Rheem G100-200-A, G100-270-A, G100-250-A, G85-400-A, G76-200 User Manual

...
Power Vent Kits for Gas Commercial Water Heaters
Manufactured by Tjernlund Products,* Rheem-Ruud commercial gas water heater power vent kits are your best choice for new construction, electric-to-gas conversions and renovations.
Construction Features:
• Certified for use on natural and propane gas models.
• Vent terminal can be installed through combustible
Power Venter (from Tjernlund)
or non-combustible surfaces – heat shield is provided.
• Vent terminal is constructed from heavy-duty corrosion resistant aluminum.
Vent Terminal
Not for use with GN or GX models
• Venter can be connected to a vent termination on an exterior wall.
• Vibration isolators are supplied to provide quiet operation.
• Safety interlocks standard.
• Complete with mounting hardware.
• Venter is pre-wired with 40 feet of #18-4 copper wire (24 volt) to minimize field connections.
Certifications and Ratings:
• Power vent kits manufactured by Tjernlund Products, Inc. are tested and certified by AGA for use on Rheem-Ruud commercial gas water heaters.
*For technical assistance, please call the Tjernlund Help Line at
1-800-255-4208
Continued on reverse.
Power Vent Kits continued.
Vent Kits
Kit # Part # Applicable Rheem-Ruud Water Heater Model
PV Kit 4 AP11646 G50-98, G75-125, G82-156, G76-180
PV Kit 5 AP11645 G37-200, G76-200, G91-200, G100-200(A), G72-250(A), G100-250(A), G100-270(A),
G72-300(A),G85-300(A), G100-310(A), G65-360(A), G65-400(A), G85-400(A), G100-400(A)
Not for use with GN or GX models.
Dimensions
Power Venter
Motor Motor Max Height Width Depth Inlet
Kit# Watts Amps Vent (H) (W) (D) Outlet
(from Tjernlund)
4 95 1.26 50 ft 7-7/8" 11" 7" 4"
5 170 1.51 50 ft 9-1/4" 11-5/8" 8-5/8" 6"
Note: Max Vent Length based on total length of straight vent pipe plus 10 feet for each 90 degree elbow and 5 feet for each 45 degree elbow.
D
H
W
Vent Terminal
Kit#
AB CDimension
4 9" 9-1/2" 7" Sq. 8" Sq.
5 10-1/8" 9-1/2" 8-1/2" Dia. 9" Dia.
B
Rough in
Model Kit Outlet Size Adapter*
Vent Hood Vent Vent
Draft
G50-98 PV Kit 4 5" 4" 5" x 4"
G75-125 PV Kit 4 5" 4" 5" x 4" G82-156 PV Kit 4 6" 4" 6" x 4" G76-180 PV Kit 4 6" 4" 6" x 4" G37-200 PV Kit 5 6" 6" Not Required G76-200 PV Kit 5 6" 6" Not Required G91-200 PV Kit 5 6" 6"
Not Required
G100-200(A) PV Kit 5 6" 6" Not Required G72-250(A) PV Kit 5 6" 6" Not Required G100-250(A) PV Kit 5 6" 6"
Not Required
G100-270(A) PV Kit 5 6" 6" Not Required G72-300(A) PV Kit 5 8" 6" 8" x 6" G85-300(A) PV Kit 5 8" 6" 8" x 6" G100-310(A) PV Kit 5 7" 6" 7" x 6" G65-360(A) PV Kit 5 8" 6" 8" x 6" G65-400(A) PV Kit 5 8" 6" 8" x 6" G85-400(A) PV Kit 5 10" 6" 10" x 6" G100-400(A) PV Kit 5 8" 6" 8" x 6"
*Note: Vent Pipe and Vent Adapter are NOT included.
Floor
Exterior Wall
A Sq.
C
Typical Application
COMMERCIAL
WATER HEATERS