num-
– Indicates the
– Indicates the
turned on (see
turned on (see
– Indicates
54
Page 55
LLIIFFEE HHIISSTT
“ information about the number of cycles and the amount of time spent in various modes of operation over the life of the furnace.
NOTE: For both 2 WK & LIFE HIST., the value saved prior to power loss may not include information from the last hour of operation. This is because the informa­tion is only stored once every hour.
11.. TTOOTTAALL DDAAYYSS PPWWRRDD the total number of days that the furnace has been powered. This number is not affected by any ther­mostat operation.
22.. LLOO HHTT HHRRSS of hours of operation of low gas heat over the life of the furnace.
33.. LLOO HHTT CCYYCCLLSS ber of cycles of operation of low gas heat over the life of the furnace.
44.. HHII HHTT HHRRSS of hours of operation of high gas heat over the life of the furnace.
55.. HHII HHTT CCYYCCLLSS ber of cycles of operation of high gas heat over the life of the furnace.
66.. BBLLOOWWEERR HHRRSS number of hours of continuous fan operation over the life of the fur­nace.
77.. BBLLOOWWEERR CCYYCCLLSS number of cycles of operation (i.e.: the number of times it turned on and off) of the continuous fan operation over the life of the furnace.
FFAAUULLTT HHIISSTTOORRYY
“ gives information recent faults experienced by the fur­nace. The most recent fault is dis­played upon entering the menu. Three seconds later the text “DAYS“ is dis­played followed by a number. The num­ber indicates the number of days since that fault was experienced.
The faults can be viewed in order of occurrence. Pressing the down arrow key once will permit viewing of the next most recent fault. Pressing the key again will display the second most recent fault and so on.
If no fault present in the memory, the text “NO FAULT” and “DAYS 0” will be displayed. It is possible that there will be less than six faults stored (if less than six faults have occurred since installation or clearing of faults). In this case, the existing faults will be dis­played in the order of occurrence and the remaining faults will be displayed as “NO FAULT” and “DAYS 0”.
The final item in this menu is “CLEAR FAULTS”. The options are “yES” and “no”. This item permits the faults to be cleared so all six positions will display “NO FAULT” and “DAYS 0”.
menu – This menu gives
– Indicates
– Indicates the number
– Indicates the num-
– Indicates the number
– Indicates the num-
– Indicates the
– Indicates the
menu – This menu
about the six most
When faults are cleared, the right seven segment display on the furnace control will flash the upper and lower horizontal bars once.
Note that the “FAULT HISTORY” only accumulates days when power is applied to the furnace control board. For example, if a fault actually occurred ten days ago and the furnace was not powered for two of the ten days, the fault will be displayed with the text “DAYS 8” instead of “DAYS 10” is dis­played to indicate the number of days since the fault occurred.
UUNNIITT IINNFFOO
“ information
11.. MMOODDEELL NNUUMMBBEERR ((MMNN))
22.. SSEERRIIAALL NNUUMMBBEERR ((SSNN))
33.. SSOOFFTTWWAARREE VVEERRSS.. SSEETTUUPP
“ the field adjustment of certain parame­ters of the furnace. The selected values will be saved in memory even when power is lost and restored. The proce­dure for making changes in the furnace setup menu will vary depending on the thermostat or service tool that is used. To enter, navigate, make changes to or exit the furnace “SETUP” menu using a communicating thermostat, see the installation and operation instructions for that thermostat.
11.. HHEEAATT AADDJJ
22.. BBLLOOWWEERR OOFFFF DDEELLAAYY
33.. SSUUPPPPLLYY AAIIRR SSEENNSS
” menu – This menu permits
the adjustment of the heat airflow. Operation of this selection is exact­ly as with the dipswitches at SW3 at the furnace control. The heat rise can be changed by increasing or decreasing the airflow slightly. Adjustments are A, B, C & D as shown in Figures 37 & 40.
The default factory setting for the low heat adjustment is “A”.
selection permits the adjustment of the heating blower off delay in com­municating mode. The selections are A, B, C and D. The actual tim­ings for the blower off delay are described in Figure 36 as selec­tions A-D of dipswitches SW2-2 and SW2-3.
The default factory setting for the blower off delay is “A”.
tion permits the disabling and enabling of the supply air sensor input. In many cases, it may not be possible to install this sensor. When this is the case, the selection can be changed to “OFF”. Selecting “on” or “OFF” will affect how the “TEMP RISE” (TEMPerature RISE) and “SUPPLY TEMP” values are displayed in the “STATUS 2” menu. See the
– This menu gives
” menu
about the furnace.
- This selection permits
- This
– This selec-
descriptions for these items in the “STATUS 2” menu descrip­tions above for more informa­tion.
Note that turning this selection to “OFF” will prevent the “82” fault code (SA SENSOR FLT) from being displayed on power­up (or at any other time) and from logging in the fault buffer.
The default factory setting for the supply air sensor input is “on”.
NNOOTTEE:: OPERATION, THE SUPPLY AIR SENSOR MUST BE INSTALLED AND THE SELEC­TION FOR THIS SENSOR SET TO “ON” IN THE “SETUP” USER MENU UNDER THE SELECTION “SUPPLY AIR SENS” FOR DUAL-FUEL OPERATION. FAILURE TO INSTALL THE SENSOR AND TO TURN IT ON IN THE USER MENUS COULD CAUSE EXCESSIVE TRIPPING OF THE PRESSURE LIMIT CON­TROLS ON THE AC SYSTEM.
55.. FFIIXXEEDD FFIIRREE RRAATTEE ture will temporarily fix the gas heating fire rate to the selection desired. The selected rate will be applied to the present heat call only. If there is no heat call already present when the selec­tion is attempted, the system will not permit the firing rate to be fixed at the user menu. The fir­ing rate and blower will be fixed at the selected rate for the dura­tion of the existinig heat call or a maximum of two hours (whichever comes first). This feature should only be used for installation, diagnostic, adjust­ment and troubleshooting pur­poses by an experienced licensed technician. Selectable firing rates are low and high.
6. RESET ALL DFLTS
selection restores all items in the “SETUP” menu to the facto­ry default selections. If “yES” is selected, all settings in this menu will be lost.
NOTE: When faults are cleared in the furnace “SETUP” user menu, the continuous fan CFM will also be restored to the facto­ry default setting. (See Continuous Fan Operation in Communicating Mode.)
BELOW USER MENU IS USED FOR NON-COMMUNICATING SYS­TEMS ONLY
“DIPSWITCH” menu – This menu
permits viewing of the dipswitch selections. It is a way to read the
FOR DUAL-FUEL
– This fea-
– This
55
Page 56
dipswitch selections without the need of translating the settings manually.
Note: The “DIPSWITCH” menus will not be displayed at the thermostat. They are invisible to the thermostat and can not be displayed. These menus can only be viewed with the field service tool. The reason is that dipswitch selec­tions do not generally affect operation of the furnace when using the communi­cating mode of operation.
NOTE: The integrated furnace control does not recognize switch setting changes while energized. To change settings, remove power to the board by turning off the disconnect or switch to the furnace control or removing power at the breaker, make changes, then return power.
11.. CCOOOOLL AAIIRRFFLLOOWW value of the cooling airflow selected. See the section of this manual titled “DIPSWITCH” under “SW1” (SW1-1 and SW1-2) for details and selec­tions.
22.. TTIIMMEEDD SSTTAAGGIINNGG FFEEAATTUURREE OFF – 2 Stage Operation ON – Timed Staging W/1 Stage Thermostat
33.. HHEEAATT AADDJJ selected at SW3, positions 1 and 2. It is the adjustment of the high heat rate airflow. See the section of this manual titled “DIPSWITCH” under “SW3” for details and selections.
44.. FFAANN SSPPDD SSEELLEECCTT fan speed selected. See the section of this manual titled “DIPSWITCH” under “SW1” (SW1-4) for details and selections.
– Displays the
– Displays the value
– Displays the
55.. AACC--HHPP AADDJJ or heat-pump airflow slightly to change or adjust the temperature rise slightly. See the section of this manual titled “DIPSWITCH” under “SW1” (SW1-5 and SW1-6) for details and selections.
66.. OONN DDEEMMAANNDD DDEEHHUUMM the dehumidification feature on or off. See the section of this manual titled “DIPSWITCH” under “SW2” (SW2-1) for details and selections.
77.. AACC HHPP SSTTGG MMUULLTT for adjustment to the airflow for low-stage of cooling and heat-pump operation. See the section of this manual titled “DIPSWITCH” under “SW2” (SW2-4) for details and selections.
DUAL-FUEL OPERATION IN COMMU­NICATING MODE
Systems configured for dual-fuel opera­tion will include a communicating con­denser with a reversing valve. Dual­fuel systems will display “ Pump heat operation at the furnace control’s (I.F.C.) dual seven-segment displays. During defrost mode, “ be displayed. All other codes apply.
The balance point can be adjusted at the thermostat for optimal operation. The balance point is the point below which gas heat will be used and above which heat-pump heat will be used.
– Adjusts the cooling
– Toggles
– This allows
HP
” for Heat-
dF
” will
For dual-fuel systems, to protect equipment, the supply air sensor must be installed. When the supply air sensor is properly installed and the system is in defrost mode, the gas heat will only operate when the outlet air is below 110°F. When the outlet air exceeds 110°F, the gas valve is turned off and the Air Circulating Blower (ACB) continues to run. When the supply air tempera­ture reaches 95°F, the gas heat will again be turned on. This cycle will continue until the call for defrost has ended.
NOTE:
TION, THE SUPPLY AIR SENSOR MUST BE INSTALLED AND THE SELECTION FOR THIS SENSOR SET TO “ON” IN THE “SETUP” USER MENU UNDER THE SELEC­TION “SUPPLY AIR SENS” FOR DUAL-FUEL OPERATION. FAIL­URE TO INSTALL THE SENSOR AND TO TURN IT ON IN THE USER MENUS COULD CAUSE EXCESSIVE TRIPPING OF THE PRESSURE LIMIT CONTROLS ON THE AC SYSTEM.
FOR DUAL-FUEL OPERA-
56
Page 57
START-UP PROCEDURES
IGNITOR PLACEMENT, ALIGNMENT & LOCATION
Ignition failure may be a result of improper ignitor alignment caused dur­ing a service call or other work done to the furnace in the field. When perform­ing any work on the burner, heat exchanger, etc., the technician must check alignment of the spark ignitor. Misalignment of the ignitor could cause a failure to light or rough ignition. The correct ignitor alignment is shown in Figure 41.
TO START THE FURNACE
DIRECT SPARK IGNITION LIGHTING INSTRUCTIONS
This appliance is equipped with a direct­spark ignition device. This device lights the main burners each time the room thermostat calls for heat. See the lighting instructions on the furnace.
During initial start-up, it is not unusual for odor or smoke to come out of any room registers. To ensure proper ventilation, it is recommended to open windows and doors, before initial firing.
The furnace has a negative pressure switch that is a safety during a call for heat. The induced draft blower must pull a negative pressure on the heat exchanger to close the negative pressure switch. The induced draft blower must maintain at least the negative pressure switch set point for the furnace to oper­ate. If the induced draft blower fails to close or maintain the closing of the nega­tive pressure switch, a “no heat call” would result.
FIGURE 41
OPTIMUM IGNITOR LOCATION
1. Remove the burner compartment control access door.
2. IMPORTANT: Be sure that the man- ual gas control has been in the “OFF” position for at least five min­utes. Do not attempt to manually light the main burners.
3. Set the room thermostat to its low­est setting and turn off the furnace electrical power.
4. Turn the gas control knob to the “ON” position.
5. Replace the burner compartment control access door.
WARNING
!
FAILURE TO REPLACE THE BURNER DOOR CAN CAUSE PRODUCTS OF COMBUSTION TO BE RELEASED INTO THE CONDI­TIONED AREA RESULTING IN PERSONAL INJURY OR DEATH.
6. Turn on the manual gas stop.
7. Turn on the furnace electrical power.
8. Turn thermostat to “Heat” mode and set the room thermostat at least 10°F above room temperature to light the main burners.
9. After the burners are lit, set the room thermostat to a desired tem­perature.
TO SHUT DOWN THE FURNACE
1. Set the room thermostat to its lowest setting and turn to “OFF” position.
2. Turn off the manual gas stop and turn off the electrical power to the furnace.
3. Remove the burner compartment control access door.
4. Shut off the gas to the main burners by turning the gas con­trol knob to the “OFF” position.
5. Replace the burner compartment control access door.
WARNING
!
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, CLOSE THE MANUAL GAS VALVE FOR THE APPLIANCE BEFORE SHUTTING OFF THE ELECTRICAL SUPPLY. FAIL­URE TO DO SO CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SEQUENCE OF OPERATION
Heating Cycle Initiation
The heating cycle is always initiated by a 24 volt signal on W of the ther­mostat or, for communicating sys­tems, a message is transmitted from the thermostat to the IFC. When the controller senses 24 volts on W or the communicated message for heat call, the following sequence occurs:
• High and low pressure switches are checked to insure contacts are open.
• Inducer is powered on high speed for a thirty (30) second prepurge.
• Pressure switches are monitored as the inducer creates the vacuum to close the contacts.
57
Page 58
TABLE 17
NORMAL OPERATION CODES
58
Page 59
• The controller sends a spark signal to spark across the electrodes.
• The main solenoid on the gas valve are energized (low fire) allowing gas to flow to the burners.
• When flame is proven, the ignition control is de-energized - 8 second maximum trial time.
• The gas valve maintains low rate through the warm-up period - 20 sec­onds (aka Blower Off Delay).
Heating Cycle Response
TWO-STAGE FUNCTION – NON-
COMMUNICATING SYSTEMS ONLY:
(Two-stage function only applies when SW1-3 is in the “OFF” position and a two-stage thermostat is installed as shown in Figure 49.)
After the warm-up period, the furnace will respond to the thermostat demand by adjusting the gas valve and blower heating speeds to the “W” signal val­ues. “W” only = low gas valve pressure and blower heating speed. “W2” = high gas valve pressure and blower heating speed if the call for heat ends, the fur­nace terminates at the present rate.
SINGLE-STAGE FUNCTION – NON-
COMMUNICATING SYSTEMS ONLY:
(SW2-2 and SW2-3 must both be turned “off” for this operation.)
(“W” signal only) After the warm-up period, the furnace will respond to the thermostat demand by altering the gas valve pressure and blower speed as follows:
Phase 1: 0 to 7 minutes = Low fire fur­nace capacity (gas valve output and blower speed)
Phase 2: After 7 minutes = 100% of fur­nace capacity (gas valve output and blower speed)
NOTE: If the call for heat ends during any phase, the furnace will terminate immediately at the firing rate of that phase.
Heating Cycle Termination
(“W” signal only, refer to dip switch set SW2 on IFC)
When the 24 volt signal is removed from W1 or, for communicatiing systems, a message is transmitted from the thermo­stat to the furnace to “end the heat call”, the heating cycle will end and the fur­nace will shut down and return to the proper off cycle operation.
ADJUSTING OR CHECKING FURNACE INPUT
NATURAL GAS:
The maximum gas supply pressure to the furnace should be 10.5” W.C. for natural gas. The minimum gas supply pressure for purposes of input adjust­ment to the furnace should be 5” W.C.
A properly calibrated manometer or gauge is required for accurate gas pres­sure readings.
1. When adjusting the furnace input, the high fire input should be checked. The high fire manifold pressure should be 3.5' W.C. Follow these steps to be sure the furnace is high fire mode:
a. With a single stage thermostat, the
furnace runs for 12 minutes on low fire before shifting to high fire. To be certain that it is on high fire, jump terminals “W” and “W2” on the control board in the blower compartment.
b. With a two stage thermostat, set
the thermostat to its highest setting to keep the furnace operating in the high fire mode.
2. To adust high fire manifold pressure, remove the adjustment cover screw on the outlet end of the gas valve and turn the adjustment screw clock­wise to increase the pressure and counterclockwise to reduce the pres­sure. Replace the cover screw securely.
3. The low fire manifold pressure should be 1.7" W.C. As mentioned above, the furnace remains in the low fire mode for 12 minutes upon a heat call with a single stage thermostat. With a two stage thermostat, disconnect the thermostat lead to the “W2” terminal on the control board and the furnace will remain in the low fire mode. To adjust the pressure, remove the regu­lator cover, on top of the valve, and adjust as noted under Step 2, above. After the adjustment replace the screw cover securely.
TABLE 18
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS
INPUT
BTU/HR
50,000
75,000
100,000
125,000
150,000
Input BTU/HR =
METER
CU. FT.
SIZE
ONE 15112 1 15 1 18 3 20 TEN 10 50 12 00 12 30 13 12 30 00
ONE 0 44 0 48 0 50 0 53 20 TEN 7 12 80819 8 48 20 0
ONE 0 33 0 36 0 38 0 40 1 30 TEN 5 24 60615 6 36 15 0
ONE 0 26 0 29 0 30 0 32 1 12 TEN 4 19 4 48 50517 12 0
ONE 0 31 0 24 0 25 0 26 10 TEN 3 36 40410 4 20 10 0
Heating Value of Gas (BTU/Ft3) x 3600 x correction factor Time in Seconds (for 1 cu.ft.) of Gas
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
NOTE: Use a 3/32allen wrench for
making the pressure adjustment.
LP GAS:
Furnaces for use on LP gas, the LP gas supply pressure must be set between 11.0” and 13.0” W.C. by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas control valve. For eleva­tions up to 7,000 feet, rating plate input ratings apply. For high altitudes (elevations 7,000 and over) and for any necessary major changes in the gas flow rate the orifice spud must be changed.
TO CHANGE ORIFICE SPUDS:
1. Shut off the manual main gas valve and remove the gas mani­fold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for leaks.
5. Check for proper operation and set to proper manifold pressure.
Check of input is important to pre­vent over firing of the furnace beyond its design-rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE.
TO CHECK FURNACE INPUT:
1. Make certain that all other gas appliances are shut off, with the exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the time required to burn one cubic foot of gas.
4. Use Table 4 to determine input rate.
59
Page 60
MAINTENANCE
!
WARNING
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING ANY MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
FILTERS
Filter application and placement are critical to airflow, which may affect the heating and cooling system perfor­mance. Reduced airflow can shorten the life of the systems major compo­nents, such as motor, limits, elements, heat exchanger, evaporator coil or com­pressor. Consequently, we recommend that the return air duct system have only one filter location. The most com­mon location will be inside the furnace or a filter base. For systems with a return air filter grill or multiple filter grills, can have a filter installed at each of the return air openings. DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM. DO NOT FILTER THE SUPPLY AIR DUCT SYSTEM.
If high efficiency filters or electronic air cleaners are used in the system, it is important that the airflow is not reduced to maximize system performance and life. Always verify that the systems air­flow is not impaired by the filtering sys-
TABLE 19 FILTER SIZES
UPFLOW FILTER SIZES AS SHIPPED
FURNACE INPUT BOTTOM SIDE
WIDTH BTUH SIZE SIZE
1
17
/2" 50, 75 153/4" X 25" 153/4" X 25" 1
21" 75, 100 19
1
/2" 125 223/4" X 25" 153/4" X 25" 1
24
1
/4" X 25" 153/4" X 25" 1
tem that has been installed, by perform­ing a temperature rise and temperature drop test.
Keep the air filters clean at all times. Vacuum dirt from filter, wash with deter­gent and water, air dry thoroughly and reinstall.
See Table 19 and Figures 42 through 44 for proper filter sizes and locations.
1. 21”-100,000 BTUH unit requires removal of 3
1
/2” segment of filter and frame to get proper width for a side filter.
1
/2”-125,000 BTUH units require
2. 24 removal of 7” segment of filter and frame to get proper width for a side filter.
QUANTITY
*NOTE: Some filters must be ordered or resized to fit certain units and applications.
IMPORTANT: Do not operate the system without filters. A portion of the dust entrained in the air may temporarily lodge in the air duct runs and at the supply registers. Any cir­culated dust particles will be heated and charred by contact with the fur­nace heat exchanger. This sooty residue will soil ceilings, walls, drapes, carpets, and other house­hold articles. Soot damage may also result when certain types of candles are burned, or candlewicks are left untrimmed.
FIGURE 42
FILTER RETAINING ROD
FILTER ROD 45-24095-01
60
Page 61
FIGURE 43
UPFLOW FILTER RETAINING ROD (SIDE RETURN)
CUT-OUT AND DRILL DETAIL
FILTER ROD SUPPORT ANGLE AE-60520-01
FILTER SUPPORT ANGLE AE-61883-01
FILTER AND ROD ASSEMBLY
FILTER ROD 45-24095-01
SOLID BOTTOM MAY BE ORDERED FROM THE FACTORY.
FIGURE 44
DOWNFLOW FILTER INSTALLATION
FILTER ROD SUPPORT ANGLE AE-60520-01
FILTER SUPPORT ANGLE (SEE ANGLE DETAIL) AE-61883-01
ROD & FILTER SUPPORT ANGLE ASSEMBLY
*BOTH SIDES FOR 1800 CFM OR ABOVE.
61
Page 62
SYSTEM OPERATION INFORMATION
Advise The Customer To:
1. Advise customer of filter location. Keep the air filters clean. The heating system will operate better, more effi­ciently and more economically.
2. Arrange the furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
3. Close doors and windows. This will reduce the heating load on the sys­tem.
4. Avoid excessive use of kitchen & bathroom exhaust fans.
5. Do not permit the heat generated by television, lamps or radios to influ­ence the thermostat operation.
6 Except for the mounting platform,
keep all combustible articles three feet from the furnace and vent sys­tem.
7. IMPORTANT: Replace all blower
doors and compartment covers after servicing the furnace. Do not operate the unit without all panels and doors securely in place.
!
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET OR WITHIN THE SPECIFIED CLEARANCES OF THE VENT PIPE. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COM­BUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMA­BLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE FURNACE OWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PUR­POSES.
ANNUAL INSPECTION
The furnace should operate for many years without excessive scale build-up in the flue passageways, however, it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the vent system and the main burners for continued safe operation paying par­ticular attention to deterioration from corrosion or other sources.
!
WARNING
HOLES IN THE VENT PIPE OR HEAT EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH. THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK.
• IMPORTANT: It is recommended that
at the beginning of the heating sea­son and approximately midway in the heating season a visual inspection be made of the main burner flames for the desired flame appearance by a qualified installer, service agency, or the gas supplier.
• IMPORTANT: It is also recommend­ed that at the beginning of the heat­ing season, the flame sensor be cleaned with steel wool by a qualified installer, service agency, or the gas supplier.
IMPORTANT: It is recommended that an annual inspection and cleaning of all furnace markings be made to assure legibility. Attach a replace­ment marking, which can be obtained through the distributor, if any are found to be illegible or miss­ing.
IMPORTANT: FOR Nox MODELS – At the beginning of the heating season a visual inspection of the Nox device should be made to ensure they have not become obstructed by insects nests or anything else which may effect per­formance.
LUBRICATION
The indoor blower motor and induced draft motor are prelubricat­ed by the motor manufacturer and do not require further attention.
The motors must be cleaned period­ically by a qualified installer, service agency, or the gas supplier to pre­vent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. Air filters should be kept clean. Dirty filters can restrict airflow and results in motor overheating.
REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas, remove the NOx insert assemblies.
TROUBLESHOOTING
Refer to Figure 45.
WIRING DIAGRAM
Figure 46 is a complete wiring dia­gram for the furnace.
62
Page 63
FIGURE 45
2-STAGE COMMUNICATING INTEGRATED
FURNACE CONTROL (IFC)
TROUBLESHOOTING GUIDE
ECM = Constant CFM Blowers. (Electronically commutated motor) TSTAT = Thermostat. IDM = Induced Draft Motor (or Inducer). IFC = Integrated Furnace Control (or control board). PS = Pressure Switch(es). PFC = Power Factor Correction Choke. SE = Spark Electrode (s). SSD = Seven Segment Display of Furnace control COMM. = Communication. I&O = Installation & Operation Instructions Manual.
1) For communicating systems, go to the “setup” menu and set fixed fire rate to high. For legacy systems ensure W2 & W1 are properly connected and make sure both are energized w/ 240ac after the heat call is palced.
2) Set FAN switch to “AUTO” on T-stat.
3) Set thermostat to call for heat (set temp. differential to greater than 10°F).
4) “H” should be displayed at “SSD’s” and should be on steady, if flashing check dip switches (Item “1”).
For Non-Comm. Systems.
“A capital H is displayed at IFC SSD’S” ?
Dual SSD’S “ON” ?
Is thermostat heat call present? For 24 VAC (Non-Comm. T-stat., is 24 VAC on W1 and/or W2 of IFC. H or h should be displayed at SSD’S. ?
Is a fault code displayed at IFC?
(After 10 Sec. a fault code will display anyway)
H or h only
For 1st 10 Sec. only
FAULT
Under ”Troubleshooting”
in I & O Manual
Check W2 & connections,
replace or repair as
necessary
Check t-stat, replace if
necessary.
(pre-purge) IDM runs for 30 sec. at low speed?
Does IDM Run for 60 Sec. and then off
for five minutes with fault
45, 46 or 57 displayed?
- See FAULT CODES under “Troubleshooting” in I&O Manual.
ECM BLOWER “ON” DELAY
J16-4
J16-5 on IFC.
NOTE: If IFC goes into lockout (”r” will be displayed at SSD’s), shut off main power to unit, wait 30 seconds then reset power or removed heat call and re-establish.
- Check all connections between I.F.C. & E.C.M. Motor.
- Check 24v to E.C.M. control (4pin connector, pin 1-4)
- Check Dip switch setting.
- Check P.F.C. choke.
- Check all wiring and connections to P.F.C choke.
- Check fault code display, see “fault codes” in I & O.
- Check line voltage to motor (115VAC).
Does ECM blower start on high heat
speed 15-20 seconds after burners light?
Note: IFC SSD’s will display “22, 33 or 23”.
?
Note: If good flame is not sensed a fault code “11” or “13” will be displayed at SSD’s Note: “12” is low flame sense, furnace should still operate well.
Fault code
“45”, “46” or
“57” displayed
at SSD’s.
- Check test mode dip switches.
- Make sure test mode has not expired (1 hour limit).
CHECK :
- Fault codes at IFC SSD - see FAULT CODES under troubleshooting in I&O manual.
- 24V Between IFC pins J16, Pin 4 & J16, Pin 5 of I.F.C.
- Make sure heat call present at T-stat.
- T-stat wires and connections
Remove heat call by setting T-stat set point below room temperature. For communicating t-stats, go to “setup” menu and set fixed fire rate to low. For legacy systems, ensure low heat call w/ 24vac on W1and 0 VAC on W2. Initiate new heat call. Allow heat call to proceed through blower on delay. The burners drop from high fire to low rate and I.B.M. energizes at low heat CFM.
Be sure to note dip switch settings before troubleshooting.
For Comm. System
Lower case “h”
Capital “H”
-Check line voltage at I.D.M.
-Check Wires And connections between I.D.M. and I.F.C.
-Ensure line voltage between J2, Pin 1 & J2, Pin 4 of I.F.C. (High IN Output).
-Check I.D.M. Capacitor.
Spark Electrodes (SE) Energize?
See I&O.
Does gas valve remain
energized?
PROBLEM PERSISTS
CHECK : AIRFLOW - ensure no restrictions, such as dirty filter, blower wheel, dampers
or closed registers, Etc. exist. LIMITS - ensure good wire and connections between I.F.C. and all limits. makes sure limits are not open when circulating air temperature is within a specific range. ROLLOUTS - Ensure rollouts or overtemperature limits do not need to be reset. make sure no flame rollout in burner compartment due to blocked flue or heat exchanger or combustion restriction. OVERFIRE - ensure furnace is not overfired (temp rise is above stated range). Check gas valve, proper orifice size, gas presure
CHECK :
-Grounding on I.F.C. in place and continuity between screw and field
-installed ground.
-Flame sense rod clean (clean if nessessary).
-Wire continunity between flame sense rod and J1, Pin1 on I.F.C.
-Flame carries across all burners, and all burners stay lit.
G0 T0
I
Does the IDM Start on Low Speed?
TROUBLESHOOTING CHART
63
Page 64
SSD = Seven Segment Display of Furnace control COMM. = Communication. I&O = Installation & Operation Instructions Manual.
2) Set FAN switch to AUTO on T-stat.
3) Set thermostat to call for heat (set temp. differential to greater than 10°F).
4) H should be displayed at SSDs and should be on steady, if flashing check dip switches (Item 1).
For Non-Comm. Systems.
A capital H is displayed at IFC SSDS ?
Dual SSDS ON ?
92-22744-24-00
Is thermostat heat call present? For 24 VAC (Non-Comm. T-stat., is 24 VAC on W1 and/or W2 of IFC. H or h should be displayed at SSDS. ?
Is a fault code displayed at IFC?
(After 10 Sec. a fault code will display anyway)
H or h only
For 1st 10 Sec. only
FAULT
Under Troubleshooting
in I & O Manual
Check W2 & connections,
replace or repair as
necessary
Check t-stat, replace if
necessary.
(pre-purge) IDM runs for 30 sec. at low speed?
Does IDM Run for 60 Sec. and then off
for five minutes with fault
45, 46 or 57 displayed?
- See FAULT CODES under Troubleshooting in I&O Manual.
ECM BLOWER ON DELAY
J16-4
J16-5 on IFC.
NOTE: If IFC goes into lockout (r will be displayed at SSDs), shut off main power to unit, wait 30 seconds then reset power or removed heat call and re-establish.
- Check all connections between I.F.C. & E.C.M. Motor.
- Check 24v to E.C.M. control (4pin connector, pin 1-4)
- Check Dip switch setting.
- Check P.F.C. choke.
- Check all wiring and connections to P.F.C choke.
- Check fault code display, see fault codes in I & O.
- Check line voltage to motor (115VAC).
Does ECM blower start on high heat
speed 15-20 seconds after burners light?
Note: IFC SSDs will display 22, 33 or 23.
?
Note: If good flame is not sensed a fault code 11 or 13 will be displayed at SSDs Note: 12 is low flame sense, furnace should still operate well.
Fault code
45, 46 or
57 displayed
at SSDs.
- Check test mode dip switches.
- Make sure test mode has not expired (1 hour limit).
CHECK :
- Fault codes at IFC SSD - see FAULT CODES under troubleshooting in I&O manual.
- 24V Between IFC pins J16, Pin 4 & J16, Pin 5 of I.F.C.
- Make sure heat call present at T-stat.
- T-stat wires and connections
Remove heat call by setting T-stat set point below room temperature. For communicating t-stats, go to setup menu and set fixed fire rate to low. For legacy systems, ensure low heat call w/ 24vac on W1and 0 VAC on W2. Initiate new heat call. Allow heat call to proceed through blower on delay. The burners drop from high fire to low rate and I.B.M. energizes at low heat CFM.
Check to make sure test mode dip switches are properly set.
- Check all connections between IFC and ECM motor.
- Check 24V to ECM Motor. (low voltage connector, pins 1 & 4)
- Check P.F.C. Choke.
- Check all wiring and connections to P.F.C. choke.
- Check fault code display and see “fault codes” In I & O.
Does I. B. M. energize at low speed?
After Blower on delay, Does IDM switch to low speed and remain at low speed after switching?
Does furnace continue to operate at low fire until T-stat satisfied or heat call removed?
Ensure T-stat not switching to high fire or test mode not timing out (1 hour limit)
Fault code displayed?
See FAULT CODES under
troubelshooting in the I & O Manual
Does IDM Shut off after post purge?
Does I. B. M. shut off after 90 seconds? (plus slew)
Double check - is heat call
completely off at IFC?
** System will attempt to light 4 times. Voltage Is present at gas valve for only 7 seconds during each ignition trial. System will enter a 1 hour lockout after 4 attempts.
For Comm. System
Lower case h
Capital H
-Check line voltage at I.D.M.
-Check Wires And connections between I.D.M. and I.F.C.
-Ensure line voltage between J2, Pin 1 & J2, Pin 4 of I.F.C. (High IN Output).
-Check I.D.M. Capacitor.
Spark Electrodes (SE) Energize?
See I&O.
Does gas valve remain
energized?
PROBLEM PERSISTS
CHECK : AIRFLOW - ensure no restrictions, such as dirty filter, blower wheel, dampers
or closed registers, Etc. exist. LIMITS - ensure good wire and connections between I.F.C. and all limits. makes sure limits are not open when circulating air temperature is within a specific range. ROLLOUTS - Ensure rollouts or overtemperature limits do not need to be reset. make sure no flame rollout in burner compartment due to blocked flue or heat exchanger or combustion restriction. OVERFIRE - ensure furnace is not overfired (temp rise is above stated range). Check gas valve, proper orifice size, gas presure
CHECK :
-Grounding on I.F.C. in place and continuity between screw and field
-installed ground.
-Flame sense rod clean (clean if nessessary).
-Wire continunity between flame sense rod and J1, Pin1 on I.F.C.
-Flame carries across all burners, and all burners stay lit.
Remove heat call by setting T-stat below room temp.
Remove power to furnace, open blower compartment and restore dip switches to original settings. Replace blower door. Restore power to unit.
- Check wire and all connections between I.F.C.J2 and I.D.M
- Check for 115 VAC on P2.
- Check I.D.M. capacitor.
- Check I.D.M. low speed. Replace if neccessary.
C
G0 T0
I
Does the IDM Start on Low Speed?
PROBLEM PERSISTS
REPEAT THIS SEQUENCE UNTIL TROUBLE- FREE OPERATION
FIGURE 45
TROUBLESHOOTING CHART – CONTINUED
64
Page 65
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS
NOTE:The text in the “DISPLAYED TEXT” box shows combinations of upper-case and lower-case letters. Upper-case letters are used in the message displayed at the thermostat active fault screen. For example, the text CARD-HARDware CoNFLiCT NOTE:The following fault codes will not be stored back-to-back in the fault buffer. These will only be stored in the buffer if the previous fault stored was a different fault. 82, 11, 45, 46 & 57. NOTE:To clear current fault codes in the furnace control buffer, turn dipswitch SW3-2 on, off, on, off, or off, on, off, on within 30 seconds. The right-most seven-segment display will ener-
gize the upper and lower horizontal members for four seconds as confirmation that the faults have been cleared. Be sure to return the dispswitch (SW3-3) to its original position after clear­ing the faults. The fault buffer can also be cleared at the user menu under “FAULT HISTORY” in the sub-menu titled “CLEAR FAULT HISTORY”. Either procedure will clear the fault codes in the buffer displayed at the dual seven-segment displays on the I.F.C. AND NOTE: The following fault codes will not be stored back-to-back in the fault buffer. These will only be stored in the buffer if the previous fault stored was a different fault. 82, 11, 45, 46 & 57.
indicates that the message displayed at the thermostat active fault screen will be CARD-HARD CNFLCT.
at the Fault History user menu on communicating thermostats.
FAULT CODES
65
Page 66
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
66
Page 67
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
67
Page 68
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
68
Page 69
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
69
Page 70
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
70
Page 71
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
71
Page 72
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
72
Page 73
TABLE 20
when the inducer is energized at high speed.
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
73
Page 74
TABLE 20
when the inducer is energized at low
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
74
Page 75
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
75
Page 76
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
76
Page 77
TABLE 20
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
77
Page 78
TABLE 20
The sensor is faulty. Check the resistance at different temperatures if possible. If resistance is more than a few hundred ohms out of range, replace sensor. @60°F (16°C), resistance = Approx. 15,400Ω @70°F (23°C), resistance = Approx. 10,700Ω @110°F (43°C), resistance = Approx. 4600Ω @150°F (66°C), resistance = Approx. 2000Ω
FURNACE FAULT CODES EXPANDED W/DESCRIPTIONS AND SOLUTIONS – CONTINUED
78
Page 79
FIGURE 46
WIRE DIAGRAM
79
Page 80
THERMOSTATS
NON-COMMUNICATING THERMOSTATS
THERMOSTAT WIRING
NOTE: Do not use 24 volt control wire smaller than No. 18 AWG.
Wire all non-communicating ther­mostats to the 24V connections on the integrated furnace control. See Figures 48 and 49.
NOTE: A larger wire gage may be be required for longer lengths of thermo­stat wire.
For proper installation of the Variable Output Thermostat, follow the “Thermostat Installation, Programming and Troubleshooting Manual” included as section II of this manual. For proper installation of a Single-Stage or Two­Stage Thermostat, see the Installation Instructions included with the thermo­stat.
SEQUENCE OF OPERATION
See the section of this book titled “Electrical Wiring - Thermostat” for a wiring diagram showing how to connect a thermostat.
SINGLE-STAGE HEAT THERMOSTAT NOTE: Single-stage heat operation is
determined by the position of dipswitch­es SW1-3 options are: 7 minutes between 1
For single-stage operation, “W” from the thermostat must be connected to “W” on the furnace control.
a. Connect the “W” terminal on the ther-
mostat to the “W” terminal on the control board.
b. When there is a call for heat, the “R”
and “W” contacts close and the IFC runs a self check routine to verify that the pressure switch contacts are open. The limit switch contacts are constantly monitored.
c. The induced draft motor starts on
high until the low pressure switch contacts close (a maximum of 60 seconds), and then changes to low speed. After a 30 second pre-purge, the spark ignitor energizes and the low fire gas valve opens, lighting the burners.
d. After the gas valve opens, the
remote flame sensor must prove igni­tion for one second using the process of flame rectification. If the burners do not light, the system goes through another ignition sequence. It does this up to 4 times. (2 tries on low fire and 2 tries on high fire.)
st
and 2ndstage, or OFF.
FIGURE 47
24-VOLT TERMINALS
e. The main blower starts on low heat
speed 30 seconds after the flame is sensed. The furnace operates on low fire for 5 or 12 minutes and then, if the thermostat is not satisfied, shifts to high fire, causing the draft inducer to go to high speed, the gas valve to shift to 100% and the main blower goes to high heat speed.
f. When the thermostat cycle ends, the
gas valve closes, and the burners go out.
g. The draft inducer will continue running
for a 10 second (low speed) or 5 sec­ond (high speed) post purge.
h. The main blower runs for 50-140
seconds on high heat speed or 80­170 seconds on low heat speed (this timing is field adjustable). See Figure 22 for switch settings.
Sequence if the system doesn’t light or doesn’t sense flame
a. If flame is not sensed within 8 sec-
onds after the gas valve opens, the valve closes and the ignitor is de­energized. The induced draft motor will run for 60 seconds on low, and then begins another heat cycle.
b. The ignition process goes through
one more try on low fire. If this fails, there are two attempts on high fire with a 30 second interpurge between trials. During high fire ignition
attempts, the inducer steps to high speed, the high pressure switch closes (both pressure switches are now closed), and the gas valve steps to high fire.
c. If there is no ignition after the 2nd
trial on high fire, the furnace goes into soft lockout for one hour.
d. The sequence repeats after a one
hour delay and continues repeat­ing until ignition is successful or the call for heat is terminated.
e. To reset the lockout, break power
either at the thermostat or at the unit disconnect switch for 5 to 10 seconds. The furnace then goes through another set of trials for ignition (provided call for heat is still present).
f. If flame is established and main-
tained during the trial for ignition period and flame is lost, the gas valve is de-energized, the draft inducer continues to run, and con­trol begins timing the inter-purge delay. The indoor blower motor will be energized and/or remain ener­gized on low speed for low fire and heat speed for high fire for the selected delay off time.
When the inter-purge delay is over, the control initiates another igni­tion trial period. The control will recycle up to 5 flame losses (4 re­cycles) within a single call for heat before going into lockout.
TWO STAGE HEAT THERMOSTAT
Connect “W1” and “W2” terminals on the thermostat to “W” and “W2” termi­nals on the control board.
See the section of this book titled “Electrical Wiring - Thermostat” for a wiring diagram showing how to con­nect a thermostat.
Call for 1st stage heat
a. The “R” and “W” thermostat con-
tacts close and the control module runs a self-check routine. After the control module verifies that both sets of pressure switch contacts are open, the induced draft motor starts on high until the low pres­sure switch contacts close (a maxi­mum of 60 seconds), then changes to low speed.
b. After a 30 second pre-purge the
spark igniter energizes and the low fire gas valve opens, lighting the burners.
80
Page 81
c. After the burners light, the remote
flame sensor must prove ignition. If the burners do not light, the system goes through another ignition sequence. It does this up to 4 times (2 attempts on low fire and 2 tries on high fire).
d. The main blower starts on low-heat
speed 30 seconds after the flame is proven. The furnace continues to run on low fire until the call for heat is sat­isfied or the 2nd stage contacts close. If the 1st stage call for heat is satis­fied the gas valve closes and the induced draft motor continues running for a 10 second post purge time. the main blower runs for its blower off delay (this timing is field adjustable). See Figure 36 for switch settings (SW2-3 & SW2-3).
Call for 2nd stage heat after 1st stage
The “R” and “W2” thermostat contacts close, calling for 2 stage heat. The induced draft motor switches to high speed and the high pressure switch con­tacts close. The gas valve switches to high fire and the main blower switches to high heat speed.
2nd stage heat satisfied, 1st stage heat still required
The “R” and “W2” thermostat contacts open. The induced draft motor switches to low speed, the main blower motor switches to low heat speed and the gas valve changes to low fire. The furnace continues to run in this mode until the 1st stage heat call is satisfied. The sys­tem will shut down as noted in “d,” under 1st stage call for heat.
NOTE: Under extreme cold conditions, the 2-stage thermostat may call for the furnace to cycle between 1st and 2nd stage operation.
81
Page 82
* NO MECHANICAL THERMOSTATS. **** 2 STAGE COOLING ONLY.
YH (Y2)
Y (Y
2)
Y
L (Y1)
YL (Y1)
****
****
Y Y
2
2-STAGE ELECTRONIC THERMOSTAT*
(NON-COMMUNICATING)
2 STAGE
GAS
FURNACE
FIGURE 48
* NO MECHANICAL THERMOSTATS. *** 2 STG. COOLING ONLY.
YL (Y1)
***
YL (Y1)
Y (Y2)
***
Y
H (Y2)
Y Y2
1-STAGE ELECTRONIC THERMOSTAT*
(NON-COMMUNICATING)
2 STAGE
GAS
FURNACE
CONTROL
WIRING DIAGRAM FOR SINGLE-STAGE HEAT (NON-COMMUNICATING)
* NO MECHANICAL THERMOSTATS. *** 2 STG. COOLING ONLY.
FIGURE 49
WIRING DIAGRAM FROM TWO-STAGE HEAT (NON-COMMUNICATING)
82
Page 83
FIGURE 50
WIRING DIAGRAM – SPECIAL CONFIGURATION: COMMUNICATING THERMOSTAT AND FURNACE WITH NON-COMMUNICATING CONDENSER
83
Page 84
COMMUNICATING THERMOSTATS
COMMUNICATING THER­MOSTATS
The furnace is capable of communicat­ing with a thermostat and condenser to improve cooling and heat-pump airflow, displaying active faults and active fur­nace information at the thermostat and improved diagnostics and troubleshoot­ing.
WIRING A FURNACE FOR COM­MUNICATIONS
MAXIMUM COMMUNICATING WIRE LENGTHS (1, 2, R & C)
Max Wire Length – Thermostat to Furnace =
Max Wi Condenser =
Notes:
When using twisted pairs, be sure the
1. wires connected to pins labeled “1” (recommended wire color = green) and “2” (recommended wire color = yellow) are a twisted pair.
2. Wires may be solid or stranded.
3. *Wire gage smaller than 18 AWG is not approved or recommended for this application.
4. When using existing wire from a pre­vious installation, be sure to trim the tip of the wire back past the insulation and strip a small amount of insulation from the wire to expose clean new copper for the communicating con­nections. Fresh copper must be exposed when making the communi­cating connections or communications may not be properly established.
Figures 51 through 52 are wiring dia­grams for connecting the furnace to an approved ClimateTalk communicating thermostat and approved Rheem or Ruud communicating condenser.
The only approved configuration for fully communicating systems is to install dedicated wires directly from the fur­nace to the thermostat and a separate set of dedicated wires directly from the furnace to the condenser. Note: The only approved configuration for systems with a communicating condenser requires that four dedicated wires (1, 2, R and C) be installed from the furnace to the condenser.
110000 FFTT
re Length – Furnace to
112255 FFTT
@ 18 AWG*
@ 18 AWG*
However, after a two-hour period, this will change and the thermostat will take as long as five minutes for every degree F to change the dis­play. Therefore, for example a rapid change of five degrees in room tem­perature will not be correctly indicat­ed at the thermostat for (up to) 25 minutes. This is done to buffer the thermostat against rapid and insignif­icant swings in temperature caused by briefly opening a door or window. This operation prevents excessive cycling of the thermostat and is a feature used in all modern ther­mostats.
FIGURE 51
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
2. For dual-fuel systems, once the thermostat has switched over to auxiliary heat (e.g. gas heat), sub­sequent heat calls may also immediately begin with auxiliary heat regardless of the dual-fuel changeover point and the actual outdoor temperature or the differ­ence between room temperatures and setpoint. This is true as long as the subsequent heat call is within 12 minutes or less of end of the previous heat call. The actual time between heat calls that will cause this operation varies but should not exceed 12 minutes.
TWO NOTES ABOUT COMMUNI­CATING THERMOSTATS
1. When power to the thermostat has been reset and/or the batteries are replaced, the thermostat will respond quickly to changes in room tempera­ture as indicated by the room tem­perature displayed at the thermostat.
84
A-1114-01
Page 85
SPECIAL CONFIGURATION – COMMUNICATING THERMOSTAT AND FURNACE WITH A NON­COMMUNICATING CONDENSER
YY11 aanndd YY22 used to connect directly to a non-com­municating condenser when a commu­nicating thermostat is installed to the furnace but a non-communicating con­denser is installed in the system. While the optimum configuration is with a communicating condenser connected to the network, there may be installations where this is not desired. In these cases, the thermostat will be communi­cating with the furnace control and the furnace control will energize the con­denser as necessary (the additional relays have been added to the furnace control to allow this operation).
The thermostat connections labeled “Y1” and “Y2” on the I.F.C. are normally inputs to the furnace control to turn on the blower when they are energized. However, in this configuration, these (normally) inputs become outputs to energize the condenser when a cooling call has been sent from the communi­cating thermostat.
When this configuration is desired, use the wiring diagram in Figure 52 to con-
– These terminals may be
nect the thermostat and condenser to the furnace control.
For single stage condensers, a jumper must be installed between Y1 & Y2 at the furnace control.
NOTE: A heat pump condenser cannot be installed with this configuration. There is no control for the reversing valve.
STARTUP FOR SYSTEMS CONFIG­URED WITH COMMUNICATIONS
WARNING
!
INSTALLATION OF LINE VOLTAGE AND GAS MUST BE PERFORMED ACCORDING TO INSTRUCTIONS WRITTEN IN THIS MANUAL. FAIL­URE TO DO SO COULD RESULT IN INJURY OR DEATH.
When the furnace is configured for communications, the components on the network (i.e. furnace, thermostat and condenser) must establish commu­nications before engaging a heat (or other) thermostat demand. The proce­dure for establishing communications is automatic and is described below. Once communications is established, the start-up procedure will be the same as the general start-up instructions described in the section of this manual titled START-UP PROCEDURES.
Once the communicating wiring is properly installed and the furnace is connected to line voltage, the sys­tem can be turned on. The thermo­stat will display the following text:
SEARCHING
is displayed several times for sever­al seconds. Next, the text
FURNACE FOUND
and
AIR CONDITIONER FOUND
or
HEAT PUMP FOUND
(depending on which is installed in the system) will be displayed. The process can take several minutes (up to a maximum of 30) to com­plete. If these messages are not dis­played within 30 minutes after ener­gizing the system, communications can not be established. There are many reasons why communications may not be established – including improper settings of the “TERM” and “BIAS” switches (see BIAS / TERMI­NATION) and improper wiring (see
WIRING A FURNACE FOR COM­MUNICATIONS above).
FIGURE 52
WIRING DIAGRAM – SPECIAL CONFIGURATION: COMMUNICATING THERMOSTAT AND FURNACE WITH NON-COMMUNICATING CONDENSER
85
Page 86
The order in which these messages will be displayed will depend on which com­ponents are energized first. The order listed here assumes that the furnace and condenser are energized at the same time. If not, the order of display will be in the order that the components are turned on.
When the system has found all neces­sary components, the text area of the communicating thermostat will go blank. This is an indicator that the sys­tem is operating properly. Proceed by engaging a typical thermostat call to determine if operation is correct as described in the section of this book titled START UP PROCEDURES” to test heating, cooling and fan operation and to make necessary adjustments.
ACTIVE FAULT CODES WITH COMMUNICATING SYSTEMS
Two levels of fault codes exist: (1) Non­critical and (2) Critical. In general a non-critical fault permits all (or nearly all) operations to proceed and a critical fault prevents all (or nearly all) opera­tions from proceeding. Detailed expla­nations are given for each fault code and how to diagnose and troubleshoot problems by fault code displayed in the “TROUBLSHOOTING” section of this manual.
Active faults of either level will be dis­played at the thermostat in the “ACTIVE FAULT” area of the thermo­stat. To enter the furnace “ACTIVE FAULT” area using a communicating thermostat, see the installation and operation instructions for that thermo­stat.
For detailed user menu text, navigation and descriptions, refer to the section of this manual titled COMMUNICATING
SYSTEMS under the subsection titled USER MENUS.
Below describes some basic methods for entering and viewing furnace fault messages and user menus for two dif­ferent communicating thermostats avail­able at the time of publication of this manual. Further setup and installation information on these thermostats can be found in their respective installation and operation instructions.
FIGURE 53
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
VIEWING DETAILED FAULT MESSAGES
ON THE (-)HC-TST501CMMS
COMMUNICATING THERMOSTAT
(-)HC-TST501CMMS PROGRAM­MABLE COMMUNICATING THER­MOSTAT
TIPS FOR NAVIGATING FURNACE USER MENUS USING THE (-)HC­TST501CMMS THERMOSTAT
NOTE: The (-)HC-TST501CMMS ther-
mostat does not have built-in humidifi­cation control in heating mode (or any other mode). However, dehumidification is possible in cooling. If humidification control is required, a separate humidis­tat or a communicating thermostat with humidification capability (such as
(-)HC-TST550CMMS) must be used. (See the section of this manual titled Accessories, Humidification and Dehumidification for wiring of a sep­arate humidistat.)
Viewing the Active Faults:
53 demonstrates how to view the furnace active faults with the (-)HC­TST501CMMS communicating ther­mostat.
ST-A1118-01-3
Figure
86
Page 87
EEnntteerriinngg aanndd VViieewwiinngg tthhee FFuurrnnaaccee MMaaiinn MMeennuu aanndd SSuubb MMeennuuss
: Figure 54 demonstrates how to view and enter the furnace user menu and subsequent sub-menus with the (-)HCTST501CMMS communicating thermostat. To get into the submenus, use the up and down arrow keys of the thermostat to display the desired menu and press the “Installer Config” button on the thermo­stat to enter that menu.
FIGURE 54
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
ST-A1118-01-4
87
Page 88
MMaakkiinngg SSeettuupp CChhaannggeess::
Figure 55 demonstrates how to make changes to the SETUP sub-menu with the (-)HC­TST501CMMS communicating thermo­stat.
FIGURE 55
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
1
2
3
IN THIS EXAMPLE, WE WANT TO CHANGE THE “MAX HEAT ADJUST” TO –15%. FIRST, ENTER THE SETUP MENU AS DESCRIBED IN “ENTERING THE FURNACE MAIN MENU”
AFTER ENTERING THE “SETUP” MENU OF THE FURNACE (SEE STEP 7 IN FIGURE 54), THERE WILL BE SEVERAL VALUES THAT CAN BE CHANGED BY THE INSTALLER (BASED ON NEEDS OF THE INSTALLATION). THESE VALUES CAN BE CHANGED TO THE DESIRED SETTING BY PRESSING THE LEFT OR RIGHT ARROW KEYS UNTIL THE DESIRED VALUE IS DISPLAYED AND THEN PRESSING EITHER THE UP OR DOWN ARROW KEY OR THE “MENU” KEY. AN EXAMPLE FOLLOWS:
A
PRESS THE UP OR DOWN ARROW KEY UNTIL THE TEXT “MAX HEAT ADJUST” IS DISPLAYED .
A
B
B
4
C
THE TEXT “0” IS DISPLAYED IN THE UPPER LEFT-HAND CORNER OF THE THERMOSTAT. PRESS THE LEFT OR RIGHT ARROW KEY A UNTIL THE TEXT “–15” IS DISPLAYED IN THE CORNER .
C
5
PRESS THE UP OR DOWN ARROW KEY OR THE “MENU” KEY TO SET THE VALUE. IF THE “MENU” KEY IS PRESSED, THE PREVIOUS MENU SCREEN WILL BE SHOWN – BUT, THE NEW VALUE (–15) WILL BE SET.
ST-A1118-01-2
88
Page 89
EEssccaappiinngg oorr RReettuurrnniinngg ffrroomm MMeennuuss:: Figure 56 demonstrates how to escape from a menu back to the main screen or how to return to a previous menu level using the (-)HC-TST501CMMS communi­cating thermostat.
FIGURE 56
WIRING DIAGRAM – COMMUNICATING CONFIGURATION
ST-A1118-01-1
89
89
Page 90
(-)HC-TST550CMMS FULL COLOR, PROGRAMMABLE COMMUNICATING THERMOSTAT
FIGURE 57
ENTER THE ADVANCED INSTALLER MENUWIRING DIAGRAM – COMMUNICATING CONFIGURATION
TIPS FOR NAVIGATING FURNACE USER MENUS USING THE (-)HC­TST550CMMS THERMOSTAT
VIEWING FURNACE FAULT MESSAGES WITH THE (-)HC-TST550CMMS THERMOSTAT
To enter a particular user menu on the (-)HC-TST550CMMS, full color communicating thermostat follow the directions below.
1.From the main screen, press the left and right arrow keys together at the same time for at least 3 seconds. The next screen below will appear. (Note that Call for Service appears at the bottom of the screen. This is an indicator that the fault messages should be viewed to deter­mine the cause of the fault.)
FIGURE 58
SELECT FAULT STATUSIRING DIAGRAM – COMMUNICATING CONFIGURATION
Home
Enter
FIGURE 59
FAULT MESSAGE (IF ANY) (MAIN LIMIT OPEN) DISPLAYED.
3. The
Home
Enter
2.The ADVANCED INSTALLER MENU is displayed. Use the up and down arrow keys to highlight Fault Status. Next, press the “M” key. The next screen below will appears
FFaauulltt SSttaattuuss
appear with a description of the current fault (if any). Use the section of this manual
FFUURRNNAACCEE FFAAUULLTT
titled
CCOODDEESS EEXXPPAANNDDEEDD WWIITTHH DDEESSCCRRIIPPTTIIOONNSS AANNDD SSOOLLUUTTIIOONNSS
nation of the fault and possi­ble solution(s). To escape from this menu, press the
EEnntteerr
(to return to the fur­nace user menus) or button or just wait a few min­utes and the main screen will appear again.
screen will
for a full expla-
HHoommee
90
Page 91
VIEWING FURNACE USER MENUS WITH THE (-)HC­TST550CMMS THERMOSTAT
To enter a particular user menu on the (-)HC-TST550CMMS, full color communicating thermostat follow the directions below.
Use the section of this manual
CCoommmmuunniiccaattiinngg SSyysstteemmss
titled under the sub-section titled
MMeennuuss
to navigate through the
user menus.
UUsseerr
FIGURE 60
ENTER THE ADVANCED INSTALLER MENU.
FIGURE 61
NAVIGATING TO COMMUNICATING DEVICES AND SELECT.
Home
Enter
FIGURE 62
NAVIGATE TO FURNACE AND SELECT.
1. From the main
screen, press the left and right arrow keys together at the same time for at least 3 seconds. The next screen below will appear.
AADDVVAANNCCEEDD
2. The
IINNSSTTAALLLLEERR MMEENNUU
is displayed. Use the up and down arrow keys to high­light
CCoommmmuunniiccaattiinngg DDeevviicceess
. Next, press the “MM” key. The next screen below will appear.
Home
Enter
FIGURE 63
NAVIGATE TO DESIRED USER MENU AND SELECT.
4. The furnace menu
Home
Enter
FIGURE 64
NAVIGATE THE USER MENUS USING UP AND DOWN ARROW KEYS.
Home
Enter
3. From the devices listed, use the up and down arrow keys to highlight the selection titled
FFuurrnnaaccee
. Next, Press the “MM” Key. The next screen below will appear.
options will appear. Use the up and down arrow keys to select the desired menu. Next, press “
MM
” to enter the desired menu. Next, the next screen below will appear.
5. Use the up and down arrow keys to view the menu items.
6. To escape from this menu, press the (to return to the fur­nace user menus) or
HHoommee
button or just wait a few minutes and the main screen will appear again.
EEnntteerr
91
Page 92
CHANGING FURNACE SETUP ITEMS ON THE (-)HC-TST550CMMS THERMOSTAT
To change a particular furnace user setup item on the (-)HC­TST550CMMS, full color communi­cating thermostat follow the direc­tions below.
Use the section of this manual
CCoommmmuunniiccaattiinngg SSyysstteemmss
titled under the sub-section titled
MMeennuuss
to navigate through the
setup user menus.
UUsseerr
FIGURE 65
ENTER THE ADVANCED INSTALLER MENU.
1. From the main
FIGURE 66
IN THE ADVANCED INSTALLER MENU SELECT COMMUNICATING DEVICES.
Home
Enter
screen, press the left and right arrow keys together at the same time for at least 3 seconds. The next screen below will appear.
AADDVVAANNCCEEDD
2. The
IINNSSTTAALLLLEERR MMEENNUU
is displayed. Use the up and down arrow keys to high­light Communicating Devices. Next, press the “MM” key. The next screen below will appear.
FIGURE 67
SELECT FURNACE FROM THE LIST OF COMMUNICATING DEVICES.
Home
Enter
FIGURE 68
SELECT SETUP FROM THE LIST OF FURNACE MENUS.
Home
Enter
3. From the devices listed, use the up and down arrow keys to highlight the selection titled
FFuurrnnaaccee
Press the “MM” Key. The next screen below will appear.
. Next,
4. The furnace menu options will appear. Use the up and down arrow keys to nav­igate to the
SSEETTUUPP
menu. Press “MM” to enter the menu. Next, the next screen below will appear.
92
Page 93
FIGURE 69
SELECT THE SETUP ITEM TO BE ADJUSTED (MAX HEAT ADJ%).
Home
Enter
FIGURE 70
SELECT THE DESIRED VALUE (7).
Home
Enter
5. Use the up and down arrow keys to view and navigate to the desired setup menu item. Once the desired menu item is highlighted, press the “
MM
enter the sub menu. In this example, we will change the
HHEEAATT AAddjj%%
rently set to 0%)
6. Use the up and down arrow keys to view and navigate to the desired setup selection. Once the desired menu item is highlighted, press
MM
the “
” key to change the selec­tion. In this exam­ple, we will change
MMAAXX HHEEAATT
the
AAddjj%%
(currently set
to 0%) to +
77
%
” key to
MMAAXX
(cur-
FIGURE 71
UPDATING THE SUBSYSTEM.
7. This screen;
UUppddaattiinngg tthhee SSuubbssyysstteemm
displayed briefly while the system updates the setting.
will be
93
Page 94
FIGURE 72
UPDATE SUCCESSFUL.
8. This screen;
SSuucccceessssffuull
UUppddaattee
will be displayed briefly upon successfully changing the setting.
9. To escape from this menu, press the
EEnntteerr
(to return to the furnace user menus) or
HHoommee
button or just wait a few minutes and the main screen will appear again.
94
Page 95
95
Page 96
96
CM 0810
Loading...