Rheem A180DL25E, A180CL35E, A180DL35E, A180DM25E, A180DM35E Installation Instructions Manual

...
92-23577-56-01
SUPERSEDES 92-23577-56-00
INSTALLATION INSTRUCTIONS
FOR COMBINATION HEATING AND COOLING ROOFTOP UNITS
15, 20 & 25 TON (-)KKB AND 15 & 20 TON (-)KMB UNITS
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INST ALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE A TTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
Recognize this symbol as an indication of Important Safety Information!
!
— Do not store or use gasoline or other
flammable vapors and liquids, or other combustible materials in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELLGAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— DO NOTRELYON SMELLALONE TO
DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT BE ABLE T O SMELL FUEL GASES.
• U.L. recognized fuel gas and CO detectors are recommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs
— Improper installation, adjustment, alteration,
service or maintenance can cause injury , property damage or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING
!
PROPOSITION 65: THIS FURNACE CONTAINS FIBERGLASS INSULATION. RESPIRABLE PARTICLES OF FIBERGLASS ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER. EXHAUST GAS FROM THIS FURNACE CONTAINS CHEMICALS, INCLUDING CARBON MONOXIDE, KNOWN TO THE STATE OF CALIFORNIA TO CAUSE BIRTH DEFECTS OR OTHER REPRO­DUCTIVE HARM.
WARNING
!
FOR YOUR SAFETY
!
DO NOT DESTROY.
PLEASE READ CAREFULLY AND KEEP
IN A SAFE PLACE FOR FUTURE
REFERENCE BYA SERVICEMAN OR
USER OF THIS APPLIANCE.
2
INTRODUCTION
I. SPECIFICATIONS
TABLE OF CONTENTS
!
WARNING
Page No.
I. SPECIFICATIONS
Components 2 Unit Dimensions 3-5 Electrical & Physical Data 6-10
II. INSTALLATION
General 11 Location Considerations 11 Exhaust & Combustion
Hoods 12 Cover Panel Installation 12 Clearances 13 Rooftop 14 Ducting 14-15 Return Air 15
III. GAS SUPPLY & PIPING 16-18 IV. ELECTRICAL WIRING
Power Supply 19 Hook-up 20 Internal Wiring 20 Thermostat 20
V. FURNACE CONTROLS 21-23
VI. OPERATION INFO 23-24
VII. AIRFLOW 25-26
VIII. TROUBLESHOOTING 27-29
IX. WIRING DIAGRAMS 30-33
X. CHARGE CHARTS 34-36
XI. WARRANTY 40
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAYALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
This booklet contains the installation and operating instructions for your combination gas heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference.
CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. IMPORTANT: Check the unit model number, heating size, electrical characteristics, and accessories to determine if they are correct.
A. GENERAL
The Combination Gas Heating/Electric Cooling Rooftop is available in 250,000 AND 350,000 BTUH heating input with nominal cooling capacity of 15 tons. 300,000 and 400,000 BTUH heating inputs are available in nominal cooling capacity of 20 & 25 tons. Units are convertible from bottom supply and return to side supply and return by relocation of supply and return air cover panels. See cover installation detail and Figures 10 &11.
The units are weatherized for mounting outside of the building.
UNITS ARE NOT DESIGN CERTIFIED TO BE INSTALLED INSIDE THE STRUCTURE. DOING SO CAN CAUSE INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE AND CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
B. MAJOR COMPONENTS
The unit includes a hermetically-sealed refrigerating system consisting of a scroll compressor, condenser coil, evaporator coil with capillary tube assembly or TXV, a circulation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assembly, combustion air motors and fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.
!
WARNING
3
FIGURE 1. BOTTOM VIEW
FIGURE 2. SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICA TIONS
Unit Dimensions
FOR CLEARANCES SEE PAGE 12, FIGURE 12.
IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM THE CONDENSER SECTION AND CONDENSATE PAN.
ST-A0886-02
ST-A0886-07
FIGURE 3. COMPONENT LOCATIONS & DIMENSIONS
ST-A0886-04
FIGURE 4. COMPONENT LOCATIONS & DIMENSIONS
ST-A0886-06
FIGURE 5. COMPONENT LOCATIONS
ST-A0886-27
4
GAS SUPPLY
(SIDE ENTRY)
3/4” INLET
5
FIGURE 7. COMPONENT ACCESS LOCATIONS & DIMENSIONS
FIGURE 6. DIMENSIONS
ST-A0886-05
ST-A0886-03
FIGURE 8. COMPONENT LOCATIONS
ST-A0886-28
6
A180CL25E 3-60-208-230 12.4/12.4 88 2.4 11.5 74/74 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1790 2010
[51 X 457 X 457] [3.345] [7551] [2325]/ [811.9] [911.7]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CL35E 3-60-208-230 12.4/12.4 88 2.4 11.5 74/74 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1817 2037
[51 X 457 X 457] [3.345] [7551] [2325]/ [824.2] [924.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CM25E 3-60-208-230 12.4/12.4 88 2.4 14.7 77/77 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1820 2040
[51 X 457 X 457] [3.345] [7551] [2325]/ [825.5] [925.3]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CM35E 3-60-208-230 12.4/12.4 88 2.4 14.7 77/77 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1847 2067
[51 X 457 X 457] [3.345] [7551] [2325]/ [837.8] [937.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DL25E 3-60-460 6.4 44 2.0 7.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1806 2026
[51 X 457 X 457] [3.345] [7551] [2325]/ [819.2] [919.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DL35E 3-60-460 6.4 44 2.0 7.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1841 2061
[51 X 457 X 457] [3.345] [7551] [2325]/ [835.1] [934.9]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DM25E 3-60-460 6.4 44 2.0 10.0 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1836 2056
[51 X 457 X 457] [3.345] [7551] [2325]/ [832.8] [932.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DM35E 3-60-460 6.4 44 2.0 10.0 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1871 2091
[51 X 457 X 457] [3.345] [7551] [2325]/ [848.7] [948.5]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YL25E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1806 2026
[51 X 457 X 457] [3.345] [7551] [2325]/ [819.2] [919.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YL35E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1817 2037
[51 X 457 X 457] [3.345] [7551] [2325]/ [824.2] [924.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YM25E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1836 2056
[51 X 457 X 457] [3.345] [7551] [2325]/ [832.8] [932.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
SHIPPING
LBS.
[KG]
TABLE 1
15, 20 & 25 TON (-)KKB – ELECTRICAL& PHYSICAL DATA
ELECTRICAL
MODEL
NUMBER
PHASE
FREQUENCY
VOLTAGE
(HZ)
(VOLTS)
RATED
LOAD
AMPERES
(RLA)[EA.]
COMPRESSOR
LOCKED
ROTOR
AMPERES
(LRA)[EA.]
FULL LOAD
AMPERES
(FLA)
FAN
MTR
[EA.]
BLWR
MTR
MINIMUM
CIRCUIT
AMPACITY
AMPERES
MIN.
AMPS
MAX.
AMPS
FUSE OR HACR
CIRCUIT
BREAKER
DRIVE
TYPE
RECOMMENDED
NO. AND SIZE
[mm x mm x mm]
AREA
SQ. FT.
[SQ. M]
NO.
ROWS
CFM
[L/s]
R22
OZ.
[G]
SYSTEM
PER
CIRCUIT
1,2/3,4
NET
LBS.
[KG]
FILTER OUTDOOR COIL WEIGHT
PHYSICAL
7
A180YM35E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1871 2091
[51 X 457 X 457] [3.345] [7551] [2325]/ [848.7] [948.5]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240CL30E 3-60-208-230 17.8/17.8 124 2.4 14.7 100/100 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1884 2104
[51 X 457 X 457] [3.345] [7551] [2183]/ [854.6] [954.4]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240CL40E 3-60-208-230 17.8/17.8 124 2.4 14.7 100/100 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1900 2120
[51 X 457 X 457] [3.345] [7551] [2183]/ [861.8] [961.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240CM30E 3-60-208-230 17.8/17.8 124 2.4 22.3 108/108 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1906 2126
[51 X 457 X 457] [3.345] [7551] [2183]/ [864.5] [964.3]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240CM40E 3-60-208-230 17.8/17.8 124 2.4 22.3 108/108 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1922 2142
[51 X 457 X 457] [3.345] [7551] [2183]/ [871.8] [971.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240DL30E 3-60-460 9.3 59.6 2.0 10.0 58 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1908 2128
[51 X 457 X 457] [3.345] [7551] [2183]/ [865.5] [965.2]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240DL40E 3-60-460 9.3 59.6 2.0 10.0 58 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1932 2152
[51 X 457 X 457] [3.345] [7551] [2183]/ [876.3] [976.1]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240DM30E 3-60-460 9.3 59.6 2.0 11.2 59 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1930 2150
[51 X 457 X 457] [3.345] [7551] [2183]/ [875.4] [975.2]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240DM40E 3-60-460 9.3 59.6 2.0 11.2 59 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1954 2174
[51 X 457 X 457] [3.345] [7551] [2183]/ [886.3] [986.1]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240YL30E 3-60-575 7.7 49.4 1.0 8.0 45 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1908 2128
[51 X 457 X 457] [3.345] [7551] [2183]/ [865.5] [965.2]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240YL40E 3-60-575 7.7 49.4 1.0 8.0 45 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1932 2152
[51 X 457 X 457] [3.345] [7551] [2183]/ [876.3] [976.1]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240YM30E 3-60-575 7.7 49.4 1.0 8.8 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1930 2150
[51 X 457 X 457] [3.345] [7551] [2183]/ [875.4] [975.2]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240YM40E 3-60-575 7.7 49.4 1.0 8.8 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 77/72 1954 2174
[51 X 457 X 457] [3.345] [7551] [2183]/ [886.3] [986.1]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
SHIPPING
LBS.
[KG]
TABLE 1 – CONTINUED
15, 20 & 25 TON (-)KKB – ELECTRICAL& PHYSICAL DATA
ELECTRICAL
MODEL
NUMBER
PHASE
FREQUENCY
VOLTAGE
(HZ)
(VOLTS)
RATED
LOAD
AMPERES
(RLA)[EA.]
COMPRESSOR
LOCKED
ROTOR
AMPERES
(LRA)[EA.]
FULL LOAD
AMPERES
(FLA)
FAN
MTR
[EA.]
BLWR
MTR
MINIMUM
CIRCUIT
AMPACITY
AMPERES
MIN.
AMPS
MAX.
AMPS
FUSE OR HACR
CIRCUIT
BREAKER
DRIVE
TYPE
RECOMMENDED
NO. AND SIZE
[mm x mm x mm]
AREA
SQ. FT.
[SQ. M]
NO.
ROWS
CFM
[L/s]
R22
OZ.
[G]
SYSTEM
PER
CIRCUIT
1,2/3,4
NET
LBS.
[KG]
FILTER OUTDOOR COIL WEIGHT
PHYSICAL
8
A300CL30E 3-60-208-230 21.0/21.0 156 2.3 14.7 114/114 125/125 125/125 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2037 2257
[51 X 457 X 457] [3.345] [7551] [3317]/ [940.3] [1023.8]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300CL40E 3-60-208-230 21.0/21.0 156 2.3 14.7 114/114 125/125 125/125 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2053 2273
[51 X 457 X 457] [3.345] [7551] [3317]/ [931.2] [1031.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300CM30E 3-60-208-230 21.0/21.0 156 2.3 22.3 122/122 125/125 125/125 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2059 2279
[51 X 457 X 457] [3.345] [7551] [3317]/ [933.9] [1033.7]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300CM40E 3-60-208-230 21.0/21.0 156 2.3 22.3 122/122 125/125 125/125 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2075 2295
[51 X 457 X 457] [3.345] [7551] [3317]/ [941.2] [1041.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300DL30E 3-60-460 10.4 70 1.5 10.0 61 70 70 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2061 2281
[51 X 457 X 457] [3.345] [7551] [3317]/ [934.8] [1034.6]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300DL40E 3-60-460 10.4 70 1.5 10.0 61 70 70 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2085 2305
[51 X 457 X 457] [3.345] [7551] [3317]/ [945.7] [1045.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300DM30E 3-60-460 10.4 70 1.5 11.2 67 70 70 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2083 2303
[51 X 457 X 457] [3.345] [7551] [3317]/ [944.8] [1044.6]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300DM40E 3-60-460 10.4 70 1.5 11.2 67 70 70 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2107 2327
[51 X 457 X 457] [3.345] [7551] [3317]/ [955.7] [1055.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300YL30E 3-60-575 8.5 54 1.0 8.0 49 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2061 2281
[51 X 457 X 457] [3.345] [7551] [3317]/ [934.8] [1034.6]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300YL40E 3-60-575 8.5 54 1.0 8.0 49 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2085 2305
[51 X 457 X 457] [3.345] [7551] [3317]/ [945.7] [1045.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300YM30E 3-60-575 8.5 54 1.0 8.8 50 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2083 2303
[51 X 457 X 457] [3.345] [7551] [3317]/ [944.8] [1044.6]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A300YM40E 3-60-575 8.5 54 1.0 8.8 50 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2107 2327
[51 X 457 X 457] [3.345] [7551] [3317]/ [955.7] [1055.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
SHIPPING
LBS.
[KG]
TABLE 1 – CONTINUED
15, 20 & 25 TON (-)KKB – ELECTRICAL& PHYSICAL DATA
ELECTRICAL
MODEL
NUMBER
PHASE
FREQUENCY
VOLTAGE
(HZ)
(VOLTS)
RATED
LOAD
AMPERES
(RLA)[EA.]
COMPRESSOR
LOCKED
ROTOR
AMPERES
(LRA)[EA.]
FULL LOAD
AMPERES
(FLA)
FAN
MTR
[EA.]
BLWR
MTR
MINIMUM
CIRCUIT
AMPACITY
AMPERES
MIN.
AMPS
MAX.
AMPS
FUSE OR HACR
CIRCUIT
BREAKER
DRIVE
TYPE
RECOMMENDED
NO. AND SIZE
[mm x mm x mm]
AREA
SQ. FT.
[SQ. M]
NO.
ROWS
CFM
[L/s]
R22
OZ.
[G]
SYSTEM
PER
CIRCUIT
1,2/3,4
NET
LBS.
[KG]
FILTER OUTDOOR COIL WEIGHT
PHYSICAL
9
A180CL25E 3-60-208-230 12.4/12.4 88 2.4 11.5 74/74 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1790 2010
[51 X 457 X 457] [3.345] [7551] [2325]/ [811.9] [911.7]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CL35E 3-60-208-230 12.4/12.4 88 2.4 11.5 74/74 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1817 2037
[51 X 457 X 457] [3.345] [7551] [2325]/ [824.2] [924.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CM25E 3-60-208-230 12.4/12.4 88 2.4 14.7 77/77 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1820 2040
[51 X 457 X 457] [3.345] [7551] [2325]/ [825.5] [925.3]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180CM35E 3-60-208-230 12.4/12.4 88 2.4 14.7 77/77 80/80 80/80 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1847 2067
[51 X 457 X 457] [3.345] [7551] [2325]/ [837.8] [937.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DL25E 3-60-460 6.4 44 2.0 7.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1806 2026
[51 X 457 X 457] [3.345] [7551] [2325]/ [819.2] [919.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DL35E 3-60-460 6.4 44 2.0 7.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1841 2061
[51 X 457 X 457] [3.345] [7551] [2325]/ [835.1] [934.9]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DM25E 3-60-460 6.4 44 2.0 10.0 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1836 2056
[51 X 457 X 457] [3.345] [7551] [2325]/ [832.8] [932.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180DM35E 3-60-460 6.4 44 2.0 10.0 46 50 50 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1871 2091
[51 X 457 X 457] [3.345] [7551] [2325]/ [848.7] [948.5]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YL25E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1806 2026
[51 X 457 X 457] [3.345] [7551] [2325]/ [819.2] [919.0]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YL35E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1841 2061
[51 X 457 X 457] [3.345] [7551] [2325]/ [835.1] [934.9]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A180YM25E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1836 2056
[51 X 457 X 457] [3.345] [7551] [2325]/ [832.8] [932.6]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
SHIPPING
LBS.
[KG]
TABLE 2
15 & 20 TON (-)KMB – ELECTRICAL& PHYSICAL DATA
ELECTRICAL
MODEL
NUMBER
PHASE
FREQUENCY
VOLTAGE
(HZ)
(VOLTS)
RATED
LOAD
AMPERES
(RLA)[EA.]
COMPRESSOR
LOCKED
ROTOR
AMPERES
(LRA)[EA.]
FULL LOAD
AMPERES
(FLA)
FAN
MTR
[EA.]
BLWR
MTR
MINIMUM
CIRCUIT
AMPACITY
AMPERES
MIN.
AMPS
MAX.
AMPS
FUSE OR HACR
CIRCUIT
BREAKER
DRIVE
TYPE
RECOMMENDED
NO. AND SIZE
[mm x mm x mm]
AREA
SQ. FT.
[SQ. M]
NO.
ROWS
CFM
[L/s]
R22
OZ.
[G]
SYSTEM
PER
CIRCUIT
1,2,3,4
NET
LBS.
[KG]
FILTER OUTDOOR COIL WEIGHT
PHYSICAL
10
A180YM35E 3-60-575 5.0 34 1.0 8.0 34 35 35 BLT (3) 2 X 18.0 X 18.0 36.0 1.00 16000 82/72 1871 2091
[51 X 457 X 457] [3.345] [7551] [2325]/ [848.7] [948.5]
(3) 2 X 18.0 X 24.0 [2041]
[51 X 457 X 610]
A240CL30E 3-60-208-230 17.5/17.5 123 2.4 14.7 99/99 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 1972 2192
[51 X 457 X 457] [3.345] [7551] [3317]/ [894.5] [994.3]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240CL40E 3-60-208-230 17.5/17.5 123 2.4 14.7 99/99 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 1988 2208
[51 X 457 X 457] [3.345] [7551] [3317]/ [901.7] [1001.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240CM30E 3-60-208-230 17.5/17.5 123 2.4 22.3 107/107 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 1994 2214
[51 X 457 X 457] [3.345] [7551] [3317]/ [904.5] [1004.3]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240CM40E 3-60-208-230 17.5/17.5 123 2.4 22.3 107/107 110/110 110/110 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2010 2230
[51 X 457 X 457] [3.345] [7551] [3317]/ [911.7] [1011.5]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240DL30E 3-60-460 9.0 62 2.0 10.0 57 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 1996 2216
[51 X 457 X 457] [3.345] [7551] [3317]/ [905.4] [1005.2]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240DL40E 3-60-460 9.0 62 2.0 10.0 57 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2020 2240
[51 X 457 X 457] [3.345] [7551] [3317]/ [916.3] [1016.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240DM30E 3-60-460 9.0 62 2.0 11.2 58 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2018 2238
[51 X 457 X 457] [3.345] [7551] [3317]/ [915.3] [1015.1]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240DM40E 3-60-460 9.0 62 2.0 11.2 58 60 60 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2042 2262
[51 X 457 X 457] [3.345] [7551] [3317]/ [926.2] [1026.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240YL30E 3-60-575 7.1 50 1.0 8.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 1996 2216
[51 X 457 X 457] [3.345] [7551] [3317]/ [905.4] [1005.2]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240YL40E 3-60-575 7.1 50 1.0 8.0 43 45 45 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2020 2240
[51 X 457 X 457] [3.345] [7551] [3317]/ [916.3] [1016.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240YM30E 3-60-575 7.1 50 1.0 8.8 43 45 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2018 2238
[51 X 457 X 457] [3.345] [7551] [3317]/ [915.3] [1015.1]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
A240YM40E 3-60-575 7.1 50 1.0 8.8 43 45 50 BLT (3) 2 X 18.0 X 18.0 36.0 2.00 16000 117/107 2042 2262
[51 X 457 X 457] [3.345] [7551] [3317]/ [926.2] [1026.0]
(3) 2 X 18.0 X 24.0 [3033]
[51 X 457 X 610]
SHIPPING
LBS.
[KG]
TABLE 2 – CONTINUED
15 & 20 TON (-)KMB – ELECTRICAL& PHYSICAL DATA
ELECTRICAL
MODEL
NUMBER
PHASE
FREQUENCY
VOLTAGE
(HZ)
(VOLTS)
RATED
LOAD
AMPERES
(RLA)[EA.]
COMPRESSOR
LOCKED
ROTOR
AMPERES
(LRA)[EA.]
FULL LOAD
AMPERES
(FLA)
FAN
MTR
[EA.]
BLWR
MTR
MINIMUM
CIRCUIT
AMPACITY
AMPERES
MIN.
AMPS
MAX.
AMPS
FUSE OR HACR
CIRCUIT
BREAKER
DRIVE
TYPE
RECOMMENDED
NO. AND SIZE
[mm x mm x mm]
AREA
SQ. FT.
[SQ. M]
NO.
ROWS
CFM
[L/s]
R22
OZ.
[G]
SYSTEM
PER
CIRCUIT
1,2,3,4
NET
LBS.
[KG]
FILTER OUTDOOR COIL WEIGHT
PHYSICAL
11
II. INSTALLATION
A. GENERAL
1. INSTALLATION — Install this unit in accordance with The American National Standard Z223.1-latest edition booklet entitled “National Fuel Gas Code,” and the requirements or codes of the local utility or other authority having jurisdiction.
Additional helpful publications available from the “National Fire Protection Association” are: NFPA­90A - Installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B - Warm Air Heating and Air Conditioning Systems 1984.
These publications are available from:
National Fire Protection
Association, Inc. Batterymarch Park Quincy, MA 02269
2. PRE-INSTALLATION CHECK­POINTS — Before attempting any installation, carefully consider the following points:
Structural strength of supporting members
(Rooftop Installation) Clearances and provision for servicing Power supply and wiring Gas supply and piping Air duct connections and sizing Drain facilities and connections Location for minimum noise and
vibration - away from bedroom
windows
IMPORTANT: Before operating unit, remove compressor shipping supports from the compressor base. Failure to remove supports will casue noise and vibration.
LOCATION CONSIDERATIONS
The metal parts of this unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive.
3. A liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
B. OUTSIDE INSTALLATION
THESE UNITS ARE DESIGNED CERTIFIED FOR OUTDOOR INSTALLATION ONLY. INSTALLATION INSIDE ANY P ART OF A STRUCTURE CAN RESULT IN INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE. INSTALLATION INSIDE CAN ALSO CAUSE RECIRCULATION OF FLUE PRODUCTS INTO THE CONDITIONED SPACE RESULTING IN PERSONAL INJURY OR DEATH.
If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment location and exposure.
1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.
2. In coastal areas locate the unit on the side of the building away from the waterfront.
3. Shielding by a fence or shrubs may give some protection.
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURYOR DEATH. REGULAR MAINTENANCE WILL REDUCE THE BUILDUP OF CONT AMINANTS AND HELP TO PROTECT THE UNIT’S FINISH.
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
2. Regular cleaning and waxing of the cabinet with an automobile polish will provide some protection.
!
WARNING
!
WARNING
FIGURE 9. Outside Slab Installation. Closet Distribution System.
Slab Floor Construction
ST-A0886-25
12
(Typical outdoor slab installation is shown in Figure 9.)
1. Select a location where external water drainage cannot collect around unit.
2. Provide a level slab sufficiently high enough above grade to prevent surface water from entering the unit
3. Locate the unit to provide proper access for inspection and servicing as shown in Figure 12.
4. Locate unit where operating sounds will not disturb owner or neighbors.
5. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
6. Where snowfall is anticipated, the height of the unit above the ground level must be considered. Mount unit high enough to be above anticipated maximum area snowfall and to allow combustion air to enter the combustion air inlet.
7. Select an area which will keep the areas of the vent, air intake, and A/C condenser fins free and clear of obstructions such as weeds, shrubs, vines, snow, etc. Inform the user accordingly.
C. A TTACHING EXHAUST AND COMBUSTION AIR INLET HOODS
IMPORTANT: Do not operate this unit without the exhaust/combustion air inlet hood properly installed. These hoods are shipped in cartons in the blower compartment inside the unit and must be attached when the unit is installed. See Figure 4.
To attach exhaust/combustion air inlet hood:
1. Remove screws securing blower access panel and remove access panel. For location of blower access panel, see Figure 3.
2. Remove exhaust/combustion air inlet hoods from the cartons, located inside the blower compartment.
3. Attach blower access panel.
4. Attach the combustion air inlet/exhaust hoods with screws. Reference Figure 4 for proper location. Screws are in carton with the hood.
5. Vent the unit using the flue exhaust hood, as supplied from the factory, without alteration or addition. The only exception is with factory approved additions.
D.
COVER PANEL
INSTALLATION/ CONVERSION PROCEDURE
DOWNFLOW TO HORIZONT AL
1. Remove the screws and covers from the outside of the supply and return sections. Also remove and discard cover plate. See Figure 7.
2. Install the covers over the bottom supply and return openings, painted side up, inserting the leading flange under the bracket provided. Place the back flange to top of the front bracket provided. See Figures 10
and 11.
3. Secure the return and supply cover to front bracket with two (2) screws.
E.
FILTER REPLACEMENT
This unit is provided with 3 - 18” X 18” X 2” and 3 - 18” X 24” X 2” disposable filters. When replacing filters, ensure they are inserted fully to the back to prevent bypass. See Figure 5.
Recommended supplier of this filter is Glassfloss Industries, Inc. or
AAF International 215 Central Avenue P.O. Box 35690 Louisville, KY 40232 Phone: 1-800-501-3146 Part #: 54-42541-01 (18" x 18" x 2")
54-42541-03 (18" x 24" x 2")
FIGURE 10. HORIZONTAL CONVERSION DETAIL
ST-A0886-30
FIGURE 11. HORIZONTAL CONVERSION DETAIL
ST-A0886-31