Rheem Residential 40 Gallon, Residential50 Gallon, Classic Series Use & Care Manual

Page 1
!
!
!
!
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
®
Warning: This water heater is not
CERTI FIED
R
!
suitable for use in manufactured (mobile) homes!
Residential Gas - FVIR Certified
Direct Vent Water Heaters
The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater; and two, for the owner– operator, to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater. This manual also includes a parts list.
It is very important that all persons who are expected to install, operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations. If you do not understand these instructions or any terms within it, seek professional assistance.
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the seller from whom it was purchased. If additional information is required, refer to the section on “If You Need Service.”
Do not destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol as an indication of Important Safety Information!
Use & Care Manual
With Installation Instructions for the Installer
Residential 40 and 50 Gallon
California Proposition 65 Warning: This product contains chemicals known to the State of
California to cause cancer, birth defects or other reproductive harm.
WARNING: If the information in these instructions is not followed exactly,
a fire or explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY!
Do not store or use gasoline or other
flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call
the fire department.
Do not return to your home until authorized
by the gas supplier or fire department.
Improper installation, adjustment, alteration,
service or maintenance can cause property damage, personal injury, or death . Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Printed in USA
AP14380 -1 (07/08)
Page 2
Safety Information
!
!
!
!
Safety Precautions ....... 3–6
LP Gas Models ........... 5
Installation Instructions
Location ................. 7
Venting ............... 9-12
Water Supply Connections . . 13
Gas Supply .............. 14
Pipe Insulation ............16
Heat Traps ...............16
Installation Checklist .......17
Potable/Space Heating .... 18
Operating Instructions
Lighting Instructions ...... 19
Water Temperature .... 20, 21
FOR YOUR RECORDS
Write the model and serial numbers here:
#
#
You can find them on a label on the appliance.
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service under the warranty.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain your water heater properly. A little preventive care on your part can save you time and money over the life of your water heater.
You’ll find many answers to common problems in the Troubleshooting Guide. If you review the chart of Troubleshooting Tips first, you may not need to call for service.
Care and Cleaning
Draining ................ 22
Maintenance ............. 22
Burner Inspection ........ 23
Extended Shut-Down ......23
Troubleshooting Tips
Before You Call
For Service ........... 24, 25
Customer Service
Parts List ................ 26
If You Need
Service ..........Back Cover
2
READ THE SAFETY INFORMATION
Your safety and the safety of others are very important. There are many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. Recognize this symbol as an indication of Important Safety Information! This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER”, “WARNING”, “CAUTION” or “NOTICE”.
These words mean:
DANGER
that will result in death or serious injury.
WARNING
could result in death or serious injury
and/or damage to property.
CAUTION
may result in minor or moderate injury.
Notice:
specified procedure or maintain a specific condition.
An imminently hazardous situation
A potentially hazardous situation that
A potentially hazardous situation that
Attention is called to observe a
Page 3
IMPORTANT SAFETY INFORMATION.
!
!
FLAMMABLES
Flammab le V a pors
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death.
Do not store or use gasoline or other flammable vapors and liquids
in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death.
W ARNING
READ ALL INSTRUCTIONS BEFORE USING.
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate this water heater. It may save you time and cost. Pay particular attention to the Safety Instructions. Failure to follow these warnings could result in serious bodily injury or death. Should you have problems understanding the instructions in this manual, or have any questions, STOP, and get help from a qualified service technician, or the local gas utility.
DANGER!
INSTALL THE VENTING SYSTEM AND PROPERLY VENT THE WATER HEATER…
Failure to install the venting system and properly vent the water heater to the outdoors as outlined in the Venting Section of the Installation Instructions in this manual can result in unsafe operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, never operate this water heater unless it is properly vented and has an adequate air supply for proper operation. Be sure to inspect the vent system for proper installation at initial start-up; and at least annually thereafter. Refer to the Care and Cleaning section of this manual for more information regarding vent system inspection.
WARNING!
Gasoline, as well as other flammable materials and liquids (which include, but not limited to adhesives, solvents, paint thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle, use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater and its vent pipe terminal or any other appliance. Be sure to read and follow warning label pictured below and other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in property damage, bodily injury or death.
3
Page 4
!
& #0)'4
*16
9CVGTVGORGTCVWTGQXGT° (ECP ECWUGUGXGTGDWTPUKPUVCPVN[QT FGCVJHTQOUECNFU
%JKNFTGPFKUCDNGFCPFGNFGTN[CTG CVJKIJGUVTKUMQHDGKPIUECNFGF
5GGKPUVTWEVKQPOCPWCNDGHQTG UGVVKPIVGORGTCVWTGCVYCVGT JGCVGT
(GGNYCVGTDGHQTGDCVJKPIQT UJQYGTKPI
6GORGTCVWTGNKOKVKPIXCNXGUCTG CXCKNCDNGUGGOCPWCN
$740
!
IMPORTANT SAFETY INFORMATION.
!
READ ALL INSTRUCTIONS BEFORE USING.
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water temperature setting of a water heater’s gas control. Water temperatures above 125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined on the label pictured below. This label is also located on the water heater.
Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 11/2 to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 11/2 seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
Notice: Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines. Contact a licensed plumber or the local plumbing authority for further information.
4
The chart shown above may be used as a guide in determining the proper water temperature for your home.
DANGER: Households with small children, disabled, or elderly persons may require a 120°F control (thermostat) setting to prevent contact with “HOT” water.
(49°C) or lower gas
Maximum water temperatures occur just after the burner has shut off. To find water temperature being delivered, turn on a hot water faucet and place a thermometer in the water stream and read the thermometer. (See page 20 and 21 for more details.)
The temperature of the water in the heater can be regulated by setting the temperature dial on the front of the gas control (thermostat). To comply with safety regulations the gas control (thermostat) was
110°F
100°F (38°C)
90°F (32°C)
80°F (27°C)
Temperatures are approximate
DANGER: Hotter water increases the potential for Hot Water SCALDS.
(43°C)
(54°C)
set at its lowest setting
120°F
before the water heater
(49°C)
was shipped from the
130°F
factory.
The illustration at the left
140°F
(60°C)
details the approximate
150°F
water temperature
(66°C)
for each mark on
160°F
the Gas Control
(71°C)
(Thermostat) Temperature Dial.
Page 5
!
DANGER!
LIQUEFIED PETROLEUM (LP PROPANE OR BUTANE) AND NATURAL GAS MODELS
LP and Natural gas have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or camouflage a gas leak.
Water heaters utilizing LP gas are
different from natural gas models. A natural gas water heater will not function safely on LP gas and vice versa.
No attempt should ever be made to
convert the water heater from natural gas to LP gas. To avoid possible equipment damage, personal injury or fire, do not connect the water heater to a fuel type not in accordance with the unit data plate. LP for LP units. Natural gas for natural gas units. These units are not certified for any other fuel type.
LP appliances should not be installed
below grade (for example, in a basement) if such installation is prohibited by federal, state and/or local laws, rules, regulations or customs.
LP gas must be used with great caution.
It is heavier than air and will collect first in lower areas making it hard to detect at nose level.
DANGER: If a gas leak is present or
suspected:
Do not attempt to find the cause
yourself.
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building.
Leave the house immediately and make
sure your family and pets leave also.
Leave the doors open for ventilation
and contact the gas supplier, a qualified service agency or the fire department.
Stay away from the house (or building)
until the service call has been made, the leak is corrected and a qualified agency has determined the area to be safe.
Before attempting to light the water
heater, make sure to look and smell for gas leaks. Use a soapy solution to check all gas fittings and connections. Bubbling at a connection indicates a leak that must be corrected. When smelling to detect a gas leak, be sure to sniff near the floor also.
Gas detectors are recommended in LP
& natural gas applications and their installation should be in accordance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
It is recommended that more than one
method, such as soapy solution, gas detectors, etc., be used to detect leaks in gas applications.
5
Page 6
IMPORTANT SAFETY INFORMATION.
!
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or strapped to resist falling or horizontal displacement due to earthquake motions. For residential water heaters up to 52-gallon capacity, a brochure with generic earthquake bracing instructions can be obtained from: Office of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95814 or you may call 916-445-8100 or ask a water heater dealer.
However, applicable local codes shall govern installation. For residential water heaters of a capacity greater than 52 gallons, consult the local building jurisdiction for acceptable bracing procedures.
SAFETY PRECAUTIONS
Have the installer show you the location of the gas shut-off valve and how to shut it off if necessary. Turn off the manual shut-off valve if the water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to shut off.
Read this manual entirely before installing
or operating the water heater.
Use this appliance only for its intended
purpose as described in this Use and Care Manual.
Be sure your appliance is properly installed in accordance with local codes and the provided installation instructions.
Do not attempt to repair or replace any part
of your water heater unless it is specifically recommended in this manual. All other servicing should be referred to a qualified technician.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
6
Page 7
Installing the water heater.
!
This water heater must be installed in accordance with these instructions, local codes, utility company requirements, and/or in the absence of local codes, use the latest edition of the American National Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400 N. Capitol Street NW, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as booklet NFPA 54. For Canada Installations use CAN/CSA B149 - Natural Gas and Propane Installation Code. A copy can be purchased from the Canadian Standards Association, 178 Rexdale Boulevard,Toronto, Ontario, CANADA, M9W 1R3.
Location
Max. 2
(5 cm)
Diameter of water heater plus 2” min.
(5 cm)
The auxiliary catch pan installation MUST conform to local codes.
WARNING: Combustible construction refers to adjacent walls and ceilings and should not be confused with combustible or flammable products and materials. Combustible and/or flammable products and materials should never be stored in the vicinity of this or any gas appliance.
The water heater should not be located in an area where leakage from the tank or connections will result in damage to the area adjacent to the heater or to lower floors of the structure.
When such areas cannot be avoided it is recommended that a suitable catch pan, adequately drained, must be installed under the water heater.
Catch pan kits are available from the store where the water heater was purchased, or any water heater distributor.
Make certain that the floor underneath the water heater is strong enough to support the weight of the water heater once it is filled with water.
A gas fired water heater or any other appliance should not be installed in a space where liquids which give off flammable vapors are to be used or stored. Such liquids include gasoline, LP gas (butane or propane), paint or adhesives and their thinners, solvents or removers.
Because of natural air movement in a room or other enclosed space, flammable vapors can be carried some distance from where liquids which give off flammable vapors are to be used or stored. The open flame of the water heater’s pilot or main burner can ignite these vapors.
Rheem Water Heating FVIR certified gas water heaters can be installed on a residential garage floor without the use of an 18-inch stand in accordance with the National Fuel Gas Code, NFPA 54, ANSI Z223.1 2006, paragraph 9.1.10 Installation in Residential Garages, unless otherwise directed by State
and Local code requirements. The water heater must be located so it is not subject to physical damage, for example, by moving vehicles, area flooding, etc
This water heater is of the direct vent
design. It therefore must be located next to the outside wall, within the range of the telescopic adjustments. (See page 9 for Locating Clearance Hole for Vent)
Long hot water lines should be insulated
to conserve water and energy.
The water heater and water lines should
be protected from exposure to freezing temperatures.
Do not install the water heater in
unprotected outdoor areas.
Minimum clearance from combustible
construction is 0” sides, 0” rear; and 3” (7.6 cm) from the front of the control. If the clearances stated on the Instruction/ Warning Label, located on the front of the heater differ, install the water heater according to the clearances stated on the label.
The water heater may be installed on
combustible floors, but not directly on carpeting. If the water heater must be installed on carpeting, place a metal or wood panel beneath the water heater, extending beyond its full width and depth at least 3” (7.6 cm) in all directions.
If the water heater is installed in an
alcove or closet, the entire floor must be covered by a wood or metal panel. A minimum of 24” (61 cm) clearance from the front and top should be available for adequate inspection and servicing.
7
Page 8
Installing the water heater.
Inspect Shipment
Inspect the water heater and the venting provided with the water heater for possible damage. Check the markings on the rating plate of the water heater to be certain the type of gas supplied corresponds to the water heater requirements.
Combustion and Ventilation Air
NOTICE: The water heater should not be installed near an air supply containing halogenated hydrocarbons.
Proper operation of the water heater requires air for combustion and ventilation. Provisions for combustion and ventilation air must comply with referenced codes and standards.
NOTICE: If the water heater is installed in an unconfined space within a building of conventional frame, masonry or metal construction, infiltration air is normally adequate for proper combustion and ventilation. If the water heater is installed in a confined space, provisions for ventilation air must be made.
Corrosive Atmospheres
The air in beauty shops, dry cleaning establishments, photo processing labs, and storage areas for liquid and powdered bleaches or swimming pool chemicals often contain such halogenated hydrocarbons.
An air supply containing halogenated hydrocarbons may be safe to breathe, but when it passes through a gas flame corrosive elements are released that will shorten the life of any gas burning appliance.
All air for combustion and all products of combustion are routed through the ducting provided, directly from and to the outside of the building.
NOTICE: If the duct openings which supply ventilation air are to be covered with a protective screen or grill, the net free area (openings in the material) of the covering material must be used in determining the size of the openings. Protective screening for the openings MUST NOT be smaller than 1/4”mesh to prevent clogging by lint or other debris.
Propellants from common spray cans or gas leaks from A/C and refrigeration equipment are highly corrosive after passing through a flame.
The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere.
8
Page 9
HOT
The water heater must be installed with the factory supplied venting system. The old venting system (vent pipe, air intake pipe, vent cap, elbows etc.) must be replaced with the vent system supplied with the new water heater.
DANGER: Failure to install the venting system and properly vent the water heater to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing bodily injury, explosion, fire or death. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting section of this manual.
18”Min
Inside
Corner
(46 cm)
18”Min.
(46 cm)
12" Min. (30 cm) above grade (Higher in areas of heavy snowfall.)
Venting
CAUTION: If there are any damaged parts, DO NOT install the water heater. Report any damage to your distributor or to the carrier.
9" Min. (23 cm)
36” Min.
Within 10 feet
(305 cm)
Any forced air inlet
into the building
(91 cm)
NOTICE: The four fasteners that are required to secure the vent cap to the external wall are not provided. These should be screw type (not nails) chosen for the type of construction and obtained locally
See the back page of this manual for additional requirements for the Commonwealth of Massachusetts.
Vent Termination Clearances
Vent Terminal must be located at least min. above grade level and above normal snow levels. Higher in areas of heavy snowfall.
Vent Terminal must be located at least 9” (23 cm) from windows, doors, or any other opening through which flue gases could enter the building.
Vent Terminal must be located at least 36” (91 cm) above any Forced Air Inlet into the building within 10’ (3 m) of the Vent Terminal. air inlet such as for a dryer or furnace area is considered to be a forced air inlet.
Vent Terminal must be located at least 18” (46 cm) from any overhang or building corner or other irregularity.
DO NOT locate the Vent Terminal under any deck or
patio structure.
12” (30.5 cm)
Any fresh or make-up
Approximately 6 1/4" Diameter (15.8 cm)
"X"
Floor
Locating Clearance Hole for Vent
Cut a clearance hole, approximately 6 1/4” (15.8 cm)
in diameter, through the exterior wall for the 6” (15.2 cm) diameter air tube.
Capacity "X"
40 Gallon 68-1/4" (173.3 cm)
50 Gallon 68" (172.7 cm)
9
Page 10
Installing the Water Heater:
Top Plenum
Top Plenum
Top Pan
Elbow with brackets bent at 90°
* Seal with silicone sealant.
3" (7.6 cm) 90° Elbow (Steel)
Moving water heater to its final location
Move the water heater to its final installed location.
Make certain clearances from combustible materials are observed.
Installing 3” (7.6 cm) Diameter Steel Elbow
Bend the brackets on the elbow as shown on left.
Place the 3” (7.6 cm) steel elbow on the water heater
flue pipe and press it firmly downward until fully seated and pointed in the desired direction. After installation of elbow, apply silicone sealant around the outside of the pipe where the 3" (7.6 cm) elbow
comes in contact with the ue pipe
seal can cause product performance and nuisance pilot outages.
Secure the 3" (7.6 cm) steel elbow to the top pan by
inserting two #8 x 3/8" long screws supplied through the bent brackets.
. An improper
3" (7.6 cm) (90° Elbow (Steel)
90° Elbow (Aluminum)
Install end of elbow with
label to top plenum.
Sheet Metal Screws
6" (15.2 cm)
Top Plenum.
Finishing Collar
Installing 6” (15.2 cm) Diameter Aluminum Elbow
Install the 6” (15.2 cm) aluminum elbow over the
3” (7.6 cm) steel elbow. Be certain both are pointed in the desired direction with the 3" (7.6 cm) centered inside the 6” (15.2 cm) inch elbow.
Leveling and attaching 6” (15.2 cm) Diameter Aluminum Elbow
As an aid to leveling the 6” (15.2 cm) elbow,
temporarily place the 6” (15.2 cm) sliding tube onto the elbow.
When leveled, drill a 1/8”
elbow into the collar at the front and back. Secure with the two #8 sheet metal screws supplied.
Place the finishing collar on the 6” (15.2 cm) elbow, as it
will be positioned later.
inch diameter hole through the
10
Page 11
 
 
 
F1
F2
3" Tube
"X"
2 1/2" Minimum extension
beyond wall.
F4
Gallons "X" Inches (cm)
40 9 1/8" (23.17 cm) -
19 1/8" (48.57 cm)
50 8 1/8" (20.63 cm)
- 18 1/8" (46 cm)
Placing 3" (7.6 cm) Diameter Main Vent Tube through Exterior Wall
Inspect the vent tube upon opening the kit to assure
three silicone sealing bands are included and positioned at the sealing points.
Install the 3" main vent tube onto the end of the 3"
inner elbow & seal with silicone band by folding the band back over the seam of both tubes.
Extend the 3” (7.6 cm) tube assembly to its required
length. Be sure a minimum of 2 1/2" extends beyond the outer wall. (F1)
Move high temperature silicone band to connecting
joints as shown. (F2)
"X" Optional kit that provides additional adjustment up to 48" (121.9 cm) can be purchased seperately.
Assembling the 6” (15.2 cm)
Vent Terminal Base (Outside)
Sheet Metal Screws & Silicone Sealant
G1
G2
G3
Diameter Vent Tube Assembly w/ vent terminal base.
Inspect the vent tube upon opening the kit to assure
two silicone sealing bands are included and positioned at the sealing points.
Attach the outer 6” (15.2 cm) main tube to the vent
terminal base as shown on left.. (G1)
Drill a 1/8”
collar of the base. (G2)
Secure with a #8 sheet metal screw, supplied. Repeat
with a second hole and screw approximately 180° from the first. (G3)
inch diameter hole through the tube and the
Vent Terminal Base (Outside)
H1
Outside
Wall
Main Tube
From the outside of the building, insert the
6” (15.2 cm) vent tube/base assembly through the hole in the exterior wall and onto the 6” (15.2 cm) elbow. Slide as needed into place. (H1).
An improper seal can cause product performance and nuisance pilot outages.
11
Attaching the 6” (15.2 cm) Diameter
Page 12
Installing the water heater.
 
*
 
 
 
���
���
*
*
���
*
V a cuum Relief V a lve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.
✚✚✚
Screw Anchors
Seal with Silicone Sealant
*
Finishing Collar (Inside)
6" Inner Sliding Tube
6
” (15.2 cm)
90° Elbow
(Aluminum)
Top of
Plenum
6" Tube
(15.2 cm)
3" Tube
(7.6 cm)
Securing Vent Cap / Base Assembly to
Wall
J3
J1
J2
Vent Terminal Base
the Exterior Wall
Next place the 3” (7.6 cm) main tube fully onto the collar
of the vent cap. Then seat the cap against the base. (J1)
Secure the vent cap/base assembly to the exterior wall
with four screw anchors appropriate for the type of wall construction. The 6” (15.2 cm) tube should be essentially level. However, a small amount of upward pitch will not affect operation. (J2)
Caulk the junctions of the vent terminal base and the
exterior wall with silicone sealant (Not Supplied). (J3)
An improper seal can cause product performance and nuisance pilot outages.
Final Assembly and Sealing of the Vent
Vent Terminal Base (Outside)
K
L4
L5
L1
L2
L2
L3
L3
✚ ✚
Seal with Silicone Band
Seal with Silicone Sealant
Vent Terminal Cap (Outside)
Outside Wall
Sheet Metal Screws
System
Position and fasten the finishing collar, previously
installed on the 6” (15.2 cm) elbow, against the wall to close the opening around the tube. (K)
Make certain the 6” (15.2 cm) inner sliding air tube has
been fully engaged onto the 6" (15.2 cm) elbow.(L1)
Drill two 1/8” inch holes (180° apart) in the junction of
the two joints in the 6" (15.2 cm) tube. (L2)
Fasten with four #8 sheet metal screws supplied. (L3)
Using a flat head screw driver inserted through the holes
in the vent cap, roll the silicone band over the seam to seal. (L4)
Seal all the 6” (15.2 cm) tube joints with the silicone
bands provided (L5). Seal the elbow joint to the plenum using silicone sealant. Again, an improper seal can cause
product performance and nuisance pilot outages. (M)
Typical Installation
Air Tube
Heat Trap
6" Min (15.2 cm).
Hot Water
Outlet to
Fixtures
NOTICE: The National Fuel Gas Code (NFGC) mandates a manual gas shut-off valve: See (NFGC) for complete instructions. Local codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions.
12
Manual Gas Shut-Off
To Gas Supply
Ground Joint Union
Sediment Trap
Gas Control (Thermostat)
Jacket Door
Auxiliary Catch Pan
Catch Pan Pipe to suitable drain.
Temperature and Pressure Relief Valve
Cap
Union
Vent Terminal Cap (Outside)
Anode Rod (Located under top pan) Not accessible. Refer to Protection Plus Kit for additional protection.
Union
Heat Trap 6" Min. (15.2 cm)
To Cold Water Supply
Shut-Off Valve
Expansion Tank (if required)
Relief Valve Discharge Line to Suitable Open Drain
Drain Valve
Air Gap - 6" (15.2 cm)
Page 13
NOTICE: Do not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the water connections on heater. Any heat applied to the water supply fittings will permanently damage the dip tube, nipples and/or heat traps.
Thermal Expansion
Determine if a check valve exists in the inlet water line. Check with your local water utility company. It may have been installed in the cold water line as a separate back flow preventer, or
it may be part of a pressure reducing valve, water meter or water softener. A check valve located in the cold water inlet line can cause what is referred to as a “closed water system”. A cold water inlet line with no check valve or back flow prevention device is referred to as an “open” water system.
As water is heated, it expands in volume and creates an increase in the pressure within the water system. This action is referred to as “thermal expansion”. In an “open” water system, expanding water which exceeds the capacity of the water heater flows back into the city main where the pressure is easily dissipated.
A “closed water system”, however, prevents the expanding water from flowing back into the main supply line, and the result of “thermal expansion” can create a rapid and dangerous pressure increase in the water heater and system piping. This rapid pressure increase can quickly reach the safety setting of the relief valve, causing it to operate during each heating cycle. Thermal expansion, and the resulting rapid, and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve, and possibly the heater itself. Replacing the relief valve will not correct the problem!
The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve (see illustration on page 12). The expansion tank is designed with an air cushion built in that compresses as the system pressure increases, thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve. Other methods of controlling thermal expansion are also available. Contact your installing contractor, water supplier or plumbing inspector for additional information regarding this subject.
Water Supply Connections
Refer to the illustration on page 12 for suggested typical installation. The installation of unions or flexible copper connectors is recommended on the hot and cold water connections so that the water heater may be easily disconnected for servicing if necessary. The HOT and COLD water connections are clearly marked and are 3/4” NPT on all models. Install a shut-off valve in the cold water line near the water heater.
A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must remain in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank. Local codes shall govern the installation of relief valves.
Relief Valve
The pressure rating of the relief valve must not exceed 150 PSI (1034 kPa), the maximum working pressure of the water heater as marked on the rating plate.
The Btuh rating of the relief valve must equal or exceed the Btuh input of the water heater as marked on its rating plate.
Position the outlet of the relief valve above a suitable open drain to eliminate potential water damage. Piping used should be of a type approved for hot water distribution.
The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow complete drainage (by gravity) of the relief valve and discharge line.
The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction, or reducer coupling should be installed in the discharge line.
13
Page 14
Installing the water heater.
WARNING: The tank must be full of water before heater is turned on. The water heater warranty does not cover damage or failure resulting from operation with an empty or partially empty tank.
NOTICE: Additional information on this subject may be found at www.rheem. com, under Rheem Water Heating, "Support", scroll down to the Technical Service Section and to Bulletins 1400 Series Section and choose Bulletin #1402.
WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type shown on the rating plate. Such conversion could result in hazardous operating conditions.
To Fill the Water Heater
Make certain that the drain valve is closed, then open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to
Condensation
Condensation can form on the tank when it is first filled with water. Condensation might also occur with a heavy water draw and very cold inlet water temperatures.
Drops of water falling on the burner can produce a sizzling or pinging sound. The water may also be seen beneath the water heater.
allow the air to vent from the water heater and piping.
A steady flow of water from the hot water faucet(s) indicates a full water heater.
This condition is not unusual, and will disappear after the water becomes heated. If, however, the condensation continues, examine the piping and fittings for possible leaks.
Gas Supply
The branch gas supply line to the water heater should be clean 1/2” black steel pipe or other approved gas piping material.
A ground joint union or ANSI design certified semi-rigid or flexible gas appliance connector should be installed in the gas line close to the water heater. A manual gas shut-off valve should be at least 5 ft. (1.5 m) above the floor and readily accessible.
Use compound sparingly on male threads only. The compound used on threaded joints of the gas piping must be of the type resistant to the action of LP gas.
Where a sediment trap is not incorporated as part of the appliance, a sediment trap shall be installed downstream of the equipment shutoff valve as close to the inlet of the appliance as practical at the time of the appliance installation. The sediment trap shall be either a tee fitting
with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap.
Do not use excessive force (over 31.5 ft lbs.) (42.7 Nm) in tightening the pipe joint at the gas control (thermostat) inlet, particularly if teflon pipe compound is used, as the valve body may be damaged.
The inlet gas pressure to the water heater must not exceed 10.5” w.c. (2.65 kPa) for natural gas or 14" w.c. (3.5 kPa) for LP gas. For purposes of input adjustment, the minimum inlet gas pressure (with main burner on) is shown on the water heater rating plate. If high or low gas pressures are present, contact your gas supplier for correction.
If flexible connectors are used, the
maximum length shall not exceed 36” (91 cm).
If lever type gas shut-offs are used,
they shall be T-Handle type.
WARNING: Never use an open flame to test for gas leaks, as property damage, personal injury, or death could result.
14
Leak Testing
The water heater and its gas connections must be leak tested at normal operating pressures before it is placed in operation.
Turn on the manual gas shut-off
valve near the water heater.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must be corrected.
The factory connections to the gas control (thermostat) should also be leak tested after the water heater is placed in operation.
Page 15
WARNING: If local codes require external application of insulation blanket kits the manufacturer’s instructions included with the kit must be carefully followed.
Pressure Testing the Gas Supply System
The water heater and its manual gas shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1/2 psi (14” w.c.).
The water heater must be isolated from the gas piping system by closing the manual gas shut-off valve during any pressure testing of the gas supply piping at pressures equal to or less than 1/2 psi (14” w.c.).
High Altitude
Ratings of gas appliances are based on sea level operation. This water heater is suitable and certified for use at high altitudes. Refer to the altitude label on the water heater for maximum allowable installation altitude Please contact your local distributor or place of purchase for a high altitude model.
WARNING: Failure to install a water heater suitable for the altitude at the location it is intended to serve, can result in improper operation of the appliance resulting in property damage and/or, producing carbon monoxide gas, which could result in personal injury, or death.
Insulation Blankets
Insulation blankets, available to the general public, for external use on gas water heaters are not necessary. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. This water heater meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary.
The manufacturer’s warranty does not cover any damage or defect caused by installation, attachment or use of any type of energy saving or other unapproved devices (other than those authorized by the manufacturer) into, onto or in conjunction with the water heater. The use of unauthorized energy saving devices may shorten the life of the water heater and may endanger life and property.
CAUTION: If local codes require the
application of an external insulation blanket to this water heater, pay careful attention to the following so as not to restrict the proper function and operation of the water heater:
Do not cover the operating or warning
labels attached to the water heater or attempt to relocate them on the exterior of insulation blanket.
Do not apply insulation to the top of the
water heater. as this will interfere with the safe operation of the water heater and venting system.
Do not cover the burner access door,
jacket door, gas control (thermostat)/gas valve or pressure and temperature relief valve.
The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices.
15
Page 16
Installing the water heater.
Hot and Cold Pipe Insulation Installation
Typical vertical piping arrangement
For increased energy efficiency, some water heaters have been supplied with two 24” (60.9 cm) sections of pipe insulation. Please install the insulation,
Typical horizontal piping arrangement
according to the illustrations above, that best meets your requirements.
Heat Trap
For increased energy efficiency, some water heaters have been supplied with factory installed 3/4” NPT heat traps in the hot outlet line and cold water inlet line.
NOTICE: Do not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the water connections on heater. Any heat applied to the water supply fittings will permanently damage the dip tube, nipples, and/or heat traps.
During Installation of this water heater...........
DO
DO check inlet gas pressure to ensure
that it is within the range specified on the rating plate.
DO provide adequate air for combustion and ventilation as discussed in the Use and Care Manual and the National Fuel Gas Code.
DO maintain proper clearances to combustibles as specified on the instruction/ warning label.
DO ensure that the venting system complies with the guidelines found in the Use and Care Manual and National Fuel Gas Code.
DO contact a qualified service technician if the pilot or main burner will not stay lit.
DON’T
DON’T block or restrict the vent
terminal.
DON’T remove the Burner Access Door unless absolutely necessary. This should only be done by a qualified service technician. A new burner access door gasket must be installed on any burner access door that has been removed.
DON’T install this water heater where standing water may occur. The base of the water heater is meant to be mounted on a dry surface.
❑ DON’T operate the water heater if the
sight glass or burner access door grommet is damaged or broken.
16
Page 17
Installation Checklist
A. Water Heater Location
Close to outside wall.
Indoors and protected from freezing
temperatures.
Proper clearance from combustible surfaces observed and water heater not installed on carpeted floor.
Sufficient fresh air supply for proper operation of water heater.
Air supply free of corrosive elements and flammable vapors.
B. Water Supply
Water heater completely filled with water.
Air purged from water heater and piping.
Water connections tight and free of leaks.
Provisions made to protect area from water
damage.
Sufficient room to service heater.
Combustible materials, such as clothing, cleaning materials, rags, etc. clear of the base of the heater.
C. Gas Supply
Gas line equipped with shut-off valve, union and sediment trap.
Approved pipe joint compound used.
D. Relief Valve
Temperature and Pressure Relief Valve properly installed and discharge line run to open drain.
Discharge line protected from freezing.
E. Venting
Flue baffle properly hung in top of heater’s flue.
Air tube and vent tube properly installed.
Soap and water solution used to check all connections and fittings for possible gas leak.
Gas Company inspected installation (if required).
Vent terminal, air tube sealed with silicone bands and sealants.
Air tube securely fastened with screws.
17
Page 18
Supplemental instructions for gas water heaters installed
V a cuum Relief Va lve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.
in potable/space heating applications.
Local codes or plumbing authority requirements may vary from the instructions or diagrams provided in this manual and take precedent over these instructions.
Hot water supply to house
Hot water supply to heating unit
From HOT
outlet on
water heater
Tee fitting for vertical hot water supply lines.
Hot water supply to house
From HOT
outlet on
water heater
Hot water supply to heating unit
Tee fitting for horizontal hot
Combination Potable and Space Heating Application
Tee fitting must be installed as shown. This ensures that any air in the water lines will be purged through the domestic water faucets and showers.
DANGER: When this system requires water for space heating at elevated temperatures [above 125°F (52°C.)], a mixing or tempering valve must be installed in the hot water supply line to the house in order to reduce the scald hazard potential.
DANGER: Any piping or components used in the installation of this water heater in a combination potable and space heating application must be suitable for use with drinking water.
DANGER: If this water heater is installed in an application intended to supply domestic hot water needs and hot water for space heating purposes, do not connect the heater to an existing heating unit or components of a heating system that have previously been used with a non drinking water system. Toxic chemicals such as those used for boiler treatment may be present and will contaminate the drinking water supply causing possible health risks. Never introduce toxic chemicals, such as those used for boiler treatment, into this system.
Notice: 50' - 0" maximum distance from water heater to fan coil (developed length) is required for Massachusetts State.
water supply lines.
Typical Piping Diagram for Combination Potable/Space Heating Installation
Nominal 3/4" size mixing or tempering valve (refer to warning above). Follow mixing or tempering valve manufacturer’s instructions for installation of the valve.
Spring loaded check valve in heating
unit hot water supply line and cold water
return line (not supplied with water
NOTE: This check valve is incorporated
in some heating units. Refer to the installation instructions supplied with specific heating unit to determine if it
Isolation valve in hot water supply
line to heating unit (not supplied with
Temperature and Pressure Relief
Valve, tie to location approved by
heater)
is required.
water heater)
local code
Minimum of 2'-0" developed length of 3/4" type "L" copper from the water heater connection.
Air vent
3/4" Shut-Off Valve (Typ.)
3/4" Tempered domestic hot water supply to house.
Heat Trap 6” Min.
2 Gallon Thermal Expansion Tank (if required-not supplied with water heater)
Pressure Gauge
3/4" Check Valve with 1/8" Hole
3/4" Shut-Off Valve (Typ.)
140°
120° to 130°
3/4" Shut-Off Valve (Typ.)
3/4" cold water supply
Piping loop between water heater and fan coil shall be flow guard gold CPVC or equal
Hot water to space heater
Hot water coil
All bronze pump.
Check valve internal in pump.
Air bleed valve.
Water Sample Tap.
Gas line to water heater
Temperature and pressure relief
Water Heater drain pan installed in accordance with the Local and
Water Heater to be in accordance with the Local and State Energy Code
All water piping shall be insulated in accordance with Local and State Energy Code.
valve discharge line
State Code
18
18
Gas Fired
Water Heater
Isolation valve in cold water return line from heating unit (not supplied with water heater)
Gas Direct Vent discharge must comply with Local and State Code
Combustion Air Inlet Openings
6” Air Gap
3/4" HWS & HWR to Heating Coil.
Drain valve (not supplied with water heater)
To HVAC Unit.
T
Air Handler
Electronically controlled pump timer. Activates every 6 hours for 60 seconds. Wire to bronze pump.
FAN ON OFF HEAT COOL
Page 19
Lighting the water heater.
instructions exactly, a re or explosion may result causing property damage, personal injury or loss of life.
If you do not follow these instructions and the Use & Care Manual
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in property damage, personal injury, or death . Should you have any problems reading or following the instructions in this manual, STOP, and get help from a qualified person.
19
Page 20
Operating the water heater.
!
CAUTION: Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE!! To dissipate such gas and to reduce risk of injury, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the water begins to flow. Do not smoke or use an open flame near the faucet at the time it is open.
Safety Precautions
Do turn off manual gas shut-off valve if water heater
has been subjected to over heating, fire, flood, physical damage or if the gas supply fails to shut off.
Do Not turn on water heater unless it is completely
filled with water.
Do Not turn on water heater if cold water supply
shut-off valve is closed.
Do Not allow combustible materials such as
newspaper, rags or mops to accumulate near water heater.
Do Not store or use gasoline or other flammable
vapors and liquids, such as adhesives or paint thinner, in vicinity of this or any other appliance. If such flammables must be used, open doors and windows for ventilation, and all gas burning appliances in the vicinity should be shut off including their pilot burners, to avoid vapors igniting.
NOTICE: Flammable vapors can be drawn by air currents from surrounding areas to the water heater.
If there is any difficulty in understanding or following
the Operating Instructions or the Care and Cleaning section, it is recommended that a qualified person or serviceman perform the work.
DANGER: Hotter water
increases the Potential for Hot Water SCALDS
. Households with small children, disabled, or elderly persons may require a 120°F (49°C) or lower gas control (thermostat) setting to prevent contact with HOT water.
Water Temperature Setting
The temperature of the water in the water heater can be regulated by setting the temperature dial on the front of the gas control (thermostat).
Safety and energy conservation are factors to be considered when selecting the water temperature setting of the water heater’s gas control (thermostat(s)). The lower the temperature setting, the greater the savings in energy and operating costs.
To comply with safety regulations, the gas control (thermostat) was set at its lowest setting before the water heater was shipped from the factory. The recommended starting point temperature is 120°F (49°C).
Water temperatures above 125°F (52° C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined in this manual and on the label located on the water heater near the gas control (thermostat).
Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines. Contact a licensed plumber or the local plumbing authority for further information. (See page 4 for more details.)
The chart below may be used as a guide in determining the proper water temperature for your home.
Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes 125°F (52°C) 11/2 to 2 minutes 130°F (54°C) About 30 seconds 135°F (57°C) About 10 seconds 140°F (60°C) Less than 5 seconds 145°F (63°C) Less than 3 seconds 150°F (66°C) About 11/2 seconds 155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
20
Page 21
Water Temperature Setting…
!
Maximum water temperatures occur just after the burner has shut off. To determine the water temperature, turn on a hot water faucet and place a thermometer in the water stream.
The reference mark p on the rim of the temperature dial, represents an approximate water temperature of 120°F (49°C).
The reference mark approximate water temperature of 130°F (54°C).
Each reference mark above or below these points indicates an approximate change of 10°F (5.5°C).
To adjust the temperature, turn the temperature dial to an initial setting of 120°F (49°C).
A condition known as “stacking” or “layering” can occur when a series of short and frequent hot water draws are taken.
The hottest temperature water will be at the top of the tank, closest to the outlet pipe delivering hot water to the home.
Stacking can cause this top layer of water to be hotter than the water toward the bottom of the tank near the gas control (thermostat).
A
represents an
Therefore, always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury.
Also, always supervise young children or others who are incapacitated.
The gas control (thermostat) is constructed with a built in safety shut-off device designed to shut off the gas supply to the burner if the pilot flame is extinguished for any reason.
The gas control (thermostat) is also equipped with a single use gas shut off device that will shut off the gas supply to the burner if the water heater exceeds normal operating temperatures. Refer to the (Before You Call For Service) section of this manual, or contact your dealer.
WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
If the water heater has been subjected to fire, flood or physical damage, turn off the manual gas control (shut-off) valve, and do not operate the water heater again until it has been checked by qualified personnel.
NOTICE: Replace any part of the gas control system which has been under water.
110°F
(43°C)
100°F (38°C)
90°F (32°C)
80°F (27°C)
Temperatures are approximate
120°F
(49°C)
130°F
(54°C)
140°F
(60°C)
150°F
(66°C)
160°F
(71°C)
21
Page 22
Care and cleaning of the water heater.
!
!
!
!
Draining the Water Heater
CAUTION: Shut off gas to the water
heater at the gas control (thermostat) gas cock or manual shut-off valve before draining water.
DANGER: Before manually operating the temperature and pressure relief valve, make certain no one will be exposed to the hot water released by the valve. The water drained from the tank may be hot enough to present a scald hazard and should be directed to a suitable drain to prevent injury or damage.
In order to drain the water heater, turn off the cold water supply. Open a hot water faucet or lift the handle on the relief valve to admit air to the tank.
Attach a garden hose to the drain valve on the water heater and direct the stream of water to a drain. Open the valve.
DANGER: Before manually operating the relief valve, make certain no one will be exposed to the danger of the hot water released by the valve. The water may be hot enough to create a scald hazard. The water should be released into a suitable drain to prevent injury or property damage.
DANGER: Hotter water increases the potential for Hot Water Scalds.
DANGER: Failure to perform the recommended Routine Preventative Maintenance can harm the proper operation of this water heater, which can cause carbon monoxide dangers, excessive hot water temperatures and other potentially hazardous conditions.
Routine Preventative Maintenance
Properly maintained, your water heater will provide years of dependable trouble­free service.
It is recommended that a periodic inspection of the gas control (thermostat), burner, relief valve, internal flue-way and venting system should be made by service personnel qualified in gas appliance repair.
It is suggested that a routine preventative maintenance program be established and followed by the user.
At least once a year, lift and release the lever handle on the temperature pressure relief valve, located near the top of the water heater, to make certain the valve operates freely. Allow several gallons to flush through the discharge line to an open drain.
NOTICE: If the temperature and pressure relief valve on the hot water heater discharges periodically, this may be due to thermal expansion in a closed water system. Contact the water supplier or your plumbing contractor on how to correct this. DO NOT plug the relief valve outlet.
A water heater’s tank can act as a settling basin for solids suspended in the water. It is therefore not uncommon for hard water deposits to accumulate in the bottom of the tank. If allowed to accumulate, these solids can cover the gas control
(thermostat) sensors, causing the sensors to operate erratically. Because accumulated solids can prevent the gas control (thermostat) sensors from accurately reading the water temperature, the water at the fixture can be hotter than the gas control (thermostat) dial setting. It is suggested that a few quarts (litres) of water be drained from the water heater’s tank every month to clean the tank of these deposits.
Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe. Strategically located risers in the water pipe system or water hammer arresting devices can be used to minimize the problem.
The anode rod should be inspected and replaced when more than 6” (15.2 cm) of core wire is exposed at either end of the rod.
Make sure the cold water supply is turned off before replacing the anode rod.
DANGER: Combustible materials, such as clothing, cleaning materials, or flammable liquids, etc., must not be placed against or next to the water heater.
22
Housekeeping
Vacuum around the base of the water heater for dust, dirt and lint on a regular basis. Visually inspect pilot burner and relight if necessary.
To ensure sufficient ventilation and combustion air supply, proper clearances must be maintained.
When installed in a closet, DO NOT block or obstruct any of the combustion air inlet openings located around the perimeter of the water heater. A minimum of 1” (2.5 cm) is required between these combustion air inlet openings and any obstruction.
Page 23
!
Proper burner and pilot burner pattern.
Venting System Inspection
It is recommended that the water heater’s internal flue, vent, and air pipes be inspected annually to be certain it is clean.
Inspect the gas venting system and the termination cap.
Make certain the vent system, vent, and air pipes is properly sealed and securely attached.
Burner Inspection
Visually inspect the pilot and main burners annually.
Through the sight glass, inspect the pilot burner flame with the main burner off and inspect the main burner while firing.
If any unusual burner operation is noted, the water heater should be shut off until qualified service assistance can be obtained.
If after inspection of the vent system you found soot or deterioration; call the local gas utility to correct the problem and clean the flue, and venting system or replace the flue baffle, before resuming operation of the water heater.
CAUTION: For your safety, cleaning of the burner must be performed only by qualified service personnel. The burner chamber is a sealed area. If the burner access door is removed, the burner access door gasket must be replaced.
For cleaning, remove the burner from the water heater. A vacuum cleaner can be used on the burner and floor shield inside the water heater. The burner can also be cleaned by scrubbing with mild detergent.
NOTICE: Refer to the Hydrogen Gas Caution in the Operating Instructions.
NOTICE: Do not remove the anode rod from the water heater’s tank, except for inspection and/or replacement, as operation with the anode rod removed will greatly shorten the life of the glass lined tank and will exclude warranty coverage.
Vacation and Extended Shut-Down
If the water heater is to remain idle for an extended period of time, the power and water to the appliance should be turned off to conserve energy and prevent a build-up of dangerous hydrogen gas.
The water heater and piping should be drained if they might be subjected to freezing temperatures.
After a long shut-down period, the water heater’s operation and controls should be checked by qualified service personnel.
Make certain the water heater is completely filled again before placing it in operation.
Anode Rod
This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank. The anode rod is slowly consumed, thereby eliminating or minimizing corrosion of the glass lined tank.
Water sometimes contains a high sulfate and/or mineral content and together with cathodic protection process can produce a hydrogen sulfide, or rotten egg odor in the heated water. Chlorination of the water supply should minimize the problem.
23
Page 24
Before You Call For Service…
Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.
Problem Possible Causes What To Do
Condensation This usually happens when This is normal. After the water in the tank warms
a new water heater is up, the condensation will disappear. If, however, the filled for the first time. condition persists, examine the piping and fittings for possible leaks.
Moisture from the products This is normal and will disappear in time. Excessive of combustion condensing condensation can cause pilot burner outage. on the tank surface.
An undersized water Use a water heater size that meets the requirements heater will cause of your needs. condensation. Contact a qualified service technician for service.
Yellow flame Scale on top of the burner. Contact a qualified service technician to remove scale. or soot
Flue or Combustion air inlet Remove obstruction or debris from flue or
openings are restricted. combustion air inlet openings on water heater jacket.
Not enough combustion or  Proper operation of the water heater requires air for ventilation air supplied to combustion and ventilation. See the Combustion and the water heater location. Ventilation Air information in the “Installing The Water Heater” section of this manual.
Unable to light Air in gas line. Contact a qualified service technician to purge the air the pilot burner from the gas line.
Pilot burner orifice clogged. The pilot burner should be cleaned or replaced by a
qualified service technician.
Pilot burner tube pinched or The pilot burner should be cleaned, repaired or clogged. replaced by a qualified service technician.
Gas cock knob not See the “Lighting The Water Heater” section of this correctly positioned. manual.
Pilot burner does not stay Loose thermocouple. The connection at the gas control (thermostat) should lit when the RED be tightened by a qualified service technician. button is released
Thermocouple defective. The thermocouple should be replaced by a qualified
service technician.
Safety magnet defective. The gas control (thermostat) should be replaced by a qualified service technician.
Gas Control’s (Thermostat’s) The gas control (thermostat) should be replaced by a single use gas shut-off device qualified service technician. has opened.
Improper vent assembly Contact a qualified service technician for service. and installation.
CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
24
Page 25
Problem Possible Causes What To Do
Rumbling noise Scale and sediment Clean tank.
in tank.
Relief valve Pressure build up This is an unacceptable condition and must be producing popping caused by thermal corrected. Contact the water supplier or plumbing noise or draining expansion to a contractor on how to correct this. Do not plug the closed system. relief valve outlet.
Not enough or Water usage may have Wait for the water heater to recover after an no hot water exceeded the capacity abnormal demand. of the water heater.
Low gas pressure. Check gas supply pressure and manifold pressure.
The pilot burner may be out. Check the pilot burner. If necessary, relight using the instructions in the “Lighting The Water Heater” section of this manual.
The gas control (thermostat) See the “Water Temperature Setting” of The Water may be set too low. Heater section of this manual.
Leaking or open hot Make sure all faucets are closed. water faucets.
Cold water inlet This is normal. The colder inlet water takes longer temperature may be to heat. colder during the winter months.
Water is too hot The gas control (thermostat) See the “Water Temperature Setting” of The Water is set too high. Heater section of this manual.
Gas Control (Thermostat) Contact a qualified service technician to replace the Defective. gas control (thermostat).
CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or
other safety devices. Refer repairs to qualified service personnel.
25
Page 26
Replacement Parts.
Ve nt
Te rminal Cap
T&P Relief Valve
Drain Valve
Shroud
Drain Valve
Inner Door
Jacket Door
Burner
Gas Control (thermostat)
Pilot Supply
Tube
Piezo
Ignitor Wire
Thermocouple
Burner Supply
Tube
Burner
Orifice
Dip Tube
Dip Tube
Gasket
Flue Baffle
and
Hanger
Main Air Tube
Sliding Air Tube
Air Tube Elbow
Inner Door
Gasket
Burner
Cone
Grommet
Instructions For Placing a Parts Order
Address parts orders to the distributor or store from where the heater was purchased.
All parts orders should include:
The model and serial number of the
water heater from the rating plate.
Specify type of gas (natural or LP)
as marked on the rating plate.
Part description (as noted below) and
number of parts desired.
CAUTION: For your safety, DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
Burner Assembly Kit
The kit provides extra speed clips and tamper resistant screws.
26
Page 27
Notes
27
Page 28
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires adjustment, repair, or routine maintenance, it is suggested that you first contact your installer, plumbing contractor or previously agreed upon service agency. In the event the firm has moved, or is unavailable, refer to the telephone directory, commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should then contact the Manufacturer’s National Service Department at the following address:
In the United States: 2600 Gunter Park Drive Montgomery, Alabama 36109-1413 Phone: 1-800-432-8373.
:
Important Instructions for the Commonwealth of Massachusetts
The Commonwealth of Massachusetts requires compliance with 5.08:
Modications to NFPA-54, Chapter 10 regulation 248 CMR 4.00 and
5.00 for installation of through – the – wall vented gas appliances as follows: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residen­tial purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7)
feet above nished grade in the area of the venting, including but not lim­ited to decks and porches, the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equip-
ment, the installing plumber or gastter shall observe that a hard wired
carbon monoxide detector with an alarm and battery back-up is installed
on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gastter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed profes­sionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equip­ment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on
the next adjacent oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, how­ever, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
ed.
3. SIGNAGE. A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-
28
When contacting the manufacturer, the following
information will be requested:
a. Model and serial number of the water heater as shown on
the rating plate attached to the jacket of the heater.
b. Address where the water heater is located and physical
location.
c. Name and address of installer and any service agency who
performed service on the water heater.
d. Date of original installation and dates any service work was
performed. e. Details of the problems as you can best describe them. f. List of people, with dates, who have been contacted
regarding your problem.
TIONS”.
4. INSPECTION. The state or local gas inspector of the side wall hori­zontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detec­tors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4. (b) EXEMPTIONS: The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. (c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a vent­ing system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equip­ment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system. (d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment
does not provide the parts for venting the ue gases, but identies “spe­cial venting systems”, the following requirements shall be satised by the
manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. (e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc­tions shall remain with the appliance or equipment at the completion of the installation.
Loading...