INSTALLATION INSTRUCTIONS
FOR REPLACEMENT UNCASED COILS FOR AIR HANDLERS: RCSA: featuring R-22 Refrigerant RCSL: featuring earth-friendly R-410A
RCSL: Refrigerant
WARNING
!
These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and opera­tion of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, serv­ice or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
NOTE: Shown with Horizontal Drip Shield.
(Requires RXHH- Horizontal Adapter Kit.)
!
!
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL- LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2000
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
TABLE 1
R-22 UNCASED COILS: RCSA- ACCESSORY INFORMATION
RCSA-HU2417AU 1817 and 2417 2417 2417 RXHH-A02
RCSA-HU3617AU 3017 and 3617 3617 3617 RXHH-A03
RCSA-HU3621AU 3621 3621 3621 RXHH-A03
RCSA-HU4821AU 4221 and 4821 4821 4821 RXHH-A04
RCSA-HU4824AU 4824 4824 4824 RXHH-A04
RCSA-HU6024AU 6024 6024 RXHH-A05
2
RC S A — HU24 17 A U
AIR HANDLER COIL
U = UNCASED
DESIGN VARIATION
A= 1stDESIGN
COIL SIZE
17 = 17.5" [431.8mm] 21 = 21" [533.4 mm] 24 = 24.5" [609.6 mm]
NOMINAL CAPACITY #
24 = 18,000 TO 24,000 BTUH
24 = [5.27 to 7.03 kW]
36 = 30,000 TO 36,000 BTUH
24 = [8.79 to 10.55 kW]
48 = 42,000 TO 48,000 BTUH
24 = [12.31 to 14.06 kW]
60 = 60,000 BTUH
24 = [17.58 kW]
AIRFLOW DIRECTION*
HU = A/C or Heat Pump,
HU = Upflow, Downflow or Horizontal
S = PRODUCT GENERATION
REFRIGERANT
A = R-22 L = R-410A
CLASSIFICATION
C = COIL
TRADE BRAND
FIGURE 1
MODEL NUMBER EXPLANATION
GENERAL
RCSA- and RCSL- are replacement only uncased coils. RCSA- replacement coils are used only in (-)HKA, (-)HLA and (-)HSA R-22 air handlers. RCSL- replacement coils are used only in (-)HKL, (-)HLL and (-)HSL R-410A air handlers.
For horizontal applications, a horizontal drip shield must be installed to catch excess condensate drainage. RCSA and RCSL replacement coils are shipped without a horizontal drip shield. For a hori­zontal adapter kit, refer to Tables 1 and 2 for cor­rect kit matchups.
The drain pan that comes with the RCSA- or RCSL- Uncased Air Handler Coil is not built with a high-heat resistant material. Do NOT use these coils with gas and oil fossil fuel furnaces, or any other high-heat device. Failure to obey this warning could result in serious equipment damage, personal injury or death.
Replacement
R-22 Uncased Coil
Model
(-)HSA-HM/AU
(-)HLA-HM
(-)HKA-HM
Original
R-22 Air Handler Model
Horizontal Adapter Kit
Model Number
TABLE 2
R-410A UNCASED COILS: RCSL- ACCESSORY INFORMATION
RCSL-HU2417AU 1817 and 2417 2417 2417 RXHH-A02
RCSL-HU3617AU 3017 and 3617 3617 3617 RXHH-A03
RCSL-HU3621AU 3621 3621 3621 RXHH-A03
RCSL-HU4821AU 4221 and 4821 4821 4821 RXHH-A04
RCSL-HU4824AU 4824 4824 4824 RXHH-A04
RCSL-HU6024AU 6024 6024 RXHH-A05
Replacement
R-410A Uncased Coil
Model
(-)HSL-HM/AU
(-)HLL-HM
(-)HKL-HM
Original
R-410A Air Handler Model
Horizontal Adapter Kit
Model Number
CM 0805
WARNING
!
*All replacement coils for HM and AU air handler applications will be HU.