Field Installed Option Accessories ..............30
Electronic Air Cleaner........................30
Humidifier .................................30
Filter .....................................30
RXGW-B01 Chimney Adapter .................30
Four Inch Flue Adapter.......................30
11 TWINNING ................................32
Furnace Twinning Installations.................32
Control Boards .......................... 33-34
12 HIGH ALTITUDE ...........................35
Natural Gas at High Altitudes..................35
LP Gas at High Altitudes .....................37
13 STARTUP PROCEDURES ...................38
Sequence of Operation ......................38
14 DIAGNOSTICS AND FAULT CODES ..........39
15 LOCKOUT ................................40
16 FIELD SELECTIONS & ADJUSTMENTS .......41
Field Selections – Dipswitches.................41
17 FAULT CLEAR ............................42
18 FAULT RECALL ...........................42
19 FLAME STATUS L.E.D. .....................42
20 TIMING DIAGRAM..........................42
21 ADJUSTING OR CHECKING FURNACE INPUT . 43
22 SETTING INPUT RATE......................44
23 AIRFLOW .................................45
Blower Speed Selection ......................46
24 SAFETY FEATURES........................47
25 MAINTENANCE ............................48
26 SYSTEM OPERATION INFORMATION.........49
27 ANNUAL INSPECTION......................49
28 REPLACEMENT PARTS ....................49
24 TROUBLESHOOTING.......................50
30 WIRING DIAGRAM .........................51
IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OF THIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TO ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIR THIS PRODUCT. UPON
UNPACKING OF THE FURNACE, INSPECT ALL PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.
2
GENERAL INFORMATION
NOTE: A heat loss calculation should be performed to properly
determine the required furnace BTU size for the structure. Also,
the duct must be properly designed and installed for proper airflow. Existing ductwork must be inspected for proper size and to
make sure that it is properly sealed. Proper airflow is necessary
for both user comfort and equipment performance.
Before opening the furnace carton, verify that the data tags
on the carton specify the furnace model number that was ordered from the distributor and are correct for the installation.
If not, return the unit without opening the carton. If the model
number is correct, open the carton and verify that the furnace
rating label specifies the same furnace model number that
is specified on the carton label. If the model numbers do not
match, return the furnace to the distributor.
IMPORTANT: Proper application, installation and maintenance of
this furnace and system is a must if consumers are to receive the
full benefits for which they have paid.
FIGURE 1
FURNACE COMPONENTS
13
14
15
16
20
17
18
1
2
3
The 80% single stage constant torque series furnaces are design
certified by CSA for use with natural and propane gases as follows:
As a Category I furnace, it may be vented vertically with type
B-1 vent pipe and also may be common vented as described
in these instructions.
This furnace should be installed in accordance with the American
National Standard Z223.1 - latest edition booklet entitled “National
Fuel Gas Code” (NFPA 54), and the requirements or codes of
the local utility or other authority having jurisdiction including local
plumbing or waste water codes.
With the introduction of higher efficiency furnaces, special attention must be paid to the venting system. Only listed venting systems may be used as stated in the installation instructions and the
National Fuel Gas Code, ANSI Z223.1 (NFPA 54),. Since furnace
technology and venting requirements are changing, awareness of
local, state, and federal codes and industry changes is imperative.
12
ITEM
11
10
9
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
8
19
20
DESCRIPTION
DOOR SWITCH
TRANSFORMER
JUNCTION BOX
LOW VOLTAGE TERMINAL
SOLID METAL BASE PAN
FURNACE CONTROL
CONTROL MOUNTING PLATE
BLOWER
IGNITER
GAS VALVE
INDUCED DRAFT BLOWER
4” FLUE ADAPTER (OPTIONAL)
COMBUSTION AIR INLET
MAIN LIMIT
COMBUSTION AIR DIFFUSER
MAIN PRESSURE SWITCH
BURNER
FLAME SENSOR
HEAT ASSISTED LIMIT CONTROL (HALC)
OVER TEMPERATURE SWITCH
General Information
19
4
7
6
5
ST-A1220-20-00
ST-A1220-20-00
3
GENERAL INFORMATION (cont.)
Install this furnace in accordance with the American National
Standard Z223.1 – latest edition entitled “National Fuel Gas Code”
(NFPA54) and requirements or codes of the local utilities or other
authorities having jurisdiction. This is available from the following:
National Fire Protection Association, Inc.
Batterymarch Park
General Information
Quincy, MA 02269
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should
be opened immediately. If damage is found, it should be noted
on the delivery papers, and a damage claim filed with the last
carrier.
• After unit has been delivered to job site, remove carton taking
care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil,
voltage, phase, etc. to be sure equipment matches what is
required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around
the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power
wires on the inside where they exit conduit opening. Caulking
is required to prevent air leakage into and condensate from
forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to
the coil/filter rack and blower/control compartment.
• Install the unit in accordance with any local code which may
apply and the national codes. Latest editions are available
from: “National Fire Protection Association, Inc., Batterymarch
Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning
systems.
• The equipment has been evaluated in accordance with the
Code of Federal Regulations, Chapter XX, Part 3280.
MATERIAL INFORMATION
All manufacturer products meet current Federal OSHA Guidelines for safety. Most consumers are aware that products present
safety and health risks, when improperly used, handled and
maintained. More details are available at the Websites for OSHA
(Occupational Safety and Health Administration), at www.osha.
gov.
EFFICIENCY TESTING NOTICE
For purposes of verifying or testing efficiency ratings, the
test procedure in Title 10 Appendix N to Subpart B of
Part 430 (Uniform Test Method for Measuring the Energy
Consumption of Furnaces and Boilers) and the clarifying
provisions provided in the AHRI Operations Manual for
Residential Furnaces that were applicable at the date of
manufacture should be used for test set up and performance.
4
Installation Instructions remain with the furnace as a reference guide to the servicing contractor. We recommend
that performance and installation data be recorded for future reference on this sheet to meet service and warranty obligations so that job site information is available when required.
______ Correct clearance to combustibles (record clearance)
______ Correct clearance for service (at front) (record clearance)
______ Remove shipping bracket from blower
DUCT STATIC PRESSURE
______ in. w.c. on heating speed (record static pressure)
______ in. w.c. on cooling speed (record static pressure)
______ Air temperature rise in heat (record air temperature rise)
______ Air temperature rise in cool (record air temperature rise)
VENTING
______ Correct vent pipe diameter and length (according to NFGC tables) _________________ Vent connection size
______ Correct venting material (according to NFGC tables)
______ Correct lining for masonry chimneys
______ Adequate clearance from combustibles
______ Proper negative pressure reading in the vent
______ Vent pipe secured to induced draft blower housing
COMBUSTION AIR
______ Proper source of combustion air
______ Correct combustion air opening size
______ Optional attic combustion air pull
Checklist
______ Non-attic combustion air pull
5
SAFETY INFORMATION
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!!
THIS FURNACE IS NOT APPROVED FOR INSTALLATION
IN A MOBILE HOME. DOING SO COULD CAUSE FIRE,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND
POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE
INSTRUCTIONS.
WARNING
!
IMPROPER INSTALLATION CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS
CONDITIONS AND ARE NOT COVERED BY THE MANU-
FACTURER’S WARRANTY.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY
SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF
A SAFETY SWITCH CAUSES THE FURNACE TO SHUT
DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICATION OF A POTENTIAL SAFETY HAZARD THAT MUST
BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET
SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
AND/OR VERIFICATION OF PROPER SAFE OPERATION
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR
Safety Information
THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY
WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN
A NEW SAFETY SWITCH IS INSTALLED, IT MUST BE
TESTED FOR A MINIMUM OF 15 MINUTES WITH THE
FURNACE OPERATING AT MAXIMUM INPUT RATE AND
WITH BOTH BLOWER AND BURNER DOOR INSTALLED.
IF THE FURNACE IS INSTALLED IN A CLOSET, THE
CLOSET DOOR MUST ALSO BE CLOSED FOR THIS
TEST. REPEAT THE TEST AT THE MINIMUM INPUT
RATE IF THE FURNACE IS A MULTI-STAGE FURNACE.
WARNING
!
USE ONLY WITH THE TYPE OF GAS APPROVED FOR
THIS FURNACE. REFER TO THE FURNACE RATING
PLATE.
WARNING
!
COMBUSTION AND VENTILATION AIR MUST BE PROVIDED TO THE FURNACE AS REQUIRED BY THE
NATIONAL FUEL-GAS CODE (U.S.) AND CSA B149.1
(CANADA) AND THE COMBUSTION AND VENTILATION
AIR SECTION OF THESE INSTRUCTIONS.
WARNING
!
COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS FURNACE TO AN APPROVED
VENT SYSTEM ONLY, AS SPECIFIED IN THE VENT PIPE
INSTALLATION SECTION OF THESE INSTRUCTIONS.
WARNING
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY
DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO
AREAS OUTSIDE THE SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL ALSO BE HANDLED
BY DUCT(S) SEALED TO THE FURNACE CASING AND
TERMINATING OUTSIDE THE SPACE CONTAINING THE
FURNACE.
WARNING
!
WHENEVER THE FACTORY RETURN-AIR CONNECTION
IS NOT USED IT MUST BE SEALED. A SOLID METAL
BASE PLATE MUST BE INSTALLED AND SEALED. FACTORY BASE PLATES ARE AVAILABLE AS ACCESSORY
ITEMS. (PART NUMBERS ARE LISTED IN THE SPEC
SHEET FOR THE FURNACE.) FAILURE TO INSTALL
AND SEAL THE BASE PLATE AND RETURN AIR DUCT
CONNECTIONS MAY ALLOW CARBON MONOXIDE AND
OTHER CONTAMINANTS TO BE DRAWN INTO THE CONDITIONED AIR SPACE AND DISTRIBUTED THROUGHOUT
THE HEATED SPACE.
WARNING
!
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A
PORTION OF THE DUST ENTRAINED IN THE AIR MAY
TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT
THE SUPPLY REGISTERS. ANY CIRCULATED DUST PARTICLES WILL BE HEATED AND CHARRED BY CONTACT
WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY
RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAMAGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS
IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE
BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME.
USE A COMMERCIALLY AVAILABLE SOAP SOLUTION
MADE SPECIFICALLY FOR THE DETECTION OF LEAKS
TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS
SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
6
WARNING
!
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER THIS FURNACE AND ANY INSTALLED
EVAPORATOR COIL THAT IS LOCATED IN ANY AREA OF
A STRUCTURE WHERE DAMAGE TO THE BUILDING OR
BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN
OVERFLOW OF THE A/C COIL DRAIN PAN.
SAFETY
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED
WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO
PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTO THE
HOME THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
WARNING
!
ALWAYS INSTALL THE FURNACE TO OPERATE WITHIN
THE FURNACE’S INTENDED TEMPERATURE-RISE
RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE
RANGE, AS SPECIFIED IN THE DUCTING SECTION OF
THESE INSTRUCTIONS. SEE ALSO FURNACE RATING
PLATE.
THE FURNACE MAY BE USED FOR HEATING OF BUILDINGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
-PROPER VENT INSTALLATION;
-FURNACE OPERATING UNDER THERMOSTAT CON-
TROL;
-RETURN AIR DUCT SEALED TO THE FURNACE;
-AIR FILTERS IN PLACE;
-SET FURNACE INPUT RATE AND TEMPERATURE
RISE PER RATING PLATE MARKINGS;
-MEANS FOR PROVIDING OUTDOOR AIR REQUIRED
FOR COMBUSTION;
-RETURN AIR TEMPERATURE MAINTAINED BE-
TWEEN 55°F (13°C) AND 80°F (27°C); AND
-CLEAN FURNACE, DUCT WORK AND COMPO-
NENTS UPON SUBSTANTIAL COMPLETION OF THE
CONSTRUCTION PROCESS, AND VERIFY THAT THE
FURNACE OPERATING CONDITIONS INCLUDING
IGNITION, INPUT RATE, TEMPERATURE RISE AND
VENTING, ACCORDING TO THE INSTRUCTIONS AND
CODES.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM
AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES
AND ODORS INTO THE HOME CAUSING PROPERTY
DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE
OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE
DRAWN INTO THE LIVING SPACE THROUGH LEAKING
DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING
PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE
AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN
THE EQUIPMENT AND DUCT MUST BE SEALED TO
LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS
INCLUDING CARBON MONOXIDE FROM MIGRATING
INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING
APPLIANCES SUCH AS WATER HEATERS OR BOILERS - ALL JOINTS, SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST ALSO BE SEALED TO
PREVENT DEPRESSURIZATION OF THE SPACE AND
POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO
LIVING SPACES
Safety Information
IMPORTANT INFORMATION ABOUT
EFFICIENCY AND INDOOR AIR
QUALITY
Central cooling and heating equipment is only as efficient as the
duct system that carries the cooled or heated air. To maintain
efficiency, comfort and good indoor air quality, it is important to
have the proper balance between the air being supplied to each
room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the
efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount
of airborne pollutants that enter homes from spaces where the
ductwork and / or equipment is located. The manufacturer and
the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a
qualified contractor for proper balance and sealing.
Adapted from Residential Duct Diagnostics and Repair, with permission of Air Conditioning
Contractors of America (ACCA).
7
LOCATION REQUIREMENTS
GENERAL INFORMATION
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE INSTALLED SO THE BURNERS
AND IGNITION SOURCE ARE LOCATED NO LESS THAN
18 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO
PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS
WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE
FURNACE MUST BE LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO
FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR
EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. IMPORTANT: If using a cooling evaporator coil with this fur-
nace, be sure the air passes over the heat exchanger before
passing over the cooling coil. The cooled air passing over the
warm ambient air inside the heat exchanger tubes can cause
condensation inside the tubes resulting in corrosion and eventual failure. An auxiliary drain pan should extend under any
evaporator coil installed with the furnace.
If there are manual dampers, they must be equipped to prevent
heating or cooling operation unless the damper is in the full heat
or cool position.
2. NOTE: This furnace is shipped with heat exchanger support
brackets installed under the back of the heat exchanger. These
may be removed before installation, but it is not required.
3. IMPORTANT: This furnace is not approved or recommended
for installation on its back, with access doors facing upwards.
4. This furnace is suitable for installation in buildings constructed
on-site. This heating unit should be centralized with respect to
the heat distribution system as much as practicable.
5. NOTE: These furnaces are approved for installation in attics,
as well as alcoves, utility rooms, closets and crawlspaces.
6. IMPORTANT: Support this unit when installed. For attic or
crawl space installation, horizontal furnaces may be installed
on combustible wood flooring or by using support brackets.
See Figure 3.
Location
7. IMPORTANT: If installing in a utility room, be sure the door is
wide enough to:
a. allow the largest part of the furnace to pass; or
b. allow any other appliance (such as a water heater) to pass.
8. IMPORTANT: This furnace is shipped with a blower motor
support bracket. This bracket must be removed before operating furnace. Remove (2) screws from front of blower and
slide bracket off motor shaft.
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK, WITH ACCESS
DOORS FACING UPWARDS.
SITE SELECTION
1. Select a site in the building near the center of the proposed, or existing, duct system.
2. Give consideration to the vent system piping when selecting the furnace location. Be sure the venting system can get from the furnace to the termination with
minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if
running a new gas line, locate the furnace to minimize
the length and elbows in the gas piping. See Figure 3.
4. Locate the furnace to maintain proper clearance to
combustibles as shown in following Figure 4.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER
TUBES. DOING SO CAN DAMAGE THE HEAT EXCHANGER ASSEMBLY.
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as
listed in the tables under Figure 4 are to combustible materials shown in inches.
See name/rating plate and clearance label for specific
model number and clearance information.
Service clearance of at least 24 inches (61 cm) is recommended in front of all furnaces.
NOTE:Use recommended 24” (61 cm) clearance if ac-
cessibility clearances are greater than fire protection clearances.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST
TAKE PRECEDENCE OVER FIRE PROTECTION CLEARANCES.
8
LOCATION REQUIREMENTS
NOTE:
GENERAL INFORMATION (cont.)
WARNING
UPFLOW AND HORIZONTAL FURNACES ARE DESIGN-
CERTIFIED FOR INSTALLATION ON COMBUSTIBLE
FLOORS. NOTE, HOWEVER, THAT FURNACES MUST
NOT BE INSTALLED DIRECTLY ON CARPETING, TILE OR
OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD
FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FIGURE 3
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION.
HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
AIR FLOW
ST-A1220-03
WARNING
!!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED
ON OR AGAINST THE FURNACE JACKET. THE AREA
AROUND THE FURNACE MUST BE KEPT CLEAR AND
FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING
GASOLINE AND OTHER FLAMMABLE VAPORS AND
LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS
ON, AGAINST OR AROUND THE FURNACE JACKET CAN
CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE
HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET
OR FOR ANY OTHER STORAGE PURPOSES.
Location
9
BOTTOM
TOP
LEFT SIDEFRONTRIGHT SIDE
GAS
CONNECTION
ELECTRICAL CONNECTION
LINE VOLTAGE
ELECTRICAL CONNECTION
LOW VOLTAGE
OPTIONAL
GAS CONNECTION
OPTIONAL LOW
VOLTAGE WIRING
OPTIONAL LINE VOLTAGE
WIRING
A
I
R
F
L
O
W
RETURN
AIR
SUPPLY
AIR
HOT
ST-A1220-04
MODELABCDEFRIGHT SIDEBACKTOPFRONTVENT
51413 27/3210 5/8①11 1/21 7/804②0136③85 lbs.
717 1/216 11/3212 3/8①152 1/203②0136③105 lbs.
102119 27/3214 1/8①18 1/22 1/2000136③120 lbs.
1224 1/223 11/3215 7/8①222 1/2000136③140 lbs.
1524 1/223 11/3215 7/8①222 1/2000136③150 lbs.
① MAY REQUIRE 3" TO 4" OR 3" TO 5" ADAPTER.
4" ADAPTER INCLUDED WITH (-)801P UNITS.
② MAY BE 0" WITH TYPE B VENT.
③ MAY BE 1" WITH TYPE B VENT.
LEFT SIDE
REDUCED CLEARANCE (IN.)
SHIP
WGTS.
FIGURE 4
UPFLOW/HORIZONTAL DIMENSIONS
Ship.
REDUCED CLEARANCE (IN.)
Back Top Front Vent
¿ May require 3” to 4” or 3” to 5” adapter.
4” adapter optional.
¿ May be 0” with type B vent.
¿ May be 1” with type B vent.
*See furnace speck sheet for availability.
Left Right
/8 0 4¿ 0 1 3 6¿ 85 lbs.
/2 0 3¿ 0 1 3 6¿ 105 lbs.
/2 0 0 0 1 3 6¿ 120 lbs.
/2 0 0 0 1 3 6¿ 120 lbs.
/2 0 0 0 1 3 6¿ 140 lbs.
1
1
7
/2 1
/2 2
1
1
/8 ¿11
/8 ¿15 2
/8 ¿18
5
3
1
/2 0 0 0 1 3 6¿ 150 lbs.
1
1
1
/2 2
1
/8 ¿18
/8 ¿22 2
/8 ¿22 2
1
7
7
ST-A1220-04
Location
/32 10
/32 12
/32 14
/32 14
/32 15
27
11
27
/2 16
1
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
Input A B C D E F
Side Side Wgts.
050 14 12
075 17
075 21 19
/32 15
27
11
11
/2 23
/2 23
1
1
100 21 19
125 24
150 24
10
DUCTING
Proper air flow is required for the correct operation of this
furnace. Restricted air flow can cause erratic operation
and can damage the heat exchanger. The duct system
must carry the correct amount of air for heating and cooling if summer air conditioning is used.
WARNING
!
SOME HEATING AIRFLOW VALUES MAY BE
HIGHER THAN THOSE REQUIRED FOR COOLING.
BE SURE TO SIZE DUCT FOR THE MAXIMUM POSSIBLE AIRFLOW VALUE.
SIZE AIRFLOW DISTRIBUTION SYSTEM TO ACCEPTABLE INDUSTRY STANDARDS AND METHODS. TOTAL STATIC PRESSURE DROP OF THE
AIR DISTRIBUTION SYSTEM SHOULD NOT EXCEED .8 INCHES W.C. THIS WILL INCLUDE ANY
AIR CONDITIONER COIL, AIR FILTRATION SYSTEM, ZONING SYSTEM, DUCTWORK, ETC. REFER
TO ADDED EQUIPMENT TECHNICAL INFORMATION TO OBTAIN PRESSURE DROP INFORMATION
WHEN EQUIPMENT IS OPERATING AT RECOMMENDED HEATING OR COOLING CFMS.
WARNING
!
ZONING SYSTEMS ARE NOT DIRECTLY SUPPORTED
IN THIS MANUAL. IF A THIRD PARTY SYSTEM IS USED
REFER TO THE MANUFACTURER OF THAT PRODUCT
FOR INSTALLATION AND OPERATION INSTRUCTIONS.
ZONING SYSTEMS USED ON THIS PRODUCT MUST
HAVE SENSORS TO PREVENT FURNACES AND/OR
HEATING ELEMENTS FROM CYCLING ON INTERNAL
LIMIT CONTROLS. THE ZONING SYSTEM MUST NOT
ALLOW THE EVAPORATOR COILS AND/OR HYDRONIC
COILS TO FREEZE.
IMPORTANT: When using outside air, design and adjust
the system to maintain a return air temperature ABOVE
55° F during the heating season.
NOTE: Return air grilles and warm air registers must not
be obstructed or closed.
UPFLOW INSTALLATIONS
1. Position the unit to minimize long runs of duct or runs
of duct with many turns and elbows.
2. For side return: Cut an opening in the side. The
opening should be cut the full width and height of the
knockouts on the unit. See Figure 6.
3. If summer air conditioning is desired, position the
indoor coil on the supply-air side of the unit. Ensure
that no air can bypass the coil.
4. Connect the furnace to the supply air plenum. See
Figure 7.
5. Connect the return air ducting to the return-air opening at the bottom and/or side of the unit. Make the
connections air-tight to prevent the migration of toxic
fumes and odors including carbon monoxide from migrating into the living space.
6. If a filter is installed near the furnace, be sure to have
adequate space for installation and removal of the
unit filter.
7. NOTE: Where the maximum airflow is 1800 CFM or
more, BOTH sides or the bottom must be used for the
return air. Do not take return air from the back of the
unit.
NOTE: DO NOT take return air from furnace rooms, garages or cold areas. Avoid return air from utility rooms,
kitchens, laundry rooms and bathrooms.
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED
WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO
PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTO THE
HOME THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
WARNING
!
THE SOLID METAL BASE PLATE MUST BE INSTALLED IN THE FURNACE BOTTOM WHEN USING
SIDE AIR RETURN. FAILURE TO INSTALL A BASE
PLATE COULD CAUSE THE PRODUCTS OF COMBUSTION TO CIRCULATE INTO THE LIVING SPACE
AND CREATE POTENTIAL LY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH. FOR BOTTOM RETURN, A SOLID
METAL BASE PAN MUST NOT BE INSTALLED. SEE
FIGURE 5.
Ducting
11
DUCTING
FIGURE 5
NOTE:
NOTE:
SOLID BASE PLATE PROVIDED WITH 80%
SOLID BASE PLATE PROVIDED WITH (-)801PMODELS ONLY.
SINGLE STAGE CONSTANT TORQUE
MODELS ONLY.
WHEN SOLID BASE PLATE IS USED . TAPE AROUND BOTTOM FLANGES OF CABINET
WHEN SOLID BASE PLATE IS USED, TAPE
BEFORE THE UNIT IS INSTALLED.
AROUND BOTTOM FLANGES OF CABINET BEFORE THE UNIT IS INSTALLED.
SOLID BASE FLANGE
FITS UNDER
CABINET BOTTOM
FIGURE 6
Ducting
LIFT UP, PULL OUT
1. REMOVE 2 SCREWS, LIFT BASE UP, SLIDE FORWARD TO REMOVE.
2. INSTALLATION IS REVERSE OF REMOVAL.
** VERIFY REAR FLANGE IS SEALED PROPERLY AS SHOWN IN DETAIL.
CUT OUT USING
EMBOSSED ANGLES
AS A GUIDE
FOR PROPER SIZE
23” X 14”
FIGURE 7
ST-A1220-10-X0
ST-A1220-10
A
I
R
F
L
O
W
CUT OUT USING
EMBOSSED ANGLES
AS A GUIDE
FOR PROPER SIZE
23” X 14”
12
ST-A1220-08
ST-A1220-11-X0
ST-A1220-11
DUCTING
NOTE:
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION.
HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
AIR FLOW
NOTE:
DO NOT BLOCK FURNACE ACCESS WITH
SUPPORT RODS, ALLOW SPACE FOR
PROPER SERVICE MAINTIENCE OR
REPLACEMENT OF THE HEAT EXCHANGER
AND BLOWER ASSEMBLY .
HORIZONTAL UNITS
1. Position the unit to minimize long runs of duct or runs of
duct with many turns and elbows.
2. Unit can be mounted left or right side airflow configuration.
3. Position the unit on adequate supports or by using
support brackets (see Figure 8) and connect supply
plenum.
4. If summer air conditioning is desired, position the indoor coil on the supply air side of the unit. Insure that
no air can bypass this coil.
5. Secure the four angle brackets to the return air opening. See Figure 9. Connect the return air ducting to the
return air opening at the top of the unit. Make the connection air tight to prevent entraining combustion gases
from an adjacent fuel-burning appliance.
NOTE: Do not block furnace access with support rods.
Maintain clearances recommended in Figure 8. Allow
enough space for proper service maintenance or replacement of the heat exchanger and blower assembly.
FIGURE 8
HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS
FIGURE 9
HORIZONTAL RETURN AIR DUCT
(LEFT-HAND AIRFLOW POSITION SHOWN)
AIRFLOW
RETURN
REAR VIEW
FOUR ANGLE BRACKETS, SHIPPED WITH 80% SINGLE STAGE
CONSTANT TORQUE UNITS, CAN BE INSTALLED HORIZONTALLY.
THESE BRACKETS MAY BE USED TO SECURE THE RETURN AIR
DUCT TO A HORIZONTAL UNIT.
ST-A1220-03
Ducting
13
COMBUSTION AND VENTILATION AIR
COMBUSTION AIR REQUIREMENTS
IMPORTANT: This is not a direct vent furnace. Review venting
instructions before installing.
WARNING
!
Combustion Air
THIS FURNACE AND ANY OTHER FUEL-BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH
AIR FOR PROPER COMBUSTION AND VENTILATION OF
THE FLUE GASES. MOST HOMES WILL REQUIRE THAT
OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA.
FAILURE TO DO SO CAN CAUSE DEATH FROM CARBON
MONOXIDE POISONING.
WARNING
!
ADEQUATE FACILITIES FOR PROVIDING AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED IN
ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILATION, OF THE NATIONAL FUEL GAS
CODE, ANSI, Z223.1 LATEST EDITION OR APPLICABLE
PROVISIONS FOR THE LOCAL BUILDING CODES, AND
NOT OBSTRUCTED SO AS TO PREVENT THE FLOW OF
AIR TO THE FURNACE.
1. IMPORTANT: Air for combustion and ventilation must not
come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty
coverage.
2. Combustion air must be free of acid forming chemicals; such
as sulphur, fluorine and chlorine. These elements are found
in aerosol sprays, detergents, bleaches, cleaning solvents,
air fresheners, paint and varnish removers, refrigerants and
many other commercial and household products. Vapors
from these products when burned in a gas flame form acid
compounds. The acid compounds increase the dew point
temperature of the flue products and are highly corrosive
after they condense.
3. The following types of installation may require OUTDOOR
AIR for combustion, due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
4. If combustion air is exposed to the following substances (but
not limited to the following), it should not be used and the furnace may require outdoor air for combustion.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry curing and acid washing materials
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH
THE NATIONAL FUEL GAS CODE AND LOCAL CODES
TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO
CAN CREATE HAZARDOUS CONDITIONS RESULTING IN
PROPERTY DAMAGE, BODILY INJURY OR DEATH FROM
SMOKE, FIRE OR CARBON MONOXIDE.
Combustion air requirements are determined by whether the
furnace is in an open (unconned) area or in a conned space
such as a closet or small room.
When the furnace is installed in the same space with other gas
appliances, such as a water heater, be sure there is an adequate
supply of combustion and ventilation air for the furnace and the
other appliances. Do not delete or reduce the combustion air
supply required by the other gas appliances in this space. See
Z223.1, National Fuel Gas Code (NFPA 54). An unconned
space must have at least 50 cubic feet (volume) for each 1,000
BTUH of the total input of all appliances in the space. If the open
space containing the appliances is in a building with tight construction (contemporary construction), outside air may still be
required for the appliances to burn and vent properly. Outside air
openings should be sized the same as for a conned space.
IMPORTANT: ONLY THE CURRENT VENT INSTRUCTIONS
APPLY. All gas furnaces cannot be common-vented.
OVERTEMPERATURE SAFETY
SWITCHES
Furnaces are equipped with safety switches in the burner compartment to protect against over-temperature conditions caused
by inadequate combustion air supply. The switches are located
in the burner compartment. If a switch is tripped it must be manually reset after clearing the fault condition which caused it to
open.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY
SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF
A SAFETY SWITCH CAUSES THE FURNACE TO SHUT
DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICATION OF A POTENTIAL SAFETY HAZARD THAT MUST
BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET
SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
AND/OR VERIFICATION OF PROPER SAFE OPERATION
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT WITH
IDENTICAL OEM REPLACEMENT PARTS ONLY.
14
COMBUSTION AND VENTILATION AIR (cont.)
TABLE 8: MINIMUM FREE AREA OPENING REQUIRED FOR A FURNACE LOCATED IN A CONFINED SPACE USING INDOOR AIR FOR COMBUSTION.
Input (BTUH)
Free Area for Each
Opening (sq inches)
50,000100
75,000100
100,000100
125,000130
150,000150
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
Combustion Air
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH
THE NATIONAL FUEL GAS CODE, NFPA 54 AND LOCAL
CODES TO PROVIDE ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE FURNACE. FAILURE TO
DO SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY
DAMAGE, CARBON MONOXIDE POISONING, PERSONAL
INJURY OR DEATH.
For improved indoor air quality, added safety and product performance we recommend direct vent type installations. If non-direct
type vent system is used, the requirements for combustion air
must be provided as identied in the National Fuel Gas Code.
Combustion air requirements are determined by whether the
furnace is in an open (unconned) area or in a conned space
such as a closet or small room.
WARNING
!
READ AND FOLLOW THE GENERAL VENTING REQUIREMENTS AND GUIDELINES OF THIS MANUAL FOR ADDI-
TIONAL VENTING REQUIREMENTS PERTAINING TO ALL
FURNACE INSTALLATIONS (INCLUDING DIRECT AND
NON-DIRECT VENTING). FAILURE TO FOLLOW ALL INSTRUCTIONS IN THIS MANUAL CAN RESULT IN EQUIPMENT FAILURE, EQUIPMENT DAMAGE, PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
FURNACE LOCATED IN AN
UNCONFINED SPACE
USING INDOOR AIR FOR COMBUSTION:
An unconned space must have at least 50 cubic feet for each
1,000 BTUH of total input for all appliances in the space. Table
1 below species minimum space requirements and a few ex-
amples of the room sizes required for different inputs. The sizes
are based on 8-foot ceilings.
If the open space containing the furnace is in a building with
tight construction, outside air may still be required for the furnace to operate and vent properly. Outside air openings should
be sized the same as for a conned space.
TABLE 1: MINIMUM SPACE REQUIREMENTS
TABLE 7: MINIMUM SPACE REQUIREMENTS
FOR UNCONFINED SPACE, NON-DIRECT VENT
FOR UNCONFINED SPACE, NON-DIRECT VENT*
Input
(BTUH)
50,000 2,500 313 16 x 20
75,000 3,750 470 24 x 20
100,000 5,000 625 32 x 20
125,000 6,300 790 36 x 30
150,000 7,500 940 32 x 30
Minimum
Space
(Cubic Ft)
Minimum Area
with 8
Ceilings (sq )
Typical Room
Size w/ 8'
Ceilings ( x )
FURNACE LOCATED IN A CONFINED
SPACE
A conned space is dened as any space for a given furnace
input rating which is smaller than that which is specied in Table
1 as minimum for an “unconned” space. If the space is less than
that specied in this table, the space is dened as “conned”.
If the space is small enough to be designated as “conned”,
it must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and B. Size connected to the heated area or to the
outside, and by the input of ALL appliances in the space.
If the conned space is within a building with tight construction,
combustion air must be taken from outdoors or from an area
freely communicating with the outdoors.
A. USING INDOOR AIR FOR COMBUSTION:
IMPORTANT: Air should not be taken from a heated space
with a replace, exhaust fan or other device that may produce negative pressure.
If combustion air is taken from the heated area, the open-
ings must each have at least 100 square inches of free
area. Each opening must have at least one square inch of
free area for each 1,000 BTUH of total input in the space.
Table 2 shows some typical examples of openings required
for combustion air openings required for a conned space.
TABLE 8: MINIMUM FREE AREA
TABLE 2: MINIMUM FREE AREA
OPENING REQUIRED FOR A
OPENING REQUIRED FOR A
FURNACE LOCATED IN A
FURNACE LOCATED IN A
CONFINED SPACE USING
B. USING OUTDOOR AIR FOR COMBUSTION:
IMPORTANT: Do not take air from an attic space that is
The conned space must communicate with the outdoors in
METHOD 1:
Two permanent openings, one located within 12 inches of
CONFINED SPACE USING
INDOOR AIR FOR COMBUSTION.
INDOOR AIR FOR COMBUSTION.
Free Area for Each
Input (BTUH)
50,000 100
75,000 100
100,000 100
125,000 130
150,000 150
equipped with power ventilation.
accordance with Methods 1 or 2 below. The minimum dimension of air openings shall not be less than 3 inches. Where
ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect.
the top and one located within 12 inches of the bottom of the
enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors.
Opening (sq inches)
15
TABLE 9: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE THROUGH AN OPENING OR THROUGH A VERTICAL VENT DUCT.*
Total Input for
ALL Gas
Appliances
(BTUH)
Free Area for
Each Opening
when 2 Separate
Openings are
used (sq inches)
Round Pipe Duct
Diameter (Vercal
Duct Only) (inches)
50,000 13 5
75,000 19 5
100,000 25 6
125,000 32 8
150,000 38 8
TABLE 11: MINIMUM FREE AREA REQUIRED FOR AN OPENING (WHEN O NE OPENING IS USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE *
Total Input for
ALL Gas
Appliances
(BTUH)
Free Areafor an
Opening when1
Opening isused
(sq inches)
Round Pipe Duct
Diameter(inches)
50,00025 6
OUTSIDE.
COMBUSTION AND VENTILATION AIR (cont.)
TABLE 9: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE THROUGH AN OPENING OR THROUGH A VERTICAL VENT DUCT.*
Total Input for
ALL Gas
Appliances
(BTUH)
Free Areafor
Each Opening
when2 Separate
Openingsare
used (sq inches)
Round Pipe Duct
Diameter (Vercal
Duct Only) (inches)
50,00013 5
75,00019 5
100,00025 6
125,00032 8
150,00038 8
TABLE 10: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
OUTSIDE THROUGH A HORIZONTAL DUCT.
Total Input for
ALL Gas
Appliances
(BTUH)
Free Area for
Each Opening
when 2 Separate
Openings are
used (sq inches)
Round Pipe Duct
Diameter
(Horizontal Duct
Only) (inches)
50,000 25 6
75,000 38 8
100,000 50 8
125,000 63 10
150,000 75 10
TABLE 11: MINIMUM FREE AREA REQUIRED FOR AN OPENING (WHEN O NE OPENING IS USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE *
Total Input for
ALL Gas
Appliances
(BTUH)
Free Areafor an Opening when1
Opening isused
(sq inches)
Round Pipe Duct
Diameter(inches)
50,00025 6
75,00038 8
100,00050 8
125,00063 10
150,00075 10
OUTSIDE.
TABLE 11: MINIMUM FREE AREA REQUIRED FOR AN OPENING (WHEN O NE OPENING IS USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE *
Total I nput for
ALL Gas
Appliances
(BTUH)
Free Area for an
Opening when 1
Opening is used
(sq inches)
Round Pipe Duct
Diameter (inches)
50,000 25 6
75,000 38 8
100,000 50 8
125,000 63 10
150,000 75 10
OUTSIDE.
),*85($,5)520+($7('63$&(
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
TABLE 3: MINIMUM FREE AREA REQUIRED
FOR EACH OPENING (WHEN TWO OPENINGS
ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
Combustion Air
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH AN OPENING OR
3. THROUGH A VERTICAL DUCT.
A. Where directly communicating with the outdoors through an
opening or where communicating to the outdoors through
vertical ducts as shown in Figure 11, each opening shall
have a minimum free area of 1 square inch for each 4,000
BTUH of total appliance input rating of all equipment in the
enclosure. Table 3 species the minimum area for
each of the 2 combustion air openings and minimum round
duct diameter for direct openings and vertical ducting only.
B. Where communicating with the outdoors through hori-
zontal ducts, each opening shall have a minimum free area
of 1 square inch for each 2,000 BTUH of total appliance
input rating of all equipment in the enclosure (see Figure
TABLE 4: MINIMUM FREE AREA REQUIRED
FOR EACH OPENING (WHEN TWO OPENINGS
ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
16
TABLE 5: MINIMUM FREE AREA REQUIRED
FOR AN OPENING (WHEN ONE OPENING IS
USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE.
12). Table 4 species the minimum area for each of the 2
combustion air openings and minimum round duct diameter
for horizontal ducting only.
METHOD 2:One permanent opening located within 12 inches of the top
of the enclosure, shall be permitted where the equipment
has clearances of at least 1 inch from the sides and back
and 6 inches from the front of the appliance. The opening
shall directly communicate with the outdoors or communicate through a vertical or horizontal duct to the outdoors or
spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum of:
FIGURE 8OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
Combustion Air
FIGURE 11
NON-DIRECT VENT
AIR FROM ATTIC
VENT PENETRATIONS
fornondirectventfurnaces
airfromattic/crawlspace
OR CRAWL
SPACE
287/(7$,5
,1$77,&
0867%(
$%29(
,168/$7,21
64,1&+3(5
%78+
287/(7$,5
*$6
:$7(5
+($7(5
*$%/(
9(17
)851$&(
237,21$/64,1&+3(5%78+,1/(7$,5
64,1&+3(5
%78+,1/(7$,5
9(17,/$7('
$77,&*$%/(25
62)),79(176
´0$;
ST-A1227-02
A. 1 Square inch for each 3,000 BTUH of the total input
rating of all equipment located in the enclosure
and
B. Not less than the sum of the areas of all vent connectors
in the conned space.
If the unit is installed where there is an exhaust fan, sufcient
ventilation must be provided to prevent the exhaust fan from
creating negative pressure.
FIGURE 12
NON-DIRECT VENT
OUTSIDE AIR
USING A
HORIZONTAL
DUCT
OUTLET AIR
1 SQ. INCH PER
4000 BTUH
INLET AIR
1 SQ. INCH PER
4000 BTUH
*$6
:$7(5
+($7(5
)851$&(
´
0$;
VENT PENETRATIONS
fornondirectventfurnaces
airfromattic/crawlspace
OUTLET AIR 1 SQ. INCH
PER 2000 BTUH
INLET AIR 1 SQ. INCH
PER 2000 BTUH
ST-A1227-03
AIR INTAKE PIPE CONNECTION
A double-elbow may be installed to top inlet air opening,
BUT IS NOT REQUIRED. This will help to prevent accidental
blockage of the intake opening. Reference Figure 13 for
proper elbow diameter.
NOTE: Inlet is specifically designed to prevent material from
being pulled into furnace. If elbows are not used, the intake
opening must be kept clean and free of debris.
FIGURE 13
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL
ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE OF
INTAKE OPENING. THIS IS NOT A REQUIREMENT. (SEE
PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED BUT
MAY NOT PREVENT DEBRIS FROM BEING DROPPED
INTO THE FURNACE.
PVC
DOUBLE
ELBOW
6” MINIMUM
CLEARANCE
#8 SCREWS
6” MIN.
GROUND OR
SHELF SURFACE
EXHAUST
METAL FLUE
PIPE ONLY
#8 SCREWS
17
COMBUSTION AND VENTILATION AIR (cont.)
It is also acceptable to run the condensate drain (or refrigerant) line access over the air intake hole as long as a 1”
minimum clearance is maintained.
Combustion air openings must not be restricted in any manner.
IMPORTANT: When indoor combustion air is used, the inlet
Combustion Air
air opening at the furnace must be protected from accidental
blockage.
IMPORTANT: If the furnace is in a location with an exhaust fan,
there must be sufficient ventilation to prevent the exhaust fan
from creating a negative pressure in the room.
Combustion air openings must NOT BE RESTRICTED in any
manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
B: Method 3
For the optimum in quiet operation, attic air may be brought directly to the furnace.
IMPORTANT: In applications using Method 3 for combustion air,
the attic must be ventilated by gable or soffit vents.
FIGURE 14
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL
ATTACH A 90° ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE
OF INTAKE OPENING.
CAUTION
!
COMBUSTION AIR INTAKES CANNOT BE TERMINATED
OUTSIDE. DOING SO CAN CAUSE IMPROPER OPERATION OF THE FURNACE.
COMBUSTION AIR FROM ATTIC
If attic combustion air is used, the inlet air opening at the furnace must be protected from accidental blockage. Install a 90°
elbow pointing horizontally at the top of inlet air pipe. See Figure
14 (maximum of 2, 45° or 90° elbows, allowed).
NOTE: Maximum length of pipe that may be used for combustion air is 10 feet with two elbows. Lengths of more than 10 feet
can result in nuisance pressure switch trips.
18
12” MIN. FROM
TOP OF INSULATION
10 FT. MAX.
INCLUDING
HORIZONTAL DIRECTION
#8 SCREW
!
CAUTION
USE OF SHEET METAL
AIR INTAKE PIPE INSTEAD
OF PVC MAY RESULT IN
NOISE ISSUES.
PVC
ELBOW
INSULATION
6” MINIMUM
CLEARANCE
PVC
COUPLER
EXHAUST
ATTIC SPACE
METAL FLUE PIPE ONLY
INDOOR SPACE
#8 SCREWS
COMBUSTION AND VENTILATION AIR (cont.)
VENTING
GENERAL INFORMATION
The furnace must be vented in accordance with these instructions, National Fuel Gas Code, ANSI Z223.1 and requirements
or codes of the local utility or other authority having jurisdiction.
WARNING
!
DEVICES ATTACHED TO THE FLUE OR VENT FOR THE
PURPOSE OF REDUCING HEAT LOSS UP THE CHIMNEY HAVE NOT BEEN TESTED AND HAVE NOT BEEN
INCLUDED IN THE DESIGN CERTIFICATION OF THIS
FURNACE. WE, THE MANUFACTURER, CANNOT AND
WILL NOT BE RESPONSIBLE FOR INJURY OR DAMAGE
CAUSED BY THE USE OF SUCH UNTESTED AND/OR UNCERTIFIED DEVICES, ACCESSORIES OR COMPONENTS.
DRAFT INDUCER
WARNING
!
VENT PIPE ATTACHING HOLES MUST BE PREDRILLED
IN THE DRAFT INDUCER COLLAR TO PREVENT DAMAGING THE INDUCER. DRILL 1/8” DIAMETER HOLES
THROUGH THE VENT PIPE AND COLLAR AND USE #8
SCREWS TO ATTACH. SEE FIGURE 16. FAILURE TO FOLLOW THIS WARNING CAN CAUSE RECIRCULATION OF
FLUE PRODUCTS CAUSING CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
FURNACE CATEGORY INFORMATION
This furnace is shipped as a Category I type induced draft furnace. A Category I furnace operates with a nonpositive vent
pressure and has a vent gas temperature at least 140°F above
the dew point of the vent gases. A Category I type may be a
draft hood equipped furnace or have a fan assisted combustion
system (induced draft). The inducer is used to pull flue products
through the combustion chamber and as they leave the furnace,
most of the energy has been dissipated. The buoyant effect of
the flue gases provides venting to the outdoors.
During the off cycle, the inducer is off and there is very little flow
through the vent, cooling the vent. During the on cycle there is
no dilution airflow, as with a draft hood type furnace. Although
the vent heats up rapidly without dilution air, the flue products
contain more water vapor, which results in a higher dew point
temperature. It is most important that you follow the guidelines
in these instructions to prevent the possible formation of condensation in the venting system.
As a Category I furnace it may be vented vertically with type
B-1 vent pipe and also may be common vented, as described in
these instructions.
Combustion Air
IMPORTANT APPLICATION NOTES
When the furnace is used as a replacement, the existing vent
system should be inspected to assure that there are no obstructions, blockage, or any signs of corrosion and is properly sized
for use with this furnace.
NOTE: When the vent table permits more than one diameter
of pipe for a connector or vent, the smallest permitted diameter
must be used.
Vent pipe may be type “B-1,” either rigid or suitable flexible construction that carries a U.L. listing.
Common venting is allowed with vertical B-1 vent systems, and
lined masonry chimneys. Follow the National Fuel Gas Code
ANSI Z223.1 or proper installation practices.
NOTE: Follow combustion air instructions as outlined in this
manual.
Single wall vent connectors to “B-1 vent or masonry chimneys”
may be used under the guidelines of the National Fuel Gas
Code ANSI Z223.1.
The entire length of the vent connector shall be readily accessible for inspection, cleaning and replacement.
“B-1” VERTICAL VENTING
NOTE: Refer to the National Fuel Gas Code, ANSI Z223.1.
Type “B-1” vents must be installed in accordance with the terms
of their listings and the vent manufacturer’s instructions.
“B-1” vents must be supported and spaced in accordance with
their listings and the manufacturer’s instructions. All vents must
be supported to maintain their minimum clearances from combustible material.
VERTICAL VENTING
Categorized
Furnace Vent
Input Size Recommended
(See NFGC)
50K 3”
75K *4”
100K *4”
125K *5”
150K *5”
*NOTE: All furnaces have a 3” vent connection as shipped from the factory. A 3” to 4”, 3” to 5”, or 4” to 5” vent transition may be required when
vertically vented or common vented with metal vent pipes. THE VENT
TRANSITION CONNECTION MUST BE MADE AT THE FURNACE
VENT EXIT. It must originate with an adapter if required, at the furnace
flue collar and terminate either in a listed cap or roof assembly. When
common venting, the vent connector size may differ from the above
diameters depending on application. See National Fuel Gas Code ANSI
Z223.1 or latest edition tables.
19
COMBUSTION AND VENTILATION AIR (cont.)
FIGURE 15TYPICAL VENTING WITH “B-1” VENT
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed
cap or listed roof assembly. Gas vents 12 inches in size or
smaller with listed caps shall be permitted to be terminated in
accordance with Figure 15, provided they are at least 8 feet
from a vertical wall or similar obstruction. All other gas vents
Combustion Air
shall terminate not less than 2 feet above the highest point
where they pass through the roof and at least 2 feet higher
than any portion of a building within 10 feet.
2. A type B-1 gas vent shall terminate at least 5 feet in vertical
height above the highest connected equipment draft hood or
flue collar.
3. Must rise 1/4” per foot away from the furnace on horizontal
runs and be supported with straps or hangers so it has no
sags or dips. Supports at 4 foot intervals and at all elbows are
recommended.
4. The vent connector must be mechanically fastened to the
outlet collar of the furnace with at least (2) sheet metal screws
except vent connectors that are B-1 material. These shall be
assembled in accordance with the manufacturer’s instructions. See Figures 16 and 17.
5. Any angle greater than 45 degrees from the vertical is considered horizontal. The total horizontal distance of a vent plus
the horizontal vent connector serving draft-hood equipped
appliances shall not be greater than 75 percent of the vertical
height of the vent.
Single appliance venting of a fan assisted furnace into a tilelined masonry chimney is prohibited. The chimney must be lined
with either Type B vent or with a listed, single wall, metal lining
system. Reference National Fuel Gas Code, ANSI Z223.1. See
Figure 18 for typical B-1 vent chase.
NOTE: A chimney adapter is available as an accessory (see
accessory section of this manual). Follow manufacturer’s instructions.
WARNING
!
DO NOT CONNECT THIS FURNACE TO A CHIMNEY USED
TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).
VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD
TO IMPROPER FUNCTIONING OF THE UNIT, AND DUE
TO SOOTING, THE POSSIBILITY OF FIRE RESULTING IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SPECIAL VENT SYSTEMS (SVS)
IMPORTANT: It is THE FURNACE MANUFACTURER’s posi-
tion now that new installations of any HTPV pipe used in a category III vent application, including Selkirk’s Selvent™ II HTPV
product, should cease immediately.
FIGURE 15
TYPICAL VENTING WITH “B-1” VENT
LISTED CAP
ST-A1220-24
ST-A1220-24
LISTED GAS VENT
X
12
ROOF PITCH“H” (MIN.) FT.
FLAT TO 6/12 1.0
OVER 6/12 TO 7/12 1.25
OVER 7/12 TO 8/12 1.5
OVER 8/12 TO 9/12 2.0
OVER 9/12 TO 10/12 2.5
OVER 10/12 TO 11/12 3.25
OVER 11/12 TO 12/12 4.0
OVER 12/12 TO 14/12 5.0
OVER 14/12 TO 16/12 6.0
OVER 16/12 TO 18/12 7.0
OVER 18/12 TO 20/12 7.5
OVER 20/12 TO 21/12 8.0
ROOF PITCH = X/12
FIGURE 16
ATTACHING TO DRAFT INDUCER COLLAR
A0991-01
20
COMBUSTION AND VENTILATION AIR (cont.)
FIGURE 17
1. STANDARD 3” FLUE CONNECTION.
2. 4” ADAPTER - OPTIONAL
SEE NATIONAL FUEL GAS CODE FOR SIZING OPTIONS
FRESH AIR INLET
1.
2.
Combustion Air
ST-A1220-09-01
FIGURE 18
DEDICATED VENTING THROUGH
CHIMNEY WITH “B-1” VENT
ST-A1220-09
21
COMBUSTION AND VENTILATION AIR (cont.)
POWER VENT SYSTEMS
When vertical venting is not possible, the only acceptable
method for horizontal venting is with the use of Tjernlund model
GPAK-1TR or Field Controls models SWG-4R power venter.
Type B vent pipe and fittings must be used. Common venting is
Combustion Air
not permitted
All application and installation instructions supplied with
the power venter must be followed.
Please address all questions regarding power venter installation, agency listings and furnace model compatibility to:
Tjernlund Products, Inc.
(800) 255-4208 or (612) 426-2993
Field Controls L.L.C.
(800) 742-8368 or (919) 522-0214
EXISTING VENT SYSTEMS
IMPORTANT RETROFIT
VENTING INSTRUCTIONS
If this furnace is a replacement installation, ALWAYS INSPECT
the existing vent system to be sure there are no obstructions,
blockages, or signs of corrosion.
When the existing furnace is removed from a venting system
serving other appliances, the venting is likely to be too large to
properly vent the remaining attached appliances.
The following steps shall be followed with each appliance that
remains connected to the common venting system, while the
other appliances that remain connected to the common venting
systems are not in operation.
NOTE: When the vent table permits more than one diameter of pipe for a connector or vent, the smallest permitted
diameter must be used.1. Seal any unused openings in the
common venting system.
NOTE: Ensure existing venting system complies with latest
addition of National Fuel Gas Code ANSI Z223.1 and all local
codes/regulations.
1. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage, restriction, leakage, corrosion or other deficiencies which could
cause an unsafe condition.
2. Insofar as is practical, close all building doors, windows and
all doors between the space where the appliances remaining
connected to the common venting system are located. Turn
on clothes dryers and any appliance not connected to the
common venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate
at maximum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
3. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so the appliance will operate continuously.
4. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or
candle, or smoke from a cigarette, cigar, or pipe.
5. After it has been determined that each appliance that remains
connected to the common venting system properly vents
(when tested as outlined above) return doors, windows,
exhaust fans, fireplace dampers and any other gas-burning
appliance to their previous conditions of use.
6. If improper venting is observed during any of the above tests,
the common venting system must be resized. Refer to National Fuel Gas Code, ANSI Z223.1.
22
GAS SUPPLY AND PIPING
GAS SUPPLY
IMPORTANT SAFETY INFORMATION
NATURAL GAS AND PROPANE
(LIQUEFIED PETROLEUM GAS / LPG)
SAFETY
GAS SUPPLY
WARNING
!
• FURNACES USING PROPANE GAS ARE DIFFERENT FROM NATURAL GAS MODELS. A NATURAL
GAS HEATER WILL NOT FUNCTION SAFELY ON
PROPANE AND VICE VERSA. CONVERSIONS OF
HEATER GAS TYPE SHOULD ONLY BE MADE BY
QUALIFIED INSTALLERS USING FACTORY SUPPLIED COMPONENTS. THE FURNACE SHOULD
ONLY USE THE FUEL TYPE IN ACCORDANCE
WITH LISTING ON RATING PLATE. ANY OTHER
FUEL USAGE WILL RESULT IN DEATH OR SERIOUS PERSONAL INJURY FROM FIRE AND/OR
EXPLOSION.
• BOTH NATURAL GAS AND PROPANE HAVE AN
ODORANT ADDED TO AID IN DETECTING A GAS
LEAK. SOME PEOPLE MAY NOT PHYSICALLY BE
ABLE TO SMELL OR RECOGNIZE THIS ODORANT. IF YOU ARE UNSURE OR UNFAMILIAR WITH
THE SMELL OF NATURAL GAS OR PROPANE,
ASK YOUR LOCAL GAS SUPPLIER. OTHER CONDITIONS, SUCH AS “ODORANT FADE,” WHICH
CAUSES THE ODORANT TO DIMINISH IN INTENSITY, CAN ALSO HIDE, CAMOUFLAGE, OR
OTHERWISE MAKE DETECTING A GAS LEAK BY
SMELL MORE DIFFICULT.
• UL OR CSA RECOGNIZED FUEL GAS DETECTORS ARE RECOMMENDED IN ALL ENCLOSED
PROPANE AND NATURAL GAS APPLICATIONS
WHEREIN THERE IS A POTENTIAL FOR AN EXPLOSIVE MIXTURE OF FUEL GAS TO ACCUMULATE.
FUEL DETECTOR INSTALLATION SHOULD BE IN
ACCORDANCE WITH THE DETECTOR MANUFAC-
TURER’S RECOMMENDATIONS AND/OR LOCAL
LAWS, RULES, REGULATIONS, OR CUSTOMS.
• BEFORE ATTEMPTING TO LIGHT THE FURNACE,
MAKE SURE TO LOOK AND SMELL FOR GAS
LEAKS. USE A SOAPY SOLUTION TO CHECK ALL
GAS FITTINGS AND CONNECTIONS.
BUBBLING AT A CONNECTION INDICATES A LEAK
THAT MUST BE CORRECTED. WHEN SMELLING TO
DETECT A GAS LEAK, BE SURE TO ALSO SNIFF
NEAR THE FLOOR. PROPANE GAS IS HEAVIER
THAN AIR AND TENDS TO COLLECT AT LOWER
LEVELS MAKING IT MORE DIFFICULT TO SMELL
AT NOSE LEVEL. NATURAL GAS IS LIGHTER THAN
(Continued on next column)
AIR AND WILL RISE, POSSIBLY ACCUMULATING IN
HIGHER PORTIONS OF THE STRUCTURE.
• IF A GAS LEAK IS PRESENT OR SUSPECTED:
- DO NOT ATTEMPT TO FIND THE CAUSE YOURSELF.
- NEVER USE AN OPEN FLAME TO TEST FOR
GAS LEAKS. THE GAS CAN IGNITE RESULTING
IN DEATH, PERSONAL INJURY, OR PROPERTY
DAMAGE.
- DO NOT TRY TO LIGHT ANY APPLIANCE.
- DO NOT TOUCH AND ELECTRICAL SWITCH.
- DO NOT USE ANY PHONE IN YOUR BUILDING.
- LEAVE THE BUILDING IMMEDIATELY AND CALL
THE GAS SUPPLIER FROM A NEIGHBOR’S
PHONE. FOLLOW THE GAS SUPPLIER’S IN-
STRUCTIONS.
- IF YOU CANNOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.
- DO NOT RETURN TO THE BUILDING UNTIL AUTHORIZED BY THE GAS SUPPLIER OR FIRE DEPARTMENT.
• SHOULD OVERHEATING OCCUR OR THE GAS
SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE FURNACE.
• CONSULT WITH THE LOCAL BUILDING DEPARTMENT AND FUEL GAS SUPPLIER BEFORE INSTALLING THE HEATER:
- THE INSTALLATION AND PURGING OF GAS
PIPING MUST CONFORM TO LOCAL CODES,
UTILITY COMPANY REQUIREMENTS, AND THE
LATEST EDITION OF NATIONAL FUEL GAS
CODE (NFGC) - ANSI Z223.1/NFPA 54.
- LP FURNACES SHOULD NOT BE INSTALLED
BELOW GRADE (IN A BASEMENT FOR EXAMPLE) IF SUCH INSTALLATION IS PROHIBITED BY
FEDERAL, STATE, PROVINCIAL, AND/OR LOCAL
LAWS, RULES, REGULATIONS, OR CUSTOMS.
- INSTALLATION OF A GAS PRESSURE REGULATOR MAY BE REQUIRED IN THE GAS SUPPLY
LINE. THE REGULATOR SHOULD NOT EXCEED
THE MAXIMUM SUPPLY PRESSURE LISTED ON
THE FURNACE RATING PLATE. DO NOT USE AN
INDUSTRIAL-TYPE GAS REGULATOR.
- FOLLOW ALL LOCAL CODES AND SECTION
8.3 OF NFGC WITH REGARD TO PURGING OF
GAS PIPING TO ENSURE THAT THE AIR AND/
OR FUEL GAS IN THE GAS PIPING IS PROPERLY
VENTED TO A LOCATION WHERE AN EXPLOSIVE MIXTURE CANNOT ACCUMULATE.
Gas Supply
23
GAS SUPPLY
GAS PIPING
WARNING
!
THIS FURNACE IS EQUIPPED AT THE FACTORY
FOR USE ON NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES A SPECIAL KIT IS
AVAILABLE AT THE DISTRIBUTOR. FAILURE TO
USE THE PROPER CONVERSION KIT CAN CAUSE
FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH. SEE THE CONVERSION KIT INDEX
SUPPLIED WITH THE FURNACE. THIS INDEX IDENTIFIES THE PROPER LP GAS CONVERSION KIT
REQUIRED FOR EACH PARTICULAR FURNACE.
IMPORTANT: Any additions, changes or conversions required
for the furnace to satisfactorily meet the application should be
made by a qualified installer, service agency or the gas supplier,
Gas Supply
using factory-specified or approved parts.
IMPORTANT: Connect this furnace only to gas supplied by a
commercial utility or commercial fuel provider.
IMPORTANT: A U.L. or CSA recognized fuel gas and CO detec-
tor(s) are recommended in all applications, and their installation
should be in accordance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
Install the gas piping according to all local codes, state codes
and regulations of the utility company, whichever holds jurisdiction.
If possible, run a separate gas supply line directly from the meter
to the furnace. Consult the local gas company for the location of
the manual main shut-off valve. The gas line and manual gas
valve must be adequate in size to prevent undue pressure
drop and never smaller than the pipe size to the combination gas valve on the furnace. Refer to Table 6 for the recom-
mended pipe size for natural gas and Table 7 for LP gas pipe
sizes.
IMPORTANT: It is permissible to run flexible gas connector in-
side the unit to a piece of black pipe. If local codes allow the use
of a flexible gas appliance connector, always use a new listed
connector. Do not use a connector which has previously serviced
another gas appliance. Massachusetts law limits flexible gas
connectors to a maximum of 36”.
Install a ground joint union outside the cabinet and within
3 feet to easily remove the control valve assembly. Install
a manual shut-off valve in the gas line outside the furnace
casing. The valve should be readily accessible to turn the gas
supply on or off. Install a drip leg in the gas supply line as close
to the furnace as possible. Always use a pipe compound resistant to the action of liquefied petroleum gases on all threaded
connections.
IMPORTANT: When making gas pipe connections, use a
back-up wrench to prevent any twisting of the control assembly
and gas valve. Do not overtighten the connection.
Any strains on the gas valve can change the position of the gas
orifices in the burners. This can cause erratic furnace operation.
IMPORTANT: ENSURE that the furnace gas control valve not be
subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual shut-off valve from
the gas supply piping during any pressure testing that ex-
ceeds 1/2 PSIG (3.48 kPa).
FIGURE 19
GAS PIPING INSTALLATION
GAS PIPE INSTALLATION
MANUAL GAS VALVE
(IN CLOSED
POSITION)
4 TO 5 FEET
ABOVE FLOOR
REQ’D BY SOME
UTILITIES
DRIP LEG
4 TO 5 FEET
ABOVE FLOOR
REQ’D BY SOME
UTILITIES
DRIP LEG
UNION
DIRECT
SPARK
IGNITOR
BURNERS
FLAME SENSOR
UPFLOW
BURNERS
FLAME SENSOR
HORIZONTAL
MANUAL GAS VALVE
(IN CLOSED POSITION)
DUCT
MANIFOLD
UNION
GAS VALVE
MANIFOLD
DIRECT SPARK
IGNITOR
GAS VALVE
24
GAS PRESSURE
IMPORTANT: ENSURE that the furnace gas valve is not to be
subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual manual gas stop
from the gas supply piping during any pressure testing that
exceeds 1/2 PSIG. (3.48 kPa).
Natural gas supply pressure must be 5” to 10.5” w.c. LP
gas supply pressure must be 11” to 13” w.c. This pressure
must be maintained with all other gas-fired appliances in
operation.
The minimum gas supply pressure to the gas valve for proper
furnace input adjustments is 5” w.c. for natural gas, however 6”
to 7” is recommended. The minimum gas supply pressure is 11”
w.c. for LP gas.
CAUTION
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT
THE FURNACE INPUT RATING BE ADJUSTED
AND THAT THE SIZE OF THE BURNER ORIFICES
BE RECALCULATED BASED ON ELEVATION AND
GAS HEATING VALUE. THE BURNER ORIFICES
MAY (OR MAY NOT) NEED TO BE CHANGED. SEE
THE SECTION TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS BOOK FOR INSTRUCTIONS.
FIGURE 20A
TYPICAL GAS VALVE (HONEYWELL)
REGULATOR CAP
GAS SUPPLY (cont.)
FIGURE 20B
WHITE RODGERS GAS VALVE
REGULATOR
CAP
WARNING
!
NEVER PURGE A GAS LINE INTO THE COMBUSTION
CHAMBER. NEVER USE MATCHES, FLAME OR ANY
IGNITION SOURCE FOR CHECKING LEAKAGE. FAILURE TO ADHERE TO THIS WARNING CAN CAUSE
A FIRE OR EXPLOSION RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
TO CHECK FOR GAS LEAKAGE, USE AN APPROVED CHLORIDE-FREE SOAP AND WATER
SOLUTION, OR OTHER APPROVED METHOD.
Gas Supply
GAS VALVE
This furnace has a 24-volt gas valve. It has ports for measuring
supply and manifold gas pressure. The valve body contains a
pressure regulator to maintain proper manifold gas pressure.
A control switch is on the valve body. It can be set to only the
“ON” or “OFF” positions. The gas valve is a slow-opening
valve. See Figures 20A and 20B.
When energized, it takes 2 to 3 seconds to fully open.
TABLE 6
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be determined
by consulting the local natural gas utility or the LP gas supplier.
Gas Input of Furnace (BTU/HR)
Heating Value of Gas (BTU/FT3)
25
GAS SUPPLY (cont.)
SETTING GAS PRESSURE
The maximum gas supply pressure to the furnace must
not exceed 10.5” w.c. natural gas, or 13” w.c. LP gas. The
minimum supply gas pressure to the gas valve should be 59 w.c.
natural gas or 119 w.c. LP gas. A properly calibrated manometer
is required for accurate gas pressure measurements.
SUPPLY GAS PRESSURE
MEASUREMENT
An inlet pressure tap is on the input side of the gas valve.
1. With gas shut off to the furnace at the manual gas valve
outside the unit, remove the inlet pressure tap plug.
2. Connect a manometer to the pressure tap.
3. Turn on the gas supply and operate the furnace and all
Gas Supply
other gas-fired units on the same gas line as the furnace.
4. Note or adjust the line gas pressure to give:
A. 59 - 10.59 w.c. for natural gas.
B. 119 - 139 w.c. for LP gas.
5. Shut off the gas at the manual gas valve and remove the
manometer and hose.
6. Replace the pressure tap plug before turning on the gas.
7. Turn on the gas supply and check for gas leaks using an
approved leak detector. Do NOT use a flame of any kind to
check for leaks. Repair any leaks and repeat.
If the supply gas line pressure is above these ranges,a high
pressure in line gas regulator may be required. Consult local
gas utility. With LP gas, have the LP supplier reduce the line
pressure at the regulator.
If supply gas line pressure is below these ranges, either remove
any restrictions in the gas supply piping or enlarge the gas pipe.
See Tables 6 and 7. With LP gas, have the LP supplier adjust
the line pressure at the regulator.
CAUTION
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE
SIZE OF THE BURNER ORIFICES BE RECALCULATED
BASED ON ELEVATION AND GAS HEATING VALUE. THE
BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE
CHANGED. SEE THE SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS” OF THIS BOOK FOR INSTRUCTIONS.
MANIFOLD GAS PRESSURE
MEASUREMENT
Natural gas manifold pressure should be 3.5” (± .3) w.c. LP
gas manifold pressure should be 10.0” (± .5) w.c. Only small
variations in gas pressure should be made by adjusting the
pressure regulator.
1. With the gas to the unit shut off at the manual gas valve,
remove the outlet pressure tap plug.
2. Connect a manometer to this pressure tap.
3. Turn on the gas supply and operate the furnace (apply a
heat call).
4. Note or adjust the manifold gas pressure to give:
A. 3.59 (± .3) w.c. for natural gas.
B. 10.09 (± .5) w.c. for LP gas.
5. To adjust the pressure regulator, remove the regulator cap.
(See Figures 20A and 20B.)
6. Turn the adjustment screw clockwise to increase pressure,
or counterclockwise to decrease pressure.
7. Securely replace the regulator cap.
8. Shut off gas at the manual gas valve and remove the manometer and hose.
9. Replace the pressure tap plug before turning on the gas.
10. Turn on the gas supply and apply a heat call to the furnace
then check for gas leaks using an approved leak detector.
Do NOT use a flame of any kind to check for leaks. Repair
any leaks and repeat.
26
GAS PRESSURE
LP CONVERSION
NOTE: The valve can be converted to use liquified petro-
leum (LP) gas by replacing the pressure regulator spring
with the conversion kit spring. This LP kit spring allows the
regulator to maintain the proper manifold pressure for LP
gas. See Figure 21.
NOTE: Order the correct LP conversion kit from the furnace manufacturer. Furnace conversion to LP gas must
be performed by a qualified installer, service agency or the
gas supplier.
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas,
remove the NOx insert assemblies. Steps for removal are listed
below:
1. Turn off all electrical power and the gas supply to the furnace.
2. Remove the burner door from the furnace.
3. Remove the burner assembly – handle with care.
4. Remove the two screws attaching the NOx insert retainer
bracket to the center panel and remove NOx inserts.
5. Put the two screws back into the holes in the center panel.
6. Re-install the burner assembly.
7. Replace burner door.
8. Turn on electrical power and gas supply to the unit.
NOTE: Some NOx models may have one less NOx insert.
ORIFICE INSTALLATION
LP Gas is a manufactured gas that has consistent heating
value across most regions.
The Sea Level input should still be reduced by 4% per
thousand ft. and the orifice size must be selected based
on the reduced input selection chart in High Alt. Instruction
Section.
To change orifice spuds for either conversion to LP or for
elevation:
1. Shut off the manual main gas valve and remove the
gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
4. Turn the gas supply back on and check for proper operation and manifold pressure.
5. Attach the notice label alerting the next service technician that the furnace has been converted to LP gas.
WARNING
!
LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FERTILIZER) EXCEPT LP GAS. THIS INCLUDES ALL
DELIVERY VESSELS (LP TRUCKS). IF MATERIAL
OTHER THAN LP GAS IS USED IN THE SAME VESSELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE
FURNACE. THIS WILL VOID THE MANUFACTUR-
ER’S WARRANTY. CONTACT THE SUPPLIER TO
MAKE SURE FERTILIZER IS NOT USED IN THE
SAME TANKS USED TO STORE AND DELIVER LP
GAS.
FIGURE 21
TYPICAL LP KIT CONTENTS
LP Conversion
TABLE 7
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column
inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4” IPS required.
27
ELECTRICAL WIRING
ELECTRICAL WIRING
WARNING
!
TURN OFF ELECTRIC POWER AT FUSE BOX OR
SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS. FAILURE TO DO SO CAN
CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
!
THE CABINET MUST HAVE AN UNINTERRUPTED
GROUND ACCORDING TO THE LATEST EDITION
OF THE NATIONAL ELECTRICAL CODE, ANSI/
NFPA70 OR LOCAL CODES THAT APPLY. DO NOT
USE GAS PIPING AS AN ELECTRICAL GROUND. A
GROUND SCREW IS PROVIDED IN THE JUNCTION
BOX. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY
OR DEATH.
WARNING
!
THIS FURNACE IS EQUIPPED WITH A BLOWER
DOOR SAFETY SWITCH. DO NOT DISABLE THIS
SWITCH. FAILURE TO FOLLOW THIS WARNING
CAN RESULT IN ELECTRICAL SHOCK, PERSONAL
INJURY OR DEATH.
These may be obtained from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
FIGURE 22
LOCKING
TABS
ST-A1220-05
ELECTRICAL CONNECTIONS
Before proceeding with the electrical connections, be certain
that the voltage, frequency and phase corresponds to that specified on the furnace rating plate. For single furnace application,
maximum over-current protection is 15 amperes.
Use a separate fused branch electrical circuit containing a properly sized fuse or circuit breaker. Run this circuit directly from
the main switch box to an electrical disconnect that is readily
accessible and located near the furnace (as required by code).
Connect from the electrical disconnect to the junction box on the
left side of the furnace, inside the blower compartment. For the
proper connection, refer to the appropriate wiring diagram located on the inside cover of the furnace control box and in these
instructions.
NOTE: The electrical junction box may be moved to the right
side if necessary. A knockout is provided. Seal the opposite hole
with plug provided.
NOTE: L1 (hot) and L2 (neutral) polarity must be observed
when making field connections to the furnace. The ignition control may not sense flame if L1 and L2 are reversed. Make all
electrical connections in accordance with the latest edition of the
National Electrical Code ANSI/NFPA70.
Electrical Wiring
REVERSING THE ELECTRICAL
CONNECTION (JUNCTION BOX)
NOTE: Reversing the junction box is not possible in 14.0 inch
cabinets.
If the line voltage electrical needs to be moved to the opposite
side of the furnace, the following steps should be taken:
1. The furnace must NOT be electrically connected to line voltage prior to reversing the electrical connection.
2. Disconnect the wires from the door switch.
3. Remove the junction box from the furnace cabinet wall by
removing the two screws that hold it to the cabinet. Leave
the wires connected to the junction box.
4. Remove 7/8” plug from hole opposite j-box location. Drill 2
@ 3/16” Ø holes in the jacket. NOTE: Dimples/marks are
provided in the sheet metal for correct drilling location.
5. Move the junction box to the opposite side of the cabinet.
Install using the two screws removed in step 3 above. Note
that all screws penetrating the junction box must be blunt –
no sharp tipped screws can be used.
6. Replace the plug from the opposite of the furnace (the new
j-box location) to the old j-box location and install qty=2 1/4”
plugs from parts bag in empty screw holes in old location of
j-box into the mounting screw holes in the old junction box
location.
28
ELECTRICAL WIRING
REVERSING ELECTRICAL CONNECTION & THERMOSTAT
7. Using a flat screwdriver, squeeze the retaining arms on the
door switch and gently pry the door switch from it’s opening.
8. Install the door switch in the same opening on the opposite
of the furnace and reconnect the electrical connectors (removed in Step 2) to the door switch.
THERMOSTAT
The room thermostat must be compatible with the furnace.
See manufacturer’s thermostat spec sheet for compatability
concerns. Generally, all thermostats that are not of the “current
robbing” type are compatible with the integrated furnace control.
The low voltage wiring should be sized as shown.
FIGURE 23
TYPICAL THERMOSTAT WIRING
NOTE: Do not use 24 volt control wiring smaller than No. 18
AWG.
Install the room thermostat in accordance with the instruction
sheet packed in the box with the thermostat. Run the thermostat
lead wires inside the blower compartment and connect to low
voltage terminals as shown on the wiring diagram. Never install
the thermostat on an outside wall or where it will be influenced
by drafts, concealed hot or cold water pipes or ducts, lighting
fixtures, radiation from fireplace, sun rays, lamps, televisions,
radios or air streams from registers.
FIGURE 24
ISOLATION RELAY FOR CURRENT-ROBBING THERMOSTAT
FIGURE 25
LINE VOLTAGE CONNECTIONS
LINE
L1B XFMRHUM
EAC
P2
ST-A1227-04
NEUTRALS
SPARK
IGNITION
TOWER
ST-A1220-18-00
ST-A0804-01
Electrical Wiring
29
ACCESSORIES
ST-A1220-27-00
1. STANDARD 3” FLUE CONNECTION.
2. 4” ADAPTERSEE NATIONAL FUEL GAS CODE FOR SIZING OPTIONS
1.
2.
FIELD INSTALLED OPTIONAL ACCESSORIES
ELECTRONIC AIR CLEANER
Line voltage power can be supplied from the terminal labeled
“EAC” and a line voltage neutral terminal on the control board.
This will power the electronic air cleaner whenever the circulat-
Accessories
ing air blower is in operation.
HUMIDIFIER
Line voltage power is supplied from the terminal labeled “HUM”
to a line voltage neutral terminal on the control board. This will
power the humidifier whenever the induced draft motor is energized.
NOTE: Maximum current – 1.0 amps for each option (humidifier
or electronic air cleaner).
RXGW-C01 4-INCH FLUE ADAPTER
(See Figure 26)
Refer to “Venting” section of this manual for more information.
See National Fuel Gas Code for sizing options.
FIGURE 26
1. STANDARD 3” FLUE CONNECTION
2. 4” ADAPTER OPTIONAL
SEE NATIONAL FUEL GAS CODE FOR SIZING OPTIONS
FILTERS (See Figure 27)
Keep filters clean at all times. A filter is not provided with the
furnace, but one must be field-supplied and installed.
It is recommended to replace the furnace filter periodically to
maintain optimum furnace performance.
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: CHIMNEY ADAPTER IS CERTIFIED FOR USE
ON 80% SINGLE STAGE CONSTANT TORQUE MODELS.
This appliance is CSA certified for use with RXGW-B01 Chimney
Adapter. Refer to Kit Installation Instructions 92-101682-01.
30
ST-A1220-27
ACCESSORIES
FIELD INSTALLED OPTION ACCESSORIES (cont.)
FIGURE 27
FILTER LOCATIONS
FLANGE WRAPS
AROUND BACK AND
SCREWS TO THE
REAR OF THE
FURNCE, AT THE
LOCATIONS
PROVIDED
CUT OUT USING
EMBOSSED ANGLES
AS A GUIDE
FOR PROPER SIZE
23” X 14”
FIELD SUPPLIED FILTER
RXGF-CD
ACCESSORY FILTER RACK
SIDE RETURN
ST-A1220-07-X0
Accessories
ST-A1220-07-00
FIELD SUPPLIED FILTER
BOTTOM RETURN
RXGF-CB ACCESSORY
FILTER RACK
RXGF-CB
ACCESSORY FILTER RACK
FIELD SUPPLIED FILTER
ST-A1220-06-X0
HORIZONTAL RETURN
ST-A1220-06-00
31
TWINNING
FURNACE TWINNING INSTALLATIONS
Twinning operation of two furnaces, installed side-by-side, connected by a common duct system with main power supplied by
the same source, and controlled by a common thermostat can
be done with the UT Electronic Controls 1194-250 integrated
control boards.
IMPORTANT: Only twin furnaces with identical control boards.
IMPORTANT: Only bottom returns can be used. No more than
two furnaces can share the same supply and return. Furnaces
must have same heating and blower capacity. Twinning furnaces
must operate off the same phase of power.
It should be noted that both blowers will run simultaneously when
there is a call for heating, cooling or fan.
NOTE: Duct system must be adequate to provide correct airflow
to each furnace for supply and return.
Twinning
UT ELECTRONIC CONTROLS
1194-250 CONTROL BOARD
(62-104058-02)
1. Single Stage Operation
a. Control board “ONE” is on furnace connected to the ther-
mostat.
b. The 24 VAC supply to both control boards must be in
phase with each other.
c. Connect the “C,” “W” and “TWIN” terminals to counter-
parts on each control.
d. Twinning is automatically detected when wire is con-
nected to the twin terminal on both controls. If twinning
is detected and then lost in the same power cycle, the
furnace control will declare and display fault code 20 at
the seven-segment display.
See Figure 28 for twinning wire diagram for 1-stage thermostat.
See Figure 29 for twinning wire diagram for 2-stage thermostat.
32
CONTROL BOARDS
UT ELECTRONIC CONTROLS 1194-250 CONTROL BOARD, TWINNING CONNECTION -- SINGLE PHASE OPERATION
TWINNING
THERMOSTAT
R
G
W
Y
CONTACTOR
COOLING
ST-A1220-25-00
Twinning
FIGURE 28
UT ELECTRONIC CONTROLS 1194-250 CONTROL BOARD, TWINNING CONNECTION – SINGLE STAGE OPERATION
33
TWINNING
UT ELECTRONIC CONTROLS 1194-250 CONTROL BOARD, TWINNING CONNECTION -- TWO PHASE OPERATION
CONTROL BOARDS (cont.)
THERMOSTAT
ST-A1220-26-00
Twinning
R
Y
G
CONTACTOR
COOLING
W1
W2
34
FIGURE 29
UT ELECTRONIC CONTROLS 1194-250 CONTROL BOARD, TWINNING CONNECTION – TWO STAGE OPERATION
NATURAL GAS AT HIGH ALTITUDES
HIGH ALTITUDE
WARNING
!
INSTALLATION OF THIS FURNACE AT ALTITUDES ABOVE
2000 FT (610 m) SHALL BE IN ACCORDANCE WITH LOCAL
CODES, OR IN THE ABSENCE OF LOCAL CODES, THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54.
CAUTION
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE
SIZE OF THE BURNER ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS HEATING VALUE. THE
BURNER ORIFICES MAY (OR MAY NOT) NEED TO BE
CHANGED. THE FOLLOWING EXAMPLES SHOW HOW
TO DETERMINE IF AN ORIFICE CHANGE WILL BE NECESSARY AND HOW TO DETERMINE THE NEW ORIFICE
SIZE.
34” 80 Plus furnaces installed above 2,000 ft. require the furnace
to be de-rated 4% per thousand feet above sea level.
IMPORTANT: Factory installed orifices are calculated and sized
based on a sea level Natural Gas heating value of 1050 BTU per
cubic ft.
NOTE: Orifices are available through your local distributor.
Reference Table 8 for approximate orifice sizing.
The following are examples of orifice sizing using the National
Fuel Gas Code Appendix E, 2015 edition.
For a simplified estimation of orifice size based on gas heating
value and elevation, Table 8 may be used. However, calculations
are the best method.
Example: 900 BTU/ft3 Regional Natural Gas Heating Value
I/H = Q
25000 / 900 = 27.78 ft
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 900
Q = 27.78 ft3 Natural Gas per hour.
From Table E1.1a of National Fuel Gas Code, 2015 (3.5( w.c.
column).
3
Orifice required at Sea Level: #40
From Table E1.1d of National Fuel Gas Code, 2015. Orifice re-
quired at 5000 ft. elevation (4% de-rate per thousand ft): #42
Orifice required at 8000 ft. elevation (4% de-rate per thousand
ft.): #44
Example: 1050 BTU/ft3 Regional Natural Gas Heating Value
I / H = Q
25000 / 1050 = 23.81ft
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 1050
Q = 23.81 ft3 Natural Gas per hour.
From Table E1.1a of National Fuel Gas Code, 2015 (3.59 w.c.
column).
Orifice required at Sea Level: #43
From Table E1.1d of National Fuel Gas Code, 2015
Orifice required at 5000 ft. elevation (4% de-rate per
thousand ft.): #45
Orifice required at 8000 ft elevation (4% de-rate per
thousand ft): #47
3
ORIFICE ORDERING INFORMATION
Orifice sizes are selected by adding the 2-digit drill size required
in the orifice part number. Drill sizes available are 39 through 64;
metric sizes available 1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill size)
Example:
# 60 drill size orifice required
Part # 62-22175-60
High Altitude
35
HIGH ALTITUDE
Notes:
3. This chart is based on the National Fuel Gas Code (NFGC) Annex F based on natural gas with a secific gravity of 0.60
5. Furnace operation is optimized when operating at design rate. Installer is responsible to verify rate.
6. This table applies to 80+ models only with 25,000BTU/Burner. DO NOT USE THIS CHART FOR ANY 90+ FURNACE MODEL.
NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE & ELEVATION*
2.
Installer must be aware of the local heating value (sea level standard) to use the chart below.
4. The recommended orifices below allow the furnace to operate within 10% of design rate. However, NFGC calculations are the best method.
1. All(-)80+ units are factory equiped with orifices sized for 1050 sea level heating value gas.
Notes:
3. This chart is based on the National Fuel Gas Code (NFGC) Annex F based on natural gas with a secific gravity of 0.60
Sea Level
to 1,999'
2,000' to
2,999'
3,000' to
3,999'
4,000' to
4,999'
5,000' to
5,999'
6,000' to
6,999'
7,000' to
7,999'
8,000' to
8,999'
9,000' to
9,999'10,000'
4344444445454647474842424343434444454647
42
424343434444454647
41
424242434344444546
40
41
42
42424343444445
39
404141424243434444
38
394041414242434344
37
383939404142424343
37
383939404142424343
36
373838394041414243
35
363637373839404142
5. Furnace operation is optimized when operating at design rate. Installer is responsible to verify rate.
6. This table applies to 80+ models only with 25,000BTU/Burner. DO NOT USE THIS CHART FOR ANY 90+ FURNACE MODEL.
NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE & ELEVATION*
*Table is derived from Appendix of the National Fuel Gas Code. To determine the correct orifice for your installation consult the National Fuel Gas Code tables F.1 and F.4
2.
Installer must be aware of the local heating value (sea level standard) to use the chart below.
4. The recommended orifices below allow the furnace to operate within 10% of design rate. However, NFGC calculations are the best method.
1. All(-)80+ units are factory equiped with orifices sized for 1050 sea level heating value gas.
ELEVATION
Grey Cells Indicate Factory
Orifice Size
Gas Heating
Value
(BTU's/ft
3
)
@ Sea
Level**
1,000-1,100
900-999
800-899
700-799
NATURAL GAS AT HIGH ALTITUDES (cont.)
TABLE 8
SUPPLEMENTAL ORIFICE SIZE CHART
NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE & ELEVATION*
Notes:
1. All (-)80+ units are factory equipped with orices sized for 1050 sea level heating value gas.
2. Installer must be aware of the local heating value (sea level standard) to use the chart below.
3. This chart is based on the National Fuel Gas Code (NFGC) Annex E, 2015 Edition, based on natural gas with a specic gravity of 0.60
4. The recommended orices below allow the furnace to operate within 10% of design rate. However, NFGC calculations are the best method.
5. Furnace operation is optimized when operating at design rate. Installer is responsible to verify rate.
6. This table applies to 80+ models only with 25,000BTU/Burner. DO NOT USE THIS CHART FOR ANY 90+ FURNACE MODEL.
ELEVATION
High Altitude
36
Grey Cells Indicate Factory
Orifice Size
1,000-1,100
Gas Heating
Value
(BTU's/ft
@ Sea
Level**
*Table is derived from Appendix of the National Fuel Gas Code. To determine the correct orice for your installation consult the National Fuel Gas
Code tables E1.1(a) and E1.1(d), 2015 Edition
**Be sure to use sea level heating value. When requesting the heating value from a local utility, it must be converted to sea level equivalent
in order to use this table.
NOTE: Keep any parts removed during LP conversion procedure
stored with the product literature for future use.
LP Gas is a manufactured gas that has consistent heating value
across most regions.
The NFGC guidelines are used with the following exception:
The recommended LP Gas high altitude orifice selections differ
slightly in that the NFGC LP orifice chart, as they are not accurate for these products. The National Fuel Gas Code LP orifices
TABLE 9
LP GAS
IMPORTANT: 80+ MODELS ONLY! DO NOT
USE THIS CHART WITH ANY 90+ MODELS.
Input (per Orifice
Altitude burner) 25000 Size
0 to 2000 ft. 25,000 54
2000*-3000* 23,000 54
3000*-4000* 22,000 54
4000*-5000* 21,000 54
5000*-6000* 20,000 55
6000*-7000* 19,000 55
7000*-8000* 18,000 55
8000*-9000* 17,000 55
9000*-10000* 16,000 55
are based on an 11” of water column pressure at the orifice,
which differs from products that use 10” of water column at the
orifice. This difference requires a deviation from the NFGC orifice size recommendations. The Sea Level input should still be
reduced by 4% per thousand ft. and the orifice size must be selected based on the reduced input in Table 9.
High Altitude
37
START-UP PROCEDURES
SEQUENCE OF OPERATIONS
This furnace is equipped with a direct ignition control. Each time
the room thermostat calls for heat, the ignitor lights the main
burners directly. See the lighting instructions on the furnace.
TO START THE FURNACE
1. Remove the burner compartment control access door.
2. IMPORTANT: Be sure that the manual gas control has been
in the “OFF” position for at least five minutes. Do not attempt
to manually light the main burners.
3. Turn off the furnace electrical power and set the room thermostat to its lowest setting.
4. Turn the gas control to the “ON” position or move the gas
control lever to the “On” position.
5. Replace the burner compartment control access door.
6. Turn on the furnace electrical power.
7. Set the room thermostat to a point above room temperature
to light the main burners.
8. After the burners are lit, set the room thermostat to a desired
temperature.
9. Operate gas heat for a minimum period of 15 minutes and
adjust input rate. (See Section of this book titled Adjusting Input Rate.)
TO SHUT DOWN THE FURNACE
1. Set the room thermostat to its lowest setting and wait for furnace to shut down.
2. Remove the burner compartment control access door.
3. Shut off the gas to the main burners by turning the gas control to the “OFF” position.
WARNING
!
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY
FAIL TO SHUT OFF, CLOSE THE MANUAL GAS VALVE
FOR THE APPLIANCE BEFORE SHUTTING OFF THE
ELECTRICAL SUPPLY. FAILURE TO DO SO CAN CAUSE
AN EXPLOSION OR FIRE RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
Start-Up Procedure
SEQUENCE OF OPERATION
UT ELECTRONIC CONTROLS
Integrated Controls with Direct Spark Ignition.
1. Each time the thermostat “W” (Heating) contacts close, the
furnace control checks to make sure the pressure switch is
open. Next the induced draft blower (inducer) begins a prepurge cycle.
2. The air proving negative pressure switch(es) closes.
3. After the 30-second pre-purge, the gas valve opens for an
8-second trial for ignition.
4. The spark igniter is energized to light the gas burners and
stays energized for the up to 7 seconds after the gas
valve opens.
5. 8 seconds after the gas valve opens the remote flame sensor must prove flame ignition for one second using the
process of flame rectification. If the burners don’t light, the
system goes through another ignition sequence. It does this
up to four times before entering a 1-hour lockout.
6. The main blower starts approximately 20 seconds after the
burners ignite.
7. When the thermostat “W” (Heat Call) ends, the gas valve
closes, flame is extinguished, the induced draft blower stops
after a 10-second post-purge, and the negative pressure
switch opens.
8. The main blower continues until timed off by the setting on
the integrated furnace control board.
Sequence if the system doesn’t light or doesn’t sense
flame:
1. On a call for heat, the furnace control checks to make sure
the pressure switch is open. Next the control runs the inducer for 30 seconds to prepurge.
2. After the 30-second pre-purge, the gas valve opens for an
8-second trial for ignition. The inducer continues and the igniter stays energized.
3. If flame is not sensed during the 8th second after the gas
valve opens, the gas valve closes, and the igniter de-energizes.
4. The inducer stops (may take up to 20 seconds for inducer
fan to stop rotating) and the control verifies that the pressure switch has opened. Once the open pressure switch
is confirmed, the control begins the next ignition cycle by
energizing the inducer for a pre-purge of 30 seconds. After a
30-second pre-purge period, the gas valve is energized and
the control looks for a flame signal for up to 8 seconds. If no
flame is sensed, the cycle is repeated up to 4 times before
entering a 1-hour lockout.
38
FAULT CODES
FAULT CODES
DIAGNOSTICS AND FAULT CODES
All furnace controls come standard with a 7-segment diagnostic
display. During standby mode with no fault codes present, the
display will read “0” (zero). During normal thermostat heating,
cooling or continuous fan operation, a letter will be displayed to
describe the mode of operation as follows:
C = Cooling or Heat-Pump Heat Operation
F = Continuous Fan Operation
H = Gas Heating Operation
When the control senses a fault present, it will display a code to
help in diagnoses. A list of normal operating codes and potential
fault codes follows:
CODE Description
0 STANDBY
C COMPRESSOR ON
(COOLING OR HEAT-PUMP HEAT)
H GAS HEAT ON
F CONTINUOS FAN ON
10 1 HOUR LOCKOUT
11 FAILED IGNITION
12 LOW FLAME SENSE
13 FLAME LOST
14 UNEXPECTED FLAME
20 TWINNING FAULT
22 MAIN LIMIT OR HALC OPEN
26 LINE AND NEUTRAL REVERSED
33 MRLC (MANUAL RESET LIMIT
CONTROL) (AKA ROLL-OUT) OPEN
55 PRESSURE SWITCH STUCK
CLOSED WHEN SHOULD BE OPEN
57 PRESS SWITCH STUCK OPEN
WHEN SHOULD BE CLOSED
61 BLOWER FAULT – BLOWER
UNABLE TO RUN
93 INTERNAL CONTROL FAULT
The method for displaying a two-digit fault is to display the first
(most significant) digit for one second immediately followed by
the second digit – which is also displayed for a duration of one
second. A ½ second pause is then displayed. Cycle repeats
until the fault is cleared. Each fault is flashed (displayed) a minimum of two times even if the fault condition has cleared before
the fault can be displayed twice.
DUAL FAULTS DISPLAYED
In some cases when two faults are present simultaneously, both
faults are displayed. These exceptions for dual faults are noted
below.
Sequence of display:
A. The first two-digit fault will be displayed once as described
above.
B. The upper-most horizontal segment of the seven-segment
display is energized for ½ second.
C. The second two-digit fault is displayed once as described
above.
D. The upper-most horizontal segment of the seven-segment
display is energized for ½ again.
This cycle repeats until one fault is gone (in which case the
remaining fault will be displayed as described above) or both
faults are gone or otherwise as noted below:
1. When a failed ignition has occurred four times in a row, the
control enters one-hour lockout and fault codes “10” and
“11” will be displayed alternately as described above.
2. When flame is lost five times in a row, the control enters
one-hour lockout and fault codes “10” and “13” will be displayed alternately as described above (A-D).
3. While the control is in one-hour lockout due to an unex-
pected flame, the fault codes “14” (unexpected flame) and
“10” (soft lockout) will be displayed alternately at the seven-segment display as described above (A-D).
4. While the control has entered a one-hour lockout after declaring a dead blower after the main limit control has been
open for more than 150 seconds, the fault codes “61”
(Non-operational blower) and “10” (soft lockout) will be
displayed alternately as described above (A-D). Note: the
dead blower fault and associated one-hour lockout will occur
up to four times in one heat call. Upon declaring this fault
for the fourth time in one heat call, the control will enter hard
lockout.
5. When the main limit has been open during a gas heat call
for more than 150 seconds and has not yet re-closed, the
fault codes “61” (Non-operational blower) and “22” (open
limit) will be displayed alternately as described above (A-D)
until the limit re-closes.
The higher priority fault code will be displayed until the condition
is corrected then the lower priority fault code will display (provided the fault condition is still present).
Fault Codes
39
1-STAGE LOCKOUT
LOCKOUT
All lockout conditions can be cleared immediately provided that
the original fault causing the lockout is cleared and power to the
unit is cycled off and then back on again or (soft lockout only) if
Lockout
a heat call is cycled off for greater than 2 seconds but less than
20 seconds.
The furnace control will not initiate a heat cycle during any
lockout condition. A call for compressor or continuous fan will
generally be responded to but control will display the lockout
error fault code instead of the “C” (for compressor) or “F” (for
Continuous fan).
FIVE-MINUTE LOCKOUT
A five minute “soft” lockout will be initiated if the low pressure
switch fails to close after 60 seconds of continuous inducer operation at the beginning of a normal heat cycle (pressure switch
proving period). The seven-segment display will display the
appropriate fault. Lockout will automatically be reset after five
minutes.
ONE-HOUR LOCKOUT
A one hour “soft” lock out will be initiated when:
- Flame has not been detected after four ignition trials.
- Flame has been lost for ve times in one heat call.
- Undesired ame has been detected. The one-hour period will
commence after ame is no longer detected.
- Dead Blower has been detected (main limit circuit open for
more than 150 seconds)
- When voltage has unexpectedly been detected on the gas
valve circuit and voltage goes away when inducer is shut off.
The seven-segment display will alternately display “10” and the
code number for the fault causing the lockout. Lockout will automatically be reset after one hour
Three conditions shall cause a hard lockout:
1. The control senses an unspecied internal fault. Fault code
“93” is set and displayed. This lockout condition cannot be
reset by cycling the heat call.
2. Voltage is detected unexpectedly on the gas valve contacts
(welded relay) and will not clear by cycling the inducer. Fault
code “93” is set and displayed. This lockout condition cannot be reset by cycling the heat call.
3. The furnace control will declare that the blower motor is inoperable (dead) if the main limit control has been open for
more than 150 seconds. Gas heating is terminated. However, the control continues to try to operate heating for up to
four attempts in case the blower motor starts working again.
If a dead blower has been declared four times in one heat
call, the furnace control enters a hard-lockout. Fault code
“61” is set and displayed. This lockout condition CAN be
reset by cycling the heat call.
HARD LOCKOUT
40
FIELD SELECTIONS & ADJUSTMENTS
FIELD SELECTIONS –– DIPSWITCHES
A dipswitch bank; SW1 is provided for some field adjustments.
Heating blower off delay, cooling (and heat-pump) blower off
delay, display (7-Segment) orientation and fault clear are the
adjustments and functions that can be handled using the dipswitches.
Seven-Segment Display Orientation; SW1
As the control will be applied in a multi-position furnace a means
of changing the orientation of the seven segment display is required. This dipswitch is to be labeled SW1. Factory setting of
the SW1 dipswitch is OFF. The factory setting display orientation is with the control placed in a vertical orientation and the low
voltage terminal block T2 is in the bottom position.
Heat Blower-Off Delay; SW2 & SW3
A means of controlling the HEAT speed blower “off” delay time
is provided. The dipswitches are labeled SW2 and SW3. The
following table defines the settings:
FIGURE 30
DIPSWITCH MAP
O
1234
N
SW2 SW3
OFF OFF 90 seconds
(Factory Setting)
ON OFF 120 seconds
OFF ON 160 seconds
ON ON 180 seconds
Cooling & Heat-Pump Heat Blower Off Delay; SW4
A means of controlling the COOL speed blower “off” delay time
is required. The dipswitch is labeled SW4. The following table
defines the settings:
SW4
OFF 30 seconds (Factory Setting)
ON 45 seconds
Field Selections
Switch 1
Seven Segment
Display Orientation
Switch Setting Orientation
ON
OFF
Downflow
Upflow
ST-A1194-110-00
Switch Pair 4 & 5
Heat Blower Off Delay
Switch Setting
A
OFF OFF
ON
B
OFF
C
OFF
ON
D
Airflow Adjustments
90 Seconds (Factory)
ON
ON
120 Seconds
160 Seconds
180 Seconds
Switch 4
Cool Off Delay
Switch SettingAirflow Adjustments
ON
OFF
45 Seconds
30 Seconds (Factory)
Manual Fault Clear
On/Off 3 TImes for Fault Clear
or
Off/On 3 times for Fault Clear
41
TIMING DIAGRAM, FIELD SELECTIONS &
ADJUSTMENTS
FAULT CLEAR
MANUAL FAULT CLEAR; SW4
Faults will automatically be cleared from the fault buffer after
one week. The fault buffer can also be manually cleared if this
is desired. For the first 30 seconds after a change in state of
dipswitch SW4, the furnace control will wait to determine if the
switch becomes on/off/on/off/on/off or off/on/off/on/off/on
FAULT RECALL
Upon power reset, the three most recent faults which are less
than one week old will be flashed in succession from the most
recent to the oldest. This will be done as a diagnostic aid to the
FLAME STATUS L.E.D. (AMBER)
Field Selections
A yellow or amber L.E.D. is provided to indicate flame status.
When normal flame is sensed, the flame L.E.D. is continuously
on. The flame L.E.D. will flash at a rate of one to four flashes
per second if a weak flame is detected. If an unexpected flame
is detected, the L.E.D. will flash rapidly. The L.E.D. is off when
TIMING DIAGRAM
within 30 seconds. When this action is detected within 30 seconds, the fault code memory buffer shall be cleared. Be sure
to return the dipswitch to the original state (on or off) or is in the
desired position after clearing the fault buffer using this method.
field technician. After one week, a fault will be removed from the
fault buffer.
there is no flame detected.
For more diagnostics information, consult the wiring diagram
and diagnostics chart at the end of this book.
On the next page is a timing diagram for normal heat sequence.
This diagram assumes no faults are present during the heat call.
42
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OPEN
OFF
OFF
CLOSED
OPEN
ON
ON
ON
ON
ON
ON
OFF
ON
TIMING DIAGRAM, FIELD SELECTIONS &
TABLE 10
TIMING DIAGRAM
ADJUSTMENTS
Field Selections
ST-A1194-27-X0
ADJUSTING OR CHECKING FURNACE INPUT
The maximum gas supply pressure to the furnace should be
10.5” w.c. for natural gas and 13.0” w.c. for L.P. The minimum
gas supply pressure for purposes of input adjustment to the furnace should be 5” w.c. for natural gas and 11.0” w.c. for L.P.
A calibrated manometer is required for accurate gas pressure
readings.
The manifold pressure should be set at 3.5” w.c. for natural
gas and 10.0” w.c. for L.P. Only small variations in the gas flow
should be made by means of the pressure regulator adjustment.
In no case should the final manifold pressure vary more than
plus or minus 0.3” w.c. from the above- specified pressures. To
adjust the pressure regulator, remove the regulator cap and turn
the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace the regulator
cap securely. Any necessary major changes in the gas flow rate
should be made by changing the size of the burner orifices.
To change orifice spuds, shut off the manual gas valve and remove the gas manifold. On LP gas furnaces, the LP gas supply
pressure must be set between 11” and 13” w.c. by means of the
tank or branch supply regulators. The furnace manifold pressure
should be set at 10” w.c. at the gas control valve. For elevations up to 2,000 feet, rating plate input ratings apply. For high
altitudes (elevations over 2,000 ft.), see conversion kit index for
derating and orifice spud sizes.
Checking furnace input is important to prevent over firing beyond its design-rated input. NEVER SET INPUT ABOVE THAT
SHOWN ON THE RATING PLATE. Use the following table or
formula to determine input rate. Start the furnace and measure
the time required to burn one cubic foot of gas. Prior to checking
the furnace input, make certain that all other gas appliances are
shut off, with the exception of pilot burners. Time the meter with
only the furnace in operation. See Table 11.
43
TIMING DIAGRAM, FIELD SELECTIONS &
ADJUSTMENTS
TABLE 11
METER TIME
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
GAS OR L.P.
INPUT
(BTU/HR)
50,000
75,000
Field Selections
100,000
125,000
150,000
METER SIZE
(FT3/REV)
ONE
TEN
ONE
TEN
ONE
TEN
ONE
TEN
ONE
TEN
Formula: Input BTU/HR =
Formula: Input BTU/HR = Time (in seconds) for 1 cubic ft of Gas
900 1000 1040 1100 2500
MIN SEC MIN SEC MIN SEC MIN SEC MIN SEC
Heating Value of Gas (BTU/ft3) × 3600 x correction factor
HEATING VALUE OF GAS (BTU/FT3)
SETTING INPUT RATE
The furnace is shipped from the factory with #42 orifices.
They are sized for natural gas having a heating value of
1050 BTU/cu. ft. and a specific gravity of .60.
Since heating values vary geo-graphically, the manifold
pressure and/or gas orifice size may need to be changed
to adjust the furnace to its nameplate input. Consult the
local gas utility to obtain the yearly average heating value
44
and orifice size required to fire each individual burner at
25,000 BTU/HR.
NOTE: Refer to the High Altitude Section of this manual
and the National Fuel Gas Code for high altitude rate adjustment above 2,000 ft.
AIRFLOW
The importance of proper air flow over the heat exchanger cannot
be over emphasized.
CAUTION
!
IT IS IMPORTANT THAT EACH DUCT SYSTEM BE SIZED
AND INSTALLED FOR THE SPECIFIC APPLICATION BY
PROPERLY APPLYING THE APPROPRIATE INDUSTRY
ACCEPTED STANDARD. IF LESS THAN MINIMUM STANDARDS ARE APPLIED, THE EQUIPMENT USER COULD
EXPECT TO EXPERIENCE HIGHER UTILITY BILLS,
MAJOR COMPONENT FAILURE, VARYING DEGREES OF
AIR NOISE OR OTHER UNSATISFACTORY ISSUES, OVER
WHICH THE MANUFACTURER HAS NO CONTROL.
One of the most common causes of heat exchanger failure is
overheating due to low air flow. An air flow table is located inside
the blower door and on the following pages.
TEMPERATURE RISE CHECK
To determine if the air flow is correct, make a temperature rise
check.
1. Insert a thermometer in the supply air duct as close to the
furnace as possible yet ot of a direct line from the heat exchanger. See Figure 31.
2. Insert a thermometer in the return air duct as close to the furnace as possible.
3. Operate the furnace.
4. When the thermometer in the supply air duct stops rising (approximately five minutes), subtract the return air temperature
from the supply air temperature. The difference is the temperature rise.
5. Compare the measured temperature rise to the approved
temperature rise range listed on the furnace name plate. See
Figure 32.
If the measured temperature rise is below the nameplate range,
the gas input rate may need to be adjusted or the airflow may be
too high. If the gas input is correct, select the next lowest speed
tap for the heating function. If the measured temperature rise is
above the nameplate range, the gas input rate may need to be
adjusted or the duct system may be too restrictive due to undersized ducts. An undersized return duct is a common cause of an
overly restrictive duct system.
IMPORTANT: The measured temperature rise should be in the
middle of the range.
IMPORTANT: Some high-efficiency filters have a greater than
normal resistance to airflow. This can adversely affect furnace operation. BE SURE TO CHECK AIRFLOW if using any filter other
than factory-provided filter.
FIGURE 31
TEMPERATURE RISE MEASUREMENT
FIGURE 32
TYPICAL FURNACE NAME PLATE
Airow
WARNING
!
THE MEASURED TEMPERATURE RISE MUST BE WITHIN
THE TEMPERATURE RISE RANGE SPECIFIED ON THE RATING PLATE. OPERATING THE UNIT WITH A RISE OUTSIDE
THE STATED RANGE COULD CAUSE DAMAGE TO THE
HEAT EXCHANGER OR INTERMITTENT OPERATION.
THIS COULD CAUSE INJURY OR DEATH AND WILL VOID
THE MANUFACTURER’S WARRANTY FOR THIS PRODUCT.
45
TABLE 12
AIR FLOW PERFORMANCE – (-)801T/(-)801C, (-)80MSX/(-)80MSC, FF(-)TS80(-)/FF(-)CS80(-) - SERIES MODELS
Input (Btu)
Cabinet Width (in)
50k
14”
75k
17”
75k
21”
100k
21”
125k
24”
NOTE: Shaded data is factory heating tap.
AIRFLOW CONTROL
SETTINGS
CIRC FANLOW894775655595533496462423357
HEAT OR HEAT/COOLMED. LO971912875839804758713684644
COOLMEDIUM1117108110511024995973938908878
COOLMED. HIGH132612911275124012041171114411141077
COOLHIGH144014321405138213531322130512721251
CIRC FANLOW10541014964911860797711657606
COOLMED. LO136313181275123011891129109110531012
HEAT OR HEAT/COOLMEDIUM144714171366132912881250121511761137
COOLMED. HIGH155315211478144414071372133212951264
COOLHIGH161615741547150814781438140213751341
CIRC FANLOW11761133109510481000951908861810
COOLMED. LO135313121267123611861149110610791016
HEAT OR HEAT/COOLMEDIUM140013461307127612251181114511031069
COOLMED. HIGH156815371498146814331399135313201287
COOLHIGH178517751736170416731629160815731550
CIRC FANLOW12771211116411031035967861800740
HEAT OR HEAT/COOLMED. LO155614981456140913531308125411981125
COOLMEDIUM164415971554151114631400135813041253
COOLMED. HIGH187918421785172916921674162115791537
COOLHIGH207120251992194819021872184017951750
CIRC FANLOW1398133812781232117711301041975909
COOLMED. LO159315461495145414141342130412511190
HEAT OR HEAT/COOLMEDIUM187818441807175317141675163415781536
COOLMED. HIGH202519671931188618561812174817211668
COOLHIGH216521242082204720121973193418941859
EXTERNAL STATIC PRESSURE in INCHES OF W.C.
SPEED TAP0.10.20.30.40.50.60.70.80.9
CFM AIR DELIVERY
BLOWER SPEED SELECTIONS
Airow
The UT Electronic Controls control boards have four quick connect terminals for connecting the motor speed leads. These are:
1. FAN SPEED* — motor runs on this speed when the thermostat is in the “FAN” position.
2. COOL — connect desired cooling speed.
3. HEAT — connect desired heating speed.
4. HEAT/COOL* — connect desired speed when heating and
cooling speed are the same.
CAUTION
!
DO NOT CONNECT ANY MOTOR SPEEDS TO “HEAT”
OR “COOL” IF YOU USE THE “HEAT/COOL” TERMINAL.
DOING SO WILL DAMAGE THE BLOWER MOTOR. UNUSED MOTOR WIRE TAPS MUST BE CONNECTED TO
PARKING TERMINALS M1 AND M2 OF THE IFC, OR PROPERLY INSULATED.
See Table 10 for instructions for setting the blower “OFF” timings.
GAS FURNACE (DIRECT DRIVE)
INSTRUCTIONS FOR CHANGING
BLOWER SPEED
WARNING
!
DISCONNECT THE ELECTRICAL SUPPLY TO THE FURNACE BEFORE ATTEMPTING TO CHANGE THE BLOWER
SPEED. FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN SEVERE PERSONAL INJURY OR
DEATH.
The blower motor is wired for blower speeds required for normal
operation as shown.
If additional blower speed taps are available (leads connected
to “M1” and “M2” on the electronic control), speeds may be
changed if necessary to fit requirements of the particular installation. Reconnect the unused motor leads to “M1” or “M2.” Check
motor lead color for speed designation.
Heating speeds should not be reduced where it could cause the
furnace air temperature to rise to exceed the maximum outlet air
temperature specified for the unit.
46
SAFETY FEATURES
LIMIT CONTROL/HALC
The high limit cut-off temperature is set at the factory and
cannot be adjusted. The temperature setting prevents the air
temperature leaving the furnace from exceeding the maximum
outlet air temperature, which, if exceeded, will shut the furnace
down.
There are several reasons for a limit switch to open and almost
always involve low airflow through the furnace.
1. A dirty or restricted air filter.
2. A dirty or restricted cooling coil.
3. Undersized or restricted return air system.
4. Undersized or restricted supply air system.
5. A problem affecting the main blower:
A. A wrong speed tap selection.
B. Failing motor bearings.
C. Low voltage to the motor.
D. Dirty blower wheel.
E. Wrong motor rotation.
F. Blower wheel slipping on the
F. motor shaft.
6. Overfiring the furnace with too much gas pressure.
7. Ventilation problems.
8. Failed blower motor.
FLAME ROLL-OUT SAFETY SWITCHES
Furnaces are equipped with safety switches to protect against
flame roll-out conditions in the burner compartment, which,
if tripped, will terminate the heating cycle. In the event of a
flame roll-out condition, the switch will shut the furnace down.
Switches for the furnaces are located on either side of the
burner cover plate. If a switch is tripped, it must be manually
reset. DO NOT jumper or reset this switch. If this switch should
trip, a qualified installer, service agency or the gas supplier
should be called to diagnose and/or correct the source of tripping. If this unit is mounted in a closet, the door must be closed
when making this check.
PRESSURE SWITCH
This furnace is equipped with a normally-open pressure switch
that monitors pressure conditions within the furnace vent system
during the heating cycle.
There are several reasons for the pressure switch not to close.
1. An inoperative induced draft blower.
2. A loose or leaky pressure switch hose.
3. A blockage in the vent.
4. Severe downdrafts canceling the draft from the inducer fan.
5. A leaky gasket at the induced draft blower.
6. Improperly sized or installed vent.
The pressure switch contacts must open before the unit can go
through another heating cycle.
See diagnostic chart in this book for diagnostic recommendations.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY
SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF
A SAFETY SWITCH CAUSES THE FURNACE TO SHUT
DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICATION OF A POTENTIAL SAFETY HAZARD THAT MUST
BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET
SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
AND/OR VERIFICATION OF PROPER SAFE OPERATION
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY
WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN
A NEW SAFETY SWITCH IS INSTALLED, IT MUST BE
TESTED FOR A MINIMUM OF 15 MINUTES WITH THE
FURNACE OPERATING AT MAXIMUM INPUT RATE AND
WITH BOTH BLOWER AND BURNER DOOR INSTALLED.
IF THE FURNACE IS INSTALLED IN A CLOSET, THE
CLOSET DOOR MUST ALSO BE CLOSED FOR THIS
TEST. REPEAT THE TEST AT THE MINIMUM INPUT
RATE IF THE FURNACE IS A MULTI-STAGE FURNACE.
Safety Features
47
MAINTENANCE
MAINTENANCE
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
RESULT IN IMPROPER INSTALLATION, ADJUSTMENT,
SERVICE OR MAINTENANCE, POSSIBLY RESULTING
FILTERS
CAUTION
!
DO NOT OPERATE THE SYSTEM FOR EXTENDED
PERIODS WITHOUT FILTERS. A PORTION OF THE
DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE
SUPPLY REGISTERS. ANY RECIRCULATED DUST
IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE
POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
DISCONNECT MAIN ELECTRICAL POWER TO THE
UNIT BEFORE ATTEMPTING ANY MAINTENANCE.
FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR
DEATH.
PARTICLES WILL BE HEATED AND CHARRED BY
CONTACT WITH THE FURNACE HEAT EXCHANGER.
THIS RESIDUE WILL SOIL CEILINGS, WALLS,
DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES.
LUBRICATION
IMPORTANT: DO NOT attempt to lubricate the bearings
on the blower motor or the induced draft blower motor.
Addition of lubricants can reduce the motor life and void
the warranty.
The blower motor and induced draft blower motor are
permanently lubricated by the manufacturer and do not
require further attention.
It is recommended that the blower motor and induced
draft blower motor be cleaned periodically by a qualified
installer, service agency, or the gas supplier to prevent
Maintenance
the possibility of overheating due to an accumulation of
dust and dirt on the windings or on the motor exterior.
And, as suggested elsewhere in these instructions, the
air filters should be kept clean. Dirty filters can restrict
airflow. The motor depends upon sufficient air flowing
across and through it to keep from overheating.
48
SYSTEM OPERATION INFORMATION
MAINTENANCE
ADVISE THE CUSTOMER
1. Keep the air filters clean. The heating system will operate better, more efficiently and more economically.
2. Arrange the furniture and drapes so that the supply air
registers and the return air grilles are unobstructed.
3. Close doors and windows. This will reduce the heating load on the system.
4. Avoid excessive use of kitchen exhaust fans.
5. Do not permit the heat generated by television, lamps
ANNUAL INSPECTION
• The furnace should operate for many years without
excessive scale build-up in the flue passageways. However, it is recommended that a qualified installer, service
agency, or the gas supplier annually inspect the flue
passageways, the vent system and the main burners for
continued safe operation. Pay particular attention to deterioration from corrosion or other sources.
• IMPORTANT: It is recommended that at the beginning
and at approximately half way through the heating season, a visual inspection be made of the main burner
flames for the desired flame appearance by a qualified
installer, service agency or the gas supplier. If the flames
are distorted and/or there is evidence of back pressure,
check the combustion and ventilation air system for blockage. If there is carbon and scale in the heat exchanger
tubes, the heat exchanger assembly should be replaced.
or radios to influence the thermostat operation.
6. Except for the mounting platform, keep all combustible articles 3 feet from the furnace and vent system.
7. IMPORTANT: Replace all blower doors and com-
partment covers after servicing the furnace. Do not
operate the unit without all panels and doors securely
in place.
8. Explain the advantages of continuous fan operation to
the customer.
• IMPORTANT: It is recommended that at the beginning
of the heating season, the flame sensor be cleaned with
fine steel wool or Scotch Bright Pad by a qualified installer, service agency or the gas supplier.
• IMPORTANT: It is recommended that an annual inspec-
tion and cleaning of all furnace markings be made to assure legibility. Attach a replacement marking, which can
be obtained through the distributor, if any are found to be
illegible or missing.
WARNING
!
HOLES IN THE VENT PIPE OR HEAT EXCHANGER
CAN CAUSE TOXIC FUMES TO ENTER THE HOME,
RESULTING IN CARBON MONOXIDE POISONING
OR DEATH. THE VENT PIPE OR HEAT EXCHANGER
MUST BE REPLACED IF THEY LEAK.
REPLACEMENT PARTS
Homeowners please visit www.rheem.com for product
information.
Replacement parts division visit
http://www.rheemparts.com/Catalog/
DIAGNOSTICS
Refer to Figure 33 for determining cause of unit problems.
WIRING DIAGRAM
Figure 34 is a complete wiring diagram for the furnace. A wiring diagram is also available on the unit.
Maintenance
49
FIGURE 33
INTEGRATED FURNACE CONTROL
TROUBLESHOOTING GUIDE
DIAGNOSTICS FLOWCHART
Diagnostics
DISCONNECT POWER BEFORE SERVICING.
SERVICE MUST BE BY A TRAINED, QUALIFIED
WARNING
LINE VOLTAGE
HAZARDOUS VOLTAGE
Always verify gas valve inlet and outlet gas
NOTE:
pressure .
START
1) Set FAN switch to “AUTO”
2) Set thermostat to call for heat (set temp. differential to greater than 10
PREPURGE
Does the IDM Energize?
SERVICE TECHNICIAN.
CONNECTIONS
IDM Runs for 30 sec. pre-purge ?
IGNITION TRIAL
Spark Ignitor Sparking?
IBM “ON” DELAY
Does Main Burner Light and stay lit?
FLAME (AMBER) LED CODES
OFF = No Flame Present
RAPID BLINK = Unexpected Flame
SLOW BLINK = Marginal Flame Sense
STEADY ON = Normal Flame Sense
F
NO
YES
CHECK BLINK CODES
- Check for open limit or limit circuit.
YES
YES
YES
NO
NO
- Check line voltage at IDM.
- Check wires and connections between IDM and IFC.
- Ensure line voltage on IDM pins of IFC connector .
- Check IDM capacitor (90+ only) .
**
NO
“FAULT DISPLAYED ?”
NO
24V on W to IFC?
YES
Does IDM Run for 60 sec. and then off for Five minutes
FOR DIRECT SPARK IGNITION
- Check ignitor connected .
- Check ignitor wires.
- Check ignitor for fractures or cracking
- Check ignitor placement .
- If problem persists, check IFC*.
Is the gas valve energized?
NO
YES
“ATTEND TO FAULT”
- Check thermostat in “heat” mode,
NO
batter y, wire, and connections.
Check IFC*.
NO
Does IDM run
YES
indefinately .
NO
YES
YES
GO TO
I
KEY TO ABBREVIATIONS
IBM = Indoor Blower Motor
IDM = Induced Draft Motor
IFC = Integrated Furnace Control
PS = Pressure Switch(es)
SE = Spark Electrode
DSI = Direct-Spark Ignition
CODEDESCRIPTION
O
C
H
F
10
11
12
13
14
20
22
26
33
55
57
58
59
61
93
H
- For Twinned units, check that both IFCs are set for “TWIN” and wire s
are connected between “TWIN” terminals .
- Check IFC*.
- For twinned units, ensure transformers are in phase.
(if out of phase, flame LED will be dim) .
- For non-twinned units, ensure “TWIN” is in the single (OFF) position.
- For Twinned units – ensure both IFC‘s have same part number .
- Check PS, PS Hoses, and wires.
- Check for blocked vent, excessive vent length or elbows, or
blocked heat exchanger.
- Check IDM wired correctly .
- Ensure against excessive wind, which can open pressure switch.
- Check for intermittent P.S. operation.
- Check switches and hoses for water or moisture.
- Check gas supply and manifold pressure.
- Ensure L1 and Neutral not swapped on IFC and junction box.
- Check igniter alignment .
- Check orifice or other restrictions to gas flo w.
- Check flame sense rod (clean with scotch brite pad).
- Check flame carry over.
I
” did not
If “
resolve issue.
Standby
Compressor on (cooling or heat pump heat)
Gas heat on
Continuous fan on
1 hour lockout
Failed ignition
Low flame sense
Flame lost
Unexpected flame
Twinning fault
Main limit open / HALC limit open
Line and neutral reversed
Mrlc (man. Reset limit cont.)(aka roll-out open)
Pres. Switch stuck closed, should be open
Pres. Switch stuck open, should be closed
Water Sensed Circuit Open
Water Sensed
Blower fault - blower unable to run
Internal control fault
- Check PS contact s
- Check wires for short.
- Check IFC*.
- Check switches and hoses for
water or moistur e
G
F
TROUBLESHOOTING GUIDE
INTEGRATED FURNACE CONTROL (IFC)
Does IBM start on heat speed 20 seconds
STEADY HEAT
Does main burner remain lit until
Always verify gas valve inlet and outlet gas pressure.
possibilities, including the ground connection, before replacing the IFC.
NOTE:
NOTE: Most failures are not due to the IFC. Double check all othe r
Does thermostat maintain reasonable room
temperature near setpoint ?
END HEAT CALL
Set thermostat to off position (W to C = ØV)
POST-PURGE
Does gas valve shut off immediately?
Does IDM shut off after ten second post-purge?
IBM “OFF” DELAY
Does IBM shut off after a max. of 3 min?
STEADY OFF
Heat-mode troubleshootin g
after burners light ?
YES
heat call ends?
YES
YES
YES
YES
YES
END
NO
- Check line voltage between “HEAT” and “NEUTRAL” on IFC.
- Check wires, connections, and continuity between IFC and IBM.
- Check IBM capacitor .
- Check IBM.
NO
D
Is Limit circuit open
Note: IFC Status LED should be blinking a Fault Code.
CHECK:
BLOCKED DRAIN - (fault “59” should be present)
AIRFLOW
- ensure no restrictions, such as dirty filte r, dampers, closed registers, etc.
LIMITS
- ensure good wire and connections between IFC and all limits. Make sur e
limits are not open when cir culating air temperature is within a specified range.
- ensure rollouts or overtemperature limits do not need to be reset. Make
ROLLOUTS
sure no flame rollout in burner compartment due to blocked flu or heat exchanger.
OVERFIRE
- ensure furnace is not overtemperature (temp rise is above stated range) .
Check gas valve, proper orifice size, gas pressure, etc.
Ensure thermostat is properly placed and not improperly affected by
NO
registers, fans, sunlight, heat through walls, pipes, or wires in walls .
Double check - Is W off at IFC?
NO
NO
(W to C = ØV?)
Ensure TSTAT is not in “FAN” position.
Is disply flashing a fault code
Is “FLAME” LED blinking or steady-on ?
NO
or
YES
NO
GO TO
Check IFC*.
opening and closing?
YES
“FLAME” LED BLINKING
OR STEADY ON
E
If “E” did not
resolve issue
Voltage present at gas valve?
Fault Code Present
REPEAT THIS PROCEDURE UNTIL TROUBLE-FREE OPERATION IS OBTAINED.
- Check wires, continuity , and connection between IFC and gas valve.
- Ensure 24 V between appropriate pins on connector of IFC.
Ensure manual switch on valve is in the “ON” position.
- Did a pressure switch open during ignition trial? If yes, go to F
- Did a limit open during ignition trial? If yes, go to D
I
NOTE: If IFC goes into lockout (“ST ATUS LED will blink code “1”), shut
off main power to unit, wait 30 seconds and then reset power .
NONO
Is t he IFC sensing a good f lame: NOTE:
Flame sense l ight sh ould b e steady-on
when burners are lit. I f flam e LED blinki ng,
or o ff, fl ame sense is low or absent.
- Check IFC*.
YES
SEE FAULT CODES
PROBLEM
PRESENT
NO
NO
CHECK:
- grounding on IFC and unit.
- check for proper polarity between L1 & neutral.
- flame sense rod (clean if necessar y).
- w ire continually between flame sense rod and appropriate pin of
connector on IFC
- flame carries across all burners, and all burners stay lit.
- Check heat anticipator setting. Furnace may need an isolation relay.
- Check installation instructions under section titled “Isolation Relay” for
STILL
details .
- Verify correct furnace sizing.
- Check gas valve.
YES
PS dropping out ?
GO TO
*Most failures are not due to the IFC. Doubl e
check all other possibilities, including th e
ground connection or wire connections, before
replacing the IFC.
**System will attempt to light 4 times. Vo ltage
is present at gas valve for only 7 seconds during each trial for ignition. The entire system will
go into a 1 hour lockout after 4 attempts.
YES
Check IFC*
F
E
ST-A1194-23-03
50
FIGURE 34
WIRE COLOR CODE
G........GREEN
GY......GRAY
O........ORANGE
PR......PURPLE
R........RED
W.......WHITE
Y........YELLOW
WARNING
-CABINETMUSTBE PERMANENTLYGROUNDED
ANDCONFORMTOI.E.C.,N.E.C.,C.E.C.,
NATIONALWIRINGREGULATIONS,ANDLOCAL
CODESASAPPLICABLE.
REPLACEMENTWIRE
-MUSTBETHESAMESIZEANDTYPE
OF INSULATIONASORIGINAL(105C.MIN.)
-FIELDINSTALLED
-FACTORY OPTION
ORIGINAL RELEASE
NO.:
ELECTRICAL WIRING DIAGRAM
MODELED
BY:
CHECKED:APPROVED:
REV:PART NO.:
DATE:
06
P1
PL-2
PL-1
FOR MODELS WITH UT ELECTRONIC CONTROLS 1194-200 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION
P3-1
P3-4
P3-2
P1-4
P1-2
P3-3
P1-3
90+ CT
1 STAGE
P5-1
P1-6
P1-5
MGV
BK......BLACK
BR......BROWN
BL.......BLUE
COMPONENT CODES
Wiring Diagram
INPUT / SIZE
40K / 17” WIDE
60K / 17” WIDE
70K / 17” WIDE
85K / 21” WIDE
115K / 24” WIDE
100K / 21” WIDE
NOTES
WIRING INFORMATION
LOW VOLTAGE
-FIELD INSTALLED
-FACTORY OPTION
-FACTORY STANDARD
LINE VOLTAGE
-FACTORY STANDARD
51
52CM 0917
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.