
AP13731 (03/05)
FOR YOUR SAFETY!
— Do not store or use gasoline or other
flammable vapors or liquids or other
combustible materials in the vicinity of this or
any other appliance. To do so may result in an
explosion or fire.
— WHAT TO DO IF YOU SMELL GAS
● Do not try to light any appliance.
● Do not touch any electrical switch; do not
use any phone in your building.
● Immediately call your gas supplier from a
neighbor’s phone. Follow the gas
supplier’s instructions.
● If you cannot reach your gas supplier, call
the fire department.
● Do not return to your home until authorized
by the gas supplier or fire department.
— Improper installation, adjustment,
alteration, service or maintenance can cause
property damage, personal injury, or death.
Refer to this manual. Installation and service
must be performed by a qualified installer,
service agency or the gas supplier.
WARNING: If the information in these instructions is not followed exactly,
a fire or explosion may result causing property damage, personal injury or death.
The purpose of this manual is twofold: one, to provide the installer with
the basic directions and recommendations for the proper installation and
adjustment of the water heater; and two, to the owner–operator, to
explain the features, operation, safety precautions, maintenance and
troubleshooting of the water heater. This manual also includes a parts
list.
It is imperative that all persons who are expected to install, operate or
adjust this water heater read the instructions carefully so they may
understand how to perform these operations. If you don’t understand
these instructions or any terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or
warranty of this water heater should be directed to the seller from whom
it was purchased. If additional information is required, refer to the
section on If You Need Service
Do not destroy this manual. Please read carefully and keep in a safe
place for future reference.
Recognize this symbol as an indication of Important Safety
Information!
California Proposition 65 Warning: This product contains
chemicals known to the State of California to cause cancer, birth
defects or other reproductive harm.
Use & Care Manual
With Installation Instructions for the Installer
Printed in Japan
Tankless Water Heater
Warning: This water heater is not suitable
for use in manufactured (mobile) homes!
31-52756
Commercial Indoor and Outdoor Gas
!
Indoor Water Heater
!
!
Outdoor Water Heater
!
!
I
S
G
E
N
D
CERTIFIED
C
E
D
R
E
I
T
F
I
R
®

Safety Information
Safety Precautions . . . . . . . 3–6
LP Gas Models . . . . . . . . . . . 5
Installation Instructions
Location of Indoor. . . . . . . . . 7
Location of Outdoor . . . . . . . . 8
Water Connections . . . . . 10-11
Gas Supply. . . . . . . . . . . . . . 12
High Altitude . . . . . . . . . . . . 12
Venting . . . . . . . . . . . . . . 13-18
Remote Control. . . . . . . . 19-20
Electrical Connection . . . . . . 21
Typical Installation Indoor. . 22
Typical Installation Outdoor 23
Pipe Insulation . . . . . . . . . . . 24
Installation Checklist . . . 24-25
Operating Instructions
Lighting Instructions . . . . . . 26
Water Temperature. . . . . 27, 28
Care and Cleaning
Maintenance. . . . . . . . . . . . . 29
Housekeeping . . . . . . . . 29, 30
Vent Inspection . . . . . . . . . . . 30
Burner Inspection . . . . . . . . 30
Extended Shut-Down . . . . . . 30
Draining . . . . . . . . . . . . . . . . 31
Freeze Protection . . . . . . . . . 31
Troubleshooting Tips
Before You Call
For Service . . . . . . . . . . . 32,33
Customer Service
Parts List . . . . . . . . . . . . . . . 34
If You Need Service. . . . . . . 36
Inside you will find many helpful hints on how to use and
maintain your water heater properly. A little preventive care on
your part can save you time and money over the life of your
water heater.
You’ll find many answers to common problems in the
Troubleshooting Guide. If you review the chart of
Troubleshooting Tips first, you may not need to call for service.
READ THIS MANUAL
FOR YOUR RECORDS
Write the model and serial numbers here:
#
#
You can find them on a label on the appliance.
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service
under the warranty.
2
Your safety and the safety of others are very important. There
are many important safety messages in this manual and on
your appliance. Always read and obey all safety messages.
This is the safety alert symbol. Recognize this symbol
as an indication of Important Safety Information!
This symbol alerts you to potential hazards that can
kill or hurt you and others.
All safety messages will follow the safety alert symbol and
either the word “DANGER”, “WARNING”, “CAUTION” or
“NOTICE”.
These words mean:
DANGER
An imminently hazardous situation
that will result in death or serious
injury.
WARNING
A potentially hazardous situation that
could result in death or serious injury
and/or damage to property.
CAUTION A potentially hazardous situation that
may result in minor or moderate
injury.
Notice:
Attention is called to observe a
specified procedure or maintain
a specific condition.
READ THE SAFETY INFORMATION
Qualified Installers Only!
Dip Switch Adjustment. . . . 35
!
!
!
!

Be sure to read and understand the entire Use and Care Manual before attempting to install or operate
this water heater. It may save you time and money. Pay particular attention to the Safety Instructions.
Failure to follow these warnings could result in serious bodily injury or death. Should you have
problems understanding the instructions in this manual, or have any questions, STOP, and get help
from a qualified service technician, or the local gas utility.
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
3
Failure to install and properly vent the water heater to the outdoors as outlined in the
Venting Section of the Installation Instructions in this manual can result in unsafe
operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from
carbon monoxide, never operate this water heater unless it is properly vented and has an
adequate air supply for proper operation.
Be sure to inspect the vent outlet on the OUTDOOR water heater, or the vent terminal
and the vent system on the INDOOR water heater for proper installation at initial startup; and at least annually thereafter. Refer to the Care and Cleaning section of this
manual for more information regarding vent system inspection.
DANGER!
INSTALL AND PROPERLY VENT THE WATER HEATER…
Gasoline, as well as other flammable materials and liquids (adhesives, solvents, paint
thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle,
use or store gasoline or other flammable or combustible materials anywhere near or in the
vicinity of a water heater or any other appliance. Be sure to read and follow the labels on
the water heater, as well as the warnings printed in this manual. Failure to do so can
result in property damage, bodily injury or death.
WARNING!
DANGER
FLAMMABLES
Vapors from flammable
liquids will explode and
catch fire causing death or
severe burns.
Do not use or store flammable
products such as gasoline,
solvents or adhesives in the
same room or area near the
water heater.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach.
Installation:
Do not install water heater
where flammable products will
be stored or used unless the
main burner flame is at least
Read and follow water heater warnings and instructions. If
owners manual is missing, contact the retailer or manufacturer.
Flammable Vapors
Water he ater has a main
burner flame.
The main burner flame:
1. which c an come on
at any time and
2. will ignite flammable
vapo rs.
Vapo rs:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the
floo r and
4. can be carried from
other r ooms to the
main burner flame by
air currents.
18" above the floor. This will
reduce, but not eliminate, the
risk of vapors being ignited
by the main burner flame.

Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 11/2 to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 11/2 seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide
in determining the proper water temperature for your
home.
DANGER: Households with small children,
disabled, or elderly persons may require a
120°F (49°C) or lower temperature setting to
prevent contact with “HOT” water.
Maximum water temperature occurs while burner is
on. To find water temperature being delivered, turn
on a hot water faucet and place a thermometer in the
water stream and read the thermometer.
(See page 27 & 28 for more details.)
The temperature of the water at the outlet of the
water heater can be regulated by setting the
temperature on Remote Control. The remote control
was set at 100°F (38°C) before it was shipped from
the factory.
The illustration to the bottom left illustrates the
Remote Control and how to adjust the water
temperature.
Notice: The factory setting allows operating
temperatures between 100°F (38°C) and 120°F
(49°C). Temperatures of up to 180°F (82°C) can be
achieved with the MAIN (UMC-117) remote control
and a dip switch adjustment. Only qualified service
personnel should perform this adjustment. Only
factory authorized remote control(s) should be used.
Notice: When this water heater is supplying general
purpose hot water requirements for use by
individuals, a thermostatically controlled mixing
valve for reducing point of use water temperature is
recommended to reduce the risk of scald injury.
Contact a licensed plumber or the local plumbing
authority for further information.
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water
temperature setting of a water heater’s remote control. Water temperatures above
125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the
warnings outlined on the label pictured below.
4
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
* Temperatures above 120°F (49°C) can be achieved
by adjusting the dip switch. See page 35 for dip
switch adjustment.
Notice:
Display
shows
°F only.
!
!
DANGER
HOT
BURN
Water temperature over 125°F can
cause severe burns instantly or
death from scalds.
Children, disabled and elderly are
at highest risk of being scalded.
See instruction manual before
setting temperature at water
heater.
Feel water before bathing or
showering.
Temperature limiting valves are
available, see manual.
Higher (Hotter) Lower (Cooler)
100 102 104 106 108 110 112 114 116 118 120* 125 130 135 140 150 160 170 180 °F
38 39 40 41 42 43 44 46 47 48 49* 52 54 57 60 66 71 77 82 °C
PRIORITY
°F
POWER
ON/OFF
!

5
Both LP and natural gas have an odorant added to aid in detecting a gas leak. Some
people may not physically be able to smell or recognize this odorant. If you are unsure or
unfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such
as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or
camouflage a gas leak.
DANGER!
NATURAL GAS AND LIQUEFIED PETROLEUM MODELS
● Water heaters utilizing LP gas are
different from natural gas models. A
natural gas water heater will not function
safely on LP gas and vice versa.
● No attempt should ever be made to
convert the water heater from natural
gas to LP gas. To avoid possible
equipment damage, personal injury or
fire, do not connect the water heater to a
fuel type not in accordance with the unit
data plate; propane for propane units
and natural gas for natural gas units.
These units are not certified for any
other fuel type.
● LP appliances should not be installed
below grade (for example, in a basement)
if such installation is prohibited by
federal, state and/or local laws, rules,
regulations or customs.
● Propane or LP gas must be used with
great caution. It is heavier than air and
will collect first in lower areas making it
hard to detect at nose level.
● Before attempting to light the water
heater, make sure to look and smell for
gas leaks. Use a soapy solution to check
all gas fittings and connections. Bubbling
at a connection indicates a leak that must
be corrected. When smelling to detect a
gas leak, be sure to sniff near the floor
also.
● Gas detectors are recommended in LP
and natural gas applications and their
installation should be in accordance with
the detector manufacturer’s
recommendations and/or local laws,
rules, regulations or customs.
● It is recommended that more than one
method, such as soapy solution, gas
detectors, etc., be used to detect leaks in
gas applications.
Notice: If a gas leak is present or suspected:
● Do not attempt to find the cause yourself.
● Do not
try to light any appliance.
● Do not
touch any electrical switch.
● Do not
use any phone in your building.
● Leave the building immediately and
make sure your family and pets leave
also.
● Leave the doors open for ventilation and
contact the gas supplier, a qualified
service agency or the fire department.
● Stay away from the building until the
service call has been made, the leak is
corrected and a qualified agency has
determined the area to be safe.

6
Have the installer show you the location of the gas shut-off valve and how to shut it off if
necessary. Turn off the manual shut-off valve if the water heater has been subjected to
overheating, fire, flood, physical damage or if the gas supply fails to shut off.
● Read this manual entirely before
installing or operating the water heater.
● Use this appliance only for its intended
purpose as described in this Use and
Care Manual.
● Be sure your appliance is properly
installed in accordance with local codes
and the provided installation
instructions.
● Do not attempt to repair or replace any
part of your water heater unless it is
specifically recommended in this
manual. All other servicing should be
referred to a qualified technician.
SAFETY PRECAUTIONS
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of
fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of
life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or
strapped to resist falling or horizontal displacement due to earthquake motions. For
residential water heaters up to 52 gallon capacity, a brochure with generic earthquake
bracing instructions can be obtained from: Office of the State Architect, 1102 Q Street,
Suite 5100, Sacramento, CA 95814 or you may call 916-445-8100 or ask a water heater
dealer.
However, applicable local codes shall govern installation. For residential water heaters
of a capacity greater than 52 gallons or tankless-style, consult the local building
jurisdiction code for acceptable bracing procedures.
READ AND FOLLOW THIS SAFETY INFORMATION
CAREFULLY.
SAVE THESE INSTRUCTIONS
!

Installing the (INDOOR) water heater :
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association,
400 North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire
Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest
edition of the CSA B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code,
CSA C22.1 Part 1, in the absence of local codes.
Location of INDOOR Water Heater
The water heater should not be located
in an area where leakage of the heat
exchanger or connections will result in
damage to the area adjacent to it or to
lower floors of the structure.
When such areas cannot be avoided it is
recommended that a suitable catch pan,
adequately drained, must be installed
under the water heater.
The pan must not restrict combustion air
flow.
A gas fired water heater or any other
appliance should not be installed
in a space where liquids which give off
flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas
(butane or propane), paint or adhesives and
their thinners, solvents or removers.
Because of natural air movement in a room
or other enclosed space, flammable vapors
can be carried some distance from where
their liquids are being used or stored. The
open flame of the water heater’s main
burner can ignite these vapors causing an
explosion or fire which may result in severe
burns, death or property damage.
The water heater must be located so it is not
subject to physical damage, for example, by
moving vehicles, area flooding, etc.
If the water heater is installed in a garage, it
should be installed so that the direct
ignition system and main burner are no less
than 18 inches (45 cm) above the garage
floor.
Raising the gas fired water heater will
reduce BUT NOT eliminate the possibility
of lighting the vapor of any flammable
liquids which may be improperly stored or
accidentally spilled.
● The water heater should be installed as
close as practical to the vent termination
to minimize vent length and the number
of elbows required for venting.
● The water heater should be installed with
the proper venting materials and
termination suitable for Category III
venting.
● Failure to install and properly vent the
water heater to the outdoors as outlined
in the Venting Section of this manual can
result in unsafe operation.
● Long hot water lines should be insulated to
conserve water and energy.
● The water heater and water lines should
be protected from exposure to freezing
temperatures.
● Do not install the water heater in
bathrooms, bedrooms, any occupied
rooms normally kept closed, or in
outdoor areas.
● Do not install the water heater in small,
poorly ventilated rooms, or in air tight
rooms with air-conditioning.
● Do not install water heater where subject
to vibrations.
● Do not install the water heater in
Recreational Vehicles, Mobile Homes,
Boats and other Watercrafts.
● Do not install the water heater near vents
for heating or cooling. A minimum of 4
feet (1.2 m) should be maintained.
● Minimum clearance from combustible
and non-combustible construction is 1/2”
(1.3 cm) sides, 0” rear (with support
bracket); 12” (30 cm) from the bottom;
12” (30 cm) from the front of the water
heater; and 12” (30 cm) from the top
(24” (61 cm) from front and top is
recommended for servicing purposes).
Maintain a minimum clearance of
2” (5 cm) around the vent pipe to
combustible or non-combustible
construction. If the clearances stated on
the Instruction/Warning Label, located
on the front panel of the heater differ,
install the water heater according to the
clearances stated on the label.
7
WARNING: Combustible
construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.
Minimum Clearance from
Combustible and
Non-Combustible
Construction.
WARNING: Follow vent
manufacturers
instructionwhile installing
vent. If required, provide
additional clearances from
vent to combustibles per
vent manufacturers
instruction.
!
min.
1/2 "
(1.3 cm)
Top = 12"(30 cm)
Vent = 2"
Front = 12"(30 cm)
* (with support bracket)
!
min. 2"
(5 cm)
min. 2"
(5 cm)(5 cm)
min. 12"
(24" (60 cm) minimum is
recommended for service)
Back = 0" *
Side = 1/2"
Bottom = 12"
2" (5 cm) min
min.
1/2 "
(1.3 cm)
(30 cm)
(1.3 cm)
(30 cm)
3" (8 cm) min
2" (5 cm) min
Vent Pipe

8
Installing the (OUTDOOR) water heater:
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400
North Capitol Street Northwest, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269 as NFPA 54. In Canada, the latest edition of the CSA
B149.1 Natural Gas and Propane Installation, and the Canadian Electrical Code, CSA C22.1 Part 1, in the
absence of local codes.
Location of the OUTDOOR water heater
This water heater is for OUTDOOR
installation ONLY!
This water
heater is an outdoor model
and must be mounted vertically. It
must not be installed indoors or in a
confined space.
The water heater should be installed
close to the most frequently used outlet
and its position chosen with safety and
service in mind.
Make sure people (particular children,
disabled, and elderly) will not touch the
hot water outlet or the flue terminal.
The flue terminal and air inlet must be
clear of obstruction and shrubbery.
The water heater should not be located
in an area where leakage of the heat
exchanger or connections will result in
damage to the area adjacent to it or to
lower floors of the structure.
A gas fired water heater or any other
appliance should not be installed
in a space where liquids which give off
flammable vapors are to be used or stored.
Such liquids include gasoline, LP gas
(butane or propane), paint or adhesives and
their thinners, solvents or removers.
Because of natural air movement in a
room or other enclosed space, flammable
vapors can be carried some distance from
where their liquids are being used or
stored. The open flame of the water
heater’s main burner can ignite these
vapors causing an explosion or fire which
may result in severe burns, death or
property damage.
The water heater must be located so it is
not subject to physical damage, for example,
by moving vehicles, area flooding, etc.
● The water heater should be installed
vertically with the water, gas, and power
connections on the underside pointing
toward the ground.
● Failure to properly install the water
heater outdoors as outlined in this
manual can result in unsafe operation.
● Hot and cold water lines should be
insulated to conserve water and energy.
● The water heater and water lines should
be protected from exposure to freezing
temperatures.
● Do not install water heater where
subject to vibrations.
● Do not install the water heater in
Recreational Vehicles, Mobile Homes,
Boats and other Watercrafts.
● Do not install the water heater near
vents for heating or cooling. A
minimum of 4 feet should be
maintained.
● Minimum clearance from combustible
and noncombustible construction is
1/2” (1.3 cm) sides, 0” rear (with
support bracket); 12” (30 cm) from the
bottom; 12” (30 cm) from the front of
the water heater; and 12” (30 cm) from
the top (24” (61 cm) from front and top
is recommended for servicing
purposes). If the clearances stated on
the Instruction/Warning Label, located
on the front panel of the heater differ,
install the water heater according to the
clearances stated on the label.
WARNING: Combustible
construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.
Minimum Clearance from
Combustible and
Non-Combustible
Construction.
!
min.
1/2 "
(1.3 cm)
Top = 12" (30 cm)
Front = 12" (30 cm)
Back = 0" (with support bracket)
Side = 1/2" (1.3 cm)
Bottom = 12" (30 cm)
(1.3 cm)
min. 12" (30 cm)
(24" (61 cm) minimum is
recommended for service)
min.
1/2 "

Installing the water heater:
Proper operation of the water heater requires air for combustion and ventilation. Provisions for
combustion and ventilation air must comply with referenced codes and standards.
Combustion and Ventilation Air (Indoor Water Heater Only)
NOTICE: If the water heater is installed in
an unconfined space within a building of
conventional frame, masonry or metal
construction, infiltration air is normally
adequate for proper combustion and
ventilation. If the water heater is installed in
a confined space, provisions for combustion
and ventilation air must be made.
A confined space is one having a volume
of less than 50 cubic feet (1.4 cubic
meters) per 1000 Btuh of the aggregate
input of all appliances within that space.
The air must be supplied through two
permanent openings of equal area. One
is to be located within 12” (30 cm) above
the floor and the other is to be located
within 12” (30 cm) below the ceiling.
The minimum net free area of each opening
must not be less than one square inch (6.5
sq cm) per 1000 Btuh of the total input
rating of all the appliances in the
enclosure (but not less than 100 square
inches (650 cm2),) if each opening
communicates with other unconfined areas
inside the building.
Buildings of unusually tight construction
shall have the combustion and ventilation
air supplied from outdoors, or a freely
ventilated attic or crawl space.
If air is supplied from outdoors, directly or
through vertical ducts, there must be two
openings located as specified above and
each must have a minimum net free area
of not less than one square inch
(6.5 sq cm) per 4000 Btuh of the total
input rating of all the appliances in the
enclosure.
If horizontal ducts are used to
communicate with the outdoors, each
opening must have a minimum net free
area of not less than one square inch
(6.5 sq cm) per 2000 Btuh of the total
input rating of all the appliances in the
enclosure. If ducts are used, the minimum
dimensions of rectangular air ducts shall
not be less than 3” (7.6 cm).
NOTICE: If the duct openings which supply
combustion and ventilation air are to be
covered with a protective screen or grill, the
net free area (openings in the material) of
the covering material must be used in
determining the size of the openings.
Protective screening for the openings MUST
NOT be smaller than 1/4” (0.64 cm) mesh to
prevent clogging by lint or other debris.
Corrosive Atmospheres
The air in beauty shops, dry cleaning
establishments, photo processing labs,
and storage areas for liquid and powdered
bleaches or swimming pool chemicals
often contain such halogenated
hydrocarbons.
An air supply containing halogenated
hydrocarbons may be safe to breathe,
but when it passes through a gas flame
corrosive elements are released that
will shorten the life of any gas burning
appliance.
Propellants from common spray cans or
gas leaks from A/C and refrigeration
equipment are highly corrosive after
passing through a flame.
The water heater warranty is voided when
failure of the heater is due to operation in
a corrosive atmosphere.
NOTICE: The water heater
should not be installed near
an air supply containing
halogenated hydrocarbons.
Inspect Shipment
Inspect the water heater for possible damage. Check the markings on the rating plate of
the water heater to be certain the type of gas supplied corresponds to the water heater
requirements. Verify all included parts are present (see below).
DANGER: OUTDOOR
water heaters must not
be installed indoors or
in a confined space.
Install outdoor water
heaters outdoors only.
9
Air Openings
Min. 200 Sq. In.
2
)
(1290 cm
Min. 3" (7.6 cm)
PRIORITY
°F
POWER
ON/OFF
Wood Screw x 5pcs.
foetacifitreC
detimiL
ytnarraW
®
AICREMMOC
SRETAEHRETAW
SSELKNATLAICREMMOC
SRETAEHRETAWSAG
DNAREGNAHCXETAEHRAEY3AHTIW
YTNARRAWDETIMILSTRAPRAEY1
)50/30(1-78431PA
Warranty
Remote Control
Assembly Kit
Washer x 4 pcs.
Use & Care Manual
With Installation Instructions for the Installer
Residential Gas
Tankless
Water Heaters
Warning: This waterheateris not suitable for
use in manufactured (mobile) homes!
The purpose of this manual is twofold: one, to provide the installerwith
the basic directions and recommendations forthe properinstallation and
adjustment of the waterheater; and two, to the owner–operator, to
explain the features, operation, safety precautions, maintenance and
troubleshooting of the waterheater. This manual also includes a parts
list.
It is imperative that all persons who are expected to install, operate or
adjust this waterheaterread the instructions carefully so they may
understand how to perform these operations. If you don’t understand
these instructions orany terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or
warranty of this waterheatershould be directed to the sellerfrom whom
it was purchased. If additional information is required, referto the
section on How to Obtain Service Assistance.
Do not destroy this manual. Please read carefully and keep in a safe
place forfuture reference.
Recognize this symbol as an indication of Important Safety
!
Information!
California Proposition 65 Warning:This product contains
!
chemicals known to the State of California to cause cancer, birth
defects orotherreproductive harm.
WARNING: If the information in these instructions is not followed exactly,
!
a fire orexplosion may result causing property damage, personal injury ordeath.
!
FOR YOUR SAFETY!
● If you cannot reach yourgas supplier, call
—Do not store or use gasoline or other
the fire department.
flammable vapors or liquids or other
combustible materials in the vicinity of this or
● Do not return to yourhome until authorized
any otherappliance. To do so may result in an
by the gas supplierorfire department.
explosion orfire.
—Improperinstallation, adjustment,
alteration, service ormaintenance can cause
—WHATTO DO IFYOU SMELL GAS
property damage, personal injury, ordeath .
●Do not try to light any appliance.
Referto this manual. Installation and service
● Do not touch any electrical switch; do not
must be performed by a qualified installer,
use any phone in yourbuilding.
service agency orthe gas supplier.
● Immediately call yourgas supplierfrom a
neighbor’s phone. Follow the gas
supplier’s instructions.
I
S
G
E
N
D
Printed in USA
Tankless Unit
C
E
D
R
E
I
T
F
I
®
Use & Care Manual
Manual Appliance
Gas Shut-off Valve

10
Water Supply Connections
IMPORTANT: Do not
apply heat to the HOT or
COLD water connections. If
sweat connections are used,
sweat tubing to adapter
before fitting adapter to the
water connections on
heater. Any heat applied to
the water supply fittings
will permanently damage
the internal components of
the water heater.
Mounting the Water Heater
Make sure the location of the appliance
allows for easy access and operation.
Wall studs should be utilized when
mounting the water heater to the wall.
Alternately, a suitable piece of wood may
be placed inside or outside of the wall to
span the distance between the wall studs.
Fasten the water heater mounting brackets
to the wood.
In case of dry wall or concrete wall use
dry wall anchors or lag bolts.
The water heater requires 120VAC/60Hz.
Have a receptacle with ground terminal
near the water heater. The length of the
power supply cord is 10 feet (3 m),
(Indoor water heater only.)
Install a wood screw for the upper bracket
with a clearance of 1/8” (.32 cm) between
the wall and the screw head. Hang the
center of the upper bracket on the screw.
Using a wood screw and a washer, affix
the lower bracket to the wall (Left and
Right). Repeat to affix the top bracket.
The brackets can be adjusted to change
the distance between the back of the
appliance and the wall within the range of
3/8” (.95 cm) to 1½” (3.8 cm).
Loosen the adjustment screws of both the
top and the bottom brackets to adjust the
distance. (See diagram below)
Plumbing should be carried out by a
qualified plumber in accordance with local
codes.
Use approved plumbing materials only.
The diameter of the pipe lines should be a
minimum of 3/4”.
To conserve energy and to prevent
freezing, insulate both cold and hot water
supply lines. DO NOT cover the drain or
pressure relief valve.
To ensure proper operation of the water
heater, the following water pressure
guidelines should be followed:
● Operation of the water heater requires
the minimum water pressure of 14 psi
(97 kPa) and a minimum water flow
rate of 0.66 gpm (2.5 lpm).
● A water pressure of 40 psi (276 kPa) is
required to achieve maximum flow rate.
● To maintain proper performance, ensure
sufficient water supply pressure. The
Required Water Pressure = Min.
Operating Water Pressure
(14 psi) (97 kPa) + Pipe Pressure Loss
+ Faucet and Shower Pressure Loss +
Safety Margin (more than 5 psi)
(34 kPa).
● To supply hot water to upper floors,
additional water pressure (0.44 psi/ft)
(10 kPa/m) must be ensured. The
measurement should be calculated by
the distance between the water inlet of
the water heater (ground level) to the
hot water faucet (upper floor level).
● Well water systems should be set to
ensure a minimum system pressure of
40 psi (276 kPa).
● When the water is supplied from a
water supply tank, the height of the
tank and the diameter of the pipes and
their relation to water pressure, should
be taken into consideration. Gravity
water pressure is not recommended.
Notice: If the water flow resistance of a
shower head is too high, the burner in the
water heater will fail to ignite. Keep the
shower head clean from debris that could
cause additional pressure drop.
Notice: If using mixing valves on the
outlet, choose one which prevents cold
water pressure from overcoming hot water
line pressure.
Notice: If multiple water heaters are
installed in a manifold system, the
water piping must be in “Parallel”. A
water pressure of 40 psi (276 kPa) is
recommended for each water heater for
proper operation of the water heaters.
CAUTION: This water
heater must only be used
with the following water
supply system conditions:
● With clean, potable water
free of corrosive
chemicals, sand, dirt, or
other contaminates.
● With inlet water
temperatures above
32°F (0°C), but not
exceeding 140°F (60°C).
● Free of lime and scale
deposits.
● DO NOT reverse the hot
and cold water
connections. The water
heater will not operate.
CAUTION:
Reinforcement of the wall is
required in case the wall is
not strong enough to hold
the appliance.
Upper Bracket
Washer
Wood Screw
Washer
Wood Screw
Lower Bracket
1/8" (.32 cm)
Clearance
Wood Screw
Washer
TOP
Adjustment Screws
Bracket
Bracket
Adjustment Screws
BOTTOM

Installing the water heater:
Relief Valve
A new pressure relief valve, complying
with the Standard for Relief Valves and
Automatic Gas Shut-Off Devices for Hot
Water Supply Systems, ANSI Z21.22/
CSA 4.4, must be installed at the hot
water outlet connection of the water
heater at the time of installation. Local
codes shall govern the installation of
relief valves.
For safe operation of the water heater, be
sure that:
● The pressure rating of the relief valve
must not exceed 150 psi (1034 kPa), the
maximum working pressure of the
water heater as marked on the rating
plate.
● The BTUH rating of the relief valve
must equal or exceed the BTUH input
of the water heater as marked on its
rating plate.
● No valve of any type should be
installed between the relief valve and
the water heater
● Discharge from the relief valve should
be piped to a suitable drain to eliminate
potential water damage. Piping used
should be of a type approved for the
distribution of hot water.
● Hot and cold water lines should be
insulated up to the water heater. Refer
to page 24 for details.
● The discharge line must be NO
SMALLER than the outlet of the relief
valve and must pitch downward to
allow complete drainage (by gravity) of
the relief valve and discharge line.
● The end of the discharge line should not
be threaded or concealed and should be
protected from freezing. No valve of
any type, restriction or reducer coupling
should be installed in the discharge line.
Notice: Local codes govern the
installation of relief valves. If local codes
require that a temperature and pressure
relief valve should be installed the
manufacturer recommends a type 40XL
Watts T&P relief valve or an equivalent
model be used.
Notice: Manual operation of relief valves
should be performed at least once a year.
Turn off the electrical power and gas
shutoff valve. Lift and release lever on the
relief valve and check the manual
operation of the relief valve. You should
take precaution to avoid contact with the
hot water coming out of the relief valve
and to prevent water damage.
Notice: If the relief valve on the system
discharges periodically, a problem exists
and service to the water system is
required.
Water Supply Connections Continued
Install a shutoff valve near the inlet of the
water heater for service and draining
purposes.
It is not recommended to use pipes with
smaller diameters than the water supply
connection of the water heater.
Before connecting the water supply pipe
to the water heater, open the shutoff valve
and clean out sand, debris, air, caulking
material, etc. inside the pipe. Connect to
the water inlet, then check water flow.
Close the shutoff valve and clean the
water filter.
Be sure to connect the water inlet and the
hot water outlet as shown on the water
heater. If reversed, the water heater will
not function.
Installation of unions or flexible copper
connections are recommended on the
HOT and COLD water lines, so that the
water heater may disconnect easily for
servicing if necessary.
Install a Check Valve between the water
heater and the water shutoff valve. (See
illustration the top left).
The following should be addressed in
regards to the HOT WATER OUTLET:
● Connections between the water heater
and point(s) of use should be as short
and direct as possible.
● DO NOT use lead or plastic pipe.
● To conserve energy and minimize heat
loss, insulation of hot water piping is
recommended. (See Hot and Cold Pipe
Insulation Installation on page 24).
Notice: The flow rate of hot water may
vary when more than two faucets
(appliances, fixtures, etc.) are being used
simultaneously.
Notice: The pipes MUST be completely
drainable. If the hot water faucets are
located at a point higher than the water
heater, place a drain valve at the lowest
point (see diagram to the left).
Union
Pressure
Relief Valve
Water
Shutoff
Valve
Cold
Water
Supply
Inlet
Hot Water
Supply
Outlet
Relief
Valve
Discharge
Line
Notice: The above illustrates a
pressure only relief valve. If local
codes require a combination
temperature and pressure relief
valve be installed, an extension
piece may be needed. (Refer to
page 22 or 23 for example of
extension piece for T&P relief
valve installation.) The T&P relief
valve probe should not be directly
in the flow path of the water.
Notice: Use only teflon tape on cold
and hot water connections and
lines.
11
Water Filter
Clean the
Water Filter
Water Inlet
Check Valve
Nipple
Air
Relief
Va lv e
Drain Valve
Wat er
Hot
Water
Tap

12
WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type
shown on the rating plate. Such conversion could result in hazardous operating conditions.
Leak Testing
The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.
Turn on the gas shut-off valve(s) to
the water heater.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.
The factory connections should also be
leak tested after the water heater is placed
in operation.
High Altitude
Input rating of this water heater is
based on sea level operation. At
higher elevations the actual input
rate may be lower than the value listed on the rating label. This water
heater can be installed at elevations
up to 3,280 feet (1000 m)without any
change or modification.
NOTICE:
Select models may be available preset
for operations at elevations up to 6,560
feet (2000 m).
NOTICE: For installations above
3,280 feet (1000 m) elevation, the
connector on the PC board must be
replaced. Do not install this water
heater at elevations above 3,280 feet
(1000 m) without installing the proper
high altitude connector. Please contact
your local distributor, dealer, or Rheem
for replacement connector.
Pressure Testing the Gas Supply System
The water heater and its manual gas shutoff valve must be disconnected
from the
gas supply piping system during any
pressure testing of the system at
pressures in excess of 1/2 psi (14” w.c.)
(3.5 kPa).
The water heater must be isolated
from
the gas piping system by closing the
manual gas shut-off valve during any
pressure testing of the gas supply piping at
pressures equal to or less than
1/2 psi (14” w.c.) (3.5 kPa).
Gas Supply
The supplied Manual Gas Appliance
Shutoff Valve must be installed at the gas
connection of the water heater at the time
of installation (see diagram to the left).
The branch gas supply line to the water
heater should be a minimum of 3/4” black
steel pipe or other approved gas piping
material.
A ground joint union or ANSI design
certified semi-rigid or flexible gas
appliance connector should be installed in
the gas line close to the water heater. The
National Fuel Gas Code (NFGC) ANSI
Z223.1 and CAN B149 code mandates a
manual gas shut-off valve: See NFGC &
B149 for complete instructions.
If flexible connectors are used, the
maximum length shall not exceed
36” (91 cm).
If lever type gas shut offs are used, they
shall be T-Handle type.
Compound used on the threaded joints of
the gas piping must be of the type
resistant to the action of LP gas. Use
compound sparingly on male threads only.
A sediment trap should be installed at the
bottom of the gas line.
Do not use excessive force
(over 31.5 ft lbs.) (42.7 Nm) in tightening
the pipe, particularly if teflon pipe
compound is used, as the unit may be
damaged.
The inlet gas pressure to the water heater
must not exceed 10.5” w.c. (2.6 kPa) for
natural or 14” w.c. (3.5 kPa) for LP gas.
For purposes of input adjustment, the
minimum inlet gas pressure (with main
burner on) is shown on the water heater
rating plate. If high or low gas pressures
are present, contact your gas supplier for
correction.
NOTICE:
To ensure proper operation
of the heater the gas pipe and gas
meter must be sized correctly.
Gas piping shall be in accordance
with local, utility company requirement and/or in the absence of local
codes, use the latest edition of the
National Fuel Gas Code. In Canada
the latest edition of CSA B149.1 Natural Gas and Propane installation
code.
WARNING: Never use
an open flame to test for
gas leaks, as property
damage, personal injury, or
death could result.
WARNING: Install a
gas pressure regulator, in
the gas supply line, which
does not exceed the
maximum supply pressure.
DO NOT use an industrial
type gas regulator.
Manual Gas
Appliance
Shut-off
(Supplied)
Union
Sediment
Trap
Cap
Manual
Gas
Supply
Line
Shut-off
Va lv e

Installing the water heater:
The water heater must be installed with a RTG20002B vent adapter or a UL approved Category III Stainless
Steel equivalent.
Venting
The installation of venting must comply with
national codes, local codes, and the vent
manufacturer’s instructions.
The water heater must be vented to the
outdoors as described in these instructions.
DO NOT connect this water heater to a
Chimney. It must be vented separately from
all other appliances.
All vent components (adapters, pipe, elbows,
terminals, etc.) should be UL1738 Certified
Stainless Steel Venting Material
(e.g. AL29-4C).
The specified vent termination must be used.
The termination should be a 90° elbow type
with screen. (Refer to page 17)
Use a vent pipe with an anti-disconnection
structure.
The use of a High Temperature Silicone
(500°F) (260°C) may be required to seal vent
connections. To prevent accidental gas
exhaust leakage, apply a 1/4” (6 mm) wide
bead approximately 1/4” (6 mm) from the
end and another bead against the joint side of
the stop bead.
Follow vent manufacturer’s installation
instructions.
The unit can be vented either horizontally or
vertically.
Vent pipe runs must be adequately supported
along both horizontal and vertical runs.
The maximum recommended unsupported
span should be no more than five (5) feet
(1.5 m) Support isolation hanging bands
should be used. DO NOT use wire. (See
diagram below).
Notes on pr
e-existing vent:
If the water heater is being installed as a
replacement for an existing water heater, a
thorough inspection of the existing venting
system must be performed prior to any
installation work. Verify that the correct
materials, vent lengths and terminal locations
as detailed in this Use and Care manual have
been met. Carefully inspect the entire
venting system for any signs of cracks or
fractures, particularly at the joints between
elbows or other fittings and the straight runs
of vent pipe. Check the system for signs of
sagging or other stresses in the joints as a
result of misalignment of any components in
the system. If any of these conditions are
found, they must be corrected in accordance
with the venting instructions in this manual
before completing the installation and
putting the water heater into service.
DANGER: Failure to
install the vent adapter and
properly vent the water
heater to the outdoors as
outlined in the Venting
section of this manual will
result in unsafe operation of
the water heater causing
death, serious injury,
explosion, or fire. To avoid
the risk of fire, explosion,
or asphyxiation from
carbon monoxide, NEVER
operate the water heater
unless it is properly vented
and has adequate air supply
for proper operation as
outlined in the Venting
section of this manual.
WARNING: Use UL
approved Category III
Stainless Steel vent material
only. No other vent
material is permitted.
WARNING: Refer to
page 7 for clearances to
combustible material.
Venting Lengths
MAXIMUM VENT LENGTH - The
system will not operate if there is excessive
restriction (pressure drop) in the venting
system. A maximum of 47 feet 6 inches
(14.4 m)
of vent pipe may be used provided
there is only one 90° elbow in the system. If
additional elbows are required: two elbows
can be used with 42 feet 6 inches
(13 m)
,
and three elbows can be used with 37 feet 6
inches
(11.4 m)
of vent pipe.
A 90° elbow is equivalent to 5 feet
(1.5 m)
to straight pipe. A 45° elbow is equivalent to
2 feet 6 inches
(76 cm)
of straight pipe.
The termination elbow does not count as an
elbow when determining total vent lengths.
The vent can be installed with a slight
downward slope of 1/4” per foot of
horizontal run toward the vent terminal (see
diagram below). This ensures that any
condensate formed during operation of the
unit is evacuated from the appliance.
A 1/4” per foot upward slope is acceptable
when it is not possible to vent with a
downward slope, however, a UL approved
Category III Stainless Steel condensate trap
MUST be installed at the beginning of the
horizontal run (See page 17 “Typical
Horizontal Termination
w/ 1/4” per foot UPWARD Slope” or
page 18, “Standard Vertical Vent
Termination” for examples).
MINIMUM VENT LENGTH - The
venting may be as short as 12” (30 cm),
provided one vent termination is installed to
the outdoors through a sidewall, one 90°
elbow is included in the installation, and the
wall thimble is installed.
Notice: Make sure that the seam of the vent
pipe in horizontal runs is toward the top of
the installation (see illustration to the far
left).
13
Number of
90° elbows
(bends)
Maximum
Length of
Straight Pipe
1
2
3
47’ 6”
(14.4 m)
42’ 6”
(13 m)
37’ 6”
(11.4 m)
NO! YES!
Vent Seam
Max. 3 feet (91 cm)
1/4" per foot
downward slope.
Min. 3"
(8 cm)

14
Venting Through Closed Spaces
If the vent piping passes through a closed space, a minimum
clearance of 8” (20 cm) when installed horizontally, 6”
(15 cm)
when installed vertically should be maintained between the vent
pipe and combustibles and noncombustibles. Be sure to follow
local codes.
For maintenance and inspection purposes, the following access
panels are required.
● Two (2) inspection access panels large enough to allow
access for venting inspection. One (1) of these access
panels should be close to where the vent pipe enters the
ceiling. The other access panel should be near the vent
termination.
● A ventilation access panel with a 16 in2(103 cm2) opening
should be provided every 10 ft (3 m).
1/4” per foot
Vent Adapter
A UL 1738 approved stainless steel vent
adapter is required for vent connection.
Read the following instructions before
installation.
● Test fit the adapter over the water
heater collar before proceeding. Adjust
clamp as needed.
● With an alcohol wipe, clean inside
surface "A" of adapter and outside
surface of "B" of heater collar.
● Apply 1/4" (6 mm) wide bead of high
temperature silicone (500°F) (260°C)
around outside of heater collar "B".
● Slide adapter end "A" down over heater
collar "B" as far as it will go.
● Tighten the clamp around the collar.
● Inspect the inside of the adapter to
verify that the collar and adapter are
sealed. If more sealant is required,
apply sealant to a flat tool, then spread
around the collar edge on inside
of
adapter.
● Ensure that the clamp does not interfere
with the damper shaft.
NOTICE: Follow the vent adapter
manufacturer’s instructions
Draining the Condensate
In order to prevent condensate from
draining back into the water heater, a
condensate trap and drain must be
installed in a horizontal vent section as
close as practical to the water heater vent
connection, uless the water heater is
vented horizontally with a 1/4” per foot
DOWNWARD slope towards the vent
terminal as shown below.
Condensate is known to be acidic; refer to
local, state (provincial) or federal codes
for proper handling and discharge
methods.
downward slope
Exhaust
High Temp.
Sealant
Water Heater
Inspection
Access Panel #1
Flow
A
B
Wall Thimble
Vent Pipe
Ceiling
Board
Inspection
Access Panel#2
Vent Adapter
RTG20002B
Clamp
Collar
1/4” per foot downward slope
3” (8 cm) Clearance
3’
(91 cm)
Max
Ve nt
Adapter
Support
Hanger

The following information should be used for determining the proper location of the vent terminal
for indoor and outdoor tankless water heaters.
Canadian Installations
1
US Installations
2
Canadian Installations
1
US Installations
2
V
VENT TERMINAL
X
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
1 In accordance with current CAN/CGA-B149 Installation Codes.
2 In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.
+ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and
serves both dwellings.
* If clearances are not specified then follow local installation codes and the requirement of the gas supplier.
Installing the water heater.
Horizontal Vent Terminal Location
H = Clearance to each side of center line
extended meter/regulator assembly.
above
3 feet (91 cm) within a height 15 feet
(4.57 m) above the meter/regulator
assembly.
*
I = Clearance to service regulator vent
outlet.
3 feet (91 cm)
*
J = Clearance to nonmechanical air
supply inlet to the combustion air
inlet to any building or other
appliance.
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (30 cm) for
appliances > 10,000 Btuh (30kW), 36
inches (91 cm) for appliances > 100,000
Btuh (30kW).
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above opening.
K = Clearance to mechanical air supply
inlet.
6 feet (1.83 m) 3 feet (91 cm) above if within 10 feet (3
m) horizontally.
L = Clearance above paved side walk or
paved driveway located on public
property.
7 feet (2.13 m) 7 feet (2.13 m)
M = Clearance under veranda, porch,
deck or balcony.
Not Allowed Not Allowed
A= Clearance above grade, veranda,
porch, deck or balcony.
12 inches (30 cm) above anticipated
snow level.
12 inches (30 cm) above anticipated
snow level.
B= Clearance to window or door that
may be opened.
6 inches (15 cm) for appliances < 10,000
Btuh (3 kW), 12 inches (30 cm) for
appliances > 10,000 Btuh (30 cm) for
appliances > 10,000 Btuh (30kW), 36
inches (91 cm) for appliances > 100,000
Btuh (30kW).
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above opening.
C= Clearance to permanently closed
window.
* *
D= Vertical Clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
4 feet (1.2 m) 4 feet (1.2 m)
E= Clearance to unventilated soffit. * *
F= Clearance to outside corner. * *
G= Clearance to inside corner. * *
M = Clearance under veranda, porch,
deck or balcony.
3 feet (91 cm) 3 feet (91 cm)
D
E
V
B
V
L
F
G
v
A
C
FIXED
v
OS
CL
E
P
O
v
B
B
ED
B
LE
RAB
B
FIXE
S
LE
CLO
B
RA
E
P
O
v
v
J
B
A
H
X
D
v
ED
X
I
v
K
M

16
Installing the water heater:
Additional Considerations
Do Not install vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building
with prevailing winter winds.
To help prevent water lines from freezing do not locate vent
terminal on the side of a building with prevailing winter
winds.
Do Not terminate vent directly on brick or masonry surfaces.
A rust-resistant sheet metal backing plate
(2 x 2 feet) (60 x 60 cm) is recommended behind vent. (See
illustration.)
Do Not locate vent terminal too close to shrubbery, as flue
gasses may damage them.
Caulk all cracks, seams and joints within six (6) feet (1.8 m)
of vent terminal.
Caulk around thimble face plate for weather tight seal.
All painted surfaces should be primed to lessen the chance of
physical damage. Painted surfaces will require maintenance.
Insulate vent pipe of indoor water heaters exposed to cold
conditions (attics, crawl spaces, etc.) with inflammable
material to help prevent moisture from accumulating in vent
pipe.
Do Not extend exposed vent pipe of indoor water heaters
outside of building.
Guard vent against accidental contact with people and pets.
WARNING: Moisture in the flue gas will condense as it
leaves the vent terminal. In cold weather this condensate can
freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration to the exterior of
the building is to be expected. However, improper location
or installation can result in severe damage to the structure
or exterior finish of the building
Outdoor Water Heater
Indoor Water Heater
Inside
Corner
Caulk
6’ (1.8 m)
Caulk Zone
If soffit vent is too close,
block off and install new
vent at another location.
Caulk
Caulk
Rising moisture will
collect under eaves.
6’
4’
2 ft. sq. (60 x 60 cm) sheet metal plate on
brick or masonary surface, recommended.
(1.8 m)
6’ (1.8 m)
Caulk
zone or to edge of window
etc.,starting within 6’ (1.8 m).
RTV silicone caulk
(1.2 m)
Caulk
If soffit vent is too close,
block off and install new
vent at another location
Inside
corner
6' (1.8 m) caulk
zone
Caulk
4'
(1.2 m)
Rising moisture will collect under eaves
(1.8 m)
6'
6' (1.8 m)
caulk zone or
to edge of
window etc., starting
within 6' (1.8 m)
Caulk

17
Vent Horizontal Wall Thimble Installation
An approved 4 inch (10 cm) Vent
Horizontal Wall Thimble must be used.
The Wall Thimble requires mechanical
support from the wall sufficient to support
any incidental loads on the system. If the
wall is not sufficient enough to support the
Wall Thimble, then appropriate additional
framing and/or blocking is required.
INSTALLATION PROCEDURE:
Prepare an opening for the Wall Thimble
in the wall. The opening must be
6-1/2 inches (16 cm) in diameter for a
4 inch (10 cm) vent system.
If there are not sufficient support members
to secure the Wall Thimble or if there is a
semirigid foam insulation layer under the
sheathing, appropriate fasteners must be
used to secure the Wall Thimble to the
support members.
The Wall Thimble is designed to adapt to
any wall thickness from 3-1/2” (9 cm) to
6” (15 cm) thick. If the wall is thicker
than 6” (15 cm) the Wall Thimble may be
extended using a piece of 6” (15 cm)
diameter snaplock or welded seam
galvanized pipe up to 6” (15 cm) long.
Select the larger diameter half of the Wall
Thimble for the outside of the wall.
● Apply a continuous bead of high
quality silicone or silicone/latex caulk
on the inside of the outer flange. This
will be the only weather seal to keep
moisture outside the building. Ensure a
sufficient seal is made.
● Position this portion of the Wall
Thimble into the prepared hole from the
outside. Secure the assembly into the
prepared opening using fasteners as
indicated by sheathing or structural
members, sealing the screw heads with
more caulking.
Use 4 hollow wall anchors, at least
1/8” (.32 cm) in diameter and of
appropriate length for the thickness of
the sheathing, if sheathing is particle
board or other composite material. Use
4 #10x1-1/4” wood screws for plywood,
solid wood sheathing or members. Use
suitable masonry anchors when passing
through solid masonry walls. Reinstall
the decorative sheathing around the
Wall Thimble. This assembly may be
painted to match the exterior decor.
● Attach a screened 4 inch (10 cm)
termination fitting to the female end of
a vent section or slip connector. Use the
method described in the Venting
installation instructions (page 13). Slide
the vent in through the outside of the
Thimble and seal the annular space
with a thick bead of caulk.
● Slide the interior portion of the Thimble
into the inside hole. Be certain the
interior and exterior Thimble halves
overlap at least 1” (2.5 cm). If
insufficient overlap exists, extend the
interior portion with single wall
galvanized pipe.
● Secure the Wall Thimble to the interior
sheathing using suitable fasteners.
● Secure the vent section or slip
connector that protrudes through the
Wall Thimble to the rest of the vent
system as described in the Venting
installation instructions (page 13).
Inner Thimble
Side View
Side View
WARNING: Use UL
approved Category III vent
material only. No other
vent material is permitted.
CAUTION: Follow the
vent manufacturers
installation instructions as
design might vary from
manufacturer to
manufacturer.
Typical Horizontal Termination
w/ ¼” per foot DOWNWARD Slope
Typical Horizontal Termination
w/ ¼” per foot UPWARD Slope
Section
Inner Wall
Inner Thimble
Section
90° Elbow
Mounting
Brackets
Wat er
Heater
Vent
Pipe
Outer
Wal l
Outside Wall
weather seal
1/4” per foot downward slope
3” (8 cm) Clearance
Outer Thimble
Section
Outer Thimble
Section
90° terminatio
with screen
Caulk for
1/4” per foot upward slope
3” (8 cm) Clearance
3’
(91 cm)
Max
Vent
Adapter
Support
Hanger
3’
(91 cm)
Max
Vent
Adapter
Condensate
Trap
Support
Hanger
To Drain. Dispose of
condensate in accordance
to local codes

18
Installing the water heater.
Vertical Vent Installation
Once the vent terminal location has been
determined, make a hole through the roof
and interior ceiling to accommodate the
vent pipe. Complete the vent pipe
installation to the water heater's vent
connector fitting on the water heater vent
collar outlet. Support vertical or horizontal
runs as previously mentioned. If required,
use silicone sealant at the point the vent
connector joins the water heater.
Install adequate flashing where the vent
pipe passes through the roof. Determine
the vent terminal height and install the
vent pipe accordingly. Refer to the
illustration above for proper vent terminal
height. Connect vent elbow on to vertical
pipe through roof. Connect short piece of
vent pipe (approximately 6" long (15 cm))
to elbow, and the terminal elbow with the
protective screen.
Standard Vertical Vent Termination
Alternate
Vertical Vent Termination with Rain Cap
Vertical Vent Termination Location
The location of the vent terminal depends on the following
minimum clearances and considerations (see illustration):
Minimum twelve (12) inches
(30 cm)
above roof.
Minimum twelve (12) inches
(30 cm)
above
anticipated snow level.
Maximum twenty-four (24) inches
(60 cm)
above
roof level without additional support for vent.
Four (4) feet
(1 m)
from any gable, dormer or other
roof structure with building interior access (i.e., vent,
window, etc.).
Ten (10) feet
(3 m)
from any forced air inlet to the
building. Any fresh or make-up air inlet such as a
dryer or furnace area is considered to be a forced air
inlet.
Min. 12"
(30 cm)
Above Roof
Min. 12"
(30 cm)
Above Anticipated
Snow Level.
Max. 24"
(60 cm)
Above Roof (Without
Additional Support)
Vent Pipe
Through Roof
Elbow
Termination Elbow
w/ Protective Screen
Small (6” min)
(15 cm)
section of vent
Chase Requires
6” (15 cm) Clearance
to Combustibles
1/4” per foot upward slope
3” (8 cm) Clearance
3’
(91 cm)
Max
Roof Jack
Vent
Adapter
Storm
Collar
Adjustable
Roof Flashing
Support
Clamp
Support
Condensate
Hanger
Trap
To Drain. Dispose of
condensate in accordance
to local codes
Firestop
Firestop
Storm
Collar
Roof Jack
Support
Clamp
Chase Requires
6” (15 cm) Clearance
to Combustibles
1/4” per foot upward slope
3” (8 cm) Clearance
3’
(91 cm)
Max
Condensate
Trap
To Drain. Dispose of
condensate in accordance
Vent
Adapter
to local codes
Rain Cap
Adjustable
Roof Flashing
Firestop
Firestop
Support
Hanger

19
Remote Control Installation
One (1) remote control is provided with
the water heater.
The following are considerations for
determining the location of the remote
control(s):
●
DO NOT install any remote control
outdoors or areas were it can come in
contact with water.
●
Place remote control out of children’s reach.
●
The remote control can be installed in
convenient locations such as the kitchen,
laundry room, utility room, or directly beside
the indoor water heater.
●
Avoid areas where the remote control
may be exposed to heat, e.g. stove
ranges or heaters.
●
Avoid areas where the remote control
may be subjected to oil and/or steam
from cooking.
●
Avoid areas where chemical agents
(such as thinner, benzine and alkaline)
are used.
●
Avoid areas of direct sunlight.
●
The MAXIMUM distance between the
water heater and the remote control
installation location is limited to 195
feet (59 m) of wire.
NOTICE: Only main remote control
(UMC-117) and manifolding control can
be connected to the water heater.
No other manufacturer’s controls are
suitable for use with this water heater.
DO NOT attempt to disassemble the
remote control.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
Remote Control
Model Number
Remote Control
Description
Temperature
Set Point Range
Availability
UMC-117 MAIN
100°F - 120°F
(38°C)-(49°C)
Factory Default
125°F - 180°F
(52°C)-(82°C)
With Dip Switch
Adjustment
NOTICE: The provided
remote control will allow
a maximum temperature
setting of 120°F (49°C).
Temperatures of up to
180°F (82°C) can be
achieved with dip switch
adjustment. Only qualified
service personnel should
perform this adjustment.
NOTICE:
Manifolding Applications: Certain Commercial installations may require more than
one water heater piped together in a manifold to supply enough capacity for high
temperature and/or water flow applications. Special manifolding control kits are
available for operating multiple heaters together. Contact your dealer for details.
MAIN
Control
Base Plate
PRIORITY
°F
POWER
ON/OFF
Mounting Screw x 2
Control screw

20
Installing the Main Remote Control.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
NOTICE: Extension cable
can be any Type-T 18 AWG
wire similar to a thermostat
wire and need not be
polarity sensitive.
Do Not apply sealant to the
remote control cable.
It is not recommended to
have wiring exposed.
Remote Control Installation
Connecting the MAIN (UMC-117 )
remote control to the water heater:
●
Drill a 1” (2.5 cm) to 1.5” (4 cm) hole
at the proposed control location.
●
Install the extension cable between the
location of the remote control and the
water heater.
●
Remove the base plate from the control.
●
Draw the remote control extension
cable through the central in the base
plate.
●
Fix the base plate to the wall using
suitable screws and wall anchors.
Ensure the projections on the base plate
are pointing upwards.
●
Connect the remote control cables to
the extension cable from the water
heater.
●
Place the remote control over the base
plate. Ensure the projections in the
base plate fit into the housings in the
remote control.
●
Fix the control to the base plate at the
bottom of the remote control using the
screw provided.
●
Proceed to “Connecting the remote
control to the water heater”, to
complete installation.
Connecting the remote control to the
water heater:
●
Ensure that the power to the water
heater has been disconnected.
●
Remove the front cover of the water
heater.
●
Insert the remote control extension
cable throught the hole at the bottom
right hand corner of the water heater.
●
Connect the wires to the terminals on
the top right hand side of the Printed
Circuit Board (PCB) as shown in
illustration to the left.
NOTICE: The remote control wire
connection terminals are not polarity
sensitive.
●
Firmly tighten the terminal screws.
●
Secure the remote control extension
cable using the appropriate clamp.
●
Replace the front cover of the water
heater.
●
Switch on the power supply to the
water heater.
●
Ensure proper operation of the remote
control and water heater.
NOTICE: If water heaters are in a
manifold system the main remote control
connected to the mainfold controller
(MIC-180) has priority over remote controls
connected to the water heaters.
Remote Control
Connection Terminals
Clamp
Gas Valve
PCB
18 AWG
Extension
Cable
Remote
Control
Control
Screw
Extension
Cable
Projections
Wall
Penetration
Suitable
Wall Anchors
Base Plate
Screws

21
Electrical Connection
POWER CORD (Indoor water heaters
only):
● The electric power supply requirement
for this water heater is 120 VAC/60HZ,
2 Amps.
● The water heater comes with a three (3)
pin power supply cord (INDOOR
MODELS ONLY). Use only a power
outlet with a ground terminal.
● The installation of an electric leakage
breaker is recommended.
● Keep any excess of the power supply
cord on the outside
of the water heater.
● If local codes require hardwiring, see
instructions for “Hardwiring the
Electrical Connections”.
HARDWIRING THE ELECTRICAL
CONNECTIONS (Indoor or Outdoor
water heaters):
● Wiring should be carried out by a
qualified electrician in accordance with
local codes.
● The water heater requires 120 VAC/60Hz
and should be properly grounded.
● DO NOT connect grounding wire to
water pipes, gas pipes, telephone
cables, lightning conductor circuits and
to grounding circuit of other equipment
that carry a ground-fault interrupter.
● An ON/OFF switch must be provided
and installed for the incoming
120VAC power.
● Wire the water heater exactly as shown
below. A wiring diagram is also found
inside of the cover panel.
● A green screw is provided in the
junction box for grounding connection.
● Connect the live wire to black leg wire
and the neutral wire to the white neutral
wire.
WARNING: Shock
hazard line voltage is
present. Before servicing
the water heater, turn off
the electrical power to the
water heater at the main
disconnect or circuit
breaker. Failure to do so
could result in severe
personal injury or death.
CAUTION: Label all
wires prior to
disconnection when
servicing controls. Wiring
errors can cause improper
and dangerous operation.
Verify correct operation
after servicing.
WARNING: Field wiring connections and electrical grounding must comply with local
codes, or in the absence of local codes, with the latest edition of the National Electrical Code,
ANSI/NFPA 70, or in Canada, Canadian Electrical Code, CSA C22.1 Part 1.
WIRING DIAGRAM
SW2
SW1
MAX
MIN
BUTTON
BUTTON
SW3
ADJUSTER
1
BK
SV3 SV2
S
S
O
O
V
L
L
A
E
E
L
N
N
V
O
O
E
I
D
D
3
234
DIP SWITCH
W
R
B
W
W
R
BK
BR
G/Y
BK
BK
SV1
S
O
V
L
V
A
E
A
L
N
L
V
O
V
E
I
E
I
D
1
2
BUTTON
FLAME ROD1
FLAME ROD2
FLAME ROD3
OVER HEAT
LIMITER
WAT E R
FLOW
SENSOR
GND
WATER VOLUME
CONTROL MOTOR
LIMITER
B8RGRY B OWBR
ON
A
OFF
M
T
L
B
LED
MOTOR
BK
R
GR
Y
B
O
W
BR
8
7
6
5
4
3
2
1
2
1
3
2
1
AIR
INTAKE
FILTER
SWITCH
W
U
S
4
1
BY
G
A
N
BK
SV0
S
I
L
E
T
CIRCUIT
2
5
W
BOARD
63
K
R
BK BK
BK
R2
R3R4
O
T
I
W
T
A
A
I
M
S
R
B
O
I
V
L
E
A
E
N
L
N
T
V
O
E
I
D
0
H
E
T
U
H
N
A
H
E
X
H
T
E
L
T
E
A
C
E
L
R
E
E
R
T
H
R
E
M
T
R
M
I
S
T
O
R
A
M
T
I
N
I
S
G
S
T
E
T
O
R
O
R
R
MAIN
REMOTE
CONTROL
(UMC-117)
W
O
2
1
7
B
6
W
5
Y
4
R
3
BK
2
BK
1
R
R
FUSE
(5A)
-
R1
PSV
T
H
H
O
V
E
T
A
R
L
M
W
V
I
A
E
S
T
T
E
O
R
R
DE
F
P
2
1
Q
2
1
T
H
E
R
W
R
M
+
O
C
O
U
P
L
E
FOR INDOOR
MODEL ONLY
BATH
REMOTE
CONTROL1
(USC1-117)
6
5
4
G
3
2
1
3
2
1
I
J
ANTI-FROST
HEATER
BATH
REMOTE
CONTROL2
(USC2-117)
FAN
FM
MOTOR
5
1234
W
B
R
O
Y
CONNECTOR FOR CHECKING
THERMOELECTROMOTIVE FORCE
GR
GR
H
6
5
4
IGNITER
GY
GY
TRANSFORMER
R
AC
100V
R
(BLUE)
W
THE CONNECTORS OF DUAL AND MULTIPLE
ARE INTERAPPLICABLE TO THE BODY
CONNECTORS EACH OTHER.(RED)
WATER BY-PASS
WV
SOLENOID VALVE
IG
BK
BK
BK
W
W
WW
BK
(RED)
W
(RED)
W
W
G/Y:GREEN/YELLOW
ELECTRODE
FUSE(3A)
WW
W
W
BK
COLOUR CODE
R:RED
W:WHITE
BR:BROWN
BK:BLACK
B:BLUE
GY:GRAY
GR:GREEN
O:ORANGE
Y:YELLOW
BK
W
BK
BK
FROST
PROTECTION
THERMOSTAT
FOR INDOOR
MODEL ONLY
BK
G/Y
W
AC
GND
120V
BK
BK
Ground Screw
Junction
Box
Connections
On/Off
Switch
Wire

22
Installing the water heater.
Typical Installation of Indoor Water Heater
NOTICE: The National Fuel Gas Code (NFGC) and B149 mandates a manual gas shut-off valve:
See NFGC/B149 for complete instructions. Local codes or plumbing authority requirements may
vary from the instructions or diagrams provided and take precedent over these instructions.
90° Elbow
Vent Adapter
1/4" Per Foot Downward Pitch
PRIORITY
°F
POWER
ON/OFF
Wall Thimble
Outside Wall
Vent Termination
With Protective
Screen
Outside Wall
To Hot Water
Faucet(s)
Water Filter
Drain Valve
Union
Cold Water
Supply
Shut-off
Val v e
Check
Val v e
Relief
Valve
Discharge
Line
(To Suitable Drain)
6" (15 cm) Air Gap
Manual Gas
Appliance
Union
Sediment
Trap
Cap
Power
Supply
Cord
Shut-off
(supplied)
Manual
Gas Supply Line
Shut-off
Val v e
Remote
Control
Vacuum Relief Valve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.

24
For increased energy efficiency, use pipe
insulation. Please install the insulation,
according to the illustrations above,
making sure to insulate all the way to the
top. Do not cover any drain or pressure
relief valve(s).
Do’s
❑ Do follow all installation instructions
convered in this manual.
❑ Do check inlet gas pressure to ensure that
it is within the range specified on the rating
plate.
❑ Do provide adequate air for combustion
and ventilation as discussed in the Use &
Care Manual and the National Fuel Gas
Code (CAN/CGA B149 in Canada).
❑ Do maintain proper clearances to
combustibles and non-combustibles as
specified on the nameplate.
❑ Do ensure that the venting system
complies with the guidelines found in the
Use & Care Manual and National Fuel Gas
Code (CAN/CGA B149 in Canada).
❑ Do contact local gas company to ensure
gas meter and gas piping are adequately
sized.
❑ Do use teflon tape on water line
connections and fittings.
Don’ts
❑ Don’t block or restrict Air Intake
Opening located bottom left corner of the
water heater.
❑ Don’t remove the front cover unless
absolutely necessary. This should only be
done after being examined by a qualified
service technician.
❑ Don’t install this product where standing
water may occur.
❑ Don’t use pipe dope on water line
connections and fittings.
During Installation of this water heater...........
Hot and Cold Pipe Insulation Installation
Insulation Blankets
Insulation blankets, available to the general
public, for external use on gas water heaters
are not necessary. The purpose of an
insulation blanket is to reduce the standby
heat loss encountered with storage tank
heaters. This water heater does not store
water making an insulation blanket
unnecessary.
The manufacturer’s warranty does not cover
any damage or defect caused by installation,
attachment or use of
any type of energy saving or other
unapproved devices (other than those
authorized by the manufacturer) into, onto or
in conjunction with the water heater. The use
of unauthorized energy saving devices may
shorten the life of the water heater and may
endanger life and property.
The manufacturer disclaims any responsibility
for such loss or injury resulting from the use
of such unauthorized devices.
CAUTION: If local codes require the
application of an external insulation
blanket to this water heater, pay careful
attention to the following so as not to
restrict the proper function and operation
of the water heater:
● Do not cover the air inlet, flue outlet, or
operating and warning labels attached to
the water heater or attempt to relocate them
on the exterior of insulation blanket.
WARNING: If local
codes require external
application of insulation
blanket kits the
manufacturer’s instructions
included with the kit must
be carefully followed.
NOTICE: The hot and cold
pipes should be insulated as
shown to provide additional
freeze protection.
Insulate all the
way to the top
Hot
Wat er
Cold Water
Check Valve
Inlet Pipe
Gas Inle

Installing the water heater:
25
A. Outdoor Water Heater Location
❑ Outdoor water heaters must be installed outdoors.
❑ Protected from freezing temperatures.
B. Indoor Water Heater Location
❑ Close to area of vent termination.
❑ Indoors and protected from freezing temperatures .
C. Outdoor and Indoor Water Heater Location
❑ Proper clearance from combustible surfaces
observed.
❑ Sufficient fresh air supply for proper operation of
water heater.
❑ Air supply free of corrosive elements and
flammable vapors.
❑ Provisions made to protect area from water
damage.
❑ Sufficient room to service heater.
❑ Combustible materials, such as clothing, cleaning
materials, rags, etc. clear of the heater and vent
piping.
❑ Water heater is properly attached to the wall.
D. Water Supply
❑ Water supply has sufficient pressure.
❑ Air purged from water heater and piping.
❑ Water connections tight and free of leaks
❑ Water filter is clean and in place.
❑ Materials used are as instructed in this manual.
❑ Water pipes are insulated and protected from
freezing.
E. Gas Supply
❑ Gas type matches rating plate.
❑ Gas supply pressure is sufficient for the water
heater.
❑ Gas line equipped with shut-off valve, union and
sediment trap.
❑ Approved pipe joint compound used.
❑ Soap and water solution used to check all
connections and fittings for possible gas leak.
❑ Gas Company inspected installation (if required).
F. Relief Valve
❑ Pressure Relief Valve properly installed and
discharge line run to open drain
❑ Discharge line protected from freezing.
G. Venting (Indoor Water Heaters Only)
❑ Materials used are as instructed in the manual.
❑ Vent connector(s) pitched downward to termination
(¼" per foot of length minimum) See page 13.
❑ Vent connector(s) securely fastened together with
high temperature silicone (500°F)
(260°C)
and air-
tight.
❑ All vent runs are properly supported.
❑ Vent terminal is properly installed.
❑ Sufficient combustion air is available.
❑ Maximum and minimum vent lengths are
observed.
H. Electrical Wiring
❑ Voltage matches rating plate.
❑ Water heater is properly grounded.
❑ Supply cord and/or wiring meets all local codes.
Installation Check List

26
Lighting the water heater:
Before operating this water heater, be sure to read and follow the instructions on the label pictured
below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to
do so can result in unsafe operation of the water heater resulting in property damage, personal injury,
or death . Should you have any problems reading or following the instructions in this manual, STOP,
and get help from a qualified person.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING : If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above on this label.
2.Turn off all electric power to the appliance.
3.Do not attempt to light the burner by hand.
4.Turn the Gas Shutoff Valve located on the outside of the unit
clockwise to the "OFF" position.
5.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in
the safety information above on this label. If you don't smell gas, go to the next step.
6.Turn the Gas Shutoff Valve located on the outside of the unit counterclockwise to
the "ON" position.
7.Turn on all electric power to the appliance.
8.If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance"
and call your service technician or gas supplier.
GAS SHUTOFF
VALVE
OPEN CLOSE
TO TURN OFF GAS TO APPLIANCE
1.Turn off all electric power to the appliance if service is to be performed.
.
Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the "OFF" position.
2

27
Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 11/2 to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 11/2 seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
DANGER: There is a
hot water scald potential
if the temperature is set
too high. Households with
small children, disabled, or
elderly persons may require
a 120°F (49°C) or lower
temperature setting to
prevent contact with HOT
water.
Water Temperature Setting
The temperature of the water in the water
heater can be regulated by setting the
temperature on the front of the remote
control.
Safety factors should be considered when
selecting the water temperature setting of
the water heater’s remote control.
The remote control was set at 100°F
(38°C) before the water heater was shipped
from the factory. This is the
recommended starting point.
Water temperatures above 125°F (52°C)
can cause severe burns or death from
scalding. Be sure to read and follow the
warnings outlined in this manual and on
the label located on the water heater.
Mixing valves are available for reducing
point of use water temperature by mixing
hot and cold water in branch water lines.
Contact a licensed plumber or the local
plumbing authority for further
information. (See page 4 for more details.)
The chart below may be used as a guide in
determining the proper water temperature
for your home.
Safety Precautions
Do turn off manual gas shut-off valve if water heater
has been subjected to over heating, fire, flood,
physical damage or if the gas supply fails
to shut off.
Do Not turn on water heater unless water and gas
supplies are fully opened.
Do Not turn on water heater if cold water supply
shut-off valve is closed.
Do Not allow combustible materials such as
newspaper, rags or mops to accumulate near
water heater.
Do Not store or use gasoline or other flammable
vapors and liquids, such as adhesives or paint thinner,
in vicinity of this or any other appliance.
If such flammables must be used, open doors
and windows for ventilation, and all gas burning
appliances in the vicinity should be shut off including
their pilot lights, to avoid vapors lighting.
NOTICE: Flammable vapors can be drawn by air
currents from surrounding areas to the water heater.
If there is any difficulty in understanding or following
the Operating Instructions or the Care and Cleaning
section, it is recommended that a qualified person or
serviceman perform the work.
Operating the water heater:
!

28
Water Temperature Setting…
Maximum water temperature occurs while
the burner is on. To determine the water
temperature, turn on a hot water faucet
and place a thermometer in the water
stream. Water temperature at the faucet
may vary depending on season and length
of pipe from the water heater.
The factory setting of the remote control
temperature range is between
100°F (38°C) and 120°F (49°C).
The remote control is factory preset to
100°F (38°C).
To turn the remote control ON or OFF,
press the POWER button.
To adjust the temperature to a required
setting , press the UP arrow temperature
button.
Pressing the UP or DOWN temperature
adjustment buttons will change the
temperature set point.
The temperature set point on the remote
control cannot be increased above 112°F
(44°C) when a hot water faucet is in the
open position.
Notice: The factory setting allows
operating temperatures between 100°F
(38°C) and 120°F (49°C). Temperatures
of up to 180°F (82°C) can be achieved
with the MAIN (UMC-117) remote
control and a dip switch adjustment. Only
qualified service personnel should perform
this adjustment. Only factory authorized
remote control(s) should be used.
The hottest temperature water will be at
the hot water faucet closest to the water
heater.
Always remember to test the water
temperature with your hand before use and
remember that hotter water increases the
risk of scald injury.
Always supervise young children or others
who are incapacitated.
The water heater is equipped with a device
that will shut off the gas supply to the
burner if the water heater exceeds normal
operating temperatures. Refer to the
(Before You Call For Service) section
located near the back of this manual, or
contact your dealer.
WARNING: Should overheating occur or
the gas supply fail to shut off, turn off the
manual gas control valve to the appliance.
If the water heater has been subjected to
fire, flood or physical damage, turn off the
manual gas shut-off valve(s), and do not
operate the water heater again until it has
been checked by qualified personnel.
Notice: The water heater may not operate
with a small water flow. In such case,
increase the water flow. If water heater still
does not operate and hot water faucet is
completely open, increase the temperature
setting on the remote control.
* Temperatures above 120°F (49°C) can be achieved by adjusting the
dip switch. See page 35 for dip switch adjustment.
In Use Indicator
(Lit during operation)
LED Display
(Displays water
temperature and error
codes)
ON/OFF
Indicator
Temperature
Adjustment
Buttons
Priority Indicator
Notice: The remote controller
cannot be turned on when
water is flowing or circulating
through the water heater.
Notice: Display shows
°F only.
!
PRIORITY
°F
POWER
ON/OFF
Higher (Hotter) Lower (Cooler)
100 102 104 106 108 110 112 114 116 118 120* 125 130 135 140 150 160 170 180 °F
38 39 40 41 42 43 44 46 47 48 49* 52 54 57 60 66 71 77 82 °C

29
Care and cleaning of the water heater:
Routine Preventative Maintenance
Properly maintained, your water heater
will provide years of dependable troublefree service.
It is recommended that a periodic
inspection of the burner, relief valve, air
intake filter, water filter and venting
system should be made by service
personnel qualified in gas appliance repair.
It is suggested that a routine preventive
maintenance program be established and
followed by the user.
At least once a year, lift and release the
lever handle on the pressure relief valve,
located in the hot outlet piping of the
water heater, to make certain the valve
operates freely. Allow several gallons to
flush through the discharge line to an open
drain.
NOTICE: If the pressure relief valve on
the hot water heater discharges
periodically, this may be due to a
problem in the water system. Contact
the water supplier or your plumbing
contractor on how to correct this. DO
NOT plug the relief valve outlet.
Rapid closing of faucets or solenoid
valves in automatic water using appliances
can cause a banging noise heard in a water
pipe. Strategically located risers in the
water pipe system or water hammer
arresting devices can be used to minimize
the problem.
Inspect the area around the water heater to
ensure a safe operating environment. Keep
appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
Ensure the unit has not been damaged. If
damage or denting is present, contact a
service personnel to verify proper
operation.
Check for any abnormal sounds during
normal operation of the water heater.
All piping should be checked for gas
and/or water leaks. Refer to page 12 of
this manual for instructions on leak
testing.
The air intake and cold water supply
filters should be cleaned monthly. Refer to
the “Housekeeping” section for further
information.
DO NOT operate the water heater if you
feel something is wrong with the unit.
DO NOT allow children to operate or
otherwise handle the unit.
Notice: After inspection, maintenance,
and/or cleaning, ensure proper operation
by turning on a hot water faucet.
Housekeeping
Before performing Housekeeping tasks to
this water heater, turn the unit off and
disconnect the power supply.
Vacuum around the water heater for dust,
dirt and lint on a regular basis.
Clean the water heater and remote control
by using a damp soft cloth with a few
drops of mild detergent and gently wiping
the surfaces of the unit. Wipe any
remaining moisture with a dry soft cloth.
To ensure sufficient ventilation and
combustion air supply, proper clearances
must be maintained.
DO NOT block or obstruct the air intake
opening located at the lower left corner of
the water heater. A minimum of 12”
(30 cm) is required between this
combustion air inlet opening and any
obstruction.
The Air Intake and Water filters should be
cleaned on a monthly basis.
HOW TO CLEAN THE WATER FILTER:
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
● Turn the water supply OFF to the
heater.
● Drain heater. See “Draining The
Water Heater” section on page 31.
● Unscrew the water filter, and slide the
filter out.
● DO NOT tap the filter as it may
deform and/or damage the filter.
● To remove severe sediment and dirt,
use a soft brush and wash with running
water.
● Return the filter to the water heater and
screw in the filter.
● Turn the electrical power supply and
cold water supply ON to the water
heater.
DANGER: Before
manually operating the
relief valve, make certain
no one will be exposed to
the danger of the hot water
released by the valve. The
water may be hot enough to
create a scald hazard. The
water should be released
into a suitable drain to
prevent injury or property
damage.
DANGER: Combustible
materials, such as clothing,
cleaning materials, or
flammable liquids, etc., must
not be placed against or next
to the water heater.
DANGER: Failure to
perform the recommended
Routine Preventative
Maintenance can harm the
proper operation of this
water heater, which can
cause carbon monoxide
dangers, excessive
hot water temperatures and
other potentially hazardous
conditions.
DANGER: Hotter water
increases the potential for
Hot Water Scalds.
DANGER: Shock Hazard
Make sure the electrical
power to the water heater is
off to avoid potential serious
injury or damage to
components.
!
!
!

30
Venting System Inspection
The venting system of an indoor water
heater should be inspected annually to
ensure all of the vent sections are secure
and air-tight.
It is recommended that qualified service
personnel familiar with Category III
venting inspect the venting system.
Check vent connection joint sections with
a solution of soapy water to assure airtightness while the unit is operating.
Bubbles around a joint connection
indicates a seal leak. Refer to page 13 for
vent sealing instructions.
DO NOT operate the unit if vent system
shows signs of leaking exhaust.
Check to make sure that the air intake and
vent outlet on the OUTDOOR water
heater or the air intake filter and the vent
terminal on the INDOOR water heater has
not been blocked or contain debris.
Burner Inspection
Visually inspect the main burners
annually.
Through the sight glass, inspect the burner
flame with the main burner off and inspect
the main burner while firing.
If any unusual burner operation is noted,
the water heater should be shut off until
qualified service assistance can be
obtained.
CAUTION: For your safety, burner
inspection and cleaning should be
performed only by qualified service
personnel.
For cleaning, a vacuum cleaner can be
used on the burner.
Proper burner pattern.
Care and cleaning of the water heater:
Vacation and Extended Shut-Down
If the water heater is to remain idle for an
extended period of time, the power and
water to the appliance should be turned
off.
The water heater and piping should be
drained if they might be subjected to
freezing temperatures.
After a long shut-down period, the water
heater’s operation and controls should be
checked by qualified service personnel.
NOTICE: Refer to the Freeze
Protection Section on page 31.
Housekeeping continued
CLEANING THE AIR INTAKE
FILTER/AIR FILTER:
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
● Unscrew the holding screw to the right
of the filter, and slide the filter down.
● Using a vacuum cleaner, remove any
loose dust particles. DO NOT tap the
filter as it may deform and/or damage
the filter.
● To remove severe dust, use a soft brush
and wash with running water.
● Allow the filter to dry completely
before reinstalling the filter on the
water heater. Be sure to secure the filter
by lining the guide tab in the hole and
tightening the screw.
CLEANING THE WATER HEATER
AND REMOTE CONTROL(S):
● Make sure the unit is OFF and the
electrical power supply has been
disconnected.
● DO NOT scrub the appliance with a
brush.
● Use only mild soapy water, other
cleaners may damage the surface of the
water heater.
● DO NOT remove any label including
the rating plate while cleaning or
servicing.
● DO NOT splash water on the remote
controls when cleaning.
DANGER: DO NOT attempt
to operate the water heater
without the air intake filter. DO
NOT alter the proving switch to
force the unit to operate without
the air intake filter.
Notice: The water heater may
not work if the air intake filter
is severely clogged.
!
!

31
Draining the Water Heater
Freeze Protection
Where the water heater may be exposed to
freezing conditions, even for a short
period of time, be sure to drain all water
from the unit as instructed above.
Exposure to freezing conditions can occur
from down draft of venting system or
from installation in areas exposed to cold
air.
The water heater is equipped with a Freeze
Protection Electric Heater. As long as the
electricity is supplied to the water heater, it
prevents freezing inside the water heater up
to an ambient temperature of approximately
minus 30°F (-34°C) (without wind
conditions)
This device only protects the internal
components of the water heater. It does
NOT protect piping and valves. Therefore,
piping and valves should be wrapped with
insulation material as instructed on page 24.
Another method of freeze prevention is by
running a small volume of water. Running
water will protect the water heater, piping
and valves.
Follow the steps below to ensure proper
water flow through the water heater and
piping:
Turn off the switch on the remote
control.
Close the gas shut-off valve.
Open the hot water faucet slightly until
a stream of approximately 1/8” (.32 cm)
is flowing. Be sure to check the flow
periodically.
WARNING: Failure
to drain the water
heater can cause serious
damage to the water
heater as well as
personal injury.
Below are instructions for draining water
out of the water heater.
Turn off the switch on the remote
control.
Close the gas shut-off valve(s).
Unplug the power supply cord (or
disconnect breaker) at least 10 seconds
after step #1.
Open all hot water faucets. Before
proceeding to the next step, make sure
that COLD water is coming out of all
hot water faucets.
Close the water shut-off valve.
Using a suitable container to catch
water, remove the water filter from
heater. Attach a garden hose to the
drain valve installed in the hot water
outlet line and direct the stream of
water to a suitable drain where it will
cause no damage. Leave water heater
as is until next use.
To put the water heater back into
operation after draining, follow the steps
below.
Reinstall the drain plug and water filter.
Close the hot water outlet drain valve.
Open the water shut-off valve and close
again after making sure that water
comes out from hot water faucets.
(This step is to remove air from the
water lines.)
Plug into an electrical outlet, fully open
the gas shut-off valve and the water
shut-off valve.
NOTICE: The water heater may not
operate unless the above procedure is
followed correctly.
Draining the water heater
WARNING: Failure
to follow these
instructions while
draining the water
heater can cause serious
damage to the water
heater as well as
personal injury
including scalding.
NOTICE: DO NOT
unplug the electric
power supply cord for
freeze protection.
Care and cleaning of the water heater:
PRIORITY
°F
POWER
ON/OFF
To Hot Water
Faucet(s)

32
Before You Call For Service…
Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.
CAUTION: For your safety DO NOT attempt repair of electrical wiring, gas piping, remote control, burners, vent
connectors or other safety devices. Refer repairs to qualified service personnel.
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
Problem Possible Cause What To Do
Not enough or no hot water. Water Shutoff valve is not fully
opened.
● Check shutoff valve and open fully.
Hot water faucet is not fully opened.
● Open how water faucet completely.
(The main burner goes off when
incoming water volume is
inadequate.)
Water piping is frozen.
● Allow piping to thaw.
No electricity or water supply is cut
off.
● Check that proper power is being
supplied and/or water supply is
adequate.
Unit is not "ON".
● Turn the unit "ON" by the button
on the remote control.
The temperature may be set too low.
● Increase the temperature setting.
Mixing Valve Malfunctions
(if applicable)
● Check and replace if necessary.
Error code displayed on remote
controller.
● See instructions for Error Code and
if required, contact a dealer for
service.
Not enough water demand.
● Increase water flow.
Water inlet filter clogged.
● Clean water inlet filter.
Fixture aerator is clogged.
● Clean aerator.
Scale build up in heat exchanger.
● Check for error code. If required,
contact a dealer for service.
Hot and cold water lines reversed.
● Reverse water connections.
Water not hot enough. The temperature may be set too low.
● Check and open the gas valve fully.
The gas valve is not fully opened.
● Call your gas company to verify
the gas meter and gas piping size.
Gas supply pressure is low.
● Call dealer for service.
Bleed over in one of the hot water
fixtures.
● Decrease the temperature setting.
Water too hot. Temperature is set too high.
● Check shutoff valve and open fully.
Water shutoff valve is not fully
opened.
● Allow more water to flow.
Small amount of water has been
heated.
● Normal operation. There is no need
to call for service.
Fan continues to rotate after hot water
faucet is closed.
This function is to supply hot water
when the hot water faucet is reopened.
● Normal operation. There is no
need to call for service.

Error Code Guide
When an error code is displayed:
● Close the hot water faucet, turn off the switch on the
remote control.
● Wait for about 5 minutes before turning the switch on
again.
● Open the hot water faucet.
If the error code remains shown:
● Close the hot water faucet and turn off the switch on the
remote control.
● Take the proper action shown below and attempt
operation of the appliance again.
If the error code is still shown:
● Turn off the hot water faucet and turn off the switch on
the remote control.
● Take note of the error code displayed and call the
customer service assistance number in the “If You Need
Service” section of the manual on the back cover.
Notice: If an error code other than those listed below is
displayed, immediately turn off the hot water faucet, take
note of the error code, turn off the switch on the remote
control and call the customer assistance number.
CAUTION: For your safety DO NOT attempt repair of gas piping, remote control, burners, vent connectors or other
safety devices. Refer repairs to qualified service personnel.
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
Error Code Possible Cause What To Do
11 The Gas Shutoff Valve is not opened
completely.
● Open the Gas Shutoff Valve
completely.
12 Gas Service has been interrupted.
LP Gas is running low. (LP models only)
● Contact Gas Utility Company.
● Fill up LP Gas container or
replacewith a new cylinder of LP Gas.
15 The hot water faucet is not opened enough.
● Open the faucet more to secure
enough volume.
16 The method of restarting the unit after
draining the water from it was not performed
in sequesnce.
● See the section "Draining the Water
Heater"
21
Indoor Water Heater Only
Air intake filter may not be attached, or may
not be firmly in place.
● See the section "Cleaning the Intake
Filter".
05
(Every 60 seconds you hear
an alarm or when the faucet is
closed, the alarm stops.)
Indoor Water Heater Only
Air intake of the unit and/or vent termination
may be blocked.
Ventilator or other vents of the room may be
blocked.
The air inside the room may be
contaminated due to long use of a fireplace
or spaceheater.
Heavy ventilation by other equipment or
appliances causing the lack of air intake to
the water heater.
Air shortage may be caused by too much
steam in the unit.
Air intake filter is clogged.
● Remove any obstructions of the air
intake or vent termination.
● Clean the air intake of any dust or
grease build up.
● Open a window or vent to keep the
air inside the room fresh.
● Lower the level of the ventilation of
other equipment or appliances.
● Avoid direct contact from steam.
● Clean the air intake filter.
13
Indoor Water Heater Only
If the error code is still displayed after
taking the above steps.
● Please contact a dealer for service.
1L Water heater has build up of lime deposits.
● Contact a dealer for service.
99
Outdoor Water Heater Only
Decrease of blower motor ventilation
amount. (Operation Stops)
● Clean any blockage from heat
exchanger fins and/or blower motor
33

34
Replacement Parts.
Indoor Water Heater
Instructions For Placing a Parts Order
Address parts orders to the distributor or store
from where the water heater was purchased.
All parts orders should include:
The model and serial number of the
water heater from the rating plate.
Specify type of gas (natural or LP) as
marked on the rating plate.
Part description (as noted below) and
number of parts desired.
CAUTION: For your safety, DO
NOT attempt repair of electrical wiring,
gas piping, burners, vent connectors
or other safety devices. Refer repairs
to qualified service personnel.
WARNING: For your
safety, DO NOT attempt to
disassemble this unit for
any reason.
Outdoor Water Heater
Unit Cover Panel
Heat Exchanger
Thermistor
3A (250V)
Fuses
Water Filter
SW1 SW2
SW3
DIP1
3A (250V)
Fuses
Water Filter
Burner Assembly
Cover
(w/ sight glass)
0401
A.C. 100V
ACS-201X
SPARK UNIT
SW1 SW2
ONOFF
ON
SW3
DIP1
4
3
2
1
4
3
2
1
Ignitor
Proving Switch
PC Board (PCB)
5A (250V) Fuse
Burner
Assembly
(with ODS)
Water Flow
Solenoid
Transformer
Inlet Thermistor
Outlet
Thermistor
Heat Exchange
Flame Rod/
Electrodes
Blower
Motor
Gas Valve
Assembly
Unit Cover Panel
Heat Exchanger
Thermistor
Burner Assembly
Cover
(w/ sight glass)
0401
A.C. 100V
ACS-201X
SPARK UNIT
ONOFF
ON
4
3
2
1
4
3
2
1
Ignitor
PC Board (PCB)
5A (250V) Fuse
Burner
Assembly
Water Flow
Solenoid
Transformer
Inlet Thermistor
Outlet
Thermistor
Heat Exchange
Flame Rod/
Electrodes
Blower
Motor
Gas Valve
Assembly

35
Required adjustment for up to 180°F (82°C) water temperature settings
WARNING: Refer to scald potential warnings on page 4 before
making adjustment. Changing this setting is done at your own risk.
DO NOT alter the #4 DIP Switch if the setting of up to 180°F (82°C) is
not required.
Follow the instructions below if it is determined that a setting of up to
180°F (82°C) is required.
●
Turn off remote control. Turn off the gas and water shutoff valves.
●
Remove the front cover.
●
Find the DIP Switch #4 located at the top left hand side of the PCB. (See
illustration to the right for DIP Switch location)
●
Change the DIP Switch #4 setting to the “ON” position. DO NOT alter any
other DIP Switch. The LED on the PCB is flashing. At the same time, the
display of the Main Remote Control starts to flash.
●
Press the “Max” button on the left hand side of the PCB for more than 1
second. The LED on the PCB starts illuminating continuously. At the same
time, the display of the Main Remote Control is on continuously.
●
Change the DIP Switch #4 setting back to the “OFF” position. DO NOT alter
any other DIP Switch. The LED on the PCB will stop illuminating. At the
same time, the display of the Main Remote Control will turn off.
●
Attach the unit’s front cover.
●
Turn on the remote control, gas and water shutoff valves.
●
Check and ensure safe operation and performance of the water heater.
See steps below to LIMIT maximum water temperature setting to 120 (49°C).
Follow first four bullets points listed above, then continue as listed below:
●
Press the “Min.” button on the left hand side of the PCB for more than 1
second. The LED on the PCB starts illuminating continuously. At the same
time, the display of the Main Remote Control is on continuously.
●
Change the DIP Switch #4 setting back to the “OFF” position. DO NOT alter
any other DIP Switch. The LED on the PCB will stop flashing. At the same
time, the display of the Main Remote Control turn off.
●
Attach the unit’s front cover.
●
Turn on the remote control, gas and water shutoff valves.
●
Check and ensure safe operation and
performance of the water heater.
Location of DIP Switches on PC Board.
Temperature Setting DIP Switch Adjustment
The content on this page is intended for use by qualified
installation/service personnel ONLY.
“Max”
Button
“Min.”
Button
LED
DIP
Switches
WARNING: Improper adjustment, alteration,
service or maintenance can cause property damage,
personal injury, or death.
Time/Temperature Relationship in Scalds
DANGER: Hotter water increases
the potential for Hot Water SCALDS.
120°F (49°C) More than 5 minutes
125°F (52°C) 1 ½ to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 1 ½ seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
Water Temperature Time To Produce a Seroius Burn
!
SW3
SW1
ON
DIP1
1
1
SW2
ONOFF
4
3
2
4
3
2
!
ON
ON
DIP1
4
3
2
1
OFF
SW1 SW2
ONOFF
ON
SW3
DIP1
4
3
2
1
4
3
2
1
ON
4
3
2
1
As set from factory
ON
4
3
2
1
Setting during adjustment
to DIP Switch #4
for temperature.
ON
4
3
2
1
Setting after adjustment
to DIP Switch #4
for temperature.

36
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires
adjustment, repair, or routine maintenance, it is suggested that you first contact
your installer, plumbing contractor or previously agreed upon service agency. In
the event the firm has moved, or is unavailable, refer to the telephone directory,
commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should
then contact the Manufacturer’s National Service Department at the following
address:
2600 Gunter Park Drive
Montgomery, Alabama 36109-1413
Phone: 1-800-432-8373.
When contacting the manufacturer, the following information will be requested:
a. Model and serial number of the water heater as shown on the rating plate attached
to the front panel of the heater.
b. Address where the water heater is located and physical location.
c. Name and address of installer and any service agency who performed service on
the water heater.
d. Date of original installation and dates any service work was performed.
e. Details of the problem as you can best describe them.
f. List of people, with dates, who have been contacted regarding your problem.