Rheem ARL-JEZ 16 Seer Series, ASL-JEZ 18 Seer Series, ARL-JEZ Series, ASL-JEZ Series Installation Instructions Manual

INSTALLATION INSTRUCTIONS
AIR-COOLED CONDENSING UNITS
(-)ARL-JEZ 16 SEER AND (-)ASL-JEZ 18 SEER MODELS EQUIPPED WITH THE INTEGRATED COMFORT CONTROL SYSTEM™
[ ] INDICATES METRIC CONVERSIONS
Featuring Industry Standard R-410A Refrigerant
92-101691-02-10
SUPERSEDES 92-101691-02-09
TABLE OF CONTENTS
Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Electrical & Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Locating Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Factory-Preferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Refrigerant Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Tools Required for Installing & Serviciing R-410A Models . . . . . . . . . . . . . .7
Specification of R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Quick Reference Guide for R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Interconnecting Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-11
Liquid Line Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Suction Line Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Evacuation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Start-Up And Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Checking Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Checking Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Factory Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Field Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Comfort Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Status and Diagnostic Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
General Service Analyzer Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-31
Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Electrical and Mechanical Checks Flow Charts . . . . . . . . . . . . . . . . . . .32-33
System Charge Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Trouble Shooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-37
CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check condensing unit model number, electrical characteristics and accessories to determine if they are correct. Check system components (evaporator coil, condens­ing unit, evaporator blower, etc.) to make sure they are properly matched.
2
FIGURE 1
AIR INLETS (LOUVERS) ALLOW 120 [305 mm] MIN. CLEARANCE 3 SIDES
AIR DISCHARGE
ALLOW 600 [1524 mm] CLEARANCE
ALLOW 240 [610 mm] ACCESS CLEARANCE
ACCESS PANEL
L
W
H
ALTERNATE HIGH VOLTAGE CONNECTION (KNOCKOUT) 1
11
/320 [34 mm]
SERVICE FITTINGS
LOW VOLTAGE CONNECTION
7
/8" [22 mm]
HIGH VOLTAGE CONNECTION 1
11
/32" [34 mm]
LIQUID LINE CONNECTION
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 24" [610 mm] CLEARANCE ONE SIDE
2
7
/8" [73 mm] DIA. ACCESSORY KNOCKOUTS
VAPOR LINE CONNECTION
A-00002
DIMENSIONS AND INSTALLATION CLEARANCES
UNIT MODEL NUMBER EXPLANATION
(-)ARL – 036 J EZ
ACCESS PANEL
AIR DISCHARGE
ALLOW 60" [1524 mm] CLEARANCE
ALLOW 24" [610 mm] ACCESS CLEARANCE
AIR INLETS (LOUVERS) ALLOW 12" [305 mm] MIN. CLEARANCE 3 SIDES
ALTERNATE LINE VOLTAGE
ENTRY (KNOCKOUT)
111⁄32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
Z-SCROLL COMPRESSOR
E = EQUIPPED WITH THE
COMFORT CONTROL SYSTEM™
J -208/230-1-60
(NOMINAL CAPACITY) 024/025 = 24000 BTU/HR 036/037/038 - 36000 BTU/HR 048/049 = 48000 BTU/HR 060/061 = 60000 BTU/HR
L = DESIGN SERIES (R-410A)
R = 16 SEER S = 18 SEER
A = REMOTE CONDENSING UNIT
TRADE NAME
BASE PAN
Model Number
RARL-
024JEZ/025JEZ
036JEZ/037JEZ/038JEZ/
049JEZ/060JEC/061JEZ
LINE VOLTAGE
ENTRY
7
8" [22 MM]
Height “H”
(Inches) [mm]
23 [584]
33 [838]
LINE VOLTAGE
111⁄32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
Length “L”
(Inches) [mm]
3
8 [1127] 311⁄2 [800]
44
3
[1127]
8
44
(Inches) [mm]
ENTRY
Width “W”
1
[800]
2
31
Model Number
ASL-
024JEZ
036JEZ
BOTTOM VIEW SHOWING DRAIN OPENINGS (\\\\\ SHADED AREAS).
Height “H”
(Inches) [mm]
33 [838]
Length “L”
(Inches) [mm]
3
[1127]
8
44
Width “W”
(Inches) [mm]
1
2
31
[800]
3
ELECTRICAL & PHYSICAL DATA
TABLE 1
(-)ARL-JEZ ELECTRICAL DATA
ELECTRICAL PHYSICAL
Model
Number
RARL-
Rev. 4/11/2012 ARL-JEZ
0245JEZ 1-60-208/230 10.3/10.3 52 0.75 14/14 20/20 20/20 15.82 [1.47] 1 2285 [1078] 115 [3260] 209 [94.8] 222 [100.7]
025JEZ 1-60-208/230 11.7/11.7 58.3 0.75 16/16 20/20 25/25 15.82 [1.47] 1 2285 [1078] 104 [2948] 197 [89.4] 210 [95.3]
037JEZ 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1 3400 [1604] 150 [4252] 247.5 [112.3] 260.5 [118.2]
038JEZ 1-60-208/230 15.3/15.3 83 1 21/21 25/25 35/35 23.01 [2.14] 1 3400 [1604] 186 [5273] 216 [98] 229 [103.9]
048JEZ 1-60-208/230 21.2/21.2 96 1 28/28 35/35 45/45 23.01 [2.14] 2 3400 [1604] 150 [4252] 245 [111.1] 258 [117]
049JEZ 1-60-208/230 21.2/21.2 104 1 28/28 35/35 45/45 23.01 [2.14] 1 3400 [1604] 180 [5103] 247 [112] 260 [118]
060JEZ 1-60-208/230 25.6/25.6 118 2.8 35/35 45/45 60/60 23.01 [2.14] 2 3500 [1652] 220 [6237] 314 [142.4] 327 [148.3]
061JEZ 1-60-208/230 28.8/28.8 152.9 2.8 39/39 50/50 60/60 23.01 [2.14] 2 3500 [1652] 243 [6889] 283 [128.4] 296 [134.3]
Rev. 4/20/2012 (-)ASL-JEZ ELECTRONICS DATA
024JEZ 1-60-208/230 10.3/10.3 52 0.5 14/14 20/20 20/20 15.8 [1.47] 1 2500 [1180] 144 [4082] 250.5 [107] 263.5 [107]
036JEZ 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1 3400 [1604] 150 [4252] 247.5 [112.3] 260.5 [118.2]
Phase
Frequency
(Hz)
Voltage
(Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked
Rotor
Amperes
(LRA)
Fan
Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Outdoor Coil Weight
Face Area
Sq. Ft. [m
No.
Rows
CFM [L/s}
2
]
Refrig.
Per Circuit Oz. [g]
Net
Lbs. [kg]
Shipping Lbs. [kg]
WARNING
!
THE MANUFACTURER’S WAR­RANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS. ACCES­SORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFAC­TURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
GENERAL
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the air conditioning system. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions (noise and compo­nent failure), and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the condensing unit specification sheet should be used.
APPLICATION
Before specifying any air conditioning equipment, a survey of the structure and a heat gain calculation must be made. A heat gain calculation begins by measuring all external surfaces and openings that gain heat from the surrounding air and quantifying that heat gain. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal.
Air conditioning systems are sized on the cooling load calculation. There are two capacities that enable the equipment to provide comfort. The first is sensible capacity.
Sensible heat is the heat energy measured on the dry bulb thermometer as it is added or removed.
The second form of heat is called latent or hidden heat. This is heat held in the humidity in the air.
A properly-sized unit removes both forms of heat, producing a comfortable living space. An oversized system cycles on and off too quickly and does not properly remove humidity, producing an uncomfortable living space. Select the indoor and outdoor equipment combination based on the manufacturer’s engineering data.
After the equipment combination has been selected, satisfying both sensible and latent conditioning requirements, the system must be properly installed. Only then can the unit provide the comfort the manufacturer intends.
There are several factors that the installers must consider:
• Outdoor unit location • Proper equipment evacuation
• System refrigerant charge • Indoor unit airflow
• Indoor unit blower speed • Supply and return air duct design and sizing
• System air balancing • Diffuser and return air grille location and sizing
4
CORROSIVE ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
A good liquid cleaner may be used several times a year to remove matter on the cabinet that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
LOCATING UNIT
CONDENSER LOCATION
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor condenser.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perfor­mance or operation.
OPERATIONAL ISSUES
IMPORTANT: Locate the condenser in a manner that will not prevent, impair or compromise the performance of other equipment horizontally installed in prox­imity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or manaufacturers’ recommendations, local code recommendations and requirements will take presidence.
Refrigerant piping and wiring should be properly sized and kept as short as possible to avoid capacity losses and increased operating costs.
Locate the condenser where water run off will not create a problem with the equipment. Position the unit away from the drip edge of the roof whenever pos­sible. Units are weatherized, but can be affected by the following:
• Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the condenser while in operation can impact fan blade or motor life.
5
Refer to clearance recommendations on Page 3. o 24” to the service panel access
o 60” above condenser fan discharge (unit top) to prevent recirculation o 12” to condenser coil grille air inlets (per condenser).
FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances: Single Unit Applications: One condenser inlet air grille side may be reduced to no
less than an 8-inch clearance. Clearances below 8 inches will reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clear­ances.
Multiple Unit Applications: When multiple unit (2 or more condensers) air inlet grilles are placed side by side, a 12-inch per unit clearance is recommended, for a total of 24” between two units. When multiple condenser grille sides are aligned, a 4-inch per unit spacing can be used, for a total of 8 inches between multiple units. Two combined clearances below 8 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service, clearances.
CUSTOMER SATISFACTION ISSUES
The condenser should be located away from the living, sleeping and recreation­al spaces of the owner and those spaces of adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from entering the unit.
NOTE: Tubing installed in walls may cause noise issues.
UNIT MOUNTING
If elevating the condensing unit, either on a flat roof or on a slab, observe the following guidelines.
The base pan provided elevates the condenser coil 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration.
NOTE: Do not block drain openings shown in Figure 1.
FACTORY-PREFERRED TIE-DOWN METHOD
FOR OUTDOOR UNITS
IMPORTANT: The Manufacturer approved/recommended method is a guide to securing equipment for wind and seismic loads. Other methods might provide the same result, but the Manufacturer method is the only one endorsed by Manufacturer for securing equipment where wind or earthquake damage can occur. Additional information is available in the PTS (Product Technical Support) section of the Manufacturer website Rheemote.net and can be found as a listing under each out­door model. If you do not have access to this site, your Distributor can offer assis­tance.
6
REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant R-410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
TOOLS REQUIRED FOR INSTALLING & SERVICING R-410A MODELS
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
7
SPECIFICATION OF R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 condens­ing units.
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
QUICK REFERENCE GUIDE FOR R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
EVAPORATOR COIL
REFER TO EVAPORATOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
CAUTION
!
Only use evaporators rated and approved for use on (-)ARL and (-)ASL R-410A systems.
8
The thermostatic expansion valve is specifically designed to operate with R-410A.
DO NOT use an R-22 TXV or evaporator. The existing evaporator must be replaced with the factory specified TXV evaporator specifically designed for R-410A.
LOCATION
Do not install the indoor evaporator coil in the return duct system of a gas or oil fur­nace. Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched toward the drain connection.
CAUTION
!
When coil is installed over a finished ceiling and/or living area, it is recommend­ed that a secondary sheet metal condensate pan be constructed and installed under entire unit. Failure to do so can result in property damage.
INTERCONNECTING TUBING
VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made. Make connections at the indoor coil first. Refer to Line Size Information in Tables 2 through 4 for correct size and multipliers to
be used to determine capacity for various vapor line diameters and lengths of run. The losses due to the lines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for 15 feet of inter­connecting lines. The factory refrigeration charge in the outdoor unit is sufficient for the unit and 15 feet of standard size interconnecting liquid and vapor lines. For dif­ferent lengths, adjust the charge as indicated below.
1/4” ± .3 oz. per foot 5/16” ± .4 oz. per foot 3/8” ± .6 oz. per foot 1/2” ± 1.2 oz. per foot
OUTDOOR UNIT INSTALLED ABOVE INDOOR COIL
Keep the vertical separation between coils to a minimum. However, the vertical dis­tance can be as great as 120 feet with the condensing unit ABOVE the indoor coil. Use the following guidelines when installing the unit:
NOTE: If exceeding these measurements, the system must be an engineered sys­tem.
OUTDOOR UNIT BELOW INDOOR COIL
Keep the vertical separation to a minimum. Use the following guidelines when installing the unit:
1. DO NOT exceed the vertical separations as indicated on Table 4.
2. Always use the smallest liquid line size permitted to minimize system charge.
3. Table 4 may be used for sizing horizontal runs. Vertical separation is limited to the total line length as defined in the liquid line sizing
charts. Examples:
1. A 2-ton condensing unit with a 1/4" liquid line cannot exceed a total line length of 25 ft.
2. A 3-ton unit with a 5/16" liquid line cannot exceed a total line length of 125 ft.
3. A 4-ton unit with a 5/16" liquid line cannot exceed a total line length of 50 ft.
IMPORTANT: Do not exceed a total line length of 125 feet in all systems.
9
TUBING INSTALLATION
Observe the following when installing correctly sized type “L” refrigerant tubing between the condensing unit and evaporator coil:
If a portion of the liquid line passes through a hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required.
Use clean, dehydrated, sealed refrigeration grade tubing.
Always keep tubing sealed until tubing is in place and connections are to be made.
Blow out the liquid and vapor lines with dry nitrogen before connecting to the outdoor unit and indoor coil. Any debris in the line set will end up plugging the expansion device.
Do not allow the vapor line and liquid line to be in contact with each other. This causes an undesirable heat transfer resulting in capacity loss and increased power consumption. The vapor line must be insulated.
If tubing has been cut, make sure ends are deburred while holding in a position to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes.
For best operation, keep tubing run as short as possible with a minimum num­ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a tubing bender on the vapor line to prevent kinking.
Route the tubing using temporary hangers, then straighten the tubing and install permanent hangers. Line must be adequately supported.
The vapor line must be insulated to prevent dripping (sweating) and prevent performance losses. Armaflex and Rubatex are satisfactory insulations for this purpose. Use 1/2” minimum insulation thickness, additional insulation may be required for long runs.
Check Table 2 for the correct vapor line size. Check Table 4 for the correct liq­uid line size.
10
TUBING CONNECTIONS
Indoor evaporator coils have only a holding charge of dry nitrogen. Keep all tube ends sealed until connections are to be made.
Use type “L” copper refrigeration tubing. Braze the connections with the follow­ing alloys:
– copper to copper - 5% – Silver alloy (no flux) – copper to steel or brass - 35% – silver alloy (with flux)
Be certain both refrigerant shutoff valves at the outdoor unit are closed.
Clean the inside of the fittings and outside of the tubing with steel wool or sand cloth before brazing. Always keep chips, steel wool, dirt, etc., out of the inside when cleaning.
Assemble tubing part way into fitting. Apply flux all around the outside of the tubing and push tubing into stop. This procedure will keep the flux from getting inside the system.
Remove the cap and schrader core from service port to protect seals from heat damage.
TABLE 2
SUCTION LINE LENGTH SIZE VS. CAPACITY MULTIPLIER (2-STAGE R-410A)
Unit Size
Suction Line
Connection
Size
Suction Line
Run Feet
Optional
25'
Standard
Optional Optional
50'
Standard
Optional Optional
100'
Standard
Optional Optional
150'
Standard
Optional
*Standard Line Size Note: Using suction line larger than shown in chart will result in poor oil return.
2 Ton
3/4" I.D. 3/4" I.D. 7/8" I.D. 7/8" I.D.
5/8*
3/4
1.00
1.00 —
0.99
1.00 —
0.97
0.98 —
0.95
0.97
3 Ton
5/8 3/4 3/4
3/4*
0.99
1.00 —
0.98
0.99 —
0.95
0.97 —
0.91
0.95 —
Use an appropriate heatsink material around the copper stub and the service valves before applying heat.
IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen into a service port and through the tubing while brazing.
After brazing:
• Use an appropriate heatsink material to cool the joint and remove any flux
residue.
• Clamp the TXV bulb securely on the suction line at the 2 o’clock position with
the strap provided in the parts bag.
• Insulate the TXV sensing bulb and suction line with the provided pressure
sensitive insulation (size 4" x 7") and secure with provided wire ties.
NOTE: TXV SENSING BULB SHOULD BE LOCATED ON A HORIZONTAL
SECTION OF SUCTION LINE, JUST OUTSIDE OF COIL BOX.
The service valves are not backseating valves. To open the valves, remove the valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the stem. Back out counterclockwise.
Replace the valve cap finger tight then tighten an additional 1/2 hex flat for a metal-to-metal seal.
4 Ton
7/8* 7/8*
——
1.00
1.00 —
0.98
0.99 —
0.95
0.97 —
0.93
0.95 —
5 Ton
0.99
1.00 —
0.98
0.99 —
0.94
0.97 —
0.91
0.95 —
TABLE 3
ELBOW EQUIVALENT LENGTHS, FT.
Short Long
Size Radius Radius
1/4 0.4 0.2
5/16 0.5 0.3
3/8 0.5 0.3 1/2 0.6 0.4 5/8 0.8 0.6 3/4 0.9 0.8
7/8 1.0 1.0 1-1/8 1.2 1.2 1-3/8 2.1 1.4 1-5/8 2.5 1.5
LEAK TESTING
Pressurize line set and coil through service fittings with dry nitrogen to 150 psig maximum. Leak test all joints using liquid detergent. If a leak is found, recover pressure and repair.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
11
TABLE 4
LIQUID LINE SIZING (2-STAGE R-410A) LIQUID LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A System
Capacity
Model
2 Ton
3 Ton
4 Ton
5 Ton
2 Ton
3 Ton
Liquid Line Connection
Size
(Inch I.D.)
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
Line Size (Inch
O.D.)
1/4” [6.35] 0010 [3.05] 37 [11.28] 64 [19.51] 91 [27.74] 5/16” [7.93] 000000 3/8” [9.52]* 000000 5/16” [7.93] 0 3 [0.91] 10 [3.05] 16 [4.88] 23 [7.01] 30 [9.14] 3/8” [9.52]* 00001 [0.31] 4 [1.22]
12” [12.70] 000000
5/16” [7.93]* 00011 [3.35] 34 [10.36] 58 [17.68]
3/8” [9.52] 000000 1/2” [12.70] 000000
3.8” [9.52]* 000002 [0.61] 1/2” [12.70] 000000
1/4” [6.35] 0014 [4.27] 41 [12.50] 69 [21.03] 96 [29.26] 5/16” [7.93] 000000 3/8” [9.52]* 000000 5/16” [7.93] 006 [1.83] 12 [3.66] 19 [5.79] 26 [7.93] 3/8” [9.52]* 000000
12” [12.70] 000000
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
Outdoor unit Above Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Liquid Line Size
Total Equivalent Length - Feet [m]
Minimum Vertical Separation - Feet
16 SEER
18 SEER
LIQUID LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
R-410A
System
Capacity
Model
2 Ton
3 Ton
4 Ton
5 Ton
2 Ton
3 Ton
*Standard Line Size N/A - Application not recommended.
Liquid Line
Connection
Size
(Inch I.D.)
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
3/8” [9.53]
Line Size (Inch
O.D.)
1/4” [6.35] 19 [5.79] N/A N/A N/A N/A N/A 5/16” [7.93] 25 [8.84] 25 [7.62] 22 [6.71] 19 [5.79] 16 [4.88] 12 [3.66]
3/8” [9.52]* 25 [9.45] 30 [9.14] 29 [8.84] 27 [8.23] 26 [7.93] 25 [7.62]
5/16” [7.93] N/A N/A N/A N/A N/A N/A
3/8” [9.52]* N/A N/A N/A N/A N/A N/A 12” [12.70] 10 [3.05] 9 [2.74] 9 [2.74] N/A N/A N/A
5/16” [7.93]* 25 [9.14] 17 [5.18] N/A N/A N/A N/A
3/8” [9.52] 25 [11.89] 35 [10.67] 30 [9.14] 25 [7.62] 21 [6.40] 16 [4.88] 1/2” [12.70] 25 [13.11] 42 [12.80] 41 [12.50] 40 [12.19] 39 [11.89] 38 [11.58]
3.8” [9.52]* 25 [7.62] 19 [5.79] 14 [4.27] 9 [2.74] N/A N/A
1/2” [12.70] 25 [8.84] 28 [8.53] 27 [8.23] 26 [7.93] 25 [7.62] 24 [7.32]
1/4” [6.35] 25 [7.93] 13 [3.96] N/A N/A N/A N/A 5/16” [7.93] 25 [10.97] 32 [9.75] 29 [8.84] 26 [7.93] 23 [7.01] 20 [6.10]
3/8” [9.52]* 25 [11.58] 37 [11.28] 35 [10.67] 34 [10.36] 33 [10.06] 32 [9.75]
5/16” [7.93] N/A N/A N/A N/A N/A N/A
3/8” [9.52]* 12 [3.66] 10 [3.05] N/A N/A N/A N/A 12” [12.70] 14 [4.27] 13 [3.96] 13 [3.96] 12 [3.66] 12 [3.66] 11 [3.35]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
Outdoor unit Below Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Liquid Line Size
Total Equivalent Length - Feet [m]
Minimum Vertical Separation - Feet
16 SEER
18 SEER
12