Rheem RGPE series, RGLE series Installation Instructions Manual

INSTALLATION INSTRUCTIONS
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISON­ING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PROPOSITION 65 WARNING: THIS PRODUCT CONTAINS CHEMICALS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
— Do not store or use gasoline or other flammable vapors and liquids, or other combustible materials
in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— DO NOT RELY ON SMELL ALONE TO DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT
BE ABLE TO SMELL FUEL GASES.
• U.L. recognized fuel gas and CO detectors are recommended in all applications, and their installa­tion should be in accordance with the manufacturer’s recommendations and/or local laws, rules regulations, or customs.
— Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
ISO 9001:2008
FOR RGPE UPFLOW, HORIZONTAL, RGLE DOWNFLOW 2 STAGE, 80+ GAS FURNACES
COMMUNICATING
THERMOSTATS
INSTALLATION
SEE PAGE 84
This Memory Card must be removed (broken away) from the furnace control when the control is replaced. The card must be inserted into the connector at J15 of the replacement con­trol. Failure to retain this memory card with the furnace when replacing the furnace control could result in no operation when the furnace control is replaced.
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN 2 OR MORE DIFFERENT FURNACES. DOING SO COULD RESULT IN UNEXPECTED OPERATION – INCLUDING INADEQUATE AIRFLOW DUR­ING HEATING (AND OTHER MODES) OR A LOSS OF HEAT.
SUPERSEDES 92-24161-77-01
92-24161-77-02
IMPORTANT: All Manufacturer products
meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain prod­ucts, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facili­tates manufacturing and shipping. We cannot always know “when, or if” prod­ucts will be sold in the California market.
You may receive inquiries from cus­tomers about chemicals found in, or pro­duced by, some of our heating and air­conditioning equipment, or found in nat­ural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene More details are available at the
Websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov
and the State of California's OEHHA(Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most con­sumers are aware that products present safety and health risks, when improperly used, handled and maintained.
Installation Instructions are updated on a regular basis. This is done as product changes occur or if new information becomes available. In this publication, an arrow denotes changes from the previous edition or additional new mater­ial.
IMPORTANT: To insure proper installa­tion and operation of this product, com­pletely read all instructions prior to attempting to assemble, install, operate, maintain or repair this product. Upon unpacking of the furnace, inspect all parts for damage prior to installation and start-up.
TABLE OF CONTENTS
SAFETY INFORMATION..........................................................................................................................................3
INSTALLATION CHECK LIST...................................................................................................................................5
GENERAL INFORMATION.......................................................................................................................................6
IMPORTANTINFORMATION ABOUT EFFICIENCYANDINDOORAIR QUALITY...................................6
RECEIVING.....................................................................................................................................................7
LOCATION REQUIREMENTSANDCONSIDERATIONS.......................................................................................7
LOCATION.......................................................................................................................................................7
CLEARANCE-ACCESSIBILITY....................................................................................................................10
SITE SELECTION.........................................................................................................................................10
DUCTING......................................................................................................................................................10
COMBUSTIONAND VENTILATION AIR ...............................................................................................................12
COMBUSTIONAIR REQUIREMENTS........................................................................................................12
VENTING.................................................................................................................................................................16
GENERAL INFORMATION...........................................................................................................................16
DRAFTINDUCER.........................................................................................................................................16
FURNACE CATEGORY INFORMATION.....................................................................................................16
IMPORTANTAPPLICATIONNOTES...........................................................................................................16
B-1 VERTICALVENTING.............................................................................................................................17
SPECIAL VENT SYSTEMS..........................................................................................................................17
POWERVENT SYSTEMS...........................................................................................................................18
EXISTING VENT SYSTEMS........................................................................................................................18
GAS SUPPLYAND PIPING....................................................................................................................................19
GAS SUPPLY................................................................................................................................................19
GAS PIPING..................................................................................................................................................19
GAS PRESSURE..........................................................................................................................................20
LP CONVERSION.........................................................................................................................................20
SETTING GAS PRESSURE.........................................................................................................................21
ADJUSTING OR CHECKINGFURNACE INPUT.......................................................................................22
ELECTRICALWIRING............................................................................................................................................23
ELECTRICALCHECKS........................................................................................................................24
ACCESSORIES.......................................................................................................................................................25
FIELDINSTALLEDOPTIONACCESSORIES............................................................................................25
OTHERACCESSORIES AVAILABLE..........................................................................................................27
RXGW-B01 CHIMNEYADAPTER...............................................................................................................27
TYPICAL WIRING FOR SELECTACCESSORIESFOR COMMUNICATING RESIDENTIAL
SYSTEMS............................................................................................................................................27
80+ HIGH ALTITUDE INSTRUCTIONS.......................................................................................................29
LP GAS..........................................................................................................................................................29
ORIFICE ORDERING INFORMATION........................................................................................................29
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE......................................................29
AIRFLOW.................................................................................................................................................................31
INTEGRATED FURNACE CONTROL...................................................................................................................33
24 VAC THERMOSTAT INPUTS..................................................................................................................33
SPECIAL CONFIGURATION–COMMUNICATINGTHERMOSTATW/NON-COMM. CONDENSER......34
24 VAC FROM TRANSFORMERCONNECTIONS....................................................................................34
FUSE.............................................................................................................................................................34
115 VAC TERMINALS...................................................................................................................................34
INDUCED DRAFTMOTOROUTPUT.........................................................................................................34
NEUTRALTERMINALS................................................................................................................................35
ELECTRONICAIR CLEANER OUTPUT.....................................................................................................35
HUMIDIFIEROUTPUT.................................................................................................................................35
15-PIN MATE-N-LOK CONNECTOR...........................................................................................................35
COMMUNICATING ECM MOTOR COMMUNICATIONS CONNECTION.................................................36
SPARK IGNITIONTRANSFORMER...........................................................................................................37
R-J11 CONNECTOR.....................................................................................................................................37
COMMUNICATIONS NETWORK CONNECTION......................................................................................37
COMMUNICATIONS L.E.D.’S......................................................................................................................37
LEARNBUTTON...........................................................................................................................................38
MEMORY CARD CONNECTOR..................................................................................................................38
MEMORY CARD...........................................................................................................................................38
REPLACINGTHE FURNACE CONTROL...................................................................................................41
DIPSWITCHES.............................................................................................................................................44
SW1...............................................................................................................................................................44
SW2...............................................................................................................................................................46
FURNACE OPERATION USINGNON-COMMUNICATING SIINGLE-STAGE AND TWO-STAGE
THERMOSTATS......................................................................................................................................46
SW3-1AND SW3-2.......................................................................................................................................47
BIAS / TERMINATION ..................................................................................................................................48
DUALSEVEN-SEGMENT DIAGNOSTICDISPLAY ...................................................................................48
FAULT CODE BUFFER................................................................................................................................48
CLEARING DIAGNOSTICFAULT CODES FROM THE BUFFER.............................................................48
COMMUNICATING SYSTEMS....................................................................................................................49
START-UP PROCEDURES....................................................................................................................................57
IGNITOR PLACEMENT, ALIGNMENT& LOCATION.................................................................................57
TO START THE FURNACE..........................................................................................................................57
TO SHUT DOWN THE FURNACE..............................................................................................................57
SEQUENCE OF OPERATION.....................................................................................................................57
ADJUSTING OR CHECKINGFURNACE INPUT.......................................................................................59
MAINTENANCE.......................................................................................................................................................60
FILTERS ........................................................................................................................................................60
SYSTEM OPERATION INFORMATION......................................................................................................62
ANNUAL INSPECTION................................................................................................................................62
LUBRICATION...............................................................................................................................................62
REPLACEMENTPARTS..............................................................................................................................62
NOx MODELS...............................................................................................................................................62
TROUBLESHOOTING............................................................................................................................62-63
WIRING DIAGRAM.......................................................................................................................................79
THERMOSTATS......................................................................................................................................................80
NON-COMMUNICATINGTHERMOSTATS.................................................................................................80
SEQUENCE OF OPERATION.....................................................................................................................80
COMMUNICATING THERMOSTATS.....................................................................................................................84
2
SAFETY INFORMATION
IMPORTANT!
THE COMMONWEALTH OF MASSA­CHUSETTS REQUIRES COMPLIANCE WITH REGULATION 248 CMR 4.00 AND 5.00 FOR INSTALLATION OF THROUGH-THE-WALL VENTED GAS APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the follow­ing requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.At the time of
installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the respon­sibility of the property owner to secure the services of qualified licensed profes­sionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizon­tally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above require­ments; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide
detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identifi­cation plate shall be permanently mount­ed to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equip­ment. The sign shall read, in print size no less than one-half (1/2) inch in size,
“GASVENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas
inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes car­bon monoxide detectors and signage installed in accordance with the provi­sions of 248 CMR 5.08(2)(a) 1 through
4. (b) EXEMPTIONS: The following equip-
ment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizon­tally vented gas fueled equipment installed in a room or structure sepa­rate from the dwelling, building or struc­ture used in whole or in part for resi­dential purposes.
(c) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installa­tion of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satis­fied by the manufacturer:
1. The referenced “special venting sys­tem” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installa­tion instructions.
(e) A copy of all installation instructions for all ProductApproved side wall hori­zontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the com­pletion of the installation.
WARNING
!
INSTALLTHIS FURNACE ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDER­ATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADE­QUATE COMBUSTION AND VENTI­LATION AIR TOTHE FURNACE SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUS­TION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECI­FIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS FURNACE TO AN APPROVEDVENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFI­CALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNEC­TIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE TION INSTRUCTIONS.
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS FACING UPWARDS, OR WITH SUPPLY AIR DISCHARGING TO THE RIGHT­HAND SIDE WHEN FACING THE FRONT OF THE FURNACE. SEE FIGURES 6 AND 7 FOR PROPER INSTALLATION OF HORIZONTAL MODELS.
WARNING
!
DO NOT INSTALLTHIS FURNACE IN A MOBILE HOME!! THIS FUR­NACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PER­SONAL INJURY OR DEATH.
WARNING
!
USE ONLYWITH TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
3
WARNING
!
WHENTHIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE,IT MUST BE INSTALLED SO THE BURN­ERS AND IGNITION SOURCE ARE LOCATED NO LESSTHAN 18 INCH­ES ABOVETHE FLOOR.THIS ISTO REDUCETHE RISK OF IGNITING FLAMMABLEVAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO,THE FURNACE MUST BE LOCATED OR PROTECTEDTO AVOID PHYSICAL DAMAGE BY VEHI­CLES. FAILURETO FOLLOWTHESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
USE OF THIS FURNACE IS ALLOWED DURING CONSTRUCTION IF THE FOLLOWINGTEMPORARY INSTALLATION REQUIREMENTS ARE MET. INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPERVENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RAT­ING PLATE MARKING;
• MEANS FOR PROVIDING OUT­DOOR AIR REQUIRED FOR COM­BUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND 80°F (27°C); AND;
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUB­STANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPERATING CONDITIONS INCLUDING IGNI­TION, INPUT RATE,TEMPERA­TURE RISE AND VENTING, ACCORDINGTOTHE INSTRUC­TIONS.
WARNING
!
DO NOT JUMPER OR OTHERWISE BYPASS OVERTEMPERATURE OR ANY OTHER LIMITS OR SWITCHES ONTHE FURNACE. IF ONE OF THESE LIMITS OR SWITCHES SHOULDTRIP OR OPEN,THE USER ISTO BE INSTRUCTEDTO CALL A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER. FOR MANUALLY RESETABLE SWITCHES,THE USER IS FURTHER INSTRUCTEDTO NEVER RESETTHE SWITCH, BUTTO CALL A QUALIFIED TECHNICIAN. MANUAL RESET SWITCHES MAY REQUIRE FURTHER CORRECTIVE ACTIONS. FAILURETO FOLLOWTHIS WARNING COULD RESULT IN CARBON MONOXIDE POISONING, SERIOUS INJURY OR DEATH. IFTHE UNIT IS INSTALLED IN A CLOSET,THE DOOR MUST BE CLOSEDWHEN MAKINGTHIS CHECK. INSTALLERS ANDTECHNI­CIANS ARE INSTRUCTEDTO REPLACE ANY LIMIT OR SAFETY SWITCH/DEVICE ONLY WITH IDENTI­CAL REPLACEMENT PARTS.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTOTHE HOME CAUSING PROPERTY DAM­AGE. FUMES AND ODORS FROM TOXIC,VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMO­BILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTOTHE LIVING SPACETHROUGH LEAKING DUCTS AND UNBAL­ANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 5).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS INTHE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTOTHE LIV­ING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CAR­BON MONOXIDE INTOTHE LIVING SPACE.
WARNING
!
ALWAYS INSTALL FURNACE TO OPERATE WITHIN THE FUR­NACE'S INTENDED TEMPERA­TURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTER­NAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FUR­NACETO AREAS OUTSIDE THE SPACE CONTAINING THE FUR­NACE,THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CAS­ING AND TERMINATING OUTSIDE THE SPACE CONTAININGTHE FURNACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITHTHE CSA INTERNATIONAL (CSA) CERTIFI­CATION OR THESE INSTRUC­TIONS, CAN RESULT IN UNSATIS­FACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOG­NIZED CODES, IT IS RECOM­MENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPO­RATOR COILS THAT ARE LOCAT­ED IN ANY AREA OF A STRUC­TURE WHERE DAMAGETOTHE BUILDING OR BUILDING CON­TENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING. SEE ACCES­SORIES SECTION OF THESE INSTRUCTIONS FOR AUXILIARY HORIZONTAL OVERFLOW PAN INFORMATION (MODEL RXBM).
WARNING
!
DO NOT EXCHANGE MEMORY CARDS BETWEEN 2 OR MORE DIFFERENT FURNACES. DOING SO COULD RESULT IN UNEX­PECTED OPERATION – INCLUD­ING INADEQUATE AIRFLOW DUR­ING HEATING (AND OTHER MODES OR A LOSS OF HEAT).
4
Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction is some­times caused by an improper installation. By completing this checklist, the problem may be found and corrected. Make copies of the checklist and complete one for every Low Profile Furnace service call for your records.
INSTALLATION CHECKLIST
(Refer to this manual for specifics.) GAS SUPPLY
Adequate pipe size No gas leaks Proper supply and manifold gas pressure (check with an accurate U-tube manometer with the furnace and all other
gas appliances operating.)
ELECTRICAL
Correct thermostat and subbase Thermostat model Subbase model Correct thermostat mode and setting Correct line supply voltage Correct power supply polarity is required with electronic ignition Correct furnace ground to electrical panel DC microamp (A) flame signal (hot surface ignition units) Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals “Y” “C” - not with wire nuts
VENTING
Correct vent pipe diameter and length (according to CSA tables) Vent connection size Correct venting material (according to CSA tables) Correct lining for masonry chimneys Adequate clearance from combustibles Proper negative pressure reading in the vent Vent pipe secured to induced draft blower housing
COMBUSTION AIR
Proper source of combustion air Optional attic combustion air pull Correct combustion air opening size Non-attic combustion air pull
FURNACE INSTALLATION
Adequate clearance from combustibles Adequate clearance for service Proper air temperature rise (See furnace rating plate) External static pressure inches w.c. Correct filter(s) Correct cooling coil or accessories (if equipped) Adequate supply and return air ducting ReturnAir Duct Size SupplyAir Duct Size Air ducts sealed to prevent leakage
5
GENERAL INFORMATION
The RGPE/RGLE series furnaces are design certified by CSA for use with nat­ural and propane gasesas follows:
As a CategoryI furnace, it may be vented vertically with type B-1 vent pipe and alsomay be common vent­ed as described in these instructions.
This furnace should be installed in accor­dancewith the American National Standard Z223.1 - latest edition booklet entitled “National Fuel Gas Code” (NFPA
54) (in Canada, CSAB149.1 and .2 Installation Codes for gas burning appli­ances), and the requirements or codes of the localutility or other authorityhaving jurisdiction including local plumbing or wastewater codes.
The NationalAppliance Energy ConservationAct (NAECA) of 1987 states that any gas furnace manufac­turedafter January 1, 1992, must have a minimumAnnual Fuel Utilization Efficiency (AFUE) of 78%.The higher the AFUE percentage the more usableheat energy the consumer gets for every dol­lar of fuel purchased.This is similarto the EPA's minimum gas mileage require­ment for automobiles. It gives the con­sumera relativelyeasy way to make direct efficiency comparisons between differentfurnace brands and styles.
A high AFUE value, which translates into a low operating cost, is not the only con­cern thatconsumers have. Theyalso want a furnace with a reasonable installed cost. They want a furnace that provides them with comfort – their main concern.And they expecta furnace with exceptional reliability and longevity.
Gas furnace manufacturers are always striving to provide consumers with the best furnace value. The Low Profile Furnace addresses all those consumer needs. It gives exceptionalefficiency with a low installationcost. It delivers the comfort the customer wants along with the reliability they expect.
The key to all these customer benefits is the furnace's heat exchanger.The mate­rialsused to construct the furnace in gen­eral and the heatexchanger in particular make it a rugged,long lasting unit. The unique heat exchanger design provides the customer with a furnace only 34 inch­es high.This gives the consumer a unit easily installed in almost every location that accepts all customary accessories.
With the introduction of higherefficiency furnaces, special attention mustbe paid to the venting system.Only listed venting systems may be used as stated in the installation instructions and the National
Fuel Gas Code, ANSI Z223.1 (NFPA 54), or the Canadian CAN/CGA B149.1 and B149.2 InstallationCodes for Gas Burning Appliances.Sincefurnace tech-
nology and ventingrequirements are changing, awarenessof local, state, and federal codes and industry changes is imperative.
NOTE: Always perform a proper heat loss calculation beforespecifying the fur­nace size. This ensures that the furnace is sized to adequately, economically, heat the building and provide the correct air­flow for yourapplication.
IMPORTANT:PROPERAPPLICATION, INSTALLATION AND MAINTENANCE OF THIS FURNACE ISA MUST IF CONSUMERSARE TO RECEIVE THE FULLBENEFITS FOR WHICH THEY HAVE PAID.
Additionalhelpful publications available from the “NationalFire Protection Association” are: NFPA-90A– Installation ofAir Conditioning and Ventilating Systems 1985 or latestedition.NFPA­90B – WarmAir Heating and Air Conditioning Systems 1984.
Thesepublications are availablefrom:
National Fire Protection Association,
Inc. Batterymarch Park Quincy, MA 02269
CSA-INTERNATIONAL 178 Rexdale Blvd. Etobicoke (Toronto), Ontario Canada M9W, 1R3
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment.
FIGURE 1
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program rec­ommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST,FUMES AND ODORS INTOTHE HOME CAUSING PROP­ERTY DAMAGE. FUMES AND ODORS FROM TOXIC,VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOX­IDE (CO), CAN BE DRAWN INTO THE LIVING SPACETHROUGH LEAKING DUCTS AND UNBAL­ANCED DUCT SYSTEMS CAUS­ING PERSONAL INJURY OR DEATH (SEE FIGURE 1).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOX­IDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH
6
AS WATER HEATERS OR BOILERS
- ALL JOINTS, SEAMS, AND OPEN­INGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CAR­BON MONOXIDE INTOTHE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITHTHE CSA INTERNATIONAL (CSA) CERTIFICA­TION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI-TIONS AND ARE NOT COV­ERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDEDTHAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORA­TOR COILS OR UNITS CONTAINING EVAPORATOR COILS OR GAS FUR­NACES USED WITH EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGETO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOP­PAGE IN THE PRIMARY CONDEN­SATE DRAIN PIPING.
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applica­tions.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is required to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in a level position to ensure proper condensate drainage. Make sure unit is level in both directions within 1/8”.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPANo. 70-(Latest Edition) National Electrical Code.
• NFPA90AInstallation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning sys­tems.
• The equipment has been evaluat­ed in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
1. NOTE: This furnace is shipped with heat exchanger support brackets installed under the back of the heat exchanger.These may be removed before installation, but it is not required.
LOCATION
!
WARNING
THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DO NOT INSTALLTHIS FUR­NACE IN A MOBILE HOME. INSTALLATION IN A MOBILE HOME COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
2. IMPORTANT: This furnace is not approved or recommended for instal­lation on its back, with access doors facing upwards.
3. This furnace is suitable for installa­tion in buildings constructed on-site. This heating unit should be central­ized with respect to the heat distribu­tion system as much as practicable.
4. NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces.
5. IMPORTANT: Support this unit when
installed.Forattic or crawl space installation, horizontal furnaces may be installed on combustible wood flooring or by using support brackets. See Figure 2.
FIGURE 2
HORIZONTAL FURNACE INSTALLEDW/SUPPORT BRACKETS
EXHAUST VENT
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure 3. Allow enough space for proper service maintenance or replacement of the heat exchanger and blower assembly.
6. IMPORTANT: If installing in a util-
ity room, be sure the door is wide enough to:
a. allow the largest part of the fur­b. allow any other appliance
nace to pass; or (such as a water heater) to
pass.
ST-A0799-01
7
FIGURE 3
UPFLOW/HORIZONTAL DIMENSIONS
Ship.
/32
19
15
REDUCED CLEARANCE (IN.)
Back Top Front Vent
Left Right
A B C D E F
20
/16
1
28
May be 1with type B vent.
May require 3to 4or 3or 5adapter.
May be 0with type B vent.
/2 0 3 0 1 3 6 105 lbs.
/2 0 3 0 1 3 6 115 lbs.
/2 0 0 0 1 3 6 120 lbs.
1
/8 15 2
3
/32 12
11
/2 16
1
/2 0 0 0 1 3 6 140 lbs.
1
1
1
/2 2
1
/8 15 2
/8 18
/8 22 2
3
1
7
/32 12
/32 14
/32 15
11
27
11
/2 16
/2 23
1
1
D
/16
9
/32
19
B
A
/16
7
24
5
ALTERNATE
GAS CONNECTION
/4
3
/8 DIA.
1
/8
5
26
/8 DIA.
7
/8 DIA.
7
OPTIONAL RETURN AIR CUTOUT
/2
1
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
23
11
/8
3
14
/32
11
RIGHT SIDE
24
34
FRONT
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
/4
1
1
BOTTOM
TOP
RGPE Side Side Wgts.
Model
05 17
07(A) 17
/32
17
23
AIR
RETURN
/2
1
24
AIR
SUPPLY
25.406
12 24
07(B),10 21 19
/32
19
SIGHT
GLASS
*Both sides for 1800 CFM or above.
AIRFLOW
/32
11
E
/16
C
13
26
/8
5
26
GAS CONNECTION
F
24
/8
3
14
/2
1
11
LOW VOLTAGE
ELECTRICAL CONNECTION
OPTIONAL RETURN AIR CUTOUT
(EITHER SIDE) FOR USE WITH
EXTERNAL SIDE FILTER FRAME*
LEFT SIDE
IMPORTANT: This furnace is not approved or recommended for
installation on its back, with access doors facing upwards.
8
FIGURE 4
DOWNFLOW DIMENSIONS
Ship.
Back Top Front Vent
REDUCED CLEARANCE (IN.)
/8
5
/8
1
20
/16
1
28
May be 1with type B vent.
May require 3to 4or 3or 5adapter.
May be 0with type B vent.
/8
5
26
/8 DIA.
/8 DIA.
7
7
/16
7
24
/8 DIA.
5
1
D
Left Right
A B C D E
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
Model
DOWNFLOW MODELS
RGLE Side Side Wgts.
/16
3
/8
/8 0 0 0 1 3 6 140 lbs.
/8 0 3 0 1 3 6 105 lbs.
/8 0 0 0 1 3 6 120 lbs.
5
1
5
3
20
/8
3
6
23
/8 23
/8 16
/8 20
1
7
5
/32 12
/32 13
/32 15
11
27
11
/2 16
/2 23
1
1
12 24
07(A) 17
07(B),10 21 19
/4
3
19
/8
5
R.A.
B
A
/8
5
/4
3
SIGHT
34
GLASS
AIRFLOW
S.A.
AIR
E
SUPPLY
/8
3
23
/8
3
20
/16
3
6
TOP BOTTOM
AIR
RETURN
1
/2
24
/8
5
26
C
LOW VOLTAGE
/16
13
26
GAS CONNECTION
ELECTRIC CONNECTION
NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.
COMBUSTIBLE FLOOR BASE REQUIRED IF FURNACE IS NOT INSTALLED ON COIL BOX.
9
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the tables on the following pages are certified by CSA for the clearances to combustible materials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches is recommended in front of all furnaces.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST TAKE PRECEDENCE OVER FIRE PROTEC­TION CLEARANCES.
!
WARNING
UPFLOW AND HORIZONTAL FURNACES MUST NOT BE INSTALLED DIRECTLY ON CARPET­ING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE CAUSING PROPER­TY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
A gas-fired furnace for installation in a residential garage must be installed so that the burner(s) and the ignition source are located not less than 18” above the floor and the furnace is locat­ed or protected to avoid physical dam­age by vehicles.
!
WARNING
DOWNFLOW UNIT DESIGN IS CERTI­FIED FOR INSTALLATION ON NON­COMBUSTIBLE FLOOR. A SPECIAL COMBUSTIBLE FLOOR SUB-BASE, FIGURE 5, IS REQUIRED WHEN INSTALLING ON A COMBUSTIBLE FLOOR. FAILURETO INSTALLTHE SUB-BASE MAY RESULT IN FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.THIS SPECIAL BASE IS OFFERED AS AN ACCES­SORY FROM THE FACTORY. SEE THE CLEARANCE LABEL LOCATED INSIDE THE FURNACE FOR THE APPROPRIATE MODEL NUMBER.
THE SPECIAL BASE IS NOT REQUIRED WHEN THE FURNACE IS INSTALLED ON TOP OF AN AIR CONDITIONING PLENUM.
SITE SELECTION
1. Select a site in the building near the center of the proposed, or existing, duct system.
2. Give consideration to the vent sys­tem piping when selecting the fur­nace location. Be sure the venting system can travel from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas pip­ing.
4. Locate the furnace to maintain prop­er clearance to combustibles as shown in Figures 3 and 4.
!
CAUTION
WHEN COILS ARE INSTALLED ABOVE A FINISHED CEILING OR LIVING AREA, IT IS RECOMMENDED THAT AN AUXILIARY SHEET METAL CONDENSATE DRAIN PAN BE FAB­RICATED AND INSTALLED UNDER ENTIRE UNIT. FAILURETO DO SO CAN RESULT IN PROPERTY DAM­AGE. RUN CONDENSATETO A LOCATION WHERE IT IS NOTICE­ABLE.
!
WARNING
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET OR WITHIN THE SPECIFIED CLEARANCES OF THE VENT PIPE. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COM­BUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMA­BLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUNDTHE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.THE FURNACE OWNER SHOULD BE CAUTIONED THATTHE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PUR­POSES.
DUCTING
Proper air flow is required for the correct operation of this furnace. Too little air flow can cause erratic oper­ation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling. Position the unit to minimize long runs or runs with many turns and elbows.
Size and install the ducts according to acceptable industry standards and methods. The total static pres­sure drop (including evaporator coil, if used) of the entire system should not exceed 0.8” w.c. adequate space for unit filter. NOTE: Airflow external static pressure mea­surements do not include filter or coil.
IMPORTANT: Some high efficiency filters have a greater than normal resistance to air flow.This can adversely affect furnace operation. BE SURE TO CHECK AIR FLOW if using any filter other than the facto­ry-provided filter.
NOTE: DO NOT take return air from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
IMPORTANT: Return air tempera- ture must be above 55°F during the heating season.
!
WARNING
NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTSTO ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED.WHEN A FURNACE IS MOUNTED ON A PLATFORM,WITH RETURN THROUGHTHE BOTTOM, IT MUST BE SEALED AIRTIGHT BETWEEN THE FURNACE AND THE RETURN AIR PLENUM. THE RETURN AIR PLENUM MUST BE PERMANENT­LY ENCLOSED. NEVER USE A DOOR AS A PART OF THE RETURN AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT OF THE FURNACE, WITHOUT SAGGING, CRACKS, GAPS, ETC., AROUND THE BASE AS TO PROVIDE A SEAL BETWEEN THE SUPPORT AND THE BASE.
Be sure to have
10
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIR­CULATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZ­ARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUM­STANCES, CONNECT RETURN OR SUPPLY DUCTWORK TO OR FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLO­SION, PERSONAL INJURY OR PROP­ERTY DAMAGE.
!
WARNING
BLOWER AND BURNERS MUST NEVER BE OPERATEDWITHOUT THE BLOWER DOOR IN PLACE.THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTOTHE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
UPFLOW UNITS
1. Set furnace in place and connect the return duct or return air cabinet to unit. Make the connection air-tight to prevent entraining combustion gases from any adjacent fuel-burning appli­ances. Unit return air may be con­nected on the sides or bottom of the return air compartment.
a. Openings in the side must be cut
out the full width of the knockouts on the unit. If using side return air,
THE BOTTOM base plate must be installed.
NOTE: Where the maximum airflow
is 1800 CFM or more, both sides or the bottom must be used for return air.
b. If using bottom return air, place fur-
nace over return air plenum and seal furnace bottom to return air plenum.
!
WARNING
A SOLID METAL BASE PLATE, (SEE TABLE 1) MUST BE IN PLACE WHEN THE FURNACE IS INSTALLED WITH SIDE AIR RETURN DUCTS. FAILURE TO INSTALL A BASE PLATE COULD CAUSE PRODUCTS OF COMBUS­TION TO BE CIRCULATED INTO THE LIVING SPACE AND CREATE POTEN­TIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH.
TABLE 1
FURNACE BASE BASE
WIDTH PLATE NO. PLATE SIZE
1
17
/2 RXGB-D17 151/8x 239/16
21” RXGB-D21 18
1
24
/2 RXGB-D24 255/8” x 239/16
5
/8” x 239/16
2. If summer air conditioning is desired, position the indoor coil on the supply air side of the furnace. Insure that no air can bypass this coil.
3. Connect the supply air plenum to the furnace plenum opening, or indoor coil.
NOTE: The RGLE has louvers to cool the inducer motor bearings.
DOWNFLOW UNITS
!
WARNING
THE DOWNFLOW FURNACE DESIGN IS CERTIFIED FOR INSTALLATION ON A NON-COMBUSTIBLE FLOOR. IF INSTALLED ON A COMBUSTIBLE FLOOR, USE THE SPECIAL BASE SPECIFIED ON THE FURNACE CLEARANCE LABEL. FAILURETO INSTALLTHE SPECIAL BASE MAY RESULT IN FIRE, PROPERTY DAM­AGE, PERSONAL INJURY OR DEATH.THIS SPECIAL BASE IS SHIPPED FROM THE FACTORY AS AN ACCESSORY.
FIGURE 5
COMBUSTIBLE FLOOR BASE (RXGC-B17, -B21, -B24)
1. Position the unit over the supply air plenum and connect.
a. If installing on a combustible
floor and not using an evapo- rator coil box, install the spe­cial combustible floor base. See Figure 5.
b. If summer air conditioning is
desired, position the indoor coil on the supply air side. Insure that no air can bypass this coil.
2. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining com­bustion gases from an adjacent fuel-burning appliance.
HORIZONTAL UNITS
1. Unit can be mounted left or right side airflow configuration.
2. Position the unit on adequate supports or by using support brackets (see Figure 2) and con­nect supply plenum and return.
3. If summer air conditioning is desired, position the indoor coil on the supply air side of the unit. Insure that no air can bypass this coil.
4. Secure the four angle brackets shipped with the unit to the return air opening. See Figure 6. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining com­bustion gases from an adjacent fuel-burning appliance.
NOTE: Do not block furnace access with support rods. Maintain clear­ances recommended in Figure 3. Allow enough space for proper ser­vice maintenance or replacement of the heat exchanger and blower assembly.
11
FIGURE 6
HORIZONTAL RETURN AIR DUCT (LEFT-HAND AIRFLOW POSITION SHOWN)
AIRFLOW
RETURN
REAR VIEW
FOUR ANGLE BRACKETS ARE SHIPPED WITH EACH UNIT THAT CAN BE USED TO SECURE THE RETURN AIR DUCT TO A HORIZONTAL UNIT.
COMBUSTION AND VENTILATION AIR
IMPORTANT: This is not a direct vent furnace. Review venting instructions before installing.
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry
rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following sub­stances in the combustion air supply may also require OUTDOOR AIR for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for
clothes dryers
• Masonry acid washing materials
!
WARNING
THIS FURNACE AND ANY OTHER FUEL-BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUS­TION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRETHAT OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAILURETO DO SO CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING.
Adequate facilities for providing air for combustion and ventilation must be provided in accordance with section
5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI, Z223.1 latest edition or CSA B149.1 and .2 or, applicable provisions for the local building codes, and not obstructed so as to prevent the flow of air to the furnace.
COMBUSTION AIR REQUIRE­MENTS
IMPORTANT: Air for combustion and ventilation must not come from a corro­sive atmosphere. Any failure due to cor­rosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation may require OUTDOOR AIR for combustion, due to chemical exposures:
FIGURE 7
AIR FROM HEATED SPACE
12
Combustion air must be free of acid forming chemicals; such as sulphur, flu­orine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresh­eners, paint and varnish removers, refrigerants and many other commercial and household products. Vapors from these products when burned in a gas flame form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they con­dense.
!
WARNING
ALL FURNACE INSTALLATIONS MUST COMPLYWITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN CREATE HAZ­ARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH FROM SMOKE, FIRE OR CARBON MONOXIDE.
Combustion air requirements are deter­mined by whether the furnace is in an open (unconfined) area or in a confined space such as a closet or small room. See Figures 7 and 8.
EXAMPLE 1. FURNACE LOCATED IN AN UNCON­FINED SPACE
Using indoor air for combustion.
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of the total input for all appli ances
in the space. Here are a few
-
examples of the room sizes required for different inputs. The sizes are based on 8 foot ceilings.
BTUH Minimum Sq. Feet Typical Room Size
Input With 8' Ceiling With 8' Ceiling
50,000 312 14*x24* or 18*x18*
75,000 469 15*x31* or 20*x24* 100,000 625 20*x31* or 25*x25* 125,000 833 23*x34* or 26*x30*
If the open space containing the fur­nace is in a building with tight construc­tion (contemporary construction), out­side air may still be required for the fur­nace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
FIGURE 8
AIR FROM ATTIC/CRAWL SPACE
EXAMPLE 2. FURNACE LOCATED IN A CONFINED SPACE
A confined space (any space smaller than shown above as “unconfined”) must have openings into the space which are located in accordance with the requirements set forth in the follow­ing subsections A and B. Size the open­ings by how they are connected to the heated area or to the outside, and by the input of all appliances in the space.
If confined space is within a building with tight construction, combustion air must be taken from outdoors or area freely communicating with the outdoors.
A. USING INDOOR AIR FOR COM-
BUSTION, ALL OF THE MODELS
IMPORTANT: Air should not be taken from a heated space with a fireplace, exhaust fan or other device that may produce a negative pressure.
If combustion air is taken from the heat-
ed area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 Btuh of total input in the space. Here are some examples of typical openings required.
Btuh Free Area
Input Each Opening
100,000 100 Square Inches
AIR INTAKE PIPE CONNECTION (RGPE UPFLOW/HORIZONTAL ONLY)
A double-elbow may be installed to top inlet air opening, BUT IS NOT REQUIRED.This will help to prevent accidental blockage of the intake opening. Reference Figure 9 for proper elbow diame­ter.
NOTE: Inlet is specifically designed
to prevent material from being pulled into furnace. If elbows are not used, the intake opening must be kept clean and free of debris.
It is also acceptable to run the condensate drain (or refrigerant) line access over the air intake hole as long as a 1" minimum clearance is maintained.
B. USING OUTDOOR AIR FOR
COMBUSTION, ALL OF THE MODELS
IMPORTANT: Never take com- bustion air from an attic space that is equipped with power ventilation.
The confined space must com­municate with the outdoors according to Methods 1 and 2. The minimum air opening dimen­sion shall not be less than 3 inch­es. When using ducts, they shall be of the same cross-sectional area as the free area of the open­ings to which they connect.
13
FIGURE 9
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET AIR OPENING TO PREVENT ACCIDENTALBLOCKAGE OF INTAKE OPENING. THIS IS NOT A REQUIREMENT. (SEE PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED BUT MAY NOT PREVENT DEBRIS FROM BEING DROPPED INTO THE FURNACE.
EXHAUST
PVC DOUBLE ELBOW
6" MININUM CLEARANCE
#8 SCREWS
6" MIN.
GROUND OR SHELF SURFACE
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
METALFLUE PIPE ONLY
#8 SCREWS
B: Method 1 Provide two permanent openings,
one located within 12 inches of the top and one located within 12 inches of the bottom of the enclosure. Each opening shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating
with the outdoors or where com­municating to the outdoors through VERTICAL DUCTS, each opening shall have a minimum free area of 1 square inch for each 4000 BTUH of total appli­ance input rating in the enclosure. Here are typical duct sizes:
VERTICAL OUTDOOR AIR OPENING DIMENSIONS
BTUH Free Area Round
Input Each Opening Pipe Size
50,000 12.50 sq. inches 4
75,000 18.75 sq. inches 5 100,000 25.00 sq. inches 6 125,000 31.25 sq. inches 7
b. Where communicating with out-
doors through HORIZONTAL DUCTS, each opening shall have a minimum free area of 1 square inch for each 2000 BTUH of total input rating for all equipment in the enclosure. Here are typical duct sizes:
HORIZONTAL OUTDOOR AIR OPENING DIMENSIONS
BTUH Free Area Round
Input Each Opening Pipe Size
50,000 25.00 sq. inches 6
75,000 37.50 sq. inches 7 100,000 50.00 sq. inches 8 125,000 62.50 sq. inches 9
B: Method 2 One permanent opening, located within
12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall directly communicate with the out­doors or communicate through a verti­cal or horizontal duct to the outdoors or spaces (crawl or attic) that freely com­municate with the outdoors and have a minimum free area of:
a. One square inch for each 3000
BTUH of the total input rating of all equipment located in the enclosure, AND
b. Not less than the sum of the
areas of all vent connectors in the confined space.
IMPORTANT: If the furnace is in a location with an exhaust fan, there must be sufficient ventilation to pre­vent the exhaust fan from creating a negative pressure in the room.
Combustion air openings must NOT BE RESTRICTED in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
14
B: Method 3, RGPE only For the optimum in quiet operation, attic
air may be brought directly to the fur­nace.
IMPORTANT: In applications using Method 3 for combustion air, the attic must be ventilated by gable or soffit vents. See Figure 8.
It is not required to provide any per­manent openings as described in Method 1
!
or Method 2.
CAUTION
COMBUSTION AIR INTAKES CAN­NOT BE TERMINATED OUTSIDE. DOING SO CAN CAUSE IMPROPER
FIGURE 10
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
OPERATION OF THE FURNACE
If attic combustion air is used, the inlet air opening at the furnace must be pro­tected from accidental blockage. Install a 90° elbow pointing horizontally at the top of inlet air pipe. See Figure 11 (maximum of 2, 22
1
2°, 45° or 90°
elbows, allowed).
NOTE: Maximum length of pipe that may be used for combustion air is 10 feet with two elbows. Lengths of more than 10 feet can result in nui­sance pressure switch trips.
FIGURE 11
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL, RGPE ONLY
ATTACH A 90° ELBOW TO TOP INLET AIR OPENING TO PREVENT ACCIDENTALBLOCKAGE OF INTAKE OPENING.
PVC ELBOW
EXHAUST
ATTIC SPACE
METALFLUE PIPE ONLY
INDOOR SPACE
10 FT. MAX.
!
CAUTION
12" MIN. FROM TOP OF INSULATION
INCLUDING HORIZONTALDIRECTION
#8 SCREW
INSULATION
6" MINIMUM CLEARANCE
PVC COUPLER
USE OF SHEET METAL AIR INTAKE PIPE INSTEAD OF PVC MAY RESULT IN NOISE ISSUES.
NOTE: PREDRILL HOLES FOR SCREWS TO PREVENT CRACKING.
#8 SCREWS
15
VENTING
GENERAL INFORMATION
The furnace must be vented in accor­dance with these instructions, National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA­B149.1 & .2 and requirements or codes of the local utility or other authority hav­ing jurisdiction.
!
WARNING
DEVICES ATTACHED TOTHE FLUE OR VENT FOR THE PURPOSE OF REDUCING HEAT LOSS UP THE CHIMNEY HAVE NOT BEEN TESTED AND HAVE NOT BEEN INCLUDED IN THE DESIGN CERTIFICATION OF THIS FURNACE. WE, THE MANUFAC­TURER, CANNOT AND WILL NOT BE RESPONSIBLE FOR INJURY OR DAMAGE CAUSED BYTHE USE OF SUCH UNTESTED AND/OR UNCER­TIFIED DEVICES, ACCESSORIES OR COMPONENTS.
DRAFT INDUCER
!
WARNING
VENT PIPE ATTACHING HOLES MUST BE PREDRILLED IN THE DRAFT INDUCER COLLAR TO PRE­VENT DAMAGINGTHE INDUCER. DRILL 1/8DIAMETER HOLES THROUGHTHE VENT PIPE AND COLLAR AND USE #8 SCREWS TO ATTACH. SEE FIGURE 12. FAILURE TO FOLLOWTHIS WARNING CAN CAUSE RECIRCULATION OF FLUE PRODUCTS CAUSING CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
FIGURE 12
ATTACHINGTO DRAFT INDUCER COLLAR
FURNACE CATEGORY INFORMATION
This furnace is shipped as a Category I type induced draft furnace. A Category I furnace operates with a nonpositive vent pressure and has a vent gas tem­perature at least 140°F above the dew point of the vent gases. A Category I type may be a draft hood equipped fur­nace or have a fan assisted combustion system (induced draft). The inducer is used to pull flue products through the combustion chamber and as they leave the furnace, most of the energy has been dissipated. The buoyant effect of the flue gases provides venting to the outdoors.
During the off cycle, the inducer is off and there is very little flow through the vent, cooling the vent. During the on cycle there is no dilution airflow, as with a draft hood type furnace. Although the vent heats up rapidly without dilution air, the flue products contain more water vapor, which results in a higher dew point temperature. It is most important that you follow the guide­lines in these instructions to prevent the possible formation of condensation in the venting system.
As a Category I furnace it may be vent­ed vertically with type B-1 vent pipe and also may be common vented, as described in these instructions.
A0991-01
IMPORTANT APPLICTION NOTES
When the furnace is used as a replacement, the existing vent sys­tem should be inspected to assure that there are no obstructions, block­age, or any signs of corrosion and is properly sized for use with this fur­nace.
NOTE: When the vent table permits more than one diameter of pipe for a connector or vent, the smallest per­mitted diameter must be used.
Vent pipe may be type “B-1,” either rigid or suitable flexible construction that carries a u.l. listing.
Common venting is allowed with vertical B-1 vent systems, and lined masonry chimneys. Follow the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2 for proper installation practices.
NOTE: Follow combustion air instructions as outlined in this manu­al.
Single wall vent connectors to “B-1 vent or masonry chimneys” may be used under the guidelines of the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
The entire length of the vent con­nector shall be readily accessible for inspection, cleaning and replacement.
16
“B-1” VERTICAL VENTING
Type “B-1” vents must be installed in accordance with the terms of their list­ings and the vent manufacturer’s instructions.
“B-1” vents must be supported and spaced in accordance with their listings and the manufacturer’s instructions. All vents must be supported to maintain their minimum clearances from com­bustible material.
VERTICAL VENTING
Categorized
Input Size Required
50K 3
75K *4 100K *4 125K *5
*NOTE: All furnaces have a 3” vent connec­tion as shipped from the factory. A 3” to 4” or 3” to 5” vent transition is required on all but the 50,000 BTUH models when vertically vented or common vented with metal vent pipes. THE VENT TRANSITION CONNEC-
TION MUST BE MADE ATTHE FURNACE VENT EXIT. It must originate with an adapter
if required, at the furnace flue collar and ter­minate either in a listed cap or roof assem­bly. When common venting, the vent con­nector size may differ from the above diame­ters depending on application. See ANSI Z21.47-1993/CSA-2.3-M93 or latest edition tables.
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed cap or listed roof assembly. Gas vents 12 inches in size or smaller with listed caps shall be permitted to be terminated in accordance with Figure 13, provided they are at least 8 feet from a vertical wall or similar obstruction. All other gas vents shall terminate not less than 2 feet above the highest point where they pass through the roof and at least 2 feet higher than any portion of a building within 10 feet.
2. A type B-1 gas vent shall terminate at least 5 feet in vertical height above the highest connected equipment draft hood or flue collar.
3. Must rise
1
/4” per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or dips. Supports at 4 foot intervals and at all elbows are recommended.
4. The vent connector must be mechan­ically fastened to the outlet collar of the furnace with at least (2) sheet metal screws except vent connectors that are B-1 material. These shall be assembled in accordance with the manufacturer’s instructions. See Figure 12.
Furnace Vent
FIGURE 13
TYPICAL VENTING WITH “B-1”VENT
5. Any angle greater than 45 degrees from the vertical is considered hori­zontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft-hood equipped appliances shall not be greater than 75 percent of the verti­cal height of the vent.
NOTE: Refer to the National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
Single appliance venting of a fan assist­ed furnace into a tile-lined masonry chimney is prohibited. The chimney must be lined with either Type B vent or with a listed, single wall, metal lining system. Reference National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2. See Figure 14 for typical B-1 vent chase.
!
WARNING
DO NOT CONNECT THIS FUR­NACETO A CHIMNEY USED TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD TO IMPROPER FUNC­TIONING OF THE UNIT, AND DUE TO SOOTING,THE POSSIBILITY OF FIRE RESULTING IN PROPER­TY DAMAGE, PERSONAL INJURY OR DEATH.
SPECIAL VENT SYSTEMS (SVS)
IMPORTANT: It is THE FURNACE MANUFACTURER’s position now that new pipe used in a category III vent application, including Selkirk’s Selvent™ II HTPV product, should cease immediately.
installations of any HTPV
17
POWER VENT SYSTEMS
When vertical venting is not possible, the only acceptable method for horizon­tal venting is with the use of Tjernlund model GPAK-1TR or Field Controls models SWG-4R power venter. Type B vent pipe and fittings must be used. Common venting is not permitted
All application and installation instructions supplied with the power venter must be followed.
Please address all questions regarding power venter installation, agency list­ings and furnace model compatibility to:
Tjernlund Products, Inc. (800) 255-4208 or (612) 426-2993
Field Controls L.L.C. (800) 742-8368 or (919) 522-0214
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: CHIMNEY ADAPTER IS CERTIFIED FOR USE ON UPFLOW (RGPE) ONLY.
This appliance is CSA certified for use with RXGW-B01 Chimney Adapter. Refer to Kit Installation Instructions 92-101682-01.
EXISTING VENT SYSTEMS
IMPORTANT RETROFIT VENTING INSTRUCTIONS
If this furnace is a replacement installa­tion, ALWAYS INSPECT the existing vent system to be sure there are no obstructions, blockages, or signs of cor­rosion.
When the existing furnace is removed from a venting system serving other appliances, the venting is likely to be too large to properly vent the remaining attached appliances.
The following steps shall be followed with each appliance that remains con­nected to the common venting system, while the other appliances that remain connected to the common venting sys­tems are not in operation.
NOTE:When the vent table permits more than one diameter of pipe for a connector or vent, the smallest per­mitted diameter must be used.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no block­age, restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all build­ing doors, windows and all doors between the space where the appli­ances remaining connected to the common venting system are located.
Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6. After it has been determined that each appliance that remains con­nected to the common venting system properly vents (when test­ed as outlined above) return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the common venting system must be resized. Refer to National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
FIGURE 14
DEDICATED VENTING THROUGH CHIMNEY WITH “B-1”VENT
18
GAS SUPPLY AND PIPING
GAS SUPPLY
!
WARNING
THIS FURNACE IS EQUIPPED ATTHE FACTORY FOR USE ON NATURAL GAS ONLY. CONVERSIONTO LP GAS REQUIRES A SPECIAL KIT AVAIL­ABLE FROMTHE DISTRIBUTOR. FAILURETO USE THE PROPER CON­VERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
See the conversion kit index supplied with the furnace.This index identifies the proper LP Gas Conversion Kit required for each particular furnace.
IMPORTANT: Any additions, changes or
conversions required for the furnace to satisfactorily meet the application should be made by a qualified installer, service agency or the gas supplier, using facto­ry-specified or approved parts. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appro­priate fuel.
IMPORTANT: Connect this furnace only to gas supplied by a commercial utility.
IMPORTANT: A U.L. recognized fuel gas and CO detector(s) are recom­mended in all applications, and their installation should be in accor­dance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
FIGURE 15
GAS PIPING INSTALLATION
MANUAL GAS VALVE
(IN CLOSED POSITION)
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
GAS PIPE INSTALLATION
UPFLOW & DOWNFLOW
UNION
HORIZONTAL
MANUAL GAS VALVE (IN CLOSED POSITION)
FLAME SENSOR
BURNERS
BURNERS
FLAME SENSOR
DUCT
UNION
GAS VALVE
MANIFOLD
DIRECT SPARK IGNITOR
GAS PIPING (SEE FIGURE 15)
Install the gas piping according to all local codes, state codes and regulations of the utility company, whichever holds jurisdiction.
If possible, run a separate gas supply line directly from the meter to the fur­nace. Consult the local gas company for the location of the manual main shut-off valve.The gas line and manual gas
valve must be adequate in size to prevent undue pressure drop and never smaller than the pipe size to the combination gas valve on the fur­nace. Refer to Table 2 for the recom-
mended pipe size for natural gas and Table 3 for LP gas pipe sizes.
IMPORTANT: It is permissible to run flexible gas connector inside the unit to a piece of black pipe. If local codes
DIRECT SPARK IGNITOR
allow the use of a flexible gas appliance connector, always use a new listed con­nector. Do not use a connector which has previously serviced another gas appliance.Massachusetts law limits flex­ible gas connectors to a maximum of 36”.
Install a ground joint union outside the cabinet to easily remove the con­trol valve assembly. Install a manual shut-off valve in the gas line outside the cabinet. The valve should be readi-
ly accessible to turn the gas supply on or off. Install a drip leg in the gas supply line as close to the furnace as possible. Always use a pipe compound resistant to the action of liquefied petroleum gases on all threaded connections.
MANIFOLD
GAS VALVE
IMPORTANT: When making gas pipe connections, use a back-up wrench to prevent any twisting of the control assembly and gas valve.Do not overtighten the connection.
Any strains on the gas valve can change the position of the gas ori­fices in the burners. This can cause erratic furnace operation.
IMPORTANT: ENSURE that the fur- nace gas control valve not be sub­jected to high gas line supply pres­sures.
DISCONNECT the furnace and its individual shut-off valve from the gas supply piping during any pressure
testing that exceeds 1/2 PSIG (14” W.C.) (3.48 kPa).
19
GAS PRESSURE
IMPORTANT: Natural gas supply pres­sure should operate between 5" to
10.5w.c. LP gas supply pressure should be 11to 13w.c. This pressure
must be maintained with all other gas-fired appliances in operation.
NOTE: Do not exceed a gas pressure of 13” w.c.
WARNING
!
ELEVATIONS ABOVE 2000 FT REQUIRETHATTHE FURNACE INPUT RATING BE ADJUSTED ANDTHAT THE SIZE OFTHE BURNER ORI­FICES BE RE-CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE.THE BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED.SEE THE SECTION TITLED“HIGH ALTITUDE INSTALLA­TIONS” OF THIS BOOK FOR INSTRUCTIONS.
WARNING
!
NEVER PURGE A GAS LINE INTO THE COMBUSTION CHAMBER. NEVER USE MATCHES, FLAME OR ANY IGNITION SOURCE FOR CHECKING LEAKAGE.FAILURETO FOLLOWTHIS WARNING CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
To check for gas leakage, use an approved chloride-free soap and water solution, or other approved method.
LP CONVERSION
NOTE: For installation, see specific LP kit installation instructions. Orifice must be ordered for the correct elevation.
NOTE:Order the correct LP conversion kit from the local distributor. Furnace conversion to LP gas must be per­formed by a qualified technician.
More information found in the high alti­tude and orifice section.
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas, remove the NOx insert assemblies. Steps for removal are listed below:
1. Turn off all electrical power and the gas supply to the furnace.
2. Remove the burner door from the furnace.
3. Remove the igniter assembly –
handle with care.
4. Remove the two screws attach­ing the NOx insert retainer brackets to the center panel. Pull the retainer rod.
5. Put the two screws back into the holes in the center panel.
6. Re-install the igniter and burner assemblies.
7. Replace burner door.
8. Turn on electrical power and gas supply to the unit.
NOTE:Some NOx models may have one less NOx insert.
20
SETTING GAS PRESSURE
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure). (Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal Length of Pipe, Feet Iron Pipe Size, Inches 10 20 30 40 50 60 70 80 90100125 150
1/2 275 189 152 129 114 103 96 89 83 78 69 63 3/4 567 393315 267 237 217 196 182 173 162 146 132
11,071 732 590504 448 409 378 346 322 307 275 252 1-1/4 2,205 1,496 1,212 1,039913 834 771 724 677 630567 511 1-1/2 3,307 2,299 1,858 1,559 1,417 1,275 1,1811,086 1,023 976 866
787
2 6,221 4,331 3,465 2,9922,646 2,394 2,205 2,047 1,9211,811 1,606 1,496
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
The maximum gas supply pressure to the furnace should be 10.5w.c. natur­al gas, or 13w.c. LP gas. The mini­mum supply gas pressure to the gas valve should be 5" w.c. natural gas or 11" w.c. LP gas. A properly calibrated manometer is required for accurate gas pressure measurements.
Supply Gas Pressure Measurement.
A line pressure tap is on the inlet side of the gas valve.
1. With gas shut off to the furnace at the manual gas valve outside the unit, remove the input pressure tap plug.
2. Connect a U-Tube manometer to the pressure tap.
3. Turn on the gas supply and oper­ate the furnace and all other gas­fired units on the same gas line as the furnace.
4. Adjust the line gas pressure to supply:
A. 5” - 10.5” w.c. for natural gas. B. 11” - 13” w.c. for LP gas.
5. Shut off the gas at the manual gas valve and remove the U-Tube manometer.
6. Replace the pressure tap plug.
7. Turn gas on, and check for leaks.
NATURAL GAS:
If the supply gas line pressure is above the operating range, install an in-line gas regulator to the furnace. If supply gas line pressure is below the operat­ing range, either remove any restric­tions in the gas supply piping or enlarge the gas pipe. See Table 2.
LP GAS:
If the supply gas line pressure is above the operating range, have the LP sup­plier reduce the line pressure at the regulator. If supply gas line pressure is below operating range, have the LP supplier adjust the line pressure at the regulator. See Table 3.
NOTE: Depending on the amount of LP vapor and the outdoor ambient tem­perature, the LP storage tank may require supplemental heat to maintain proper pressure levels. Ensure LP stor­age tank does not drop below 15% capacity during heating season.
FIGURE 16
TYPICAL HOSE CONNECTION TO LINE PRESSURETAP
TABLE 2
NATURALGAS PIPE CAPACITYTABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of 0.60 (natural gas).
Nominal Length of Pipe, Feet Iron Pipe
Size, Inches 10 20 30 40 50 60 70 80
1/2 132 92 73 63 56 50 46 43 3/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 1-1/4 1,050 730 590 500 440 400 370 350 1-1/2 1,600 1,100 890 760 670 610 560 530
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be determined by consulting the local natural gas utility or the LP gas supplier.
Gas Input of Furnace (BTU/HR) Heating Value of Gas (BTU/FT3)
TABLE 3
LP GAS PIPE CAPACITYTABLE (CU.FT./HR.)
21
ADJUSTING OR CHECKING FURNACE INPUT
NATURAL GAS:
The maximum gas supply pressure to the furnace should be 10.5” W.C. for natural gas. The minimum gas supply pressure for purposes of input adjust­ment to the furnace should be 5” W.C.
A properly calibrated manometer or gauge is required for accurate gas pressure readings.
1. When adjusting the furnace input, the high fire input should be checked. The high fire manifold pres­sure should be 3.5' W.C. Follow these steps to be sure the furnace is high fire mode:
a. With a single stage thermostat,
the furnace runs for 12 minutes on low fire before shifting to high fire. To be certain that it is on high fire, jump terminals “W” and “W2” on the control board in the blower compartment.
b. With a two stage thermostat, set
the thermostat to its highest set­ting to keep the furnace operating in the high fire mode.
2. To adust high fire manifold pressure, remove the adjustment cover screw on the outlet end of the gas valve and turn the adjustment screw clock­wise to increase the pressure and counterclockwise to reduce the pres­sure. Replace the cover screw securely.
3. The low fire manifold pressure should be 1.7" W.C. As mentioned above, the furnace remains in the low fire mode for 12 minutes upon a heat call with a single stage thermo­stat. With a two stage thermostat, disconnect the thermostat lead to the “W2” terminal on the control board and the furnace will remain in the low fire mode. To adjust the pressure, remove the regulator cover, on top of the valve, and adjust as noted under Step 2, above. After the adjustment replace the screw cover securely.
NOTE: Use a 3/32allen wrench for
making the pressure adjustment.
LP GAS:
Furnaces for use on LP gas, the LP gas supply pressure must be set between
11.0” and 13.0” W.C. by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas control valve. For elevations up to 7,000 feet, rating plate input ratings apply. For high alti­tudes (elevations 7,000 and over) and for any necessary major changes in the gas flow rate the orifice spud must be changed.
TO CHANGE ORIFICE SPUDS:
1. Shut off the manual main gas valve and remove the gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for leaks.
5. Check for proper operation and set to proper manifold pressure.
TABLE 4
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS
INPUT
BTU/HR
50,000
75,000
100,000
125,000
150,000
Input BTU/HR =
METER
CU. FT.
SIZE
ONE 15112 1 15 1 18 3 20 TEN 10 50 12 00 12 30 13 12 30 00
ONE 0 44 0 48 0 50 0 53 20 TEN 7 12 80819 8 48 20 0
ONE 0 33 0 36 0 38 0 40 1 30 TEN 5 24 60615 6 36 15 0
ONE 0 26 0 29 0 30 0 32 1 12 TEN 4 19 4 48 50517 12 0
ONE 0 31 0 24 0 25 0 26 10 TEN 3 36 40410 4 20 10 0
Heating Value of Gas (BTU/Ft3) x 3600 x correction factor Time in Seconds (for 1 cu.ft.) of Gas
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
Check of input is important to pre­vent over firing of the furnace beyond its design-rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE.
TO CHECK FURNACE INPUT:
1. Make certain that all other gas appliances are shut off, with the exception of pilot burners.
2. Start the furnace
3. Time the meter to measure the time required to burn one cubic foot of gas.
4. Use Table 4 to determine input rate.
22
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRI­CAL CONNECTIONS. FAILURETO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSON­AL INJURY OR DEATH.
WARNING
!
THE CABINET MUST HAVE AN UNINTERRUPTED GROUND ACCORDINGTO THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, ANSI/ NFPA70-, OR IN CANADA,THE CANADIAN ELECTRICAL CODE, CSA-C22.1 OR LOCAL CODES THAT APPLY. A GROUND SCREW IS PROVIDED IN THE JUNCTION BOX. FAILURE TO PROPERLY CONNECTTHE GROUNDWIRE CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSON­AL INJURY OR DEATH.
ate wiring diagramlocated on the inside cover of the furnacecontrol box and in these instructions.
NOTE:The electrical junction box may be moved to the right sideif necessary. A knockout is provided.Seal the opposite holewith plugprovided.
WARNING
!
L1TERMINAL AND NEUTRALTERMI­NAL POLARITY MUST BE OBSERVED WHENMAKINGFIELD CONNECTIONS TOTHE FURNACE. FAILURETO DO SOWILL EXPOSE LIVEWIRING IN THE BLOWER COMPARTMENTWHEN THE DOOR IS REMOVED.TOUCHING THESE LIVE CIRCUITS COULD RESULT IN PERMANENT INJURY OR DEATH FROMELECTRICALSHOCK.
FIGURE 17
JUNCTION BOX LOCATION
UPFLOW/HORIZONTAL
Make all electrical connections in accordance with the latest edition of the National Electrical Code ANSI/NFPA70 – or in Canada, the Canadian Electrical Code Part 1­CSA Standard C22.1 and local codes having jurisdiction.
These may be obtained from: National Fire Protection
Association, Inc. Batterymarch Park Quincy, MA 02269
Canadian StandardsAssociation 178 Rexdale Boulevard Rexdale, Ontario, Canada M9W 1R3
WARNING
!
THIS FURNACE IS EQUIPPED WITH A BLOWER DOOR SAFETY SWITCH. DO NOT DISABLETHIS SWITCH. FAILURETO FOLLOW THISWARNING CAN RESULT IN ELECTRICAL SHOCK, PERSON­AL INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical compo­nents are protected from water.
A grounding wire is provided to connect to the incoming grounding wire from line power. The furnace must be perma­nently grounded in accordance with all national and local codes.
Before proceeding with the electrical connections, be certain that the service panel voltage, frequency and phase cor­responds to that specified on the fur­nace rating plate. Maximum over-current protection is 15 amperes.
Use a separate,fused branch electrical circuitcontaininga properly sizedfuse or circuitbreaker. Connect this circuitdirectly fromthe main switchbox to an electrical disconnect that is readily accessible and locatedwithin arm’s reach (2 ft.)of the furnace. Connect fromthe electrical dis­connectto the junction boxon the left sideof the furnace, inside the blower compartment. See Figure 17.For the proper connection,refer to the appropri-
DOWNFLOW
23
ELECTRICAL CHECKS
Line Power Check
The furnace must have a nominal 115 volt power supply for proper opera­tion. If there is not a consistent power supply, contact a licensed electrician to correct the problem.
1. With the blower compartment door off, manually hold the push button door switch in.
2. Call for heat at the thermostat.
3. With the unit operating, use a volt­meter to measure the voltage from any 120 VAC terminal to any neu­tral connection.
4. The voltage should be a nominal 115 volts (acceptable 105­120VAC).
This test should be made with the unit in full operation.
Polarity Check
If line & neutral are reversed, a fault code (26) will be displayed at the fur­nace seven segment display (SSD) and at the communicating thermostat active fault display screen (communi­cating systems only).
Proper line voltage polarity, or phas­ing, is a must for this furnace to oper­ate. Use a volt meter to make this check.
1. With the blower compartment door off, manually hold the push button door switch in.
2. Use a voltmeter to measure the voltage from any 120 VAC terminal to any bare metal ground on the furnace.
3. The voltage should be a nominal 115 volts (acceptable 105­120VAC).
4. Use a voltmeter to measure the voltage from any neutral terminal to the bare metal ground on the furnace.
5. The voltage should be less than
1.0 VAC.
6. If the voltage from any 120 VAC terminal to ground is less than 1.0 VAC volts and the voltage from a neutral to ground is a nominal 115 volts, the polarity is reversed.
7. To correct the problem, either reverse the hot and neutral wires to the furnace or have a licensed electrician check the building wiring.
ControlVoltage Check
1. With the blower compartment door off, manually hold the push button door switch in.
2. Call for heat at the thermostat. (Does not include communicating thermostats.)
3. With the unit operating, use a volt­meter to measure the voltage from control voltage terminal “W” to ter­minal “C” on the furnacecontrol board.
4. The voltage should be a nominal 24 volts (Acceptable 18-30 VAC).
This test should be made with the unit
in full operation.
24
ACCESSORIES
FIELD-INSTALLED OPTION ACCESSORIES
TWINNING: Most installations of (-)GPE/ (-)GLE furnaces cannot be twinned. However, a few exceptions exist for installations with some commercial evaporator coils. Consult the installation instructions of the coil to see if the fur­nace(s) can be twinned. If so, a twinning kit will be required and the part number for the kit can be found in the installation instructions for the coil.
ELECTRONIC AIR CLEANER
Line voltage power is supplied from the screw terminal “EAC”, see Figure 18, and a line voltageneutral screw terminal on the control board. This will power the electronic air cleaner whenever the blower is operating and delivering the recommended minimum CFM. The 50 and 75 KBTU models, which are capa­ble of a maximum delivery of 1200 CFM, will operate the electronic air cleaner at 500 CFM and above. The 100 and 120 KBTU models, which are capable of a maximum delivery of 2000 CFM, will operate the electronic air cleaner at 800 CFM and above. These limits are set to prevent excessive production of ozone at the lower airflows of the furnaceand are based on average requirements of commercially available electronic air cleaners. Continuous fan speeds are selectable and some lower fan speeds may not deliver enough airflow to operate an electronic air cleaner. The IFC deter­mines the minimum airflow necessary to operate an electronic air cleaner and will not turn on the electronic air cleaner unless the airflow is high enough for the EAC.
FIGURE 18
EAC AND HUMIDIFIER TERMINALS ON FUR­NACE CONTROL (IFC)
HUMIDIFICATION AND DEHUMIDIFI­CATION
HUMIDIFIER – The humidifier contacts (labeled “HUM OUT”) are “dry” contacts on the I.F.C. This means that the termi­nals are connected directly to the con­tacts of a board-mounted relay. The coil of the relay is controlled by the microprocessor of the IFC. The coil is engaged roughly any time the heat speed blower is engaged and (1) 24VAC is present on the thermostat ter­minal of the IFC labeled “HUM STAT” or (2) a communicating thermostat with humidification and dehumidification capability is installed with call for humidification present.
FIGURE 19
WIRING FOR OPTIONAL HUMIDIFICATION (AND DEHUMIDIFICATION WITH COMMUNICATING THERMOSTAT) WITH OPTIONAL HUMIDIFIER AND NO HUMIDISTAT (HUMIDIFICATION ACTIVE DURING ANY HEAT CALL) (FOR USE WITH COMMUNICATING AND NON-COMMUNICATING THERMOSTATS)
FIGURE 20
WIRING FOR OPTIONAL DEHUMIDIFICATIONWITH HUMIDIFICATION (WITH OPTIONAL HUMIDISTAT AND HUMIDIFIER) NOTE: CAN BE USED WITH COMMUNICATING OR NON-COMMUNICATING SYSTEMS
An optional 24VAC humidistat can be installed as shown in Figures 19 thru 54 (II thru IV). With the optional humidistat, two separate conditions must be met before humidification can begin 1). There must be a call for heat and the blower must be engaged and 2.) The humidistat must determine that there is a need for humidification.
Note: Dipswitch SW2-1 (labeled “ODD”) enables (“ON”) or disables (“OFF”) dehumidification operation. However, it has no affect on humidi­fication operation. If this switch is set to the “ON” position and no humidistat is installed, the cooling
25
FIGURE 21
WIRING FOR OPTIONAL DEHUMIDIFICATION OPERATION AND HUMIDIFICATION WITH OPTIONAL HUMIDIFIER (HUMIDIFIER WITH INTERNAL POWER SUPPLY) (FOR USE WITH NON-COMMUNICATINGTHERMOSTATS)
FIGURE 22
HUMIDISTAT USEDTO CONTROL DEHUMIDIFICATION IN COOLING ONLY (NO HUMIDIFIER) (FOR USE WITH NON-COMMUNICATINGTHERMOSTATS)
airflow will be permanently reduced by approximately 15% giving less than optimal performance and possibly caus­ing problems. It is not recommended to leave this switch in the “ON” position without a humidistat installed.
Control of dehumidification in cooling and/or humidification in heating can be done with a variety of methods depend­ing on whether there is a communicat­ing thermostat or a humidistat available and depending on the type of operation desired.
With systems configured with communi­cating thermostats and condensers, dehumidification is controlled by the condenser and is not affected by the position of dipswitch SW2-1 or the volt­age (or lack of voltage) at the thermo­stat terminal labeled “HUM STAT”.
To determine which wiring diagram and method to use, select from the following configurations:
A. HUMIDIFICATION CONTROL ONLY
WITH NO DEHUMIDIFICATION (REQUIRES OPTIONAL HUMIDIFI­ER).
A1. WITH COMMUNICATING
THERMOSTAT Humidifier control is included with the (-)HC-TST412MDMS (modulating, non-communicat­ing) and (-)HC-TST550CMMS (full-color communicating) model thermostats. However, it is not included with the (-)HC­TST501CMMS model commu­nicating thermostat. The latter thermostat should not be used if humidification control is required. To wire the furnace for humidification control using the former thermostat, refer to the wiring diagram in Figure 19(I). Be sure not
to install the
jumper between “R” and “HUM
STAT” on the furnace con­trol. Installing this jumper will operate the humidifier any time there is a heat call. Without the jumper, the humidification call from the thermostat must be active and a heat call must be pre­sent with the blower running.
A2. WITH NON-COMMUNICAT-
ING THERMOSTAT A2-1 CONTINOUS HUMID-
IFIER OPERATION DURING HEATING. For continuous humid­ifier operation during heating, refer to Figure 19 (I) and make sure to install the jumper between the thermostat termi­nals labeled “R” and “HUM STAT”. A sepa­rate humidistat is not required for this con­figuration and the humidifier will turn on whenever there is a call for heat and the blower is running.
A2-2 CONTROLED
HUMIDIFIER OPERA­TION USING A HUMIDISTAT (REQUIRES OPTION­AL HUMIDISTAT). Controlled humidifica­tion can be accom­plished using a humidistat as shown in Figures 20 (II) or 21 (III). These figures show installation of a humidifier with exter­nal and internal power supplies respectively. Dehumidification oper­ation will be disabled if the dipswitch SW2-1 is in the “OFF” posi­tion. If this switch is in the “ON” position, dehumidification con­trol will be active.
B. DEHUMIDIFICATION CONTROL
WITH NO HUMIDIFICATION B1. For communicating ther-
mostats listed with this fur­nace, dehumidification is controlled automatically when selected at the ther­mostat and additional wiring is not necessary. The actual airflow demand (reduced for dehumidification) is request­ed of the furnace by the condenser.
26
B2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES OPTIONAL HUMIDISTAT).
Control of dehumidification only (no humidification) can be accomplished by installing an optional humidistat as shown in Figure 22 (IV). The dipswitch SW2-1 must be set to the “ON” position. If this switch is not turned “ON”, dehumidification operation will not take place. Further, if this switch is “ON” and no humidistat is installed, airflow in cooling will be perma­nently reduced by approximate­ly 15%.
C. HUMIDIFICATION AND DEHUMIFI-
CATION CONTROL (REQUIRES OPTIONAL HUMIDIFI­ER).
C1. WITH COMMUNICATING
THERMOSTAT
Humidifier control is included with the (-)HC-TST412MDMS (modulating, non-communicat­ing) and (-)HC-TST550CMMS (full-color communicating) model thermostats. However, it is not included with the (-)HC­TST501CMMS model commu­nicating thermostat. Do not purchase the latter thermostat if humidification control is required. To wire the furnace for humidification and dehumidi­fication control using the former thermostat, refer to the wiring diagram in Figure 19 (I). Be sure not between “R” and “HUM STAT” on the furnace control. Installing this jumper will oper­ate the humidifier any time
to install the jumper
THERMOSTAT AND ACCESSORIES FOR THERMOSTAT
Programmable Communicating:
(-)HC-TST501CMMS
Full-Color, Programmable Communicating:
(-)HC-TST550CMMS
Remote Sensor:
(For Thermostats Above Only)
F1451378
Thermostat Wall Plate ForThermostat HC-TST501CMMS Above Only:
F61-2600
there is a heat call and dehu­midification will never take place when in cooling. Without the jumper, a humidification call from the thermostat must be active and a heat call must be present with the blower running for the “HUM OUT” relay con­tacts to close.
C2. WITH NON-COMMUNICATING
THERMOSTAT (REQUIRES OPTIONAL HUMIDISTAT.)
For non-communicating ther­mostats, an optional humidistat must be installed. Controlled humidification and dehumidifi­cation can be accomplished using a humidistat as shown in Figures 20 (II) or 21 (III). These figures show installation of a humidifier with external and internal power supplies respec­tively. Dehumidification opera­tion will be disabled if the dip­switch SW2-1 is in the “OFF” position. If this switch is in the “ON” position, dehumidification control will be active.
OTHER ACCESSORIES AVAILABLE
FOSSIL FUEL KIT (non-communicat-
ing systems only)
Use of a heat pump with the two stage furnace requires a heat pump thermostat used in conjunction with the fossil fuel kit. For proper operation use the follow­ing procedures:
a. With the RXPF-F01 kit, connectthe
thermostat “E” terminal, one side of the plenum switch, and the black wire from the fossil fuel kit to “W2” on the IFC.
b. For the RXPF-F02 kit, connect
“W” on the fossil fuel kit interface wiring board to “W2” on the IFC.
Regardless of which fossil fuel kit is used, when activated, the two stage furnace follows the sequence of operation for a single stage thermo­stat.
IMPORTANT: ALWAYS FOLLOW THE MANUFACTURER’S FOSSIL FUEL KIT INSTRUCTIONS.
TWINNING: Most installations of (-)GPE and (-)GLE furnaces cannot be twinned. However, a few excep­tions exist for installations with some commercial evaporator coils. Consult the installation instructions of the coil to see if the furnace can be twinned. If so, a twinning kit will be required and the part number for the kit can be found in the installation instruc­tions for the coil.
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: Chimney adapter is certified for use on upflow only.
This appliance is CSA certified for use with RXGW-B01 chimney adapter. Refer to kit installation instructions 92-101682-01.
TYPICAL WIRING FOR SELECT ACCESSORIES FOR COMMUNICATING RESIDENTIAL SYSTEMS
The Rheem Serial Communicating (CC2) system allows accessories to be connected to shut down the sys­tem in the event of a fault. Typical devices that can be connected are the drain overflow switch, smoke detector and freeze protection switch. There are two methods of connecting the switch to the system depending on the device configura­tion normally closed or normally open. The blower can run during a fault or the blower can shut off dur­ing a fault depending on how the system is connected. Please refer to local and/or state codes for installing these devices. The following opera­tion applies only when BOTH the condenser and thermostat are serial communicating devices. If the con­denser is non-communicating (tradi­tional, legacy 24VAC controlled) this diagram is not valid.
27
METHOD BLOWER
ACTIVATION
CONTACTS WIRING CONFIGURATION
NORMALLY
OPEN
When 24 VAC is applied to Y1 at the furnace control in a communicating system a SYSTEM BUSY message appears on the thermostat. When the SYSTEM BUSY message appears the outdoor unit will shut down and the indoor unit will continue to run at first stage cooling airflow.
A
BLOWER
RUNS
(Y1)
NORMALLY
CLOSED
If the device does not have normally open contacts an additional relay must be used for proper system operation.
NORMALLY
OPEN
When the device is connected to Y2 and a fault occurs the blower will shut down. The Y2 input can still be used with normally open or normally closed contacts.
B
BLOWER
DOES NOT
RUN
(Y2)
NORMALLY
CLOSED
If the device does not have normally open contacts an additional relay must be used for proper system operation.
OPERATION WITH SELECTED ACCESSORIES
28
80+ HIGH ALTITUDE
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT INPUT RATING FOR INSTALLATION AT ALTITUDES
BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION
DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
D'ALTITUDE.
92-24399-01-01
INSTRUCTIONS (TABLE 13)
!
CAUTION
INSTALLATION OFTHIS FURNACE AT ALTITUDES ABOVE 2000 FT (610 m) SHALL BE IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES,THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54 OR NATIONAL STAN­DARD OF CANADA, NATURAL GAS AND PROPANE INSTALLATION CODE, CAN B149.1.
Furnaces can be ordered from the fac­tory already converted for high altitude elevations. The factory option for high altitude elevations would be ordered as a 278 option (example: a 75k BTU upflow furnace which is factory convert­ed for high altitude elevations would have the model number (-)GPE­07EAMKR). These factory converted furnaces come with pressure switches for high-altitude elevations already attached. Also, different burner orifices are installed at the factory which are one drill size smaller (#43 DMS) than standard (-)GPE/(-)GLE gas furnaces (#42 DMS). The smaller orifice is installed to accommodate for average heating values expected in most high altitude areas and a required 4% per thousand feet reduction in input as specified by the National Fuel Gas Code (NFGC). Specific orifices should always
be recalculated for all high alti­tude installations as outlined below. Orifices should be changed, if neces­sary, based on gas heating value and elevation.
34" 80 Plus furnaces installed above 2,000 ft. require the furnace to be de­rated 4% per thousand feet.
IMPORTANT: Factory installed orifices are calculated and sized based on a sea level Natural Gas heating value of 1075 BTU per cubic ft.
NOTE:Orifices are available through your local distributor.
Reference Tables 11, 12 and 13 for appropriate orifice sizing.
NOTE:Keep any parts removed during LP conversion procedure stored with the product literature for future use.
The following are examples of orifice sizing using the National Fuel Gas Code Appendix F:
Example: 900 BTU/ft Natural Gas Heating Value
I/H = Q 25000 / 900 = 27.78 ft
I = Sea Level input (per burner): 25000 H = Sea Level Heating Value: 900 Q = 27.78 ft
3
Natural Gas per hour.
From Table F.1 of National Fuel Gas Code Handbook, 2002 (3.5w.c. col- umn).
Orifice required at Seal Level: #40 From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4% de-rate per thousand ft): #42
3
Regional
3
Orifice required at 8000 ft. elevation (4% de-rate per thousand ft.): #44
TABLE 11
LP GAS
Example: 1050 BTU/ft3 Regional Natural Gas Heating Value
I / H = Q 25000 / 1050 = 23.81ft
3
I = Sea Level input (per burner): 25000 H = Sea Level Heating Value: 1050 Q = 23.81 ft
3
Natural Gas per hour.
From Table F.1 of Natural Fuel Gas Code Handbook, 2002 (3.5w.c. col- umn).
Orifice required at Sea Level: #43 From Table F.4 of National Fuel Gas
Code Handbook, 2002
Orifice required at 5000 ft. elevation (4% de-rate per thousand ft.): #45
Orifice required at 8000 ft elevation (4% de-rate per thousand ft): #47
LP GAS (TABLE 11)
LP Gas is a manufactured gas that has consistent heating value across most regions.
The NFGC guidelines are used with the following exception:
The recommended LP Gas high altitude orifice selections differ slightly in that the NFGC LP orifice chart, as they are not accurate for Rheem products. The National Fuel Gas Code LP orifices are based on an 11" of water column pres­sure at the orifice, which differs from products that use 10" of water column at the orifice. This difference requires a deviation from the NFGC orifice size recommendations. The Sea Level input
Altitude burner) 25000 Size
0 to 2000 ft. 25000 #54 2000-3000 24000 #54 3000-4000 23000 #54 4000-5000 22000 #54 5000-6000 21000 #54 6000-7000 20000 #54 7000-8000 19000 #55 8000-9000 18000 #55
9000-10000 17000 #55
sand ft. and the orifice size must be selected based on the reduced input in Table 11.
ORIFICE ORDERING INFORMATION
Orifice sizes are selected by adding the 2-digit drill size required in the orifice part number. Drill sizes avail­able are 39 through 64; metric sizes available 1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill size)
Example 1: # 60 drill size orifice required Part # 62-22175-60
Example 2:
1.15mm drill size orifice required Part # 62-22175-91
should still be reduced by 4% per thou-
TABLE 12
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE
NATURAL GAS LP GAS
ORIFICE
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
50,000
75,000 100,000 125,000 150,000
45,000
67,500
90,000 112,500 135,000
OUTPUT
40,000 60,000
80,000 100,000 120,000
36,000
54,000
72,000
90,000 108,000
SIZE
#42
#42
MANIFOLD
PRESSURE
3.5” W.C.
2.9” W.C.
ALTITUDE
0’ - 2000’
2001’ - 4500’
FIGURE 23
MANIFOLD PRESSURE-CHANGE LABEL
INPUT
50,000
75,000 100,000 125,000 150,000
45,000
67,500
90,000 112,500 135,000
Input (per Orifice
ORIFICE
OUTPUT
40,000 60,000
80,000 100,000 120,000
36,000
54,000
72,000
90,000 108,000
SIZE
#54
#54
MANIFOLD PRESSURE
10” W.C.
8.1” W.C.
29
Loading...
+ 67 hidden pages