Rheem RCQD Installation Manual

Page 1
INSTALLATION INSTRUCTIONS
WARNING
ISO 9001:2008
FOR RCQD COILS
SUPERSEDES 92-100105-05-02
92-100105-05-03
Page 2
TABLE OF CONTENTS
Model Number Explanation .. . . . . . . . . . . . . . . . . . . . . . 2
Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Airflow Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Coil Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 5
Codes/Regulations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Coil Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Vertical Upflow and Horizontal Left Installation . . . . . . . . 6
Vertical Downflow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Horizontal Left Installation . . . . . . . . . . . . . . . . . . . . . . . . 7
Horizontal Right Installation . . . . . . . . . . . . . . . . . . . . . . . 7
FIGURE 1
MODEL NUMBER EXPLANATION
RCQD—24 17 AS
Refrigerant Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 7
TXV Sensing Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Condensate Drain Tubing . . . . . . . . . . . . . . . . . . . . . . . . 7
Horizontal Drain Pan Extension . . . . . . . . . . . . . . . . . . . . 9
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Plenum Adapter Accessory . . . . . . . . . . . . . . . . . . . . . . 10
Sweat Variation
A - 16 & 18 SEER Application
Coil Casing 17 = 17" [431.8 mm] 21 = 21" [533.4 mm] 24 = 24" [609.6 mm]
Nominal Capacity 24 = 24,000 BTUH
[7.03 kW]
36 = 36,000 BTUH
[10.55 kW]
48 = 48,000 BTUH
[14.06 kW]
60 = 60,000 BTUH
[17.58 kW]
Design Series
Type of Coil Q=High Efficiency AC/Heat Pump Coil
with Expansion Valve
Coil
TRADE NAME
Page 3
FIGURE 2
197/8
UNIT SPECIFICATIONS
AIRFLOW
FRONT VIEW
3/4 NPT DRAIN (SECONDARY)
3/4 NPT DRAIN
(PRIMARY)
A
PLENUM WIDTH
“A” Minus One Inch
B
3-3/8
1-51/64
LIQUID LINE
C
SIDE VIEW
SUCTION LINE
7-5/8
5-5/8
22
DIMENSIONS AND WEIGHTS DATA
Coil
Model
Number
RCQD-2417AS 3/8 [9.53] 3/4 [19.05] 17-1/2 [445] 19-7/8 [505] 28 [711] 59 [27] 67 [30] RCQD-3621AS 3/8 [9.53] 7/8 [22.23] 21 [533] 24-3/4 [629] 28 [711] 74 [34] 83 [38] RCQD-3624AS 3/8 [9.53] 7/8 [22.23] 24-1/2 [622] 24-3/4 [629] 28 [711] 80 [36] 90 [41] RCQD-4821AS 3/8 [9.53] 7/8 [22.23] 21 [533] 24-3/4 [629] 28 [711] 74 [34] 83 [38] RCQD-4824AS 3/8 [9.53] 7/8 [22.23] 24-1/2 [622] 24-3/4 [629] 28 [711] 80 [36] 90 [41] RCQD-6024AS 3/8 [9.53] 7/8 [22.23] 24-1/2 [622] 24-3/4 [629] 28 [711] 80 [36] 90 [41]
Connections
Sweat (in.) [mm]
Liquid Suction
I.D. I.D.
ABC
Dimensions (in.) [mm] – Weight (lbs.) [Kg]
Coil Weight
(lbs.) [Kg]
Shipping Weight
(lbs.) [Kg]
Page 4
TABLE 1
COIL SPECIFICATIONS / AIRFLOW PRESSURE DROP
Approx.
Model
Number
RCQD-
Type
Flow
Air
Design
Air Flow
CFM [L/s]
Range
HIGH EFFICIENCY COOLING COILS
2417AS U-H
3621AS U-H
3624AS U-H
4821AS U-H
4824AS U-H
6024AS U-H
450/800 4.38
[212/378] [0.41] [.015] [.024] [.035] [.042] [.052] [.062] [.072]
720/1200 5.83 [340/566] [0.54] [.02] [.025] [.032] [.04] [.045] [.052]
720/1200 5.83 [340/566] [0.54] [.017] [.022] [0.27] [0.32] [0.37] [0.42]
960/1600 5.83 [453/755] [0.54] [.035] [.042] [.047] [.055] [.062] [.072] [.08]
960/1600 5.83 [453/755] [0.54] [.027] [.032] [.037] [.042] [.047] [.057] [.062]
1050/1700 5.83
[496/802] [0.54] [.027] [.032] [.037] [.042] [.047] [.055] [.060] [.067]
H = Horizontal airflow, U = Upflow
Face Area
Sq. Ft.
[m
Fins-in.
Rows Deep
2
]
600
[283]
0.06 0.10 0.14 0.17 0.21 0.25 0.29
14/3
14/3
14/3
14/3
14/3
14/3
Static Pressure Drop Through Wet Cooling Coil [kPa] (Inches H
700
800
900
1000
1100
1200
[330]
[378]
[425]
[472]
[519]
[566]
1300 [614]
0.08 0.10 0.13 0.16 0.18 0.21
0.07 0.09 0.11 0.13 0.15 0.17
0.14 0.17 0.19 0.22 0.25 0.29 .032
.11 .13 .15 .17 .19 .23 .25
.11 .13 .15 .17 .19 .22 .24 .27
1400 [661]
1500 [708]
2
O) CFM [L/s]
1600 [755]
1700 [802]
1800 [850]
1900 [897]
Page 5
TABLE 2
COIL APPLICATION
Coil Model
RCQD
2417AS
3621AS
4821AS
3624AS, 4824AS,
6024AS
NOTES:
* U = UPFLOW
H = HORIZONTAL
WARNING
!
Type Air
Flow*
U-H U-H U-H U-H U-H U-H U-H U-H U-H U-H
PROPOSITION 65: THIS APPLIANCE CONTAINS FIBERGLASS INSULATION. RESPIRABLE PARTI­CLES OF FIBERGLASSARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER.
All Rheem products meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California'sProposition65 requires warnings for products sold in Californiathat contain or produce any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglassinsulation,lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or pro­duces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturingand shipping. We can­not always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemi­cals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural gas used with some of our products. Listed below are those chemi­cals and substances commonly associatedwith similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide(CO).
• Formaldehyde
• Benzene More details are availableat the websitesfor OSHA
(OccupationalSafety and Health Administration), at www.osha.gov
and the State of California’s OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org
. Consumer education is important since the chemicals and substanceson the list are found in our daily lives. Most consumersare aware that products pre­sent safety and health risks, when improperly used, han­dled and maintained.
Furnace Width
inches [mm]
Oil Gas
21 [533]
21 [533]
24-1/2 [622]
I. INSPECTION
Immediatelyupon receipt, all cartons,and contents should be inspected for transit damage. Units with damaged car­tons should be opened immediately. If damage is found, it should be noted on the deliverypapers and a damage claim filed with the last carrier.
• Afterunit has been delivered to job site, remove carton taking care not to damage unit.
• Checkthe unit rating plate to be sure equipment match­es what is required for the job specification.
• Read the entire instructions before starting the installa­tion. This is particularlyimportant if this is the first instal­lation for this specific model series.
• Many installationsteps done prior to setting the unit in place can save time and simplify the installation.
II. GENERAL INFORMATION
CODES/REGULATIONS
Units should be installed in accordance with any local code which may apply and the national codes. Latest edi­tions are available from: “National Fire Protection Association,Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA Latest Edition (NEC) National Electrical Code.
• NFPA90A Installation of Air conditioning and Ventilating Systems.
• NFPA90B Installation of Warm Air Heating and Air Conditioning Systems.
REPLACEMENT PARTS
Any replacement part must be the same as or an approved alternate to the original part supplied. The man­ufacturer will not be responsible for replacement parts not designed to physically fit or operate within the design parameters the original parts were selected for.
When ordering replacement parts, it is necessary to order by part number and include the complete model number and serial number from the unit rating plate. (See parts list for unit component part numbers.)
Plenum Adapter
Upflow
17-1/2 [445] N/A
14 [356]
21 [533]
17-1/2 [445]
21 [533]
17-1/2 [445]
24-1/2 [622]
21 [533]
RXBA-AC
N/A N/A
RXBA-AC
N/A
RXBA-AC
N/A N/A
RXBA-AC
Page 6
III. INSTALLATION
COIL INSTALLATION
CAUTION
!
WHEN INSTALLING A UNIT WITH COOLING COIL OVER A FINISHED CEILING AND/OR LIVING SPACE, INSTAL­LATION OF A SECONDARY FIELD FABRICATED DRAIN PAN UNDER THE ENTIRE UNIT, TO AVOID DAMAGE TO CEILING, IS RECOMMENDED.
RCQD- coils can be applied in various upflow and horizon­tal flow configurations. (See Figure 3. Refer to Table 2 for approved applications).
CAUTION
!
FOR HORIZONTAL APPLICATIONS, THE HORIZONTAL DRAIN PAN MUST BE LOCATED UNDER THE INDOOR COIL. FAILURE TO PLACE THE PAN UNDER THE COIL CAN RESULT IN PROPERTY DAMAGE.
FIGURE 3
FACTORY SHIPPED COIL INSTALLATION
VERTICAL UPFLOW AND HORIZONTAL LEFT INSTALLATION
(SEE FIGURE 3)
1. For vertical or horizontal left installation, no modifica-
tion from current factory configurationis required.
2. Seal the gap around the refrigerant lines with the per-
magum provided in the parts bag.
NOTE: The coil is shipped from factory for the vertical or horizontal left position. The coil must be convertedfor use in horizontal right position.
VERTICAL DOWNFLOW
IMPORTANT: The RCQD-series coil is not approved for vertical downflow applications.
CAUTION
!
SEVERE CONDENSATE BLOWOFF CAN OCCUR IF THE RCQD COIL IS APPLIED IN A VERTICAL DOWNFLOW APPLICATION.
HORIZONTAL LEFT
UPFLOW
FIGURE 4
HORIZONTAL RIGHT INSTALLATION
Page 7
HORIZONTAL LEFT INSTALLATION
All RCQD-series coils are shipped for vertical and horizon­tal left applications. Conversion is required for horizontal right applications.
HORIZONTAL RIGHT INSTALLATION
(SEE FIGURE 4) THE FOLLOWING COIL MODIFICATIONS MUST BE IMPLEMENTED:
1. Remove the entire front panel assembly by removing all necessary screws.
2. Remove the refrigerant access panel from the front panel and reinstall it with the right-handside mounting holes (see Figure 5).
3. Switch the positions of the left condensate plate and right blank plate on the front panel.
4. Slide the coil outside of the coil box.
5. Remove the vertical bracket on the right side of the ver­tical drain pan (see Figure 6).
6. Removethehorizontal drainpanandplace it on the right sideofthecoil(see Figure7).
7. Re-install the vertical bracket on the left side of the verti­cal drain pan.
8. Remove all screws from the top of the air stop (see Figure 8).
9. Remove the center drain trough by removing the screw located at the back triangular plate (see Figure 8). Ensure glue stop on the bottom of the drain trough.
10. Rotate the center drain trough 180°, front to back (see Figure 9).
NOTE: Failure to properly rotate the center drain trough
may permit condensate water to blow off the cooling coil.
11. Apply permagum supplied in parts bag to underside of drain trough (see Figure 10) in four corners.
12. Re-install the center drain trough and secure it by tightening the screw through the hole located on the front triangular plate. Reinstall the top air stop.
13. Replace the coil assembly into the coil box (be sure to align the vertical bracketsproperly with the side rail), taking care not to tear insulation.
14. Locate TXV sensing bulb and slide it through the uni­versal grommet on the access panel.
15. Reinstall front panel.
16. Seal the gap around the refrigerant lines with the per­magum provided in the parts bag.
REFRIGERANT CONNECTIONS
Keep the coil connections sealed until refrigerant connec­tions are to be made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information.
Install refrigerant tubing so that it does not block service access to the front of the unit.
Use a brazing shield to protect the cabinet’s paint from being damaged by torch flames.
Coil is shippedwith a low (5 - 10 PSIG) pressure charge of dry nitrogen. Evacuate the system before charging with R­410A refrigerant.
FIGURE 5
REFRIGERANT ACCESS PANEL
NOTE: WHEN CON­VERTING TO HORIZON­TAL RIGHT INSTALLA­TION, USE THE RIGHT­HAND SIDE MOUNTING HOLES IN THE REFRIG­ERANT ACCESS PANEL
TXV SENSING BULB
IMPORTANT:Do notperformanybrazingwiththeTXVbulb attachedto theline.
Afterbrazingoperationshavebeencompleted,clamptheTXV bulb securelyonthe suctionlineat the 2 o’clock position with the strapprovidedinthepartsbag.
InsulatetheTXVsensingbulbandsuction linewith the provid­ed pressure sensitiveinsulation (size4”x 7”) and secure with providedwireties.
NOTE:TXVsensing bulbshould be located on a horizontal section of suction line,justoutsideofcoilbox.
CONDENSATE DRAIN TUBING
Consultlocalcodesorordinancesforspecificrequirements. IMPORTANT:Whenmakingdrainfittingconnectionstodrain
pan,useathinlayerofteflonpaste,siliconeorteflontapeand installhandtight.
IMPORTANT:When making drainfitting connections to drain pan,donotovertighten.Overtightening fittings can splitpipe connections on drainpan.
• Donotreducedrainlinesizelessthanconnectionsizeprovid­edon condensatedrainpan.
• Alldrainlinesmustbepitcheddownwardawayfromtheunita minimumof1/8”perfootoflinetoensureproperdrainage.
Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or outdoors.
• The drain line should be insulated wherenecessary to pre­ventsweatinganddamageduetocondensate forming on the outside surface of the line.
• Make provisions fordisconnectingandcleaningofthepri­mary drain line should it become necessary. Install a 2 in.trapintheprimarydrain line as closetotheunitas possible. Make sure that the top of the trap is below connection to the drain pan to allow complete drainage of pan (see Figure 5).
Page 8
FIGURE 6
VERTICAL BRACKET
FIGURE 7
DRAIN PAN PLACEMENT
FIGURE 8
AIR STOP SCREWS
SCREW REMOVAL
DRAIN
TROUGH
SCREW
FIGURE 9
ROTATE DRAIN TROUGH
FIGURE 10
PERMAGUM APPLICATION
Page 9
FIGURE 11
CONDENSATE DRAIN TRAP
DO NOT OPERATE UNIT WITHOUT
CONDENSATE DRAIN TRAP.
FIGURE 12
HORIZONTAL DRAIN PAN EXTENSION KIT RXCH-A141
DUCT
COIL
AIRFLOW
UNIT
2''
DO NOT OVERTIGHTEN DRAIN FITTING
UNIT MUST BE SLOPED
TOWARD DRAIN CONNECTION.
• Auxiliary drain if used should be run to a place where it will be noticeable if it becomes operational. Occupant should be warned that a problem exists if water should begin running from the auxiliary drain line.
• Test condensate drain pan and drain line after instal­lation is complete. Pour several quarts of water into drain pan, enough to fill drain trap and line. Check to make sure drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the termination of the primary drain line.
HORIZONTAL DRAIN PAN EXTENSION (SHIPPED FROM FACTORY)
Attach the two parallel flanges on the drain pan exten­sion over the vertical flange on the horizontal drain pan. The drain pan extension will extend into the duct as shown in Figure 12.
HORIZONTAL DRAIN PAN
DETAIL A
HORIZONTAL DRAIN PAN
HORIZONTAL DRAIN PAN EXTENSION
SEE DETAIL A
HORIZONTAL DRAIN PAN EXTENSION
IV. MAINTENANCE
For continuing high performance and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to the proper frequency of maintenanceand the avail­ability of a maintenance contract.
AIR FILTER
Check the system filter every ninety days or as often as found to be necessary and if obstructed, clean or replace at once.
Horizontal RCQC Applications Requiring Coil Pan
Extension and Extension Part Number
Coil Size Extension Coil Size Extension
2417AS NONE 2417AS NONE 3021BS 3121AS 3124AS 3617AS 3621AS 3621AS 3624BS 3624AS 4821AS 4821AS 4824AS 4824AS 4921AS
RCQB RCQD
4924AS 6024AS
6124AS
AS-57535-04
AS-57535-07
6024AS
AS-57535-04
AS-57535-07
Page 10
IMPORTANT: DO NOT OPERATE THE SYSTEM WITH­OUT A FILTER IN PLACE.
INDOOR COIL - DRAIN PAN - DRAIN LINE
Inspect the indoor coil once each year for cleanliness and clean as necessary. In some cases, it may be necessary to remove the filter and check the return side of the coil with a mirror and flashlight.
• Generally, the coil can be easily cleaned when it is dry. If the coil is coated with dirt or lint, blow compressed air or nitrogen through the supply air side of the coil fins blowing dirt or lint from the return air side of the coil onto the filter or cardboard placed between filter and coil. Be sure lint and dirt is removed from the filter and return air system.
• If the coil is coated with oil or grease, clean it with a mild automatic dishwasher detergent and water solu­tion. Rinse the coil thoroughly with clear water. Be careful not to splash water excessively into unit and system.
• Inspect the drain pan and condensate drain at the same time the cooling coil is checked. Clean the drain pan and condensate drain by removing any foreign matter from the pan. Flush the pan and drain tube with clear water.
• If the drain tube is restricted, it can generally be cleaned with high pressurewater. Remove the drain line from the unit away from the pan and coil to clear the drain line.
IMPORTANT: Do not use caustic household drain cleaners in the condensate pan or near the indoor coil. Drain cleaners will quickly damage the indoor coil.
V. ACCESSORIES
PLENUM ADAPTER ACCESSORY RXBA-AC
This plenum adapter accessory is for installation on cased indoor cooling and heat pump coils. This allows a nominal size cased coil to be installed on the next small­er size gas or oil furnace. NOTE: This accessory is for
installation on coil casings to fit gas or oil furnaces only - this accessory must not be used on electric furnaces or heat pump air handlers. Consult the instal-
lation instructions packaged with the accessory for prop­er installation. The RXBA-AC (upflow) can be ordered factory installed by designation as “with adapters” in the coil model number.
PLENUM ADAPTER ACCESSORY RXBA-AE
This plenum adapter accessory is for use with the 24-1/2" wide cased indoor cooling and heat pump coils. This allows a 24-1/2” wide cased coil to be installed on a 28” wide oil furnace. This is a field installed accessory only.
10
Page 11
11
Page 12
12
CM 1109
Loading...