Rheem High Efficiency - X-13 Motor - Standard N Coil Specification

Page 1
Rheem High Efficiency Air Handler
FORM NO. H11-543 REV. 2
RHLL- Series
X-13 (ECM) Motor Efficiencies up to 16 SEER
• RHLL feature an X-13 (ECM) motor which provides enhanced SEER performance with most Rheem outdoor units.
• Factory-installed high efficiency indoor coil.
• Sturdy cabinet construction with 1.0 inch [25.4 mm] of foil faced insulation for excellent sound and insulating characteristics.
• Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect.
•1
1
/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between
42
1
/2 to 551/2 inches [1080 to 1410 mm] tall and 22 inches
[559 mm] deep.
• All models meet or exceed 330 to 400 CFM [156 to 189 L/s] per ton at .3 inches [.7 kPa] of external static pressure.
• Enhanced airflow up to .7" external static pressure.
Air
Air Handlers
RHLL Series
Page 2
Air
Table of Contents
RHLL Series
2
TABLE OF CONTENTS
Engineering Features ......................................................................................3
Model Number Identification ............................................................................4
Dimensional Data............................................................................................5
Airflow Directional Data ..................................................................................6
Airflow Performance Data ..........................................................................7-11
Electrical Data ........................................................................................12-15
Electrical Wiring ............................................................................................16
Accessories ............................................................................................................16
Limited Warranty ..........................................................................................17
Page 3
Air
Engineering Features
RHLL Series
3
Engineering Features
RHLL- Series
• The most compact unit design available, all standard heat air handler models only 42
1
/2 to 551/2 inches [1079 to 1409 mm] high.
• Attractive pre-painted cabinet exterior.
• Rugged wall steel cabinet construction, designed for added strength and versatility.
• 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance.
• Four leg blower motor mount.
• Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience.
• Traditional open wire element design for heat applications.
• Field convertible for vertical downflow, horizontal left hand or right hand air supply.
• 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors.
• Indoor coil design provides low air side pressure drop, high performance and extremely compact size.
• Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil.
• Coils are constructed of aluminum fins bonded to internally grooved copper tubing.
• Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils.
• Supply duct flanges provided as standard on air handler cabinet.
• Provisions for field electrical, connections available from either side or top of the air handler cabinet.
• Connection point for high voltage wiring is inside the air han­dler cabinet. Low voltage connection is made on the outside of the air handler cabinet.
• Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 1
1
/2 inch [38 mm] conduit.
• Front refrigerant and drain connections.
• Suitable for application in mobile homes.
[ ] Designates Metric Conversions
Page 4
Air
Model Number Identification
RHLL Series
4
Model Number Identification
Coil Specifications/Airflow Pressure Drop
RHL L—HM2417J A
Design Variation
A = 1st Design D = 2nd Design
Voltage
A = 115/1/60 J = 208/240/1/60 D = 480/3/60
Cabinet Size
17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1400-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM)
Capacity
24 = 18,000/24,000 BTU/H [5.27/7.03 kW] 36 = 30,000/36,000 BTU/H [8.79/10.55 kW] 38 = 30,000/36,000/42,000 BTU/H
[8.79/10.55/12.31 kW] 48 = 42,000/48,000 BTU/H [12.31/14.06 kW] 60 = 60,000 BTU/H [17.58 kW]
HM = A/C or HP Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration)
Refrigerant
L = R-410A
L = High Efficiency (X-13 (ECM) Motor)
Classification
H = Air Handler
Rheem
[ ] Designates Metric Conversions
Available Models at 115V A Voltage
RHLL-HM2417AD RHLL-HM3617AA RHLL-HM4821AA RHLL-HM4824AA RHLL-HM6024AA RHLL-HM3821AA
Available Models at 480V D Voltage
RHLL-HM6024DA
Available Models at 240V J Voltage
RHLL-HM2417JD RHLL-HM3617JA RHLL-HM3821JA RHLL-HM4821JA RHLL-HM4824JA RHLL-HM6024JA
Page 5
Air
Dimensional Data
RHLL Series
5
ELECTRICAL CONNECTIONS
Unit Dimensions
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
Return Air Opening Dimensions
Model
Size
RHLL
Refrigerant Connections
Sweat (In.) [mm] ID
Unit
Width
“W” In. [mm]
Unit
Height
“H” In. [mm]
Supply
Duct
“A” In. [mm]
Air Flow
CFM (Nom.) [L/s]
Unit Weight/Shipping Weight
(Lbs.) [kg]
Liquid Vapor
Lo Hi
Unit With
Coil (Max. KW)
2417
3
/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
600 [283] 800 [378] 82/96 [37/44]
3617
3
/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
1000 [472] 1200 [566] 92/106 [37/48]
3621
3
/8 [9.53]
3
/4 [19.05] 211/2 [533] 421/2 [1080] 191/2 [495] 1200 [566] 97/112 [44/51]
3821
3
/8 [9.53]
7
/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1000 [472] 1200 [566] 150/166 [68/75]
4821
3
/8 [9.53]
7
/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1400 [661] 1600 [755] 150/166 [68/75]
4824
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584]
1600 [755] 162/180 [73/81]
6024
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584] 1800 [850] 181/198 [82/90]
*Maximum dehumidification airflow.
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
MAY EXIT TOP OR EITHER SIDE
HIGH VOLTAGE CONNECTION
3
/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS.
1
LOW VOLTAGE CONNECTION
5
/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION COPPER (SWEAT)
VAPOR LINE CONNECTION COPPER (SWEAT)
7
/8 [22.2 mm],
SUPPLY AIR
5
/16
10
[262 mm]
A
191/2 [495 mm]
RETURN AIR
OPENING
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
NOTE: 24 CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE.
W
H
11
/16
21
[551 mm]
Model
Cabinet Size
Return Air
Opening Width
(Inches)
17 157/8 193/4 21 193/8 193/4 24 227/8 193/4
Return Air Opening
Depth/Length
(Inches)
HORIZONTAL ADAPTER KIT
VAPOR LINE
CONNECTION
AUXILIARY HORIZONTAL
DRAIN CONNECTION
PRIMARY DRAIN
CONNECTION
AUXILIARY UPFLOW/DOWNFLOW
DRAIN CONNECTION
515/16
[151 mm]
1
/8
4
[105 mm]
1
3
/16
[76 mm]
3
1
/16[48 mm]
1
1
/8[29 mm]
1
/16
1
[27 mm]
1
[35 mm]
2
[71 mm]
3
/8
13
/16
1
/4
5
[133 mm]
3
5
/8
[136 mm]
LIQUID LINE CONNECTION
VERTICAL DRAIN PAN
Page 6
Air
Airflow Directional Data
RHLL Series
6
UPFLOW DOWNFLOW
Airflow Directional Data
HORIZONTAL RIGHT HAND AIRFLOW
HORIZONTAL LEFT HAND AIRFLOW
Page 7
Air
Airflow Performance Data
RHLL Series
7
Airflow Performance
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for
appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows oper­ation within the minimum and maximum limits shown in table
below for both cooling and electric heat operation. For opti­mum blower performance, operate the unit in the .3 [8 mm] to .7 inches [18 mm] W.C. external static range. Units with coils should be applied with a minimum of .1 inch [3 mm] W.C. external static range.
Airflow Operating Limits
[ ] Designates Metric Conversions
Model Cabinet Size 17 17/21
Cooling BTUH x 1,000 Cooling Tons Nominal
Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal)
Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal)
Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,200 BTUH) (360 CFM [170 L/s]/Ton Nominal)
Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s]13487 [230]13617 [291]18814 [384]181054 [497]
Maximum Electric Heat Rise °F [°C] 80 [26.7] 63 [17.2] 66 [18.9] 51 [10.6] 49 [9.4] 50 [10] 50 [10]
-018
1.5
675
[319]
600
[283]
540
[255]
-024 2
900
[425]
800
[378]
720
[340]
-030
2.5
1125
[531]
1000 [472]
900
[425]
-036 3
1350 [637]
1200 [566]
1080 [510]
-038
3.5
1350 [637]
1200 [566]
1080 [510]
18
1042 [492]
21
-042
3.5
1575
[743]
1400 [661]
1260 [595]
20
1171 [553]251502 [709]251502 [709]
-048 4
1800
[850]
1600 [755]
1440 [680]
-048 4
1800
[850]
1600
[755]
1440
[680]
24
-060 5
1930
[911]
1800 [850]
1620 [765]
30
1666 [786]
54 [12.2]52 [11.1]
Page 8
Air
Airflow Performance Data
RHLL Series
8
External Static Pressure—Inches W.C. [kPa]
X-13 CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
RPM 592
Blower Size/
Motor
HP [W]
# of Speed
-3617
No Heater
613
Tonnage
Application
656
Manufacturer Recommended Air-Flow Range
(Min/Max) CFM
719 778
Watts 108 90 97 82 73
10x8
1/3 HP [249]
5 Speed
CFM 808 [381] 629 [297] 584 [276]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
789 842
RPM 565 587 630 692 751
892
Model
No.
RHLL
-2417
with 13 kW
Heater
-2417
No Heat
-2417
with 13 kW
Heater
-2417
No Heat
Watts 95 81 88 74 66
10x8
1/3 HP [249]
5 Speed
-3617
No Heater
RPM
1.5 Ton
683/485
[322/229 L/s]
CFM 683 [322] 615 [290] 572 [270]
CFM 814 [384] 692 [326] 589 [278] 535 [252]
RPM 789 842 892
467 [220]
Watts 148 168 163
RPM 596 645
-3617
with 18 kW
Heater
694 741 791
775
816 846 882
Watts 105 108 116 121 130
10x8
1/3 HP [249]
5 Speed
CFM
926
858 [276] 816 [385] 770 [363]
RPM 834 879 925
Watts 237 249 259 268 277
2 Ton
858/697
[405/329 L/s]
CFM 902 [426] 846 [399] 788 [372] 742 [350] 679 [320]
Watts 185 182 214
RPM 595 670 719 767 817
Watts 113 125 124 129 197
10x8
1/3 HP [249]
5 Speed
CFM 833 [393] 791 [373]
746 [352]
RPM 852 898
10x8
1/2 HP [373]
5 Speed
CFM
2 Ton
683/485
[322/229 L/s]
CFM 882 [416] 827 [390] 769 [363] 723 [341] 661 [312]
Watts 192 189 222
RPM 671 725 764 809 852
Watts 153 168 174 180 188
10x8
1/2 HP [373]
5 Speed
CFM 1084 [512] 1040 [491] 1001 [472]
RPM
1.5 Ton
896
683/485
[322/229 L/s]
CFM 837 [395] 713 [366] 608 [287] 554 [261] 485 [229]
936 971
1275 [602] 1244 [587] 1211 [571]
Watts 140 159 155
RPM
2.5 Ton
935/1084 CFM
[441/512 L/s]
CFM 1093 [516] 1050 [496] 1017 [480] 977 [461] 935 [441]
Watts
249 257 261
RPM 711 765 804 849 892
Watts 164 179 185 191 199
10x8
1/2 HP [373]
5 Speed
CFM 1059 [500] 1015 [479] 976 [461]
RPM 936 976 1011
963 999 1029
3 Ton
1130/1275 CFM
[533/602 L/s]
2.5 Ton
910/1059 CFM
[429/500 L/s]
CFM 1068 [504] 1025 [484] 992 [468] 952 [449] 910 [429]
Watts
260 268 272
CFM 1270 [599] 1237 [584] 1199 [566] 1165 [550] 1130 [533]
Watts
338 348 363
Motor
Speed
From
Factory
5
5
5
5
5
5
5
-3617
with 18 kW
Heater
RPM 815 856 886 922 966
Watts 248 260 270 279 288
10x8
1/2 HP [373]
5 Speed
CFM 1250 [590] 1219 [575] 1186 [560]
RPM 1003 1039 1069
3 Ton
1105/1250 CFM
[521/590 L/s]
CFM 1245 [588] 1212 [572] 1174 [554] 1140 [538] 1105 [521]
Watts 349 359 374
5
Motor
Speed
2
2
4
4
4
2
2
4
3
3
5
5
3
3
5
5
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor)
[ ] Designates Metric Conversions
Page 9
Air
Airflow Performance Data
RHLL Series
9
Notes: X-13 (ECM) motor speed changes. All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage. X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor. The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage) and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor) (con’t.)
Model
No.
RHLL
-3821
No Heater
-3821
with 18 kW
Heater
-3821
No Heater
-3821
with 18 kW
Heater
Tonnage
Application
2.5 Ton
2.5 Ton
3 Ton
3 Ton
Motor
Speed
From
Factory
4
4
4
4
Manufacturer Recommended Air-Flow Range
(Min/Max) CFM
854/1103 CFM
[403/521 L/s]
828/1016 CFM
[391/479 L/s]
1070/1288 CFM
[505/608 L/s]
1042/1257 CFM
[492/593 L/s]
Blower Size/
Motor
HP [W]
# of Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
5 Speed
Motor Speed
2
3
2
3
4
5
4
5
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 1073 [506] 1016 [479] 963 [454] 906 [428] 854 [403]
RPM 637
Watts 130 142 153 165 176
CFM 1103 1059 1000
RPM
Watts 262 271 285
CFM 1044 [493] 988 [466] 936 [442] 880 [415] 828 [391]
RPM 678 734 791 844 883
Watts 141 155 158 171 182
CFM 1016 961 904
RPM 939 968 1015
Watts 233 243 265
CFM 1264 [597] 1223 [577] 1171 [553] 1112 [525] 1070 [505]
RPM 724 761 814 868 900
Watts 198 208 222 237 245
CFM 1288 1244 1200
RPM 974 1012 1044
Watts 345 362 371
CFM 1233 [582] 1193 [563] 1142 [539] 1084 [512] 1042 [492]
RPM 759 794 845 915 933
Watts 219 215 227 251 261
CFM 1257 1213 1169
RPM 1020 1023 1054
Watts 355 368 376
917 957 1001
External Static Pressure—Inches W.C. [kPa]
692
746
801 847
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
Page 10
Air
Airflow Performance Data
RHLL Series
10
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor) (con’t.)
[ ] Designates Metric Conversions
Model
No.
RHLL
-4821
No Heater
-4821
with 20 kW
Heater
-4821
No Heater
-4821
with 25 kW
Heater
-4824
No Heater
-4824
with 25 kW
Heater
-6024
No Heater
-6024
with 30 kW
Heater
Tonnage
Application
3.5 Ton
3.5 Ton
4 Ton
4 Ton
4 Ton
4 Ton
5 Ton
5 Ton
Motor
Speed
From
Factory
5
5
5
5
3
3
5
5
Manufacturer Recommended Air-Flow Range
(Min/Max) CFM
1337/1447 CFM
[631/683 L/s]
1297/1333 CFM
[612/629 L/s]
1535/1654 CFM
[724/781 L/s]
1495/1614 CFM
[706/762 L/s]
1545/1732 CFM
[729/817 L/s]
1505/1692 CFM
[710/798 L/s]
1517/1699 CFM
[715/800 L/s]
1477/1655 CFM
[687/785 L/s]
Blower Size/
Motor
HP [W]
# of Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
5 Speed
10x10
3/4 HP [559]
2 Speed
11x11
3/4 HP [559]
5 Speed
11x11
3/4 HP [559]
5 Speed
11x11
3/4 HP [559]
5 Speed
11x11
3/4 HP [559]
5 Speed
Motor Speed
2
3
2
3
4
5
4
5
2
3
2
3
2
3
2
3
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631]
RPM 781 825 867 905 949
Watts 257 271 303 307 315
CFM 1447 [683] 1433 [676] 1402 [662]
RPM 987 1034 1065
Watts
CFM 1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612]
RPM
Watts 277 295 313 319 325
CFM
RPM
Watts
CFM 1665 [786] 1631 [770] 1601 [756] 1572 [742] 1535 [724]
RPM 853 893 934 968 1015
Watts 351 387 401 406 422
CFM 1654 [781] 1624 [766] 1563 [738]
RPM 1036 1078 1095
Watts
CFM 1625 [767] 1591 [751] 1561 [737] 1532 [723] 1495 [706]
RPM 894 932 970 1020 1052
Watts 389 400 410 430 450
CFM 1614 [762] 1584 [748] 1523 [719]
RPM 1085 1090 1105
Watts 514 520 530
CFM 1748 [825] 1669 [788] 1639 [773] 1599 [755] 1545 [729]
RPM 660
Watts 297 311 326 340 353
CFM 1732 [817] 1683 [794] 1630 [769]
RPM
Watts 448 467 480
CFM 1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710]
RPM 680 736
Watts 305 330 341 350 361
CFM
RPM 865 890 1014
Watts 460 470 481
CFM 1705 [800] 1661 [703] 1632 [770] 1572 [741] 1517 [915]
RPM 663 701 741 782 819
Watts 292 309 321 343 357
CFM 1699 [500] 1646 [776] 1601 [725]
RPM 857 895 920
Watts 447 466 473
CFM 1665 [995] 1621 [965] 1592 [751] 1532 [723] 1477 [697]
RPM 701 739 779 820 857
Watts 313 330 342 364 378
CFM 1657 [787] 1606 [759] 1561 [735]
RPM
Watts 968 487 494
394 406 405
831
350 364 377
500 513 523
840 872 899
1692 [798] 1643 [775] 1590 [750]
External Static Pressure—Inches W.C. [kPa]
875 919 954
698
1011 1046 1080
734
760 790 820
1333 [629] 1300 [613] 1267 [598]
762 795
895 933 958
989
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
Page 11
11
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor) (con’t.)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
Air
Airflow Performance Data
RHLL Series
Model
No.
RHLL
-6024
No Heater
-6024
with 30 kW
Heater
Tonnage
Application
5 Ton
5 Ton
Motor Speed
From
Factory
5
5
Manufacturer Recommended Air-Flow Range
(Min/Max) CFM
1739/1905 CFM
[821/899 L/s]
1699/1865 CFM
[802/880 L/s]
Blower Size/
Motor
HP [W]
# of Speed
11x11
3/4 HP [559]
5 Speed
11x11
3/4 HP [559]
5 Speed
Motor
Speed
4
5
4
5
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
CFM 1902 [898] 1862 [879] 1809 [854] 1781 [840] 1739 [821]
RPM 712 749 787 815 856
Watts 389 409 419 432 459
CFM 1905 [899] 1866 [881] 1832 [865]
RPM 894 924 950
Watts 565 570 592
CFM 1862 [879] 1822 [860] 1769 [835] 1741 [822] 1699 [802]
RPM 750 790 810 850 880
Watts 410 420 430 455 479
CFM 1865 [880] 1826 [862] 1792 [846]
RPM 920 945 970
Watts 565 587 610
External Static Pressure—Inches W.C. [kPa]
X-13 CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
Page 12
Air
Electrical Data
RHLL Series
12
Model
RHLL
Voltage
Application
Phase*
Hertz HP [W] RPM Speeds
Circuit Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
3617/3621 1/2 [373] 300-1100 4 2.8 4.0 15
2417
208/240 1 & 3 60
1/3 [249] 300-1100 4 1.6 2.0 15
3821/4821/4824 3/4 [559] 300-1100 4 4.0 5.0 15
6024 3/4 [559] 300-1100 4 4.6 6.0 15
6024 3/4 [559] 300-1100 4 8.4 11.0 15
2417
115
1 60
1/3 [249] 300-1100 4 4.8 6.0 15
3821/4821/4824 3/4 [559] 300-1100 4 8.4 11.0 15
6024 3/4 [559] 300-1100 4 3.2 4.0 15480 3 60
Electrical Data – Blower Motor Only – No Electric Heat
* Blower motors are all single phase motors.
[ ] Designates Metric Conversions
Page 13
Air
Electrical Data
RHLL Series
13
Air Handler
Model
RHLL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
2417
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE 10.8/12.5 1.6 16/18 20/20
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 1.6 24/27 25/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 1.6 35/40 35/40
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 1.6 46/52 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 1.6 59/68 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 1.6 21/24 25/25
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 1.6 21/24 25/25
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 1.6 27/31 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 1.6 35/40 35/40
3617
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE
10.8/12.5 2.8 17/20 20/20
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 2.8 26/29 30/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 2.8 36/41 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 2.8 47/54 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 2.8 60/69 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 2.8 23/26 25/30
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60 2.8 69/79 70/80
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 2.8 26/29 30/30
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 2.8 81/92 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 2.8 30/33 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 2.8 23/26 25/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 2.8 29/33 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 2.8 37/42 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 2.8 41/47 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 2.8 48/55 50/60
3821/4821
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE
10.8/12.5 4.0 19/21 20/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 4.0 27/30 30/30
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 4.0 38/43 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 4.0 49/55 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 4.0 62/71 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 4.0 24/27 25/30
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60 4.0 70/80 70/80
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 4.0 27/30 30/30
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 4.0 82/94 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 4.0 31/35 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J (4-ton only) 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 4.0 92/105 100/110
Electrical Data – With Electric Heat
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Page 14
Air
Electrical Data
RHLL Series
14
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Air Handler
Model
RHLL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
3821/4821
RXBH-24A20J (4-ton only)
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 4.0 49/55 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J (4-ton only) 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 4.0 113/130 125/150
RXBH-24A25J (4-ton only) 6.0/8.0 1/60 2.4.0 MULTIPLE CKT 1
28.8/33.3 4.0 41/47 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 4.0 24/27 25/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 4.0 30/34 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 4.0 38/43 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 4.0 43/49 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 4.0 50/57 50/60
RXBH-24A20C (4-ton only) 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 4.0 55/63 60/70
RXBH-24A20C (4-ton only)
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1
20.0/23.1 4.0 30/34 30/35
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C (4-ton only) 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 4.0 68/78 70/80
RXBH-24A25C (4-ton only)
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 4.0 37/42 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
4824
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE
10.8/12.5 4.6 20/22 20/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 4.6 28/31 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 4.6 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 4.6 49/56 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 4.6 63/71 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 4.6 25/28 25/30
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60 4.6 71/81 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 4.6 28/31 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 4.6 83/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 4.6 32/36 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 4.6 93/106 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 4.6 49/56 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 4.6 114/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2.4.0 MULTIPLE CKT 1
28.8/33.3 4.6 42/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 4.6 25/28 25/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 4.6 31/35 35/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 4.6 39/44 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 4.6 44/49 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 4.6 51/57 60/60
RXBH-24A20C 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 4.6 56/64 60/70
Page 15
Air
Electrical Data
RHLL Series
15
Air Handler
Model
RHLL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
4824
RXBH-24A20C
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1 20.0/23.1 4.6 31/35 35/35
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 4.6 69/78 70/80
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 4.6 37/42 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
4824/6024
RXBH-1724?03J 2.25/3.0 1/60 1 - 3.0 SINGLE
10.8/12.5 4.6 20/22 20/25
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 4.6 28/31 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 4.6 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 4.6 49/56 50/60
RXBH-1724A13J 9.4/12.5 1/60 3-4.17 SINGLE
45.1/52.1 4.6 63/71 60/70
RXBH-1724A13J
3.1/4.2 1/60 1-4.17 MULTIPLE CKT 1
15.0/17.4 4.6 25/28 25/30
6.3/8.3 1/60 2-4.17 MULTIPLE CKT 2
30.1/34.7 0.0 38/44 40/45
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60 4.6 71/81 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 4.6 28/31 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 4.6 83/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 4.6 32/36 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 4.6 93/106 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 4.6 49/56 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 4.6 114/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2.4.0 MULTIPLE CKT 1
28.8/33.3 4.6 42/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-24A30J (5-ton only) 21.6/28.8 1/60 6-4.8 SINGLE
103.8/120 4.6 136/156 150/175
RXBH-24A30J (5-ton only)
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1
34.6/40.0 4.6 49/56 50/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
7.2/9.6 1/60 2-4.8 MULTPLE CKT 3
34.6/40.0 0.0 44/50 45/50
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 4.6 25/28 25/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 4.6 31/35 35/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 4.6 39/44 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 4.6 44/49 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 4.6 51/57 60/60
RXBH-24A20C 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 4.6 56/64 60/70
RXBH-24A20C
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1
20.0/23.1 4.6 31/35 35/35
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 4.6 69/78 70/80
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 4.6 37/42 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
RXBH-24A30C (5-ton only) 21.6/28.8 3/60 6-4.8 SINGLE
60.0/69.4 4.6 81/93 90/100
RXBH-24A30C (5-ton only)
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 1
30.0/34.7 4.6 44/50 45/50
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 2
30.0/34.7 0.0 38/44 40/45
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions
Page 16
Air
Electrical Wiring
RHLL Series
16
Electrical Wiring
Power Wiring
• Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance.
• Supply wiring must be 75°C minimum copper conductors only.
• See electrical data for product Ampacity rating and Circuit Protector requirement.
Grounding
• This product must be sufficiently grounded in accordance with National Electrical Code (C.E.C. in Canada) and any applicable local ordinance.
• A grounding lug is provided.
RXHF-
Accessories
Auxiliary Horizontal Overflow Pan Accessory RXBM-
Combustible Floor Base RXHB-
Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple three circuit units to a single supply circuit. Kit includes cover and screw for line side terminals.
Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple two circuit units to a single supply circuit. Kit includes cover and screw for line side terminals.
Note: No jumper bar kit is available to convert three phase multiple two circuit units to a single supply circuit.
Auxiliary Electric Heater Kits RXBH- Heater Kits include circuit breakers which meet UL and cUL requirements for service disconnect. See the Electric Heat Electrical Data in this specification sheet for specific Heater Kit Model numbers.
External Filter Rack RXHF-B17, B21, B24
*Accommodates 1" filter
[ ] Designates Metric Conversions
17 21 24
RXHB-17 RXHB-21 RXHB-24
Model Cabinet Size
Combustible Floor
Base Model Number
Nominal Cooling
Capacity-Tons
Auxiliary Horizontal Overflow Pan
Accessory Model Number
11/2 - 3
RXBM-AC48
31/2 - 5 RXBM-AC61
RXHF-B
B
A
B
A
11/2
[38 mm]
External Filter Base RXHF-
*Accommodates 1" or 2" filter
Horizontal Adapter Kit RXHH- This horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit.
Model Cabinet Size Filter Size In. [mm]
21 20 x 20 [508 x 508]
Part Number*
RXHF-21 RXHF-2424 25 x 20 [635 x 508] 22.70
19.20
A
25.5
21.0
B
Model Cabinet Size Part Number*
RXHF-B17 RXHF-B21
Filter Size In. [mm]
RXHF-B24
24
25 x 20 [635 x 508]
17
16 x 20 [406 x 508]
21
20 x 20 [508 x 508]
A
16.90
20.40
25.00
B
20.77
20.77
21.04
External Filter Base RXHF-
*Accommodates 1" or 2" filter
Model Cabinet Size Filter Size In. [mm]
17 16 x 20 [406 x 508] 21 20 x 20 [508 x 508]
Part Number*
RXHF-17 RXHF-21 RXHF-2424 25 x 20 [635 x 508] 22.70
19.20
15.70
A
25.5
21.0
17.5
B
Coil Model
Horizontal Adapter Kit
Model Number (10-Pack Qty.)
RXHH-A01 x 10 RXHH-A02 x 10
Horizontal Adapter Kit
Model Number (Single Qty.)
RXHH-A03 x 103617/3621 RXHH-A03
2414 RXHH-A01 2417 RXHH-A02
3821/4821/4824 RXHH-A04 RXHH-A04 x 10
8024 RXHH-A05 RXHH-A05 x 10
Page 17
Air
Limited Warranty
RHLL Series
17
GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.
Conditional Parts (Registration Required) ..........Ten (10) Years
*For complete details of the Limited and Conditional Warranties, including
applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
Page 18
Air
Notes
RHLL Series
18
Page 19
Air
Notes
RHLL Series
19
Page 20
The new degree of comfort.
Rheem Heating, Cooling & Water Heating • P.O. Box 17010
Fort Smith, Arkansas 72917 • www.rheem.com
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
PRINTED IN U.S.A 4/14 QG FORM NO. H11-543 REV. 2
Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1
Brampton, Ontario • L6Y 0P5
Loading...