IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY
INFORMATION!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS
THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PROPOSITION 65 WARNING: THIS PRODUCT CONTAINS CHEMICALS KNOWN TO THE STATE OF
CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
— Do not store or use gasoline or other flammable vapors and liquids, or other combustible materials
in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— DO NOT RELY ON SMELL ALONE TO DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT
BE ABLE TO SMELL FUEL GASES.
• U.L. recognized fuel gas and CO detectors are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules
regulations, or customs.
— Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or death. Refer to this manual. Installation and service must be performed by a qualified
installer, service agency or the gas supplier. In the commonwealth of Massachusetts, installation
must be performed by a licensed plumber or gas fitter for appropriate fuel.
ISO 9001:2008
FOR RGPE UPFLOW, HORIZONTAL, RGLE DOWNFLOW 2 STAGE,
80+ GAS FURNACES
COMMUNICATING
THERMOSTATS
INSTALLATION
SEE PAGE 84
This Memory Card must be removed (broken away) from the
furnace control when the control is replaced. The card must
be inserted into the connector at J15 of the replacement control. Failure to retain this memory card with the furnace when
replacing the furnace control could result in no operation
when the furnace control is replaced.
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN 2 OR MORE DIFFERENT FURNACES. DOING
SO COULD RESULT IN UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DURING HEATING (AND OTHER MODES) OR A LOSS OF HEAT.
SUPERSEDES 92-24161-77-01
92-24161-77-02
IMPORTANT: All Manufacturer products
meet current Federal OSHA Guidelines
for safety. California Proposition 65
warnings are required for certain products, which are not covered by the
OSHA standards.
California's Proposition 65 requires
warnings for products sold in California
that contain, or produce, any of over 600
listed chemicals known to the State of
California to cause cancer or birth
defects such as fiberglass insulation,
lead in brass, and combustion products
from natural gas.
All “new equipment” shipped for sale in
California will have labels stating that the
product contains and/or produces
Proposition 65 chemicals. Although we
have not changed our processes, having
the same label on all our products facilitates manufacturing and shipping. We
cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and airconditioning equipment, or found in natural gas used with some of our products.
Listed below are those chemicals and
substances commonly associated with
similar equipment in our industry and
other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the
Websites for OSHA (Occupational
Safety and Health Administration), at
www.osha.gov
and the State of
California's OEHHA(Office of
Environmental Health Hazard
Assessment), at www.oehha.org.
Consumer education is important since
the chemicals and substances on the list
are found in our daily lives. Most consumers are aware that products present
safety and health risks, when improperly
used, handled and maintained.
Installation Instructions are updated on a
regular basis. This is done as product
changes occur or if new information
becomes available. In this publication,
an arrow ➤ denotes changes from the
previous edition or additional new material.
IMPORTANT: To insure proper installation and operation of this product, completely read all instructions prior to
attempting to assemble, install, operate,
maintain or repair this product. Upon
unpacking of the furnace, inspect all
parts for damage prior to installation and
start-up.
GENERAL INFORMATION.......................................................................................................................................6
IMPORTANTINFORMATION ABOUT EFFICIENCYANDINDOORAIR QUALITY...................................6
SITE SELECTION.........................................................................................................................................10
GAS SUPPLYAND PIPING....................................................................................................................................19
GAS SUPPLY................................................................................................................................................19
GAS PIPING..................................................................................................................................................19
GAS PRESSURE..........................................................................................................................................20
THE COMMONWEALTH OF MASSACHUSETTS REQUIRES COMPLIANCE
WITH REGULATION 248 CMR 4.00
AND 5.00 FOR INSTALLATION OF
THROUGH-THE-WALL VENTED GAS
APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented
gas fueled equipment installed in every
dwelling, building or structure used in
whole or in part for residential purposes,
including those owned or operated by
the Commonwealth and where the side
wall exhaust vent termination is less than
seven (7) feet above finished grade in
the area of the venting, including but not
limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON
MONOXIDE DETECTORS.At the time of
installation of the side wall horizontal
vented gas fueled equipment, the
installing plumber or gasfitter shall
observe that a hard wired carbon
monoxide detector with an alarm and
battery back-up is installed on the floor
level where the gas equipment is to be
installed. In addition, the installing
plumber or gasfitter shall observe that a
battery operated or hard wired carbon
monoxide detector with an alarm is
installed on each additional level of the
dwelling, building or structure served by
the side wall horizontal vented gas
fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the installation of hard wired
carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is
installed in a crawl space or an attic, the
hard wired carbon monoxide detector
with alarm and battery back-up may be
installed on the next adjacent floor level.
b. In the event that the requirements of
this subdivision can not be met at the
time of completion of installation, the
owner shall have a period of thirty (30)
days to comply with the above requirements; provided, however, that during
said thirty (30) day period, a battery
operated carbon monoxide detector with
an alarm shall be installed.
2. APPROVED CARBON MONOXIDE
DETECTORS. Each carbon monoxide
detector as required in accordance with
the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed
and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above
grade directly in line with the exhaust
vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall read, in print size
no less than one-half (1/2) inch in size,
“GASVENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas
inspector of the side wall horizontally
vented gas fueled equipment shall not
approve the installation unless, upon
inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through
4.
(b) EXEMPTIONS: The following equip-
ment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10
entitled “Equipment Not Required To Be
Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side
wall horizontally vented gas equipment
provides a venting system design or
venting system components with the
equipment, the instructions provided by
the manufacturer for installation of the
equipment and the venting system shall
include:
1. Detailed instructions for the installation of the venting system design or the
venting system components; and
2. A complete parts list for the venting
system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product
Approved side wall horizontally vented
gas fueled equipment does not provide
the parts for venting the flue gases, but
identifies “special venting systems”, the
following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with
the appliance or equipment installation
instructions; and
2. The “special venting systems” shall
be Product Approved by the Board, and
the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions
for all ProductApproved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for
venting instructions, and/or all venting
design instructions shall remain with
the appliance or equipment at the completion of the installation.
WARNING
!
INSTALLTHIS FURNACE ONLY IN
A LOCATION AND POSITION AS
SPECIFIED IN THE LOCATION
REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE
INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TOTHE FURNACE
SPACE AS SPECIFIED IN THE
VENTING SECTION OF THESE
INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO
THE FURNACE SPACE AS SPECIFIED IN THE COMBUSTION AND
VENTILATION AIR SECTION OF
THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST
BE DISCHARGED OUTDOORS.
CONNECT THIS FURNACE TO AN
APPROVEDVENT SYSTEM ONLY,
AS SPECIFIED IN VENT PIPE
INSTALLATION SECTION OF
THESE INSTRUCTIONS.
WARNING
!
NEVER TEST FOR GAS LEAKS
WITH AN OPEN FLAME. USE A
COMMERCIALLY AVAILABLE
SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF
LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS
SUPPLY AND PIPING SECTION OF
THESE TION INSTRUCTIONS.
WARNING
!
THIS FURNACE IS NOT
APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK,
WITH ACCESS DOORS FACING
UPWARDS, OR WITH SUPPLY AIR
DISCHARGING TO THE RIGHTHAND SIDE WHEN FACING THE
FRONT OF THE FURNACE. SEE
FIGURES 6 AND 7 FOR PROPER
INSTALLATION OF HORIZONTAL
MODELS.
WARNING
!
DO NOT INSTALLTHIS FURNACE
IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR
INSTALLATION IN A MOBILE
HOME. DOING SO COULD CAUSE
FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
USE ONLYWITH TYPE OF GAS
APPROVED FOR THIS FURNACE.
REFER TO THE FURNACE RATING
PLATE.
3
WARNING
!
WHENTHIS FURNACE IS INSTALLED
IN A RESIDENTIAL GARAGE,IT
MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE
LOCATED NO LESSTHAN 18 INCHES ABOVETHE FLOOR.THIS ISTO
REDUCETHE RISK OF IGNITING
FLAMMABLEVAPORS WHICH MAY
BE PRESENT IN A GARAGE.
ALSO,THE FURNACE MUST BE
LOCATED OR PROTECTEDTO
AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURETO FOLLOWTHESE
WARNINGS CAN CAUSE A FIRE OR
EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
WARNING
!
USE OF THIS FURNACE IS
ALLOWED DURING CONSTRUCTION
IF THE FOLLOWINGTEMPORARY
INSTALLATION REQUIREMENTS
ARE MET. INSTALLATION MUST
COMPLY WITH ALL INSTALLATION
INSTRUCTIONS INCLUDING:
• PROPERVENT INSTALLATION;
• FURNACE OPERATING UNDER
THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO
THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND
TEMPERATURE RISE PER RATING PLATE MARKING;
• MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE
MAINTAINED BETWEEN 55°F
(13°C) AND 80°F (27°C); AND;
• CLEAN FURNACE, DUCT WORK
AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE
CONSTRUCTION PROCESS, AND
VERIFY FURNACE OPERATING
CONDITIONS INCLUDING IGNITION, INPUT RATE,TEMPERATURE RISE AND VENTING,
ACCORDINGTOTHE INSTRUCTIONS.
WARNING
!
DO NOT JUMPER OR OTHERWISE
BYPASS OVERTEMPERATURE OR
ANY OTHER LIMITS OR SWITCHES
ONTHE FURNACE. IF ONE OF
THESE LIMITS OR SWITCHES
SHOULDTRIP OR OPEN,THE USER
ISTO BE INSTRUCTEDTO CALL A
QUALIFIED INSTALLER, SERVICE
AGENCY OR THE GAS SUPPLIER.
FOR MANUALLY RESETABLE
SWITCHES,THE USER IS FURTHER
INSTRUCTEDTO NEVER RESETTHE
SWITCH, BUTTO CALL A QUALIFIED
TECHNICIAN. MANUAL RESET
SWITCHES MAY REQUIRE FURTHER
CORRECTIVE ACTIONS. FAILURETO
FOLLOWTHIS WARNING COULD
RESULT IN CARBON MONOXIDE
POISONING, SERIOUS INJURY OR
DEATH. IFTHE UNIT IS INSTALLED
IN A CLOSET,THE DOOR MUST BE
CLOSEDWHEN MAKINGTHIS
CHECK. INSTALLERS ANDTECHNICIANS ARE INSTRUCTEDTO
REPLACE ANY LIMIT OR SAFETY
SWITCH/DEVICE ONLY WITH IDENTICAL REPLACEMENT PARTS.
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND DRAW
POLLUTANTS SUCH AS DIRT, DUST,
FUMES AND ODORS INTOTHE
HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM
TOXIC,VOLATILE OR FLAMMABLE
CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON
MONOXIDE (CO), CAN BE DRAWN
INTOTHE LIVING SPACETHROUGH
LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING
PERSONAL INJURY OR DEATH (SEE
FIGURE 5).
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL JOINTS,
SEAMS, AND OPENINGS INTHE
EQUIPMENT AND DUCT MUST BE
SEALED TO LIMIT THE MIGRATION
OF TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE
FROM MIGRATING INTOTHE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH AS
WATER HEATERS OR BOILERS ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND
DUCT MUST ALSO BE SEALED TO
PREVENT DEPRESSURIZATION
OF THE SPACE AND POSSIBLE
MIGRATION OF COMBUSTION
BYPRODUCTS INCLUDING CARBON MONOXIDE INTOTHE LIVING
SPACE.
WARNING
!
ALWAYS INSTALL FURNACE TO
OPERATE WITHIN THE FURNACE'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT
SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN
THE ALLOWABLE RANGE, AS
SPECIFIED IN DUCTING SECTION
OF THESE INSTRUCTIONS. SEE
ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED
SO THAT SUPPLY DUCTS CARRY
AIR CIRCULATED BY THE FURNACETO AREAS OUTSIDE THE
SPACE CONTAINING THE FURNACE,THE RETURN AIR SHALL
ALSO BE HANDLED BY DUCT(S)
SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE
THE SPACE CONTAININGTHE
FURNACE.
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITHTHE CSA
INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR
DANGEROUS CONDI-TIONS AND
ARE NOT COVERED BY THE UNIT
WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY
DRAIN PAN BE INSTALLED
UNDER ALL EVAPORATOR COILS
OR UNITS CONTAINING EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGETOTHE
BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT
OF AN OVERFLOW OF THE COIL
DRAIN PAN OR A STOPPAGE IN
THE PRIMARY CONDENSATE
DRAIN PIPING. SEE ACCESSORIES SECTION OF THESE
INSTRUCTIONS FOR AUXILIARY
HORIZONTAL OVERFLOW PAN
INFORMATION (MODEL RXBM).
WARNING
!
DO NOT EXCHANGE MEMORY
CARDS BETWEEN 2 OR MORE
DIFFERENT FURNACES. DOING
SO COULD RESULT IN UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DURING HEATING (AND OTHER
MODES OR A LOSS OF HEAT).
4
Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction is sometimes caused by an improper installation. By completing this checklist, the problem may be found and corrected. Make copies
of the checklist and complete one for every Low Profile Furnace service call for your records.
INSTALLATION CHECKLIST
(Refer to this manual for specifics.)
GAS SUPPLY
Adequate pipe size
No gas leaks
Proper supply and manifold gas pressure (check with an accurate U-tube manometer with the furnace and all other
gas appliances operating.)
ELECTRICAL
Correct thermostat and subbaseThermostat modelSubbase model
Correct thermostat mode and setting
Correct line supply voltage
Correct power supply polarity is required with electronic ignition
Correct furnace ground to electrical panel
DC microamp (∝A) flame signal (hot surface ignition units)
Correct control voltage
Measure and set heat anticipator amperage
Air conditioning low voltage wires connected to terminals “Y” “C” - not with wire nuts
VENTING
Correct vent pipe diameter and length (according to CSA tables)Vent connection size
Correct venting material (according to CSA tables)
Correct lining for masonry chimneys
Adequate clearance from combustibles
Proper negative pressure reading in the vent
Vent pipe secured to induced draft blower housing
COMBUSTION AIR
Proper source of combustion airOptional attic combustion air pull
Correct combustion air opening sizeNon-attic combustion air pull
FURNACE INSTALLATION
Adequate clearance from combustibles
Adequate clearance for service
Proper air temperature rise (See furnace rating plate)
External static pressureinches w.c.
Correct filter(s)
Correct cooling coil or accessories (if equipped)
Adequate supply and return air ductingReturnAir Duct SizeSupplyAir Duct Size
Air ducts sealed to prevent leakage
5
GENERAL INFORMATION
The RGPE/RGLE series furnaces are
design certified by CSA for use with natural and propane gasesas follows:
As a CategoryI furnace, it may be
vented vertically with type B-1 vent
pipe and alsomay be common vented as described in these instructions.
This furnace should be installed in accordancewith the American National
Standard Z223.1 - latest edition booklet
entitled “National Fuel Gas Code” (NFPA
54) (in Canada, CSAB149.1 and .2
Installation Codes for gas burning appliances), and the requirements or codes of
the localutility or other authorityhaving
jurisdiction including local plumbing or
wastewater codes.
The NationalAppliance Energy
ConservationAct (NAECA) of 1987
states that any gas furnace manufacturedafter January 1, 1992, must have a
minimumAnnual Fuel Utilization
Efficiency (AFUE) of 78%.The higher the
AFUE percentage the more usableheat
energy the consumer gets for every dollar of fuel purchased.This is similarto
the EPA's minimum gas mileage requirement for automobiles. It gives the consumera relativelyeasy way to make
direct efficiency comparisons between
differentfurnace brands and styles.
A high AFUE value, which translates into
a low operating cost, is not the only concern thatconsumers have. Theyalso
want a furnace with a reasonable
installed cost. They want a furnace that
provides them with comfort – their main
concern.And they expecta furnace with
exceptional reliability and longevity.
Gas furnace manufacturers are always
striving to provide consumers with the
best furnace value. The Low Profile
Furnace addresses all those consumer
needs. It gives exceptionalefficiency with
a low installationcost. It delivers the
comfort the customer wants along with
the reliability they expect.
The key to all these customer benefits is
the furnace's heat exchanger.The materialsused to construct the furnace in general and the heatexchanger in particular
make it a rugged,long lasting unit. The
unique heat exchanger design provides
the customer with a furnace only 34 inches high.This gives the consumer a unit
easily installed in almost every location
that accepts all customary accessories.
With the introduction of higherefficiency
furnaces, special attention mustbe paid
to the venting system.Only listed venting
systems may be used as stated in the
installation instructions and the National
Fuel Gas Code, ANSI Z223.1 (NFPA 54),
or the Canadian CAN/CGA B149.1 and
B149.2 InstallationCodes for Gas
Burning Appliances.Sincefurnace tech-
nology and ventingrequirements are
changing, awarenessof local, state, and
federal codes and industry changes is
imperative.
NOTE: Always perform a proper heat
loss calculation beforespecifying the furnace size. This ensures that the furnace
is sized to adequately, economically, heat
the building and provide the correct airflow for yourapplication.
IMPORTANT:PROPERAPPLICATION,
INSTALLATION AND MAINTENANCE
OF THIS FURNACE ISA MUST IF
CONSUMERSARE TO RECEIVE THE
FULLBENEFITS FOR WHICH THEY
HAVE PAID.
Additionalhelpful publications available
from the “NationalFire Protection
Association” are: NFPA-90A– Installation
ofAir Conditioning and Ventilating
Systems 1985 or latestedition.NFPA90B – WarmAir Heating and Air
Conditioning Systems 1984.
IMPORTANT INFORMATION
ABOUT EFFICIENCY AND
INDOOR AIR
QUALITY
Central cooling and heating equipment
is only as efficient as the duct system
that carries the cooled or heated air. To
maintain efficiency, comfort and good
indoor air quality, it is important to have
the proper balance between the air
being supplied to each room and the air
returning to the cooling and heating
equipment.
FIGURE 1
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Proper balance and sealing of the
duct system improves the efficiency
of the heating and air conditioning
system and improves the indoor air
quality of the home by reducing the
amount of airborne pollutants that
enter homes from spaces where the
ductwork and / or equipment is
located. The manufacturer and the
U.S. Environmental Protection
Agency’s Energy Star Program recommend that central duct systems
be checked by a qualified contractor
for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN
UNBALANCED SYSTEM AND
DRAW POLLUTANTS SUCH AS
DIRT, DUST,FUMES AND ODORS
INTOTHE HOME CAUSING PROPERTY DAMAGE. FUMES AND
ODORS FROM TOXIC,VOLATILE
OR FLAMMABLE CHEMICALS, AS
WELL AS AUTOMOBILE
EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO
THE LIVING SPACETHROUGH
LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR
DEATH (SEE FIGURE 1).
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
GARAGES OR OFF-GARAGE
STORAGE AREAS - ALL
JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND
DUCT MUST BE SEALED TO
LIMIT THE MIGRATION OF
TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE FROM MIGRATING INTO
THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR
DUCTWORK IS LOCATED IN
SPACES CONTAINING FUEL
BURNING APPLIANCES SUCH
6
AS WATER HEATERS OR BOILERS
- ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND
DUCT MUST ALSO BE SEALED TO
PREVENT DEPRESSURIZATION OF
THE SPACE AND POSSIBLE
MIGRATION OF COMBUSTION
BYPRODUCTS INCLUDING CARBON MONOXIDE INTOTHE LIVING
SPACE.
NOTICE
IMPROPER INSTALLATION, OR
INSTALLATION NOT MADE IN
ACCORDANCE WITHTHE CSA
INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS,
CAN RESULT IN UNSATISFACTORY
OPERATION AND/OR DANGEROUS
CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED
CODES, IT IS RECOMMENDEDTHAT
AN AUXILIARY DRAIN PAN BE
INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING
EVAPORATOR COILS OR GAS FURNACES USED WITH EVAPORATOR
COILS THAT ARE LOCATED IN ANY
AREA OF A STRUCTURE WHERE
DAMAGETO THE BUILDING OR
BUILDING CONTENTS MAY OCCUR
AS A RESULT OF AN OVERFLOW OF
THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING.
RECEIVING
Immediately upon receipt, all cartons
and contents should be inspected for
transit damage. Units with damaged
cartons should be opened immediately.
If damage is found, it should be noted
on the delivery papers, and a damage
claim filed with the last carrier.
• After unit has been delivered to job
site, remove carton taking care not to
damage unit.
• Check the unit rating plate for unit
size, electric heat, coil, voltage,
phase, etc. to be sure equipment
matches what is required for the job
specification.
• Read the entire instructions before
starting the installation.
• Some building codes require extra
cabinet insulation and gasketing
when unit is installed in attic applications.
• If installed in an unconditioned
space, apply caulking around the
power wires, control wires, refrigerant
tubing and condensate line where
they enter the cabinet. Seal the
power wires on the inside where they
exit conduit opening. Caulking is
required to prevent air leakage into
and condensate from forming inside
the unit, control box, and on electrical
controls.
• Install the unit in such a way as to
allow necessary access to the
coil/filter rack and blower/control
compartment.
• Install the unit in a level position
to ensure proper condensate
drainage. Make sure unit is level
in both directions within 1/8”.
• Install the unit in accordance with
any local code which may apply
and the national codes. Latest
editions are available from:
“National Fire Protection
Association, Inc., Batterymarch
Park, Quincy, MA 02269.” These
publications are:
• ANSI/NFPANo. 70-(Latest
Edition) National Electrical Code.
• NFPA90AInstallation of Air
Conditioning and Ventilating
Systems.
• NFPA90B Installation of warm air
heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of
Federal Regulations, Chapter XX,
Part 3280.
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
1. NOTE: This furnace is shipped with
heat exchanger support brackets
installed under the back of the heat
exchanger.These may be removed
before installation, but it is not
required.
LOCATION
!
WARNING
THIS FURNACE IS NOT APPROVED
FOR INSTALLATION IN A MOBILE
HOME. DO NOT INSTALLTHIS FURNACE IN A MOBILE HOME.
INSTALLATION IN A MOBILE HOME
COULD CAUSE FIRE, PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
2. IMPORTANT: This furnace is not
approved or recommended for installation on its back, with access doors
facing upwards.
3. This furnace is suitable for installation in buildings constructed on-site.
This heating unit should be centralized with respect to the heat distribution system as much as practicable.
4. NOTE: These furnaces are approved
for installation in attics, as well as
alcoves, utility rooms, closets and
crawlspaces.
5. IMPORTANT: Support this unit when
installed.Forattic or crawl space
installation, horizontal furnaces may
be installed on combustible wood
flooring or by using support brackets.
See Figure 2.
FIGURE 2
HORIZONTAL FURNACE INSTALLEDW/SUPPORT BRACKETS
EXHAUST
VENT
NOTE: Do not block furnace
access with support rods. Maintain
clearances recommended in Figure 3.
Allow enough space for proper service
maintenance or replacement of the heat
exchanger and blower assembly.
6. IMPORTANT: If installing in a util-
ity room, be sure the door is wide
enough to:
a. allow the largest part of the furb. allow any other appliance
nace to pass; or
(such as a water heater) to
pass.
ST-A0799-01
7
FIGURE 3
UPFLOW/HORIZONTAL DIMENSIONS
Ship.
/32
19
15
REDUCED CLEARANCE (IN.)
BackTopFrontVent
LeftRight
ABCDEF
20
/16
1
28
➂ May be 1” with type B vent.
➀ May require 3” to 4” or 3” or 5” adapter.
➁ May be 0” with type B vent.
/203➁0136➂105 lbs.
/203➁0136➂115 lbs.
/2000136➂120 lbs.
1
/8➀152
3
/32 12
11
/2 16
1
/2000136➂140 lbs.
1
1
1
/22
1
/8➀152
/8➀18
/8➀222
3
1
7
/32 12
/32 14
/32 15
11
27
11
/2 16
/2 23
1
1
D
/16
9
/32
19
B
A
/16
7
24
5
ALTERNATE
GAS CONNECTION
/4
3
/8 DIA.
1
/8
5
26
/8 DIA.
7
/8 DIA.
7
OPTIONAL RETURN AIR CUTOUT
/2
1
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
23
11
/8
3
14
/32
11
RIGHT SIDE
24
34
FRONT
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
/4
1
1
BOTTOM
TOP
RGPESideSideWgts.
Model
0517
07(A)17
/32
17
23
AIR
RETURN
/2
1
24
AIR
SUPPLY
25.406
1224
07(B),10 2119
/32
19
SIGHT
GLASS
*Both sides for 1800 CFM or above.
AIRFLOW
/32
11
E
/16
C
13
26
/8
5
26
GAS CONNECTION
F
24
/8
3
14
/2
1
11
LOW VOLTAGE
ELECTRICAL CONNECTION
OPTIONAL RETURN AIR CUTOUT
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
LEFT SIDE
IMPORTANT: This furnace is not approved or recommended for
installation on its back, with access doors facing upwards.
8
FIGURE 4
DOWNFLOW DIMENSIONS
Ship.
BackTopFrontVent
REDUCED CLEARANCE (IN.)
/8
5
/8
1
20
/16
1
28
➂ May be 1” with type B vent.
➀ May require 3” to 4” or 3” or 5” adapter.
➁ May be 0” with type B vent.
/8
5
26
/8 DIA.
/8 DIA.
7
7
/16
7
24
/8 DIA.
5
1
D
LeftRight
ABCDE
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
Model
DOWNFLOW MODELS
RGLESideSideWgts.
/16
3
/8
/8000136➂140 lbs.
/803➁0136➂105 lbs.
/8000136➂120 lbs.
5
1
5
3
20
/8
3
6
23
/8➀23
/8➀16
/8➀20
1
7
5
/3212
/3213
/3215
11
27
11
/216
/223
1
1
1224
07(A)17
07(B),102119
/4
3
19
/8
5
R.A.
B
A
/8
5
/4
3
SIGHT
34
GLASS
AIRFLOW
S.A.
AIR
E
SUPPLY
/8
3
23
/8
3
20
/16
3
6
TOPBOTTOM
AIR
RETURN
1
/2
24
/8
5
26
C
LOW VOLTAGE
/16
13
26
GAS CONNECTION
ELECTRIC CONNECTION
NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.
COMBUSTIBLE FLOOR BASE REQUIRED IF FURNACE IS NOT INSTALLED ON COIL BOX.
9
CLEARANCE –
ACCESSIBILITY
The design of forced air furnaces with
input ratings as listed in the tables on
the following pages are certified by
CSA for the clearances to combustible
materials shown in inches.
See name/rating plate and clearance
label for specific model number and
clearance information.
Service clearance of at least 24 inches
is recommended in front of all furnaces.
ACCESSIBILITY CLEARANCES,
WHERE GREATER, MUST TAKE
PRECEDENCE OVER FIRE PROTECTION CLEARANCES.
!
WARNING
UPFLOW AND HORIZONTAL
FURNACES MUST NOT BE
INSTALLED DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE
MATERIAL OTHER THAN WOOD
FLOORING. INSTALLATION ON A
COMBUSTIBLE MATERIAL CAN
RESULT IN FIRE CAUSING PROPERTY DAMAGE, SEVERE PERSONAL
INJURY OR DEATH.
A gas-fired furnace for installation in a
residential garage must be installed so
that the burner(s) and the ignition
source are located not less than 18”
above the floor and the furnace is located or protected to avoid physical damage by vehicles.
!
WARNING
DOWNFLOW UNIT DESIGN IS CERTIFIED FOR INSTALLATION ON NONCOMBUSTIBLE FLOOR. A SPECIAL
COMBUSTIBLE FLOOR SUB-BASE,
FIGURE 5, IS REQUIRED WHEN
INSTALLING ON A COMBUSTIBLE
FLOOR. FAILURETO INSTALLTHE
SUB-BASE MAY RESULT IN FIRE,
PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.THIS SPECIAL
BASE IS OFFERED AS AN ACCESSORY FROM THE FACTORY. SEE THE
CLEARANCE LABEL LOCATED
INSIDE THE FURNACE FOR THE
APPROPRIATE MODEL NUMBER.
THE SPECIAL BASE IS NOT
REQUIRED WHEN THE FURNACE IS
INSTALLED ON TOP OF AN AIR
CONDITIONING PLENUM.
SITE SELECTION
1. Select a site in the building near the
center of the proposed, or existing,
duct system.
2. Give consideration to the vent system piping when selecting the furnace location. Be sure the venting
system can travel from the furnace to
the termination with minimal length
and elbows.
3. Locate the furnace near the existing
gas piping. Or, if running a new gas
line, locate the furnace to minimize
the length and elbows in the gas piping.
4. Locate the furnace to maintain proper clearance to combustibles as
shown in Figures 3 and 4.
!
CAUTION
WHEN COILS ARE INSTALLED
ABOVE A FINISHED CEILING OR
LIVING AREA, IT IS RECOMMENDED
THAT AN AUXILIARY SHEET METAL
CONDENSATE DRAIN PAN BE FABRICATED AND INSTALLED UNDER
ENTIRE UNIT. FAILURETO DO SO
CAN RESULT IN PROPERTY DAMAGE. RUN CONDENSATETO A
LOCATION WHERE IT IS NOTICEABLE.
!
WARNING
COMBUSTIBLE MATERIAL MUST
NOT BE PLACED ON OR AGAINST
THE FURNACE JACKET OR WITHIN
THE SPECIFIED CLEARANCES OF
THE VENT PIPE. THE AREA AROUND
THE FURNACE MUST BE KEPT
CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
PLACEMENT OF COMBUSTIBLE
MATERIALS ON, AGAINST OR
AROUNDTHE FURNACE JACKET
CAN CAUSE AN EXPLOSION OR
FIRE RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.THE FURNACE OWNER
SHOULD BE CAUTIONED THATTHE
FURNACE AREA MUST NOT BE
USED AS A BROOM CLOSET OR
FOR ANY OTHER STORAGE PURPOSES.
DUCTING
Proper air flow is required for the
correct operation of this furnace. Too
little air flow can cause erratic operation and can damage the heat
exchanger. The duct system must
carry the correct amount of air for
heating and cooling. Position the
unit to minimize long runs or runs
with many turns and elbows.
Size and install the ducts according
to acceptable industry standards
and methods. The total static pressure drop (including evaporator coil,
if used) of the entire system should
not exceed 0.8” w.c.
adequate space for unit filter. NOTE:
Airflow external static pressure measurements do not include filter or
coil.
IMPORTANT: Some high efficiency
filters have a greater than normal
resistance to air flow.This can
adversely affect furnace operation.
BE SURE TO CHECK AIR FLOW if
using any filter other than the factory-provided filter.
NOTE: DO NOT take return air from
bathrooms, kitchens, furnace rooms,
garages, utility or laundry rooms, or
cold areas.
IMPORTANT: Return air tempera-
ture must be above 55°F during the
heating season.
!
WARNING
NEVER ALLOW PRODUCTS OF
COMBUSTION OR THE FLUE
PRODUCTSTO ENTER THE
RETURN AIR DUCTWORK, OR
THE CIRCULATING AIR SUPPLY.
ALL RETURN DUCTWORK MUST
BE ADEQUATELY SEALED AND
SECURED TO THE FURNACE
WITH SHEET METAL SCREWS,
AND JOINTS TAPED.WHEN A
FURNACE IS MOUNTED ON A
PLATFORM,WITH RETURN
THROUGHTHE BOTTOM, IT MUST
BE SEALED AIRTIGHT BETWEEN
THE FURNACE AND THE RETURN
AIR PLENUM. THE RETURN AIR
PLENUM MUST BE PERMANENTLY ENCLOSED. NEVER USE A
DOOR AS A PART OF THE
RETURN AIR PLENUM. THE
FLOOR OR PLATFORM MUST
PROVIDE SOUND PHYSICAL
SUPPORT OF THE FURNACE,
WITHOUT SAGGING, CRACKS,
GAPS, ETC., AROUND THE BASE
AS TO PROVIDE A SEAL
BETWEEN THE SUPPORT AND
THE BASE.
Be sure to have
10
FAILURE TO PREVENT PRODUCTS
OF COMBUSTION FROM BEING CIRCULATED INTO THE LIVING SPACE
CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING
CARBON MONOXIDE POISONING
THAT COULD RESULT IN PERSONAL
INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR
SUPPLY DUCTWORK TO OR FROM
ANY OTHER HEAT PRODUCING
DEVICE SUCH AS A FIREPLACE
INSERT, STOVE, ETC. DOING SO
MAY RESULT IN FIRE, CARBON
MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR PROPERTY DAMAGE.
!
WARNING
BLOWER AND BURNERS MUST
NEVER BE OPERATEDWITHOUT
THE BLOWER DOOR IN PLACE.THIS
IS TO PREVENT DRAWING GAS
FUMES (WHICH COULD CONTAIN
HAZARDOUS CARBON MONOXIDE)
INTOTHE HOME THAT COULD
RESULT IN PERSONAL INJURY OR
DEATH.
UPFLOW UNITS
1. Set furnace in place and connect the
return duct or return air cabinet to
unit. Make the connection air-tight to
prevent entraining combustion gases
from any adjacent fuel-burning appliances. Unit return air may be connected on the sides or bottom of the
return air compartment.
a. Openings in the side must be cut
out the full width of the knockouts
on the unit. If using side return air,
THE BOTTOM base plate must be
installed.
NOTE: Where the maximum airflow
is 1800 CFM or more, both sides or
the bottom must be used for return
air.
b. If using bottom return air, place fur-
nace over return air plenum and
seal furnace bottom to return air
plenum.
!
WARNING
A SOLID METAL BASE PLATE, (SEE
TABLE 1) MUST BE IN PLACE WHEN
THE FURNACE IS INSTALLED WITH
SIDE AIR RETURN DUCTS. FAILURE
TO INSTALL A BASE PLATE COULD
CAUSE PRODUCTS OF COMBUSTION TO BE CIRCULATED INTO THE
LIVING SPACE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS,
INCLUDING CARBON MONOXIDE
POISONING OR DEATH.
TABLE 1
FURNACEBASEBASE
WIDTHPLATE NO.PLATE SIZE
1
17
/2”RXGB-D17151/8” x 239/16”
21”RXGB-D2118
1
24
/2”RXGB-D24255/8” x 239/16”
5
/8” x 239/16”
2. If summer air conditioning is desired,
position the indoor coil on the supply
air side of the furnace. Insure that no
air can bypass this coil.
3. Connect the supply air plenum to the
furnace plenum opening, or indoor
coil.
NOTE: The RGLE has louvers to cool
the inducer motor bearings.
DOWNFLOW UNITS
!
WARNING
THE DOWNFLOW FURNACE DESIGN
IS CERTIFIED FOR INSTALLATION
ON A NON-COMBUSTIBLE FLOOR.
IF INSTALLED ON A COMBUSTIBLE
FLOOR, USE THE SPECIAL BASE
SPECIFIED ON THE FURNACE
CLEARANCE LABEL. FAILURETO
INSTALLTHE SPECIAL BASE MAY
RESULT IN FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.THIS SPECIAL BASE IS
SHIPPED FROM THE FACTORY AS
AN ACCESSORY.
FIGURE 5
COMBUSTIBLE FLOOR BASE (RXGC-B17, -B21, -B24)
1. Position the unit over the supply
air plenum and connect.
a. If installing on a combustible
floor and not using an evapo-rator coil box, install the special combustible floor base. See
Figure 5.
b. If summer air conditioning is
desired, position the indoor coil
on the supply air side. Insure
that no air can bypass this coil.
2. Connect the return air ducting to
the return air opening at the top of
the unit. Make the connection air
tight to prevent entraining combustion gases from an adjacent
fuel-burning appliance.
HORIZONTAL UNITS
1. Unit can be mounted left or right
side airflow configuration.
2. Position the unit on adequate
supports or by using support
brackets (see Figure 2) and connect supply plenum and return.
3. If summer air conditioning is
desired, position the indoor coil
on the supply air side of the unit.
Insure that no air can bypass this
coil.
4. Secure the four angle brackets
shipped with the unit to the return
air opening. See Figure 6.
Connect the return air ducting to
the return air opening at the top of
the unit. Make the connection air
tight to prevent entraining combustion gases from an adjacent
fuel-burning appliance.
NOTE: Do not block furnace access
with support rods. Maintain clearances recommended in Figure 3.
Allow enough space for proper service maintenance or replacement of
the heat exchanger and blower
assembly.
11
FIGURE 6
HORIZONTAL RETURN AIR DUCT
(LEFT-HAND AIRFLOW POSITION SHOWN)
AIRFLOW
RETURN
REAR VIEW
FOUR ANGLE BRACKETS ARE SHIPPED WITH EACH
UNIT THAT CAN BE USED TO SECURE THE RETURN
AIR DUCT TO A HORIZONTAL UNIT.
COMBUSTION AND VENTILATION AIR
IMPORTANT: This is not a direct vent furnace. Review venting instructions
before installing.
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry
rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following substances in the combustion air supply
may also require OUTDOOR AIR for
combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for
clothes dryers
• Masonry acid washing materials
!
WARNING
THIS FURNACE AND ANY OTHER
FUEL-BURNING APPLIANCE MUST
BE PROVIDED WITH ENOUGH
FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE
FLUE GASES. MOST HOMES WILL
REQUIRETHAT OUTSIDE AIR BE
SUPPLIED INTO THE FURNACE
AREA. FAILURETO DO SO CAN
CAUSE DEATH FROM CARBON
MONOXIDE POISONING.
Adequate facilities for providing air for
combustion and ventilation must be
provided in accordance with section
5.3, Air for Combustion and Ventilation,
of the National Fuel Gas Code, ANSI,
Z223.1 latest edition or CSA B149.1
and .2 or, applicable provisions for the
local building codes, and not obstructed
so as to prevent the flow of air to the
furnace.
COMBUSTION AIR REQUIREMENTS
IMPORTANT: Air for combustion and
ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is
excluded from warranty coverage.
The following types of installation may
require OUTDOOR AIR for combustion,
due to chemical exposures:
FIGURE 7
AIR FROM HEATED SPACE
12
Combustion air must be free of acid
forming chemicals; such as sulphur, fluorine and chlorine. These elements are
found in aerosol sprays, detergents,
bleaches, cleaning solvents, air fresheners, paint and varnish removers,
refrigerants and many other commercial
and household products. Vapors from
these products when burned in a gas
flame form acid compounds. The acid
compounds increase the dew point
temperature of the flue products and
are highly corrosive after they condense.
!
WARNING
ALL FURNACE INSTALLATIONS
MUST COMPLYWITH THE NATIONAL
FUEL GAS CODE AND LOCAL
CODES TO PROVIDE ADEQUATE
COMBUSTION AND VENTILATION
AIR FOR THE FURNACE. FAILURE
TO DO SO CAN CREATE HAZARDOUS CONDITIONS RESULTING
IN PROPERTY DAMAGE, BODILY
INJURY OR DEATH FROM SMOKE,
FIRE OR CARBON MONOXIDE.
Combustion air requirements are determined by whether the furnace is in an
open (unconfined) area or in a confined
space such as a closet or small room.
See Figures 7 and 8.
EXAMPLE 1.
FURNACE LOCATED IN AN UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at
least 50 cubic feet for each 1,000
BTUH of the total input for all appli
ances
in the space. Here are a few
-
examples of the room sizes required for
different inputs. The sizes are based on
8 foot ceilings.
BTUH Minimum Sq. FeetTypical Room Size
InputWith 8' CeilingWith 8' Ceiling
50,00031214*x24* or 18*x18*
75,00046915*x31* or 20*x24*
100,00062520*x31* or 25*x25*
125,00083323*x34* or 26*x30*
If the open space containing the furnace is in a building with tight construction (contemporary construction), outside air may still be required for the furnace to operate and vent properly.
Outside air openings should be sized
the same as for a confined space.
FIGURE 8
AIR FROM ATTIC/CRAWL SPACE
EXAMPLE 2.
FURNACE LOCATED IN A CONFINED
SPACE
A confined space (any space smaller
than shown above as “unconfined”)
must have openings into the space
which are located in accordance with
the requirements set forth in the following subsections A and B. Size the openings by how they are connected to the
heated area or to the outside, and by
the input of all appliances in the space.
If confined space is within a building
with tight construction, combustion air
must be taken from outdoors or area
freely communicating with the outdoors.
A. USING INDOOR AIR FOR COM-
BUSTION, ALL OF THE MODELS
IMPORTANT: Air should not be taken
from a heated space with a fireplace,
exhaust fan or other device that may
produce a negative pressure.
If combustion air is taken from the heat-
ed area, the openings must each
have at least 100 square inches of
free area. Each opening must have
at least one square inch of free area
for each 1,000 Btuh of total input in
the space. Here are some examples
of typical openings required.
BtuhFree Area
InputEach Opening
100,000100 Square Inches
AIR INTAKE PIPE CONNECTION
(RGPE UPFLOW/HORIZONTAL
ONLY)
A double-elbow may be installed
to top inlet air opening, BUT IS
NOT REQUIRED.This will help to
prevent accidental blockage of
the intake opening. Reference
Figure 9 for proper elbow diameter.
NOTE: Inlet is specifically designed
to prevent material from being pulled
into furnace. If elbows are not used,
the intake opening must be kept
clean and free of debris.
It is also acceptable to run the
condensate drain (or refrigerant)
line access over the air intake
hole as long as a 1" minimum
clearance is maintained.
B. USING OUTDOOR AIR FOR
COMBUSTION, ALL OF THE
MODELS
IMPORTANT: Never take com-
bustion air from an attic space
that is equipped with power
ventilation.
The confined space must communicate with the outdoors
according to Methods 1 and 2.
The minimum air opening dimension shall not be less than 3 inches. When using ducts, they shall
be of the same cross-sectional
area as the free area of the openings to which they connect.
13
FIGURE 9
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTALBLOCKAGE OF
INTAKE OPENING. THIS IS NOT A REQUIREMENT. (SEE
PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED BUT
MAY NOT PREVENT DEBRIS FROM BEING DROPPED
INTO THE FURNACE.
EXHAUST
PVC
DOUBLE
ELBOW
6" MININUM
CLEARANCE
#8 SCREWS
6" MIN.
GROUND OR
SHELF SURFACE
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
METALFLUE
PIPE ONLY
#8 SCREWS
B: Method 1
Provide two permanent openings,
one located within 12 inches of the
top and one located within 12 inches
of the bottom of the enclosure. Each
opening shall communicate directly,
or by ducts, with the outdoors or
spaces (crawl or attic) that freely
communicate with the outdoors.
a. Where directly communicating
with the outdoors or where communicating to the outdoors
through VERTICAL DUCTS, each
opening shall have a minimum
free area of 1 square inch foreach 4000 BTUH of total appliance input rating in the enclosure.
Here are typical duct sizes:
doors through HORIZONTALDUCTS, each opening shall have
a minimum free area of 1 squareinch for each 2000 BTUH of total
input rating for all equipment in
the enclosure. Here are typical
duct sizes:
12 inches of the top of the enclosure,
shall be permitted where the equipment
has clearances of at least 1 inch from
the sides and back and 6 inches from
the front of the appliance. The opening
shall directly communicate with the outdoors or communicate through a vertical or horizontal duct to the outdoors or
spaces (crawl or attic) that freely communicate with the outdoors and have a
minimum free area of:
a. One square inch for each 3000
BTUH of the total input rating of
all equipment located in the
enclosure, AND
b. Not less than the sum of the
areas of all vent connectors in the
confined space.
IMPORTANT: If the furnace is in a
location with an exhaust fan, there
must be sufficient ventilation to prevent the exhaust fan from creating a
negative pressure in the room.
Combustion air openings must NOT
BE RESTRICTED in any manner.
CONSULT LOCAL CODES FOR
SPECIAL REQUIREMENTS.
14
B: Method 3, RGPE only
For the optimum in quiet operation, attic
air may be brought directly to the furnace.
IMPORTANT: In applications using
Method 3 for combustion air, the attic
must be ventilated by gable or soffit
vents. See Figure 8.
It is not required to provide any permanent openings as described in
Method 1
!
or Method 2.
CAUTION
COMBUSTION AIR INTAKES CANNOT BE TERMINATED OUTSIDE.
DOING SO CAN CAUSE IMPROPER
FIGURE 10
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
OPERATION OF THE FURNACE
If attic combustion air is used, the inlet
air opening at the furnace must be protected from accidental blockage. Install
a 90° elbow pointing horizontally at the
top of inlet air pipe. See Figure 11
(maximum of 2, 22
1
⁄2°, 45° or 90°
elbows, allowed).
NOTE: Maximum length of pipe that
may be used for combustion air is
10 feet with two elbows. Lengths of
more than 10 feet can result in nuisance pressure switch trips.
FIGURE 11
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH A 90° ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTALBLOCKAGE
OF INTAKE OPENING.
PVC
ELBOW
EXHAUST
ATTIC SPACE
METALFLUE PIPE ONLY
INDOOR SPACE
10 FT. MAX.
!
CAUTION
12" MIN. FROM
TOP OF INSULATION
INCLUDING
HORIZONTALDIRECTION
#8 SCREW
INSULATION
6" MINIMUM
CLEARANCE
PVC
COUPLER
USE OF SHEET METAL
AIR INTAKE PIPE
INSTEAD OF PVC MAY
RESULT IN NOISE ISSUES.
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
#8 SCREWS
15
VENTING
GENERAL INFORMATION
The furnace must be vented in accordance with these instructions, National
Fuel Gas Code, ANSI Z223.1 and/or
the Natural Gas Installation Code, CSAB149.1 & .2 and requirements or codes
of the local utility or other authority having jurisdiction.
!
WARNING
DEVICES ATTACHED TOTHE FLUE
OR VENT FOR THE PURPOSE OF
REDUCING HEAT LOSS UP THE
CHIMNEY HAVE NOT BEEN TESTED
AND HAVE NOT BEEN INCLUDED IN
THE DESIGN CERTIFICATION OF
THIS FURNACE. WE, THE MANUFACTURER, CANNOT AND WILL NOT BE
RESPONSIBLE FOR INJURY OR
DAMAGE CAUSED BYTHE USE OF
SUCH UNTESTED AND/OR UNCERTIFIED DEVICES, ACCESSORIES OR
COMPONENTS.
DRAFT INDUCER
!
WARNING
VENT PIPE ATTACHING HOLES
MUST BE PREDRILLED IN THE
DRAFT INDUCER COLLAR TO PREVENT DAMAGINGTHE INDUCER.
DRILL 1/8” DIAMETER HOLES
THROUGHTHE VENT PIPE AND
COLLAR AND USE #8 SCREWS TO
ATTACH. SEE FIGURE 12. FAILURE
TO FOLLOWTHIS WARNING CAN
CAUSE RECIRCULATION OF FLUE
PRODUCTS CAUSING CARBON
MONOXIDE POISONING RESULTING
IN PERSONAL INJURY OR DEATH.
FIGURE 12
ATTACHINGTO DRAFT INDUCER COLLAR
FURNACE CATEGORY
INFORMATION
This furnace is shipped as a Category I
type induced draft furnace. A Category
I furnace operates with a nonpositive
vent pressure and has a vent gas temperature at least 140°F above the dew
point of the vent gases. A Category I
type may be a draft hood equipped furnace or have a fan assisted combustion
system (induced draft). The inducer is
used to pull flue products through the
combustion chamber and as they leave
the furnace, most of the energy has
been dissipated. The buoyant effect of
the flue gases provides venting to the
outdoors.
During the off cycle, the inducer is off
and there is very little flow through the
vent, cooling the vent. During the on
cycle there is no dilution airflow, as with
a draft hood type furnace. Although the
vent heats up rapidly without dilution
air, the flue products contain more
water vapor, which results in a higher
dew point temperature. It is most
important that you follow the guidelines in these instructions to prevent the
possible formation of condensation in
the venting system.
As a Category I furnace it may be vented vertically with type B-1 vent pipe and
also may be common vented, as
described in these instructions.
A0991-01
IMPORTANT APPLICTION
NOTES
When the furnace is used as a
replacement, the existing vent system should be inspected to assure
that there are no obstructions, blockage, or any signs of corrosion and is
properly sized for use with this furnace.
NOTE: When the vent table permits
more than one diameter of pipe for a
connector or vent, the smallest permitted diameter must be used.
Vent pipe may be type “B-1,” either
rigid or suitable flexible construction
that carries a u.l. listing.
Common venting is allowed with
vertical B-1 vent systems, and lined
masonry chimneys. Follow the
National Fuel Gas Code, ANSI
Z223.1 and/or the Natural Gas
Installation Code, CSA-B149.1 & .2
for proper installation practices.
NOTE: Follow combustion air
instructions as outlined in this manual.
Single wall vent connectors to “B-1
vent or masonry chimneys” may be
used under the guidelines of the
National Fuel Gas Code, ANSI
Z223.1 and/or the Natural Gas
Installation Code, CSA-B149.1 & .2.
The entire length of the vent connector shall be readily accessible
for inspection, cleaning and
replacement.
16
“B-1” VERTICAL VENTING
Type “B-1” vents must be installed in
accordance with the terms of their listings and the vent manufacturer’s
instructions.
“B-1” vents must be supported and
spaced in accordance with their listings
and the manufacturer’s instructions. All
vents must be supported to maintain
their minimum clearances from combustible material.
VERTICAL VENTING
Categorized
InputSize Required
50K3”
75K*4”
100K*4”
125K*5”
*NOTE: All furnaces have a 3” vent connection as shipped from the factory. A 3” to 4” or
3” to 5” vent transition is required on all but
the 50,000 BTUH models when vertically
vented or common vented with metal vent
pipes. THE VENT TRANSITION CONNEC-
TION MUST BE MADE ATTHE FURNACE
VENT EXIT. It must originate with an adapter
if required, at the furnace flue collar and terminate either in a listed cap or roof assembly. When common venting, the vent connector size may differ from the above diameters depending on application. See ANSI
Z21.47-1993/CSA-2.3-M93 or latest edition
tables.
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the
roof surface with a listed cap or listed
roof assembly. Gas vents 12 inches
in size or smaller with listed caps
shall be permitted to be terminated in
accordance with Figure 13, provided
they are at least 8 feet from a vertical
wall or similar obstruction. All other
gas vents shall terminate not less
than 2 feet above the highest point
where they pass through the roof and
at least 2 feet higher than any portion
of a building within 10 feet.
2. A type B-1 gas vent shall terminate
at least 5 feet in vertical height above
the highest connected equipment
draft hood or flue collar.
3. Must rise
1
/4” per foot away from the
furnace on horizontal runs and be
supported with straps or hangers so
it has no sags or dips. Supports at 4
foot intervals and at all elbows are
recommended.
4. The vent connector must be mechanically fastened to the outlet collar of
the furnace with at least (2) sheet
metal screws except vent connectors
that are B-1 material. These shall be
assembled in accordance with the
manufacturer’s instructions. See
Figure 12.
Furnace Vent
FIGURE 13
TYPICAL VENTING WITH “B-1”VENT
5. Any angle greater than 45 degrees
from the vertical is considered horizontal. The total horizontal distance
of a vent plus the horizontal vent
connector serving draft-hood
equipped appliances shall not be
greater than 75 percent of the vertical height of the vent.
NOTE: Refer to the National Fuel Gas
Code, ANSI Z223.1 and/or the Natural
Gas Installation Code,
CSA-B149.1 & .2.
Single appliance venting of a fan assisted furnace into a tile-lined masonry
chimney is prohibited. The chimney
must be lined with either Type B vent or
with a listed, single wall, metal lining
system. Reference National Fuel Gas
Code, ANSI Z223.1 and/or the Natural
Gas Installation Code, CSA-B149.1 &
.2. See Figure 14 for typical B-1 vent
chase.
!
WARNING
DO NOT CONNECT THIS FURNACETO A CHIMNEY USED TO
VENT A SOLID FUEL APPLIANCE
(WOOD OR COAL).VENTING
WITH A SOLID FUEL APPLIANCE
CAN LEAD TO IMPROPER FUNCTIONING OF THE UNIT, AND DUE
TO SOOTING,THE POSSIBILITY
OF FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
SPECIAL VENT SYSTEMS
(SVS)
IMPORTANT: It is THE FURNACE
MANUFACTURER’s position now
that new
pipe used in a category III vent
application, including Selkirk’s
Selvent™ II HTPV product, should
cease immediately.
installations of any HTPV
17
POWER VENT SYSTEMS
When vertical venting is not possible,
the only acceptable method for horizontal venting is with the use of Tjernlund
model GPAK-1TR or Field Controls
models SWG-4R power venter. Type B
vent pipe and fittings must be used.
Common venting is not permitted
All application and installation
instructions supplied with the power
venter must be followed.
Please address all questions regarding
power venter installation, agency listings and furnace model compatibility to:
Tjernlund Products, Inc.
(800) 255-4208 or (612) 426-2993
Field Controls L.L.C.
(800) 742-8368 or (919) 522-0214
RXGW-B01 CHIMNEY
ADAPTER
IMPORTANT: CHIMNEY ADAPTER IS
CERTIFIED FOR USE ON UPFLOW
(RGPE) ONLY.
This appliance is CSA certified for use
with RXGW-B01 Chimney Adapter.
Refer to Kit Installation Instructions
92-101682-01.
EXISTING VENT SYSTEMS
IMPORTANT RETROFIT
VENTING INSTRUCTIONS
If this furnace is a replacement installation, ALWAYS INSPECT the existing
vent system to be sure there are no
obstructions, blockages, or signs of corrosion.
When the existing furnace is removed
from a venting system serving other
appliances, the venting is likely to be
too large to properly vent the remaining
attached appliances.
The following steps shall be followed
with each appliance that remains connected to the common venting system,
while the other appliances that remain
connected to the common venting systems are not in operation.
NOTE:When the vent table permits
more than one diameter of pipe for a
connector or vent, the smallest permitted diameter must be used.
1. Seal any unused openings in the
common venting system.
2. Visually inspect the venting system
for proper size and horizontal pitch
and determine that there is no blockage, restriction, leakage, corrosion or
other deficiencies which could cause
an unsafe condition.
3. Insofar as is practical, close all building doors, windows and all doors
between the space where the appliances remaining connected to the
common venting system are located.
Turn on clothes dryers and any
appliance not connected to the
common venting system. Turn on
any exhaust fans, such as range
hoods and bathroom exhausts, so
they will operate at maximum
speed. Do not operate a summer
exhaust fan. Close fireplace
dampers.
4. Follow the lighting instructions.
Place the appliance being
inspected into operation. Adjust
the thermostat so the appliance
will operate continuously.
5. Test for spillage at the draft hood
relief opening after 5 minutes of
main burner operation. Use the
flame of a match or candle, or
smoke from a cigarette, cigar, or
pipe.
6. After it has been determined that
each appliance that remains connected to the common venting
system properly vents (when tested as outlined above) return
doors, windows, exhaust fans,
fireplace dampers and any other
gas-burning appliance to their
previous conditions of use.
7. If improper venting is observed
during any of the above tests, the
common venting system must be
resized. Refer to National Fuel
Gas Code, ANSI Z223.1 and/or
the Natural Gas Installation Code,
CSA-B149.1 & .2.
FIGURE 14
DEDICATED VENTING THROUGH
CHIMNEY WITH “B-1”VENT
18
GAS SUPPLY AND PIPING
GAS SUPPLY
!
WARNING
THIS FURNACE IS EQUIPPED ATTHE
FACTORY FOR USE ON NATURAL
GAS ONLY. CONVERSIONTO LP GAS
REQUIRES A SPECIAL KIT AVAILABLE FROMTHE DISTRIBUTOR.
FAILURETO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE,
CARBON MONOXIDE POISONING,
EXPLOSION, PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
See the conversion kit index supplied
with the furnace.This index identifies
the proper LP Gas Conversion Kit
required for each particular furnace.
IMPORTANT: Any additions, changes or
conversions required for the furnace to
satisfactorily meet the application should
be made by a qualified installer, service
agency or the gas supplier, using factory-specified or approved parts. In the
commonwealth of Massachusetts,
installation must be performed by a
licensed plumber or gas fitter for appropriate fuel.
IMPORTANT: Connect this furnace only
to gas supplied by a commercial utility.
IMPORTANT: A U.L. recognized
fuel gas and CO detector(s) are recommended in all applications,
and their installation should be in accordance with the detector manufacturer’s
recommendations and/or local laws,
rules, regulations or customs.
FIGURE 15
GAS PIPING INSTALLATION
MANUAL GAS VALVE
(IN CLOSED POSITION)
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
GAS PIPE INSTALLATION
UPFLOW & DOWNFLOW
UNION
HORIZONTAL
MANUAL GAS VALVE (IN CLOSED POSITION)
FLAME
SENSOR
BURNERS
BURNERS
FLAME SENSOR
DUCT
UNION
GAS VALVE
MANIFOLD
DIRECT SPARK
IGNITOR
GAS PIPING (SEE FIGURE 15)
Install the gas piping according to all
local codes, state codes and regulations
of the utility company, whichever holds
jurisdiction.
If possible, run a separate gas supply
line directly from the meter to the furnace. Consult the local gas company for
the location of the manual main shut-off
valve.The gas line and manual gas
valve must be adequate in size to
prevent undue pressure drop and
never smaller than the pipe size to
the combination gas valve on the furnace. Refer to Table 2 for the recom-
mended pipe size for natural gas and
Table 3 for LP gas pipe sizes.
IMPORTANT: It is permissible to run
flexible gas connector inside the unit to
a piece of black pipe. If local codes
DIRECT SPARK IGNITOR
allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a connector which
has previously serviced another gas
appliance.Massachusetts law limits flexible gas connectors to a maximum of
36”.
Install a ground joint union outside
the cabinet to easily remove the control valve assembly. Install a manual
shut-off valve in the gas line outside
the cabinet. The valve should be readi-
ly accessible to turn the gas supply on
or off. Install a drip leg in the gas supply
line as close to the furnace as possible.
Always use a pipe compound resistant
to the action of liquefied petroleum
gases on all threaded connections.
MANIFOLD
GAS VALVE
IMPORTANT: When making gas
pipe connections, use a back-up
wrench to prevent any twisting of the
control assembly and gas valve.Do
not overtighten the connection.
Any strains on the gas valve can
change the position of the gas orifices in the burners. This can cause
erratic furnace operation.
IMPORTANT: ENSURE that the fur-
nace gas control valve not be subjected to high gas line supply pressures.
DISCONNECT the furnace and its
individual shut-off valve from the gas
supply piping during any pressure
testing that exceeds 1/2 PSIG (14”
W.C.) (3.48 kPa).
19
GAS PRESSURE
IMPORTANT: Natural gas supply pressure should operate between 5" to
10.5”w.c. LP gas supply pressure
should be 11” to 13” w.c. This pressure
must be maintained with all other
gas-fired appliances in operation.
NOTE: Do not exceed a gas pressure
of 13” w.c.
WARNING
!
ELEVATIONS ABOVE 2000 FT
REQUIRETHATTHE FURNACE INPUT
RATING BE ADJUSTED ANDTHAT
THE SIZE OFTHE BURNER ORIFICES BE RE-CALCULATED BASED
ON ELEVATION AND GAS HEATING
VALUE.THE BURNER ORIFICES MAY
(OR MAY NOT) NEED TO BE
CHANGED.SEE THE SECTION
TITLED“HIGH ALTITUDE INSTALLATIONS” OF THIS BOOK FOR
INSTRUCTIONS.
WARNING
!
NEVER PURGE A GAS LINE INTO
THE COMBUSTION CHAMBER.
NEVER USE MATCHES, FLAME OR
ANY IGNITION SOURCE FOR
CHECKING LEAKAGE.FAILURETO
FOLLOWTHIS WARNING CAN
CAUSE AN EXPLOSION OR FIRE
RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.
To check for gas leakage, use an
approved chloride-free soap and water
solution, or other approved method.
LP CONVERSION
NOTE: For installation, see specific LP
kit installation instructions. Orifice must
be ordered for the correct elevation.
NOTE:Order the correct LP conversion
kit from the local distributor. Furnace
conversion to LP gas must be performed by a qualified technician.
More information found in the high altitude and orifice section.
NOx MODELS
When converting furnaces equipped
with NOx inserts to LP gas, remove
the NOx insert assemblies. Steps for
removal are listed below:
1. Turn off all electrical power and
the gas supply to the furnace.
2. Remove the burner door from
the furnace.
3. Remove the igniter assembly –
handle with care.
4. Remove the two screws attaching the NOx insert retainer
brackets to the center panel.
Pull the retainer rod.
5. Put the two screws back into the
holes in the center panel.
6. Re-install the igniter and burner
assemblies.
7. Replace burner door.
8. Turn on electrical power and
gas supply to the unit.
NOTE:Some NOx models may have
one less NOx insert.
20
SETTING GAS PRESSURE
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
NominalLength of Pipe, FeetIron PipeSize, Inches102030405060708090100125 150
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
The maximum gas supply pressure to
the furnace should be 10.5” w.c. natural gas, or 13” w.c. LP gas. The minimum supply gas pressure to the gas
valve should be 5" w.c. natural gas or
11" w.c. LP gas. A properly calibrated
manometer is required for accurate gas
pressure measurements.
Supply Gas Pressure Measurement.
A line pressure tap is on the inlet side
of the gas valve.
1. With gas shut off to the furnace at
the manual gas valve outside the
unit, remove the input pressure
tap plug.
2. Connect a U-Tube manometer to
the pressure tap.
3. Turn on the gas supply and operate the furnace and all other gasfired units on the same gas line as
the furnace.
4. Adjust the line gas pressure to
supply:
A. 5” - 10.5” w.c. for natural gas.
B. 11” - 13” w.c. for LP gas.
5. Shut off the gas at the manual gas
valve and remove the
U-Tube manometer.
6. Replace the pressure tap plug.
7. Turn gas on, and check for leaks.
NATURAL GAS:
If the supply gas line pressure is above
the operating range, install an in-line
gas regulator to the furnace. If supply
gas line pressure is below the operating range, either remove any restrictions in the gas supply piping or
enlarge the gas pipe. See Table 2.
LP GAS:
If the supply gas line pressure is above
the operating range, have the LP supplier reduce the line pressure at the
regulator. If supply gas line pressure is
below operating range, have the LP
supplier adjust the line pressure at the
regulator. See Table 3.
NOTE: Depending on the amount of
LP vapor and the outdoor ambient temperature, the LP storage tank may
require supplemental heat to maintain
proper pressure levels. Ensure LP storage tank does not drop below 15%
capacity during heating season.
FIGURE 16
TYPICAL HOSE CONNECTION TO LINE PRESSURETAP
TABLE 2
NATURALGAS PIPE CAPACITYTABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
gravity of 0.60 (natural gas).
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per
hour required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required=
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be
determined by consulting the local natural gas utility or the LP gas supplier.
Gas Input of Furnace (BTU/HR)
Heating Value of Gas (BTU/FT3)
TABLE 3
LP GAS PIPE CAPACITYTABLE (CU.FT./HR.)
21
ADJUSTING OR CHECKING
FURNACE INPUT
NATURAL GAS:
The maximum gas supply pressure to
the furnace should be 10.5” W.C. for
natural gas. The minimum gas supply
pressure for purposes of input adjustment to the furnace should be 5” W.C.
A properly calibrated manometer or
gauge is required for accurate gas
pressure readings.
1. When adjusting the furnace input,
the high fire input should be
checked. The high fire manifold pressure should be 3.5' W.C. Follow
these steps to be sure the furnace is
high fire mode:
a. With a single stage thermostat,
the furnace runs for 12 minutes on
low fire before shifting to high fire.
To be certain that it is on high fire,
jump terminals “W” and “W2” on
the control board in the blower
compartment.
b. With a two stage thermostat, set
the thermostat to its highest setting to keep the furnace operating
in the high fire mode.
2. To adust high fire manifold pressure,
remove the adjustment cover screw
on the outlet end of the gas valve
and turn the adjustment screw clockwise to increase the pressure and
counterclockwise to reduce the pressure. Replace the cover screw
securely.
3. The low fire manifold pressure
should be 1.7" W.C. As mentioned
above, the furnace remains in the
low fire mode for 12 minutes upon a
heat call with a single stage thermostat. With a two stage thermostat,
disconnect the thermostat lead to the
“W2” terminal on the control board
and the furnace will remain in the low
fire mode. To adjust the pressure,
remove the regulator cover, on top of
the valve, and adjust as noted under
Step 2, above. After the adjustment
replace the screw cover securely.
NOTE: Use a 3/32⬙ allen wrench for
making the pressure adjustment.
LP GAS:
Furnaces for use on LP gas, the LP gas
supply pressure must be set between
11.0” and 13.0” W.C. by means of the
tank or branch supply regulators. The
furnace manifold pressure should be
set at 10” W.C. at the gas control valve.
For elevations up to 7,000 feet, rating
plate input ratings apply. For high altitudes (elevations 7,000 and over) and
for any necessary major changes in the
gas flow rate the orifice spud must be
changed.
TO CHANGE ORIFICE SPUDS:
1. Shut off the manual main gas valve
and remove the gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and
check for leaks.
5. Check for proper operation and set
to proper manifold pressure.
TABLE 4
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS
Heating Value of Gas (BTU/Ft3) x 3600 x correction factor
Time in Seconds (for 1 cu.ft.) of Gas
HEATING VALUE OF GAS BTU PER CU. FT.
9001000104011002500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
Check of input is important to prevent over firing of the furnace
beyond its design-rated input.
NEVER SET INPUT ABOVE THAT
SHOWN ON THE RATING PLATE.
TO CHECK FURNACE INPUT:
1. Make certain that all other gas
appliances are shut off, with the
exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the
time required to burn one cubic
foot of gas.
4. Use Table 4 to determine input
rate.
22
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT
FUSE BOX OR SERVICE PANEL
BEFORE MAKING ANY ELECTRICAL CONNECTIONS. FAILURETO
DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
!
THE CABINET MUST HAVE AN
UNINTERRUPTED GROUND
ACCORDINGTO THE LATEST
EDITION OF THE NATIONAL
ELECTRICAL CODE, ANSI/
NFPA70-, OR IN CANADA,THE
CANADIAN ELECTRICAL CODE,
CSA-C22.1 OR LOCAL CODES
THAT APPLY. A GROUND SCREW
IS PROVIDED IN THE JUNCTION
BOX. FAILURE TO PROPERLY
CONNECTTHE GROUNDWIRE
CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
ate wiring diagramlocated on the inside
cover of the furnacecontrol box and in
these instructions.
NOTE:The electrical junction box may
be moved to the right sideif necessary. A
knockout is provided.Seal the opposite
holewith plugprovided.
WARNING
!
L1TERMINAL AND NEUTRALTERMINAL POLARITY MUST BE OBSERVED
WHENMAKINGFIELD CONNECTIONS
TOTHE FURNACE. FAILURETO DO
SOWILL EXPOSE LIVEWIRING IN
THE BLOWER COMPARTMENTWHEN
THE DOOR IS REMOVED.TOUCHING
THESE LIVE CIRCUITS COULD
RESULT IN PERMANENT INJURY OR
DEATH FROMELECTRICALSHOCK.
FIGURE 17
JUNCTION BOX LOCATION
UPFLOW/HORIZONTAL
Make all electrical connections in
accordance with the latest edition of
the National Electrical Code
ANSI/NFPA70 – or in Canada, the
Canadian Electrical Code Part 1CSA Standard C22.1 and local codes
having jurisdiction.
These may be obtained from:
National Fire Protection
Association, Inc.
Batterymarch Park
Quincy, MA 02269
Canadian StandardsAssociation
178 Rexdale Boulevard
Rexdale, Ontario, Canada M9W 1R3
WARNING
!
THIS FURNACE IS EQUIPPED
WITH A BLOWER DOOR SAFETY
SWITCH. DO NOT DISABLETHIS
SWITCH. FAILURETO FOLLOW
THISWARNING CAN RESULT IN
ELECTRICAL SHOCK, PERSONAL INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical components are protected from water.
A grounding wire is provided to connect
to the incoming grounding wire from
line power. The furnace must be permanently grounded in accordance with all
national and local codes.
Before proceeding with the electrical
connections, be certain that the service
panel voltage, frequency and phase corresponds to that specified on the furnace rating plate. Maximum over-current
protection is 15 amperes.
Use a separate,fused branch electrical
circuitcontaininga properly sizedfuse or
circuitbreaker. Connect this circuitdirectly
fromthe main switchbox to an electrical
disconnect that is readily accessible and
locatedwithin arm’s reach (2 ft.)of the
furnace. Connect fromthe electrical disconnectto the junction boxon the left
sideof the furnace, inside the blower
compartment. See Figure 17.For the
proper connection,refer to the appropri-
DOWNFLOW
23
ELECTRICAL CHECKS
Line Power Check
The furnace must have a nominal 115
volt power supply for proper operation. If there is not a consistent power
supply, contact a licensed electrician
to correct the problem.
1. With the blower compartment door
off, manually hold the push button
door switch in.
2. Call for heat at the thermostat.
3. With the unit operating, use a voltmeter to measure the voltage from
any 120 VAC terminal to any neutral connection.
4. The voltage should be a nominal
115 volts (acceptable 105120VAC).
This test should be made with the unit
in full operation.
Polarity Check
If line & neutral are reversed, a fault
code (26) will be displayed at the furnace seven segment display (SSD)
and at the communicating thermostat
active fault display screen (communicating systems only).
Proper line voltage polarity, or phasing, is a must for this furnace to operate. Use a volt meter to make this
check.
1. With the blower compartment door
off, manually hold the push button
door switch in.
2. Use a voltmeter to measure the
voltage from any 120 VAC terminal
to any bare metal ground on the
furnace.
3. The voltage should be a nominal
115 volts (acceptable 105120VAC).
4. Use a voltmeter to measure the
voltage from any neutral terminal
to the bare metal ground on the
furnace.
5. The voltage should be less than
1.0 VAC.
6. If the voltage from any 120 VAC
terminal to ground is less than 1.0
VAC volts and the voltage from a
neutral to ground is a nominal 115
volts, the polarity is reversed.
7. To correct the problem, either
reverse the hot and neutral wires
to the furnace or have a licensed
electrician check the building
wiring.
ControlVoltage Check
1. With the blower compartment door
off, manually hold the push button
door switch in.
2. Call for heat at the thermostat.
(Does not include communicating
thermostats.)
3. With the unit operating, use a voltmeter to measure the voltage from
control voltage terminal “W” to terminal “C” on the furnacecontrol
board.
4. The voltage should be a nominal 24
volts (Acceptable 18-30 VAC).
This test should be made with the unit
in full operation.
24
ACCESSORIES
FIELD-INSTALLED
OPTION ACCESSORIES
TWINNING: Most installations of (-)GPE/
(-)GLE furnaces cannot be twinned.
However, a few exceptions exist for
installations with some commercial
evaporator coils. Consult the installation
instructions of the coil to see if the furnace(s) can be twinned. If so, a twinning
kit will be required and the part number
for the kit can be found in the installation
instructions for the coil.
ELECTRONIC AIR CLEANER
Line voltage power is supplied from the
screw terminal “EAC”, see Figure 18,
and a line voltageneutral screw terminal
on the control board. This will power the
electronic air cleaner whenever the
blower is operating and delivering the
recommended minimum CFM. The 50
and 75 KBTU models, which are capable of a maximum delivery of 1200 CFM,
will operate the electronic air cleaner at
500 CFM and above. The 100 and 120
KBTU models, which are capable of a
maximum delivery of 2000 CFM, will
operate the electronic air cleaner at 800
CFM and above. These limits are set to
prevent excessive production of ozone
at the lower airflows of the furnaceand
are based on average requirements of
commercially available electronic air
cleaners.
Continuous fan speeds are selectable
and some lower fan speeds may not
deliver enough airflow to operate an
electronic air cleaner. The IFC determines the minimum airflow necessary to
operate an electronic air cleaner and will
not turn on the electronic air cleaner
unless the airflow is high enough for the
EAC.
FIGURE 18
EAC AND HUMIDIFIER TERMINALS ON FURNACE CONTROL (IFC)
HUMIDIFICATION AND DEHUMIDIFICATION
HUMIDIFIER – The humidifier contacts
(labeled “HUM OUT”) are “dry” contacts
on the I.F.C. This means that the terminals are connected directly to the contacts of a board-mounted relay. The
coil of the relay is controlled by the
microprocessor of the IFC. The coil is
engaged roughly any time the heat
speed blower is engaged and (1)
24VAC is present on the thermostat terminal of the IFC labeled “HUM STAT” or
(2) a communicating thermostat with
humidification and dehumidification
capability is installed with call for
humidification present.
FIGURE 19
WIRING FOR OPTIONAL HUMIDIFICATION (AND DEHUMIDIFICATION WITH COMMUNICATING
THERMOSTAT) WITH OPTIONAL HUMIDIFIER AND NO HUMIDISTAT (HUMIDIFICATION ACTIVE
DURING ANY HEAT CALL) (FOR USE WITH COMMUNICATING AND NON-COMMUNICATING
THERMOSTATS)
FIGURE 20
WIRING FOR OPTIONAL DEHUMIDIFICATIONWITH HUMIDIFICATION (WITH OPTIONAL
HUMIDISTAT AND HUMIDIFIER)
NOTE: CAN BE USED WITH COMMUNICATING OR
NON-COMMUNICATING SYSTEMS
An optional 24VAC humidistat can
be installed as shown in Figures 19
thru 54 (II thru IV). With the optional
humidistat, two separate conditions
must be met before humidification
can begin 1). There must be a call
for heat and the blower must be
engaged and 2.) The humidistat
must determine that there is a need
for humidification.
Note: Dipswitch SW2-1 (labeled
“ODD”) enables (“ON”) or disables
(“OFF”) dehumidification operation.
However, it has no affect on humidification operation. If this switch is
set to the “ON” position and no
humidistat is installed, the cooling
25
FIGURE 21
WIRING FOR OPTIONAL DEHUMIDIFICATION OPERATION AND HUMIDIFICATION WITH
OPTIONAL HUMIDIFIER (HUMIDIFIER WITH INTERNAL POWER SUPPLY) (FOR USE WITH
NON-COMMUNICATINGTHERMOSTATS)
FIGURE 22
HUMIDISTAT USEDTO CONTROL DEHUMIDIFICATION IN COOLING ONLY (NO HUMIDIFIER)
(FOR USE WITH NON-COMMUNICATINGTHERMOSTATS)
airflow will be permanently reduced by
approximately 15% giving less than
optimal performance and possibly causing problems. It is not recommended to
leave this switch in the “ON” position
without a humidistat installed.
Control of dehumidification in cooling
and/or humidification in heating can be
done with a variety of methods depending on whether there is a communicating thermostat or a humidistat available
and depending on the type of operation
desired.
With systems configured with communicating thermostats and condensers,
dehumidification is controlled by the
condenser and is not affected by the
position of dipswitch SW2-1 or the voltage (or lack of voltage) at the thermostat terminal labeled “HUM STAT”.
To determine which wiring diagram and
method to use, select from the following
configurations:
A. HUMIDIFICATION CONTROL ONLY
WITH NO DEHUMIDIFICATION
(REQUIRES OPTIONAL HUMIDIFIER).
A1. WITH COMMUNICATING
THERMOSTAT
Humidifier control is included
with the (-)HC-TST412MDMS
(modulating, non-communicating) and (-)HC-TST550CMMS
(full-color communicating)
model thermostats. However, it
is not included with the (-)HCTST501CMMS model communicating thermostat. The latter
thermostat should not be used
if humidification control is
required. To wire the furnace
for humidification control using
the former thermostat, refer to
the wiring diagram in Figure
19(I). Be sure not
to install the
jumper between “R” and “HUM
STAT” on the furnace control. Installing this jumper
will operate the humidifier
any time there is a heat call.
Without the jumper, the
humidification call from the
thermostat must be active
and a heat call must be present with the blower running.
A2. WITH NON-COMMUNICAT-
ING THERMOSTAT
A2-1 CONTINOUS HUMID-
IFIER OPERATION
DURING HEATING.
For continuous humidifier operation during
heating, refer to
Figure 19 (I) and
make sure to install
the jumper between
the thermostat terminals labeled “R” and
“HUM STAT”. A separate humidistat is not
required for this configuration and the
humidifier will turn on
whenever there is a
call for heat and the
blower is running.
A2-2 CONTROLED
HUMIDIFIER OPERATION USING A
HUMIDISTAT
(REQUIRES OPTIONAL HUMIDISTAT).
Controlled humidification can be accomplished using a
humidistat as shown
in Figures 20 (II) or 21
(III). These figures
show installation of a
humidifier with external and internal power
supplies respectively.
Dehumidification operation will be disabled if
the dipswitch SW2-1
is in the “OFF” position. If this switch is in
the “ON” position,
dehumidification control will be active.
B. DEHUMIDIFICATION CONTROL
WITH NO HUMIDIFICATION
B1. For communicating ther-
mostats listed with this furnace, dehumidification is
controlled automatically
when selected at the thermostat and additional wiring
is not necessary. The actual
airflow demand (reduced for
dehumidification) is requested of the furnace by the
condenser.
26
B2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES
OPTIONAL HUMIDISTAT).
Control of dehumidification only
(no humidification) can be
accomplished by installing an
optional humidistat as shown in
Figure 22 (IV). The dipswitch
SW2-1 must be set to the “ON”
position. If this switch is not
turned “ON”, dehumidification
operation will not take place.
Further, if this switch is “ON”
and no humidistat is installed,
airflow in cooling will be permanently reduced by approximately 15%.
C. HUMIDIFICATION AND DEHUMIFI-
CATION CONTROL
(REQUIRES OPTIONAL HUMIDIFIER).
C1. WITH COMMUNICATING
THERMOSTAT
Humidifier control is included
with the (-)HC-TST412MDMS
(modulating, non-communicating) and (-)HC-TST550CMMS
(full-color communicating)
model thermostats. However, it
is not included with the (-)HCTST501CMMS model communicating thermostat. Do not
purchase the latter thermostat if
humidification control is
required. To wire the furnace
for humidification and dehumidification control using the former
thermostat, refer to the wiring
diagram in Figure 19 (I). Be
sure not
between “R” and “HUM STAT”
on the furnace control.
Installing this jumper will operate the humidifier any time
there is a heat call and dehumidification will never take
place when in cooling. Without
the jumper, a humidification call
from the thermostat must be
active and a heat call must be
present with the blower running
for the “HUM OUT” relay contacts to close.
C2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES
OPTIONAL HUMIDISTAT.)
For non-communicating thermostats, an optional humidistat
must be installed. Controlled
humidification and dehumidification can be accomplished
using a humidistat as shown in
Figures 20 (II) or 21 (III).
These figures show installation
of a humidifier with external and
internal power supplies respectively. Dehumidification operation will be disabled if the dipswitch SW2-1 is in the “OFF”
position. If this switch is in the
“ON” position, dehumidification
control will be active.
OTHER ACCESSORIES
AVAILABLE
FOSSIL FUEL KIT (non-communicat-
ing systems only)
Use of a heat pump with the two stage
furnace requires a heat pump thermostat
used in conjunction with the fossil fuel
kit. For proper operation use the following procedures:
a. With the RXPF-F01 kit, connectthe
thermostat “E” terminal, one side of
the plenum switch, and the black wire
from the fossil fuel kit to “W2” on the
IFC.
b. For the RXPF-F02 kit, connect
“W” on the fossil fuel kit interface
wiring board to “W2” on the IFC.
Regardless of which fossil fuel kit is
used, when activated, the two stage
furnace follows the sequence of
operation for a single stage thermostat.
➢ IMPORTANT: ALWAYS FOLLOW
THE MANUFACTURER’S FOSSIL
FUEL KIT INSTRUCTIONS.
TWINNING: Most installations of
(-)GPE and (-)GLE furnaces cannot
be twinned. However, a few exceptions exist for installations with some
commercial evaporator coils. Consult
the installation instructions of the coil
to see if the furnace can be twinned.
If so, a twinning kit will be required
and the part number for the kit can
be found in the installation instructions for the coil.
RXGW-B01 CHIMNEY
ADAPTER
IMPORTANT: Chimney adapter is
certified for use on upflow only.
This appliance is CSA certified for
use with RXGW-B01 chimney
adapter. Refer to kit installation
instructions
92-101682-01.
TYPICAL WIRING FOR
SELECT ACCESSORIES
FOR COMMUNICATING
RESIDENTIAL SYSTEMS
The Rheem Serial Communicating
(CC2) system allows accessories to
be connected to shut down the system in the event of a fault. Typical
devices that can be connected are
the drain overflow switch, smoke
detector and freeze protection
switch. There are two methods of
connecting the switch to the system
depending on the device configuration normally closed or normally
open. The blower can run during a
fault or the blower can shut off during a fault depending on how the
system is connected. Please refer to
local and/or state codes for installing
these devices. The following operation applies only when BOTH the
condenser and thermostat are serial
communicating devices. If the condenser is non-communicating (traditional, legacy 24VAC controlled) this
diagram is not valid.
27
METHOD BLOWER
ACTIVATION
CONTACTS WIRING CONFIGURATION
NORMALLY
OPEN
When 24 VAC is applied to Y1 at the furnace control in a
communicating system a SYSTEM BUSY message appears on
the thermostat. When the SYSTEM BUSY message appears the
outdoor unit will shut down and the indoor unit will continue
to run at first stage cooling airflow.
A
BLOWER
RUNS
(Y1)
NORMALLY
CLOSED
If the device does not have normally open contacts an
additional relay must be used for proper system operation.
NORMALLY
OPEN
When the device is connected to Y2 and a fault occurs the
blower will shut down. The Y2 input can still be used with
normally open or normally closed contacts.
B
BLOWER
DOES NOT
RUN
(Y2)
NORMALLY
CLOSED
If the device does not have normally open contacts an
additional relay must be used for proper system operation.
OPERATION WITH SELECTED ACCESSORIES
28
80+ HIGH ALTITUDE
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT
INPUT RATING FOR INSTALLATION AT ALTITUDES
BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION
DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
D'ALTITUDE.
92-24399-01-01
INSTRUCTIONS (TABLE 13)
!
CAUTION
INSTALLATION OFTHIS FURNACE
AT ALTITUDES ABOVE 2000 FT (610
m) SHALL BE IN ACCORDANCE
WITH LOCAL CODES, OR IN THE
ABSENCE OF LOCAL CODES,THE
NATIONAL FUEL GAS CODE, ANSI
Z223.1/NFPA 54 OR NATIONAL STANDARD OF CANADA, NATURAL GAS
AND PROPANE INSTALLATION
CODE, CAN B149.1.
Furnaces can be ordered from the factory already converted for high altitude
elevations. The factory option for high
altitude elevations would be ordered as
a 278 option (example: a 75k BTU
upflow furnace which is factory converted for high altitude elevations would
have the model number (-)GPE07EAMKR). These factory converted
furnaces come with pressure switches
for high-altitude elevations already
attached. Also, different burner orifices
are installed at the factory which are
one drill size smaller (#43 DMS) than
standard (-)GPE/(-)GLE gas furnaces
(#42 DMS). The smaller orifice is
installed to accommodate for average
heating values expected in most high
altitude areas and a required 4% per
thousand feet reduction in input as
specified by the National Fuel GasCode (NFGC). Specific orifices should
always
be recalculated for all high altitude installations as outlined below.
Orifices should be changed, if necessary, based on gas heating value and
elevation.
34" 80 Plus furnaces installed above
2,000 ft. require the furnace to be derated 4% per thousand feet.
IMPORTANT: Factory installed orifices
are calculated and sized based on a
sea level Natural Gas heating value of
1075 BTU per cubic ft.
NOTE:Orifices are available through
your local distributor.
Reference Tables 11, 12 and 13 for
appropriate orifice sizing.
NOTE:Keep any parts removed during
LP conversion procedure stored with the
product literature for future use.
The following are examples of orifice
sizing using the National Fuel Gas Code
Appendix F:
Example: 900 BTU/ft
Natural Gas Heating Value
I/H = Q
25000 / 900 = 27.78 ft
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 900
Q = 27.78 ft
3
Natural Gas per hour.
From Table F.1 of National Fuel GasCode Handbook, 2002 (3.5ⴖ w.c. col-
umn).
Orifice required at Seal Level: #40
From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4%
de-rate per thousand ft): #42
3
Regional
3
Orifice required at 8000 ft. elevation (4%
de-rate per thousand ft.): #44
TABLE 11
LP GAS
Example: 1050 BTU/ft3 Regional
Natural Gas Heating Value
I / H = Q
25000 / 1050 = 23.81ft
3
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 1050
Q = 23.81 ft
3
Natural Gas per hour.
From Table F.1 of Natural Fuel GasCode Handbook, 2002 (3.5⬙ w.c. col-
umn).
Orifice required at Sea Level: #43
From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4%
de-rate per thousand ft.): #45
Orifice required at 8000 ft elevation (4%
de-rate per thousand ft): #47
LP GAS (TABLE 11)
LP Gas is a manufactured gas that has
consistent heating value across most
regions.
The NFGC guidelines are used with the
following exception:
The recommended LP Gas high altitude
orifice selections differ slightly in that the
NFGC LP orifice chart, as they are not
accurate for Rheem products. The
National Fuel Gas Code LP orifices are
based on an 11" of water column pressure at the orifice, which differs from
products that use 10" of water column
at the orifice. This difference requires a
deviation from the NFGC orifice size
recommendations. The Sea Level input
sand ft. and the orifice size must be
selected based on the reduced input
in Table 11.
ORIFICE ORDERING
INFORMATION
Orifice sizes are selected by adding
the 2-digit drill size required in the
orifice part number. Drill sizes available are 39 through 64; metric sizes
available 1.10mm (-90) and 1.15mm
(-91):
Orifice Part Number 62-22175-(drill
size)
Example 1:
# 60 drill size orifice required
Part # 62-22175-60
Example 2:
1.15mm drill size orifice required
Part # 62-22175-91
should still be reduced by 4% per thou-
TABLE 12
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE
NATURAL GASLP GAS
ORIFICE
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
50,000
75,000
100,000
125,000
150,000
45,000
67,500
90,000
112,500
135,000
OUTPUT
40,000
60,000
80,000
100,000
120,000
36,000
54,000
72,000
90,000
108,000
SIZE
#42
#42
MANIFOLD
PRESSURE
3.5” W.C.
2.9” W.C.
ALTITUDE
0’ - 2000’
2001’ - 4500’
FIGURE 23
MANIFOLD PRESSURE-CHANGE LABEL
INPUT
50,000
75,000
100,000
125,000
150,000
45,000
67,500
90,000
112,500
135,000
Input (perOrifice
ORIFICE
OUTPUT
40,000
60,000
80,000
100,000
120,000
36,000
54,000
72,000
90,000
108,000
SIZE
#54
#54
MANIFOLD
PRESSURE
10” W.C.
8.1” W.C.
29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.