Rheem (-)GRC-04EMAES, (-)GRC-06EMAES, (-)GRC-07EMAES, (-)GRC-07ERBGS, (-)GRC-09EZAJS Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
FOR UPFLOW & DOWNFLOW/HORIZONTAL HIGH EFFICIENCY CONDENSING GAS FURNACES
(-)GRC/(-)GTC SERIES
U.L. recognized fuel gas and CO (carbon monoxide) detectors are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
92-24161-88-00
REFER TO INSTALLATION INSTRUCTIONS
GAS SUPPLY
Adequate pipesize Correct supply pressure (during furnace operation) Manifold pressure No gas leaks L.P. Kit Number (if applicable)
ELECTRICAL
115 V.A.C. supply (Single Circuit) Polarity observed Furnace properly grounded Adequate wire size
FURNACE INSTALLATION
Adequate clearance to combustibles Adequate clearance for service (at front)
DUCT STATIC PRESSURE
in. w.c. on heating speed in. w.c. on cooling speed Air temperature rise
TERMINATIONS – DIRECT VENT
VERTICAL
Intake – 12" min. above roof/snow level Correct relationship – exhaust to intake
HORIZONTAL/VERTICAL – CONCENTRIC (RXGY-E03A)
Intake – 12" min. above roof/snow level Intake “Y” rotated above center Exhaust sloped toward furnace
HORIZONTAL – STANDARD (RXGY-D02, -D02A, -D03, D03A)
Correct relationship – exhaust to intake 12" min. above grade/snow level
HORIZONTAL – ALTERNATE (RXGY-D02, -D02A, -D03, ­D03A)
Correct relationship – exhaust to intake Above anticipated snow level
VENTING – NON-DIRECT VENT
in. diameter – exhaust pipe ft. of pipe – exhaust
CONDENSATE LINE
Trap filled with water Vented Sloped toward drain Condensate drain line hoses connected
and clamped Freeze protection (if necessary)
VENTING – DIRECT VENT
in. diameter – intake pipe in. diameter – exhaust pipe ft. of pipe – intake air no. of elbows – intake air ft. of pipe – exhaust pipe no. of elbows – exhaust pipe Exhaust vent temp.
no. of elbows
TERMINATION – NON-DIRECT VENT
VERTICAL
12" min. above roof/snow level
HORIZONTAL – STANDARD
12" min. above grade/snow level
HORIZONTAL – ALTERNATE
Above anticipated snow level Model Number Serial # Date of Installation
2
SAFETY INFORMATION
SAFETY INFORMATION
WARNING
!
USE ONLY WITH TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.
WARNING
!
PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE FURNACE SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS FURNACE TO AN APPROVED VENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.
WARNING
!
DO NOT OPERATE THE SYSTEM FOR EXTENDED PERIODS WITHOUT FILTERS. A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY CIRCULATED DUST PARTICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAMAGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
WARNING
!
ALWAYS INSTALL FURNACE TO OPERATE WITHIN THE FURNACE'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
WARNING
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO AREAS OUTSIDE THE SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE FURNACE.
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR. THIS IS TO REDUCE THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
• PROPER VENT INSTALLATION;
• FURNACE OPERATING UNDER THERMOSTATIC CONTROL;
• RETURN AIR DUCT SEALED TO THE FURNACE;
• AIR FILTERS IN PLACE;
• SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKING;
• MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION;
• RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55°F (13°C) AND 80°F (27°C); AND
• CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERATURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS.
3
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGHLEAKING DUCTS AND UNBALANCEDDUCT SYSTEMSCAUSING PERSONAL INJURY OR DEATH (SEE FIGURE
3).
• IF AIR-MOVINGEQUIPMENT OR DUCTWORK IS LOCATED IN GARAGESOR OFF-GARAGE STORAGEAREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVINGEQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNINGAPPLIANCES SUCH AS WATER HEATERS OR BOILERS- ALL JOINTS,SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI­TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS OR GAS FURNACES USED WITH EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING.
SAFETY INFORMATION
IMPORTANT!
THE COMMONWEALTH OF MASSACHUSETTSREQUIRES COMPLIANCE WITH REGULATION 248 CMR 4.00 AND 5.00 FOR INSTALLATION OF THROUGH-THE­WALL VENTED GAS APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealthand where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time
of installation of the side wall horizontal ventedgas fueled equipment,the instal­ling plumberor gasfitter shall observe that a hard wiredcarbonmonoxidedetector with an alarm and battery back-upis installed on the floor level where the gas equipment is to be installed.In addition, the installingplumber or gasfittershall observethata battery operated or hard wiredcarbonmonoxidedetector with an alarmis installed on each additional level of the dwelling, building or structure servedby the side wall horizontalvented gas fueled equipment.It shall be the responsibilityof the property owner to securethe servicesof qualified licensed professionalsfor the installationof hard wiredcarbonmonoxidedetectors.
a. In the event that the side wall horizon­tally vented gas fueled equipment is in­stalled in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above require­ments; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide
detector is required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3.SIGNAGE. A metal or plastic identifica­tion plate shall be permanently mounted to the exterior of the building at a mini­mum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local
gas inspector of the side wall horizontallyvented gas fueled equipment shall not approve the installationunless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR
5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall hori­zontally vented gas fueled equipment installed in a room or structure sepa­rate from the dwelling, building or structure used in whole or in part for residentialpurposes.
(c) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM PROVIDED. When the manufacturerof Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installationof the equipment and the venting system shall include:
1. Detailed instructions for the instal­lation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIRE­MENTS – GAS EQUIPMENT VENT­ING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identified “special venting systems”, the following requirementsshall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installationinstructions;and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installationinstructions.
(e) A copy of installationinstructions for all Product Approved side wall horizontallyvented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
4
IMPORTANT: All manufacturer products meet current Federal OSHA Guidelines for safety. California Proposition65 warnings are required for certain products, which are not covered by the OSHA standards.
California'sProposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene More details are available at the
Websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov California'sOEHHA (Office of EnvironmentalHealth Hazard Assessment),at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and maintained.
and the State of
CONTENTS
Safety Precautions...................................................................................................1
InstallationCheck List ..............................................................................................2
Safety Information....................................................................................................3
General Information..................................................................................................6
Location Requirements and Considerations............................................................8
Ducting...................................................................................................................13
Venting and Combustion Air Piping.......................................................................14
Combustion and Ventilation Air..............................................................................16
Vent Pipe Installation..............................................................................................19
Condensate Drain/Neutralizer................................................................................32
Converting Downflow to Horizontal........................................................................34
Gas Supply and Piping...........................................................................................36
High Altitude Instructions........................................................................................38
Electrical Wiring......................................................................................................41
Accessories............................................................................................................42
Furnace Twinning...................................................................................................42
Start-Up Procedures...............................................................................................46
Air Flow...................................................................................................................48
Maintenance...........................................................................................................51
Troubleshooting......................................................................................................54
Wiring Diagrams................................................................................................55-56
IMPORTANT: TO INSURE PROPER INSTALLATIONAND OPERATION OF THIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TO ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIR THIS PRODUCT. UPON UNPACKING OF THE FURNACE, INSPECT ALL PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.
5
GENERAL INFORMATION
The (-)GRC and (-)GTC series furnaces are design-certifiedby CSA for use with naturaland propane gasesas follows:
1. As non-direct vent central forced air furnaces taking combustion air from the installationarea or using air ducted from the outside.
2. As direct vent central forced air furnaces with all combustion air supplied directly to the furnace burners through a special air intake system outlined in these instructions.
Install this furnace in accordance with the American National Standard Z223.1 – latest edition entitled “National Fuel Gas Code” (NFPA54) and requirements or codes of the local utilities or other authorities having jurisdiction. This is available from the following:
National Fire Protection
Association,Inc. BatterymarchPark Quincy, MA 02269
CSA-INTERNATIONAL 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
Install units in Canada in accordance with CSA-B149, local installation codes and authorities having jurisdiction.CSA-B149 is available from:
CSA-INTERNATIONAL 178 Rexdale Blvd. Toronto, Ontario Canada M9W, 1R3
FIGURE 1
UPFLOW FURNACE
FIGURE 2
DOWNFLOW/HORIZONTAL FURNACE
ITEM ITEM
NO. PART NAME NO. PART NAME
1 CONDENSATE TRAP 13 TOP PLATE 2 DOOR SWITCH 14 BURNER 3 JUNCTION BOX 15 IGNITER (HSI ONLY) 4 TRANSFORMER 16 COMBUSTION AIR INLET 5 BLOCKED DRAIN PRESSURE SWITCH 17 GAS VALVE 6 MAIN PRESSURE SWITCH 18 INDUCED DRAFT BLOWER 7 EXHAUST TRANSITION 19 CAPACITOR 8 CONNECTOR 20 LOW VOLTAGE (THERMOSTAT)
9 OUTLET AIR PIPE TERMINAL 10 SHIPPING PLUG 21 CONTROL MOUNTING PLATE 11 FLAME SENSOR 22 BLOWER 12 OVERTEMPERATURE SWITCH
6
I409 I409
ITEM ITEM
NO. PART NAME NO. PART NAME
1 INDUCED DRAFT BLOWER 14 LOW VOLTAGE TERMINAL (THERMOSTAT) 2 CAPACITOR 15 TRANSFORMER 3 INLET AIR CHASE 16 PRESSURE SWITCH 4 DOOR SWITCH 17 OUTLET AIR PIPE 5 JUNCTION BOX 18 GAS VALVE 6 INLET PIPE CONNECTOR 19 CONNECTOR 7 TOP PLATE 20 EXHAUST TRANSITION 8 CONTROL MOUNTING PLATE 21 CONDENSATE TRAP
9 AUXILIARY LIMIT 22 IGNITER (HSI) 10 SHIPPING PLUG 23 MANIFOLD 11 EXHAUST CONNECTION 24 OVERTEMPERATURE SWITCH 12 BLOWER 25 ROLLOUT SWITCH 13 EXHAUST PIPE EXTENSION 26 FLAME SENSOR
27 BURNER
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and/or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE
3).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
NOTICE
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDI­TIONS AND ARE NOT COVERED BY THE UNIT WARRANTY.
NOTICE
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS OR GAS FURNACES USED WITH EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING.
FIGURE 3
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment
matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is required to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in a level position to ensure proper condensate drainage. Make sure unit is level in both directions within 1/8”.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from:
“National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
7
LOCATION REQUIREMENTS AND CONSIDERATIONS
GENERAL INFORMATION
WARNING
!
DO NOT USE THIS FURNACE DURING CONSTRUCTION IF AIR LADEN CORROSIVE COMPOUNDS ARE PRESENT SUCH AS CHLORINE AND FLUORINE. OTHERWISE, PROVISIONS MUST BE TAKEN TO PROVIDE CLEAN, UNCONTAMINATED COMBUSTION AND VENTILATION AIR TO THE FURNACE. FURNACE COMBUSTION AND VENTILATION AIR CONTAMINATED WITH THESE COMPOUNDS FORMS ACIDS DURING COMBUSTION WHICH CORRODES THE HEAT EXCHANGER AND COMPONENT PARTS. SOME OF THESE CONTAMINANTS ARE FOUND IN, BUT NOT LIMITED TO, PANELING, DRY WALL, ADHESIVES, PAINTS, STAINES, VARNISHES, SEALERS, AND MASONRY CLEANING MATERIALS.
WARNING
!
DO NOT INSTALL THIS FURNACE
IN A MOBILE HOME!! This furnace
is not approved for installation in a mobile home. Doing so could cause
FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES ABOVE THE FLOOR. THIS IS TO PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. IMPORTANT: If installing the unit over a finished ceiling or living area, be certain to install an auxiliary condensate drain pan under the entire unit. This auxiliary drain pan should extend under any evaporator coil installed with the furnace and the open portion of the condensate drain assembly. See “CondensateDrain/Neutralizer” section for more details.
2. IMPORTANT: If using a cooling evaporator coil with this furnace:
a. be sure the air passes over
the heat exchanger before passing over the cooling coil. The cooled air passing over the warm ambient air inside the heat exchanger tubes can cause condensationinside the tubes resulting in corrosion and eventual failure.
b. install a parallel duct system
to divert all the air from the furnace allowing it to pass over the cooling coil only. Use dampers or other means to prevent chilled air from passing over the heat exchanger.
If these are manual dampers, they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position.
FIGURE 4
HORIZONTAL FURNACE W/HEAT TAPE ON CONDENSATE TRAP
DRAIN PIPE
3. IMPORTANT: Install the furnace level. If it is not level, condensate cannot drain properly, possibly causing furnace shut down.
NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces.Provisions must be made to prevent freezing of condensate.
4.
!
If this furnace is installed in a garage, attic and/or any unconditioned space, install a self-regulating heat tape around the condensate trap and along the entire length of the condensate drain in the unconditioned space. See Figure 4.
When the condensing horizontal gas furnace is installed in an unconditionedspace where the temperaturewould be capable of reaching close to or below 32°F (0°C). a self-regulating heat tape is required on the condensate drain, along with an insulation wrap. The heat tape should meet the following requirements:
a. The heat tape must be UL
b. The heat tape must be
CAUTION
listed.
installed per the manufacturer’sinstructionsfor the entire length of drain pipe in the unconditioned space.
HEAT TAPE
TRAP
I526
8
8
c. The heat tape should be rated
at 5 or 6 watts per foot at 120V.
IMPORTANT: Support this unit when installed. Since this furnace is suitable for attic or crawl space installation,it may be installed on combustiblewood flooring or by using support brackets. See
Figure 5.
5. IMPORTANT: If installing in a
utility room, be sure the door is wide enough to:
a. allow the largest part of the
furnace to pass; or
b. allow any other appliance
(such as a water heater) to pass.
6. IMPORTANT: This furnace is not approved or recommended for installationon its back, with access doors facing upwards.
FIGURE 5
HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS
GAS PIPE
TRAP
INTAKE VENT
ELECTRICAL CONDUIT
EXHAUST FAN
I522
CLEARANCE ­ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the tables under Figures 6, 7, and 8 are certified by CSA-International for the clearances to combustiblematerials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches is recommended in front of all furnaces.
NOTE: Userecommended24” clearance if accessibilityclearances are greater than fire protection clearances.
WARNING
!
UPFLOW AND HORIZONTAL FURNACES ARE DESIGN­CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. NOTE, HOWEVER, THAT FURNACES MUST NOT BE INSTALLED DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Upflow furnaces are shipped with a bottom closure panel installed. When bottom return air is used, remove the panel by removing the two screws attaching the panel to the front base angle. See Figure 51.
SITE SELECTION
1. Select a site in the building near the center of the proposed, or existing, duct system.
2. Give consideration to the vent system piping when selecting the furnace location. Be sure the venting system can get from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas piping.
4. Locate the furnace to maintain proper clearance to combustibles as shown in the following tables.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES. DOING SO CAN CRACK THE HEAT EXCHANGER ASSEMBLY AND CAUSE CO2 TO BE RELEASED INTO THE ENVIRONMENT, WHICH CAN RESULT IN PERSONAL INJURY OR DEATH.
WARNING
!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES.
9
FIGURE 6
CLEARANCE TO COMBUSTIBLES, UPFLOW UNITS
WGTS
BACK TOP FRONT VENT
SIDE SIDE
LEFT RIGHT SHIP
32 0 0 0 1 2* 0 111
32 0 0 0 1 2* 0 117
32 0 0 0 1 2* 0 124
8 0 0 0 1 2* 0 137
32 0 0 0 1 2* 0 148
32 0 0 0 1 2* 0 152
3
9
25
25
25
8 2 15 13
8 2 15 13
8 2 15 13
5
5
5
9
2 17
2 17
2 17
1
1
1
8 2 18
8 2 18
16 2 18
1
1
3
2 DIA.
GAS CONNECTION
UPFLOW MODELS MINIMUM CLEARANCE (IN.)
32 15
32 15
32 15
32 19
32 19
11
11
11
2 16
2 16
2 16
1
1
1
04 17
06 17
MODEL A B C D E F
07 17
32 19
27
27
27
07 21 19
09 21 19
10 21 19
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIRFLOW
AIR
8
3
27
RETURN
2 DIA.
AIR
SUPPLY
16
7
26
GAS CONNECTION
10
I392
FIGURE 7
CLEARANCE TO COMBUSTIBLES, DOWNFLOW UNITS
WGTS
BACK TOP FRONT VENT
SIDE SIDE
LEFT RIGHT SHIP
8 0 0 0 1 2* 0 111
8 0 0 0 1 2* 0 117
8 0 0 0 1 2* 0 137
8 0 0 0 1 2* 0 148
7
7
8 13
8 13
5
5
8 2 16
8 2 16
5
5
8 0 0 0 1 2* 0 160
3
3
7
8 17
8 17
8 20
1
1
5
8 2 23
16 2 20
16 2 20
5
3
3
16
13
25
2 DIA.
ALT. GAS
CONNECTION
8
3
4
DOWNFLOW MODELS MINIMUM CLEARANCE (IN.)
32 15
32 15
32 19
32 19
27
07 21 19
11
11
1
09 21 19
SUPPLY
32 22
2 23
10 24
*A service clearance of at least 24 inches is recommended in front of all furnaces.
AIR
AIRFLOW
11
11
2 16
2 16
1
1
04 17
06 17
MODEL A B C D E F
AIR
RETURN
2 DIA.
GAS CONNECTION
NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.
I393
11
FIGURE 8
CLEARANCE TO COMBUSTIBLES, HORIZONTAL UNITS
WGTS
BACK TOP FRONT VENT
SIDE SIDE
LEFT RIGHT SHIP
8 0 0 0 1 2* 0 111
8 0 0 0 1 2* 0 117
8 0 0 0 1 2* 0 137
8 0 0 0 1 2* 0 148
7
7
8 13
8 13
5
5
8 2 16
8 2 16
5
5
8 0 0 0 1 2* 0 160
3
3
5
8 17
8 17
8 20
1
1
5
8 2 23
16 2 20
16 2 20
5
3
3
IMPORTANT: This furnace is not approved or recommended for
installation on its back, with access doors facing upwards.
DOWNFLOW MODELS MINIMUM CLEARANCE (IN.)
32 15
32 15
32 19
32 19
11
11
2 16
2 16
1
1
04 17
06 17
MODEL A B C D E F
32 22
27
27
11
2 23
1
07 21 19
09 21 19
10 24
*A service clearance of at least 24 inches is recommended in front of all furnaces.
16
13
25
2 DIA.
GAS
CONNECTION
2 DIA.
ALT. GAS
CONNECTION
8
3
4
12
12
I520
DUCTING
JACKET
DRILL (2) 3/16" DIA. HOLES
8.000
4.875
1.531
Proper air flow is required for the correct operation of this furnace. Too little air flow can cause erratic operation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling if summer air conditioningis used.
Size the ducts according to acceptable industry standards and methods. The total static pressure drop of the air distribution system should not exceed 0.5" w.c.
NOTE: Return air grilles and warm air registers must not be obstructed
WARNING
!
NEVER ALLOW THE PRODUCTS OF COMBUSTION FROM THE FLUE TO ENTER THE RETURN AIR DUCTWORK OR THE CIRCULATED AIR SUPPLY. ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO THE FURNACE WITH SHEET METAL SCREWS; AND JOINTS, TAPED. ALL OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS AND SEALED AIRTIGHT. WHEN AN UPFLOW FURNACE IS MOUNTED ON A PLATFORM WITH RETURN THROUGH THE BOTTOM, IT MUST BE SEALED AIRTIGHT BETWEEN THE FURNACE AND THE RETURN AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT OF THE FURNACE WITHOUT SAGGING, CRACKS, OR GAPS, AROUND THE BASE, PROVIDING A SEAL BETWEEN THE SUPPORT AND THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCULATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR SUPPLY DUCTWORK TO OR FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY OR PROPERTY DAMAGE.
IMPORTANT: Some high efficiency
filters have a greater than normal resistance to air flow. This can adversely affect furnace operation. BE SURE TO CHECK AIR FLOW.
IMPORTANT: When using outside air, design and adjust the system to maintain a return air temperature ABOVE 50° F during the heating season.
UPFLOW UNITS
1. Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2. Open the return air compartment.
WARNING
!
UPFLOW FURNACE: A SOLID METAL BASE PLATE MUST BE INSTALLED IN THE FURNACE BOTTOM WHEN USING SIDE RETURN. FAILURE TO INSTALL A BASE PLATE COULD CAUSE THE PRODUCTS OF COMBUSTION TO CIRCULATE INTO THE LIVING SPACE AND CREATE POTENTIAL­LY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH.
a. Cut an opening in the side.
The opening should be cut the full width of the knockouts on the unit. See Figure 9.
NOTE: Where the maximum air flow is 1800 CFM or more, both sides or the bottom must be used for return air.
3. Connect the return duct or return air cabinet to the unit. Make the connection air tight to prevent entraining combustion gases from an adjacent fuel-burning appliance.
4. Be sure to have adequate
space for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
NOTE: DO NOT use a rear air return.
FIGURE 9
CUTOUT AND DRILL INFORMATION
5. If summer air conditioning is desired, position the indoor coil on the top of the unit. Insure that no air can bypass this coil.
6. Connect the supply air plenum to the furnace plenum opening.
IMPORTANT: If a flexible duct connector must be used, it
be rated for a minimum
MUST temperatureof 250°F continuous.
.
DOWNFLOW UNITS
1. Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2. If summer air conditioning is desired, position the indoor coil on the bottom of the unit. Insure that no air can bypass this coil.
3. If installing on a combustible floor
and not using an air
conditioning plenum, install the
special non-combustible floor base. See Figure 10.
WARNING
!
THE DOWNFLOW FURNACE DESIGN IS CERTIFIED FOR INSTALLATION ON A NON­COMBUSTIBLE FLOOR. USE THE SPECIAL BASE SPECIFIED ON THE FURNACE CLEARANCE LABEL. FAILURE TO INSTALL THE SPECIAL BASE MAY RESULT IN FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THIS SPECIAL BASE IS SHIPPED FROM THE FACTORY AS AN ACCESSORY.
13
4. Connect the furnace to the supply air plenum.
5. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining combustion gases from an adjacent fuel-burning appliance.
6. Be sure to have adequate
space for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
HORIZONTAL UNIT
IMPORTANT: This furnace may only be installed so that when facing the front of the furnace, supply air is discharged on the left hand side.
1. Position the unit to minimize long runs or runs with many turns and elbows.
2. If summer air conditioning is desired, position the indoor coil on the left end of the unit. Insure that no air can bypass this coil.
3. Connect the furnace to the supply air plenum.
4. Connect the return air ducting to the return air opening at the right end of the unit. Make the connection air tight to prevent pulling combustion gases from an adjacent fuel-burning appliance.
FIGURE 10
COMBUSTIBLE FLOOR BASE
5. Be sure to have adequate
space for the unit filter.
NOTE: DO NOT take return air
from bathrooms, kitchens, furnace rooms, garages, utility or laundry rooms, or cold areas.
VENTING AND COMBUSTION AIR PIPING
VENTING AND COMBUSTION AIR PIPING*
GENERAL INFORMATION
WARNING
!
READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
This furnace removes both sensible and latent heat from the combustion flue gases. Removal of latent heat results in condensation of flue gas water vapor. This condensed water vapor drains from the secondary heat exchanger and out of the unit into a drain trap.
When installed as a non-direct vent furnace, only exhaust piping is required and inside combustion air may be used. Refer to section on “
COMBUSTION & VENTILATION AIR
FOR FURNACE INSTALLATIONS.” Direct vent installationsrequire a
dedicated combustion air and venting system. All air for combustion is taken from the outside atmosphere and all combustion products are discharged to the outdoors.
WARNING
!
IN CANADA, PRODUCTS CERTIFIEDFOR INSTALLATION
AND INTENDED TO BE VENTED WITHPLASTIC VENT SYSTEMS (PVC,CPVC) MUST USE VENT SYSTEMS THAT ARE CERTIFIED AND STAMPED TO THE STANDARD FOR TYPE BH GAS VENTING SYSTEMS, ULC S636.
THE COMPONENTSOF THE CERTIFIEDMATERIAL MUSTNOT BE INTERCHANGED WITH OTHER VENTSYSTEMS OR UNLISTED PIPE/FITTINGS.
PLASTIC COMPONENTS AND SPECIFIEDPRIMERS AND GLUES OF THE CERTIFIED SYSTEMMUST BE FROM A SINGLE SYSTEM MANUFACTURER AND NOT
U.S. PIPE & FITTING MATERIAL*
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891 Schedule 40 PVC (Fittings) D2466 SDR-21PVC (Pipe) D2241 SDR-26 PVC (Pipe) D2241 Schedule 40 ABS Cellular Core DWV (Pipe) F628 Schedule 40 ABS (Pipe) D1527 Schedule 40 ABS (Fittings) D2468 ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings) PVC-DWV (Drain Waste & Vent)
(Pipe & Fittings)
*Starting in 2007, Canada allows ULC-S636 PVC or CPVC only.
INTERMIXEDWITH OTHER SYSTEM MANUFACTURER’S PARTS.
NOTE:INLET AIR PIPING IS NOT CONSIDEREDTO BE A PARTOF THE “VENTING SYSTEM”. THE REQUIREMENT THAT VENT MATERIAL BE CERTIFIED TO ULC S636DOESNOTAPPLYTO INLET AIR PIPING.
The combustion air and vent pipe fittings must conform to American National Standards Institute (ANSI) and American Society for Testing Materials (ASTM) standards as shown below:
ASTM
SPECIFICATION
D2661
D2665
14
OVERTEMPERATURE SAFETY SWITCHES
Furnaces are equipped with safety switches in the control compartment to protect against overtemperature conditions caused by inadequate combustion air supply. The switches for the upflow and downflow models are located in the burner compartment.If a switch is tripped it must be manually reset.
WARNING
!
DO NOT JUMPER THESE DEVICES! IF ONE OF THESE SWITCHES SHOULD TRIP, A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER MUST BE CALLED TO CHECK AND/OR CORRECT FOR ADEQUATE COMBUSTION AIR SUPPLY. DO NOT RESET THE SWITCHES WITHOUT TAKING CORRECTIVE ACTION TO ASSURE THAT AN ADEQUATE SUPPLY OF COMBUSTION AIR IS MAINTAINED UNDER ALL CONDITIONS OF OPERATION. FAILURE TO DO SO CAN RESULT IN CARBON MONOXIDE POISONING OR DEATH. IF THIS UNIT IS MOUNTED IN A CLOSET, THE DOOR MUST BE CLOSED WHEN MAKING THIS CHECK.
REPLACE THESE SWITCHES ONLY WITH THE IDENTICAL REPLACEMENT PART.
EXISTING VENT SYSTEMS*
*In Canada see ULC-S636 requirements.
When the installation of this furnace replaces an existing furnace that is removed from a vent system serving other appliances, the vent system is likely to be too large to properly vent the remaining attached appliances.
The following steps should be followed with each appliance remaining connected to the original common vent system. Place the appliance to be tested in operation, while the other appliances remaining connected to the common vent system are not in operation. Test the operation of each appliance individuallyby the following method.
1. Permanently seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage, restriction,leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. If practical, close all building doors, windows and all doors between the space where the appliances remaining connected to the common venting system are located. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance that remains connected to the common venting system properly vents (when tested as outlined above), return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the common venting system must be resized. See vent tables in these instructions
Whenthefurnace is installed in the samespacewith other gas appliances suchas a water heater,besurethere is an adequatesupply of combustion andventilation air for theother appliances. Do not delete or reduce thecombustionairsupply required by theothergasappliancesinthisspace. SeeZ223.1, National Fuel Gas Code (NFPA54)for determiningthe combustionairrequirements for gas appliances. An unconfined space must haveat least50 cubicfeet(volume)for each1,000BTUH of thetotalinput of allappliancesin the space.Ifthe open spacecontaining the appliances is in a buildingwithtightconstruction (contemporaryconstruction),outside airmay stillbe required for the appliancestoburnandventproperly. Outside air openings shouldbe sized thesameas for a confined space.
JOINING PIPE AND FITTINGS
WARNING
!
PVC SOLVENT CEMENTS AND PRIMERS ARE HIGHLY FLAMMABLE. PROVIDE ADEQUATE VENTILATION AND DO NOT ASSEMBLE NEAR HEAT SOURCE OR AN OPEN FLAME. DO NOT SMOKE. AVOID SKIN OR EYE CONTACT. OBSERVE ALL CAUTIONS AND WARNINGS PRINTED ON MATERIAL CONTAINERS. FAILURE TO FOLLOW THESE GUIDELINES MAY RESULT IN FIRE, EXPLOSION OR ASPHYXIATION CAUSING PERSONAL INJURY OR DEATH.
All pipe, fittings,solventcement, primersand procedures must conform to American NationalStandard Institute and AmericanSociety for Testingand Materials(ANSI/ASTM) standards in the U.S.
Pipe and Fittings - ASTM-D1785, D2466, D2665, D2231, D2661 and F628.
PVC Primer and Solvent Cement ­ASTM-D2564
ABS Pipe and Fittings - Use ABS Primer and Solvent Cement D2235
Procedure for Cementing Joints ­ASTM-D2855
IMPORTANT: The plastic combustion air and venting components are of PVC. If using ABS piping, ensure that the solvent cement is compatible for joining PVC to ABS components or use a mechanical connection that can withstand the vent temperatures and are corrosion resistant.
CEMENTING JOINTS
Properly seal all joints in the PVC vent using the following materials and procedures.
PVC CLEANER-PRIMER AND PVC MEDIUM-BODY SOLVENT CEMENT
IMPORTANT: After cutting pipe,
remove all ragged edges and burrs. This is important to prevent reduction in pressure drop throughout the system.
1. Cut pipe end square. Chamfer edge of pipe. Clean fitting socket and pipe joint area of all dirt, grease and moisture.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer.Apply a liberal coat of primer to inside surface of socket and outside of pipe. Read instructions included with the primer for proper application.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting movement until it bottoms out.
NOTE: Cement must be fluid; if not, recoat.
4. Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity.
NOTE: Stir the solvent cement frequently while using. Use a natural bristle brush or the dauber supplied with the can. The proper brush size is one inch.
IMPORTANT: For Proper Installation
DO NOT use solvent cement that has become curdled, lumpy or thickened.
DO NOT thin. Observe shelf precautionsprinted on containers.
For application below 32°F, use only low-temperature-type solvent cement.
15
COMBUSTION AND VENTILATION AIR
NON-DIRECT FURNACE INSTALLATIONS
WARNING
!
THE FURNACE AND ANY OTHER FUEL-BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE PERSONAL INJURY OR DEATH FROM CARBON MONOXIDE POISONING.
Adequate facilities for providing air for combustion and ventilation must be provided in accordance with section
5.3, “Air for Combustion and Ventilation”of the National Fuel Gas Code, ANSI Z223.1 (latest edition) or applicable provisions for the local building codes, and not obstructed so as to prevent the flow of air to the furnace.
IMPORTANT: Air for combustion and ventilationmust not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation (but not limited to the following) will require OUTDOOR AIR for combustion,due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
Exposure to the following substances in the combustion air supply (but not limited to the following) will also require OUTDOOR AIR for combustion:
• Permanent wave solutions
• Chlorinatedwaxes and cleaners
• Chlorine-basedswimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloricacid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry curing and acid washing materials
Combustion air must be free of acid­forming chemicals such as sulphur, fluorine and chlorine. These elements are found in aerosol sprays, detergents,bleaches, cleaning solvents, air fresheners,paint and varnish removers, refrigerants and many other commercial and household products. When burned in a gas flame, vapors from these products form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they condense.
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY DAMAGE, CARBON MONOXIDE POISONING, PERSONAL INJURY OR DEATH.
Combustion air requirements are determined by whether the furnace is in an open (unconfined) area or in a confined space such as a closet or small room.
EXAMPLE 1: FURNACE LOCATED IN AN UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of the total input for all appliances in the space. Here are a few examples of the room sizes required for different inputs. The sizes are based on 8-foot ceilings.
BTUH Minimum Sq. Feet Typical Room Size
Input With 8' Ceiling With 8' Ceiling
45,000 281 14' x 20' OR 16' x 18'
60,000 375 15' x 25' OR 19' x 20'
75,000 469 15' x 31' OR 20' x 24'
90,000 563 20’ x 28’ OR 24’ x 24’
105,000 657 20' x 33' OR 26' x 25'
If the open space containing the furnace is in a building with tight construction,outside air may still be required for the furnace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
EXAMPLE 2: FURNACE LOCATED IN A CONFINED SPACE
A confined space (any space smaller than shown above as “unconfined”) must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and B. Size the openings by how they are connected to the heated area or to the outside, and by the input of all appliances in the space.
If confined space is within a building with tight construction, combustion air must be taken from outdoors or area freely communicating with the outdoors.
A. USING INDOOR AIR FOR
COMBUSTION IMPORTANT: Air should not be
taken from a heated space with a fireplace, exhaust fan or other device that may produce a negative pressure.
If combustion air is taken from the heated area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 BTUH of total input in the space. Here are some examples of typical openings required.
16
BTUH Free Area
Input Each Opening
45,000 100 square inches
60,000 100 square inches
75,000 100 square inches
90,000 100 square inches
105,000 105 square inches
FIGURE 11
AIR FROM HEATED SPACE
B. USING OUTDOOR AIR FOR
COMBUSTION IMPORTANT: Do not take air from
an attic space that is equipped with power ventilation.
The confined space must communicatewith the outdoors in accordance with Methods 1 or 2. The minimum dimension of air openings shall not be less than 3 inches. Where ducts are used, they shall be of the same cross­sectional area as the free area of the openings to which they connect.
Method 1 Two permanent openings, one located within 12 inches of the top and one located within 12 inches of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicatewith the outdoors.
a. Where directly communicating with the outdoors or where communicatingto the outdoors
GAS
WATER
HEATER
through vertical ducts as shown in Figure 12, each opening shall have a minimum free area of 1 square inch for each 4,000 BTUH of total appliance input rating in the enclosure.
BTUH Free Area Round Pipe
Input Each Opening Size
45,000 11.25 square inches 4"
60,000 15.00 square inches 5"
75,000 18.75 square inches 5"
90,000 22.50 square inches 6"
105,000 26.25 square inches 6"
FURNACE
NOTE: EACH OPENING SHALL HAVE A FREE AREA OF NOT LESS THAN ONE SQUARE INCH PER 1,000 BTU PER H0UR OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN THE ENCLOSURE, BUT NOT LESS THAN 100 SQUARE INCHES.
b. Where communicating with outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch for each 2,000 BTUH of total input rating of all equipment in the enclosure (Seee Figure 13).
Here are some typical sizes:
BTUH Free Area Round Pipe
Input Each Opening Size
45,000 22.50 square inches 6"
60,000 30.00 square inches 6"
75,000 37.50 square inches 7"
90,000 45.00 square inches 8"
105,000 52.50 square inches 8"
FIGURE 12
AIR FROM ATTIC/CRAWL SPACE
OUTLET AIR IN ATTIC MUST BE ABOVE INSULATION
1 SQ. INCH PER
4000 BTUH
OUTLET AIR
FURNACE
GAS
WATER
HEATER
1 SQ. INCH PER 4000 BTUH INLET AIR
GABLE
VENT
OPTIONAL 1 SQ. INCH PER 4000 BTUH INLET AIR
VENTILATED ATTIC GABLE OR SOFFIT VENTS
12" MAX.
FIGURE 13
OUTSIDE AIR USING A HORIZONTAL DUCT
OUTLET AIR 1 SQ. INCH
FURNACE
GAS
WATER
HEATER
INLET AIR 1 SQ. INCH
12"
MAX.
PER 2000 BTUH
PER 2000 BTUH
17
Method 2 (Not Shown) One permanent opening, located within 12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall directly communicatewith the outdoors or communicatethrough a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicatewith the outdoors, and shall have a minimum free area of:
a. 1 square inch for each 3,000 BTUH of the total input rating of all equipment located in the enclosure and
FIGURE 14
COMBUSTION AIR FITTING
BTUH Free Area Round Pipe
Input Each Opening Size
45,000 15.00 square inches 4"
60,000 16.67 square inches 5"
75,000 25.00 square inches 6"
90,000 30.00 square inches 6"
105,000 35.00 square inches 7"
b. Not less than the sum of the areas of all vent connectors in the confined space.
If unit is installed where there is an exhaust fan, sufficient ventilation must be provided to prevent the exhaust fan from creating a negative pressure.
Combustion air openings must not be restricted in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
CONNECTION TO FURNACE
IMPORTANT: When indoor combustion air is used, the inlet air opening at the furnace must be protected from accidental blockage. On upflow models, install a 90° elbow pointing downward in the side inlet air opening or a double elbow pointing downward in the top inlet air opening. On downflow/horizontal models, install a double elbow in the top inlet air opening. See Figure 14.
UPFLOW DOWNFLOW/HORIZONTAL
ATTACH DOUBLE ELBOW TO TOP INLET AIR OPENING OR 90° ELBOW TO SIDE INLET AIR OPENING TO PREVENT ACCIDENTAL BLOCKAGE OF INTAKE OPENING. PLUG OPENING NOT USED.
EXHAUST
2" PVC DOUBLE
2" PVC DOUBLE ELBOW
TOP OPTION
2" PVC ELBOW
SIDE OPTION
I337 I336
ELBOW*
COMBUSTION AIR
*NOTE: WHEN FURNACE IS INSTALLED IN A HORIZONTAL POSITION ONLY ONE 90° ELBOW IS REQUIRED. INSTALL THE ELBOW SO THE OPEN END IS POINTED DOWNWARD.
ATTACH DOUBLE ELBOW TO INTAKE AIR COLLAR AND SECURE WITH TWO SHEET METAL SCREWS TO PREVENT ACCIDENTAL BLOCKAGE OF INTAKE AIR OPENING.
EXHAUST
18
VENT PIPE INSTALLATION
NON-DIRECT VENT INSTALLATION
GUIDELINES
IMPORTANT: Failure to correctly follow all venting guidelines may result in erratic furnace operation, freeze-up of combustion air or exhaust air piping or sooting of the furnace.
All exhaust piping must be installed in compliance with Part 7, “Venting of Equipment,”of the latest edition of the National Fuel Gas Code NPFA54/ ANSI Z223.1-, local codes or ordinances and these instructions.
1. Vertical piping is preferred.
2. All horizontal piping must slope upward a minimum of per foot of run so that condensate drains toward the furnace.
3. All horizontal runs must be supported at least every 4 feet. No sags or dips are permitted.
4. IMPORTANT: Do not common vent with any other appliance. Do not install in the same chase or chimney with a metal or high temperatureplastic pipe from another gas or fuel-burning appliance unless the required minimum clearances to combustiblesare maintained between the PVC pipe and other pipes.
5. All vent runs through unconditionedspaces where below-freezing temperaturesare expected should be insulated with 1-in. thick, medium-density, foil-faced fiberglass. An equivalent “arm-a-flex” or
1
4 inch
TABLE 1
FOR NON-DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM INDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE PIPE
NUMBERS OF ELBOWS
FURNACE
INPUT
45,000
60,000
75,000
90,000
105,000
NOTES:
1. *N.A. - NOT APPLICABLE.
2. MAXIMUM OF 6 - 90 DEGREE ELBOWS MAY BE USED. DO NOT COUNT ELBOWS REQUIRED FOR ALTERNATE TERMINATION. USE ONLY MEDIUM OR LONG SWEEP ELBOWS.
3. A 45° DEGREE ELBOW IS CONSIDERED ONE ELBOW.
PIPE SIZE
2”
2”
3”
2”
GRC Only
3”
GRC Only
3”
GTC Only
3”
GRC Only
3”
GTC Only
3”
GRC Only
3”
GTC Only
TERMINATION
Standard 60 50
Alternate 50 40
Standard 50 40
Alternate 40 30
Standard 60 50
Alternate 50 40
Standard 25 N/A
Alternate N/A N/A
Standard 50 40
Alternate 40 30
Standard 50 40
Alternate N/A N/A
Standard 50 50
Alternate 50 40
Standard 50 40
Alternate N/A N/A
Standard 60 50
Alternate 50 40
Standard 50 40
Alternate N/A N/A
45° OR 90°
Medium / Long Radius ONLY
1-2 3-4
ELEVATED SINGLE PIPE ALTERNATE TEE TERMINATION
See Figure 16. The tee termination may be elevated up to 24 inches above the wall penetration if required for anticipated snow levels. Use 2 medium-radius, 2-in. PVC elbows and 2-in. PVC pipe, attaching the tee so it is 12 inches from the wall.
FIGURE 15
TEE TERMINAL – FOR STANDARD HORIZONTAL SINGLE PIPE INSTALLATION
VENT
12"
12" MIN. ABOVE
GRADE OR
SNOW LEVEL
FIGURE 16
ALTERNATE HORIZONTAL TERMINATION FOR NON-DIRECT VENT INSTALLATIONS
NOT APPLICABLE TO GTC-07 MODELS GTC-09 MODELS GTC-10 MODELS
OUTSIDE WALL
24"
MAX.
12"
FROM
PIPE SUPPORT STRAP
I198
19
“rub-a-tex”insulation may also be used as long as there is no heat tape appliedto the vent pipe. For horizontal runs where water may collect, wrap the vent pipe with self-regulating3 or 5 watt heat tape.The heat tape must be U.L. listed and installed per the manufacturer’sinstructions.
6. The minimum vent pipe length is 5 feet.
STANDARD INSTALLATIONS
The single-pipe system requires an exhaustpipeonly. Combustion air may be taken from the furnace installation area or ducted to the furnace area from the outside.
Size the exhaust pipe as specifiedin Table1. This tablelists the maximum allowable length in feet of the exhaust pipe that may be used for all furnace inputsas related to the number of elbowsrequired and the termination. (See shaded area.)
Vertical through-the-roof installations do not require a vent termination. Use 2-in. PVC pipe extending a minimumof 12 inchesabovethe anticipatedlevelof snow accumulation. See exhaust pipe requirements,Figure19. When 3-in. vent pipe is used from furnace to the roof,reduceit to 2 inchesbefore penetrating the roof. A maximum of 18 inchesof 2-in. pipe may be used below the roof. Maximum exposed vent length abovethe roof line is 30.
Horizontal vent terminationsrequire a 2-in.PVC tee positioned 12 inchesfrom the outside wall. See exhaust pipe requirements,Figure22. When 3-in. pipe is used from the furnace to the outsidewall,reduceit to 2 inches beforepenetrating the wall. A maximum of 18 inchesof 2-in. pipe may be used insidethe wall.
An alternatetermination may be used as shown in Figure 16 to clear anticipated snow levels. The tee may be raised up to 24 inches above the wall penetration. Use two medium­radiusbend,2-in. PVC elbows and a lengthof 2-in. PVC pipe so that the elbowsare on 24-in.centers.
INSTALLATION CAN CAUSE STRUCTURAL OR EXTERIOR FINISH DAMAGE TO THE BUILDING.
Non-direct venting location requirements are slightly differentin some cases than direct venting. Install a non-directvent with the following minimumclearances. See Figure 17.
1. Locatethe bottom of the vent terminal at least 12 inchesabove grade.Increase the 12-in. minimumto keep the terminal openings above the level of snow accumulation,where applicable.
2. The vent shall not terminateover publicwalkways or over an area wherecondensate or vapor could createa nuisance or hazard.
3. 4 feet below,4 feet horizontally from,or 1 foot above any door, windowsoffit,undereave vent or gravityair inlet to the building.
4. The vent terminal shall have a minimumhorizontal clearanceof 4 feet from electricmeters,gas meters,regulators and relief equipment.
5. 6 feet from an inside corner formedby two exterior walls – 10 feet is the recommended distance.
6. Locateit 3 feet above any forced air inlet located within 10 feet. Any fresh air or make-up air inlet, such as for a dryeror furnace area,is considereda forced air inlet.
7. Avoid areas where dripping condensate may cause problems, such as above planters, patios, or adjacent to windows where steammay cause fogging.
In addition to the minimumclearances listedabove,the vent location should also be governed by the following guidelines.
1. Do not terminate under any kind of patio or deck. If runningthe vent under a deck, insulateit to insureno condensatefreezes and blocks the pipe.
2. Do not locateon the side of a building with prevailing winter winds.This will help prevent moisture from freezingon walls and overhangs(undereaves).
3. Do not extendvent directly throughbrickor masonry surfaces. Use a rust-resistant sheetmetal or plastic backing platebehindvent.
4. Do not locatetoo close to shrubs as condensatemay stunt or kill them.
5. Minimumvertical clearancesof 1 foot are recommendedfor overhangs up to 1 foot horizontal. The verticalclearance should be increased equally for each additional increase in horizontal overhang to a maximumvertical clearance of 6 feet.
6. Caulk all cracks, seams and jointswithin6 feet horizontally and above and belowvent.
NON-DIRECT VENT TERMINATION LOCATION REQUIREMENTS
CAUTION
!
MOISTURE IN THE COMBUSTION PRODUCTS CONDENSES AS IT LEAVES THE TERMINATION. THIS CONDENSATE CAN FREEZE ON EXTERIOR WALLS, UNDER THE EAVES, AND ON SURROUNDING OBJECTS. SOME DISCOLORATION IS TO BE EXPECTED. HOWEVER, IMPROPER LOCATION OR
20
FIGURE 17
Natural Gas and Propane Installation Code
National Fuel Gas Code
Canadian Installations
US Installations
Canadian Installations
US Installations
OTHER THAN DIRECT VENT TERMINAL CLEARANCES
21
DIRECT VENT INSTALLATIONS
WARNING
!
READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Direct vent installationsrequire a dedicated combustion air and venting system. All air for combustion is taken from the outside atmosphere and all combustion products are discharged to the outdoors. Therefore, no
ventilation or combustion air openings are required.
IMPORTANT: The plastic combustion
air and venting components are of Schedule 40 PVC. If using ABS piping ensure that the solvent cement is compatible for joining PVC to ABS components or use a mechanical connection that can withstand the vent temperatures and are corrosion resistant.
INSTALLATION GUIDELINES
All exhaust piping must be installed in compliance with Part 7, “Venting of Equipment,”of the latest edition of the National Fuel Gas Code NPFA54/ ANSI Z223.1-, local codes or ordinances and these instructions.
1. Vertical piping is preferred.
2. All horizontalpipingmust slope upwarda minimum of per foot of run so that condensate drains toward the furnace.
3. All horizontal runs must be supported at least every 4 feet. No sags or dips are permitted.
4. IMPORTANT: Do not common vent with any other appliance. Do not install in the same chase or chimney with a metal or high temperatureplastic pipe from another gas or fuel-burning appliance unless the required minimum clearances to combustiblesare maintained between the PVC pipe and other pipes.
1
4 inch
TABLE 2
FOR DIRECT VENT APPLICATIONS - AIR FOR COMBUSTION PROVIDED FROM OUTDOORS
MAXIMUM ALLOWABLE LENGTH IN FEET OF EACH EXHAUST PIPE AND INTAKE AIR PIPE
FURNACE
INPUT
45,000 2”
60,000
75,000
90,000
105,000
NOTES:
PIPE
TERMINATION
SIZE
Standard/Concentric RXGY-D02/RXGY-D02A/RXGY-E03A/RXGY-G02 60 50
Alternate RXGY-D02/RXGY-D02A 50 40
Standard/Concentric RXGY-D02/RXGY-D02A/RXGY-E03A/RXGY-G02 50 40
2”
3”
2“
(-)GRC
3“
(-)GRC
3“
(-)GTC
3“
(-)GRC Only
3“
(-)GTC Only
3“
(-)GRC Only
3“
(-)GTC Only
1. N.A. - NOTAPPLICABLE.
2. MAXIMUM OF6 ELBOWSMAY BE USED.DO NOTCOUNT ELBOWS IN ALTERNATETERMINATIONKIT. MEDIUMOR LONGSWEEPELBOWS MAY BE USED.
3. A 45 DEGREEELBOWIS CONSIDEREDONE ELBOW.
4. CONCENTRICTERMINATIONNO. RXGY-E03/RXGY-E03AIS FORTHRU-THE-ROOF OR THRU-THE-WALL VENTING.
5. USE KITS RXGY-DO2/D02A (2"), RXGY-G02(2"), ORRXGY-D03/D03A(3") FORSTANDARDOR ALTERNATE THRU-THE-WALLVENTING.
6. USE KITS RXGY-D04/D04A FORALTERNATE VENTING OF 120,000BTUH UNITS WITHLONG RUNS.
7. KIT NUMBERSCONTAINING SUFFIX “A” ARE APPROVED FOR INSTALLATIONIN CANADA.
8. NO SCREENSMAY BEUSED TOCOVER COMBUSTIONAIR ANDEXHAUST.
Alternate RXGY-D02/RXGY-D02A 40 30
Standard/Concentric RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate RXGY-D03/RXGY-D03A 50 40
Standard/Concentric RXGY-D02/RXGY-D02A/RXGY-E03A/RXGY-G02 25 N/A
Alternate Not Applicable N/A N/A
Standard/Concentric RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate RXGY-D03/RXGY-D03A 40 30
Standard/Concentric RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate Not Applicable N/A N/A
Standard RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate RXGY-D03/RXGY-D03A 50 40
Standard RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate Not Applicable N/A N/A
Standard RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate RXGY-D03/RXGY-D03A 50 40
Standard RXGY-D03/RXGY-D03A/RXGY-E03A/RXGY-G02 50 40
Alternate Not Applicable N/A N/A
VENT TERMINATION KIT RECOMMENDED
(RXGY-D0* Kits for
Horizontal Venting Only)
NUMBER OF ELBOWS
45 or 90 Degrees
Medium / Long Radius ONLY
1 - 2 3 - 4
5. For horizontal runs where water may collect, wrap the vent pipe with self-regulating 3 or 5 watt heat tape. The heat tape must be U.L. listed and installed per the manufacturer’sinstructions.
6. The minimum vent pipe length is 5 feet.
Size the exhaust and combustion air intake pipes as specified in Table 2. This table lists the maximum allow­able length in feet of the exhaust and combustion air intake pipes that may be used for all furnace inputs as related to the number of elbows required and the termination (see shaded area).
7. The maximum exposed vent length (above the roof line) is 30.
22
COMBUSTION AIR FOR DIRECT VENT INSTALLATIONS
THE COMBUSTION AIR SYSTEM DESIGNED FOR THIS FURNACE MUST BE USED.
When this furnace is installed as a direct vent forced air furnace, all combustion air is supplied directly to the burner through a special air inlet system outlined in these instructions. This system consists of field-supplied Schedule 40 or 26 SDR-PVC pipe and one of the following horizontal vent termination kits: RXGY-D02 or D02A, RXGY-D03 or D03A, or RXGY-E03A.
NOTE: Schedule 40 ABS-DWV pipe and fittings may be used as an alternate to PVC pipe for the combustion air inlet and vent pipes.
The combustion air for this furnace is supplied directly from the outdoors through the combustion air inlet system.
When the furnace is installed in the same space with other gas appliances,such as a water heater, be sure there is an adequate supply of combustion and ventilation air for the other appliances. Do not delete or reduce the combustion air supply required by the other gas appliances in this space. See Z223.1, National Fuel Gas Code (NFPA54) for deter­mining the combustion air requirementsfor gas appliances. An unconfined space must have at least 50 cubic feet (volume) for each 1,000 BTUH of the total input of all appliances in the space. If the open space containing the appliances is in a building with tight construction (contemporaryconstruction), outside air may still be required for the appliances to burn and vent properly. Outside air openings should be sized the same as for a confined space.
STANDARD TERMINATIONS
STANDARD VERTICAL TERMINATIONS
COMBUSTION AIR PIPING Use two medium-radius sweep
elbows to keep the inlet downward to prevent entry of rain. See Figure 20 for the proper relationship of combustion air to exhaust termination.
STANDARD HORIZONTAL TERMINATIONS
COMBUSTION AIR PIPING When 3-in. pipe is used between the
furnace and outside wall, reduce it to 2 inches before penetrating the wall. Up to 18 inches of 2-in. pipe may be used inside the wall.
The standard horizontal intake air terminationfor all models is a 2-in. PVC coupling with a wind deflector vane (provided) attached. Cut a
1
2
4-in. length of 2-in. PVC pipe. Connect this pipe and another 2-in. PVC coupling to the coupling at the wall. The outer coupling must terminate 4 inches from the wall. See Figure 21, Detail B, for vane location. Attach vane in vertical position with PVC solvent.
IMPORTANT: To ensure proper furnace operation, the supplied vane must be installed in the vertical position as shown in Figure 21, Detail B.
The combustion air inlet terminal must be located with respect to the exhaust terminal as shown in Figure 21, Detail C.
IMPORTANT: All furnaces with horizontal air intakes, except those using concentric vent kit RXGY-E03A, must have a drain tee assembly and trap installed as close to the furnace as possible. This is to drain any water that may be in the combustion air pipe to prevent it from entering the furnace combustion chamber.
These parts are included in kits RXGY-D02 or D02A (for 2-in. pipe), RXGY-D03 or D03A (for 3-in. pipe). Attach the trap to the bottom of the tee with PVC solvent. Connect the other end to a suitable drain, as to the downstream of a condensate trap on the furnace.
STANDARD VERTICAL TERMINATIONS
EXHAUST VENT PIPING Vertical through-the-roofvent
applicationsdo not require an exhaust terminal. The exhaust vent must terminate at least 12 inches above the combustion intake air termination.The exhaust vent for models with inputs of 60,000 through 105,000 BTUH is 2-in. PVC pipe.
Refer to Table 2 for proper application.See Figure 24.
STANDARD HORIZONTAL TERMINATIONS
EXHAUST PIPING
For direct vent systems the standard terminationis 2-in. PVC pipe extending 12 inches from the wall for furnaces with inputs from 60,000 to 105,000 BTUH. Install a 2-in. coupling at the outside wall to prevent the terminationfrom being pushed inward. When 3-in. pipe is used between the furnace and outside wall, reduce to 2 inches before penetrating the wall. The standard termination is 2-in. PVC pipe extending outward 12 inches from the wall for models with inputs of 45,000 to 105,000 BTUH. See Figure 21, Detail B.
The combustion air and exhaust terminationsmust be at least 12 inches above grade and must be oriented with respect to each other as shown in Figure 21. Refer to section on alternate venting options when higher snow levels are anticipated.
ALTERNATE TERMINATIONS
ALTERNATE HORIZONTAL DIRECT VENT TERMINATIONS
KIT NOS. RXGY-D02, -D02A, -D03, D03A
The combustion air and exhaust terminationsmay be raised a maximum of 60/24 inches above the wall penetration to maintain the required 12 inch clearance above grade or snow level respectively. See Figure 18. Size the pipe length according to Table 2.
IMPORTANT: The following guidelines must be met when extending beyond 24 inches of pipe on the exterior of the structure:
• Sizethe entire vent system according to the alternate, not standard, termination shown in Table 2.
23
• Insulate the entire length of vent pipe, between the elbow where the pipe exits the wall and the elbow where the termination is made, with a closed-cell insulation,such as “Arm-a-Flex”or “Rub-a-Tex” with a minimum of 1/2” thickness.
• Allelbows installed on the exterior of the building must be of the long sweep nature.
• As required for the horizontal piping ran within the structure, any pipe ran horizontal outside the structure must slope upward a minimum of 1/4” per foot run so that condensate drains toward the furnace.
From the top elbow in the exhaust pipe, extend a length of PVC pipe outward so that it terminates exactly 12 inches from the wall. See Figure
18.
FIGURE 18
ALTERNATE HORIZONTAL DIRECT VENT TERMINATION NOT APPLICABLE TO
GTC-07 MODELS GTC-09 MODELS GTC-10 MODELS
SEE DETAILA
3MAX. NOTE: 3-1/2 MAX. WHEN D04 KIT IS USED.
60”
MAX.
24”
MAX.
EXHAUST VENT 2" PVC FOR MODELS WITH INPUTS OF 45,000 AND 105,000 BTU. ELBOWS AND RISERS ARE 2" PVC.
12FROM WALL
PIPE SUPPORT STRAP
2" PVC ELBOWS AND RISER MODELS WITH INPUTS OF 45,000 THRU 105,000BTU.
USE KIT NO. RXGY-D02 WHEN 2" PIPE IS USED BETWEEN FURNACE AND OUTSIDE WALL. USE KIT NO. RXGY-D03 WHEN 3" PIPE IS USED.
The 45,000 BTUH unit only uses kit RXGY-D02 or D02A. The 60,000 BTUH and 75,000 BTUH units may use kits RXGY-D02 or D02A or RXGY-D03 or D03A depending on pipe lengths and number of elbows. See Table 2.
The following are parts lists for the RXGY-D02 or D02A, RXGY-D03 or D03A alternate horizontal direct vent terminationkits:
RXGY-D02/D02A
1. 2-in. tee with reducer assembly
1
2.
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
1
5. 1
2-in. PVC nipple with coupling
6. PVC strap
7. vent template
3
24
MIN.
INTAKE
EXHAUST / INTAKE RELATIONSHIP
EXHAUST
DETAIL B
OPTIONAL
INTAKE
RXGY-D03/D03A
1. 3-in. tee with reducer assembly
1
2.
2-in. PVC 6-in. dia. trap
3. PVC vane
4. 2-in. PVC elbow
5. PVC strap
6. vent template
RXGY-D02A
1. 2” Tee assembly w/ connection
1
2.
2” PVC-5” diameter trap
3. Wind deflector vane
4. Vent template
RXGY-D03A
1. 3” Tee assembly w/ connection
1
2.
2” PVC-5” diameter trap
3. Wind deflector vane
4. Vent Template
1
2” drain
1
2” drain
I339
24
CONCENTRIC TERMINATIONS
VERTICAL/HORIZONTAL CONCENTRIC VENT KIT NO. RXGY-E03A
This kit is for vertical/horizontal intake air/vent runs and may be installed through roofs and sidewalls. One 5” diameter hole is required for the installation. See Figure 19 for the general layout. Complete installation instructions are included with the kit.
NOTE: The following IPEX brand concentric terminations (System 636) may be purchased in the field used in place of factory supplied kits:
3” Concentric Kit – Item # 196006
and
FIGURE 19
CONCENTRIC VENT KIT NO. RXGY-E03A
SIDEWALL ASSEMBLY
FIELD-SUPPLIED STRAP
C
B
D
ITEM No. DESCRIPTION
A 2.5" PVC PIPE SCHEDULE 40 -- 37.125" LONG B4"PVC PIPE SCHEDULE 40 -- 24" LONG C3" x 3" x 4" SPECIAL CONCENTRIC FITTING D3" x 45° STREET ELBOW (FIELD SUPPLIED)
E
A
1" MAXIMUM
ROOF INSTALLATION
A
E
C
MAINTAIN 12 IN. MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF.
B
D
E PVC RAINCAP
25
FIGURE 20
STANDARD VERTICAL DIRECT VENTING UPFLOW MODEL SHOWN (TYPICAL FOR DOWNFLOW MODELS)
3" MAX. SEPARATION
COMBUSTION AIR PIPE
12" MIN. SEPARATION
12" MIN. ABOVE ROOF LEVEL
EXHAUST PIPE
30MAX
ROOF LINE
3
COMBUSTION AIR PIPE
NOTES:
THE COMBUSTION AIR PIPE MUST
1
TERMINATE IN THE SAME PRESSURE ZONE AS THE EXHAUST PIPE.
INCREASE THE 12-IN. MINIMUM
2
TO KEEP TERMINAL OPENING ABOVE ANTICIPATED LEVEL OF SNOW ACCUMULATION WHERE APPLICABLE.
WHEN 3-IN. DIAM. PIPE IS USED,
3
REDUCE TO 2-IN. DIAMETER BEFORE PENETRATING ROOF. A MAXIMUM OF 18 IN. OF 2-IN. PIPE MAY BE USED BEFORE PASSING THROUGH ROOF.
SUPPORT VERTICAL PIPE EVERY 6
4
FEET. EXHAUST TERMINATION - TERMINATE
5
THE LAST 12 INCHES WITH 2PVC PIPE ON 45,000 AND 105,000 BTUH MODELS.
30” MAXIMUM EXPOSED VENT
6
LENGTH.
4
SUPPLY AIR
2
RETURN AIR
EXHAUST VENT
12"
3"
1
COMBUSTION AIR PIPE
MAX.
EXHAUST VENT
12"
MIN.
MIN.
3"
MAX.
COMBUSTION AIR PIPE
12" MIN.
5
12" MIN.
ROOF LINE
ANTICIPATED SNOW LEVEL
5
EXHAUST VENT
12" MIN.
30MAX
PITCHED ROOF INSTALLATIONS
3"
MAX.
12" MIN. ABOVE
ANTICIPATED SNOW LEVEL
5
I407
FIGURE 21
STANDARD HORIZONTAL DIRECT VENTING UPFLOW MODEL SHOWN (TYPICAL FOR DOWNFLOW MODELS)
1
SUPPLY AIR
EXHAUST PIPE
COMBUSTION AIR PIPE
NOTES:
SUPPORT HORIZONTAL PIPE
1
EVERY FOUR FEET. WHEN 3 IN. PIPE IS USED REDUCE TO 2 IN.
2
BEFORE PENETRATING OUTSIDE WALL. 18 IN. MAXIMUM. 2 IN. DIAMETER PIPE MAY
3
BE USED INSIDE THE WALL. DETAIL “A” - EXHAUST TERMINATION
4
TERMINATE THE LAST 12 INCHES WITH 2 PVC PIPE ON 45,000 AND 105,000 BTUH MODELS.
INCREASE THE 12 IN. MINIMUM ABOVE
5
GRADE TO KEEP TERMINAL OPENINGS ABOVE ANTICIPATED LEVEL OF SNOW ACCUMULATION WHERE APPLICABLE.
DETAIL “B”, INSTALL WIND DEFLECTOR
6
VANE IN 2 IN. PVC COUPLING IN VERTICLE POSITION USING PVC SOLVENT.
THE COMBUSTION AIR TERMINATION MUST BE IN THE SAME PRESSURE ZONE AS THE EXHAUST TERMINATION.
2OR 3TEE
W/DRAIN TRAP
COMBUSTION AIR TERMINATION
DETAIL B
CONNECT TO DRAIN
RETURN AIR
VANE
6
TRAP
2
2PVC COUPLING
3
12
4
12MIN. ABOVE GRADE LEVEL
SEE DETAIL B
SEE DETAIL A
4
5
3
4
INTAKE
EXHAUST / INTAKE RELATIONSHIP
EXHAUST
DETAIL C
OPTIONAL
INTAKE
I407
26
FIGURE 22
Natural Gas and Propane Installation Code
National Fuel Gas Code
Canadian Installations
US Installations
Canadian Installations
US Installations
DIRECT VENT TERMINAL CLEARANCES
27
LOCATION REQUIREMENTS HORIZONTAL DIRECT VENTS
CAUTION
!
THE COMBUSTION PRODUCTS AND MOISTURE IN THE FLUE GASES WILL CONDENSE AS THEY LEAVE THE TERMINATION. THE CONDENSATE CAN FREEZE ON THE EXTERIOR WALL, UNDER THE EAVES AND ON SURROUNDING OBJECTS. SOME DISCOLORATION TO THE EXTERIOR OF THE BUILDING IS TO BE EXPECTED. HOWEVER, IMPROPER LOCATION OR INSTALLATION CAN RESULT IN STRUCTURAL OR EXTERIOR FINISH DAMAGE TO THE BUILDING AND MAY RECIRCULATE PRODUCTS OF COMBUSTION INTO THE COMBUSTION AIR TERMINAL AND FREEZE.
The vent must be installed with the following minimum clearances. See Figures 22 & 23.
1. The bottom of the vent terminal and the air inlet shall be located at least 12 inches above grade. Increase the 12-in. minimum to keep the terminal openings above the level of snow accumulation,where applicable.
2. The vent shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard.
3. The vent terminal shall be located at least one foot from any opening through which flue gases could enter a building.
4. The vent terminal shall be at least 3 feet above any forced air inlet located within 10 feet, except the combustion air inlet of a direct vent appliance.
5. The vent terminal shall have a minimum horizontal clearance of 4 feet from electric meters, gas meters, regulators and relief equipment.
6. Locate the furnace combustion air inlet minimum of 3 feet from the vent of any other gas or fuel burning appliance or clothes dryer to prevent recirculation of the flue gases into the furnace combustion air inlet. The only exception to this requirement is the case of multiventing two or more furnaces, which is covered in the section on multiventing in these instructions.
In addition to the minimum clearances listed above, the vent location should also be governed by the following guidelines.
1. Do not terminate under any
kind of patio or deck. If running the vent under a deck, insulate it to insure no condensate freezes and blocks the pipe.
2. Do not terminate behind any area that may allow the flue products to become stagnant and recirculate.
3. Do not locate on the side of a building with prevailing winter winds. This will help prevent moisture from freezing on walls and overhangs (under eaves).
4. Do not extend vent directly through brick or masonry
FIGURE 23
MOISTURE ZONES
surfaces, unless a rust-resistant sheet metal or plastic backing plate behind vent. See Figure 23.
5. Do not locate too close to shrubs as condensate may stunt or kill them.
6. Minimum vertical clearances of 1 foot are recommended for overhangs up to 1 foot horizontal. The vertical clearance should be increased equally for each additional increase in horizontal overhang to a maximum vertical clearance of 6 feet.
7. Caulk all cracks, seams and joints within 6 feet horizontally and above and below vent. See Figure 23.
2 FT. SQ. SHEET METAL PLATE ON BRICK OR MASONRY SURFACE RECOMMENDED, BUT NOT REQUIRED BY CODE.
28
28
FIGURE 24
8"
MINIMUM 12" ABOVE AVERAGE
SNOW ACCUMULATION. MAXIMUM
OF 24 IN.ABOVE ROOF.
8"
MAXIMUM 1"
DISTANCE
FROM WALL
MINIMUM 12"
ABOVE GRADE
6' MINIMUM
10' RECOMMENDED
TWO FURNACE VENTING THROUGH ROOF
FIGURE 25
TWO FURNACE VENTING THROUGH WALL
TWO-PIPE VENTING
EXHAUST VENT MODELS 04-06 TO BE REDUCED TO 2” PVC LAST 12”.
3” MINIMUM 24” MAXIMUM
CONCENTRIC VENTING
8” MINIMUM 24” MAXIMUM
TWO-PIPE VENTING
3” MINIMUM 24” MAXIMUM
CONCENTRIC VENTING
8. Painted surfaces must be sound and in good condition with no cracking, peeling, etc. Painted surfaces will require maintenance.
9. Do not expose 3" x 2" reducer/ bushing to outdoor ambient temperatures.
SEE CONCENTRIC VENT SECTION ON PAGE 23 FOR MORE INFORMATION.
8” MINIMUM 24” MAXIMUM
SEE CONCENTRIC VENT SECTION ON PAGE 23 FOR MORE INFORMATION.
MULTIVENTING
IF VENTING TWO OR MORE FURNACES NEAR EACH OTHER IS REQUIRED, EACH FURNACE MUST BE INDIVIDUALLY VENTED – NO COMMON VENTING IS PERMITTED.
See Figures 24 and 25 for positioning of the terminations. When more than two furnaces are to be vented, there must be at least 4 feet between the first two furnaces and the third, etc.
29
29
RXGY-G02 SIDE WALL VENT
EXHAUST
AIR INTAKE
2 inch
or 3 inch piping
REDUCING COUPLING, FIELD SUPPLIED. (2” PIPE DOES NOT REQUIRE COUPLING.)
This termination for horizontal venting only.
IMPORTANT: Do not install on the prevailing winter wind side of the structure. Observe same clearances specified for horizontal,standard termination.
NOTE: Multi-venting-No common venting.
FIGURE 26
VENT KIT INSTALLATION OPTIONS
NOTE: Install the vent and air intake
piping into the vent plate openings. Seal all gaps between the pipes and wall. Be Sure To Use Silicone Sealant to seal the vent pipe to the vent cap to permit field disassembly for annual inspection and cleaning. Also seal all pipe penetrations in wall. To prevent possibility of condensate freeze-up or recirculation,do not
install vent kits one above the other.
NOTE: The vent illustration in Figure
27 can be used for Non-direct vent terminationsalso.
FIGURE 27
VENT KIT INSTALLATION OPTIONS
30
For 90000 thru 105000 BTUH models­reduce to a length between 12 inches and 30 inches of 2 inch pipe. for 45000 thru 75000 BTUH models­when 3 inch pipe is used: reduce last 30 inches to 18 inches of 2 inch pipe. Note:Vent should protrude a maximum of 2-1/4” beyond vent plate. Air intake should protrude a maximum of 1 inch beyond vent plate.
Seal all wall cavities
CONNECTING TO FURNACE
IMPORTANT: Clean and debur all pipe cuts. The shavings must not be allowed to block the exhaust, inlet or condensate drain pipes.
UPFLOW FURNACE
The exhaust pipe connection is a 2-in. female PVC pipe fitting extending through the left side of the furnace top plate. This opening has a protective cap which should be removed just prior to installing the exhaust pipe. When 2-in. pipe is used, connect it directly to this fitting. When 3-in. pipe is used, connect a 2 to 3-in. coupling to this fitting with a short piece of 2-in. PVC pipe.
The inlet combustion air connection is at the right side of the top plate. An alternate combustion inlet air connection may be made on the right side of the jacket. This opening has a plastic cap. A combustion inlet air connection fitting is supplied with the furnace and it must be installed in the furnace by screwing it into the opening. Make sure the rubber “O-ring” supplied with the furnace is used with this fitting. See Figure 28.
FIGURE 28
UPFLOW COMBUSTION AIR AND VENT PIPE CONNECTION
“O” RING
TOP PLATE
VENT CAP/PLUG
OUTLET AIR PIPE
EXHAUST TRANSITION
CONNECTOR
CONDENSATE TRAP
COMBUSTION AIR ADAPTER
NOTE: WHEN COMBUSTION AIR INLET IS IN OPTIONAL POSITION SWAP LOCATION OF INLET AIR ADAPTER AND “O” RING WITH PLUG.
PLUG OPT. COMBUSTION AIR INLET POSITION
INDUCED DRAFT BLOWER
I329
DOWNFLOW/HORIZONTAL FURNACE
The exhaust pipe connection is a 2-in. upflow only PVC pipe fitting extending through the right side of the furnace top cover. This opening has a pro­tective cap which should be removed just prior to installing the exhaust pipe. When 2-in. pipe is used, con­nect it directly to this fitting. When 3-in. pipe is used, connect with a 2- to 3-in. coupling directly to the 2-in. pipe.
The combustion inlet air connection is a 2-in. extruded hole on the left side of the top plate. When a 2-in. pipe is used, attach a 2-in. PVC coupling over this hole with RTV sealant and also add two sheet metal screws through the coupling into the extrusion to secure it in place, and add the required piping. When 3-in. pipe is required, use a 2- to 3-in. coupling and add the required piping. See Figure 29.
FIGURE 29
DOWNFLOW/HORIZONTAL COMBUSTION AIR AND VENT PIPE CONNECTION
TOP PLATE
COUPLING
NOTE: ATTACH COUPLING TO EXTRUDED COLLAR WITH TWO SCREWS. PUT BEAD OF SILICONE AROUND BASE BEFORE MOUNTING COUPLING.
COMBUSTION AIR CHASE
INDUCED DRAFT BLOWER
EXHAUST TRANSITION
VENT CAP/PLUG
PIPE - PVC
CONNECTOR
OUTLET AIR PIPE
I329
31
CONDENSATE DRAIN/NEUTRALIZER
GENERAL INFORMATION
CAUTION
!
DO NOT RUN DRAIN OUTDOORS. FREEZING OF CONDENSATE CAN CAUSE PROPERTY DAMAGE.
IMPORTANT: Do not connect into a
common drain line with an air con­ditioner evaporator coil drain located below the furnace. A blocked or restricted drain line can result in over­flow of the coil pan and negate the furnace blocked drain shutoff control.
FILL TRAP ASSEMBLY WITH WATER BEFORE OPERATING THE
FURNACE. This can be done by
removing the drain hose from the trap and pouring about a cup of water into the vent trap. Water will flow into the house drain when the trap is full.
If local codes require, install a condensate neutralizer cartridge in the drain line. Install cartridge in horizontal position only. Also install an overflow line if routing to a floor drain. See Figures 30 and 31.
If no floor drain is available, install a condensate pump that is resistant to acidic water. Pumps are available from your local distributor. If pump used is not resistant to acidic water, a condensate neutralizer must be used ahead of the pump. The condensate pump must have an auxiliary safety switch to prevent operation of the furnace and resulting overflow of condensate in the event of pump failure. The safety switch must be wired through the “R” circuit only (low voltage) to provide operation in either heating or cooling modes.
drain is present, install a riser which is a minimum of 10
13
16”. If the furnace is installed in an attic, crawlspace or other area where freezing temperatures may occur, the furnace drain can freeze while shut off for long periods of time.
Use a solvent cement that is compatible with PVC material. Cut the drain hoses to the appropriate length and connect to the trap with hose clamps. Tighten the clamps with pliers and check for leaks after attaching.
DOWNFLOW MODELS
IMPORTANT: There are two options
when choosing a height for the condensate riser:
FIGURE 30
UPFLOW CONDENSATE DRAIN
NOTE: SEE UPFLOW MODEL NOTES FOR PIPE HEIGHT
16
1013/
NEUTRALIZER CARTRIDGE (OPTIONAL)
OVERFLOW LINE (REQUIRED ONLY WHEN OPTIONAL NEUTRALIZER CARTRIDGE IS USED.)
TO FLOOR DRAIN OR CONDENSATE PUMP
CONDENSATE OVERFLOW: With a
3
1
4 inch riser installed above the tee, a blocked drain will result in overflow from the riser.
FURNACE SHUTDOWN: To cause the furnace to shut down when a blocked drain is present, install a riser which is a minimum of 5 furnace is installed in an attic, crawlspace or other area where freezing temperatures may occur, the furnace drain can freeze while shut off for long periods of time.
Use a solvent cement that is compatible with PVC material.
DRAIN LINE
CONDENSATE TRAP
1
2”. If the
I408
UPFLOW MODELS
The condensate drain trap is located in the blower compartment on the left­hand side of the jacket. A short piece of
1
2-in. PVC pipe and a1⁄2-in. tee are provided. Connect the1⁄2-in. pipe to the elbow on the trap and the tee to this pipe so that the open end is upward. Run a drain tube from the bottom of the tee to a floor drain or condensate pump.
IMPORTANT: If installing the unit over a finished ceiling or living area, be certain to install an auxiliary condensate drain pan under the entire unit extending out under the condensate tee.
IMPORTANT: There are two options when choosing a height for the condensate riser:
CONDENSATE OVERFLOW: With a
1
5
2 inch riser installed above the tee, a blocked drain will result in overflow from the riser.
FURNACE SHUTDOWN: To cause the furnace to shut down when a blocked
32
FIGURE 31
DOWNFLOW CONDENSATE DRAIN
CONDENSATE TRAP
DRAIN LINE
NEUTRALIZER CARTRIDGE
(OPTIONAL)
NOTE: SEE DOWNFLOW MODEL NOTES FOR PIPE HEIGHT
OVERFLOW LINE (REQUIRED ONLY WHEN OPTIONAL NEUTRALIZER CARTRIDGE IS USED.)
TO FLOOR DRAIN OR CONDENSATE PUMP
I408
REVERSING THE TRAP
UPFLOW UNITS
The trap may be moved to the right side for right side drainage. Open the knockout for the drain on the right side of the cabinet. Remove the bracket holding the trap from the left side. Seal the left side drain hole with a plug provided in the cloth bag with the furnace. Position the mounting bracket and trap so that the drain elbow is centered in the hole on the right. See Figure 32.
Drill two holes in the cabinet to mount the bracket. Mount the trap and bracket to the right side with the drain elbow pointing through the knockout. Connect the noted above. Route the drain hoses behind the control box, cut to the appropriatelength, and connect to the trap with hose clamps.
IMPORTANT: DO NOT ALLOW ANY SAGS OR KINKS IN THE HOSES. This prevents proper condensate flow.
IMPORTANT: Do not connect into a common drain line with an air conditionerevaporator coil drain located above the furnace. A blocked or restricted drain line can result in overflow of the coil pan and negate the furnace blocked drain shutoff control.
1
/2-in. pipe and tee as
insure a good seal in the burner compartment.
1
A length of
/2” black PVC pipe is also provided in the RXGY-H01 downflow alternate drain kit. Glue one end of the pipe to the elbow in the trap. Cut the pipe so that it extends through the alternate drain hole in the left side of the cabinet one inch (see Figure 33). Connect the
1
/2” PVC tee (supplied with the furnace) to the pipe with a 1­3/4” riser. Use the 1-5/8” plug
the trap. Remove the double-elbow black molded hose from the trap and exhaust transition and discard. Remove the trap from its mounting bracket, rotate it 180 degrees and mount in place with the drainage elbow pointing to the left. Reattach the long black molded hose. Use the 2-9/16” length of black hose included in the RXGY-H01 kit between the trap and exhaust transition. Clamp the hoses tight with white nylon clamps.
supplied in the RXGY-H01 downflow alternate drain kit to seal the right side drainage hole.
IMPORTANT: Do not connect into a common drain line with an air conditionerevaporator coil drain located above the furnace. A blocked or restricted drain line can result in overflow of the coil pan and negate the furnace blocked-drainshutoff control.
To convert to left side drainage, remove the long molded hose from
FILLING THE TRAP
FILL THE TRAP ASSEMBLY WITH WATER BEFORE OPERATING THE
FURNACE. Do this by removing the
drain hose from the trap or from the connection to the secondary coil. Pour about a cup of water into the vent trap. Any excess water flows into the house drain when the trap is full.
NOTE: Fill the trap assembly with water every heating season.
FIGURE 32
UPFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
PROPER DRAIN SLOPE REQUIRED
(NO KINKS ALLOWED)
CUT DRAIN HOSES AS REQUIRED AND CONNECT TO INLETS ON TOP OF CONDENSATE TRAP
DOWNFLOW UNITS
To convert downflow models to left­hand drain, a kit (RXGY-H01) must be ordered from the distributor. The kit includes a 24” piece of
1
2” black PVC pipe, a 2-9/16” length of black hose, a 2” rubber grommet, a 1-5/8” plug and instructions. Note the location of the alternate drain hole as shown in Figure 33.
First remove the long molded hose from the trap. Remove the double­elbow black molded hose from the trap and exhaust transition and discard. Remove the trap from its mounting bracket, rotate it 180°, and mount in place with drainage elbow pointing to the left. Reattach the long black molded hose. Use the 2-9/16” length of black hose included in the kit between the trap and exhaust transition.Clamp the hoses tight with white nylon clamps.
Remove the plug from the 2” alternate drain hole (see Figure 33) and replace it with the 2” rubber grommet supplied in the RXGY- H01 downflow alternate drain kit. Also, remove the 1-5/8” grommet supplied in the primary drain hole and replace it with the 1-5/8” diameter plug that is also supplied in the RXGY-H01 downflow alternate drain kit. Both the hole-plug and grommet must be in place to
IFC MOUNTING
PLATE
CONDENSATE TRAP
FIGURE 33
DOWNFLOW OPPOSITE SIDE CONDENSATE TRAP CONNECTION
DRAIN VENT
DRAIN
EXTENSION
TEE
ALTERNATE DRAIN HOLE LOCATED HERE ON JACKET. (REMOVE PLASTIC PLUG AND REPLACE WITH GROMMET).
TO FLOOR DRAIN OR
CONDENSATE PUMP
CONDENSATE TRAP
TO FLOOR
DRAIN
EXISTINGDRAIN HOLE. PLUG WITH 15⁄8” PLUG SUPPLIED IN KIT
ROTATE TRAP 180° AND INSTALL RIGID PIPE FROM ELBOW TO OPPSOITE SIDE OF JACKET AS SHOWN
DRAIN RISER
TEE
DRAIN EXTENSION
I394
I394
33
CONVERTING DOWNFLOW TO HORIZONTAL
CONDENSATE DRAIN FOR HORIZONTAL INSTALLATION
Refer to Figure 35 for Steps 1-5.
1. This unit is shipped factory ready for downflow condensate trap assembly and drain hoses require conversion for horizontal installation. Remove the existing condensate trap with the unit in the upright position.
IMPORTANT: This furnace may only be installed so that when facing the front of the furnace, supply air is discharged on the left hand side.
2. Remove the burner compartment door from the unit.
3. Remove the two screws from the right side of the furnace jacket which support the trap mounting bracket . Remove the two plastic plugs on either side of the trap outlet hole and discard.
4. Remove the black molded 90°
C
hose from the top of the existing trap and from the furnace collector box. Cut 1.0 inch from the long end of the hose.
5. Remove the double-elbow black molded hose from the exhaust transition . Discard this hose and the downflow trap. Retain the clamps for future use. Additional clamps are provided in the parts bag if any clamps are damaged during conversion process.
NOTE: The following steps should take place with the furnace in the horizontal position.
installation.The
B
A
D
E
Refer to Figure 36 for Steps 6-11.
6. Locate the parts bag in the burner compartment. Install two plastic plugs in the side of the
F
jacket from bottom side up.
7. Attach the gasket onto the trap
H
assembly so that the gasket holes on the gasket line up with the holes on the trap assembly.
8. Fill the trap assembly with 1/2
G
cup of water.
9. Insert the trap assembly with gasket up through the existing hole in the jacket and secure from inside the jacket. Use two screws provided. Screw down into the two “ears” molded into either side of the trap. Snug the trap assembly against the furnace jacket compressing the gasket slightly to eliminate any air leaks. Do not
overtighten!
10. Attachthe black molded rubber 90° elbow to the straight spout
I
on the trap top using a white nylon clamp . Attach the other
J
end of the rubber elbow to the
K
spout located on the exhaust transition using a white nylon
E
clamp.
11. Attachthe 90° end of the molded
L
hose to the collector box. Clamp the hose tight with a white
FIGURE 34
HORIZONTAL CONDENSATE DRAIN
NOTE: SEE GENERAL NOTES FOR HORIZONTAL MODELS FOR PIPE HEIGHT.
nylon clamp. Then attach the long end of the molded hose to the 45° elbow molded into the top of the trap assembly. Clamp the hose tight with white nylon clamp.
IMPORTANT: Tighten all clamp connectionswith a pair of pliers and check for leaks after conversion is complete.
11. IMPORTANT: There are two options when choosing a height for the condensate riser:
CONDENSATE OVERFLOW: With a 1
3
4 inch riser installed above the tee, a blocked drain will result in overflow from the riser.
FURNACE SHUTDOWN: To cause the furnace to shut down when a blocked drain is present, install a riser which is a minimum
1
of 5
2”. If the furnace is installed in an attic, crawlspace or other area where freezing temperaturesmay occur, the furnace drain can freeze while shut off for long periods of time.
Use a solvent cement that is compatible with PVC material.
34
OVERFLOW LINE
(REQUIRED ONLY WHEN
OPTIONAL NEUTRALIZER
CARTRIDGE IS USED.)
TO FLOOR DRAIN OR CONDENSATE PUMP
DRAIN LINE
NEUTRALIZER CARTRIDGE
(OPTIONAL)
CONDENSATE TRAP
I408
I534
CONDENSATE TRAP CONVERSION FROM DOWNFLOW TO
HORIZONTAL INSTALLATION
FIGURE 36
HORIZONTAL POSITION: CONDENSATE TRAP INSTALLATION
FOR HORIZONTAL OPERATION
FIGURE 35
UPRIGHT POSITION: REMOVAL OF EXISTING DOWNFLOW CONDENSATE TRAP
35
GAS SUPPLY AND PIPING
GAS SUPPLY
WARNING
!
THIS FURNACE IS EQUIPPED AT THE FACTORY FOR USE ON NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES A SPECIAL KIT SUPPLIED BY THE DISTRIBUTOR OR MANUFACTURER. MAILING ADDRESS IS LISTED ON THE WARRANTY. FAILURE TO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. See the conversion kit index supplied with the furnace. This index identifies the proper LP Gas Conversion Kit required for each particular furnace.
IMPORTANT: Any additions,
changes or conversions required for the furnace to satisfactorily meet the applicationshould be made by a qualified installer, service agency or the gas supplier, using factory­specified or approved parts.
IMPORTANT: Connect this furnace only to gas supplied by a commercial utility.
IMPORTANT: A U.L. recognized fuel gas and carbon monoxide detector(s)are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations or customs.
FIGURE 37
GAS PIPING INSTALLATION
MAIN GAS
VALVE
4 TO 5 FEET ABOVE FLOOR REQ’D BY SOME UTILITIES.
GROMMET (IN NORMAL POSITION)
DRIP LEG
UNION
MAIN GAS
VALVE
4 TO 5 FEET ABOVE FLOOR REQ’D BY SOME UTILITIES.
GROMMET (IN NORMAL POSITION)
DRIP LEG
UPFLOW
TOP VIEW OF GAS LINE AND VALVE
IN OPT. POSITION
BURNERS
DOWNFLOW
TOP VIEW OF GAS LINE AND VALVE
IN OPT. POSITION
UNION
BURNERS
HORIZONTAL
MANUAL GAS VALVE
GAS VALVE
IGNITOR
GROMMET
NOTE: WHEN GAS LINE IS IN OPT. POSITION, SWAP LOCATION OF GROMMET AND PLUG.
OPT. GAS LINE POSITION
PLUG (IN NORMAL POSITION)
MANIFOLD PRESSURE TAP
IGNITOR
MANIFOLD
GROMMET
NOTE: WHEN GAS LINE IS IN OPT. POSITION, SWAP LOCATION OF GROMMET AND PLUG.
GAS VALVE
PLUG (IN NORMAL POSITION)
MANIFOLD PRESSURE TAP
MANIFOLD
I328
GAS PIPING
Install the gas piping according to all local codes and regulations of the utility company.
If possible, run a separate gas supply line directly from the meter to the furnace. Consult the local gas company for the location of the manual main shut-off valve. The gas
line and manual gas valve must be adequate in size to prevent undue pressure drop and never smaller than the pipe size to the com­bination gas valve on the furnace.
Refer to Table 3 for the recom­mended gas pipe size. See Figure 37 for typical gas pipe connections.
36
UNION
DRIP LEG
BURNERS
MANIFOLD
GAS VALVE
I524
IMPORTANT: DO NOT RUN A FLEXIBLE GAS CONNECTOR INSIDE THE UNIT. Extend the 1/2" black pipe from the gas valve to the outside of the cabinet. Connect any flexible gas connector from there to the gas piping.
Install a ground joint union inside the cabinet to easily remove the control valve assembly. Install a manual shut-off valve in the gas line outside the furnace casing.
The T-valve should be readily accessible to turn the gas supply on or off. Install a drip leg in the gas supply line as close to the furnace as possible. Always use a pipe compound resistant to the action of liquefied petroleum gases on all threaded connections.
IMPORTANT: When making gas pipe connections,use a back-up wrench to prevent any twisting of the control assembly and gas valve.
Any strains on the gas valve can change the position of the gas orifices in the burners. This can cause erratic furnace operation.
IMPORTANT: Do not run a flexible gas connector inside the unit. If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance. Massachusettslaw requires that all flexibile connectors be less than 36.
The gas pipe gasket in the cabinet does not seal around a flexi-ble gas connector. It is important to have all
openings in the cabinet burner compartment sealed for proper furnace operation.
IMPORTANT: ENSURE that the
furnace gas control valve not be subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual shut-off valve from the gas supply piping during any pressure
testing that exceeds 1/2 PSIG. (3.48 kPa).
TABLE 3
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of 0.60 (natural gas).
Nominal Length of Pipe, Feet Iron Pipe
Size, Inches 10 20 30 40 50 60 70 80
1/2 132 92 73 63 56 50 46 43 3/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 1-1/4 1,050 730 590 500 440 400 370 350 1-1/2 1,600 1,100 890 760 670 610 560 530
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be determined by consulting the local natural gas utility or the LP gas supplier.
however 6to 7is recommended. The minimum supply pressure is 11 w.c. for LP gas.
WARNING
!
NEVER PURGE A GAS LINE INTO THE COMBUSTION CHAMBER. NEVER USE MATCHES, FLAME OR
Gas Input of Furnace (BTU/HR) Heating Value of Gas (BTU/FT
3
)
pressure regulator to maintain proper manifold pressure.
A manual control is on the valve body. It can be set to only the “ON” or “OFF” positions. The gas valve is a slow-opening valve. See Figure 39.
When energized, it takes 6 to 8 seconds to fully open.
ANY IGNITION SOURCE FOR CHECKING LEAKAGE. FAILURE TO ADHERE TO THIS WARNING CAN CAUSE A FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
To check for gas leakage, use an approved chloride-free soap and
FIGURE 39
TYPICAL GAS VALVES
HONEYWELL
CONTROL REGULATOR
KNOB ADJUSTMENT
PRESSURE
water solution, an electronic com­bustible gas detector (see Figure 38), or other approved method.
GAS VALVE
This furnace has a 24-volt operated valve. It has ports for measuring supply pressure and manifold pressure. The valve body contains a
GAS PRESSURE
Natural gas supply pressure should be 5" to 10.5" w.c. LP gas supply pressure should be 11" to 13" w.c.
This pressure must be maintained with all other gas-fired appliances in operation.
CAUTION
!
ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE­CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE. THE BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED. SEE THE SECTION TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS BOOK FOR INSTRUCTIONS.
The minimum supply pressure to the gas valve for proper furnace input adjustmentsis 5w.c. for natural gas,
FIGURE 38
ELECTRONIC COMBUSTIBLE GAS DETECTOR
WHITE RODGERS
37
LP CONVERSION
NOTE: See Page 47 for Canadian High-AltitudeDerate
IMPORTANT: LP gas from trucks used to transport liquid-based fertilizerscan contain chemicals that will damage the furnace. Verify that your gas supplier does not use the same trucks to transport materials other than LP.
The valve can be converted to use liquified petroleum (LP) gas by replacing the pressure regulator spring with the conversion kit spring. This LP kit spring allows the regulator to maintain the proper manifold pressure for LP gas. See Figure 40.
NOTE: Order the correct LP conversion kit from the furnace manufacturer.Furnace conversion to LP gas must be performed by a qualified installer, service agency or the gas supplier.
ORIFICE INSTALLATION
LP Gas is a manufactured gas that has consistent heating value across most regions.
The Sea Level input should still be reduced by 3.5-4% per thousand ft. and the orifice size must be selected based on the reduced input selection chart below.
Altitude Orifice Size
0 to 5000 1.15 mm
5000-8000 1.10 mm
To change orifice spuds for either conversion to LP or for elevation:
1. Shut off the manual main gas valve and remove the gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for proper operation and manifold pressure. See Figures 41, 42 and 43.
5. Attach the notice label alerting the next service technician that the furnace has been converted to LP gas.
FIGURE 40
TYPICAL LP KIT CONTENTS
ORIFICE ORDERING INFORMATION
Orifice sizes are selected by adding the 2-digit drill size required in the orifice part number. Drill sizes available are 39 through 64; metric sizes available 1.10mm (-90) and
1.15mm (-91): Orifice Part Number 62-22175-(drill
size) Example 1:
#60 drill size orifice required Part # 62-22175-60
Example 2:
1.15mm drill size orifice required Part # 62-22175-91
90+ HIGH ALTITUDE INSTRUCTIONS
The GRC and GTC models do not require any changes for high altitude application,except L.P. conversion case.
See the L.P. conversion section on this page.
38
SETTING GAS PRESSURE
The maximum gas supply pressure to the furnace should be 10.5" w.c.
natural gas, or 13" w.c. LP gas. The
minimum supply gas pressure to the gas valve should be 5w.c. natural gas or 11w.c. LP gas. A properly calibrated U-Tube manometer is required for accurate gas pressure measurements.
CAUTION
!
ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE­CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE. THE BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED. SEE THE SECTION TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS BOOK FOR INSTRUCTIONS.
FIGURE 41
MANIFOLD PRESSURE TAP
Supply Gas Pressure Measure-
ment. A line pressure tap is on the
input side of the gas valve. See Figure 40.
1. With gas shut off to the furnace at the manual gas valve outside the unit, remove the input pressure tap plug.
2. Connect a U-Tube manometer to the pressure tap.
3. Turn on the gas supply and operate the furnace and all other gas-fired units on the same gas line as the furnace.
4. Note or adjust the line gas pressure to give:
A. 5- 10.5w.c. for natural gas. B. 11- 13w.c. for LP gas.
5. Shut off the gas at the manual gas valve and remove the U-Tube manometer.
6. Replace the pressure tap plug before turning on the gas.
If the supply gas line pressure is above these ranges, install an in-line gas regulator to the furnace for natural gas units. With LP gas, have the LP supplier reduce the line pressure at the regulator.
If supply gas line pressure is below these ranges, either remove any restrictionsin the gas supply piping or enlarge the gas pipe. See Tables 3 and 4. With LP gas, have the LP supplier adjust the line pressure at the regulator.
CAUTION
!
ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE­CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE. THE BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED. SEE THE SECTION TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS BOOK FOR INSTRUCTIONS.
TABLE 4
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure). (Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal Length of Pipe, Feet Iron Pipe
Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150
1/2 275 189 152 129 114 103 96 89 83 78 69 63 3/4 567 393 315 267 237 217 196 182 173 162 146 132
1 1,071 732 590 504 448 409 378 346 322 307 275 252 1-1/4 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 1-1/2 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787
2 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
Manifold Gas Pressure Measurement. Natural gas manifold pressure should be 3.5" w.c. LP gas manifold pressure
should be 10.0" w.c. Only small
variations in gas pressure should be made by adjusting the pressure regulator.
1. With the gas to the unit shut off at the manual gas valve, remove the pressure tap plug in the gas manifold. See Figure 41.
2. Connect a U-Tube manometer to this pressure tap. See Figure 42.
3. Turn on the gas supply and operate the furnace.
4. Note or adjust the manifold gas pressure to give:
A. 3.5w.c. for natural gas. B. 10.0w.c. for LP gas.
5. To adjust the pressure regulator, remove the regulator cap.
6. Turn the adjustment screw clockwise to increase pressure, or counterclockwise to decrease pressure.
7. Securely replace the regulator cap.
8. Shut off gas at the manual gas valve and remove the U-Tube manometer.
9. Replace the manifold pressure tap plug before turning on the gas.
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
39
FIGURE 42
MANIFOLD PRESSURE READING
FIGURE 43
UPFLOW GROUNDING CONNECTIONS
JUNCTION
BOX
CONDENSATE
TRAP
CONTROL IS GROUNDED
WHEN ATTACHED TO BLOWER
LOW VOLTAGE TERMINALS
IFC MOUNTING PLATE
BLOWER COMPARTMENT
I409-3
40
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
!
THE CABINET MUST HAVE AN UNINTERRUPTED GROUND ACCORDING TO THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, ANSI/ NFPA70- OR IN CANADA, THE CANADIAN ELECTRICAL CODE, CSA-C221 OR LOCAL CODES THAT APPLY. DO NOT USE GAS PIPING AS AN ELECTRICAL GROUND. A GROUND SCREW IS PROVIDED IN THE JUNCTION BOX. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
sense flame if L1 and L2 are reversed. See Figure 42.
Make all electrical connections in accordance with the latest edition of the National Electrical Code ANSI/NFPA70 and local codes having jurisdiction.
These may be obtained from: National Fire Protection
Association,Inc. BatterymarchPark Quincy, MA 02269
CSA - International 178 Rexdale Blvd. Etobicoke (Toronto), Ontario Canada M9W, 1R3
THERMOSTAT
The room thermostat must be com­patible with the integrated furnace control on the furnace. Generally, all thermostatsthat are not of the “current robbing” type are compatible with the
FIGURE 44
LINE VOLTAGE CONNECTIONS
UT ELECTRONIC CONTROLS 1028-928 CONTROL BOARD
integrated furnace control. The low voltage wiring should be sized as shown.
NOTE: Do not use 24 volt control wiring smaller than No. 18 AWG.
NOTE: An isolation relay can be added to prevent any compatibility problems that may occur. Use a single-pole,single-throwrelay with a 24-volt AC coil. The contacts should be rated for .5 amps minimum at 24 volts. See Figure 45.
Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat. Run the thermostat lead wires inside the blower compartment and connect to low voltage terminals as shown on the wiring diagram. Never install the thermostat on an outside wall or where it will be influenced by drafts, concealed hot or cold water pipes or ducts, lighting fixtures, radiation from
WARNING
!
THIS FURNACE IS EQUIPPED WITH A BLOWER DOOR SAFETY SWITCH. DO NOT DISABLE THIS SWITCH. FAILURE TO FOLLOW THIS WARNING CAN RESULT IN ELECTRICAL SHOCK, PERSONAL INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical components are protected from water (condensate).
Before proceeding with the electrical connections,be certain that the voltage, frequency and phase correspondsto that specified on the furnace rating plate. For single furnace application, maximum over­current protection is 15 amperes.
Use a separate fused branch electrical circuit containing a properly sized fuse or circuit breaker. Run this circuit directly from the main switch box to an electrical disconnect that is readily accessible and located near the furnace. Connect from the electrical disconnect to the junction box on the left side of the furnace, inside the blower compartment. For the proper connection, refer to the appropriatewiring diagram located on the inside cover of the furnace control box and in these instructions.
NOTE: UPFLOW MODELS ONLY
The electrical junction box may be moved to the right side if necessary. A knockout is provided. Seal the opposite hole with plug provided.
NOTE: L1(hot) and L2 (neutral) polarity must be observed when making field connections to the furnace. The ignition control may not
UT ELECTRONIC CONTROLS 1012-925 CONTROL BOARD
INVENSYS CLIMATE CONTROLS ICC-H1MC7-01 HOT SURFACE IGNITION, IFC
FIGURE 45
ISOLATION RELAY
I677
ST-A0804-01
41
fireplace, sun rays, lamps, televisions, radios or air streams from registers. Refer to instructions packed with the thermostat for “heater” selection or adjustment.
ACCESSORIES
FIELD-INSTALLED OPTION ACCESSORIES
ELECTRONIC AIR CLEANER
Line voltage power can be supplied from the screw terminal “EAC” and a line voltage neutral screw terminal on the control board. This will power the electronic air cleaner whenever the circulating air blower is in operation.
HUMIDIFIER
Line voltage power can be supplied from screw terminal “HUM” to a line voltage neutral screw terminal on the control board. This will power the humidifier whenever the burner is on and the circulating air blower is operating in the heating mode.
NOTE: Maximum current – 1.0 amps for each option.
ALTERNATE (LEFT SIDE) DRAIN KIT - RXGY-H01 (DOWNFLOW MODELS ONLY)
FURNACE TWINNING INSTALLATIONS
Twinning operation of two furnaces, installed side-by-side, connected by a common duct system with main power supplied by the same source, and controlled by a common thermostat can be done with the UT Electronic Controls 1028-928 integrated control boards.
IMPORTANT: Only twin furnaces with identical control boards.
IMPORTANT: Only bottom returns can be used. No more than two furnaces can share the same supply and return. Furnaces must have same heating and blower capacity. Twinning furnaces must operate off the same phase of power.
It should be noted that both blowers will run simultaneously when there is a call for heating, cooling or fan.
The “OK” LED will flash if twinning is not set up properly.
NOTE: Duct system must be adequate to provide correct airflow to each furnace for supply and return.
UT ELECTRONIC CONTROLS 1028-928 CONTROL BOARD
1. Single Stage Operation (See Figure 46)
a. Control board “ONE” is on
furnace connected to the thermostat.
b. The 24 VAC supply to both
control boards must be in phase with each other.
c. Connect the “C,” “W” and
“TWIN” terminals to counterpartson each control.
d. Both control boards must have
switch #3 in the “ON” position.
2. Two Stage Operation
(See Figure 47)
a. Follow above instructions.
Connect “W2” on thermostat to “W” on control board “TWO.”
42
FIGURE 46
UT Electronic Controls 1028-928 CONTROL BOARD, TWINNING CONNECTION -- SINGLE STAGE OPERATION
Control Board 1
Control Board 2
43
FIGURE 47
UT ELECTRONIC CONTROLS 1028-928 CONTROL BOARD, TWINNING CONNECTION -- TWO-STAGE OPERATION
Control Board 1
Control Board 2
44
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT
INPUT RATING FOR INSTALLATION AT ALTITUDES
BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION
DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
D'ALTITUDE.
92-24399-01-01
ALTERNATE METHOD FOR CANADIAN
HIGH-ALTITUDE
DERATE
In Canada, unless an orifice change is specificallymandated by local codes, an alternate method of altitude deration through a reduction in manifold pressure is acceptable as described in Table 8.
The information in Table 8 is based on a heating value of 1000 BTU per cubic feet of natural gas, and 2500 BTU per cubic feet of LP gas.
IMPORTANT: Actual input rates must be measured on-site with manifold pressure adjustment to ensure that an actual 10% reduction in input rate is achieved.
Once this field adjustment has been made, the label shown in Figure 48 must be affixed in a conspicuous location on the front of the furnace cabinet:
NOTE: This label is supplied in the informationpacket shipped with each furnace.
TABLE 7
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE IMPORTANT: 90 Plus Models only. Do not
use this chart for any 80 Plus Models
NATURAL GAS LP GAS
ORIFICE
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
45,000 60,000 75,000
90,000 105,000 120,000
40,500
54,000
67,500
81,000
94,500 108,000
OUTPUT
40,500 54,000 67,500 81,000 94,500
108,000
36,450 48,600 60,750 72,900 85,050 97,200
SIZE
#50
#50
MANIFOLD PRESSURE
3.5” W.C.
3.0” W.C.
ALTITUDE
0’ - 2000’
2001’ - 4500’
INPUT
45,000 60,000 75,000
90,000 105,000 120,000
40,500
54,000
67,500
81,000
94,500 108,000
OUTPUT
40,500 54,000 67,500 81,000 94,500
108,000
36,450 48,600 60,750 72,900 85,050 97,200
ORIFICE
SIZE
1.15mm
1.15mm
MANIFOLD PRESSURE
10” W.C.
7.6” W.C.
FIGURE 48
MANIFOLD PRESSURE-CHANGE LABEL
45
START-UP PROCEDURES
This furnace is equipped with a direct ignition device. Each time the room thermostat calls for heat, the ignitor lights the main burners directly. See the lighting instructions on the furnace.
TO START THE FURNACE
1. Remove the burner compartment control access door.
2. IMPORTANT: Be sure that the manual gas control has been in the “OFF” position for at least five minutes. Do not attempt to manually light the main burners.
3. Turn off the furnace electrical power and set the room thermostat to its lowest setting.
4. Turn the gas control knob to the “ON” position or move the gas control lever to the “On” position.
5. Replace the burner compartment control access door.
6. Turn on the furnace electrical power.
7. Set the room thermostat to a point above room temperature to light the main burners.
8. After the burners are lit, set the room thermostat to a desired temperature.
TO SHUT DOWN THE FURNACE
1. Set the room thermostat to its lowest setting and wait for furnace to shut down.
2. Remove the burner compartment control access door.
3. Shut off the gas to the main burners by turning the gas control knob to the “OFF” position. See Figure 37.
WARNING
!
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, CLOSE THE MANUAL GAS VALVE FOR THE APPLIANCE BEFORE SHUTTING OFF THE ELECTRICAL SUPPLY. FAILURE TO DO SO CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SEQUENCE OF OPERATION
UT ELECTRONIC CONTROLS & INVESYS CLIMATE CONTROLS
Integrated Controls with Hot Surface Ignition.
1. Each time the thermostat “W” (Heating) contacts close, the induced draft blower (inducer) begins a prepurge cycle.
2. The air proving negative pressure switch(es) closes.
3. 5 seconds after the pressure
switch(es) close, the hot surface igniter begins heating for 30
seconds to full temperature. The
induced draft blower operates for the complete heating cycle.
4. After the 30-second igniter warm up,
the gas valve opens for an 8-second trial for ignition.
5. The igniter lights the gas burners and stays energized for the first 7
seconds after the gas valve opens.
6. 8 seconds after the gas valve opens
the remote flame sensor must prove flame ignition for one
second using the process of flame rectification. If the burners don’t light, the system goes through another ignition sequence. It does this up to four times.
7. The main blower starts approximately 20 seconds after the burners ignite.
8. When the thermostat “W” (Heat Call) ends, the gas valve closes, the burners go out, the induced draft blower stops after a 10-second post-purge, and the negative pressure switch(es) open.
9. The main blower continues until timed off by the setting on the integrated furnace control board.
Sequence if the system doesn’t light or doesn’t sense flame:
1. On a call for heat, the control runs the inducer for 35 seconds to prepurge.
2. 5 seconds into prepurge, the hot surface igniter heats for 30 seconds. The inducer continues to run.
3. After the 30-second igniter warm up, the gas valve opens for an 8-second trial for ignition. The inducer continues and the igniter stays energized.
4. If flame is not sensed during the 8th second after the gas valve opens, the gas valve closes, and the igniter de-energizes.
5. After a 10-second post-purge, the inducer stops and the control verifies that the pressure switch has opened. Once the open pressure switch is confirmed, the control begins the next ignition cycle by energizing the inducer for a pre-purge of 30 seconds. After the 30-second pre­purge, the igniter energizes and begins a 30-second warm-up period (inducer is still running). After a 30­second igniter warm-up period (60 sec. of ind. running), the gas valve opens and the control looks for a flame signal for up to 8 seconds. If no flame is sensed, the control goes into “self-healing” mode, in which the blower and inducer both run for three minutes before another ignition attempt is made.
NOTE: The following applies only to units manufactured before third
Quarter 2003: After 5-second inter-
purge, the control begins a 30­second pre-purge followed by a 30­second igniter warm-up period (inducer is still running). After the 30-
second igniter warm-up period, the gas valve opens and the control looks for a flame signal for up to 8 seconds. If no flame is sensed, the control goes into “self-healing” mode, in which the blower and inducer both run for three minutes before another ignition attempt is made.
6. The control attempts to ignite up to four times (first attempt followed by three retries). After the fourth failure to ignite, the control goes into a one-hour “soft-lockout,” during which the control will not respond to the thermostat heat call (W). The lockout can be reset by shutting off main power to the furnace for five seconds, or by turning the heat call (W) from the thermostat off and then back on. Note that second and fourth ignition attempts will have a 30­second pre-purge followed by a 30­second igniter warm-up period. This prevents the igniter from overheating.
7. The above sequence will repeat after a one hour delay. It will continue repeating until ignition is successful or the call for heat is terminated.
8. To reset the lock out, make and
break power either at the thermostat or at the unit disconnect switch for 5 to 10
seconds. It then goes through
another set of trials for ignition.
UT Electronic Controls Direct Spark Ignition
1. Each time the thermostat contacts close, the induced draft blower (inducer) begins a prepurge cycle.
2. The air proving negative pressure switch(es) closes.
3. 30 seconds after the pressure
switch(es) close, the spark
igniter energizes. The induced
draft blower operates for the complete heating cycle.
4. After the spark igniter energizes, the gas valve opens for a 8
second trial for ignition.
5. The igniter lights the gas burners.
6. After the gas valve opens the
flame sensor must prove flame
ignition for one second using the
process of flame rectification. If the burners don’t light, the system goes through another ignition sequence. It does this up to four times.
7. The main blower starts 20 seconds after the burners ignite.
8. When the thermostat cycle ends, the gas valve closes, the burners go out, the induced draft blower stops after a 10-second post- purge, and the negative pressure switch(es) open.
9. The main blower continues until timed off by the setting on the integrated furnace control board.
46
Sequence if the system doesn’t light or doesn’t sense flame:
1. On a call for heat, the control runs the inducer for 30 seconds to pre-purge.
2. After the 30-second pre-purge, the spark igniter energizes. The inducer continues to run.
3. After the spark igniter energizes, the gas valve opens for an 8­second trial for ignition. The inducer continues and the igniter stays energized.
4. If flame is not sensed within 8 seconds after the gas valve opens, the gas valve closes, the igniter de-energizes and:
5. The inducer completes a 10­second post-purge, the inducer stops, and the control verifies that the pressure switch has opened. Once the open pressure switch is confirmed, the control begins the next ignition cycle by energizing the inducer for a pre-purge of 30 seconds. After the pre-purge, the igniter energizes and the gas valve opens (inducer continues to run). If no flame is sensed on the second attempt, the control goes into a “self-healing” mode, in which the blower and the inducer run for 3 minutes before another ignition attempt is made.
NOTE: The following applies only to units manufactured
before third Quarter 2003: After
a 30-second inter-purge (inducer runs continuously), the igniter is energized, and the gas valve opens for 8 seconds. If flame is not sensed in 8 seconds, the gas valve is closed and the igniter de­energizes. If no flame is sensed on this second attempt, the control goes into a “self-healing” mode, in which the blower and inducer run for 3 minutes before another ignition attempt is made.
6. The control attempts to ignite up to four times (first attempt followed by three retries). After the fourth failure to ignite, the control goes into a one-hour “soft-lockout” during which the control will not respond to the thermostat heat call (W). The lockout can be reset by shutting off main power to the furnace for five seconds, or by turning the heat call (W) from the thermostat off and then back on.
7. The above sequence will repeat after a one hour delay. It will continue repeating until ignition is successful or the call for heat is terminated.
8. To reset the lock out, make and break power either at the thermostat or at the unit disconnect switch for 5 to 10 seconds. It then goes through another set of trials for ignition.
TABLE 8
METER TIME
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES
METER
INPUT SIZE
BTU/HR CU. FT. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
45,000 TEN 12 0 13 20 13 50 14 40 33 20
60,000 TEN 9010 0 10 24 11 0 25 0
75,000 TEN 7 12 80819 8 48 20 0
90,000 TEN 60640 70720 16 40
105,000 TEN 5 10 5 40 60620 14 20
120,000 TEN 4 30 50510 5 30 12 30
Formula: Input BTU/HR =
ADJUSTING OR CHECKING FURNACE INPUT
The maximum gas supply pressure to the furnace should be 7" w.c. for natural gas. The minimum gas supply pressure for purposes of input adjustment to the furnace should be 5" w.c.
A properly calibrated magnehelic gauge or manometer is required for accurate gas pressure readings.
The manifold pressure should be set at 3.5" w.c. for natural gas. Only small variations in the gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or
EQUIPPED FOR NATURAL OR LP GAS
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500 (LP)
ONE 1 12 1 20 1 23 1 28 3 20
ONE 0 54 101316230
ONE 0 44 0 48 0 50 0 53 20
ONE 0 36 0 40 0 42 0 44 1 40
ONE 0 31 0 34 0 36 0 38 1 26
ONE 0 27 0 30 0 31 0 33 1 15
3
Heating Value of Gas (BTU/FT
Time in Seconds (for 1 cu. ft.) of Gas
) x 3600 x correction factor
ratings apply. For high altitudes (elevations over 2,000 ft.), see conversion kit index for derating and orifice spud sizes.
Checking furnace input is important to prevent over firing beyond its design-rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate. Start the furnace and measure the time required to burn one cubic foot of gas. Prior to checking the furnace input, make certain that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.
minus 0.3" w.c. from the above­specified pressures. To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace the regulator cap securely. Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices.
To change orifice spuds, shut off the manual gas valve and remove the gas manifold. On LP gas furnaces, the LP gas supply pressure must be set between 11" and 14" w.c. by means of the tank or branch supply
SETTING INPUT RATE
The furnace is shipped from the factory with #50 orifices. They are sized for natural gas having a heating value of 1075 BTU/cu. ft. and a specific gravity of .60.
Since heating values vary geo­graphically, the manifold pressure and/or gas orifice size may need to be changed to adjust the furnace to its nameplate input. Consult the local gas utility to obtain the yearly average heating value and orifice size required to fire each individual burner at 15,000 BTU/HR.
regulators. The furnace manifold pressure should be set at 10" w.c. at the gas control valve. For elevations up to 2,000 feet, rating plate input
NOTE: Refer to the National Fuel Gas Code for high altitude rate adjustment above 2,000 ft.
47
AIR FLOW
The importance of proper air flow over the heat exchanger cannot be over emphasized.
CAUTION
!
IT IS IMPORTANT THAT EACH DUCT SYSTEM BE SIZED AND INSTALLED FOR THE SPECIFIC APPLICATION BY PROPERLY APPLYING THE APPROPRIATE INDUSTRY ACCEPTED STANDARD. IF LESS THAN MINIMUM STANDARDS ARE APPLIED, THE EQUIPMENT USER COULD EXPECT TO EXPERIENCE HIGHER UTILITY BILLS, MAJOR COMPONENT FAILURE, VARYING DEGREES OF AIR NOISE OR OTHER UNSATISFACTORY ISSUES, OVER WHICH THE MANUFACTURER HAS NO CONTROL.
TEMPERATURE RISE CHECK
To determine if the air flow is correct, make a temperature rise check.
1. Insert a thermometer in the supply
air duct as close to the furnace as possible yet out of a direct line from the heat exchanger. See Figure 49.
2. Insert a thermometer in the return air
duct as close to the furnace as possible.
3. Operate the furnace.
4. When the thermometer in the supply
air duct stops rising (approximately five minutes), subtract the return air temperaturefrom the supply air temperature.The difference is the temperaturerise.
5. Compare the measured temperature
rise to the approved temperature rise range listed on the furnace name plate. See Figure 50.
If the measured temperature rise is above the approved range, the air flow is too low. More air must be moved by speeding up the blower, by removing restrictionsin the duct system, or by adding more supply or return air duct. If the measured temperaturerise is below the approved range, the air flow is too much. Use lower speed tap on the multi-speed blower.
FIGURE 49
TEMPERATURE RISE MEASUREMENT
FIGURE 50
TYPICAL FURNACE NAME PLATE
INSTALLER MUST ADJUST THE TEMPERATURE RISE TO THIS "MIDDLE" POINT AS CLOSELY AS POSSIBLE. ALSO, THE TEMPERATURE RISE SHOULD NEVER BE ABOVE OR FALL BELOW THE STATED RANGE. DOING SO COULD CAUSE DAMAGE TO THE HEAT EXCHANGER OR INTERMITTENT OPERATION WHICH COULD CAUSE INJURY OR DEATH AND WILL VOID THE MANUFACTURER'S WARRANTY FOR THIS PRODUCT.
AIR CONDITIONING DIVISION
FORT SMITH, ARKANSAS
WARNING
!
THE MEASURED TEMPERATURE RISE SHOULD BE AS CLOSE TO THE MIDDLE OF THE STATED RANGE AS POSSIBLE. FOR EXAMPLE, IF THE RISE RANGE IS 40 TO 70 DEGREES, THE MOST IDEAL RISE WOULD BE 55 DEGREES (THE MIDDLE OF THE RISE RANGE). IN ALL APPLICATIONS, THE
48
TABLE 10
90 PLUS AIR FLOW PERFORMANCE – (-)GRC & (-)GTC MODELS
Model
(-)GRC-04 1/2 [373] Med. Lo 920 885 850 810 775 730 690
EMAES 11 x 7 Med. Hi 1140 1110 1085 1045 1010 950 890
(-)GRC-06 1/2 [373] Med. Lo 880 845 815 790 760 715 670
EMAES 11 x 7 Med. Hi 1060 1025 990 960 925 880 835
(-)GRC-07 1/2 [373] Med. Lo 880 850 825 785 750 702 655
EMAES 11 x 7 Med. Hi 1090 1050 1010 970 925 875 825
(-)GRC-07 1/2 [373] Med. Lo 1326 1315 1304 1270 1236 1197 1157
ERBGS 11 x 10 Med. Hi 1535 1512 1488 1453 1418 1373 1327
(-)GRC-09 3/4 [559] Med. Lo 1442 1416 1390 1360 1329 1288 1247
EZAJS 12 x 11 Med. Hi 1666 1637 1606 1554 1501 1456 1407
(-)GRC-10 3/4 [559] Med. Lo 1490 1445 1405 1375 1350 1295 1240
EZAJS 12 x 11 Med. Hi 1710 1665 1620 1570 1540 1475 1410
(-)GTC-04 1/2 [373] Med. Lo 890 866 842 811 779 750 721
EMAES 11 x 7 Med. Hi 1110 1084 1057 1023 989 946 902
(-)GTC-06 1/2 [373] Med. Lo 924 895 866 832 798 754 710
EMAES 11 x 7 Med. Hi 1164 1122 1080 1044 1008 966 923
(-)GTC-07 1/2 [373] Med. Lo 1338 1309 1280 1253 1225 1185 1145
ERBGS 11 x 10 Med. Hi 1555 1516 1477 1440 1402 1349 1295
(-)GTC-09 3/4 [559] Med. Lo 1504 1474 1443 1415 1387 1348 1308
EZAJS 12 x 11 Med. Hi 1734 1698 1662 1621 1579 1526 1472
(-)GTC-10 3/4 [559] Med. Lo 1617 1595 1573 1533 1493 1448 1402
ERBJS 11 x 10 Med. Hi 1842 1812 1781 1728 1674 1619 1564
Blower Size
IN [MM]
[279 x 178] High 1360 1320 1280 1235 1195 1140 1080
[279 x 178] High 1260 1215 1175 1135 1100 1040 985
[279 x 178] High 1300 1255 1210 1160 1110 1055 1005
[279 x 254] High 1765 1723 1681 1639 1596 1544 1492
[305 x 279] High 2040 1993 1946 1888 1829 1758 1686
[305 x 279] High 2010 1955 1900 1855 1810 1710 1610
[279 x 178] High 1383 1350 1317 1274 1230 1171 1112
[279 x 178] High 1409 1367 1325 1284 1242 1195 1148
[279 x 254] High 1743 1696 1649 1604 1559 1501 1442
[305 x 279] High 2111 2059 2007 1946 1885 1821 1756
[279 x 254] High 2204 2153 2102 2040 1977 1905 1833
Spd Tap
Low 805 780 760 720 685 645 605
Low* 770 740 710 675 645 605 570
Low* 780 745 710 675 640 595 555
Low* 1115 1091 1067 1044 1020 984 948
Low* 1199 1183 1167 1132 1097 1062 1026
Low* 1230 1205 1160 1155 1130 1090 1050
Low* 794 765 735 704 672 633 594
Low* 816 792 767 739 711 686 661
Low* 1126 1097 1068 1036 1003 963 923
Low* 1213 1196 1179 1158 1136 1108 1079
Low* 1324 1309 1294 1272 1250 1221 1191
0.1 0.2 0.3 0.4 0.5 0.6 0.7
Motor HP [W]
External Static Pressure, Water Column
CFM Air Delivery
49
SETTING BLOWER TIMINGS
The Honeywell UT ELECTRONIC CONTROLS and Invensys Climate Controls IFC’S (Integrated Furnace Controls) have three or four quick connect terminals for connecting the motor speed leads. These are:
1. FAN SPEED — motor runs on
this speed when the thermostat is in the “FAN ON” position.
2. COOL — connect desired
cooling speed.
3. HEAT — connect desired
heating speed.
4. HEAT/COOL (not available on
UT Electronic Controls-1028-925 control board) or Invensys Climate Controls ICC-H1MC7-01 — connect desired speed when heating and cooling speed are the same.
IMPORTANT: Do not connect any motor speeds to “HEAT” and “COOL” if you use the “HEAT/COOL” terminal.
5. If heating and continuous fan
speed are the same, “piggyback” jumper across “FAN” and “HEAT” terminals.
See Figures 51, 52 & 53 for instructionsfor setting the blower “OFF” timings.
If cooling speed and fan speed are desired to be the same, this may be accomplishedby not connecting “Y” to the integrated furnace control.
If desired for cool, fan and heat to all be the same speed, then “piggyback” jumper “H/C” to “FAN” and do not connect “Y” to the integrated furnace control. Do not connect anything to “H” or “C.”
FIGURE 51 UT Electronic Controls 1028-928 BLOWER OFF TIMINGS
TWINSINGLE
ON
NOTE: SWITCH 3 IS USED FOR TWINNING APPLICATIONS.
I402
OFF TIME SWITCH 1 SWITCH 2
90 SEC. OFF ON
120 SEC. OFF OFF
160 SEC. ON OFF
180 SEC. ON ON
FIGURE 52 UT Electronic Controls 1012-925A & Invensys Climate Controls ICC-H1MC7 BLOWER OFF TIMINGS
(TIMER IS RED BLOCK ON BOARD)
I335
OFF TIME SWITCH 1 SWITCH 2
90 SEC. OFF ON
120 SEC. OFF OFF
160 SEC. ON OFF
180 SEC. ON ON
FIGURE 53 UT Electronic Controls 1012-925B BLOWER OFF TIMINGS
GAS FURNACE (DIRECT DRIVE) INSTRUCTIONS FOR CHANGING BLOWER SPEED
WARNING
!
DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE BEFORE ATTEMPTING TO CHANGE THE BLOWER SPEED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
The blower motor is wired for blower speeds required for normal operation as shown.
If additional blower speed taps are available (leads connected to “M1” and “M2” on the electronic control), speeds may be changed if necessary to fit requirements of the particular installation.Reconnect the unused motor leads to “M1” or “M2.” Check motor lead color for speed designation.
Heating speeds should not be reduced where it could cause the furnace air temperature to rise to exceed the maximum outlet air temperaturespecified for the unit.
IMPORTANT: Always check air temperaturerise after changing the heating speed for any reason.
50
MAINTENANCE
TABLE 9
FILTER SIZES
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING ANY MAINTE­NANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
UPFLOW FILTER SIZES
FURNACE INPUT BOTTOM SIDE
WIDTH MBTUH SIZE SIZE
1
17
2" 45, 60, 75 153⁄4" X 25" 153⁄4" X 25" 1
21" 90, 105 19
DOWNFLOW FILTER SIZES
FURNACE INPUT
WIDTH MBTUH
1
17
2" 45, 60, 75 12" X 20" 2
21" 90 12" X 20" 2
1
2" 105 14" X 20" 2
24
1
4" X 25" 153⁄4" X 25" 1
SIZE QUANTITY
FILTERS
Keep the filters clean at all times. Vacuum dirt from filter, wash with detergent and water, air dry thoroughly and reinstall.
Keep the filters clean at all times. Vacuum dirt from filter, wash with detergent and water, air dry thoroughly and reinstall.
NOTE: Somefilters must be resized to fit certain units and applications. See Table 11 and Figures 54 and 55.
1. 21” - 90,000 & 105,000 BTUH units require removal of a
QUANTITY
3.5-in. segment of filter and frame to get the proper width for a side filter.
2. 24.5” - 105,000 BTUH unit requires removal of a 7" segment of filter and frame to get the proper width for a side filter.
CAUTION
!
DO NOT OPERATE THE SYSTEM FOR EXTENDED PERIODS WITHOUT FILTERS. A PORTION OF THE DUST
FIGURE 54
BOTTOM PANEL REMOVAL
JACKET ASSEMBLY
SOLID BOTTOM
SCREW (2) REQ’D.
NOTE: BACK FLANGE OF SOLID BOTTOM FITS UNDERNEATH JACKET. SIDES AND FRONT FLANGES FIT OVER FLANGES ON JACKET.
SOLID BOTTOM REMOVAL
JACKET ASSEMBLY
FILTER
FILTER & ROD LOCATION
FILTER ROD
51
FIGURE 55
DOWNFLOW
JACKET
DRILL (2) 3/16" DIA. HOLES
8.000
4.875
1.531
JACKET
JACKET
ANGLE
FILTER ROD SUPPORT ANGLE
FILTER SUPPORT ANGLE (SEE ANGLE DETAIL)
ATTACH WITH SHEET METAL SCREWS (2 REQÕD)
ANGLE DETAIL
CUT-OUT AND DRILL DETAIL
ROD & FILTER SUPPORT ANGLE ASSEMBLY
FILTER AND ROD ASSEMBLY
FILTER ROD SUPPORT ANGLE
FILTER SUPPORT ANGLE
FILTER
FILTER ROD
JACKET
I332
I413
UPFLOW
I528
HORIZONTAL
FILTER LOCATIONS
FILTER ROD SUPPORT ANGLE
FILTER SUPPORT ANGLE
FILTER SUPPORT ANGLE (SEE ANGLE DETAIL)
FILTER ROD SUPPORT ANGLE
FILTER
FILTER ROD 45-24095-01
52
ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY RECIRCULATED DUST PARTICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES.
LUBRICATION
IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the warranty.
The blower motor and induced draft blower motor are permanently lubricated by the manufacturer and do not require further attention.
The blower motor and induced draft blower motor must be cleaned periodicallyby a qualified installer, service agency, or the gas supplier to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. And, as suggested elsewhere in these instructions, the air filters should be kept clean. Dirty filters can restrict airflow. The motor depends upon sufficient air flowing across and through it to keep from overheating.
SYSTEM OPERATION INFORMATION
Advise The Customer
1. Keep the air filters clean. The heating system will operate better, more efficiently and more economically.
2. Arrange the furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
3. Close doors and windows. This will reduce the heating load on the system.
4. Avoid excessive use of kitchen exhaust fans.
5. Do not permit the heat generated by television, lamps or radios to influence the thermostat operation.
6. Except for the mounting platform, keep all combustible articles 3 feet from the furnace and vent system.
7. IMPORTANT: Replace all blower doors and compartment covers after servicing the furnace. Do not operate the unit without all panels and doors securely in place.
8. Explain proper operation of the system with constant air circulation.
ANNUAL INSPECTION
• The furnace should operate for many years without excessive scale build-up in the flue passageways. However, it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the vent system and the main burners for continued safe operation. Pay particular attention to deterioration from corrosion or other sources.
IMPORTANT: It is recommended that at the beginning and at approximatelyhalf way through the heating season, a visual inspection be made of the main burner flames for the desired flame appearance by a qualified installer, service agency or the gas supplier. If the flames are distorted and/or there is evidence of back pressure, check the vent and inlet air system for blockage. If there is carbon and scale in the heat exchanger tubes, the heat exchanger assembly should be replaced.
WARNING
!
HOLES IN THE VENT PIPE OR HEAT EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME, RESULTING IN CARBON MONOXIDE POISONING OR DEATH. THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK.
• IMPORTANT: It is recommended
that at the beginning of the heating season, the flame sensor be cleaned with steel wool by a qualified installer, service agency or the gas supplier.
• IMPORTANT: It is recommended that at the beginning of the heating season, the condensate trap be inspected for debris or blockage. A blocked condensate trap can cause water to back up into the primary heat exchanger and lead to nuisance tripping of the overtemperature switches.
• IMPORTANT: It is recommended that at the beginning of the heating season, the condensate neutralizer if used be replaced by a qualified installer, service agency or the gas supplier.
• IMPORTANT: It is recommended that an annual inspection and cleaning of all furnace markings be made to assure legibility. Attach a replacementmarking, which can be obtained through the distributor, if any are found to be illegible or missing.
REPLACEMENT PARTS
See sheet enclosed with furnace for replacementpart information.
TROUBLESHOOTING
Refer to Figures 56 for determining cause of unit problems.
WIRING DIAGRAMS
Figures 57 through 60 are complete wiring diagrams for the furnace and power sources.
53
FIGURE 56
GO TO
E
WARNING
INTEGRATED FURNACE CONTROL (IFC)
TROUBLESHOOTING GUIDE
HAZARDOUS VOLTAGE
LINE VOLTAGE
CONNECTIONS
DISCONNECT POWER BEFORE SERVICING. SERVICE MUST BE BY A TRAINED, QUALIFIED SERVICE TECHNICIAN.
NOTE: Most failures are not due to the IFC. Double check all other possibilities, including the ground connection, before replacing the IFC.
NOTE:
Always verify gas valve inlet and outlet gas
pressure.
KEY TO ABBREVIATIONS
IBM = Indoor Blower Motor IDM = Induced Draft Motor IFC = Integrated Furnace Control PS = Pressure Switch(es) SE = Spark Electrode HSI = Hot-Surface Ignition DSI = Direct-Spark Ignition
FLAME (AMBER) LED CODES
OFF = No Flame Present RAPID BLINK = Unexpected Flame SLOW BLINK = Marginal Flame Sense STEADY ON = Normal Flame Sense
BLINK CODES (GREEN LED)
1 Blink - Soft lockout
Reset System power and start over from beginning
2 Blinks - PS Circuit open
go to point “F.”
3 Blinks - Limit circuit open
go to point “D.”
4 Blinks - PS Circuit closed
Go to point “G.”
5 Blinks - Twin Fault (Optional)
*Go to point “H.”
1) Set FAN switch to “AUTO”
2) Set thermostat to call for heat (set temp. differ­ential to greater than 10°F
Does the IDM Energize?
IDM Runs for 30 sec. pre-purge?
Spark Ignitor Electrode (SE) Energizes
or HSI Ignitor Glowing?
Does Main Burner Light and stay lit?
Is the gas valve energized?
PS dropping out?
Check IFC*
Does IBM start on heat speed 20 seconds
after burners light?
Does main burner remain lit until
heat call ends?
Does thermostat maintain reasonable room
temperature near setpoint?
Set thermostat to off position (W to C = ØV)
Does gas valve shut off immediately?
Does IDM shut off after ten second post-purge?
Does IBM shut off after a max. of 3 min?
END
Heat-mode troubleshooting
“POWER” LED ON?
24V on W to IFC?
Is “STATUS” LED blinking,
steady-on, or off?
Check IFC*.
Check IFC*.
Does IDM run indefinately.
Does IDM Run for 60 sec. and then off for Five minutes
- Check thermostat in “heat” mode, battery, wire, and connections.
SEE BLINK CODES
- Check 24V at IFC.
- Check Fuse.
- Check Door Switch and Line Power.
- Check Transformer.
- Check Breaker.
- Check PS contacts
- Check wires for short.
- Check IFC*.
- Check switches and hoses for water or moisture
- For Twinned units, check that both IFCs are set for “TWIN” and wires are connected between “TWIN” terminals.
- Check IFC*.
- For twinned units, ensure transformers are in phase. (if out of phase, flame LED will be dim).
- For non-twinned units, ensure “TWIN” is in the single (OFF) position.
- For Twinned units – ensure both IFC‘s have same part number.
- Check PS, PS Hoses, and wires.
- Check for blocked vent, excessive vent length or elbows, or blocked heat exchanger.
- Check IDM wired correctly.
- Ensure against excessive wind, which can open pressure switch.
- If downflow 90+, check aux. limit – shoud be closed
- Check for intermittent P.S. operation.
- Check switches and hoses for water or moisture.
- Check gas supply and manifold pressure.
- Ensure L1 and Neutral not swapped on IFC and junction box.
- Check SE alignment.
- Check orifice or other restrictions to gas flow.
- Check flame sense rod (clean with sandpaper).
- Check flame carry over.
- Check wires, continuity, and connection between IFC and gas valve.
- Ensure 24 V between appropriate pins on connector of IFC.
- Ensure manual switch on valve is in the “ON” position.
- 90+ check aux. limit open? Should be closed
- 90+ upflow models – check drain pressure switch between IFC and gas valve – should be closed – replace drain pressure switch if drain is not blocked or clear drain if blocked.
- Did a pressure switch open during ignition trial? If yes, go to F
- Did a limit open during ignition trial? If yes, go to D
- Check line voltage between “HEAT” and “NEUTRAL” on IFC.
- Check wires, connections, and continuity between IFC and IBM.
- Check IBM capacitor.
- Check IBM.
CHECK:
- grounding on IFC and unit.
- check for proper polarity between L1 & neutral.
- flame sense rod (clean if necessary).
- wire continually between flame sense rod and appropriate pin of connector on IFC
- flame carries across all burners, and all burners stay lit.
CHECK: AIRFLOW - ensure no restrictions, such as dirty filter, dampers, closed registers, etc. LIMITS - ensure good wire and connections between IFC and all limits. Make sure limits are not open when circulating air temperature is within a specified range. ROLLOUTS - ensure rollouts or overtemperature limits do not need to be reset. Make sure no flame rollout in burner compartment due to blocked flu or heat exchanger. OVERFIRE - ensure furnace is not overtemperature (temp rise is above stated range). Check gas valve, proper orifice size, gas pressure, etc.
Is Limit circuit or IDM wire through aux. limit open or opening and closing? Note: IFC Status LED should be blinking a Fault Code 3.
Is the IFC sensing a good flame: NOTE: Flame sense light should be steady-on when burners are lit. If flame LED blinking, or off, flame sense is low or absent.
Ensure thermostat is properly placed and not improperly affected by registers, fans, sunlight, heat through walls, pipes, or wires in walls.
- Check heat anticipator setting. Furnace may need an isolation relay.
- Check installation instructions under section titled “Isolation Relay” for details.
- Verify correct furnace sizing.
NOTE: If IFC goes into lockout (“STATUS LED will blink code “1”), shut off main power to unit, wait 30 seconds and then reset power.
PROBLEM
STILL
PRESENT
“STATUS” LED
BLINKING
“FLAME” LED BLINKING OR STEADY ON
If “E” did not resolve issue
Double check - Is W off at IFC?
(W to C = ØV?)
Voltage present at gas valve?
- Check gas valve.
SEE BLINK CODES
- Check IFC*.
Check IFC*.
*Most failures are not due to the IFC. Double check all other possibilities, including the ground connection or wire connections, before replacing the IFC.
Ensure TSTAT is not in “FAN” position. Is “STATUS” LED blinking? Is “FLAME” LED blinking or steady-on?
**System will attempt to light 4 times. Voltage is present at gas valve for only 7 seconds dur­ing each trial for ignition. The entire system will go into a 1 hour lockout after 4 attempts. The main blower and IDM will run 180 seconds between 2nd and 3rd ignition attempts.
- Check line voltage at IDM.
- Check wires and connections between IDM and IFC.
- Ensure line voltage on IDM pins of IFC connector.
- Check IDM capacitor (90+ only).
CHECK BLINK CODES
- Check for open limit or limit circuit.
- Check for intermittent PS operation.
- Check for vent restrictions.
- Ensure vent lengths not excessive or too small diameter.
- Check for blocked heat exchanger.
FOR SPARK IGNITION
- Check SE wire & connections.
- Clean SE with sandpaper. Replace SE if necessary.
- If problem persists, check IFC*.
- Check SE gas and proper SE ground.
- Check SE wire for spark arcing to metal before electrode.
FOR HOT SURFACE IGNITION
- Check ignitor connected.
- Check ignitor wires.
- Check ignitor resistance. If open circuit, low or high resistance, replace.
- Check ignitor for fractures or cracking
- Check ignitor placement.
- If problem persists, check IFC*.
START
REPEAT THIS PROCEDURE UNTIL TROUBLE-FREE OPERATION IS OBTAINED.
NO
NO
NO
If “
I
” did not
resolve issue.
NO NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
BLINKING
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
STEADY-ON
I
D
F
H
E
G
YES
NO
YES
PREPURGE
IGNITION TRIAL
IBM “ON” DELAY
STEADY HEAT
END HEAT CALL
POST-PURGE
IBM “OFF” DELAY
STEADY OFF
NO
OFF
**
92-101654-01-00
GO TO
F
GO TO
I
(-)GRC/(-)GTC MODELS W/INTEGRATED FURNACE CONTROL (IFC) UT Electronic Controls 1012-925 (115 VAC IGNITER)
54
FIGURE 57
(-)GRC MODELS WITH UT ELECTRONIC CONTROLS 1028-928 & SPARK IGNITION
55
FIGURE 58
(-)GTC MODELS WITH UT ELECTRONIC CONTROLS 1028-928 & SPARK IGNITION
56
CM 0709
Loading...