Rheem High Efficiency - X-13 Motor - Standard N Coil Specification

Rheem High Efficiency Air Handler
FORM NO. H11-543 REV. 2
RHLL- Series
X-13 (ECM) Motor Efficiencies up to 16 SEER
• RHLL feature an X-13 (ECM) motor which provides enhanced SEER performance with most Rheem outdoor units.
• Factory-installed high efficiency indoor coil.
• Sturdy cabinet construction with 1.0 inch [25.4 mm] of foil faced insulation for excellent sound and insulating characteristics.
• Field-installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect.
•1
1
/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between
42
1
/2 to 551/2 inches [1080 to 1410 mm] tall and 22 inches
[559 mm] deep.
• All models meet or exceed 330 to 400 CFM [156 to 189 L/s] per ton at .3 inches [.7 kPa] of external static pressure.
• Enhanced airflow up to .7" external static pressure.
Air
Air Handlers
RHLL Series
Air
Table of Contents
RHLL Series
2
TABLE OF CONTENTS
Engineering Features ......................................................................................3
Model Number Identification ............................................................................4
Dimensional Data............................................................................................5
Airflow Directional Data ..................................................................................6
Airflow Performance Data ..........................................................................7-11
Electrical Data ........................................................................................12-15
Electrical Wiring ............................................................................................16
Accessories ............................................................................................................16
Limited Warranty ..........................................................................................17
Air
Engineering Features
RHLL Series
3
Engineering Features
RHLL- Series
• The most compact unit design available, all standard heat air handler models only 42
1
/2 to 551/2 inches [1079 to 1409 mm] high.
• Attractive pre-painted cabinet exterior.
• Rugged wall steel cabinet construction, designed for added strength and versatility.
• 1.0" foil faced insulation mechanically retained in blower compartment for excellent thermal and sound performance.
• Four leg blower motor mount.
• Blower housing with controls, motor and blower. Slide out design for service and maintenance convenience.
• Traditional open wire element design for heat applications.
• Field convertible for vertical downflow, horizontal left hand or right hand air supply.
• 3 combustible floor base accessories fit all model sizes when required for downflow installations on combustible floors.
• Indoor coil design provides low air side pressure drop, high performance and extremely compact size.
• Expansion valve on indoor coil provides for operation with air conditioning or heat pump using the same coil.
• Coils are constructed of aluminum fins bonded to internally grooved copper tubing.
• Molded polymer corrosion resistant condensate drain pan is provided on all indoor coils.
• Supply duct flanges provided as standard on air handler cabinet.
• Provisions for field electrical, connections available from either side or top of the air handler cabinet.
• Connection point for high voltage wiring is inside the air han­dler cabinet. Low voltage connection is made on the outside of the air handler cabinet.
• Concentric knockouts are provided for power connection to cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 1
1
/2 inch [38 mm] conduit.
• Front refrigerant and drain connections.
• Suitable for application in mobile homes.
[ ] Designates Metric Conversions
Air
Model Number Identification
RHLL Series
4
Model Number Identification
Coil Specifications/Airflow Pressure Drop
RHL L—HM2417J A
Design Variation
A = 1st Design D = 2nd Design
Voltage
A = 115/1/60 J = 208/240/1/60 D = 480/3/60
Cabinet Size
17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1400-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM)
Capacity
24 = 18,000/24,000 BTU/H [5.27/7.03 kW] 36 = 30,000/36,000 BTU/H [8.79/10.55 kW] 38 = 30,000/36,000/42,000 BTU/H
[8.79/10.55/12.31 kW] 48 = 42,000/48,000 BTU/H [12.31/14.06 kW] 60 = 60,000 BTU/H [17.58 kW]
HM = A/C or HP Multi-Position (Vertical Upflow/Horizontal Left is the factory configuration)
Refrigerant
L = R-410A
L = High Efficiency (X-13 (ECM) Motor)
Classification
H = Air Handler
Rheem
[ ] Designates Metric Conversions
Available Models at 115V A Voltage
RHLL-HM2417AD RHLL-HM3617AA RHLL-HM4821AA RHLL-HM4824AA RHLL-HM6024AA RHLL-HM3821AA
Available Models at 480V D Voltage
RHLL-HM6024DA
Available Models at 240V J Voltage
RHLL-HM2417JD RHLL-HM3617JA RHLL-HM3821JA RHLL-HM4821JA RHLL-HM4824JA RHLL-HM6024JA
Air
Dimensional Data
RHLL Series
5
ELECTRICAL CONNECTIONS
Unit Dimensions
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
Return Air Opening Dimensions
Model
Size
RHLL
Refrigerant Connections
Sweat (In.) [mm] ID
Unit
Width
“W” In. [mm]
Unit
Height
“H” In. [mm]
Supply
Duct
“A” In. [mm]
Air Flow
CFM (Nom.) [L/s]
Unit Weight/Shipping Weight
(Lbs.) [kg]
Liquid Vapor
Lo Hi
Unit With
Coil (Max. KW)
2417
3
/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
600 [283] 800 [378] 82/96 [37/44]
3617
3
/8 [9.53]
3
/4 [19.05] 171/2 [445] 421/2 [1080] 161/2 [406]
1000 [472] 1200 [566] 92/106 [37/48]
3621
3
/8 [9.53]
3
/4 [19.05] 211/2 [533] 421/2 [1080] 191/2 [495] 1200 [566] 97/112 [44/51]
3821
3
/8 [9.53]
7
/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1000 [472] 1200 [566] 150/166 [68/75]
4821
3
/8 [9.53]
7
/8 [22.23] 211/2 [533] 501/2 [1282] 191/2 [495] 1400 [661] 1600 [755] 150/166 [68/75]
4824
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584]
1600 [755] 162/180 [73/81]
6024
3
/8 [9.53]
7
/8 [22.23] 241/2 [622] 551/2 [1410] 231/2 [584] 1800 [850] 181/198 [82/90]
*Maximum dehumidification airflow.
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
MAY EXIT TOP OR EITHER SIDE
HIGH VOLTAGE CONNECTION
3
/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS.
1
LOW VOLTAGE CONNECTION
5
/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION COPPER (SWEAT)
VAPOR LINE CONNECTION COPPER (SWEAT)
7
/8 [22.2 mm],
SUPPLY AIR
5
/16
10
[262 mm]
A
191/2 [495 mm]
RETURN AIR
OPENING
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
NOTE: 24 CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE.
W
H
11
/16
21
[551 mm]
Model
Cabinet Size
Return Air
Opening Width
(Inches)
17 157/8 193/4 21 193/8 193/4 24 227/8 193/4
Return Air Opening
Depth/Length
(Inches)
HORIZONTAL ADAPTER KIT
VAPOR LINE
CONNECTION
AUXILIARY HORIZONTAL
DRAIN CONNECTION
PRIMARY DRAIN
CONNECTION
AUXILIARY UPFLOW/DOWNFLOW
DRAIN CONNECTION
515/16
[151 mm]
1
/8
4
[105 mm]
1
3
/16
[76 mm]
3
1
/16[48 mm]
1
1
/8[29 mm]
1
/16
1
[27 mm]
1
[35 mm]
2
[71 mm]
3
/8
13
/16
1
/4
5
[133 mm]
3
5
/8
[136 mm]
LIQUID LINE CONNECTION
VERTICAL DRAIN PAN
Air
Airflow Directional Data
RHLL Series
6
UPFLOW DOWNFLOW
Airflow Directional Data
HORIZONTAL RIGHT HAND AIRFLOW
HORIZONTAL LEFT HAND AIRFLOW
Loading...