Rheem **96MDV series, 95P series, 95MSP series Installation Instructions Manual

ISO 9001:2008
INSTALLATION INSTRUCTIONS
FOR 4 POSITION CONDENSING TWO-STAGE, COMMUNICATING GAS FURNACES W/ECM BLOWER
(-)96V SERIES & (-)(-)96MDV SERIES
U.L. and/or C.S.A. recognized fuel gas and CO (carbon monoxide) detectors are rec­ommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
Factory Use Only
92-24161-124-06
SUPERSEDES 92-24161-124-05
TABLE OF CONTENTS
1 TABLE OF CONTENTS. . . . . . . . . . . . . . . . . . . . . . . 2
2 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . 3
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
California Proposition 65 Note . . . . . . . . . . . . . . . . . . 4
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 SAFETY INFORMATION. . . . . . . . . . . . . . . . . . . . . . 6
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Contents
Important Information About Efficiency and Quality. . 7
Commonwealth of Massachusetts Note . . . . . . . . . . 8
4 LOCATION REQUIREMENTS . . . . . . . . . . . . . . . . . 9
Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Site Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Clearance Accessibility. . . . . . . . . . . . . . . . . . . . . . . 10
Clearance Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 FIELD CONVERSION . . . . . . . . . . . . . . . . . . . . . . . 12
General Conversion Instructions and Tips. . . . . . . . 12
Lists of Materials for Parts Bag and
Conversion Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Conversion Table of Contents . . . . . . . . . . . . . . . . . 14
Upflow with Vertical Vent. . . . . . . . . . . . . . . . . . . 15-16
Upflow with Left Side Vent . . . . . . . . . . . . . . . . . 17-18
Downflow with Right Vent (Non Zero Clearance)
Downflow Zero-Clearance . . . . . . . . . . . . . . . . . 23-27
Horizontal Right with Right Vent . . . . . . . . . . . . . 28-30
Horizontal Right with Vertical Vent . . . . . . . . . . . 31-33
Horizontal Left with Right Vent . . . . . . . . . . . . . . 34-38
Horizontal Left with Left Vent . . . . . . . . . . . . . . . 39-41
6 DUCTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7 VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
General Venting Requirements and Guidelines
(All Instructions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Venting and Combustion Air Piping
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Piping Requirements . . . . . . . . . . . . . . . . . . . . . . 46
Vent Pipe Sizing and Maximum Lengths . . . . 48-49
Equivalent Vent Length. . . . . . . . . . . . . . . . . . . . . 48
Polypropylene Vent Products . . . . . . . . . . . . . . . . 50
Termination Requirements . . . . . . . . . . . . . . . . . . 51
Non-Direct Venting . . . . . . . . . . . . . . . . . . . . . . . . . 52
Non-Direct Venting in an Unconfined Space . . . . 52
Non-Direct Venting in a Confined Space . . . . . . . 52
Non-Direct Venting Terminations . . . . . . . . . . . . . 55
Non-Direct Venting Termination Clearances . . . . 57
Direct Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Option 1: Standard Vertical Direct Vent
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Option 2: Standard Horizontal Direct Vent
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Option 3: Variants of Standard Horizontal
Direct Vent Termination. . . . . . . . . . . . . . . . . . . 60
Option 4: Alternate Horizontal Direct Vent
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Option 5: Variants of Alternate Horizontal
Direct Vent Termination. . . . . . . . . . . . . . . . . . . 61
Optional Termination Angles for Alt. Horizontal and Variant of Alt. Horizontal Direct-Vent Terminations (Options 4 and 5) . . . 62 Option 6 & 7: Vertical and Horizontal Concentric Vent Termination (RXGY-E02A and
RXGY-E03A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
19-22
Options 8 & 9:Sidewall Vent Kit for Direct Vent
Termination (RXGY-G02 & RXGY-G01) . . . . . . 64
Direct Venting Termination Clearances . . . . . . . . 65
Multiventing of Direct Vent Furnaces . . . . . . . . . . 66
8 CONDENSATE DRAIN AND DRAIN
NEUTRALIZER . . . . . . . . . . . . . . . . . . . . . . . . . . 67
9 GAS SUPPLY AND PIPING
Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
10 LP CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11 Setting the Gas Pressure. . . . . . . . . . . . . . . . . . . . 75
12 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . 76
Reversing the Electrical Connection . . . . . . . . . . . . 76
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
13 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Electronic Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . 78
Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
14 TWINNING (NOT PERMITTED) . . . . . . . . . . . . . . . 78
15 HIGH ALTITUDE INSTALLATIONS . . . . . . . . . . . . 80
Natural Gas at High Altitudes . . . . . . . . . . . . . . . . . . 80
LP Gas at High Altitudes. . . . . . . . . . . . . . . . . . . . . . 82
16 STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
17 SEQUENCE OF OPERATIONS . . . . . . . . . . . . . . . 83
18 INTEGRATED FURNACE CONTROL . . . . . . . . . . 84
19 HUMIDIFICATION/DEHUMIDIFICATION . . . . . . . . 86
20 DIPSWITCHES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
21 MODEL DATA CARD. . . . . . . . . . . . . . . . . . . . . . . . 92
22 DUAL 7-SEGMENT DISPLAY. . . . . . . . . . . . . . . . . 92
23 PUSHBUTTON. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
24 SUPPLY & OUTDOOR AIR TEMP SENSORS. . . . 97
25 AUXILIARY INPUTS . . . . . . . . . . . . . . . . . . . . . . . . 98
26 THERMOSTAT WIRING DIAGRAMS . . . . . . . . . . . 99
Communicating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Legacy (Non-Communicating) . . . . . . . . . . . . . . . . 101
27 FUSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
28 TIMING DIAGRAM. . . . . . . . . . . . . . . . . . . . . . . . . 103
29 ADJUSTING AND CHECKING FURNACE
INPUT RATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
30 SETTING INPUT RATE . . . . . . . . . . . . . . . . . . . . . 104
31 AIRFLOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
32 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Annual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . 107
33 REPLACEMENT PARTS. . . . . . . . . . . . . . . . . . . . 107
34 DIAGNOSTICS AND TROUBLESHOOTING . . . . 108
Normal Operation Codes . . . . . . . . . . . . . . . . . . . . 108
Fault Codes with Descriptions and Solutions . . . . 109
Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Replacing the Furnace Control. . . . . . . . . . . . . . . . 118
Diagnosing Blower Motor Issues . . . . . . . . . . . . . . 119
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . 121
Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
2
GENERAL INFORMATION
21
23
20
22
4
3
13
16
15
17
5
18
19
2
1
5
6
9
8
7
11
10
12
14
24
25
OTE: A heat loss calculation should be performed to
N
properly determine the required furnace BTU size for the structure. Also, the duct must be properly designed and in­stalled for proper airflow. Existing ductwork must be in­spected for proper size and to make sure that it is properly sealed. Proper airflow is necessary for both user comfort and equipment performance.
Before opening the furnace carton, verify that the data tags on the carton specify the furnace model number that was ordered from the distributor and are correct for the installation. If not, return the unit without open­ing the carton. If the model number is correct, open the carton and verify that the furnace rating label specifies the same furnace model number that is specified on the carton label. If the model numbers do not match, return the furnace to the distributor.
IMPORTANT: Proper application, installation and mainte­nance of this furnace and system is a must if consumers are to receive the full benefits for which they have paid.
The (-)96V and (-)(-)96MDV series furnaces are design­certified by CSA for use with natural and propane gases as follows:
FIGURE 1
FURNACE COMPONENTS
1. As non-direct vent central forced air furnaces taking ombustion air from the installation area or using air
c
ucted from the outside.
d
General Information
2. As direct vent central forced air furnaces with all com­bustion air supplied directly to the furnace burners through a special air intake system outlined in these instructions.Install this furnace in accordance with the American National Standard Z223.1 – latest edition entitled “National Fuel Gas Code” (NFPA54) or, for Canada, CSA B149.1; Canadian Natural Gas and Propane Installation Code and requirements or codes of the local utilities or other authorities having jurisdic­tion. This is available from the following:
National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269
CSA-INTERNATIONAL 5060 Spectrum Way Mississauga, Ontario Canada L4W5N6 Online: www.csa.ca
ITEM
NO. DESCRIPTION
1 CONDENSATE TRAP 2 DOOR SWITCH 3 JUNCTION BOX 4 TRANSFORMER 5 WATER SENSOR (2) 6 PRESSURE SWITCHES,
HIGH & LOW STAGE 7 EXHAUST TRANSITION 8 COUPLING (ELBOW TO TRANSITION) 9 EXHAUST
10 SHIPPING PLUG 11 FLAME SENSOR 12 OVER TEMPERATURE SWITCH 13 TOP PLATE 14 BURNER 15 IGNITER 16 COMBUSTION AIR INLET 17 GAS VALVE 18 INDUCED DRAFT BLOWER (IDB) 19 POWER FACTOR CORRECTION CHOKE
(PFC) (NOT USED ON THE 42KBTU,
56KBTU AND 70KBTU)
20 CONTROL MOUNTING PLATE 21 BLOWER 22 LOW VOLTAGE TERMINAL 23 COUPLING (IDB TO ELBOW) 24 FURNACE CONTROL
ST-A1205-01
3
GENERAL INFORMATION (cont.)
In Canada installations must comply with CSA B149.1.
Install units in Canada in accordance with CSA-B149, local installation codes and authorities having jurisdiction.
SA-B149.1 is available from:
C
CSA INTERNATIONAL 5060 Spectrum Way Mississauga, Ontario Canada L4W 5N6
online: www.csa.ca
General Information
NOTICE: Any equipment immersed in water (including by flooding) must be replaced. Equipment and products im­mersed in water will have operation adversely affected thereby voiding the warranty.
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged car­tons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate to be sure equipment matches job specifications.
• Read the entire instructions before starting the installa­tion.
• Install the unit in such a way as to allow necessary ac­cess for service.
• Always remove the solid metal base pan from the top of the furnace. The base pan is installed in this location for shipping purposes only and should never remain in the as-shipped location after installation.
• Install the unit with a 1/4” to 1/2” forward slope (toward front) to ensure proper drainage.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical
Code.
• NFPA90A Installation of Air Conditioning and Ventilat-
ing Systems.
• NFPA90B Installation of warm air heating and air con-
ditioning systems.
• In Canada CSA 22.2 Canadian Electrical Code.
• In Canada CSA B149.1; Canadian Natural Gas and
Propane Installation Code.
CALIFORNIA RESIDENTS ONLY
MPORTANT: All manufacturer products meet current
I
Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemi­cals found in, or produced by, some of our heating and air­conditioning equipment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equip­ment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the Websites for OSHA (Oc­cupational Safety and Health Administration), at www.osha.gov of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products pres­ent safety and health risks, when improperly used, han­dled and maintained.
and the State of California's OEHHA (Office
4
Installation Instructions remain with the furnace as a reference guide to the servicing contractor. We recommend that performance and installation data be recorded for future reference on this sheet to meet service and warranty
bligations so that job site information is available when required.
o
Installation Checklist
REFER TO INSTALLATION INSTRUCTIONS
GAS SUPPLY
______ Correct pipe size (record size)
______ Correct supply pressure (during furnace operation)
______ (record pressure)
______ Manifold pressure (record upstream pressure)
______ No gas leaks
______ L.P. Kit Number (if applicable) (record kit number)
ELECTRICAL
______ 115 V.A.C. supply (Dedicated Circuit)
(record voltage)
______ Polarity observed
______ Furnace properly grounded
______ Correct wire size (record type and gauge)
FURNACE INSTALLATION
______ Correct clearance to combustibles (record
______ clearance)
______ Correct clearance for service (at front) (record
______ clearance)
DUCT STATIC PRESSURE
______ in. w.c. on heating speed (record static pressure)
______ in. w.c. on cooling speed (record static pressure)
______ Air temperature rise in heat (record air temperature
______ rise)
______ Air temperature rise in cool (record air temperature
______ rise)
______ ft. of pipe – exhaust pipe (record length)
______ no. of elbows – exhaust pipe (record number of
______ elbows)
______ Exhaust Vent Temperature (record temperature)
TERMINATIONS – DIRECT VENT
VERTICAL
______ Intake – 12" [305mm] min. above roof/snow level
(record height above anticipated snow level) or, in Canada, intake and exhaust vents conform with CSA B149.1; Canadian Natural Gas and Propane Installation Code
______ Correct relationship – exhaust to intake
HORIZONTAL/VERTICAL – CONCENTRIC (RXGY-E03A)
______ Intake – 12" [305mm] min. above roof/snow level
(record height above anticipated snow level) or, in Canada, intake and exhaust vents conform with CSA B149.1; Canadian Natural Gas and Propane Installation Code
______ Exhaust sloped down toward furnace
______ Correct distances (horizontal and vertical) –
exhaust to intake
______ 12" [305mm] min. above grade/snow level (record
height above anticipated snow level) or, in Canada, intake and exhaust vents conform with CSA B149.1; Canadian Natural Gas and Propane Installation Code
______ Above anticipated snow level (record maximum
______ anticipated snow level)
VENTING – NON-DIRECT VENT
______ in. diameter – exhaust pipe (record diameter)
______ ft. of pipe – exhaust (record length)
General Information
CONDENSATE LINE
______ Trap filled with water
______ Vented
______ Sloped toward drain
______ Condensate drain line hoses connected and
______ clamped
______ Freeze protection (if necessary)
VENTING – DIRECT VENT
______ in. diameter – intake pipe (record diameter)
______ in. diameter – exhaust pipe (record diameter)
______ ft. of pipe – intake air (record length)
______ no. of elbows – intake air (record number of
______ elbows)
______ no. of elbows (record number of elbows)
TERMINATION – NON-DIRECT VENT
VERTICAL
______ 12" [305mm] min. above roof/snow level (record
height above anticipated snow level) or, in Canada, intake and exhaust vents conform with CSA B149.1; Canadian Natural Gas and Propane Installation Code
HORIZONTAL – STANDARD
______ 12" [305mm] min. above grade/snow level (record
height above anticipated snow level) or, in Canada, intake and exhaust vents conform with CSA B149.1; Canadian Natural Gas and Propane Installation Code
5
SAFETY INFORMATION
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND PO­SITION AS SPECIFIED IN THE LOCATION REQUIRE­MENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS.
WARNING
!
IMPROPER INSTALLATION, OR INSTALLATION NOT MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL (CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN RESULT IN UNSATISFACTORY OPERATION AND/OR DAN­GEROUS CONDITIONS AND ARE NOT COVERED BY THE MANUFACTURER’S WARRANTY.
Safety Information
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A SAFETY SWITCH CAUSES THE FURNACE TO SHUT DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICA­TION OF A POTENTIAL SAFETY HAZARD THAT MUST BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET SAFETY CONTROLS WITHOUT CORRECTIVE ACTION AND/OR VERIFICATION OF PROPER SAFE OPERATION BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN A NEW SAFETY SWITCH IS INSTALLED, IT MUST BE TESTED FOR A MINIMUM OF 15 MINUTES WITH THE FURNACE OPERATING AT MAXIMUM INPUT RATE AND WITH BOTH BLOWER AND BURNER DOOR INSTALLED. IF THE FURNACE IS INSTALLED IN A CLOSET, THE CLOSET DOOR MUST ALSO BE CLOSED FOR THIS TEST. REPEAT THE TEST AT THE MINIMUM INPUT RATE IF THE FURNACE IS A MULTI-STAGE FURNACE.
WARNING
!
USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUC­TIONS.
WARNING
!
COMBUSTION AND VENTILATION AIR MUST BE PRO­VIDED TO THE FURNACE AS REQUIRED BY THE NA­TIONAL FUEL-GAS CODE (U.S.) AND CSA B149.1 (CANADA) AND THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.
W
AR
N
IN
!
C
O
MB
U
STI
D
O
O
V
E
N
I
N
S
T
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO AREAS OUTSIDE THE SPACE CONTAINING THE FUR­NACE, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CASING AND TERMI­NATING OUTSIDE THE SPACE CONTAINING THE FUR­NACE.
!
WHENEVER THE FACTORY RETURN-AIR CONNECTION IS NOT USED IT MUST BE SEALED. A SOLID METAL BASE PLATE MUST BE INSTALLED AND SEALED. FAC­TORY BASE PLATES ARE AVAILABLE AS ACCESSORY ITEMS. (PART NUMBERS ARE LISTED IN THE SPEC SHEET FOR THE FURNACE.) FAILURE TO INSTALL AND SEAL THE BASE PLATE AND RETURN AIR DUCT CON­NECTIONS MAY ALLOW CARBON MONOXIDE AND OTHER CONTAMINANTS TO BE DRAWN INTO THE CON­DITIONED AIR SPACE AND DISTRIBUTED THROUGHOUT THE HEATED SPACE.
!
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY CIRCULATED DUST PAR­TICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CAR­PETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAM­AGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
!
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS REC­OMMENDED THAT AN AUXILIARY DRAIN PAN BE IN­STALLED UNDER THIS FURNACE AND ANY INSTALLED EVAPORATOR COIL THAT IS LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE FURNACE CONDENSATE DISPOSAL SYSTEM OR THE COIL DRAIN PAN OR A STOPPAGE IN THE PRIMARY CONDENSATE DRAIN PIPING.
O
R
S
.
C
O
T
S
Y
S
TE
A
LLA
TI
WARNING
WARNING
WARNING
WARNING
G
N
PR
O
D
U
C
TS
MU
S
T
B
E
D
I
S
C
H
A
R
G
E
D
O
U
N
N
E
C
T
TH
I
S
FU
R
N
A
C
E
TO
A
N
A
P
P
M
O
N
L
Y
,
A
S
S
P
EC
I
FI
E
D
I
N
O
N
S
E
C
TI
O
N
O
F
TH
E
TH
S
E
I
N
S
TR
E
U
VEN C
TI
R
O
OV
T
T
E
D
PI
P
E
N
S
.
-
6
SAFETY
WARNING
!
ALWAYS INSTALL THE FURNACE TO OPERATE WITHIN THE FURNACE’S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTER­NAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN THE DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
THE FURNACE MAY BE USED FOR HEATING OF BUILD­INGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
PROPER VENT INSTALLATION;
-
FURNACE OPERATING UNDER THERMOSTAT­CONTROL; RETURN AIR DUCT SEALED TO THE FURNACE;
-
AIR FILTERS IN PLACE;­SET FURNACE INPUT RATE AND TEMPERATURE­RISE PER RATING PLATE MARKINGS; MEANS FOR PROVIDING OUTDOOR AIR RE-
-
QUIRED FOR COMBUSTION; RETURN AIR TEMPERATURE MAINTAINED BE-
-
TWEEN 55°F (13°C) AND 80°F (27°C); AND CLEAN FURNACE, DUCT WORK AND COMPO-
-
NENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY THAT THE FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERA­TURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS AND CODES.
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air qual­ity, it is important to have the proper balance between the air supplied to each room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reduc­ing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified con­tractor for proper balance and sealing.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMO­BILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN­CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN SPACES CONTAINING FUEL BURNING AP­PLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIP­MENT AND DUCT MUST ALSO BE SEALED TO PRE­VENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPROD­UCTS INCLUDING CARBON MONOXIDE INTO THE LIV­ING SPACE.
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CON­TAIN HAZARDOUS CARBON MONOXIDE) INTO THE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Safety Information
Adapted from Residential Duct Diagnostics and Repair, with permission of Air Conditioning Contractors of America (ACCA).
7
COMMONWEALTH OF MASSACHUSETTS NOTE
IMPORTANT! THE COMMONWEALTH OF MASSACHU­SETTS REQUIRES COMPLIANCE WITH REGULATION 248 CMR 4.00 AND 5.00 FOR INSTALLATION OF THROUGH-THE-WALL VENTED GAS APPLIANCES AS FOLLOWS:
(a) For all side wall horizontally vented gas fueled equip­ment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETEC­TORS. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall ob-
Safety Information
serve that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each ad­ditional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the in­stallation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the
ide wall horizontally vented gas fueled equipment shall
s not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and sig­nage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fu­eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIP­MENT VENTING SYSTEM PROVIDED. When the manu­facturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or vent­ing system components with the equipment, the instruc­tions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIP­MENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installa­tion instructions; and
2. The “special venting systems” shall be Product Ap­proved by the Board, and the instructions for that system shall include a parts list and detailed installation instruc­tions.
(e) A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall re­main with the appliance or equipment at the completion of the installation.
8
1/4" MIN. TO 1/2" MAX. TILT
TOWARD THE FRONT
OF THE CABINET IN ALL
INSTALLATIONS AND
ORIENTATIONS
1/4" MIN. TO 1/2" MAX. TILT
TOWARD THE FRONT
OF THE CABINET IN ALL
INSTALLATIONS AND
ORIENTATIONS
UPFLOW / DOWNFLOW
HORIZONTAL (LEFT OR RIGHT)
GENERAL INFORMATION
1. IMPORTANT: If installing the unit over a finished ceil-
2. IMPORTANT: If using a cooling evaporator coil with
If these are manual dampers, they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position.
3. IMPORTANT: Furnace must be installed level from
NOTE: These furnaces are approved for installation in at­tics, as well as alcoves, utility rooms, closets and crawl­spaces. Provisions must be made to prevent freezing of condensate.
FREEZE PROTECTION
For installations where the furnace may reach tempera­tures below 32°F (0°C) (such as an alcove or attic installa­tion), the installer must take precautions to ensure that the drain trap and connected drain pipe do not freeze. Local codes and practices should be followed in order to prevent freezing.
If the drain trap is installed within the furnace cabinet, no freeze protection is required. When the trap is mounted outside or partially outside the cabinet, it must be pro-
LOCATION REQUIREMENTS
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESI­DENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO PREVENT THE RISK OF IGNIT­ING FLAMMABLE VAPORS WHICH MAY BE PRES­ENT IN A GARAGE. ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLO­SION, RESULTING IN PROPERTY DAMAGE, PER­SONAL INJURY OR DEATH.
ing or living area, be certain to install an auxiliary con­densate drain pan under the entire unit. This auxiliary drain pan should extend under any evaporator coil in­stalled with the furnace and the open portion of the condensate drain assembly. See “Condensate Drain/Neutralizer” section for more details.
this furnace, be sure the air passes over the heat ex­changer before passing over the cooling coil. The cooled air passing over the warm ambient air inside the heat exchanger tubes can cause condensation in­side the tubes resulting in corrosion and eventual fail­ure.
front-to-back or with a slight tilt such that the back of the furnace is up to 1/2” higher than the front of the furnace as shown in Figure 3.
ected from freezing. Regardless of the location of the
t drain trap, any exposed drain piping must be protected from freezing as required by local practices or codes. A UL or CSA listed heat tape or UL or CSA approved heating cable with a rating of 3-6 watts per foot is acceptable pro­tection when installed and maintained in accordance with the manufacturer’s instructions. Good installation practices necessitate that the installer verify heat tape operation in accordance with the manufacturer’s instructions at the time of installation.
IMPORTANT: Support this unit when installed. Since this furnace is suitable for attic or crawl space installation, it may be installed on combustible wood flooring or by using support brackets.
FIGURE 3
BACK FRONT
0-1/2HIGHER
THAN FRONT OF FURNACE
BACK FRONT
0-1/2HIGHER
THAN FRONT
OF FURNACE
ST-A1194-13-X0
Location
9
A
I
R
F
L
O
W
NOTE:
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION. HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
OPTION - B
2” - 3” PIPE
OPTION - A
2” PIPE
8
6
LOCATION REQUIREMENTS
GENERAL INFORMATION (cont.)
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOM­MENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS FACING UPWARDS.
SITE SELECTION
1. Select a site in the building near the center of the pro­posed, or existing, duct system.
2. Give consideration to the vent system piping when se­lecting the furnace location. Be sure the venting sys­tem can get from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas piping. See Figure 5.
4. Locate the furnace to maintain proper clearance to combustibles as shown in following Figure 6.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES. DOING SO CAN DAMAGE THE HEAT EX­CHANGER ASSEMBLY.
CLEARANCE – ACCESSIBILITY
Location
The design of forced air furnaces with input ratings as listed in the tables under Figure 6 are certified by CSA-In­ternational for the clearances to combustible materials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches (30 cm) is recom­mended in front of all furnaces.
NOTE: Use recommended 24” (30 cm) clearance if acces­sibility clearances are greater than fire protection clear­ances.
For downflow non-zero clearance furnace installations, the minimum clearance required on the right side of the fur­nace is shown in Figure 4. If this clearance cannot be maintained, a downflow zero-clearance kit; RXGY-ZK will need to be installed.
WARNING
!
UPFLOW FURNACES ARE DESIGN­INSTALLATION ON COMBUSTIBLE FLOORS. NOTE, HOWEVER, THAT FURNACES MUST NOT BE IN­STALLED DIRECTLY ON CARPETING, TILE OR OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD FLOORING. INSTALLATION ON A COM­BUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUS­ING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COM­BUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQ­UIDS. PLACEMENT OF COMBUSTIBLE MATERI­ALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES.
FIGURE 4
NOTE: These
dimensions refer to furnace clearance only. For required vent clearances and supports, refer to vent manufacturer’s instructions.
NOTE: THESE ILLUSTRATIONS ARE INTENTIONALLY GENERIC.
NOTE: SOME PARTS OF YOUR FURNACE MAY APPEAR DIFFERENT.
FIGURE 5
CLEARANCE FLUE VENT TO WALL
6
8
ST-A1194-40-X0
CERTIFIED FOR
ST-A1194-05-X0
10
FIGURE 6
TOPBOTTOM
FRONTLEFT SIDE RIGHT SIDE
RIGHT BACK TOP FRONT VENT
(-)96VA040
(-)(-)96MDV040
(-)96VA060
(-)(-)96MDV060
(-)96VA070
(-)(-)96MDV070
(-)96VA085
(-)(-)96MDV085
(-)96VA100
(-)(-)96MDV100
(-)96VA115
(-)(-)96MDV115
0 0 0 1 2 0
0 0 0 1 2 0
0 0 0 1 2 0
0 0 0 1 2 0
SHIPPING
WEIGHTS
MINIMUM CLEARANCE (IN.)
MODEL
LEFT
SIDE
UNIT DIMENSIONS
(CLEARANCE TO COMBUSTIBLES)
A
I
R
F
L
O
W
A
B
.62
.62
34.00
23.33
25.44
26.19
22.63
25.81
26.31
8.00
11.03
17.50
18.13
26.11
29.05
32.65
24.19
22.31
OPTIONAL TRAP
LOCATION
(HORIZONTAL)
OPTIONAL CONDENSATE
DRAIN (DOWNFLOW)
GAS
CONNECTION
OPTIONAL COMBUSTION
VENT LOCATION
OPTIONAL TRAP
LOCATION
(HORIZONTAL)
OPTIONAL VENT
AIR INLET
CONDENSATE DRAIN
(UPFLOW)
ELECTRICAL CONNECTION
LINE VOLTAGE
ELECTRICAL CONNECTION
LOW VOLTAGE
22.96
23.80
8.00
11.00
17.44
29.05
26.17
32.88
23.00
14.00
28.06
1.12
29.62
.62
19.83
OPTIONAL LINE VOLTAGE
WIRING
OPTIONAL LOW VOLTAGE
WIRING
OPTIONAL CONDENSATE
DRAIN (UPFLOW)
TRAP LOCATION
(HORIZONTAL)
OPTIONAL
GAS CONNECTION
OPTIONAL
CONDENSATE DRAIN
(DOWNFLOW)
1.76
1.66
24.86
26.26
B
19.83
SUPPLY
AIR
23.21
1.62
1.67
24.91
.30
C
19.77
A
.65
RETURN
AIR
OPTIONAL
VENT OUTLET
KNOCKOUT
OPTIONAL COMBUSTION
AIR INLET KNOCKOUT
SUPPLY AND RETURN DEPICTED AS UPFLOW CONFIGURATION.
FLANGE CONFIGURATION WILL VARY DEPENDING ON INS TALLATION ORIENTATION.
A B C
17 1/2 16 17/64 16 13/64
21 19 49/ 64 19 45/64
24 1/2 23 17/64 23 13/64
FLANGE DIMENSIONS
*A SERVICE CLEARANCE OF AT LEAST 24” IS RECOMMENDED IN FRONT OF ALL FURNACES
0 0 0 1 2 0
0 0 0 1 2 0
UNIT DIMENSIONS (CLEARANCE TO COMBUSTIBLES)
ST-A1194-01-X0
Location
11
FIELD CONVERSIONS
CONDENSATE PVC/HOSE OPTIONS
BULKHEAD COUPLING
CONDENSATE DRAINIAGE HAS OPTIONS FOR 3/4" OR 1/2" PVC CONNECTIONS. THE BULKHEAD COUPLING CONNECTS THE RUBBER HOSES FROM INSIDE THE UNIT TO THE PVC PIPE EXTERIOR OF THE UNIT. PVC PIPE CAN BE CEMENTED DIRECTLY TO THE COUPLING AND THE TRAP WITH PROPER PVC CEMENT AND PRIMER.
1
/2" PVC
P
IPE
3/4" PVC
TEE
RUBBER HOSE CONNECTION
PVC FITTING/PIPE
3/4" PVC
C
OUPLING
IN ADDITION TO PVC CONNECTIONS, THE CONDENSATE TRAP CAN ACCOMODATE A 5/8" RUBBER HOSE WITH A HOSE CLAMP WHEN LOCATED INSIDE THE UNIT. PLIERS ARE NECCESSARY TO ADD OR REMOVE CLAMP.
NOTE: IMPROPER HOSE CONNECTIONS WILL PREVENT CONDENSATE FROM DRAINING.
CONDENSATE TRAP
THE CONDENSATE TRAP HAS 2 SIDES PLEASE NOTE THEIR LOCATIONS FOR DRAIN CONNECTIONS DURING CONVERSION.
OUT TO DRAIN
COLLECTOR BOX
IN FROM
IN FROM FLUE
ELBOW OR COUPLING
1/4" VENT IN
FROM COLLECTOR BOX
GENERAL CONVERSION INSTRUCTIONS
ST-A1194-37-01
-2010°
CONVERSION AND INSTALLATION
C
ONSIDERATIONS
ALL CONVERSIONS REQUIRE THE CONDENSATE PLUMBING TO HAVE DECLINE IN THE DIRECTION OF THE WATER FLOW.
WHEN INSTALLING AND MOVING CONDENSATE PLUMBING THE HOSES SHOULD BE FREE OF KINKS FOR PROPER WATER FLOW.
WHEN DRAIN HOSE OR CONDENSATE TRAP HOSE ROUTING CHANGES ARE NECESSARY BE SURE TO PLUG OR CAP ANY UNUSED HOSE TAPS.
THE INDUCER COUPLING COMES FROM THE FACTORY WITH A 10
TILT FOR UP FLOW INSTALLATIONS. WHEN CONVERTED TO DOWN FLOW THE COUPLING REQUIRES A ROTATION A MINIMUM OF 10
FROM HORIZONTAL AS SHOWN.
HORIZONTAL INSTALLATIONS REQUIRE CONDENSATE TRAP TO BE MOUNTED EXTERNALLY BELOW THE UNIT:
-USE CAUTION-MOUNT THE TRAP AFTER THE UNIT IS AT THE POINT OF INSTALLATION TO PREVENT DAMAGE TO THE TRAP DURING TRANSPORT.
-HAND TIGHTEN SCREWS WHEN MOUNTING THE TRAP OR THE BULKHEAD COUPLING TO THE CABINET TO PREVENT DAMAGE TO THE MOUNTING FLANGE.
-USE PROPER FREEZE PROTECTION IF REQUIRED.
-ALLOW MINIMUM OF 6" BELOW THE FURNACE FOR CLEARANCE.
10-20°
TILT ON INDUCER COUPLING
GROUND
GROUND
LEVEL
MIDLINE
WORM DRIVE
CLAMP
COUPLING
THE WORM DRIVE FOR THE HOSE CLAMPS USED ON THE FLUE TRANSITION COUPLING OR THE IDB COUPLING MUST BE ABOVE THE LEVEL MIDLINE WHEN IN THE HORIZONTAL POSITION AS DETAILED HERE.
IF THE IDB COUPLING IS REMOVED, IT MUST BE REPLACED IN THE PROPER ORIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIRECTION OF EXHAUST FLOW. MAKE SURE THE ARROW POINTS IN THE CORRECT DIRECTION.
NOTE:
Field Conversions
12
FIELD CONVERSIONS
PARTS BAG (PROVIDED WITH UNIT)
CONVERSION KIT RXGY-CK
CONVERSION KIT RXGY-ZK
(X2)
2-5/8" FLUSH
MOUNT PLUG
1/2" DRAIN
HOSE E
INTAKE
C
OUPLING
.559" CONDENSATE
TRAP DRAIN PLUG
#8 X 1/2"
SCREW
(X2)
INTAKE
PIPE
1/4" BLACK
VENT TUBE
BULKHEAD COUPLING
HOSE DOUBLE ELBOWTUBE C
HOSE CLAMP
INTAKE AIR
DIFFUSER
#8 X 1/2"
SCREW
(
X4)
#8 X 1/2"
SCREW
(X10)
5/8" DRAIN
HOSE B
CONDENSATE TRAP
BRACKET (DOWN FLOW)
2" PVC VANE
1/4" HOLE
PLUG
1/2" DRAIN
HOSE F
1/2" DRAIN
HOSE G
CONDENSATE TRAP GASKET
2" PIPE GROMMET
(
3.375)
1/2" VINYL
CAP (YELLOW)
PIPE COLLAR
GASKET ASSEMBLY
(X2)
ST-A1194-38-03
GENERAL PARTS REQUIRED FOR CONVERSIONS
(X3)
FLUE PIPE ASSEMBLY W/ O-RING
O-RING
Field Conversions
SEE NEXT PAGE FOR APPLICABLE CONFIGURATIONS
13
FIELD CONVERSIONS
AIRFLOW
AIRFLOW
AIRFLOW
AIRFLOW
FIELD CONVERSION TO VARIOUS CONFIGURATIONS
Furnaces can be converted in the field from upflow (as-shipped) to downflow, horizontal left or horizontal right as necessary. In addition, there are different venting options, including a zero-clearance option, to give the installer flexibility in locating the venting for this furnace.
LISTS OF MATERIALS FOR PARTS BAGS AND CONVERSION KITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 12
GENERAL CONVERSION INSTRUCTIONS AND TIPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 13
UPFLOW WITH VERTICAL VENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 15-16
UPFLOW WITH LEFT SIDE VENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 17-18
(REQUIRES CONVERSION KIT RXGY-CK)
DOWNFLOW WITH RIGHT VENT (NON-ZERO CLEARANCE). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 19-22
(REQUIRES CONVERSION KIT RXGY-CK)
DOWNFLOW ZERO-CLEARANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 23-27
(REQUIRES CONVERSION KIT RXGY-CK AND ZERO­CLEARANCE KIT RXGY-ZK)
HORIZONTAL RIGHT WITH RIGHT VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 28-30
(REQUIRES CONVERSION KIT RXGY-CK)
HORIZONTAL RIGHT WITH VERTICAL VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 31-33
(REQUIRES CONVERSION
Field Conversions
KIT RXGY-CK)
HORIZONTAL LEFT WITH RIGHT VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 34-38
(REQUIRES CONVERSION
KIT RXGY-CK AND ZERO-
CLEARANCE KIT RXGY-ZK)
HORIZONTAL LEFT WITH LEFT VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pg 39-41
(REQUIRES CONVERSION
KIT RXGY-CK)
14
IRFLOW
A
AIRFLOW
AIRFLOW
AIRFLOW
TUBE C
CUT TO FIT
CABINET WIDTH
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
4B
4b - RIGHT SIDE DRAIN OPTION
4b1 - CUT TUBE “C” TO FIT CORRESPONDING CABINET WIDTH. 4b2 - INSERT TUBE “C” INTO END “2” OF HOSE- DOUBLE ELBOW 4b3 - SLIDE TWO WIRE CLAMPS OVER TUBE “C”, SLIDE ONE WIRE CLAMP OVER END “1” OF HOSE - DOUBLE ELBOW. 4b4 - INSTALL TUBE “C” WITH HOSE CLAMP AS SHOWN TO HOSE “A” “PRE ASSEMBLED”. 4b5 - ATTACH HOSE - DOUBLE ELBOW TO BULKHEAD COUPLING POSITION WIRE HOSE CLAMP.
HOSE A
TUBE C
4A
HOSE A
4a - LEFT SIDE DRAIN OPTION
ATTACH HOSE A (PRE-INSTALLED) TO BULKHEAD COUPLING. INSTALL HOSE CLAMP ON HOSE OVER BULK HEAD COUPLING.
3
INSTALL BULKHEAD COUPLING USING (2) SCREWS. INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
INSTALL
2
OPTION DRAIN RIGHT
DETERMINE RIGHT OR LEFT DRAIN OPTION. LOCATE 7/8" HOLE IN JACKET SIDE. REMOVE PLUG - DISCARD. DRILL (2) Ø 1/8" HOLES FOR THE BULKHEAD COUPLING.
DRILL 1/8”
DRILL 1/8”
7
/8” PLUG
D
ISCARD
OPTION DRAIN LEFT
7/8” PLUG
DISCARD
1
INSTALL INTAKE COUPLING IN TOP PLATE.
INSTALL
UPFLOW VERTICAL VENT
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
ST-A1194-28-03
PARTS NEEDED:
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS FROM THE PARTS BAG ONLY. NO OTHER CONVERSION KITS ARE NEEDED.
!
TUBE C
B
ULKHEAD
COUPLING
FROM PARTS BAG (PROVIDED WITH UNIT)
(X2)
#8 X 1/2"
SCREW
H
OSE
CLAMP
INTAKE
COUPLING
W/ NUT
DRILL
1/8" DRILL BIT
PLIERS
1/4" HEX HEAD DRIVER
TUBING CUTTER
TOOLS/MATERIALS NEEDED:
" * 3
'
- 0 8
(X3)
(X3)
HOSE -
DOUBLE ELBOW
1
2
HOSE -
D
OUBLE ELBOW
Field Conversions
15
ST-A1194-28-03
Notes:
Checklist:
__ ALL DRAIN PORTS ARE PLUGGED
__ UNIT HAS FORWARD PITCH
__ HEAT TAPE INSTALLED(IF REQUIRED)
__ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED.
__ CONFIRM THAT ALL HOSES ARE FREE OF KINKS
__ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW
__ ALL CLAMPS AND COUPLINGS ARE TIGHTENED
Field Conversions
16
DRILL 1/8" DRILL BIT
PLIERS FLAT HEAD SCREWDRIVER
5/16 HEX HEAD DRIVER
1/4" HEX HEAD DRIVER
TUBING CUTTER
TOOLS/MATERIALS NEEDED:
UPFLOW LEFT VENT
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
ST-A1194-29-03
PARTS NEEDED:
(X2)
FROM PARTS BAG (PROVIDED W/UNIT)
INTAKE
COUPLING
W/ NUT
BULKHEAD
COUPLING
#8 X 1/2"
SCREW
TUBE C
HOSE
CLAMP
4
INSTALL BULKHEAD COUPLING USING (2) SCREWS. INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
3
DETERMINE RIGHT OR LEFT DRAIN OPTION. LOCATE 7/8" HOLE IN JACKET SIDE. REMOVE PLUG - DISCARD. DRILL (2)
ø1/8" HOLES FOR THE BULKHEAD COUPLING.
DRILL 1/8”
DISCARD
OPTION DRAIN RIGHT
DRILL 1/8”
DISCARD
OPTION DRAIN LEFT
2
2a - INSTALL 2-5/8" FLUSH MOUNT PLUG IN TOP PLATE. 2b - INSTALL 2" PIPE GROMMET AS SHOWN. 2c - INSTALL INTAKE COUPLING AS SHOWN.
2b
2c
2
a
2-5/8”
1a
1b
1c
1
1a - REMOVE FLUE TRANSITION, TRANSITION COUPLING, AND ELBOW.
(NOTE: REMOVE INDUCER COUPLING W/ELBOW FOR EASIER REMOVAL).
1b - REMOVE 3-3/8" FLUSH MOUNT PLUG FROM JACKET - DISCARD. 1c - RELOCATE 2-3/8" FLUSH MOUNT PLUG FROM JACKET TO TOP PLATE.
R
E
-LO
C
A
T
E
DISCARD
IDB COUPLING
(RETAIN)
FLUE TRANSITION (DISCARD)
TRANSITION COUPLING (DISCARD)
ELBOW (DISCARD)
FROM CONVERSION KIT RXGY-CK
2-3/8" PIPE
G
ROMMET
2-5/8" FLUSH MOUNT PLUG
PARTS NEEDED FOR THIS CONVERSION REQUIRE THE OUTLINED ITEMS FROM THE PARTS BAG AND CONVERSION KIT RXGY-CK. YOU MUST HAVE THESE PARTS BEFORE PROCEEDING.
!
" * 3 '
- 0 8
IF THE IDB COUPLING IS REMOVED, IT MUST BE REPLACED IN THE PROPER ORIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIRECTION OF EXHAUST FLOW. MAKE SURE THE ARROW POINTS IN THE CORRECT DIRECTION.
NOTE:
(X3)
HOSE -
DOUBLE
ELBOW
SEE CRITICAL HOSE CLAMP LOCATION NOTE IN THE GENERAL COVERSION INSTRUCTIONS.
Field Conversions
17
(
X3)
5B
HOSE A
T
UBE C
T
UBE C
C
UT TO FIT
CABINET WIDTH
5A
HOSE A
5
a - LEFT SIDE DRAIN OPTION
ATTACH HOSE A (PRE-INSTALLED) TO BULKHEAD COUPLING. P
LACE CLAMP OVER HOSE ON BULKHEAD COUPLING.
Checklist:
ST-A1194-29-03
Notes:
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
HOSE -
DOUBLE ELBOW
1
2
5b - RIGHT SIDE DRAIN OPTION
5b1 - CUT TUBE “C” TO FIT CORRESPONDING CABINET WIDTH. 5b2 - INSERT TUBE “C” INTO END “2” OF HOSE- DOUBLE ELBOW 5b3 - SLIDE TWO WIRE CLAMPS OVER TUBE “C”, SLIDE ONE WIRE CLAMP OVER END “1” OF HOSE - DOUBLE ELBOW. 5b4 - INSTALL TUBE “C” WITH HOSE CLAMP AS SHOWN TO HOSE “A” “PRE ASSEMBLED”. 5b5 - ATTACH HOSE - DOUBLE ELBOW TO BULKHEAD COUPLING POSITION WIRE HOSE CLAMP.
__ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED.
__ CONFIRM THAT ALL HOSES ARE FREE OF KINKS.
__ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW
__ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP OF THE COUPLING. SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTRUCTIONS AT THE BEGINNING OF THIS SECTION.
__ ALL CLAMPS AND COUPLINGS ARE TIGHTENED
__ ALL DRAIN PORTS ARE PLUGGED
__ UNIT HAS FORWARD PITCH
__ HEAT TAPE INSTALLED(IF REQUIRED)
Field Conversions
18
DOWNFLOW W/ RIGHT VENT (NON-ZERO CLEARANCE)
DOWNFLOW W/ RIGHT VENT (NON-ZERO CLEARANCE)
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
DOWNFLOW W/ RIGHT VENT (NON-ZERO CLEARANCE)
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
DOWNFLOW W/ RIGHT VENT (NON-ZERO CLEARANCE)
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
DOWNFLOW W/ RIGHT VENT (NON-ZERO CLEARANCE)
PARTS NEEDED:
(X2)
F
ROM PARTS BAG (PROVIDED WITH UNIT)
3
*
"
8
0
-
'
(X3)
FROM THE YOU MUST HAVE THE PARTS OUTLINED BELOW BEFORE PROCEEDING.
!
PARTS NEEDED:
F
ROM PARTS BAG (PROVIDED WITH UNIT)
FROM THE PARTS BAG AND CONVERSION KIT YOU MUST HAVE THE PARTS OUTLINED BELOW BEFORE PROCEEDING.
HOSE -
D
OUBLE
ELBOW
AND CONVERSION KIT RXGY-CK.
YOU MUST HAVE THE PARTS OUTLINED BELOW BEFORE
FROM CONVERSION KIT RXGY-CK
2-5/8" FLUSH
2" PIPE GROMMET
#8 X 1/2"
SCREW
HOSE
CLAMP
FROM CONVERSION KIT RXGY-CK
2-5/8" FLUSH
#
8 X 1/2"
SCREW
(X4)
TUBE C
CONDENSATE TRAP DRAIN PLUG .559”
COUPLING
INTAKE AIR
DIFFUSER
CONDENSATE
TRAP BRACKET
INTAKE
COUPLING
W/ NUT
BULKHEAD COUPLING
1/4" BLACK
CONDENSATE
TRAP BRACKET
NOTE: STEPS 1- 5 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
DRILL (1) 1/8" DRILL BIT
TOOLS/MATERIALS NEEDED:
2-5/8" FLUSH
MOUNT PLUG
(
3.375)
NOTE: STEPS 1- 5 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
(1) 3/16" DRILL BIT PLIERS
TOOLS/MATERIALS NEEDED:
2-5/8" FLUSH
MOUNT PLUG
NOTE: STEPS 1- 5 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
(1) 1/4" HEX HEAD DRIVER (1) 5/16 HEX HEAD DRIVER
TOOLS/MATERIALS NEEDED:
5/8" DRAIN
HOSE B
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
FLAT HEAD SCREWDRIVER
TUBING CUTTER
TRAP BRACKET
(DOWN FLOW)
1/2" DRAIN
HOSE E
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
FLAT HEAD SCREWDRIVER
1/4" BLACK
VENT TUBE
TRAP BRACKET
(DOWN FLOW)
1
1a
TRANSITION COUPLING (DISCARD)
FLUE TRANSITION (DISCARD)
ELBOW (DISCARD)
IDB COUPLING (RETAIN)
2
2-5/8"
TRANSITION COUPLING (DISCARD)
FLUE TRANSITION (DISCARD)
ELBOW (DISCARD)
IDB COUPLING (RETAIN)
2d
2-5/8"
INSTALL
1b
VENT HOSE (DISCARD)
HOSE “D” (RETAIN)
DISCARD
2a
VENT HOSE (DISCARD)
HOSE “D” (RETAIN)
IF THE IDB COUPLING IS REMOVED, IT MUST BE REPLACED IN THE PROPER ORIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIREC-
NOTE:
2c
IF THE IDB COUPLING IS REMOVED, IT MUST BE REPLACED IN THE PROPER ORIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIREC-
M
O
V
2b
1a - REMOVE FLUE TRANSITION, TRANSITION COUPLING, AND ELBOW.
(NOTE: REMOVE COUPLING ON INDUCER WITH ELBOW FOR EASIER REMOVAL)
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE:TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
1a - REMOVE FLUE TRANSITION, TRANSITION COUPLING, AND ELBOW.
(NOTE: REMOVE COUPLING ON INDUCER WITH ELBOW FOR EASIER REMOVAL)
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE:TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
2a-REMOVE 3-3/8" FLUSH MOUNT PLUG FROM JACKET - DISCARD. 2b-RELOCATE 2-3/8" FLUSH MOUNT PLUG FROM JACKET TO TOP PLATE. 2c-RELOCATE 1/2" VINYL CAP (YELLOW) IN INDUCER COUPLING. 2d-INSTALL 2-5/8" FLUSH PLUG IN TOP PLATE.
1a - REMOVE FLUE TRANSITION, TRANSITION COUPLING, AND ELBOW.
(NOTE: REMOVE COUPLING ON INDUCER WITH ELBOW FOR EASIER REMOVAL).
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE:TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
TION OF EXHAUST FLOW. MAKE SURE THE ARROW POINTS IN THE CORRECT DIRECTION.
2a-REMOVE 3-3/8" FLUSH MOUNT PLUG FROM JACKET - DISCARD. 2b-RELOCATE 2-3/8" FLUSH MOUNT PLUG FROM JACKET TO TOP PLATE. 2c-RELOCATE 1/2" VINYL CAP (YELLOW) IN INDUCER COUPLING. 2d-INSTALL 2-5/8" FLUSH PLUG IN TOP PLATE.
TION OF EXHAUST FLOW. MAKE SURE THE ARROW POINTS IN THE CORRECT
ST-A1194-30-02
2a-REMOVE 3-3/8" FLUSH MOUNT PLUG FROM JACKET - DISCARD. 2b-RELOCATE 2-3/8" FLUSH MOUNT PLUG FROM JACKET TO TOP PLATE. 2c-RELOCATE 1/2" VINYL CAP (YELLOW) IN INDUCER COUPLING.
Field Conversions
19
ST-A1194-30-02
ROTATE UNIT
5b
5a
5a - PRE-DRILL (2) Ø 3/16" HOLES IN JACKET AS SHOWN FOR CONDENSATE TRAP BRACKET. 5b - ROTATE UNIT 180°
DRILL (2)
Ø3/16" HOLES
5
.559
DRAIN PLUG
4c
4a
4b
DISCARD
4a - REMOVE THE SMALL MOUNTING BRACKET AND THE .403" DRAIN PLUG - DISCARD. 4b - INSTALL THE DOWN FLOW CONDENSATE TRAP BRACKET WITH (2) SCREWS AS SHOWN. 4c - INSTALL .559" DRAIN PLUG IN THE CONDENSATE TRAP.
4
3d
3c
3a
3
b
3a - RELOCATE .403" DRAIN PLUG IN THE COLLECTOR BOX. 3b - INSTALL 2" PIPE GROMMET 3c - INTAKE COUPLING IN JACKET AS SHOWN. 3d - INSERT AIR DIFFUSER INTO COUPLING UNTIL TABS ARE SEATED.
3
INSERT AIR DIFFUSER UNTIL TABS ARE FULLY SEATED
INSTALL
M
O
V
E
NOTE: DIFFUSER MAY HAVE A TENDENCEY TO FALL OUT OF THE COUPLING AT THIS STEP. THE INSTALLER MAY ELECT TO INSTALL THE DIFFUSER AFTER ROTATING THE FURNACE TO THE HORIZONTAL POSITION.
Field Conversions
20
9b - RIGHT SIDE DRAIN OPTION ATTACH HOSE A (FACTORY INSTALLED) TO BULKHEAD COUPLING.
OPTION
9b
DRAIN RIGHT SIDE
HOSE A
ATTACH SIDE "2" TO BULKHEAD COUPLING
OPTION
DRAIN LEFT SIDE
9a
TUBE C
CUT TO FIT
CABINET WIDTH
1
2
TUBE C
HOSE B
8
INSTALL BULKHEAD COUPLING USING (2) SCREWS. INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
INSTALL
1/8" DRILL
DISCARD
7/8" PLUG
1/8" DRILL
DISCARD
7/8" PLUG
DETERMINE RIGHT OR LEFT DRAIN OPTION. LOCATE 7/8" HOLE IN JACKET SIDE AND REMOVE PLUG - DISCARD. DRILL (2)
1/8" HOLES FOR BULKHEAD COUPLING.
OPTION: RIGHT DRAIN
OPTION: LEFT DRAIN
7
6
b
6
e
6
d
6
c
6
HOSE E
HOSE D
6b - INSTALL CONDENSATE TRAP BY MOUNTING BRACKET TO JACKET USING (2) SCREWS 6c - CUT 1/4” VENT TUBE TO FIT (APPROX. 10-1/2"). INSTALL AS SHOWN. 6d - INSTALL HOSE D (REMOVED IN STEP 1) FROM INDUCER COUPLING TO THE FLUE TAP IN THE CONDENSATE TRAP. 6e - INSTALL HOSE E FROM COLLECTOR BOX TO TOP OF CONDENSATE TRAP.
-2010°
APPROXIMATELY 10-20° TILT
O
N INDUCER COUPLING
GROUND
ROTATE INDUCER COUPLING TO ENSURE DOWNWARD FLOW OF CONDENSATE FROM FLUE VENTING
6a
N
OTE:
USE SOAPY WATER TO FACILITATE EASY
H
OSE AND TUBE ASSEMBLY
1/4” TUBE CUT
TO FIT (APPROX
10-1/2”)
ST-A1194-30-02
NOTE: REMAINING STEPS SHOWN WITH FURNACE IN DOWN FLOW ORIENTATION
S
EE CRITICAL HOSE CLAMP LOCATION NOTE
IN THE GENERAL COVERSION INSTRUCTIONS.
(X3)
9a - LEFT SIDE DRAIN OPTION.
9a-1 - REMOVE HOSE “A” (FACTORY INSTALLED) ON CONDENSATE TRAP & REPLACE WITH HOSE “B” REUSING SUPPLIED CLAMP. 9a-2 - CUT TUBE “C” ON MARKED LINES CORRESPONDING TO CABINET WIDTH. 9a-3 - SLIDE (2) WIRE CLAMPS OVER TUBE “C” AND (1) WIRE CLAMP OVER SIDE “2” OF HOSE-DOUBLE ELBOW. 9a-4 - CONNECT HOSE - DOUBLE ELBOW END “1” TO TUBE “C”, CONNECT END “2” TO BULKHEAD COUPLING. CONFIRM ALL (4) CLAMPS ARE PLACED CORRECTLY.
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
Field Conversions
21
ST-A1194-30-02
Notes:
Checklist:
__ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED.
_
_ ALL DRAIN PORTS ARE PLUGGED
__ UNIT HAS FORWARD PITCH
__ HEAT TAPE INSTALLED(IF REQUIRED)
__ CONFIRM THAT ALL HOSES ARE FREE OF KINKS
__ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW
__ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP OF THE COUPLING. SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTRUCTIONS AT THE BEGINNING OF THIS SECTION
__ ALL CLAMPS AND COUPLINGS ARE TIGHTENED
__ DOUBLE CHECK DIFFUSER IS INSTALLED IN INTAKE COUPLING
Field Conversions
22
DOWN FLOW ZERO CLEARANCE
DOWN FLOW ZERO CLEARANCE
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS FROM THE PARTS BAG
!
DOWN FLOW ZERO CLEARANCE
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
PARTS BAG, CONVERSION KIT RXGY-CK
DOWN FLOW ZERO CLEARANCE
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
AND RXGY-ZK
FROM PARTS BAG(PROVIDED W/UNIT)
COUPLING
3
*
"
8
0
-
'
PARTS NEEDED:
FROM PARTS BAG(PROVIDED W/UNIT)
INTAKE
COUPLING
W/ NUT
BULKHEAD COUPLING
PARTS NEEDED:
FROM PARTS BAG(PROVIDED W/UNIT)
#8 X 1/2" SCREW
(X2)
HOSE
C
LAMP
PARTS NEEDED:
FROM THE PARTS BAG YOU MUST HAVE THE OUTLINED PARTS FROM THESE KITS BEFORE PROCEEDING.
!
(X3)
TUBE C
PARTS BAG, CONVERSION KIT RXGY-CK
YOU MUST HAVE THE OUTLINED PARTS FROM THESE KITS BEFORE PROCEEDING.
HOSE -
DOUBLE ELBOW
INTAKE AIR
DIFFUSER
AND RXGY-ZK.
YOU MUST HAVE THE OUTLINED PARTS FROM THESE KITS BEFORE PROCEEDING.
HOSE -
DOUBLE ELBOW
F
ROM CONVERSION KIT RXGY-CK
2-5/8" FLUSH
MOUNT PLUG
#8 X 1/2"
SCREW
(X4)
FROM ZERO-CLEARANCE CONVERSION KIT RXGY-ZK
F
ROM CONVERSION KIT RXGY-CK
1/4" BLACK
VENT TUBING
#8 X 1/2"
SCREW
FROM ZERO-CLEARANCE CONVERSION KIT RXGY-ZK
.559" CONDENSATE
TRAP DRAIN PLUG
5/8" DRAIN
HOSE B
1/2" DRAIN
HOSE E
.559" CONDENSATE
TRAP DRAIN PLUG
CONDENSATE
TRAP BRACKET
(
DOWN FLOW)
O-RING
#8 X 1/2"
SCREW
(X10)
ELECTRIC DRILL
TOOLS/MATERIALS NEEDED:
PIPE
COLLAR/GASKET
ASSEMBLY
(X2)
TOOLS/MATERIALS NEEDED:
3/16" DRILL BIT
INTAKE
PIPE
TOOLS/MATERIALS NEEDED:
TUBING CUTTER 1/4" HEX HEAD DRIVER 5/16 HEX HEAD DRIVER
INTAKE
FLUE PIPE
ASSEMBLY
PVC GLUE AND PRIMER HAMMER
1/4" HEX HEAD DRIVER 5/16 HEX HEAD DRIVER
W/ O-RING
FLUE PIPE
ASSEMBLY
PVC GLUE AND PRIMER
W/ O-RING
O-RING
1/8" DRILL BIT
1
NOTE: STEPS 1- 4 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
PLIERS
TRANSITION COUPLING (RETAIN)
FLUE TRANSITION (DISCARD)
ELBOW “RETAIN”
NOTE: STEPS 1- 4 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
5/16 HEX HEAD DRIVER
TRANSITION COUPLING (RETAIN)
FLUE TRANSITION (DISCARD)
ELBOW “RETAIN”
2
2a
NOTE: STEPS 1- 4 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
FLAT HEAD SCREWDRIVER
5/16 HEX HEAD DRIVER
2-5/8"
2a
INSTALL
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
FLAT HEAD SCREWDRIVER
O
V
E
2c
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
1a
1b
IDB COUPLING (RETAIN)
VENT HOSE (RETAIN)
HOSE “D” (RETAIN)
IDB COUPLING (RETAIN)
VENT HOSE (RETAIN)
HOSE “D” (RETAIN)
M
O
2d
1a - REMOVE ELBOW, (2) COUPLINGS, AND FLUE TRANSITION. (RETAIN ELBOW AND COUPLINGS FOR LATER USE.)
(NOTE: REMOVE COUPLING ON INDUCER WITH ELBOW FOR EASIER REMOVAL).
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE: TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
1a - REMOVE ELBOW, (2) COUPLINGS, AND FLUE TRANSITION. (RETAIN ELBOW AND COUPLINGS FOR LATER USE.)
(NOTE: REMOVE COUPLING ON INDUCER WITH ELBOW
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE: TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
1b - REMOVE TRAP AND HOSES. RETAIN HOSE D FOR LATER USE.
(NOTE: TO REMOVE TRAP REMOVE (2) SCREWS AND PULL STRAIGHT OUT).
2a - INSTALL 2-5/8" FLUSH MOUNT PLUG.
2b - REMOVE LEFT 2-3/8" FLUSH PLUG IN BLOWER SHELF - DISCARD.
2c - RELOCATE RIGHT 2-3/8" FLUSH MOUNT PLUG FROM BLOWER SHELF TO TOP PLATE.
2d - RELOCATE .403" DRAIN PLUG IN THE COLLECTOR BOX.
2a - INSTALL 2-5/8" FLUSH MOUNT PLUG.
2b - REMOVE LEFT 2-3/8" FLUSH PLUG IN BLOWER SHELF - DISCARD.
2c - RELOCATE RIGHT 2-3/8" FLUSH MOUNT PLUG FROM BLOWER SHELF TO TOP PLATE.
2d - RELOCATE .403" DRAIN PLUG IN THE COLLECTOR BOX.
DISCARD
2b
2b - REMOVE LEFT 2-3/8" FLUSH PLUG IN BLOWER SHELF - DISCARD.
2c - RELOCATE RIGHT 2-3/8" FLUSH MOUNT PLUG FROM BLOWER SHELF TO
2d - RELOCATE .403" DRAIN PLUG IN THE COLLECTOR BOX.
ST-A1194-31-04
Field Conversions
23
3
4
IF THE IDB COUPLING IS REMOVED, IT MUST BE REPLACED IN THE PROPER O
RIENTATION. AN ARROW IS
NOTE: IF THE IDB COUPLING IS
REMOVED, IT MUST BE REPLACED IN THE PROPER O
RIENTATION. AN ARROW IS
NOTE:
ST
ALL
4a
O
4
b
O
RIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIREC­TION OF EXHAUST FLOW. MAKE SURE THE ARROW P
OINTS IN THE CORRECT
DIRECTION.
O
RIENTATION. AN ARROW IS PRESENT ON THE COUPLING TO INDICATE THE DIREC­TION OF EXHAUST FLOW. MAKE SURE THE ARROW P
OINTS IN THE CORRECT
DIRECTION.
5
INSTALL HOSE E ON COLLECTOR BOX AS SHOWN. LET THE OPEN END HANG FREE UNTIL STEP 11.
NOTE: USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
RELOCATE JUNCTION BOX AND DOOR SWITCH SEE ELECTRICAL WIRING SECTION
REMOVE KNOCKOUTS
INSTALL HOSE E ON COLLECTOR BOX AS SHOWN. LET THE OPEN END HANG FREE UNTIL STEP 11.
USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
RELOCATE JUNCTION BOX AND DOOR SWITCH SEE ELECTRICAL WIRING SECTION
REMOVE KNOCKOUTS
5
b
4a - RE-INSTALL ELBOW AND COUPLINGS (REMOVED IN STEP 1) IN THE ORIENTATION AS SHOWN. 4b - RELOCATE 1/2" VINYL CAP (YELLOW) ON INDUCER COUPLING TO OPPOSITE SIDE.
NOTE: LEAVE COUPLING CLAMP CONNECTIONS LOOSE UNTIL STEP 11.
USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
RELOCATE JUNCTION BOX AND DOOR SWITCH
4a - RE-INSTALL ELBOW AND COUPLINGS (REMOVED IN STEP 1) IN THE ORIENTATION AS SHOWN. 4b - RELOCATE 1/2" VINYL CAP (YELLOW) ON INDUCER COUPLING TO
NOTE: LEAVE COUPLING CLAMP CONNECTIONS LOOSE UNTIL STEP 11.
4a - RE-INSTALL ELBOW AND COUPLINGS (REMOVED IN STEP 1) IN THE
4b - RELOCATE 1/2" VINYL CAP (YELLOW) ON INDUCER COUPLING TO
NOTE: LEAVE COUPLING CLAMP CONNECTIONS LOOSE UNTIL STEP 11.
ROTATE UNIT
5a
SEE ELECTRICAL WIRING SECTION FOR INSTRUCTIONS
5c
SEE ELECTRICAL WIRING SECTION FOR INSTRUCTIONS
5c
DRILL (2)
1/8" HOLES IN BLOWER SHELF
5d
6
5a - ROTATE UNIT 180° 5b - REMOVE KNOCKOUTS WITH HAMMER AND FLAT HEAD SCREWDRIVER. 5c - THE JUNCTION BOX WILL HAVE TO BE RELOCATED FOR FLUE PIPE INSTALLATION.
SEE ELECTRICAL WIRING SECTION FOR INSTRUCTIONS. 5d - RE-DRILL (2) Ø1/8" HOLES IN BLOWER SHELF AS SHOWN FOR FLUE PIPE ASSEMBLY. 5e - PRE-DRILL (2) Ø3/16" HOLES IN JACKET AS SHOWN FOR CONDENSATE TRAP BRACKET.
5b - REMOVE KNOCKOUTS WITH HAMMER AND FLAT HEAD SCREWDRIVER. 5c - THE JUNCTION BOX WILL HAVE TO BE RELOCATED FOR FLUE PIPE INSTALLATION.
SEE ELECTRICAL WIRING SECTION FOR INSTRUCTIONS. 5d - RE-DRILL (2) Ø1/8" HOLES IN BLOWER SHELF AS SHOWN FOR FLUE PIPE ASSEMBLY. 5e - PRE-DRILL (2) Ø3/16" HOLES IN JACKET AS SHOWN FOR CONDENSATE TRAP BRACKET.
7
7b
5b - REMOVE KNOCKOUTS WITH HAMMER AND FLAT HEAD SCREWDRIVER. 5c - THE JUNCTION BOX WILL HAVE TO BE RELOCATED FOR FLUE PIPE INSTALLATION.
5d - RE-DRILL (2) Ø1/8" HOLES IN BLOWER SHELF AS SHOWN FOR FLUE PIPE ASSEMBLY. 5e - PRE-DRILL (2) Ø3/16" HOLES IN JACKET AS SHOWN FOR CONDENSATE TRAP BRACKET.
DRILL (2)
3/16" HOLES
5e
DIFFUSER FULLY SEATED
.559
DRAIN PLUG
(X2)
.559
DRAIN PLUG
7a
7c
DISCARD
7c
FULLY SEATED
INSTALL INTAKE COUPLING IN BLOWER SHELF HOLE AS SHOWN.
INSERT AIR DIFFUSER INTO COUPLING UNTIL TABS ARE SEATED.
INSTALL INTAKE COUPLING IN BLOWER
INSERT AIR DIFFUSER INTO COUPLING
7a - REMOVE THE SMALL MOUNTING BRACKET AND THE .403" DRAIN PLUG - DISCARD.
7b - INSTALL .559" DRAIN PLUG IN CONDENSATE TRAP.
7c - INSTALL DOWN FLOW CONDENSATE TRAP BRACKET WITH (2) SCREWS AS SHOWN.
7a - REMOVE THE SMALL MOUNTING BRACKET AND THE .403" DRAIN PLUG - DISCARD.
7b - INSTALL .559" DRAIN PLUG IN CONDENSATE TRAP.
7c - INSTALL DOWN FLOW CONDENSATE TRAP BRACKET WITH (2) SCREWS AS SHOWN.
7a - REMOVE THE SMALL MOUNTING BRACKET AND THE .403" DRAIN PLUG - DISCARD.
7c - INSTALL DOWN FLOW CONDENSATE TRAP BRACKET WITH (2) SCREWS AS SHOWN.
ST-A1194-31-04
Field Conversions
24
8
1
/8" DRILL
1/8" DRILL
DISCARD
DISCARD 7/8" PLUG
9
DETERMINE RIGHT OR LEFT DRAIN OPTION. LOCATE 7/8" HOLE IN JACKET SIDE REMOVE PLUG - DISCARD. DRILL (2)
1/8" HOLES FOR THE BULKHEAD COUPLING.
LEFT DRAIN OPTION
7/8" PLUG
DETERMINE RIGHT OR LEFT DRAIN OPTION. LOCATE 7/8" HOLE IN JACKET SIDE REMOVE PLUG - DISCARD.
1/8" HOLES FOR THE BULKHEAD COUPLING.
LEFT DRAIN OPTION
RIGHT DRAIN OPTIONRIGHT DRAIN OPTION
INSTALL BULKHEAD COUPLING USING (2) SCREWS. INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
INSTALL BULKHEAD COUPLING USING (2) SCREWS. INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
INSTALL IN JACKET WITH THE BARBED FITTING POINTED INTO THE VESTIBULE.
10
COVER PLATE
“BOTTOM
10a
“BOTTOM”
PRE-DRILL 1/8"
HOLES AND
ATTACH W/SCREWS
(2) PLACES
X10
O-RING
PVC GLUE JOINTPVC GLUE JOINT
10b
INSTALL SCREWS
10c
10a - INSTALL INTAKE PIPE
SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS SHOWN
10b - INSTALL FLUE PIPE ASSEMBLY
INSERT FLUE PIPE ASSEMBLY THROUGH RIGHT SIDE KNOCKOUT ON COVER PLATE (NOTE: SLIDE FROM UNDER PLATE).
SLIDE ANGLED END THROUGH OPENING IN BLOWER SHELF AND ALIGN WITH ELBOW COUPLING.
SECURE PIPE ASSEMBLY TO BLOWER SHELF WITH (2) SCREWS AS SHOWN. ENSURE O-RING IS PROPERLY SEATED.
10c - SLIDE PIPE COLLAR ASSEMBLIES FROM STEP 7 OVER THE (2) PIPES AND DRILL (8)
PVC GLUE JOINT
SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS SHOWN
10b - INSTALL FLUE PIPE ASSEMBLY
INSERT FLUE PIPE ASSEMBLY THROUGH RIGHT SIDE KNOCKOUT ON COVER PLATE (NOTE: SLIDE FROM UNDER PLATE).
SLIDE ANGLED END THROUGH OPENING IN BLOWER SHELF AND ALIGN WITH ELBOW COUPLING.
SECURE PIPE ASSEMBLY TO BLOWER SHELF WITH (2) SCREWS AS SHOWN. ENSURE O-RING IS PROPERLY SEATED.
10c - SLIDE PIPE COLLAR ASSEMBLIES FROM STEP 7 OVER THE (2) PIPES AND DRILL (8)
PVC GLUE JOINT
SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS SHOWN
INSERT FLUE PIPE ASSEMBLY THROUGH RIGHT SIDE KNOCKOUT ON COVER PLATE (NOTE: SLIDE FROM UNDER PLATE).
SLIDE ANGLED END THROUGH OPENING IN BLOWER SHELF AND ALIGN WITH ELBOW COUPLING.
SECURE PIPE ASSEMBLY TO BLOWER SHELF WITH (2) SCREWS AS SHOWN. ENSURE O-RING IS PROPERLY SEATED.
10c - SLIDE PIPE COLLAR ASSEMBLIES FROM STEP 7 OVER THE (2) PIPES AND DRILL (8)
SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS SHOWN
INSERT FLUE PIPE ASSEMBLY THROUGH RIGHT SIDE KNOCKOUT ON COVER PLATE (NOTE: SLIDE FROM UNDER PLATE).
SECURE PIPE ASSEMBLY TO BLOWER SHELF WITH (2) SCREWS AS SHOWN. ENSURE O-RING IS PROPERLY SEATED.
SLIDE INTAKE PIPE THROUGH THE LEFT SIDE KNOCKOUT ON COVER PLATE CLEAN AND PVC GLUE TO INTAKE COUPLING AS SHOWN
ST-A1194-31-04
Field Conversions
25
11
SEE CRITICAL HOSE CLAMP
1/4” TUBE CUT
APPROXIMATLY 10-20° TILT
11a
APPROXIMATLY 10-20° TILT
LOCATION NOTE IN THE GENERAL CONVERSION INSTRUCTIONS.
HOSE D
I
N
T
S
A
L
L
1
1
d
)
HOSE E
A
A
L
L
11c
1/4” TUBE CUT
TO FIT (APPROX
1
1
e
10°
ON INDUCER COUPLING
ROTATE INDUCER COUPLING TO ENSURE DOWNWARD FLOW OF CONDENSATE FROM
-2010°
ON INDUCER COUPLING
GROUND
ROTATE INDUCER COUPLING TO ENSURE DOWNWARD FLOW OF CONDENSATE FROM
1
1b - INSTALL CONDENSATE TRAP BY MOUNTING
BRACKET TO JACKET USING (2) SCREWS.
11c - CUT 1/4" VENT TUBE TO FIT (APPROX.10-1/2").
INSTALL AS SHOWN.
11a - ROTATE INDUCER COUPLING 10°
! NOTE: TIGHTEN ELBOW COUPLING CLAMPS TO FLUE PIPE WITH 5/16" NUT DRIVER. (NOT SHOWN)
FLUE VENTING
1
1b - INSTALL CONDENSATE TRAP BY MOUNTING
BRACKET TO JACKET USING (2) SCREWS.
11c - CUT 1/4" VENT TUBE TO FIT (APPROX.10-1/2").
11a - ROTATE INDUCER COUPLING 10°
! NOTE: TIGHTEN ELBOW COUPLING CLAMPS TO FLUE PIPE WITH 5/16" NUT DRIVER. (NOT SHOWN)
NOTE: USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
ELBOW NOT SHOWN
FOR CLARITY
USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
ELBOW NOT SHOWN
11b
USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
11e - ATTACH HOSE E TO THE TOP OF
CONDENSATE TRAP.
11d - INSTALL HOSE D (REMOVED IN STEP 1) FROM
TRANSITION COULPLING TO THE FLUE TAP ON THE CONDENSATE TRAP.
11e - ATTACH HOSE E TO THE TOP OF
11d - INSTALL HOSE D (REMOVED IN STEP 1) FROM
TRANSITION COULPLING TO THE FLUE TAP ON THE CONDENSATE TRAP.
12a
ATTACH SIDE
"2" TO BULKHEAD
COUPLING
OPTION
DRAIN LEFT
SIDE
ATTACH SIDE
"2" TO BULKHEAD
COUPLING
TUBE “C”
CUT TO FIT
CABINET WIDTH
12b
OPTION
DRAIN RIGHT
SIDE
HOSE “B”
(X3)
HOSE A
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
NOTE: PLIERS NECCESSARY TO ADD OR REMOVE CLAMPS
ST-A1194-31-04
Field Conversions
26
ST-A1194-31-04
Notes:
Checklist:
_
_ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED.
__ CONFIRM THAT ALL HOSES ARE FREE OF KINKS.
__ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW.
__ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP OF THE COUPLING. SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTRUCTIONS AT THE BEGINNING OF THIS SECTION.
__ ALL DRAIN PORTS ARE PLUGGED.
__ UNIT HAS FORWARD PITCH.
__ HEAT TAPE INSTALLED(IF REQUIRED).
__ ALL CLAMPS AND COUPLINGS ARE TIGHTENED
Field Conversions
27
PARTS NEEDED:
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS FROM THE PARTS BAG AND CONVERSION KIT RXGY-CK. YOU MUST HAVE THE PARTS OUTLINED BELOW BEFORE PROCEEDING.
!
NOTE: STEPS 1- 5 SHOWN WITH FURNACE IN “AS SHIPPED CONDITION”
NOTE: THESE CONVERSION INSTRUCTIONS ARE INTENTIONALLY GENERIC, SOME PARTS MAY BE DIFFERENT IN YOUR FURNACE
HORIZONTAL RIGHT / RIGHT VENT
ST-A1194-32-01
2
2a - RELOCATE 1/2" VINYL CAP (YELLOW) ON THE INDUCER COUPLING 2b - RELOCATE THE .403" DRAIN PLUG IN THE COLLECTOR BOX. 2c - RELOCATE 1/4" VINYL CAP (YELLOW) ON COLLECTOR BOX VENT TAP.
2a
2b
2c
MOVE
MOVE
MOVE
1
1a - REMOVE TRAP AND HOSES
(NOTE: TO REMOVE TRAP, REMOVE (2) SCREWS AND PULL STRAIGHT OUT)
1b - INSTALL INTAKE COUPLING IN TOP PLATE AS SHOWN.
1a
1b
HOSE “D” (DISCARD)
VENT HOSE (DISCARD)
DRILL 1/8" DRILL BIT
PLIERS
FLAT HEAD SCREWDRIVER
5/16 HEX HEAD DRIVER 1/4" HEX HEAD DRIVER
TOOLS/MATERIALS NEEDED:
C
ONDENSATE
TRAP GASKET
.559 DRAIN PLUG
#8 X 1/2"
SCREW
(X3)
1/4" BLACK
VENT TUBE
1
/2" DRAIN HOSE E
1
/2" DRAIN
HOSE F
FROM CONVERSION KIT RXGY-CK
INTAKE
COUPLING
A
ND NUT
F
ROM PARTS BAG
(PROVIDED WITH UNIT)
AIRFLOW
PARTS NEEDED FOR THIS CONVERSION REQUIRE ITEMS
ROM THE PARTS BAG AND CONVERSION KIT RXGY-CK.
F
OU MUST HAVE THE PARTS OUTLINED BELOW BEFORE PROCEEDING.
Y
Field Conversions
28
SEE CRITICAL HOSE CLAMP LOCATION NOTE IN THE GENERAL CONVERSION INSTRUCTIONS.
5
CUT
IF REQ’D.
INSTALL
HOSE E
HOSE F
CUT
INSTALL
CUT
INSTALL
ROTATE UNIT 90°
5a - ROTATE UNIT 90 5b - CUT 1/4" VENT HOSE TO FIT (APPROX. 5-1/2") AND INSTALL AS SHOWN. 5c - CUT HOSE E AT LINE 1- INSTALL
NOTE: MAKE SURE CUT IS STRAIGHT AND SQUARE
5d - CUT HOSE F ON LINE CORRESPONDING TO UNIT WIDTH AND INSTALL NOTE: 17.5": LINE 1, 21": LINE 2, 24.5": DO NOT CUT
NOTE: USE SOAPY WATER TO FACILITATE EASY HOSE AND TUBE ASSEMBLY
1/4” TUBE CUT
TO FIT (APPROX. 4”)
5a
5b
5c 5d
4
4a - REMOVE METAL BRACKET AND THE Ø.403 DRAIN PLUG- DISCARD. 4b - REMOVE HOSE “A” - DISCARD 4c - INSTALL Ø .559" CONDENSATE DRAIN PLUG AND CONDENSATE TRAP GASKET AS SHOWN. 4d - INSTALL CONDENSATE TRAP. MAKE SURE THE CHANNEL AT THE LOCATION SHOWN IN THE “IMPORTANT SECTION” ENGAGES THE EDGE OF THE JACKET AT THE LOCATION SPECIFIED. 4e - SECURE USING (3) SCREWS.
NOTE: TO PREVENT DAMAGE TO THE TRAP, THE INSTALLER MAY ELECT TO INSTALL IT DURING A LATER STEP. (AFTER THE UNIT IS ROTATED)
DISCARD
HOSE A
DISCARD
INSTALL
4a
4b
4c
4d
R
ECTANGLE PLUG
DISCARD
DRILL (3)
Ø1/8" HOLES
3a - REMOVE RECTANGLE FLUSH MOUNT PLUG FROM JACKET SIDE-DISCARD 3
b - PRE-DRILL (3) Ø 1/8" HOLES AS SHOWN
FOR CONDENSATE TRAP
3a
3b
3
NOTE: REMAINING STEPS SHOWN WITH FURNACE IN HORIZONTAL RIGHT ORIENTATION
ST-A1194-32-01
!! IMPORTANT !!
THIS CHANNEL MUST ENGAGE JACKET AT THIS EDGE TO AVOID AIR LEAKS TO THE BURNER VESTIBULE!
CONDENSATE TRAP
INFORMATION
TRAP
JACKET
I
NSTALL CONDENSATE TRAP
INSTALL CONDENSATE TRAP
Field Conversions
29
ST-A1194-32-01
Notes:
__ VERIFY ALL HOSES ARE SECURE AND FULLY SEATED.
__ CONFIRM THAT ALL HOSES ARE FREE OF KINKS.
__ CONFIRM ALL HOSES AND OTHER DRAIN PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW.
__ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE FLUE TRANSITION MUST BE LOCATED ON THE TOP OF THE COUPLING. SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTRUCTIONS AT THE BEGINNING OF THIS SECTION.
__ ALL CLAMPS AND COUPLINGS ARE TIGHTENED
__ ALL DRAIN PORTS ARE PLUGGED.
__ UNIT HAS FORWARD PITCH.
__ HEAT TAPE INSTALLED(IF REQUIRED)
Checklist:
Field Conversions