Rheem RCF2414STAVUA, RCFL-HU2414CU, RCF2417STAVUA, RCFL-HU2417CU, RCF2417MTAVUA Installation Manual

...
Page 1
INSTALLATION INSTRUCTIONS
WARNING
ISO 9001:2008
FOR UNCASED COILS FOR GAS AND OIL FURNACES: (-)CF: featuring Industry Standard R-410A Refrigerant
These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
!
92-100105-13-01
SUPERSEDES 92-100105-13-00
Page 2
TABLE OF CONTENTS
1.0 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.0 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.2 Codes & Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.4 Model Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.5 Coil Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.5A Coil Specifications: Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . .6
2.5B Coil Specifications: Airflow Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . .7
3.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.2 Refrigerant Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.3 TXV Sensing Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.4 Flow Check Piston . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.5 Condensate Drain Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4.0 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4.1 Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4.2 Indoor Coil - Drain Pan - Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5.0 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.1 Plenum Adapter Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.2 Horizontal Flow Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3 RXBC- Indoor Coil Casing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.4 Uncased Coil Adapter Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2
Page 3
1.0 SAFETY INFORMATION
WARNING
!
These instructions are intended as an aid to qualified licensed service person­nel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, serv­ice or maintenance possibly resulting in fire, electrical shock, property dam­age, personal injury or death.
WARNING
!
PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the State of California to cause cancer.
All manufacturer products meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain or produce any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or pro­duced by, some of our heating and air-conditioning equipment, or found in nat­ural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO).
• Formaldehyde
• Benzene More details are available at the websites for OSHA (Occupational Safety and
Health Administration), at www.osha.gov (Office of Environmental Health Hazard Assessment), at www.oehha.org Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products pres­ent safety and health risks, when improperly used, handled and maintained.
and the State of California’s OEHHA
.
CAUTION
For horizontal applications, the horizontal drain pan must be located under the indoor coil. Failure to place the pan under the coil can result in property dam­age.
CAUTION
It is recommended that an auxiliary/secondary drain pan be installed under units containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage in the primary condensate drain piping.
3
Page 4
2.0. GENERAL INFORMATION
2.1. INSPECTION
Immediately upon receipt, all cartons, and contents should be inspected for transit dam­age. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers and a damage claim filed with the last carrier. Shipping damage is not covered by the warranty.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate to be sure equipment matches what is required for the job specification.
• Read the entire instructions before starting the installation. This is particularly impor­tant if this is the first installation for this specific model series.
• Many installation steps done prior to installing the unit can save time and simplify the installation.
2.2. CODES/REGULATIONS
Units should be installed in accordance with any local or national codes which may apply. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.”
These publications are:
• ANSI/NFPA Latest Edition (NEC) National Electrical Code.
• NFPA90A Installation of Air conditioning and Ventilating Systems.
• NFPA90B Installation of Warm Air Heating and Air Condition ing Systems.
4
Page 5
2.3. REPLACEMENT PARTS
Any replacement part must be the same as or an approved alternate to the original part supplied. The manufacturer will not be responsible for replacement parts not designed to physically fit or operate within the design parameters the original parts were selected for.
When ordering replacement parts, it is necessary to order by part number and include the complete model number and serial number from the coil rating plate. (See parts list for unit component part numbers. Parts are available through the local distributor.)
2.4 MODEL NUMBER EXPLANATION
FIGURE 1
MODEL NUMBER EXPLANATION
RCF24 17 STAUCA*
CASING
U - UNCASED
OPTION CODE
*TBD
MINOR SERIES**
COMPONENT CHANGE COST REDUCTION NON-PERFORMANCE
CHANGES
ORIENTATION
M - MULTIPOISE V - VERTICAL ONLY/CONVERTIBLE* H - DED. HORIZONTAL ONLY
MAJOR SERIES*
FEATURE SET CHANGE PERFORMANCE CHANGE
METERING DEVICE
T - TXV E - EEV P - PISTON
EFFICIENCY
S - STANDARD EFF. M - MID EFF. H - HIGH EFF.
WIDTH
14 - 14” 21 - 21” 17 - 17.5” 24 - 24.5”
CAPACITY
24 - 2 TON 48 - 4 TON 36 - 3 TON 60 - 5 TON
TYPE
F - FURN COIL H - AIR-HANDLER COIL
PRODUCT CATEGORY
C - EVAP COIL
BRAND
R - RHEEM/RUUD
*CONVERTIBLE TO HORIZONTAL USING PARTS FROM ORIGINAL COIL OR USING RXHH KIT.
NEW REPLACEMENT
AVAILABLE COILS ORIGINAL COILS
RCF2414STAVUA RCFL-HU2414CU RCF2417STAVUA RCFL-HU2417CU RCF2417MTAVUA RCFL-HU2617CU RCF2421MTAVUA RCFL-HU2621CU RCF3617STAVUA RCFL-HU3617CU RCF3621STAVUA RCFL-HU3621CU RCF3621MTAVUA RCFL-HU3821CU RCF3624MTAVUA RCFL-HU3824CU RCF4821STAVUA RCFL-HU4821CU RCF4824STAVUA RCFL-HU4824CU RCF6024STAVUA RCFL-HU6024CU RCF2417HTAVUA RCFN-HU2417CU RCF2421HTAVUA RCFN-HU2421CU RCF3624HTAVUA RCFN-U3624CU RCF4824HTAVUA RCFN-HU4824CU RCF6024HTAVUA RCFN-HU6024CU RCF2417SPAVUA RCFP-HU2417CU RCF3617SPAVUA RCFP-HU3617CU RCF3621SPAVUA RCFP-HU3621CU RCF4821SPAVUA RCFP-HU4821CU RCF4824SPAVUA RCFP-HU4824CU
5
Page 6
B
A
4-11/16
1/8
1-11/16
1-13/16
11/16
7/16
3-9/16
5-3/8
21-3/8
1-23/32
FRONT VIEW
SIDE VIEW
SUCTION
TUBE
LIQUID
TUBE
2.5 COIL SPECIFICATIONS
2.5A Coil Specifications: Dimensions & Weights (See Figure 2)
FIGURE 2
DIMENSIONS & WEIGHTS
6
DIMENSIONS AND WEIGHTS DATA
Liquid
Connections I.D. Sweat (in) [mm]
Suction
BA
1
1
/2 [445] 141/2 [368] 43 [19] 48 [21]
1
/2 [445] 177/8 [454] 49 [22] 54 [24]
1
/2 [622] 253/8 [645] 83 [38] 93 [42]
1
/2 [622] 301/4 [768] 100 [45] 110 [50]
/16 [535] 45 [20] 49 [22]
1
/2 [445] 51 [23] 57 [25]
7
/8 [657] 71 [32] 78 [35]
Coil
Model
2414S 3/8 [9.53] 3/4 [19.05] 14 [356] 20
2417S 3/8 [9.53] 3/4 [19.05] 17 2417M 3617S 2417H 3/8 [9.53] 3/4 [19.05] 17 2421M 3621S 2417H 3/8 [9.53] 3/4 [19.05] 21 [533] 17
3621M 4821S 3/8 [9.53] 7/8 [22.23] 21 [533] 25 3624M 4824S 3/8 [9.53] 7/8 [22.23] 24
3624H 4824H 6024H 6024S 3/8 [9.53] 7/8 [22.23] 24
*The 14 inch, 2 ton (-)CFA/(-)CFL Coil (2414/2514) is part of the “N” Design Series, even though the coil shape resembles an “A” design.
Coil Weight
(lbs.) [Kg]
WeightCased Coil Dimensions (in.) [mm]
Shipping Weight
(lbs.) [Kg]
Page 7
2.5B Coil Specifications: Airflow Pressure Drop
TABLE 1
AIRFLOW PRESSURE DROP
Coil
Model
RCF
HIGH EFFICIENCY COOLING COILS
2414S
2417S
2417H / 2417M 3617S
2421M / 2421H 3621S
3621M / 4821S
3624M / 4824S
3624H / 4824H 6024S / 900/1900 9.98
6024H [897] [0.93] [.02] [.025] [.03] [.04] [.05] [.05] [.06] [.070] [.076] [.084] [.094]
NOTE: Represents Coil-Only Airflow Ratings. [ ] Designates Metric Conversion
Approx.
Design
Air Flow
CFM [L/s]
Range
600/900 4.56
[283] [0.42] [.055] [.072] [.090] [.110]
600/900 4.56
[283] [0.42] [.039] [.049] [.059] [.076]
600/1300 5.70
600/1300 5.70
900/1700 8.55
900/1700 8.55
Face
Fins-in./
Area
Rows
Sq. Ft.
Deep
2
[m
]
[0.53] [.03] [.035] [.043] [.053] [.064] [.080] [.092] [.103]
[0.53] [.02] [.03] [.047] [.058] [.069] [.080] [.094]
[0.79] [.03] [.04] [.05] [.056] [.063] [.071] [.081] [.092] [.103]
[0.79] [.03] [.04] [.05] [.056] [.063] [.071] [.081] [.092] [.103]
600
[283]
[330]
.22 .29 .36 .44
16/2
.15 .19 .23 .30
16/2
.11 .14 .17 .21 .26 .31 .36 .41
16/2
.08 .11 .14 .18 .23 .27 .31 .37
16/2
———
16/2
———
16/2
——
14/3
3.0 INSTALLATION
700
Static Pressure Drop Through Wet Cooling Coil [kPa]
800
900
[378]
[425]
0.15 .18 0.2 .22 .25 .28 .32 .36 .41
0.15 0.18 0.2 .22 .25 .28 .32 .36 .41
0.09 0.11 0.14 0.16 0.19 0.21 0.24 .27 .30 .34 .37
CFM [L/s] / (Inches W.C.) [kPa]
1000
1100
1200
1300
1400
1500
1600
[472]
[519]
[566]
[614]
[661]
[708]
——— —— ——— —
——————————
—————
—————
[755]
1700 [802]
1800
1900
[850]
[897]
——
——
TABLE 2
COIL APPLICATION
Coil Model (-)CF
2414S 2417S 2417M 3617S 2417H
2417S 2417M 3617S
2417H
2421M 3621S 3621M 4821S
2421H 4821S
3624H 9824H 6024H 3624M
6024S 4824S
3.1 APPLICATIONS
(-)CF coils can be applied in upflow and downflow applications without modification. Coils to be applied in horizontal left or right application will require the installation of a horizontal drip shield and water management part form old coil. See Figure 3.
Furnace Width
(In.) [mm]
Oil
14 [356]
17 [431]
21 [533]
1
2 [622]
24
FIGURE 3
PARTS TO BE REUSED ON HORIZONTAL COILS ONLY.
Gas
171⁄2 [444]
14 [356] 21 [533]
171⁄2 [444]
1
24
2 [622]
21 [533]
7
Page 8
FIGURE 5
BULB LOCATION
FIGURE 4
BULB LOCATION
3.2 REFRIGERANT CONNECTIONS
Keep the coil connections sealed until refrigerant connections are to be made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information.
Coil is shipped with a low (5 - 10 PSIG) pressure charge of dry nitrogen. Evacuate the system before charging with refrigerant.
Install refrigerant tubing so that it does not block service access to the front of the unit. Nitrogen should flow through the refrigerant lines while brazing. Use a brazing shield to protect the cabinet’s paint from being damaged by torch flames. After the refrigerant connections are made, seal the gap around the connections with
pressure sensitive gasket. If necessary, cut the gasket into two pieces for a better seal (See Figure 4.)
3.3 TXV SENSING BULB
IMPORTANT: DO NOT perform any solderiing with the TEV bulb attached to any line. After soldering operations have been completed, clamp the TEV bulb securely on the
suction line at the 10 to 2 o’clock position with the strap provided in the parts bag. Insulate the TEV sensing bulb and suction line with the provided pressure sensitive
insulation (size 4” x 7”) and secure with provided wire ties. IMPORTANT: TEV sensing bulb should be located on a horizontal section of suction line,
just outside of coil box. Sensing bulb should never be placed on any aluminum tube.
3.4 FLOW CHECK PISTON
NOTICE
!
FOR PROPER SYSTEM OPERATION, IT MAY BE NECESSARY TO REPLACE THE PISTON INSTALLED IN THE INDOOR COIL. CHECK THE SERVICE VALVES ON THIS UNIT TO SEE IF A NOTICE TAG ALONG WITH A PLASTIC BAG CONTAINING A PISTON IS ATTACHED. IF ONE IS PRESENT A CHANGE OF THE PISTON IS REQUIRED. FAILURE TO CHANGE THE PISTON CAN RESULT IN IMPROPER PERFORMANCE OF THE SYSTEM.
The flow check piston is a multi-purpose device. With flow into the compression nut end from the liquid line, the piston is in a check position and acts as the expansion device with flow through the metering orifice in the center of the piston. The “O” ring on the end of the piston prevents refrigerant from bypassing the metering ori­fice. Flow from the metering orifice is centered into a distributor which serves to evenly distribute refrigerant to the evaporator circuits. With flow in the reverse direction (direction of arrows on the distributor body), the piston is forced off the seat and liquid from the condenser is allowed to free flow around the piston.
It is essential that the heat pump indoor and outdoor sections be properly matched. Use only matched components as shown in sales specification sheets.
A piston size that is too small will cause starving and one that is too large will cause flooding. In either case, system performance, reliability and charge balance (heating and cooling) will be unacceptable.
8
Page 9
Change the piston in the distributor on the indoor coil before installing the coil and charging the system following the procedure below:
• Using a back-up wrench on the distributor body, loosen the compression nut to gain access to the piston.
• Using the wire provided with replacement pistons, run (hooked end) through hole in piston.
• Hook nose end of piston and lift gently from distributor body.
• Replace piston with one of proper size (see Table 4), install piston with gasket end of piston in distributor. Do not force piston into distributor.
NOTE: With piston in distributor, seal end should be down and should not be seen looking in end of distributor. Piston must be free to rotate and move up and down. Make sure piston is free to move in distributor body.
• Insure distributor gasket is located properly in the distributor body.
• Replace compression nut using back-up wrench on distributor body. Torque com­pression nut end with 8 to 10 ft. lbs.
• Original piston size is stamped on outside of distributor body. Remove new pis­ton size label from poly bag new piston came in and install new size label on out­side of distributor tube.
• Check fittings for leaks after installation, evacuation and charging is complete.
IMPORTANT: Do not attempt to drill pistons to size in the field. Metering holes have a special chamfered inlet and cannot be modified.
IMPORTANT: Do not replace the neoprene “O” ring on the piston with any type of seal. Contact the parts department for the exactly replacement of “O” ring.
FIGURE 6
PISTON AND DISTRIBUTOR ASSEMBLY
3.5 CONDENSATE DRAIN TUBING
Condensate trap (on gas furnace applications) for the primary drain is optional except when required by local code or ordinance.
IMPORTANT: When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, silicone or Teflon tape and install hand tight.
IMPORTANT: When making drain fitting connections to drain pan, do not overtighten. Overtightening fittings can split pipe connetions on the drain pan.
• Install drain lines so they do not block service access to front of the unit. Minimum
clearance of 24 inches is required for filter, coil or blower removal and service access.
• Make sure unit is level or pitched slightly toward primary drain connection so that
water will drain completely from the pan. (See Figure 7.)
• Do not reduce drain line size less than connection size provided on condensate drain pan.
• All drain lines must be pitched downward away from the unit a minimum of 1/8” per foot of
line to ensure proper drainage.
9
Page 10
• Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or outdoors.
• The drain line should be insulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line.
• Make provisions for disconnecting and cleaning of the primary drain line should it become necessary. Install a 3 in. trap in the primary drain line as close to the unit as possible. Make sure that the top of the trap is below connection to the drain pan to allow complete drainage of pan (See Figure 7).
FIGURE 7
CONDENSATE DRAIN TRAP
DO NOT OPERATE UNIT WITHOUT
CONDENSATE DRAIN TRAP.
UNIT
3''
3''
DO NOT OVERTIGHTEN DRAIN FITTING
UNIT MUST BE SLIGHTLY INCLINED
TOWARD DRAIN CONNECTION.
• Auxiliary drain line should be run to a place where it will be noticeable if it becomes opera­tional. Occupant should be warned that a problem exists if water should begin running from the auxiliary drain line.
• Plug the unused drain connection with the plugs provided in the parts bag, using a thin layer of teflon paste, silicone or teflon tape to form a water tight seal.
• Test condensate drain pan and drain line after installation is complete. Pour water into drain pan, enough to fill drain trap and line. Check to make sure drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the ter­mination of the primary drain line.
CAUTION
It is recommended that an auxiliary/secondary drain pan be installed under units containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage in the primary condensate drain piping.
4.0 MAINTENANCE
WARNING
!
These instructions are intended as an aid to qualified licensed service person­nel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
10
For continuing high performance and to minimize possible equipment failure, it is essen­tial that annual maintenance be performed on this equipment. Consult your local dealer as to the availability of a maintenance contract.
4.1 AIR FILTER
Check the system filter every ninety days or as often as found to be necessary and if obstructed, clean or replace at once.
IMPORTANT: Do not operate the system without a filter in place.
Page 11
4.2 INDOOR COIL - DRAIN PAN - DRAIN LINE
Inspect the indoor coil once each year for cleanliness and clean as necessary. In some cases, it may be necessary to remove the filter and check the return side of the coil with a mirror and flashlight.
IMPORTANT: Do not use caustic household drain cleaners or bleach in the condensate pan or near the indoor coil. Drain cleaners will quickly damage the indoor coil.
5.0 ACCESSORIES
5.1 PLENUM ADAPTER ACCESSORIES
NOTE: In a plenum installation on an unknown manufacturer’s furnace, there must be a minimum of 6” clearance from the top of the furnace to avoid limit-tripping.
RXBA-AE
This plenum adapter accessory is for use with the 24-1/2” wide cased indoor cooling and heat pump coils. This allows a 24-1/2 wide cased coil to be installed on a 28” wide oil furnace. This is a field-installed accessory only.
RXBA-AC (Upflow/Horizontal 80% Furnaces) RXBA-AD (Downflow/Horizontal 90 Plus Furnaces)
This plenum adapter accessory is for installation on cased indoor cooling and heat pump coils. This allows a nominal size cased coil to be installed on the next smaller size gas or oil furnace. NOTE: This accessory is for installation on coil casings to fit gas or oil
furnaces only - this accessory must not be used on electric furnaces or heat pump air handlers. Consult the installation instructions packaged with the accessory for proper
installation.
TABLE 3
HORIZONTAL ADAPTER KIT
Coil Model
RCF2414STAVUA RXHH-A01 RCF2417STAVUA RXHH-A02 RCF2417STAVUA RXHH-A03 RCF2421STAVUA RXHH-A03 RCF3617STAVUA RXHH-A03 RCF3621STAVUA RXHH-A03 RCF3621STAVUA RXHH-A04 RCF3624STAVUA RXHH-A04 RCF4821STAVUA RXHH-A04 RCF4824STAVUA RXHH-A04 RCF6024STAVUA RXHH-A05 RCF2417HTAVUA RXHH-A03 RCF2421HTAVUA RXHH-A03 RCF3624HTAVUA RXHH-A05 RCF4824HTAVUA RXHH-A05 RCF6024HTAVUA RXHH-A05 RCF2417SPAVUA RXHH-A02 RCF3617SPAVUA RXHH-A03 RCF3621SPAVUA RXHH-A03 RCF4821SPAVUA RXHH-A04 RCF4824SPAVUA RXHH-A04
Horizontal Adapter
Kit Model No.
5.2 HORIZONTAL ADAPTER KIT RXHH- (See Figure 8)
This horizontal adapter kit is used to convert an upflow or downflow coil for a horizontal application. See Table 3 to order the proper horizontal adapter kit.
FIGURE 8
HORIZONTAL ADAPTER KIT ILLUSTRATION
AIRFLOW: HORIZONTAL­DUAL DIRECTION
HORIZONTAL ADAPTER KIT (RXHH-)
11
Page 12
5.3 INDOOR COIL CASING RXBC - (See Figure 9 & Table 4)
FIGURE 9
MODEL NUMBER EXPLANATION
RX B C — D 14 I
INSULATION
I = Insulated Blank = Uninsulated
CABINET WIDTH
14 = 14” [355.6 mm] 17 = 17.5” [444.6 mm] 21 = 21” [533.4 mm] 24 = 24.5” [622.3 mm]
DESIGN SERIES
COIL CASING
BLOWER UNIT
ACCESSORY
TRADEBRAND
TABLE 4
UNIT DIMENSIONS & WEIGHTS — RXBC- INDOOR COIL CASINGS
Indoor Coil
Casing Model
Number
Width
In.
Height
In.
Depth
In.
Lbs [Kg] Lbs [Kg]
Supply Air/Return Air OpeningsShipping WeightWeight
Width
In.
Depth
RXBC-D14AI 14 233⁄16 19 [9] 23 [10] 13
1
RXBC-D17AI 17
2 20 18 [8] 23 [10] 161⁄2 RXBC-D21AI 21 20 21-5/8 20 [9] 26 [12] 20 1931⁄32 RXBC-D21BI 21 28 27 [12] 36 [17] 20
1
RXBC-D24AI 24
2 321⁄2 34 [16] 44 [20] 231⁄2
In.
12
Page 13
FIGURE 10
UNCASED COIL ADAPTER KIT ILLUSTRATION
7.7
5.4 UNCASED COIL ADAPTER KIT RXBA- (See Figure 10 & 11)
This uncased coil adapter kit is used to adapt the coil to a furnace or ductwork. See Table 5 to order the proper adapter kit. Each kit contains a quantity a 20 adapters.
1.6
A
TABLE 5
UNCASED COIL ADAPTER KIT
Uncased Coil
Adapter Uncased
Model A Coil
Number Model
RXBA Width In. (-)CFA/L
B14x20 13.1 -HUxx14 B17x20 16.6 -HUxx17 B21x20 20.1 -HUxx21 B24x20 23.6 -HUxx24
20.3
FIGURE 11
UNCASED COIL ADAPTER KIT ASSEMBLED
NOTE: Sliding the coil into the coil rail before attaching coil rack front.
13
Page 14
141516
Page 15
Page 16
CM 0913
Loading...