Rheem H-84DV, H-84X, H-95DV, H-95X Troubleshooting Manual

TANKLESS GAS
TR UBLESHOOTING
POCKET MANUAL
SVC 820P
For Mid & High Efficiency Platforms
Rheem.com
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 1
This manual is specific to the following model numbers:
MID EFFICIENCY
64DV, 64X / 68DV / 68X
84DV, 84X / 95DV, 95X
150DV, 150X / 180DV, 180X / 200DV, 200X
2-20RDV, 2-20ROF / 2-25RDV, 2-25ROF
2-28RDV, 2-28ROF
-
HIGH EFFICIENCY
(Condensing)
H-84DV, H-84X / H-95DV, H-95X
H-160DV, H-160X / H-200DV, H-200X
H-25RDV, H-25ROF / H-32RDV, H-32ROF
DASH 2 REVISION
1
1
1
1
1
-
2 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
2
TABLE OF CONTENTS
General Information
Installation Guidelines……………………………………………….. 8 Mid & High-Efficiency Flow Rates…………………………….. 12 Control Board Connectors………………………………………… 14
Diagnostic Points (Voltage & Resistance Readings)……16 Maintenance Mode Instructions………………………………. 21
Altitude Settings on Control Board…………………………… 25 Reset Procedures……………………………………………………..26 Clearing Fault History……………………………………………….27
Error Code Diagnostics
No Error Code & No Hot Water 28
P1 Warning Code 31 1L Warning Code 32 03 Error Code 34 05 Warning Code 35 10 Warning Code 37 11 Error Code 40 12 Error Code 46 13 Error Code 48 14 Error Code 50 15 Error Code 52 16 Error Code 53 24 Error Code 54 29 Error Code
High-Efficiency ONLY (A)…………………………….. 55 Mid & High-Efficiency (B)…………………………… 56
31 Error Code 58 32 Error Code 60 33 Error Code 62 34 Error Code 64 35 Error Code 66 51 Error Code 67 52 Error Code 70
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 3
3
61 Error Code 73 65 Error Code 76 66 Error Code 78 71 Error Code 79 72 Error Code 81 76 Error Code 84 79 Error Code 85 80 Error Code 89 82 Error Code 92 90 Error Code 94 92 Warning Code 95 93 Error Code 95 99 Error Code 94
HOW TO REMOVE COMPONENTS Section 1: Control Board Bracket…98 Section 2: Blower Motor…100 Section 3: Flame Rod; Igniter Rod; Igniter Coil…102 Section 4: Orifice Assembly…104 Section 5: Burner Assembly…106 Section 6: Gas Control Valve…107 Section 7: Water Control Valves…111 Section 8: Heat Exchanger Thermistor…114 Section 9: Outlet Thermistor…116 Section 10: Inlet Thermistor…118 Section 11: Ambient Thermistor…120 Section 12: Control Board…122
How to Program Control Board…123
4 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
4
Important Safety Information
READ the Safety Information
Before inspecting, diagnosing, repairing or operating any water heater, be sure to examine all of the safety and warning labels on the water heater. Follow the instruction on these warning labels. Read and understand the Use and Care Manual that was shipped with the water heater. Failure to do so can result in unsafe operation of the water heater resulting in property damage, bodily injury, or death. Should you have any problems reading or following the instructions in the Use and Care Manual, seek the help of a licensed and qualified professional.
ELECTRICAL SHOCK
Troubleshooting and repairing this water heater can expose you to electrical shock. Some of the diagnostic procedures require the presence of AC and DC volt electricity. Use extreme caution when performing these procedures. When replacing an unserviceable component, turn off all power to the water heater and check for the presence of power with a multi-meter or test lamp. The ignition cable carries more than 10,000 volts of electrical energy. Use extreme caution when diagnosing the Tankless Gas Water Heater.
FLAMMABLE LIQUIDS AND VAPORS
Gasoline, as well as other flammable material and
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 5
5
liquids (adhesives, solvents, etc.), and vapors they produce are extremely dangerous. DO NOT handle, use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater. The spark ignition and burner assembly in the water heater controls can ignite these vapors. Failure to do so can result in property damage, bodily injury or death.
WATER TEMPERATURE ADJUSTMENT
Safety and energy conservation are factors to be considered when selecting the water temperature setting on the thermostat. Water temperatures above 125° F can cause severe burns or death from scalding. The chart shown here may be used as a guide in determining the proper water temperature for your application.
6 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
6
Multi-Meter
Used to
measure
Resistance &
Voltage
Multi-Meter
Needle Set
Used on meter
test leads to
access
connectors
while measuring
Resistance &
Voltage
Manometer
Used to
measure gas
pressure
during standby
and operation
WARNING: WHILE MEASURING VOLTAGE, DO NOT touch any grounding areas on unit (unless specified in
SAFETY FIRST
Your safety and safety of others is very important.
This manual is only intended for qualified service technicians. ALWAYS USE CAUTION while testing
voltages and/or gas supply.
Troubleshooting Tools
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 7
7
WARNING: WHILE MEASURING VOLTAGE, DO NOT cross/touch
multi-meter leads together. This will cause damage to electrical components.
WHEN INSERTING LEADS INTO WIRING CONNECTOR, insert on the wiring side to prevent damage to connector.
BEFORE MEASURING RESISTANCE, TURN OFF all electrical power and make sure to REMOVE CONNECTOR from the circuit (control board). Check resistance on connector that was removed.
WHEN MEASURING VOLTAGE, DO NOT REMOVE CONNECTOR; insert multi-meter leads prior to operating unit.
WHEN MEASURING DC VOLTAGE, if the meter displays the dash (--­) symbol, swap the position of your black and red leads on the connector.
Multi-Meter Needle Leads
Wiring
Connector
Do NOT touch any
grounding areas while measuring
voltage
MEASURING VOLTAGE & RESISTANCE
8 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
8
Installation Guidelines for
HIGH-Efficiency ONLY:
GAS TYPE: Liquid Propane (LP) or Natural (NG) NG MAX INLET GAS PRESSURE: 10.5 (In. of w.c.) NG MIN INLET GAS PRESSURE: 4.0 (In. of w.c) LP MAX INLET GAS PRESSURE: 13.0 (In. of w.c.) LP MIN INLET GAS PRESSURE: 8.0 (In. of w.c.) MAX INPUT RATE: 199,900 (Btu/hr) MIN INPUT RATE: 11,000 (Btu/hr) GAS CONNECTION: 3/4” NPT ELECTRICAL CONSUMPTION: Normal: 100 W Standby: 3-5 W Antifreeze Protection: 200 W MINIMUM ACTIVATION FLOW RATE (gpm): 0.4 EXTINCTION FLOW RATE (gpm): 0.25 VENT SIZE (Indoor ONLY): 2” or 3”
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 9
9
The vent exhaust and air intake must be vented outside as described in the use and care manual. DO NOT vent this water heater through a chimney. It must be vented seperately from all other appliances.
NOTICE: The unit can be vented using only the following recommended pipe material. Use only 2 – or 3-inch diameter pipe. Refer to local codes for restrictions on the use of PVC, CPVC, or ABS pipe and fittings. All exhaust venting materials for product installed in Canada must meet ULC-S636. Acceptable materials or equivalent:
PVC (Schedule 40, ASTM D-1785 CPVC (Schedule 40, ASTM F-441) ABS (Schedule 40, ASTM D-2661) (Not permitted in Canada)
The fittings other than the VENT TERMINAL should be equivalent to the following: PVC (Schedule 40, DMW, ASTM D-2665 CPVC (Schedule 40, DMW, ASTM F-438) ABS (Schedule 40, DMW, ASTM D-2661) (Not permitted in Canada) Category III Stainless Steel DO NOT USE Schedule 20, Cell Core, Drain Pipe, Galvanized, Aluminum, or B-Vent.
Installation Guidelines for
HIGH-Efficiency ONLY:
Number of 90 Degree
Elbows
Maximum
Length of 2”
Straight Pipe
Maximum
Length of 3”
Straight Pipe
0 or 1
5 ft.
38 2 3.5 ft.
36’ 6”
3
2.0 ft.
35
4
Not available
33’ 6”
5
Not available
32
Number of 90 Degree
Elbows
Maximum
Length of 2”
Straight Pipe
Maximum
Length of 3”
Straight Pipe
0 or 1
60
150’ 2 586”
148’6” 3 57
147’ 4 55’ 6”
145’ 6” 5 54’
144’
10 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
10
Installation Guidelines for
MID-Efficiency ONLY:
GAS TYPE: Liquid Propane (LP) or Natural (NG) NG MAX INLET GAS PRESSURE: 10.5 (In. of w.c.) NG MIN INLET GAS PRESSURE: 4.0 (In. of w.c) LP MAX INLET GAS PRESSURE: 13.0 (In. of w.c.) LP MIN INLET GAS PRESSURE: 8.0 (In. of w.c.) MAX INPUT RATE: 199,900 (Btu/hr) MIN INPUT RATE: 11,000 (Btu/hr) GAS CONNECTION: 3/4” NPT ELECTRICAL CONSUMPTION: Normal: 100 W Standby: 3-5 W Antifreeze Protection: 200 W MINIMUM ACTIVATION FLOW RATE (gpm): 0.4 EXTINCTION FLOW RATE (gpm): 0.25 VENT SIZE (Indoor ONLY): 3”/5” concentric
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 11
11
WARNING:
Use 3-in. /5-in. UL-approved Category III
Stainless Steel vent materials or water heater manufacturer-approved vent material. No other vent material is permitted for use with this appliance.
Venting Requirements
The installation of the venting must comply with national codes, local codes and the vent manufacturer’s instructions.
The water heater must be vented to the outdoors. DO NOT vent this water heater through a chimney. It must be vented separately from all other appliances.
All coaxial vent components (adapters, pipe, elbows, terminals, etc.) should be water heater manufacturer­approved Stainless Steel Venting Material (e.g., AL29-4C).
Number of 90 Degree
Elbows (bends)
Maximum Length of
Straight Pipe
1
39’
2
37’ 6”
3
36’
4
34’ 6”
5
33’
6
31’ 6”
Installation Guidelines for
MID-Efficiency ONLY:
12 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
12
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
6.4
5.6
5.1
4.2
3.6
3.3
3.2
2.8
2.5 Max Water Flow - GPM (gallons per minute)
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
6.6
5.1
4.6
3.8
3.4
3.3
2.9
2.6
2.3 Max Water Flow - GPM (gallons per minute)
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
8.4
6.7
6.1
5.1
4.3
3.9
3.8
3.4
3.0 Max Water Flow - GPM (gallons per minute)
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
9.5
7.4
6.6
5.5
4.7
4.3
4.1
3.7
3.3 Max Water Flow - GPM (gallons per minute)
MID-EFFICIENCY FLOW RATES
64DV & 64X
95DV & 95X
84DV & 84X
68DV & 68X
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 13
13
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
8.4
6.6
6.0
5.0
4.3
3.9
3.7
3.3
3.0
Max Water Flow - GPM (gallons per minute)
Temperature Rise ( ° F)
35
45
50
60
70
77
80
90
100
9.5
8.4
7.6
6.3
5.4
4.9
4.7
4.2
3.8
Max Water Flow - GPM (gallons per minute)
H95DV & H95X
H84DV & H84X
HIGH-EFFICIENCY FLOW RATES
(Condensing)
14 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
14
G
C
S
U
R
H
K
B
T
M
P
***FUEL TYPE CHIP*** – When replacing Control Board, you must use the original chip on the new Control Board. New Control Board must be programmed (refer to page 122).
P – Red, Red (High Efficiency ONLY) M – White Molex: Grey T – Blue Molex: Blue (Indoor Models ONLY) K – Red, Black, Green, Yellow, White, Grey, Blue H – White, White, Grey, Grey U – White, White S – Brown, Black, Red C – Brown, White, Orange, Blue, Yellow, Green, Red, Black B - Brown, White, Orange, Blue, Yellow, Green, Red, Black G – Indoor Units: Blue, Yellow, White, Black, Red G – Outdoor Units: Yellow, Orange, Red, Blue, White R – Mid Efficiency: Red, Black, Black, Red, Yellow, White, Blue R – High Efficiency: Red, Black, Black, Red, Green, White, Blue
Control Board
Connectors
Connector Wire
Colors
Fuel Type Chip
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 15
15
CONTROL BOARD CONNECTORS
M
T
P
F
A
R
U
C
B
S
V
FUSES
(3A)
POWER
LED
DIP1
DIP2
MIN
MAX
ADJ
H
K
G
16 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
16
Diagnostic Points on Control Board
Connection
Wire
Color
Normal Value
What are
you
checking?
I – J
W1-BK2
AC108-132V
Do you have power to the
control
board?
U
W1-W2
50KΩ-500KΩ
Is the
overheat film
wrap OK?
S
BR1-BK2
DC 2-5V
(Pulse)
More than 1,310
pulses/minute
Does the
water flow
sensor send
a pulse?
(Only when
water is
flowing thru
the unit)
S
R3-BK2
DC 11-17V
Does the
water flow
sensor have
voltage?
(Power ON;
no water
flow)
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 17
17
Connection
Wire Color
Normal Value
What are
you
checking?
G
BK4-R6
DC 144-192V
Does the
fan motor
have the
proper
voltage?
W3-BK4
DC 12-18V
Is the
overheat
film wrap
OK?
BR1-BK2
DC 4-10V
(Pulse)
Is the fan
motor
producing
regular
pulse?
R
W6-BK3
68°F=10.3KΩ
104°F=4.9KΩ
Is the water
inlet
thermistor
working?
R
Mid-
Efficiency:
Y5-BK3
High-
Efficiency
(condensing):
G5-BK3
68°F=10.3KΩ
104°F=4.9KΩ
Is the heat exchanger
thermistor
working?
18 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
18
Connection
Wire Color
Normal Value
What are
you
checking?
R
R4-BK3
68°F=10.3KΩ
104°F=4.9KΩ
Is the water
outlet
thermistor
working?
R
BL7-BK4
Mid-Efficiency
INDOOR
Units:
68°F=10.3KΩ
104°F=4.9KΩ
Is the
ambient air
thermistor
working?
ALL
OUTDOOR &
ALL
CONDENSING
units:
68°F=10.3KΩ
104°F=4.9KΩ
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 19
19
Connection
Wire
Color
Normal Value
What are
you
checking?
R
R1-BK2
DC1.5-14V
40Ω-80Ω
Is the
P.G.F.R.
valve
operating?
(Proportional
Gas Flow
Regulator –
full
modulating
valve)
M
W1-GND
AC 1-100 V
Flame rod
detecting
flame?
T
BL1-GND
AC 1-100 V
Flame rod detecting flame?
H
GY3-GY4
AC 108-132 V
Is the igniter
working
properly?
20 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
20
Connection
Wire
Color
Normal Value
What are
you
checking?
K
Y1-BK6
DC 90-120 V
0.8KΩ-2.4KΩ
Gas inlet
solenoid
valve OK?
K
W2-BK6
DC 90-120 V
0.8KΩ-2.4KΩ
Solenoid
valve 1 OK?
K
GY3-BK6
DC 90-120 V
0.8KΩ-2.4KΩ
Solenoid
valve 2 OK?
K
R5-BK6
DC 90-120 V
0.8KΩ-2.4KΩ
Solenoid
valve 3 OK?
K
BL4-BK6
DC 90-120 V
0.8KΩ-2.4KΩ
Solenoid
valve 4 OK?
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 21
21
Maintenance Mode Panel Display
INSTRUCTIONS
The Rheem/Ruud Tankless has a maintenance mode chart on the remote control. To access the maintenance mode, turn the unit OFF at remote control and make sure water flow is OFF. Then hold down the UP and DOWN arrow keys at the same time for 5 seconds. You will hear an audible beep and see the display go to 1E (NOTE: Unit will default to 120° F). By pressing the UP and DOWN arrow keys on the remote control, you can access a variety of information about the water heater. To activate the unit while displaying the maintenance panel: push the power button once, open a hot water fixture, and the green LED will illuminate. This will allow you to access a variety of real time information while the unit is in operation.
Shortcut: (See Diagram on Page 22) DIP1 - Lift dip switch #1 to the up position to go immediately into maintenance mode. This can be done while the water heater is in operation. (NOTE: Unit will maintain the set temperature)
While in maintenance mode you want to push the UP arrow key to select the table you wish to view. The table is designated by a letter and is always displayed as the second digit. Then push the DOWN arrow key to display the number item in the table you selected. The number is always displayed as the first digit. You can select as many as 8 readings for each table.
To perform diagnostics in this service manual, press the UP arrow until you get to table1Y.
Now using your DOWN arrow you can change the number in front of Y. As you move through the diagnostic readings, the selected table will flash first and then the diagnostic reading.
(Maintenance Mode Table on Page 23)
22 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
22
You will see the following as you navigate the Y table in maintenance mode:
0Y = Flame rod status 1Y = Water flow in gallons per minute 2Y = Ambient air temperature 3Y = Water inlet temperature 4Y = Heat exchanger temperature 5Y = Hot water outlet temperature 6Y = Fan speed (x 100 rpm) 7Y = Power for modulating gas valve 8Y = Null (no reading) 9Y = Null (no reading)
control board
DIP1
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 23
23
24 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
24
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 25
25
Altitude Settings on Control Board
Locate the two DIP switches at top right of Control Board. Switch labeled DIP2 is the bottom switch. Altitude adjustments must be performed on DIP2 ONLY.
Sea Level (0ft 2000ft)
All switches should be in the OFF position (DOWN)
2000ft – 5400ft
3RD switch should be in the ON position (UP)
5400ft –8500ft
4TH switch should be in the ON position (UP)
DIP1
DIP2
26 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
26
ONLY for ‘Hard Lockouts’ - Error Codes: 10, 13 & 99
1. Turn remote control OFF; leave unit plugged in. Remove front cover. Locate the DIP Switches (Upper Right on the control board).
2. Make sure all the DIP Switches are OFF (down position).
3. Locate DIP1 – Switch #2 and turn it ON (up position) then immediately turn it OFF.
4. Within 5 seconds, press and hold the MIN and MAX buttons for at least 2 seconds.
5. The remote control will flash “UL” then it will go solid. This indicates the heater has been reset.
6. Release the buttons.
7. Turn remote control ON. You may operate unit.
control board
RESET PROCEDURE
DIP1
MIN
MAX
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 27
27
1. Turn remote control OFF; leave unit plugged in. Remove front cover. Locate the DIP Switches (Upper Right on the control board).
2. Make sure all the DIP Switches are OFF (down position).
3. Locate DIP1 – Switch #1 and turn it ON (up position) then immediately turn it OFF.
4. Within 5 seconds, press and hold the MIN or MAX button for at least 2 seconds.
5. The remote control will flash “CL” then it will go solid. This indicates the fault history has been cleared.
6. Release the buttons.
7. You can verify clearing history by entering maintenance mode and check the code at location 1E. Should read NULL (- - two dashes).
8. Turn remote control ON. You may operate unit.
control board
CLEARING FAULT HISTORY
DIP1
MIN
MAX
28 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
28
No Error Code & No Hot Water
Explanation: No hot water is delivered when water is
flowing through unit and remote control displays the
hot water temperature setting. [For ‘NO POWER’
complaint (remote control will not turn on) – check wall outlet for 120 volts. If voltage is present, check the two 3-amp fuses at the control board]
Possible Causes:
Water flow (0.4 GPM to activate)  DIP1 setting on main control board  Water flow sensor
Water Flow:
1. Use cold water shutoff valve to turn OFF water supply to unit. Turn remote control OFF; unplug power cord at wall outlet. Wait 10 seconds; plug power cord back into outlet; wait 20 seconds; turn the remote control ON. Turn water supply ON; check the nearest hot water fixture for hot water.
2. Open multiple hot water fixtures. If unit fires then there is not enough water flow to engage the unit at a particular fixture. Check your fixture aerator screen(s) for debris. Clean if necessary.
3. Your water flow may be restricted by debris in water filter. Remove the water filter and inspect. Clean if necessary.
4. Your water lines might be crossed. Make sure your hot and cold water supply lines are connected to the appropriate hot and cold water assembly connections on the unit.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 29
29
FINAL CHECK: Water flow sensor in water volume control valve.
Check connector S between the Red and Black wires. With the unit ON and no water flow, you should read 11-17 DC volts. If not, replace the control
board. IF you have voltage, then.......
With the water flowing, measure 2-5 DC volts between the Brown and Black wire. (This is measuring water flow thru the control). IF you have a reading and no main burner, replace the control board. If you do not have a reading, remove any debris from water volume control valve.
Single Unit Installations ONLY:
All DIP1 switches must be in the ‘OFF’ position (DOWN).
DIP 1
Manifold (Multiple) Unit Installations ONLY:
Go to 03 - Error Code to verify proper DIP1 setting.
Water Flow Sensor:
Connector Location
On Page 14
30 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
30
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 31
31
1. Turn the water supply to the unit OFF. Turn the remote control OFF, wait 10 seconds and turn the remote control ON. Turn the water supply to the unit ON and check the nearest hot water fixture for hot water. If you have hot water, then the unit needed to be reset.
2. Your water lines might be crossed. Make sure your hot and cold water supply lines are connected to the appropriate hot and cold water connections on the unit.
3. Your water flow may be restricted by a dirty In-Line Water Filter. Remove the water filter and inspect. Clean if necessary.
4. Possible plumbing cross-over in the home. Turn OFF hot water valve to the water heater. Go to each water fixture in the home and turn ON the hot water ONLY (test washing machine by setting it to hot ONLY). If water flows freely through the hot water side of the fixture, this is a plumbing crossover. HINT: During this test, to prevent scalding, pressure-balancing valves on single-handle fixtures will not allow any water to flow if there is a plumbing crossover.
5. Water flow might be too low. Open multiple hot water fixtures. If unit fires then there is not enough water flow to engage the unit at a particular fixture. Check your fixture aerator screen(s) for debris. Clean if necessary. FOR RECIRCULATION LINES: check pump size, aqua­stat, check valve, and operation.
P1 - Warning Code
Explanation: No hot water is delivered when water
is flowing through unit and remote control displays P1 - Warning Code.
Possible Causes:
Not Enough Water Flow
32 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
32
.
1L - Warning Code
Explanation: The control board has detected lime
build-up inside the heat exchanger. To prevent permanent damage to the unit, the unit must be drained and flushed. Flushing procedures may need to be repeated for excessive lime and scale build-up. *To reset 1L Code, hold down the MIN and MAX
buttons at the same time for 10 seconds
NOTE: Flushing instructions utilize a submersible utility pump (provided with the Rheem/Ruud Tankless Flush Kit – RTG20124)
Tankless Water Heater
Gas Supply
Valve
Cold Water
Service
Valve
(cold water side)
Hot Water
Service
Valve
(hot water side)
Drain Hose
(cold water side)
Drain Hose
(hot water side)
5-Gallon
Bucket
Utility Pump
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 33
33
1. Turn OFF gas and both the cold and hot water supply to the water heater. The gas must remain OFF during the flushing process.
2. At the remote control, turn OFF the power and wait 10 seconds. Turn ON the power and wait 10 seconds. Disconnect the water heater from the electrical source.
3. Connect a hose to the hose connections on the service valves under the water heater.
4. Place the loose end of the hoses into a 5-gallon bucket.
5. Open the service port valve on each side of the service valves, to allow the heater to drain. Connect the cold water side hose to the outlet side of the utility pump and set the pump into the bottom of the bucket.
6. Pour 2 gallons of virgin food grade white vinegar into the bucket and turn the pump ON.
7. Allow the pump to circulate the vinegar for 45 to 60 minutes. (time will vary depending upon mineral build-up and hardness of the water)
8. Turn OFF the pump and remove the hose from the pump. Allow the vinegar to drain from water heater into the bucket.
9. Place the hot water side hose in another bucket or route it to a suitable drain.
10. Close the service port valve on the cold water side and disconnect the cold water hose from the service valve.
11. Follow instructions in the Use & Care manual, supplied with the water heater, to clean the water inlet filter.
12. Turn ON the cold water supply to the heater. DO NOT TURN ON THE HOT WATER SUPPLY TO THE HEATER. Water will begin to flow through the heater; this will rinse out any remaining vinegar from the water heater. Allow the water to run for approximately 5 minutes.
13. Close the hot water service port valve and disconnect the drain hose.
14. Open a hot water fixture in the home, such as a tub. Allow the water to flow for a minute to ensure there is no air remaining in the system. Turn OFF the hot water fixture.
15. Reconnect power to water heater, turn ON gas supply, and turn ON power at the remote control.
16. Turn ON a hot water fixture to ensure the water heater is operating.
34 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
34
Only for manifold (multiple) unit installations: EZ­Link; MIC-6; or MIC-185 manifold controllers.
Explanation: Communication failure between water heaters, remote control, and/or manifold controller.
Diagnostic Checks:
DIP1 setting on main control board (PCB)
DIP1 SETTING:
Manifold units only: DIP1, switch #4 must be in the ON position (UP) for each unit.
Check ALL Molex connections on ALL control boards.
If 03 - Error Code is displayed after completing all checks: Call Technical Support (800)-432-8373
03 - Error Code
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 35
35
Make sure DIP2 on control board is set to the correct altitude. Refer to Page 25 for altitude settings.
`
05 – Warning Code
Explanation: The flame rod has detected improper
burner combustion (Indoor Units ONLY). This warning code is commonly caused by VENTING and/or GAS SUPPLY.
Diagnostic Checks:
GAS SUPPLY & VENTING (refer to pages 8-11)
DIP2 setting on main control board
DIP1
DIP2
36 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
36
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 37
37
10 – Warning Code
Explanation: Unit was operated prior to vent
installation OR blower motor is not creating enough ventilation.
First: Follow reset procedure on page 26. Next: Check VENTING.
Diagnostic Checks:
VENTING (refer to pages 8-11) Blower motor
Remove control board bracket. (How to remove: Section 1)
Remove blower motor. (How to remove: Section 2)
Clean blower motor and blower motor housing.
Reassemble & operate unit.
Does 10-Warning Code appear?
Locate MIN & MAX buttons
on upper right-hand corner of
control board.
Continue diagnostics on next
page.
YES
Blower motor needed to be
cleaned or you had a loose
connection.
Unit appears to be operating
OK.
NO
MIN & MAX
BUTTONS
CONTROL
BRACKET
38 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
38
Blower Motor Diagnostics: INDOOR Models ONLY
Upper Right-Hand Corner of Control Board
Test DC voltage across
Black and Red wires
on connector G:
144 – 192 DC Volts
YES
Remove & re insert G.
Operate unit again.
IF Code 10 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & White wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 10 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & Blue wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 10 appears:
Replace blower motor .
NO
Control board and blower
motor are OK.
CHECK VENTING.
IMPORTANT: While performing voltage checks, DO NOT touch
multimeter leads across BLUE & White wires. Damage may occur
to blower motor and control board.
Connector Location
On Page 14
MIN
MAX
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 39
39
Blower Motor Diagnostics: OUTDOOR Models ONLY
Test DC voltage across
Blue and White wires
on connector G:
144 – 192 DC Volts
YES
Remove & re insert G.
Operate unit again.
IF Code 10 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Red wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 10 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Yellow wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 10 appears:
Replace blower motor .
NO
Control board and blower
motor are OK.
CHECK VENTING.
IMPORTANT: While performing voltage checks, DO NOT touch
multimeter leads across YELLOW & RED wires. Damage may
occur to blower motor and control board.
Connector Location
On Page 14
Upper Right-Hand Corner of Control Board
MIN
MAX
40 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
40
Igniter Rod Diagnostics (spark is NOT visible)
11 – Error Code
Explanation: Flame rod(s) does not detect flame.
Commonly GAS SUPPLY and/or VENTING.
IMPORTANT: If all water heater components test OK, you must
thoroughly inspect your GAS SUPPLY & VENTING.
Diagnostic Checks:
GAS SUPPLY & VENTING (refer to pages 8-11) Igniter rod  Flame rod(s) Gas control valve
Connector Location
On Page 14
HINT: Make sure DIP2 (altitude setting) is properly
set – see Page 25
Turn Power OFF.
Remove and reinsert: connector H(White Molex on
bottom of igniter coil) & black insulated igniter
cable on igniter rod.
Turn Power ON.
Operate unit and determine IF spark is visible
through sight glass.
You had a loose connection.
Igniter is OK.
YES
Continue diagnostic on next
page.
NO
SIGHT GLASS
IGNITER ROD
IGNITER COIL
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 41
41
While attempting to ignite,
test AC Volts across 2 Grey
wires on connector H:
108 – 132 AC Volts
YES
Remove & reinsert H.
Operate unit again.
IF Code 11 appears:
Replace control board.
NO
Turn GAS OFF.
Remove and hold igniter
cable 1/8 inch from igniter
connection. With GAS OFF,
operate unit. Determine IF
there is a spark
at igniter connection.
YES
Replace igniter coil..
NO
Turn power OFF.
Remove and clean igniter
rod. Reassemble & operate
unit. Is spark visible through
sight glass?
YES
Replace igniter rod.
NO
Igniter rod needed to be
cleaned and is OK. Turn GAS
ON and check for normal
operation.
Igniter Rod Diagnostics (spark is NOT visible)
IGNITER ROD
IGNITER COIL
IGNITER
CABLE
WHITE MOLEX
42 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
42
Turn Power OFF.
Remove and reinsert connector M, T, and
terminal on flame rod(s).
Turn Power ON.
While viewing through sight glass, operate unit to determine
IF flame is touching the flame rod(s).
Indoor models – 2 flame rods (Connectors M& T).
Outdoor models – 1 flame rod (Connector M).
Access maintenance mode
to check flame rod status &
continue to diagnostic chart
on next page.
YES
Remove any foreign debris.
IF foreign debris is not
present: CHECK GAS
SUPPLY & VENTING.
NO
(See maintenance mode instructions on page 21)
Flame Rod Diagnostics (flame IS visible)
SIGHT GLASS
FLAME ROD(S)
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 43
43
Flame Rod(s) Diagnostics
Outdoor: 1 flame rod
White Molex – Grey Wire
Indoor: 2 flame rods
White Molex – Grey Wire
Blue Molex – Blue Wire
Test AC volts on
connector M
(Grey wire to Ground)
1 – 100 AC Volts
YES
Remove & reinsert M.
Operate unit again.
IF code 11 appears:
Replace control board.
NO
Test AC volts on connector
T(Blue wire to Ground)
1 – 100 AC Volts
YES
Remove & reinsert T.
Operate unit again.
IF code 11 appears:
Replace control board.
NO
Cycle unit ON; while in
maintenance mode, check
flame rod status under
table 0Y.
IF flame rod(s) is detecting
flame, maintenance mode
will display:
Indoor Models – 05
Outdoor Models - 01
YES
Clean flame rod(s). Operate
unit again. IF still does not
detect flame:
Replace flame rod(s).
NO
Flame rod(s) test OK.
CHECK GAS SUPPLY, VENTING, & GROUND.
44 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
44
Gas Control Valve Diagnostics
(Igniter Rod Sparks & NO flame)
IMPORTANT: DURING VOLTAGE CHECKS – CONNECTOR KONLY
(water is flowing and unit is attempting to ignite):
IF you do NOT get a voltage reading, push and hold the MAX button on
upper right hand corner of control board to activate unit at full BTUs. This will force voltage to ALL gas valve solenoids during diagnostics.
CAUTION: DO NOT hold MAX button down for more than 5 Seconds
*MAY CAUSE DAMAGE TO THE HEAT EXCHANGER*.
Connector Location
On Page 14
Turn Power OFF.
Remove and reinsert connectors K& R.
(Connector Kis Gas Valves.
Connector Ris PGFR valve.)
Locate PGFR valve on lower right side of unit
(round black piece on bottom of gas valve.
PGFR is a full modulating gas valve).
Remove and reinsert Molex connectors with
Red and Black wires on PGFR.
Turn Power ON.
While viewing through sight glass, operate unit to
determine IF flame is visible.
You had a loose connection.
Gas control valve is OK.
YES
Continue diagnostics on
next page.
NO
MAX
GAS VALVE
PGFR
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 45
45
Gas Control Valve Diagnostics
While attempting to ignite
test DC volts across #1 wire
(Red) & #2 wire (Black) on
connector R:
1.5 – 14 DC Volts
YES
Remove & reinsert R.
Operate unit again.
IF Code 11 appears:
Replace control board.
NO
Turn power OFF. Remove
connector R& measure
resistance across same
wires:
40 – 80 OHMS
YES
Remove & reinsert PGFR
connectors. Retest R.
IF resistance test fails:
Replace gas control valve.
NO
Turn power OFF.
Remove connector K.
On connector K: Using the
BLACK WIRE as the
common – individually check
resistance for Yellow, White,
Grey, Red, & Blue wires:
0.8K – 2.4K OHMS
YES
Make sure all wires are
connected to Gas Control
Valve. Retest connector K.
IF test fails: Replace gas
control valve.
NOTE: IF Grey wire failed
ohms test, replace manifold
assembly.
NO
Gas control valve is OK.
Reconnect connector K.
Turn power ON.
While unit is attempting to
ignite - On connector K:
Using the BLACK WIRE as
the common – Individually
check DC volts for Yellow,
White, Grey, Red, & Blue
wires:
90 – 120 DC Volts
Remove & reinsert K.
Operate unit again. IF 11-
Error Code appears:
Replace control board.
NO
Control board is OK.
IF ALL components tested
OK: CHECK GAS SUPPLY,
VENTING, & GROUND.
YES
46 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
46
.
12 – Error Code
Explanation: Commonly GAS SUPPLY and/or
VENTING. Unit detected the presence of flame and then lost it.
Diagnostic Checks:
GAS SUPPLY & VENTING (refer to pages 8-11)
Flame rod(s)
(See maintenance mode instructions on page 21)
Connector Location
On Page 14
Turn Power OFF.
Remove and reinsert connector M; T;
and terminal on flame rod(s).
Turn Power ON.
While viewing through sight glass, operate unit to determine
IF flame is touching the flame rod(s).
Indoor models – 2 flame rods (Connectors M& T).
Outdoor models – 1 flame rod (Connector M).
Access maintenance mode
to check flame rod status &
continue to diagnostic chart
on next page.
YES
Remove any foreign debris.
IF foreign debris is not
present: CHECK GAS
SUPPLY & VENTING.
NO
HINT:: Make sure DIP2 (altitude setting) is properly
set – see Page 25
SIGHT GLASS
FLAME ROD(S)
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 47
47
Test AC volts on
connector M
(Grey wire to Ground)
1 – 100 AC Volts
YES
Remove & reinsert M.
Operate unit again.
IF code 12 appears:
Replace control board.
NO
Test AC volts on connector
T(Blue wire to Ground)
1 – 100 AC Volts
YES
Remove & reinsert T.
Operate unit again.
IF code 12 appears:
Replace control board.
NO
Cycle unit ON; while in
maintenance mode, check
flame rod status under
table 0Y.
IF flame rod(s) is detecting
flame, maintenance mode
will display:
Indoor Models – 05
Outdoor Models - 01
YES
Clean flame rod(s). Operate
unit again. IF still does not
detect flame:
Replace flame rod(s).
NO
Flame rod(s) test OK.
CHECK GAS SUPPLY, VENTING, & GROUND.
Outdoor: 1 flame rod
White Molex – Grey Wire
Indoor: 2 flame rods
White Molex – Grey Wire
Blue Molex – Blue Wire
48 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
48
13 – Error Code
Explanation: Indoor units ONLY. Flame rod is
detecting poor combustion. This is commonly caused by inadequate GAS SUPPLY and/or VENTING.
Diagnostic Checks:
GAS SUPPLY & VENTING (refer to pages 8-11) Flame rod FL-2
(See maintenance mode instructions on page 21)
Turn Power OFF.
Remove and reinsert connector Tand
Terminals on flame rods.
Turn Power ON.
While viewing through sight glass, operate unit to determine
IF flame is touching the flame rod(s).
Indoor models – 2 flame rods
(Connectors M& T).
Access maintenance mode
to check flame rod status &
continue to diagnostic chart
on next page.
YES
Remove any foreign debris.
IF foreign debris is not
present: CHECK GAS
SUPPLY & VENTING.
NO
HINT: Make sure DIP2 (altitude setting) is properly
set – see Page 25
(If unit shuts down 5 times within a 4 hour period
due to 13 – Error Code, the unit must be
reset by performing reset procedure
on page 26).
Connector Location
On Page 14
SIGHT GLASS
FLAME ROD(S)
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 49
49
Test AC volts on
connector T
(Blue wire to Ground)
1 – 100 AC Volts
YES
Remove & reinsert T.
Operate unit again.
IF code 13 appears:
Replace control board.
NO
Cycle unit ON; while in
maintenance mode, check
flame rod status under table
0Y. IF flame rod(s) is
detecting flame, maintenance
mode will display: 05
YES
Unit is operating correctly.
Burner and/or manifold
needed to be cleaned.
CHECK the area around the
air intake for the possible
cause of dirty manifold and/
or burner.
Flame rod(s) test OK.
Remove and clean the
manifold assembly and
burner assembly (How to
Remove: Sections 4 & 5).
Reassemble and operate
unit again.
Did Error Code - 13 appear?
YES
Clean flame rod(s). Operate
unit again. IF still does not
detect flame:
Replace flame rod(s).
NO
CHECK GAS SUPPLY,
VENTING, & GROUND.
Indoor: 2 flame rods
White Molex – Grey Wire
Blue Molex – Blue Wire
50 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
50
14 – Error Code
Explanation: OHL (Over Heat Limiter) or Over Temp Limit
Switch activated. IF the OHL or Over Temp Limit Switch has been activated, this is normally caused by inadequate/wrong GAS SUPPLY and/or VENTING.
CHECK GAS SUPPLY & VENTING (refer to pages 8-11).
Diagnostic Checks:
OHL  High-Efficiency ONLY: Over Temp Limit
Switch (monitors vent temperature)
High-Efficiency Indoor (condensing) ONLY:
Locate the Over Temp Limit Switch (circled in red)
Connector Location
On Page 14
Turn Power OFF.
Remove & reinsert connector U.
Attempt to operate unit.
Does 14 – Error Code appear?
Continue to diagnostic chart
on next page.
YES
Unit had a loose connection
or over temp limit switch
cooled down. Unit appears
to be operating OK.
NO
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 51
51
Turn power OFF. Remove
connector U. Measure
resistance across both White
wires:
50K – 500K OHMS
YES
Mid Efficiency ONLY:
Replace Unit.
High Efficiency
Indoor ONLY:
Continue to over
temp switch diagnostics.
(bottom of page)
NO
Reconnect connector U.
Attempt to operate unit.
YES
Unit had a loose connection.
Operation appears to be
normal.
IF error code 14 appears:
Replace control board.
NO
Over Temp Limit Switch - High Efficiency Indoor
(Condensing) ONLY:
Disconnect two White Molex
connectors for the over temp
limit switch.
On female end of Molex,
check continuity across both
Black wires.
YES
Switch automatically resets
once it cools down.
Allow limit switch to
cool down. IF switch does
NOT have continuity
once unit cools down:
Replace over temp
limit switch.
IF switch automatically
resets, check VENTING.
Limit switch possibly cooled
down. Operate unit.
IF error code 14 appears and
you have continuity through
Over Temp Limit Switch:
Replace Unit.
52 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
52
15 – Error Code
Explanation: The hot water temperature and/or heat
exchanger temperature reached 207 degrees F for more than 15 seconds.
Diagnostic Checks:
GAS SUPPLY & VENTING (refer to pages 8-11)
Sediment build-up in heat exchanger  Heat exchanger thermistor
Sediment Build-Up Diagnostics
Go to Error Code 1L for flushing instructions.
Heat Exchanger Thermistor Diagnostics
Go to Error Code - 32 for heat exchanger thermistor diagnostic instructions.
IMPORTANT: Inadequate GAS SUPPLY and/or VENTING
will create hot spots in the heat exchanger.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 53
53
16 – Error Code
Explanation: Outlet water temperature is above the
set point on the remote control.
Diagnostic Checks:
Outlet thermistor  Water bypass valve
Outlet Thermistor Diagnostics:
Go to Error Code 33 for outlet thermistor diagnostic instructions.
Water Bypass Valve Diagnostics:
Go to Error Code 66 for water bypass valve diagnostic instructions.
IMPORTANT: Check the outlet thermistor FIRST.
54 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
54
24 – Error Code
Explanation: Remote control buttons were
depressed for more than 20 seconds, release buttons and operate unit. IF error code 24 appears again, continue to remote control diagnostics.
Diagnostic Checks:
Remote control
Visually inspect remote
control wiring for damaged
or loose connections.
Is wiring OK?
YES
Tighten loose
Connections or replace
damaged wiring.
NO
Turn Power OFF & unplug
unit from power source.
Remove wires from wiring
terminals on remote control
and bottom of unit. Use a
new short piece of wire to
connect remote control
directly to wiring terminals at
bottom of unit.
Plug unit in, turn power ON
and open a hot water source.
Does 24 – Error Code
appear?
YES
Replace remote control.
Replace remote control
wiring
NO
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 55
55
29 – Error Code (A)
Explanation: High-Efficiency (condensing) Units ONLY: Condensation is NOT draining.
Diagnostic Checks:
Plug not removed from condensate drain  Pinch in condensate drain line  Blockage in condensate drain line  Drain line has unnecessary “P” trap
Condensate Drain Diagnostics:
1. Ensure you removed the condensate
protection plug located at bottom of unit & attached a condensate drain line to the unit.
2. Check condensate drain line for internal or external blockage. Make sure drain line is NOT pinched.
3. Remove “P” trap on condensate drain line.
BOTTOM OF UNIT
56 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
56
29 – Error Code (B)
Explanation: Heat exchanger temperature too low
for more than 3 minutes.
Diagnostic Checks:
Inlet & heat exchanger thermistors  Gas control valve  Water volume control valve
Inlet thermistor Diagnostics:
Go to 31 – Error Code.
Heat Exchanger thermistor Diagnostics:
Go to 32 – Error Code.
Turn power OFF.
Remove connector Rand
measure resistance across #1 wire (Red)
and #2 wire (Black):
40-80 OHMS
Remove connector K. Using the BLACK WIRE
as the common – Individually check resistance for
Yellow, White, Red, & Blue wires:
0.8K – 2.4K OHMS
Continue to diagnostic chart
on next page.
YES
Replace gas control valve.
NO
Connector Location
On Page 14
HINT: High-Efficiency (condensing) Units ONLY:
make sure condensate is draining properly
prior to continuing diagnostics
(go to previous page for diagnostics).
HINT: ALWAYS diagnose thermistors before
continuing to next steps.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 57
57
Calculate Temperature Rise & Gallons per Minute:
1. Enter maintenance mode & select table 3Y. Turn on
water flow to determine inlet water temperature.
2. Using the formula below, determine temperature rise.
Remote control temp - Incoming water temp = Temperature Rise
3. Select table 1Y. Using the incoming water shut off valve
Turn OFF incoming water at the unit. Turn ON ALL hot water fixtures in the home/business to full flow. Using the incoming water shut-off valve, turn ON incoming water at unit. Determine MAX GPM flowing through unit.
*BEFORE continuing - Refer to pages 12 & 13 to obtain MAX GPM possible for appropriate model number.
Maintenance Mode
Instructions on Page 21
With ALL hot water fixtures
turned ON full flow, will the
unit EXCEED MAX GPM it
can produce?
YES
Remove & reinsert C.
Operate unit again.
IF Code 29 appears:
Replace control board.
NO
Turn water & remote control
OFF. Turn remote control
ON. Open ALL hot water fixtures. Measure DC Volts across Black & White wires
on connector C:
8 – 16 DC Volts
YES
NO
Measure DC Volts across
black & red wires on
connector C:
8 – 16 DC Volts
YES
NO
Replace water volume
control valve.
Remove & reinsert C.
Operate unit again.
IF Code 29 appears:
Replace control board.
Remove & reinsert C.
Operate unit again.
IF Code 29 appears:
Replace control board.
58 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
58
31 – Error Code
Explanation: Inlet thermistor malfunction.
Diagnostic Checks:
Inlet thermistor
Connector Location
On Page 14
Turn Power OFF.
Remove connector R. Measure resistance
between #3 wire (Black) & #6 wire (White):
7K – 23K Ohms
Reinsert connector R.
Operate unit.
IF Error Code 31 appears:
Replace control board.
YES
Remove control board bracket to access inlet
thermistor Molex near
blower motor
(How to Remove: Section 1).
Continue diagnostics
on next page.
NO
CONTROL
BRACKET
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 59
59
Locate & separate WHITE
Molex (located near blower
motor). Check resistance
across White wires on female
end of Molex:
7K – 23K Ohms
YES
Clean scale build-up on inlet thermistor. Operate unit. IF
Error Code 31 appears:
Replace inlet thermistor.
NO
Reconnect Molex. Check resistance on connector R between #3 wire (Black) and
#6 wire (White): 7K – 23K Ohms
YES
Replace wiring harness for
connector R.
NO
Reinsert connector R.
Operate unit.
IF 31 - Error Code
appears:
Replace control board.
Blower Motor
Molex Connectors
60 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
60
32 – Error Code
Explanation: Heat exchanger thermistor malfunction.
Diagnostic Checks:
Heat exchanger thermistor
Connector Location
On Page 14
Turn Power OFF. Remove connector R:
Mid-Efficiency Units ONLY: Measure resistance between
#3 wire (Black) & #5 wire (YELLOW):
High-Efficiency Units ONLY: Measure resistance between
#3 wire (Black) & #5 wire (GREEN):
7K – 23K OHMS
Reinsert connector R.
Operate unit.
IF Error Code 32 appears:
Replace control board.
YES
Remove control board
bracket to access heat
exchanger thermistor Molex
near
blower motor
(How to Remove: Section 1).
Continue diagnostics
on next page.
NO
CONTROL
BRACKET
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 61
61
Locate & separate Yellow or
Green Molex (located near
blower motor). Check
resistance across White
wires on female end of
Molex:
7K – 23K Ohms
YES
Clean scale build-up on heat
exchanger thermistor.
Reassemble and operate
unit. IF Error Code 32
appears:
Replace heat exchanger
thermistor.
Reconnect Molex. Check resistance on connector R between #3 wire (Black) and
#5 wire (Yellow) OR #3 wire (Black) and #5 wire (Green):
7K – 23K Ohms
YES
Replace wiring harness for
connector Ron control
board.
NO
Reinsert connector R.
Operate unit.
IF 32 - Error Code
appears:
Replace control board.
Blower Motor
Molex Connectors
62 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
62
33 – Error Code
Explanation: Outlet thermistor malfunction.
Diagnostic Checks:
Outlet thermistor
Turn Power OFF.
Remove connector R:
Measure resistance between
#3 wire (Black) & #4 wire (RED):
7K – 23K OHMS
Reinsert connector R.
Operate unit.
IF Error Code 33 appears:
Replace control board.
YES
Remove control board
bracket to access outlet
thermistor Molex near
blower motor
(How to Remove: Section 1).
Continue diagnostics
on next page.
NO
Connector Location
On Page 14
CONTROL
BRACKET
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 63
63
Blower Motor
Molex Connectors
Locate & separate Black
Molex (located near blower
motor). Check resistance
across White wires on female
end of Molex:
7K – 23K Ohms
YES
Clean scale build-up outlet
thermistor. Reassemble and
operate unit. IF Error Code
33 appears:
Replace outlet thermistor.
Reconnect Molex. Check
resistance on connector R between #3 wire (Black) and
#4 wire (Red):
7K – 23K Ohms
YES
Replace wiring harness for
connector Ron control
board.
NO
Reinsert connector R.
Operate unit.
IF 33 - Error Code
appears:
Replace control board.
64 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
64
34 – Error Code
Explanation: Ambient thermistor malfunction.
Diagnostic Checks:
Ambient thermistor
Turn Power OFF. Remove connector R:
Measure resistance between
#3 wire (Black) & #7 wire (Blue):
64DV; 84DV; 95DV: 7K – 23K Ohms
64X; 84X; 95X; H95X; H95DV: 2K – 72K Ohms
Reinsert connector R.
Operate unit.
IF Error Code 34 appears:
Replace control board.
YES
Remove control board
bracket to access ambient
thermistor Molex near
blower motor
(How to Remove: Section 1).
Continue diagnostics
on next page.
NO
Connector Location
On Page 14
CONTROL
BRACKET
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 65
65
Locate & separate Blue
Molex (located near blower
motor). Check resistance
across White wires on female
end of Molex: 2K – 72K Ohms 7K – 23K Ohms
YES
Clean scale build-up ambient
thermistor. Reassemble and
operate unit. IF Error Code
34 appears:
Replace ambient thermistor.
NO
Reconnect Molex. Check resistance on connector R between #3 wire (Black) and
#7 wire (Blue): 2K – 72K Ohms 7K – 23K Ohms
YES
Replace wiring harness for
connector Ron control
board.
NO
Reinsert connector R.
Operate unit.
IF 34 - Error Code
appears:
Replace control board.
Blower Motor
Molex Connectors
66 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
66
35 – Error Code
Explanation: Improper thermistor connection. Unit
has four thermistors; one or more possibly has a poor connection or not connected in proper location.
Diagnostic Checks:
Inlet, heat exchanger, outlet, & ambient
thermistors
Connector Location
On Page 14
Turn Power OFF. Remove connector R.
Turn Power ON. Operate Unit.
Does 35 – Error Code Appear?
Test ALL thermistors.
Follow Instructions for:
31 – Error Code
32 – Error Code
33 – Error Code 34 – Error Code
YES
Unit had a loose connection.
Thermistors appear to be
OK.
NO
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 67
67
(See maintenance mode instructions on page 21)
51 – Error Code
Explanation: Gas control valve malfunction. Unit
detected the presence of flame when demand for hot water terminated & the unit turned OFF.
Diagnostic Checks:
Flame rod(s)  Gas control valve
Connector Location
On Page 14
Turn Power OFF.
Remove and reinsert connector M, T,
and terminal on flame rod(s).
Turn Power ON. Operate unit.
Did 51 – Error Code appear?
Indoor models – 2 flame rods (Connectors M& T).
Outdoor models – 1 flame rod (Connector M).
Access maintenance mode
to check flame rod status.
Locate sight glass.
Continue to diagnostic chart
on next page
YES
Unit had a loose connection
or foreign debris that is no
longer present.
Thermistors appear to be
OK.
NO
Connector Location
On Page 14
SIGHT GLASS
FLAME ROD(S)
68 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
68
While viewing burner
chamber through sight glass:
In 10 second intervals, cycle
unit 3 times -
ON-OFF; ON-OFF; ON-OFF
Determine if flame is visible
when OFF.
YES
Follow maintenance mode
instructions at bottom of
page & continue to
diagnostics on next page.
NO
Visually inspect burner
chamber through sight glass
for foreign debris.
YES
Operate unit.
IF 51 – Error Code appears & flame IS visible while unit has
been OFF longer than 5
seconds:
Replace gas control valve.
NO
Remove and clean
burner assembly
On remote control, go to maintenance mode 0Y table. For
maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done
immediately after turning the unit OFF. IF Flame Rod(s) is
detecting flame, maintenance mode will display:
Indoor Units: 05
Outdoor Units: 01
Outdoor: 1 flame rod
Indoor: 2 flame rods
Open a hot water fixture
and use shut-off
valve at the unit to
cycle unit On-Off.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 69
69
In 10 second intervals, cycle
unit 3 times by turning unit:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in maintenance mode indicate presence of flame while unit
has been off >5 seconds?
YES
Follow maintenance mode
instructions at bottom of
page & continue to
diagnostics on next page.
NO
Disconnect wires at flame
rod(s). While viewing burner
chamber through sight glass:
In 10 second intervals, cycle
unit 3 times by turning unit:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in maintenance mode indicate presence of flame while unit
has been off >5 seconds?
YES
Clean flame rod(s).
IF 51 – Error Code appears
after cleaning flame rod(s):
Replace flame rod(s).
Replace control board.
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done
immediately after turning the unit OFF.
IF Flame Rod(s) is detecting flame, maintenance mode will
display:
Indoor Units: 05
Outdoor Units: 01
70 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
70
52 – Error Code
Explanation: PGFR malfunction. The PGFR is
the only modulating valve in the gas control valve.
Diagnostics: PGFR (Proportional Gas Flow Regulator)
Connector Location
On Page 14
Turn Power OFF.
Remove and reinsert connector R.
Locate PGFR valve on lower right side of
unit (round black piece on bottom of gas control valve).
Remove and reinsert Molex connectors with Red and Black
wires on PGFR.
Operate unit.
While viewing through sight glass,
determine if flame is visible.
Unit had a loose connection
Gas control valve is OK.
_______________________
IF 52 – Error Code appears
and flame IS visible:
Replace gas control valve
YES
Continue diagnostics on
next page.
NO
PGFR
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 71
71
While unit is attempting to
ignite:
Check DC volts across
#1 wire (Red) and #2 wire
(Black) on connector R:
1.5 – 14 DC Volts
YES
Remove & reinsert R.
Operate unit.
If 52 – Error Code appears:
Replace control board.
NO
While unit is attempting to
ignite:
Check DC volts across Red
and Black wires at PGFR:
1.5 – 14 DC Volts
YES
Replace wiring harness for
connector Ron control
board.
NO
Make sure Black & Red wires
are properly connected to
PGFR. Operate unit.
IF 52 - Error Code appears:
Replace gas control valve.
PGFR
RED & BLACK
WIRES
72 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
72
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 73
73
Explanation: The Blower motor speed was not appropriate to allow proper combustion.
Diagnostic Checks:
Blower motor
61 – Error Code
Turn Power OFF.
Remove control board bracket (How to Remove: Section 1).
Remove blower motor (How to Remove: Section 2).
Clean blower motor and blower motor housing.
Reassemble & operate unit.
Does 61 – Error Code appear?
Locate MIN & MAX buttons
on upper right- hand corner
of control board.
Continue diagnostics on next
page
YES
Unit had a loose connection.
Unit appears to be operating
OK.
NO
MIN & MAX
BUTTONS
CONTROL
BRACKET
74 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
74
Blower Motor Diagnostics:
Indoor Models ONLY
Upper Right-Hand Corner of Control Board
Test DC voltage across
Black and Red wires
on connector G:
144 – 192 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & White wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & Blue wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61 appears:
Replace blower motor.
NO
Control board and blower
motor are OK.
CHECK GAS SUPPLY AND
VENTING.
IMPORTANT: While performing voltage checks, DO NOT touch
multimeter leads across BLUE & White wires. Damage may occur
to blower motor and control board.
Connector Location
On Page 14
MIN
MAX
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 75
75
Blower Motor Diagnostics:
Outdoor Models ONLY
Upper Right-Hand Corner of Control Board
IMPORTANT: While performing voltage checks, DO NOT touch
multimeter leads across YELLOW & RED wires. Damage may
occur to blower motor and control board.
Test DC voltage across
Blue and White wires
on connector G:
144 – 192 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Red wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Yellow wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 61 appears:
Replace blower motor.
NO
Control board and blower
motor are OK.
CHECK VENTING.
Connector Location
On Page 14
MIN
MAX
76 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
76
Turn on all hot water fixtures to activate water control valve
(refer to 29 – ErrorCode (B) Page 56).
Explanation: Water volume control valve malfunction.
Diagnostic Checks:
Water volume control valve
65 – Error Code
Blower Motor
Connector Location
On Page 14
Turn Power Off, Remove & Reinsert connector C.
Remove control board bracket. (How to remove: Section 1)
Visually inspect water volume control valve for
loose or damaged connections
Reassemble & operate unit.
Does 10-Warning Code appear?
Locate MIN & MAX buttons
on upper right-hand corner of
control board.
Continue diagnostics on next
page.
YES
Blower motor needed to be
cleaned or you had a loose
connection.
Unit appears to be operating
OK.
NO
IMPORTANT: The water volume control valve will only activate IF
demand for hot water EXCEEDS the units limitations. If water flow is within the units limitations, you will not get a voltage reading for
diagnostics.
Water volume control
valve, located to right of
blower motor, connected
directly to water inlet.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 77
77
While water is flowing & unit
is attempting to ignite; check
DC volts across White &
Black wires at connector C:
8 – 16 DC Volts
YES
Check connector C.
Operate unit again. IF code
65 appears:
Replace control board.
NO
Turn Power OFF then ON.
While water is flowing & unit
is attempting to ignite; check DC volts across Red & Black
wires at connector C:
8 – 16 DC Volts
YES
Check connector C.
Operate unit again. IF code
65 appears:
Replace control board.
NO
Turn Power OFF then ON.
While water is flowing & unit
is attempting to ignite; check
DC volts across Green &
Black wires at connector C:
4 – 6 DC Volts
YES
Check connector C.
Operate unit again. IF code
65 appears:
Replace control board.
NO
Operate unit. IF 65 – Error
Code appears:
Replace water volume
control valve..
CAUTION: Hot water temperatures above
120 will scald. Return to original setting
once test is complete.
If voltages are NOT
registering, ATTEMPT to
activate water volume control
valve by turning remote control
to highest temperature
setting & opening all
hot water fixtures.
78 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
78
Turn Power OFF. Remove
and reinsert connector B.
Remove control board
bracket (How to Remove:
Section 1). Visually inspect
water bypass valve for loose
or damaged connections.
Reassemble & operate unit.
Does 66 – Error Code
appear?
YES
Unit had a loose connection. Unit appears to be operating
OK
NO
Turn remote control OFF;
unplug unit. Plug unit in.
Turn Power ON. Operate
unit. Check DC volts across
Red & Black wires at
connector B:
8 – 16 DC Volts
YES
Check connector B.
Operate unit again.
IF 66 – Error Code appears:
Replace control board.
NO
Operate unit.
IF 66 – Error Code appears:
Replace water bypass valve.
IMPORTANT: Prior to measuring voltage, turn remote
temperature down to 102 degrees. Water bypass valve will
activate at this time.
66 – Error Code
Explanation: Water by-pass valve malfunction.
Diagnostic Checks:
Water bypass valve
For water bypass valve
location: Refer to 65 -
Error Code diagram. Water bypass valve is located right of blower
motor; connected directly
to bottom of two copper
pipes.
Connector Location
On Page 14
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 79
79
Explanation: Gas control valve malfunction (inlet solenoid).
Diagnostic Checks:
Gas control valve
71 – Error Code
Connector Location
On Page 14
Turn Power OFF. Remove
and reinsert connector K.
Operate unit.
Does 71 – Error Code
appear?
YES
Unit had a loose connection. Unit appears to be operating
OK
NO
While unit is attempting to
ignite; check DC voltage
across Yellow & black wires
on connector K:
90 – 120 DC Volts
YES
Check connector K.
Operate unit again.
IF 71 – Error Code appears:
Replace control board.
NO
Operate unit.
IF 71 – Error Code appears:
Replace gas control valve.
GAS VALVE
80 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
80
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 81
81
(See maintenance mode instructions on page 21)
72 – Error Code
Explanation: Flame rod(s) malfunction. Flame rod(s)
is detecting the presence of flame BEFORE igniter is activated.
Diagnostic Checks:
Flame rod(s)  Gas control valve
Turn Power OFF.
Remove and reinsert connector M, T,
and terminal on flame rod(s).
Turn Power ON and operate unit.
Did 72 – Error Code appear?
Indoor models – 2 flame rods (Connectors M& T).
Outdoor models – 1 flame rod (Connector M).
Access maintenance mode to
check flame rod status.
Locate sight glass.
Continue to diagnostic chart
on next page.
YES
Unit had a loose connection
or foreign debris that is no
longer present.
Unit appears to be operating
OK.
NO
Connector Location
On Page 14
SIGHT GLASS
FLAME ROD(S)
82 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
82
Turn Power OFF.
Unplug unit and plug back in.
Turn Power ON.
While viewing through sight
glass, turn on water flow to
begin ignition sequence.
Is flame visible before igniter
sparks?
YES
Follow maintenance mode
instructions at bottom of
page & continue to
diagnostics on next page.
NO
Visually inspect burner
chamber through sight glass
for foreign debris.
YES
Operate unit again. IF 72 – Error Code appears & flame IS visible before igniter
rod sparks:
Replace gas control valve.
NO
Remove & clean burner
assembly.
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done
immediately after turning the unit ON. IF Flame Rod(s) is
detecting flame, maintenance mode will display:
Indoor Units: 05
Outdoor Units: 01
Outdoor: 1 flame rod
Indoor: 2 flame rods
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 83
83
Operate unit.
Does 0Y status in
maintenance mode indicate
presence of flame BEFORE
igniter rod sparks?
YES
Unit appears to be OK.
Operate unit.
IF 72 – Error Code appears:
Replace control board.
NO
Turn Power OFF.
Unplug unit. Disconnect
wires at flame rod(s). Plug
unit in.
Turn Power ON.
Operate unit.
Does 0Y status in
maintenance mode indicate
presence of flame BEFORE
igniter rod sparks?
YES
Clean flame rod(s).
IF 72 – Error Code appears
after cleaning flame rod(s):
Replace flame rod(s).
NO
Remove & clean burner
assembly.
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done
immediately after turning the unit ON. IF Flame Rod(s) is
detecting flame, maintenance mode will display:
Indoor Units: 05
Outdoor Units: 01
84 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
84
76 – Error Code
Explanation: Communication fault with remote
control. Remote control is not communicating with control board.
Diagnostic Checks:
Remote control
Visually inspect remote
control wiring for damaged or
loose connections.
Is wiring OK?
YES
Tighten loose connections or
replace damaged wiring.
NO
Unplug unit and remove
remote control wires from
bottom of unit. Plug unit in
and operate.
Did unit go to main burner?
YES
Replace control board.
NO
Turn Power OFF then ON.
While water is flowing & unit
is attempting to ignite; check
DC volts across Green &
Black wires at connector C:
4 – 6 DC Volts
YES
Replace remote control
wiring.
NO
Replace remote control
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 85
85
Explanation: Blower motor current fault.
Diagnostic Checks:
Blower motor
79 – Error Code
Turn Power OFF.
Remove control board bracket (How to Remove: Section 1).
Remove blower motor (How to Remove: Section 2).
Clean blower motor and blower motor housing.
Reassemble & operate unit.
Does 79 – Error Code appear?
Locate MIN & MAX buttons
on upper right- hand corner
of control board.
Continue diagnostics on next
page
YES
Unit had a loose connection.
Unit appears to be operating
OK.
NO
MIN & MAX
BUTTONS
86 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
86
Blower Motor Diagnostics:
Indoor Models ONLY
Upper Right-Hand Corner of Control Board
Test DC voltage across
Black and Red wires
on connector G:
144 – 192 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & White wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Black & Blue wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace blower motor.
NO
Control board and blower
motor are OK.
CHECK GAS SUPPLY &
VENTING.
IMPORTANT: While performing
voltage checks, DO NOT touch
multimeter leads across BLUE &
White wires. Damage may occur to
blower motor and control board.
Connector Location
On Page 14
MIN
MAX
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 87
87
Blower Motor Diagnostics:
Outdoor Models ONLY
Upper-Right Hand Corner of Control Board
Test DC voltage across
Blue and White wires
on connector G:
144 – 192 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Red wires
on connector G:
12 – 18 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace control board.
NO
Hold down MAX button.
Test DC voltage across
Blue & Yellow wires
on connector G:
4 – 10 DC Volts
YES
Remove & reinsert G.
Operate unit again.
IF Code 79 appears:
Replace blower motor.
NO
Operate Unite.
If 79 – Error Code appears:
Replace control board.
IMPORTANT: While performing
voltage checks, DO NOT touch
multimeter leads across YELLOW &
RED wires. Damage may occur to
blower motor and control board.
Connector Location
On Page 14
MIN
MAX
88 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
88
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 89
89
(See maintenance mode instructions on page 21)
80 – Error Code
Explanation: Gas control valve malfunction. Unit
detected the presence of flame when demand for hot water terminated & the unit turned OFF.
Diagnostic Checks:
Flame rod(s)  Gas control valve
Turn Power OFF.
Remove and reinsert connector M, T,
and terminal on flame rod(s).
Turn Power ON. Operate unit.
Did 80 – Error Code appear?
Indoor models – 2 flame rods (Connectors M& T).
Outdoor models – 1 flame rod (Connector M).
Access maintenance mode
to check flame rod status.
Locate sight glass.
Continue to diagnostic chart
on next page
YES
Unit had a loose connection
or foreign debris that is no
longer present.
Thermistors appear to be
OK.
NO
Connector Location
On Page 14
SIGHT GLASS
FLAME ROD(S)
90 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
90
While viewing burner
chamber through sight glass:
In 10 second intervals, cycle
unit 3 times -
ON-OFF; ON-OFF; ON-OFF
Determine if flame is visible
when OFF.
YES
Follow maintenance mode
instructions at bottom of
page & continue to
diagnostics on next page.
NO
Visually inspect burner
chamber through sight glass
for foreign debris.
YES
Operate unit.
IF 80 – Error Code appears & flame IS visible while unit has
been OFF longer than 5
seconds:
Replace gas control valve.
NO
Remove and clean
burner assembly
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done
immediately after turning the unit OFF. IF flame rod(s) is
detecting flame, maintenance mode will display:
Indoor Units: 05
Outdoor Units: 01
Outdoor: 1 flame rod
Indoor: 2 flame rods
Open a hot water fixture
and use shut-off
valve at the unit to
cycle unit On-Off.
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 91
91
In 10 second intervals; cycle
unit 3 times by turning unit:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in
maintenance mode indicate
presence of flame after 5
seconds?
YES
Unit appears to be OK.
Operate unit.
IF 80 – Error Code appears:
Replace control board.
NO
Disconnect wires at flame
rod(s). While viewing burner
chamber through sight glass:
In 10 second intervals; cycle
unit 3 times:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in
maintenance mode indicate
presence of flame after 5
seconds?
YES
Clean flame rod(s).
IF 80 – Error Code appears
after cleaning flame rod(s):
Replace flame rod(s).
NO
Remove & clean burner
assembly.
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode ‘0Y’ readings should be done immediately
after turning the unit OFF.
IF Flame Rod(s) is detecting flame, maintenance mode will
display:
Indoor Units: 05
Outdoor Units: 01
92 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
92
82 – Error Code
Explanation: Control board program chip
malfunction.
Diagnostic Checks:
Program chip
Control Board
Connector Location
On Page 14
Turn Power OFF.
Verify correct program chip is installed.
Remove and reinsert
program chip.
Operate unit.
IF 82 – Error Code appears:
Replace program chip.
YES
Insert correct
program chip.
NO
PROGRAM
CHIP
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 93
93
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
94 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
94
90 & 99 – Error Code
Explanation: Unit was operated prior to vent
installation OR unit detected blockage in the venting during pre-purge OR post-purge cycle.
90 Error Code will occur BEFORE unit goes to ignition.
99 – Error Code will occur AFTER unit shuts down. Unit must be reset by performing reset procedure
on page 26.
Diagnostic Checks:
Perform reset procedure on page 26 VENTING – refer to pages 8-11 or refer to
Use & Care manual for installation instructions:
1. Approved vent materials
2. Approved terminations
3. Approved vent lengths
4. Location and distance between venting
(recirculation of exhaust)
5. Blocked venting
6. Venting not sealed properly
(recirculation of exhaust)
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 95
95
92 & 93 – Error Code
Explanation: High-Efficiency (condensing) Units ONLY: 92 – Error Code: This is a warning code and unit will
continue to operate but will eventually shut down.
REPLACE NEUTRALIZER ASAP
Neutralizer rocks made from Calcium Carbonate (CACO3) Neutralizer kit may be ordered through Rheem/Ruud Supplier.
93 – Error Code: Unit will NOT operate until the Neutralizer is replaced.
REPLACE NEUTRALIZER IMMEDIATELY
Neutralizer rocks made from Calcium Carbonate (CACO3) Neutralizer kit may be ordered through Rheem/Ruud Supplier.
UNIT MUST BE RESET AFTER NEUTRALIZER IS REPLACED
With remote control ON and no water is running through unit: Push MIN & MAX buttons at same time – CL is displayed on remote control. Push MIN & MAX buttons again for more than 5 seconds – CL disappears.
MIN & MAX
BUTTONS
NEUTRAILER
96 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
96
NOTES: _________________________
_________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ _________________________
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 97
97
HOW TO REMOVE COMPONENTS
OUTDOOR UNIT
INDOOR UNIT
98 | P a g e S V C 8 2 0 ( P ) P o c k e t M a n u a l
98
1
Remove ‘TOP’ center screw from
control board mounting bracket.
Section 1: Control Board Bracket
ALWAYS TURN OFF Power, Water & Gas
3 2 1
S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e 99
99
2
Remove connectors: ‘M’; ‘T’; & ‘G’.
Condensing ONLY: ALSO remove connector ‘P’.
3
*Remove 2 control board bracket screws located on bottom, outer shell of unit. *Pull control board bracket out of way to access components.
M
T
P
G
Loading...