FORM NO. C11-211 REV. 5
Supersedes Form No. C11-211 Rev. 4
INDOOR COILS
CASED/UNCASED COILS
FOR GAS AND
OIL FURNA CES
AIRFLOW CAPACITIES
600-1,900 CFM
[283-897 L/s]
Rheem®Indoor Coils are designed for use with Rheem outdoor units and are available for vertical upflow or downflow,
and horizontal left or horizontal right airflow. When matched
with Rheem outdoor units, the coils provide a nominal
capacity range from 18,000 BTU/HR [5.24 kW] to 60,000
BTU/HR [17.58 kW].
■ Constructed of aluminum fins bonded to internally
grooved copper tubing.
■ Coils are tested at the factory with an extensive refriger-
ant leak check.
■ Coils have sweat refrigerant connections.
■ Ideally suited for new installations or add on air
conditioning.
■ Feature two sets of
3
/4" [14.1 mm] N.P.T. Condensate
drain connections for ease of connection.
■ Coils are A.R.I. certified for system application with variety
of Rheem outdoor units.
■ Condensate drain pan is constructed of high grade, heat
resistant, corrosion free thermal-set material.
■ Compatible with Germicidal Light System (UV resistant)
■ Bi-Directional airflow eliminates the need to switch any
internal components from horizontal left to right.
■ Unique drain pan design maximizes application flexibility
and condensate removal.
■ Universal Duct Flanges are included with all coil models.
RCFA- featuring
R-22 Refrigerant
RCFL- featuring
New Industry Standard
R-410ARefrigerant

2 Rheem Heating, Cooling and Water Heating
RCFA—HM2414AC
Gas/Oil Furnace Coil
C = Cased
U = Uncased
Design Variation
A = 1st Design
B = 2nd Design
C = 3rd Design
Coil Size
14 = 14" [356 mm]
17 = 17.5" [431.8 mm]
21 = 21" [533.4 mm]
24 = 24.5" [609.6 mm]
Nominal Capacity
24 = 18,000 to 24,000 BTU/HR
[5.27 to 7.03 kW]
36/38 = 30,000 to 36,000 BTU/HR
[8.79 to 10.55 kW]
48 = 42,000 to 48,000 BTU/HR
[12.31 to 14.06 kW]
60 = 60,000 BTU/HR
[17.58 kW]
Cased Coil Airflow:
HM = A/C or Heat Pump, Multi-Position
AU = A/C Only, Upflow/Downflow
Uncased Coil Airflow:
HU = A/C or Heat Pump, Upflow/Downflow
Refrigerant
A = R-22
L = R-410A
F = Product Generation
Classification
C = Coil
Rheem
MODEL NUMBER DATA
Table 1: Coil Specifications/Airflow Pressure Dr op
NOTE: Represents Coil-Only Airflow Ratings
[ ] Designates Metric Conversions
Available Models of RCFA(L) Coils
RCFA(L)-HM2414AC RCFL-HM3617CCRCFA(L)-AU4821BC
RCFA(L)-HM2417AC RCFA(L)-AU4824BC
RCFA-HM3617AC RCFA(L)-AU6024BC
RCFA-HM3621AC RCFA(L)-HU2414AU
RCFA(L)-HM4821AC RCFA(L)-HU2417AU
RCFA(L)-HM4824AC RCFA(L)-HU3617AU
RCFA(L)-HM6024AC RCFA(L)-HU3621AU
RCFA(L)-AU2414BC RCFA(L)-HU4821AU
RCFA(L)-AU2417BC RCFA(L)-HU4824AU
RCFA-AU3617BC RCFA(L)-HU6024AU
RCFA-AU3621BC
Available Models
of RCFL Coils
RCFL-HM2414CC
RCFL-HU2414CU
RCFL-HM2417CC
RCFL-HU2417CU
RCFL-HM3821CC
RCFL-HU3821CU
RCFL-HM3824CC
RCFL-HU3824CU
RCFL-HM4821CC
RCFL-HU4821CU
RCFL-HM4824CC
RCFL-HU4824CU
RCFL-HM6024CC
RCFL-HU6024CU
RCFL-HM3621CC
RCFL-AU3617CC
RCFL-AU3621CC
RCFL-HU3617CU
RCFL-HU3621CU
Coil
Model
RCFA/
RCFL
Approx.
Design
Air Flow
CFM [L/s]
Range
Face
Area
Sq. Ft.
2
[m
]
Fins-in.
Rows
Deep
HIGH EFFICIENCY COOLING COILS
2414
2417
3617
3621
3821/4821
3824/4824
6024
600/1000
[283/472]
600/1000
[283/472]
900/1400
[424/661]
900/1400
[424/661]
1200/1800
[566/850]
1200/1800
[566/850]
1600/1900
[755/897]
4.56
[0.42]
4.56
[0.42]
5.70
[0.53]
5.70
[0.53]
8.55
[0.79]
8.55
[0.79]
9.98
[0.93]
16/2
16/2
16/2 — —
16/2 — —
16/2 — — — — — —
16/2 — — — — — —
14/3 — — — — — — — — — —
600
[285]
.17
[.043]
.15
[.039]
700
[330]
.21
[.053]
.19
[.049]
Static Pressure Drop Through Wet Cooling Coil [kPa] (Inches W.C.) CFM [L/s]
800
900
1000
[380]
.25
[.063]
.23
[.059]
.17
[.043]
.15
[.038]
[425]
.31
[.080]
.30
[.076]
.21
[.053]
.18
[.047]
[470]
.40
[.100]
.38
[.096]
.26
[.064]
.23
[.058]
1100
[519]
.46
[.117]
.45
[.113]
.31
[.080]
.27
[.069]
1200
1300
1400
1500
1600
1700
[565]
[614]
[660]
[708]
[755]
[802]
1800
[850]
— — — — — — — —
— — — — — — — —
.36
.41
[.092]
.31
[.080]
.22
[.056]
.22
[.056]
[.103]
[.094]
[.063]
[.063]
— — — — — —
.37
— — — — — —
.25
.28
.32
.25
[.071]
.28
[.071]
[.081]
[.081]
.32
.36
[.092]
.32
[.081]
[.103]
[.103]
.27
[.070]
[.076]
.41
.41
.30
— —
— —
.34
[.084]
1900
[897]
.37
[.094]

Rheem Heating, Cooling and Water Heating 3
[ ] Designates Metric Conversions
FRONT VIEW
SIDE VIEW
FIGURE 1: DIMENSIONS
➀ Casing top and bottom openings are the same dimensions.
Table 2: Coil Dimensions and W eights
*The 14 inch, 2 ton RCFA/RCFL coil (2414) is part of the “N-Coil” design series, even though the coil shape resembles an “A” coil design.
[ ] Designates Metric Conversions
Coil
Model
RCFA/RCFL
2417
3617
3621
3821/4821
3824/4824
Sweat (in.) [mm]
Liquid Suction
I.D. I.D.
3
/8[9.53]
3
/8[9.53]
3
/8[9.53]
3
/8[9.53]
3
/8[9.53]
3
/8[9.53]
3
/8[9.53]
3
/4[19.05] 14 1/2[356] 21 1/2[533] 46 [21] 233/16[584]
3
/4[19.05] 171/2[445] 141/2[368] 46 [21]
3
/4[19.05] 171/2[445] 177/8[454] 52 [24] 57 [26]20 1/2[508]
3
/4[19.05] 21 1/2[533] 171/2[445] 54 [24] 60 [27]20 1/2[508]
7
/8[22.23] 21 1/2[533] 257/8[657] 76 [34]
7
/8[22.23] 241/2[622] 253/8[645] 89 [40] 99 [45]32 1/2[812]
7
/8[22.23] 241/2[622] 301/4[768] 108 [49]
A B
Connections
Cased Coil Dimensions
(in) [mm]
C
28 1/2[711]
Coil Weight
(lbs.) [Kg.]
Weight
Shipping Weight
(lbs.) [Kg.]
50 [23]2414*
51 [23]20 1/2[508]
83 [38]
118 [55]32 1/2[812]6024
197/8
[505 mm]
A MINUS ONE INCH ➀
NOTE:
FLANGES ARE
PROVIDED
FOR FIELD
INSTALLATION
13
/16 [46 mm]
53/8
[136.5 mm]
PRIMARY DRAIN
3
/4 N.P.T.
(VERTICAL &
HORIZONTAL)
1
1
/4 [57.1 mm]
2
SECONDARY DRAIN
3
/4 N.P.T. (VERTICAL)
7
/16
[11.1 mm]
1
1
/4
[31.7 mm]
PRIMARY DRAIN
3
/4 N.P.T. (VERTICAL)
SUCTION LINE
LIQUID LINE
15
5
[150.8 mm]
1
17/16
[36.5 mm]
/16
1
/8
4
[104.7 mm]
11
/16
21
[550.8 mm]
/2 [12.7 mm]

4 Rheem Heating, Cooling and Water Heating
Table 4: Horizontal Adapter Kit Model No.
Accessories
• PLENUM ADAPTER ACCESSORY
RXBA-AE
This plenum adapter accessory is for use with the 24
1
/2" wide
cased indoor cooling and heat pump coils. This allows a 24
1
/2"
wide cased coil to be installed on a 28" wide oil furnace. This is a
field-installed accessory only.
• RXBA-AC (Upflow/Horizontal)
These plenum adapter accessories are for use when a cooling
coil is matched with a gas furnace of one smaller size.
• HORIZONTAL ADAPTER KIT RXHH (See Figure 2)
This horizontal adapter kit is used to convert a upflow or downflow
coil for a horizontal application. See Table 4 to order the proper
horizontal adapter kit.
*Note: The horizontal adapter kit cannot be used for RCFA/RCFL-
AU****BC applications.It can only be used on RCFA/RCFL-AU****AC
applications and for RCFA/RCFL-HU****AC applications.
Table 3: Coil Application
Coils can be matched to heating products as listed in table below.
FIGURE 2: HORIZONTAL ADAPTER KIT ILLUSTRATION
RXBC—D14I
INSULATION
I = Insulated
Blank = Uninsulated
CABINET WIDTH
14 = 14" [356 mm]
17 = 17.5" [444 mm]
21 = 21" [533 mm]
24 = 24.5" [622 mm]
DESIGN SERIES
COIL CASING
BLOWER UNIT
ACCESSORY
RHEEM
T able 5:Unit Dimensions and Weights- RXBC Indoor Coil Casings
[ ] Designates Metric Conversions
• INDOOR COIL CASING- RXBC (See Table 5)
HORIZONTALADAPTER KIT (RXHH-)
*Note: Due to the proximity of the drain pan to the high temperature oil furnace drain, horizontal left application is not permitted on all oil furnaces.
Coil Model
RCFA/RCFL
2414
2417
3617
2417
3617
3621
3821
4821
3824
4824
6024
Oil Gas
— 14 [356]
21 [533]
21 [533]
241/2[622]
Furnace Width
(In.) (mm)
171/2[444]
14 [356]
21 [533]
2
171/
241/
2
21 [533]
[444]
[622]
Coil Model Horizontal Adapter Kit Model No.
2414 RXHH-A01
2417 RXHH-A02
3617/3621 RXHH-A03
3821/3824/4821/4824 RXHH-A04
6024 RXHH-A05
Unit Weight
Weight
(lbs.) [Kg.]
19 [9] 13 [330]
8
34 [16]
Ship. Wt.
(lbs.) [Kg.]
23 [10]
23 [10]
26 [12]
36 [17]
44 [20]
Model
Number
RXBC-D14AI 14 [356] 233/16[589]
RXBC-D17AI 171/2[445] 20 [508] 18 [8] 161/2[419]
RXBC-D21AI 21 [533] 20 [508] 20 [9] 20 [508]
RXBC-D21BI 21 [533] 28 [711] 27 [12] 20 [508]
RXBC-D24AI 241/2[622] 321/2[826]
Width
(in.) [mm]
(in.) [mm]
Height
Depth
(in.)
[mm]
215/
[549]
Supply Air/Return
Air Openings
Depth
Width
(in.) [mm]
231/2[597]
(in.)
[mm]
1931/
[508]
32
AIR FLOW
HORIZONTAL-DUAL
DIRECTION

Rheem Heating, Cooling and Water Heating 5
Table 6: Uncased Coil Adapter Kit
NOTE: Valve can be R-22 or R-410A if date code is M2308 or later.
• TXV CONVERSION KITS — RXCT
Accessories (cont.)
• TXV REPLACEMENT KITS
NOTES: Valve can be R-22 or R-410A if date code is M2308 or later. If original
coil is AC only it can only be converted to Upflow/Downflow configuration.
[ ] Designates Metric Conversions
R-22
Obsolete Kit Part No.Coil Model TXV Kit
RC*A-**24* RXCT-EBA
RC*A-**36* RXCT-EBB
RC*A-**48* RXCT-EBC
RC*A-**60* RXCT-EBD 611019
R-410A
RC*L-**24*
RC*L-**48* RXCT-FBC
RC*L-**60* 611023RXCT-FBD
RXCT-FBA
RXCT-FBB
611016
611017
611018
Obsolete Kit Part No.Coil Model TXV Kit
611020
611021RC*L-**36*
611022
R-22 to R-410A
Makes CoilCoil Model TXV Kit
RC*A-**24* RC*L-H*24*RXCT-FBA
RC*A-**36* RC*L-H*36*RXCT-FBB
RC*A-**48* RC*L-H*48*RXCT-FBC
RC*A-**60* RC*L-H*60*RXCT-FBD
R-410A to R-22
Makes CoilCoil Model TXV Kit
RC*L-**24* RC*A-H*24*RXCT-EBA
RC*L-**36* RC*A-H*36*RXCT-EBB
RC*L-**48* RC*A-H*48*RXCT-EBC
RC*L-**60* RC*A-H*60*RXCT-EBD
Uncased Coil Adapter
Model Number RXBA
B14x20 131/8[333]
B17x20
B21x20 201/
B24x20 235/
A
Width (in.) [mm]
165/8[422]
8
[511]
8
[599]
Uncased Coil
Model RCFA/L
-HUxx14
-HUxx17
-HUxx21
-HUxx24

FIGURE 4: UNCASED COIL ADAPTER KIT ASSEMBLED
Note: Sliding the coil into the coil rail before attaching coil rack front.
6 Rheem Heating, Cooling and Water Heating
FIGURE 3: UNCASED COIL ADAPTER KIT ILLUSTRATION
• UNCASED COIL ADAPTER KIT
RXBA- (See Figure 3 & 4)
This uncased coil adapter kit is used to adapt the coil to a furnace
or ductwork. See Table 6 to order the proper adapter kit. Each kit
contains a quantity of 20 adapters.
Accessories (cont.)
[ ] Designates Metric Conversions
11/2
[41 mm]
11
7
/16
[196 mm]
A
5
/16
20
[516 mm]

Rheem Heating, Cooling and Water Heating 7
NOTES

Before proceeding with installation,refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
Rheem Heating,
Cooling and
Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reser ves the right to make changes without notice.”
PRINTED IN U.S.A. 3-10 DC FORM NO. C11-211 REV. 5