FOR UPFLOW/HORIZONTAL TWO STAGE
GAS FURNACES
(-)802P UPFLOW/HORIZONTAL SERIES
(-)(-)80MDP UPFLOW/HORIZONTAL SERIES
U.L. and/or C.S.A. recognized fuel gas and CO (carbon monoxide) detectors are recommended in all applications, and their installation should be in accordance with the
manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OF THIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TO ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIR THIS PRODUCT. UPON UNPACKING
OF THE FURNACE, INSPECT ALL PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.
2
ST-A1220-16-00
1.) DOOR SWITCH
2.) TRANSFORMER
3.) JUNCTION BOX
4.) LOW VOLTAGE TERMINAL
5.)HEAT ASSISTED LIMIT CONTROL (HALC)
6.) SOLID METAL BASE PAN
7.) FURNACE CONTROL
8.) CONTROL MOUNTING PLATE
9.) CAPACITOR
10.) BLOWER
11.) IGNITER
12.) GAS VALVE
13.) INDUCED DRAFT BLOWER
14.) 4” FLUE ADAPTER (OPTIONAL)
15.) COMBUSTION AIR INLET
16.) MAIN LIMIT
17.) COMBUSTION AIR DIFFUSER
18.) PRESSURE SWITCHES,
HIGH AND LOW STAGE
19.) OVER TEMPERATURE SWITCH
20.) BURNER
21.) FLAME SENSOR
1
15
16
17
18
19
20
21
2
3
4
5
6
7
8
9
10
11
12
13
14
GENERAL INFORMATION
NOTE: A heat loss calculation should be performed to properly
determine the required furnace BTU size for the structure. Also,
the duct must be properly designed and installed for proper airflow. Existing ductwork must be inspected for proper size and to
make sure that it is properly sealed. Proper airflow is necessary
for both user comfort and equipment performance.
Before opening the furnace carton, verify that the data tags on
the carton specify the furnace model number that was ordered
from the distributor and are correct for the installation. If not,
return the unit without opening the carton. If the model number
is correct, open the carton and verify that the furnace rating
label specifies the same furnace model number that is specified on the carton label. If the model numbers do not match, return the furnace to the distributor.
IMPORTANT: Proper application, installation and maintenance of
this furnace and system is a must if consumers are to receive the full
benefits for which they have paid.
FIGURE 1
FURNACE COMPONENTS
The (-)802P/(-)(-)80MDP series furnaces are design certified by
CSA for use with natural and propane gases as follows:
As a Category I furnace, it may be vented vertically with type B1 vent pipe and also may be common vented as described in
these instructions.
This furnace should be installed in accordance with the American
National Standard Z223.1 - latest edition booklet entitled “National
Fuel Gas Code” (NFPA 54), and the requirements or codes of the
local utility or other authority having jurisdiction including local
plumbing or waste water codes.
With the introduction of higher efficiency furnaces, special attention
must be paid to the venting system. Only listed venting systems
may be used as stated in the installation instructions and the Na-tional Fuel Gas Code, ANSI Z223.1 (NFPA 54),. Since furnace
technology and venting requirements are changing, awareness of
local, state, and federal codes and industry changes is imperative.
General Information
ST-A1220-16
3
GENERAL INFORMATION (cont.)
Install this furnace in accordance with the American National Standard Z223.1 – latest edition entitled “National Fuel Gas Code”
NFPA54) or, for Canada, CSA B149.1; Canadian Natural Gas
(
and Propane Installation Code and requirements or codes of the
local utilities or other authorities having jurisdiction. This is available
from the following:
General Information
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
CSA-INTERNATIONAL
5060 Spectrum Way
Mississauga, Ontario
Canada L4W5N6
Online: www.csa.ca
RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should
be opened immediately. If damage is found, it should be noted on
the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking
care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around
the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on
the inside where they exit conduit opening. Caulking is required to prevent air leakage into and condensate from forming
inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to
the coil/filter rack and blower/control compartment.
• Install the unit in accordance with any local code which may
apply and the national codes. Latest editions are available
from: “National Fire Protection Association, Inc., Batterymarch
Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning
systems.
• The equipment has been evaluated in accordance with the
Code of Federal Regulations, Chapter XX, Part 3280.
CALIFORNIA RESIDENTS ONLY
IMPORTANT: All manufacturer products meet current Federal
OSHA Guidelines for safety. California Proposition 65 warnings
are required for certain products, which are not covered by the
OSHA standards.
California's Proposition 65 requires warnings for products sold in
California that contain, or produce, any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion
products from natural gas.
All “new equipment” shipped for sale in California will have labels
stating that the product contains and/or produces Proposition 65
chemicals. Although we have not changed our processes, having
the same label on all our products facilitates manufacturing and
shipping. We cannot always know “when, or if” products will be
sold in the California market.
You may receive inquiries from customers about chemicals found
in, or produced by, some of our heating and air-conditioning equipment, or found in natural gas used with some of our products.
Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the Websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov
State of California's OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org.
portant since the chemicals and substances on the list are found
in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and
maintained.
Consumer education is im-
and the
4
Installation Instructions remain with the furnace as a reference guide to the servicing contractor. We recommend
that performance and installation data be recorded for future reference on this sheet to meet service and warranty
bligations so that job site information is available when required.
______ Correct clearance to combustibles (record clearance)
______ Correct clearance for service (at front) (record clearance)
DUCT STATIC PRESSURE
______ in. w.c. on heating speed (record static pressure)
______ in. w.c. on cooling speed (record static pressure)
______ Air temperature rise in heat (record air temperature rise)
______ Air temperature rise in cool (record air temperature rise)
VENTING
______ Correct vent pipe diameter and length (according to NFGC tables) _________________ Vent connection size
______ Correct venting material (according to NFGC tables)
______ Correct lining for masonry chimneys
______ Adequate clearance from combustibles
______ Proper negative pressure reading in the vent
______ Vent pipe secured to induced draft blower housing
COMBUSTION AIR
______ Proper source of combustion air
______ Correct combustion air opening size
______ Optional attic combustion air pull
______ Non-attic combustion air pull
5
SAFETY INFORMATION
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!!
THIS FURNACE IS NOT APPROVED FOR INSTALLATION
IN A MOBILE HOME. DOING SO COULD CAUSE FIRE,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE
INSTRUCTIONS.
WARNING
!
IMPROPER INSTALLATION, OR INSTALLATION NOT
MADE IN ACCORDANCE WITH THE CSA INTERNATIONAL
(CSA) CERTIFICATION OR THESE INSTRUCTIONS, CAN
RESULT IN UNSATISFACTORY OPERATION AND/OR DANGEROUS CONDITIONS AND ARE NOT COVERED BY THE
MANUFACTURER’S WARRANTY.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY
SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A
SAFETY SWITCH CAUSES THE FURNACE TO SHUT
DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICATION OF A POTENTIAL SAFETY HAZARD THAT MUST BE
ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE
AGENCY OR THE GAS SUPPLIER. DO NOT RESET
SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
Safety Information
AND/OR VERIFICATION OF PROPER SAFE OPERATION
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE
GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY
WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN A
NEW SAFETY SWITCH IS INSTALLED, IT MUST BE
TESTED FOR A MINIMUM OF 15 MINUTES WITH THE
FURNACE OPERATING AT MAXIMUM INPUT RATE AND
WITH BOTH BLOWER AND BURNER DOOR INSTALLED.
IF THE FURNACE IS INSTALLED IN A CLOSET, THE
CLOSET DOOR MUST ALSO BE CLOSED FOR THIS
TEST. REPEAT THE TEST AT THE MINIMUM INPUT RATE
IF THE FURNACE IS A MULTI-STAGE FURNACE.
WARNING
!
USE ONLY WITH THE TYPE OF GAS APPROVED FOR
THIS FURNACE. REFER TO THE FURNACE RATING
PLATE.
WARNING
!
COMBUSTION AND VENTILATION AIR MUST BE PROVIDED TO THE FURNACE AS REQUIRED BY THE NATIONAL FUEL-GAS CODE (U.S.) AND CSA B149.1
(CANADA) AND THE COMBUSTION AND VENTILATION
AIR SECTION OF THESE INSTRUCTIONS.
W
AR
N
IN
!
C
O
MB
U
STI
D
O
O
VE
N
I
N
S
T
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY
DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO
AREAS OUTSIDE THE SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL ALSO BE HANDLED BY
DUCT(S) SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE FURNACE.
!
WHENEVER THE FACTORY RETURN-AIR CONNECTION
IS NOT USED IT MUST BE SEALED. A SOLID METAL
BASE PLATE MUST BE INSTALLED AND SEALED. FACTORY BASE PLATES ARE AVAILABLE AS ACCESSORY
ITEMS. (PART NUMBERS ARE LISTED IN THE SPEC
SHEET FOR THE FURNACE.) FAILURE TO INSTALL AND
SEAL THE BASE PLATE AND RETURN AIR DUCT CONNECTIONS MAY ALLOW CARBON MONOXIDE AND
OTHER CONTAMINANTS TO BE DRAWN INTO THE CONDITIONED AIR SPACE AND DISTRIBUTED THROUGHOUT
THE HEATED SPACE.
!
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A
PORTION OF THE DUST ENTRAINED IN THE AIR MAY
TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT
THE SUPPLY REGISTERS. ANY CIRCULATED DUST PARTICLES WILL BE HEATED AND CHARRED BY CONTACT
WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY
RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CARPETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAMAGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN
PLACE, WHEN CERTAIN TYPES OF CANDLES ARE
BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
O
R
S
.
C
O
T
SY
S
TE
A
LLA
TI
WARNING
WARNING
WARNING
G
N
PR
O
D
U
C
TS
MU
S
T
B
E
D
I
S
C
H
A
R
G
E
D
O
U
N
N
E
C
T
TH
I
S
FU
R
N
A
C
E
TO
A
N
A
P
P
M
O
N
L
Y
,
A
S
S
P
E
C
I
FI
ED
I
N
O
N
S
E
C
TI
O
N
O
F
TH
E
TH
S
E
I
N
S
TR
R
E
V
EN
U
C
TI
O
OV
T
T
E
D
PI
PE
N
S
.
-
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME.
USE A COMMERCIALLY AVAILABLE SOAP SOLUTION
MADE SPECIFICALLY FOR THE DETECTION OF LEAKS
TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS
SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.
6
WARNING
!
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS RECOMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER THIS FURNACE AND ANY INSTALLED
EVAPORATOR COIL THAT IS LOCATED IN ANY AREA OF
A STRUCTURE WHERE DAMAGE TO THE BUILDING OR
BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN
OVERFLOW OF THE A/C COIL DRAIN PAN.
SAFETY
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED
WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO
PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTO THE
HOME THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
WARNING
!
ALWAYS INSTALL THE FURNACE TO OPERATE WITHIN
THE FURNACE’S INTENDED TEMPERATURE-RISE
RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE
RANGE, AS SPECIFIED IN THE DUCTING SECTION OF
THESE INSTRUCTIONS. SEE ALSO FURNACE RATING
PLATE.
THE FURNACE MAY BE USED FOR HEATING OF BUILDINGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION
INSTRUCTIONS INCLUDING:
PROPER VENT INSTALLATION;
-
FURNACE OPERATING UNDER THERMOSTATCONTROL;
RETURN AIR DUCT SEALED TO THE FURNACE;
-
AIR FILTERS IN PLACE;SET FURNACE INPUT RATE AND TEMPERATURERISE PER RATING PLATE MARKINGS;
MEANS FOR PROVIDING OUTDOOR AIR RE-
-
QUIRED FOR COMBUSTION;
RETURN AIR TEMPERATURE MAINTAINED BE-
-
TWEEN 55°F (13°C) AND 80°F (27°C); AND
CLEAN FURNACE, DUCT WORK AND COMPO-
-
NENTS UPON SUBSTANTIAL COMPLETION OF
THE CONSTRUCTION PROCESS, AND VERIFY
THAT THE FURNACE OPERATING CONDITIONS
INCLUDING IGNITION, INPUT RATE, TEMPERATURE RISE AND VENTING, ACCORDING TO THE
INSTRUCTIONS AND CODES.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM
AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES
AND ODORS INTO THE HOME CAUSING PROPERTY
DAMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE
OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMOBILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE
DRAWN INTO THE LIVING SPACE THROUGH LEAKING
DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING
PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN GARAGES OR OFF-GARAGE STORAGE
AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE
EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT
THE MIGRATION OF TOXIC FUMES AND ODORS INCLUDING CARBON MONOXIDE FROM MIGRATING
INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LOCATED IN SPACES CONTAINING FUEL BURNING APPLIANCES SUCH AS WATER HEATERS OR BOILERS ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND
POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO
LIVING SPACES
Safety Information
IMPORTANT INFORMATION ABOUT
EFFICIENCY AND INDOOR AIR
QUALITY
Central cooling and heating equipment is only as efficient as the
duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have
the proper balance between the air being supplied to each room
and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves
the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the
U.S. Environmental Protection Agency’s Energy Star Program
recommend that central duct systems be checked by a qualified
contractor for proper balance and sealing.
Adapted from Residential Duct Diagnostics and Repair, with permission of Air Conditioning
Contractors of America (ACCA).
7
LOCATION REQUIREMENTS
GENERAL INFORMATION
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE INSTALLED SO THE BURNERS
AND IGNITION SOURCE ARE LOCATED NO LESS THAN
8 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO PRE-
1
VENT THE RISK OF IGNITING FLAMMABLE VAPORS
WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID
PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW
THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION,
RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH.
1. IMPORTANT: If installing the unit over a finished ceiling or liv-
ing area, be certain to install an auxiliary condensate drain pan
under the entire unit. This auxiliary drain pan should extend
under any evaporator coil installed with the furnace.
2. IMPORTANT: If using a cooling evaporator coil with this fur-
nace, be sure the air passes over the heat exchanger before
passing over the cooling coil. The cooled air passing over the
warm ambient air inside the heat exchanger tubes can cause
condensation inside the tubes resulting in corrosion and eventual failure.
If there are manual dampers, they must be equipped to prevent
heating or cooling operation unless the damper is in the full heat
or cool position.
3. NOTE: This furnace is shipped with heat exchanger support
brackets installed under the back of the heat exchanger. These
may be removed before installation, but it is not required.
4. IMPORTANT: This furnace is not approved or recommended
for installation on its back, with access doors facing upwards.
5. This furnace is suitable for installation in buildings constructed
on-site. This heating unit should be centralized with respect to
the heat distribution system as much as practicable.
6. NOTE: These furnaces are approved for installation in attics,
as well as alcoves, utility rooms, closets and crawlspaces.
Location
7. IMPORTANT: Support this unit when installed. For attic or crawl
space installation, horizontal furnaces may be installed on combustible wood flooring or by using support brackets. See Figure
3.
8. IMPORTANT: If installing in a utility room, be sure the door is
wide enough to:
a. allow the largest part of the furnace to pass; or
b. allow any other appliance (such as a water heater) to pass.
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED
FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS
FACING UPWARDS.
SITE SELECTION
1. Select a site in the building near the center of the proposed, or existing, duct system.
2. Give consideration to the vent system piping when selecting the furnace location. Be sure the venting system
can get from the furnace to the termination with minimal
length and elbows.
3. Locate the furnace near the existing gas piping. Or, if
running a new gas line, locate the furnace to minimize
the length and elbows in the gas piping. See Figure 3.
4. Locate the furnace to maintain proper clearance to
combustibles as shown in following Figure 4.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER
TUBES. DOING SO CAN DAMAGE THE HEAT EXCHANGER ASSEMBLY.
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as
listed in the tables under Figure 4 are certified by CSA-International for the clearances to combustible materials
shown in inches.
See name/rating plate and clearance label for specific
model number and clearance information.
Service clearance of at least 24 inches (30 cm) is recommended in front of all furnaces.
NOTE: Use recommended 24” (30 cm) clearance if accessibility clearances are greater than fire protection clearances.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST
TAKE PRECEDENCE OVER FIRE PROTECTION CLEARANCES.
8
LOCATION REQUIREMENTS
NOTE:
HORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION.
HORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
AI
R
FLO
W
GENERAL INFORMATION (cont.)
WARNING
!
UPFLOW AND HORIZONTAL FURNACES ARE DESIGNCERTIFIED FOR INSTALLATION ON COMBUSTIBLE
FLOORS. NOTE, HOWEVER, THAT FURNACES MUST NOT
BE INSTALLED DIRECTLY ON CARPETING, TILE OR
OTHER COMBUSTIBLE MATERIAL OTHER THAN WOOD
FLOORING. INSTALLATION ON A COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FIGURE 3
ST-A1220-03
WARNING
!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON
OR AGAINST THE FURNACE JACKET. THE AREA
AROUND THE FURNACE MUST BE KEPT CLEAR AND
FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON,
AGAINST OR AROUND THE FURNACE JACKET CAN
CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. THE
HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET
OR FOR ANY OTHER STORAGE PURPOSES.
Location
9
BOTTOM
TOP
LEFT SIDEFRONTRIGHT SIDE
GAS
CONNECTION
ELECTRICAL CONNECTION
LINE VOLTAGE
ELECTRICAL CONNECTION
LOW VOLTAGE
OPTIONAL
GAS CONNECTION
OPTIONAL LOW
VOLTAGE WIRING
OPTIONAL LINE VOLTAGE
WIRING
A
I
R
F
L
O
W
RETURN
AIR
SUPPLY
AIR
HOT
MODELABCDEFRIGHTSIDEBACKTOPFRONTVENT
5141327/32105/8༃111/217/804༄0136༅85lbs.
7171/21611/32123/8༃1521/203༄0136༅105lbs.
10211927/32141/8༃181/221/2000136༅120lbs.
12241/22311/32157/8༃2221/2000136༅140lbs.
15241/22311/32157/8༃2221/2000136༅150lbs.
༃MAYREQUIRE3"TO4"OR3"TO5"ADAPTER.
4"ADAPTERINCLUDEDWITH(-)801PUNITS.
༄MAYBE0"WITHTYPEBVENT.
༅MAYBE1"WITHTYPEBVENT.
LEFTSIDE
REDUCEDCLEARANCE(IN.)
SHIP
WGTS.
FIGURE 4
UPFLOW/HORIZONTAL DIMENSIONS
Ship.
Back Top Front Vent
REDUCED CLEARANCE (IN.)
4” adapter optional.
➁ May be 0” with type B vent.
➂ May be 1” with type B vent.
➀ May require 3” to 4” or 3” or 5” adapter.
Left Right
/8 0 4➁ 0 1 3 6➂ 85 lbs.
/2 0 3➁ 0 1 3 6➂ 105 lbs.
/2 0 0 0 1 3 6➂ 120 lbs.
/2 0 0 0 1 3 6➂ 140 lbs.
1
7
/2 1
1
/8 ➀ 11
/8 ➀ 15 2
5
3
/2 0 0 0 1 3 6➂ 150 lbs.
1
1
1
/2 2
1
/8 ➀ 18
/8 ➀ 22 2
/8 ➀ 22 2
1
7
7
ST-A1220-04
/32 10
/32 12
/32 14
/32 15
27
11
/2 16
1
Model A B C D E F
Side Side Wgts.
5 14 13
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
UPFLOW/HORIZONTAL MODELS
Location
7 17
/32 15
27
11
11
/2 23
/2 23
1
1
10 21 19
12 24
15 24
10
roper air flow is required for the correct operation of this
P
furnace. Restricted air flow can cause erratic operation and
can damage the heat exchanger. The duct system must
carry the correct amount of air for heating and cooling if
summer air conditioning is used.
WARNING
!
SOME HEATING AIRFLOW VALUES MAY BE
HIGHER THAN THOSE REQUIRED FOR COOLING.
BE SURE TO SIZE DUCT FOR THE MAXIMUM POSSIBLE AIRFLOW VALUE.
SIZE AIRFLOW DISTRIBUTION SYSTEM TO ACCEPTABLE INDUSTRY STANDARDS AND METHODS. TOTAL STATIC PRESSURE DROP OF THE AIR
DISTRIBUTION SYSTEM SHOULD NOT EXCEED .8
INCHES W.C. THIS WILL INCLUDE ANY AIR CONDITIONER COIL, AIR FILTRATION SYSTEM, ZONING
SYSTEM, DUCTWORK, ETC. REFER TO ADDED
EQUIPMENT TECHNICAL INFORMATION TO OBTAIN
PRESSURE DROP INFORMATION WHEN EQUIPMENT IS OPERATING AT RECOMMENDED HEATING OR COOLING CFMS.
IMPORTANT: When using outside air, design and adjust
the system to maintain a return air temperature ABOVE
55° F during the heating season.
NOTE: Return air grilles and warm air registers must not
be obstructed or closed.
DUCTING
UPFLOW INSTALLATIONS
1. Position the unit to minimize long runs of duct or runs
of duct with many turns and elbows.
2. For side return: Cut an opening in the side. The opening should be cut the full width and height of the
knockouts on the unit. See Figure 6.
3. If summer air conditioning is desired, position the indoor coil on the supply-air side of the unit. Ensure that
no air can bypass the coil.
4. Connect the furnace to the supply air plenum. See Figure 7.
5. Connect the return air ducting to the return-air opening
at the bottom and/or side of the unit. Make the connections air-tight to prevent the migration of toxic fumes
and odors including carbon monoxide from migrating
into the living space.
6. If a filter is installed near the furnace, be sure to have
adequate space for installation and removal of the unit
filter.
7. NOTE: Where the maximum airflow is 1800 CFM or
more, BOTH sides or the bottom must be used for the
return air. Do not take return air from the back of the
unit.
NOTE: DO NOT take return air from furnace rooms,
garages or cold areas. Avoid return air from utility rooms,
kitchens, laundry rooms and bathrooms.
WARNING
!
UPFLOW FURNACE: THE SOLID METAL BASE
(SHIPPED WITH THE FURNACE) PLATE MUST BE INSTALLED IN THE FURNACE BOTTOM WHEN USING
SIDE AIR RETURN. FAILURE TO INSTALL A BASE
PLATE COULD CAUSE THE PRODUCTS OF COMBUSTION TO CIRCULATE INTO THE LIVING SPACE
AND CREATE POTENTIAL LY HAZARDOUS CONDITIONS, INCLUDING CARBON MONOXIDE POISONING OR DEATH. FOR BOTTOM RETURN, A SOLID
METAL BASE PAN MUST NOT BE INSTALLED. SEE
FIGURE 5.
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED
WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO
PREVENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTO THE
HOME THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
Ducting
11
DUCTING
NOTE:
SOLID BASE PLATE PROVIDED WITH (-)801P
MODELS ONLY.
WHEN SOLID BASE PLATE IS USED . TAPE
AROUND BOTTOM FLANGES OF CABINET
BEFORE THE UNIT IS INSTALLED.
LIFT UP, PULL OUT
1. REMOVE 2 SCREWS, LIFT BASE UP, SLIDE FORWARD TO REMOVE.
2. INSTALLATION IS REVERSE OF REMOVAL.
** VERIFY REAR FLANGE IS SEALED PROPERLY AS SHOWN IN DETAIL.
ST-A1220-10-X0
SOLID BASE FLANGE
F
ITS UNDER
CABINET BOTTOM
FIGURE 5
Ducting
FIGURE 6
ST-A1220-08
ST-A1220-10
FIGURE 7
ST-A1220-11
12
DUCTING
NOTE:
H
ORIZONTAL LEFT ORIENTATION DEPICTED IN ILLUSTRATION.
H
ORIZONTAL RIGHT ORIENTATION IS SIMILAR IN INSTALLATION.
A
I
R
F
LO
W
NOTE:
DO NOT BLOCK FURNACE ACCESS WITH
SUPPORT RODS, ALLOW SPACE FOR
PROPER SERVICE MAINTIENCE OR
REPLACEMENT OF THE HEAT EXCHANGER
AND BLOWER ASSEMBLY .
HORIZONTAL UNITS
1. Position the unit to minimize long runs of duct or runs of
duct with many turns and elbows.
2. Unit can be mounted left or right side airflow configuration.
3. Position the unit on adequate supports or by using support
brackets (see Figure 8) and connect supply plenum.
4. If summer air conditioning is desired, position the indoor coil on
the supply air side of the unit. Insure that no air can bypass
this coil.
5. Secure the four angle brackets to the return air opening. See
Figure 9. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent entraining combustion gases from an adjacent
fuel-burning appliance.
NOTE: Do not block furnace access with support rods. Maintain clearances recommended in Figure 8. Allow enough
space for proper service maintenance or replacement of the
heat exchanger and blower assembly.
IGURE 8
F
B
RT
PPO
W/SU
ED
L
L
A
ST
E IN
AC
N
R
U
F
L
A
T
N
O
IZ
R
O
H
S
ET
K
AC
R
FIGURE 9
HORIZONTAL RETURN AIR DUCT
LEFT-HAND AIRFLOW POSITION SHOWN)
(
RETURN
REAR VIEW
FOUR ANGLE BRACKETS CAN BE INSTALLED HORIZONTALLY.
THESE BRACKETS MAY BE USED TO SECURE THE RETURN AIR
DUCT TO A HORIZONTAL UNIT.
AIRFLOW
ST-A1220-03
Ducting
13
COMBUSTION AND VENTILATION AIR
COMBUSTION AIR REQUIREMENTS
IMPORTANT: This is not a direct vent furnace. Review venting
instructions before installing.
WARNING
!
Combustion Air
THIS FURNACE AND ANY OTHER FUEL-BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR
FOR PROPER COMBUSTION AND VENTILATION OF THE
FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE DEATH FROM CARBON
MONOXIDE POISONING.
WARNING
!
ADEQUATE FACILITIES FOR PROVIDING AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED IN ACCORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION
AND VENTILATION, OF THE NATIONAL FUEL GAS CODE,
ANSI, Z223.1 LATEST EDITION OR CSA B149.1 AND .2
OR, APPLICABLE PROVISIONS FOR THE LOCAL BUILDING CODES, AND NOT OBSTRUCTED SO AS TO PREVENT THE FLOW OF AIR TO THE FURNACE.
1. IMPORTANT: Air for combustion and ventilation must not
come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty
coverage.
2. Combustion air must be free of acid forming chemicals; such
as sulphur, fluorine and chlorine. These elements are found in
aerosol sprays, detergents, bleaches, cleaning solvents, air
fresheners, paint and varnish removers, refrigerants and many
other commercial and household products. Vapors from these
products when burned in a gas flame form acid compounds.
The acid compounds increase the dew point temperature of
the flue products and are highly corrosive after they condense.
3. The following types of installation may require OUTDOOR AIR
for combustion, due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
4. If combustion air is exposed to the following substances (but
not limited to the following), it should not be used and the furnace may require outdoor air for combustion.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry curing and acid washing materials
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH
THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO
PROVIDE ADEQUATE COMBUSTION AND VENTILATION
AIR FOR THE FURNACE. FAILURE TO DO SO CAN CREATE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH FROM
SMOKE, FIRE OR CARBON MONOXIDE.
Combustion air requirements are determined by whether the furnace is in an open (unconfined) area or in a confined space such
as a closet or small room.
When the furnace is installed in the same space with other gas appliances, such as a water heater, be sure there is an adequate
supply of combustion and ventilation air for the furnace and the
other appliances. Do not delete or reduce the combustion air supply required by the other gas appliances in this space. See Z223.1,
National Fuel Gas Code (NFPA 54). An unconfined space must
have at least 50 cubic feet (volume) for each 1,000 BTUH of the
total input of all appliances in the space. If the open space containing the appliances is in a building with tight construction (contemporary construction), outside air may still be required for the
appliances to burn and vent properly. Outside air openings should
be sized the same as for a confined space.
IMPORTANT: ONLY THE CURRENT VENT INSTRUCTIONS
APPLY. All gas furnaces cannot be common-vented.
OVERTEMPERATURE SAFETY
SWITCHES
Furnaces are equipped with safety switches in the burner compartment to protect against over-temperature conditions caused
by inadequate combustion air supply. The switches are located
in the burner compartment. If a switch is tripped it must be manually reset after clearing the fault condition which caused it to
open.
TABLE 8: MINIMUM FREE AREA
OPENINGREQUIRED FORAFURNACELOCATED IN A CONFINEDSPACEUSINGINDOORAIRFORCOMBUSTION.
Input (BTUH)
Free Area for Each
Opening (sq inches)
50,000
100
75,000
100
100,000
100
125,000
130
150,000 150
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
Combustion Air
ARNI
W
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH
THE NATIONAL FUEL GAS CODE, NFPA 54 AND LOCAL
CODES TO PROVIDE ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE FURNACE. FAILURE TO DO
SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY DAMAGE, CARBON MONOXIDE POISONING, PERSONAL INJURY OR DEATH.
For improved indoor air quality, added safety and product performance we recommend direct vent type installations. If non-direct type vent system is used, the requirements for combustion
air must be provided as identified in the National Fuel Gas Code.
Combustion air requirements are determined by whether the furnace is in an open (unconfined) area or in a confined space such
as a closet or small room.
WARNING
!
N
A
D
A
E
R
M
T
F
N
S
M
D
A
S
T
N
E
V
L
A
N
O
I
C
A
N
R
U
R
I
D
-
N
O
I
T
C
U
R
T
A
F
T
N
E
E
G
A
M
A
NG
-
E
R
I
U
Q
E
R
G
N
I
T
N
E
V
L
A
R
E
N
E
G
E
H
T
W
O
L
L
O
F
D
N
E
E
E
O
L
I
,
D
I
U
G
D
G
N
I
T
N
L
A
T
S
N
I
N
E
V
T
C
T
N
I
S
N
E
,
E
R
U
O
S
R
E
P
S
E
N
I
L
E
R
I
U
Q
E
R
N
O
I
T
A
L
T
H
Q
N
F
.
)
G
N
I
N
A
M
S
I
E
M
P
I
U
J
N
I
L
A
I
H
T
F
O
T
N
E
M
E
L
C
N
I
(
S
R
U
L
I
A
C
L
A
U
M
A
D
T
N
R
O
Y
R
U
U
N
A
M
S
T
R
E
P
S
U
E
A
D
G
N
I
D
O
F
O
T
S
E
R
N
P
,
E
G
A
H
T
A
E
D
R
O
F
L
A
G
N
I
N
I
A
T
C
E
R
I
W
O
L
L
N
I
T
L
U
R
E
P
O
R
.
-
I
D
D
A
L
L
A
O
T
D
N
A
-
N
I
L
L
A
-
P
I
U
Q
E
Y
T
FURNACE LOCATED IN AN UNCONFINED SPACE
USING INDOOR AIR FOR COMBUSTION:
An unconfined space must have at least 50 cubic feet for each
1,000 BTUH of total input for all appliances in the space. Table 1
below specifies minimum space requirements and a few examples of the room sizes required for different inputs. The sizes are
based on 8-foot ceilings.
If the open space containing the furnace is in a building with tight
construction, outside air may still be required for the furnace to
operate and vent properly. Outside air openings should be sized
the same as for a confined space.
FURNACE LOCATED IN A CONFINED
SPACE
A confined space is defined as any space for a given furnace input
rating which is smaller than that which is specified in Table 1 as
minimum for an “unconfined” space. If the space is less than that
specified in this table, the space is defined as “confined”.
If the space is small enough to be designated as “confined”, it
must have openings into the space which are located in accordance with the requirements set forth in the following subsections
A and B. Size connected to the heated area or to the outside, and
by the input of ALL
If the confined space is within a building with tight construction,
combustion air must be taken from outdoors or from an area
freely communicating with the outdoors.
A. USING INDOOR AIR FOR COMBUSTION:
IMPORTANT: Air should not be taken from a heated space
with a fireplace, exhaust fan or other device that may produce negative pressure.
If combustion air is taken from the heated area, the openings
must each have at least 100 square inches of free area.
Each opening must have at least one square inch of free
area for each 1,000 BTUH of total input in the space. Table 2
shows some typical examples of openings required for combustion air openings required for a confined space.
TABLE 2: MINIMUM FREE AREA
OPENING REQUIRED FOR A
FURNACE LOCATED IN A
CONFINED SPACE USING
INDOOR AIR FOR COMBUSTION.
appliances in the space.
TABLE 1: MINIMUM SPACE REQUIREMENTS
FOR UNCONFINED SPACE, NON-DIRECT VENT
B. USING OUTDOOR AIR FOR COMBUSTION:
IMPORTANT: Do not take air from an attic space that is
equipped with power ventilation.
The confined space must communicate with the outdoors in
accordance with Methods 1 or 2 below. The minimum dimension of air openings shall not be less than 3 inches. Where
ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect.
METHOD 1:
Two permanent openings, one located within 12 inches of the
top and one located within 12 inches of the bottom of the enclosure, shall be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces (crawl or
attic) that freely communicate with the outdoors.
NOTE:
EACH OPENING SHALL
HAVE A FREE AREA OF
NOT LESS THAN ONE
SQUARE INCH PER
1,000 BTU PER HOUR OF
THE TOTAL INPUT
RATING OF ALL
EQUIPMENT IN THE
ENCLOSURE, BUT NOT
LESS THAN 100
SQUARE INCHES.
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
TABLE 3: MINIMUM FREE AREA REQUIRED
FOR EACH OPENING (WHEN TWO OPENINGS
ARE USED) WITH A FURNACE:
Combustion Air
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH AN OPENING OR
3. THROUGH A VERTICAL DUCT.
A. Where directly communicating with the outdoors through an
opening or where communicating to the outdoors through
vertical ducts as shown in Figure 11, each opening shall
have a minimum free area of 1 square inch for each 4,000
BTUH of total appliance input rating of all equipment in the
enclosure. Table 3 specifies the minimum area for
each of the 2 combustion air openings and minimum round
duct diameter for direct openings and vertical ducting only.
B. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1
square inch for each 2,000 BTUH of total appliance input rating of all equipment in the enclosure (see Figure 12). Table 4
TABLE 4: MINIMUM FREE AREA REQUIRED
FOR EACH OPENING (WHEN TWO OPENINGS
ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
TABLE 5: MINIMUM FREE AREA REQUIRED
FOR EACH OPENING (WHEN TWO OPENINGS
ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
specifies the minimum area for each of the 2 combustion air
openings and minimum round duct diameter for horizontal
ducting only.
METHOD 2:
One permanent opening located within 12 inches of the top of
the enclosure, shall be permitted where the equipment has
clearances of at least 1 inch from the sides and back and 6
inches from the front of the appliance. The opening shall directly communicate with the outdoors or communicate
through a vertical or horizontal duct to the outdoors or spaces
(crawl or attic) that freely communicate with the outdoors,
and shall have a minimum of:
FIGURE 10
NON-DIRECT VENT
AIR FROM
HEATED
SPACE
VENT PENETRATIONS
FORNONDIRECTVENTFURNACES
AIR FROM HEATED SPACE
16
ST-A1227-01
COMBUSTION AND VENTILATION AIR (cont.)
GAS
WATER
HEATER
FURNACE
OPTIONAL 1 SQ. INCH PER 4000 BTUH INLET AIR
GABLE
VENT
VENTILATED
ATTIC GABLE OR
SOFFIT VENTS
OUTLET AIR
IN ATTIC
MUST BE
ABOVE
INSULATION
1
SQ. INCH PER
4000 BTUH INLET AIR
1
2” MAX
1 SQ. INCH PER
4000 BTUH
OUTLET AIR
GAS
WATER
HEATER
FURNACE
12”
MAX
I
NLET AIR 1 SQ. INCH
P
ER 2000 BTUH
OUTLET AIR 1 SQ. INCH
PER 2000 BTUH
O
UTLET AIR
1
SQ. INCH PER
4000 BTUH
INLET AIR
1 SQ. INCH PER
4000 BTUH
COMBUSTION AIR REQUIREMENTS: CONFINED AND
UNCONFINED SPACES
ENT PENETRATIONS
FIGURE 11
NON-DIRECT VENT
IR FROM ATTIC
A
OR CRAWL
PACE
S
VENT PENETRATIONS
OR NON DIRECT VENT FURNACES
F
AIR FROM ATTIC/CRAWL SPACE
T-A1227-02
S
FIGURE 12
ON-DIRECT VENT
N
UTSIDE AIR
O
SING A
U
ORIZONTAL
H
UCT
D
V
FORNONDIRECTVENTFURNACES
AIR FROM ATTIC/CRAWL SPACE
Combustion Air
ST-A1227-03
A. 1 Square inch for each 3,000 BTUH of the total input rat-
ing of all equipment located in the enclosure
and
B. Not less than the sum of the areas of all vent connectors
in the confined space.
If the unit is installed where there is an exhaust fan, sufficient
ventilation must be provided to prevent the exhaust fan from creating negative pressure.
FIGURE 13
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL
6" MIN.
AIR INTAKE PIPE CONNECTION
A double-elbow may be installed to top inlet air opening,
BUT IS NOT REQUIRED. This will help to prevent accidental
blockage of the intake opening. Reference Figure 13 for
proper elbow diameter.
NOTE: Inlet is specifically designed to prevent material from
being pulled into furnace. If elbows are not used, the intake opening must be kept clean and free of debris.
ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE OF
INTAKE OPENING. THIS IS NOT A REQUIREMENT. (SEE
PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED BUT
MAY NOT PREVENT DEBRIS FROM BEING DROPPED
INTO THE FURNACE.
PVC
DOUBLE
ELBOW
6" MININUM
CLEARANCE
#8 SCREWS
EXHAUST
METAL FLUE
PIPE ONLY
#8 SCREWS
GROUND OR
SHELF SURFACE
17
COMBUSTION AND VENTILATION AIR (cont.)
It is also acceptable to run the condensate drain (or refrigerant) line access over the air intake hole as long as a 1" minimum clearance is maintained.
Combustion air openings must not be restricted in any manner.
IMPORTANT: When indoor combustion air is used, the inlet air
Combustion Air
opening at the furnace must be protected from accidental blockage.
IMPORTANT: If the furnace is in a location with an exhaust fan,
there must be sufficient ventilation to prevent the exhaust fan
from creating a negative pressure in the room.
Combustion air openings must NOT BE RESTRICTED in any
manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
B: Method 3
For the optimum in quiet operation, attic air may be brought directly to the furnace.
IMPORTANT: In applications using Method 3 for combustion air,
the attic must be ventilated by gable or soffit vents.
FIGURE 14
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL
ATTACH A 90° ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE
OF INTAKE OPENING.
CAUTION
!
COMBUSTION AIR INTAKES CANNOT BE TERMINATED
OUTSIDE. DOING SO CAN CAUSE IMPROPER OPERATION OF THE FURNACE.
COMBUSTION AIR FROM ATTIC
If attic combustion air is used, the inlet air opening at the furnace
must be protected from accidental blockage. Install a 90° elbow
pointing horizontally at the top of inlet air pipe. See Figure 14
(maximum of 2, 45° or 90° elbows, allowed).
NOTE: Maximum length of pipe that may be used for combustion
air is 10 feet with two elbows. Lengths of more than 10 feet can
result in nuisance pressure switch trips.
18
12" MIN. FROM
TOP OF INSULATION
10 FT. MAX.
INCLUDING
HORIZONTAL DIRECTION
#8 SCREW
!
CAUTION
USE OF SHEET METAL
AIR INTAKE PIPE INSTEAD
OF PVC MAY RESULT IN
NOISE ISSUES.
PVC
ELBOW
INSULATION
6" MINIMUM
CLEARANCE
PVC
COUPLER
EXHAUST
ATTIC SPACE
METAL FLUE PIPE ONLY
INDOOR SPACE
#8 SCREWS
COMBUSTION AND VENTILATION AIR (cont.)
VENTING
GENERAL INFORMATION
The furnace must be vented in accordance with these instructions,
National Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2 and requirements or codes of
the local utility or other authority having jurisdiction.
WARNING
!
DEVICES ATTACHED TO THE FLUE OR VENT FOR THE
PURPOSE OF REDUCING HEAT LOSS UP THE CHIMNEY
HAVE NOT BEEN TESTED AND HAVE NOT BEEN INCLUDED IN THE DESIGN CERTIFICATION OF THIS FURNACE. WE, THE MANUFACTURER, CANNOT AND WILL
NOT BE RESPONSIBLE FOR INJURY OR DAMAGE
CAUSED BY THE USE OF SUCH UNTESTED AND/OR UNCERTIFIED DEVICES, ACCESSORIES OR COMPONENTS.
DRAFT INDUCER
WARNING
!
VENT PIPE ATTACHING HOLES MUST BE PREDRILLED
IN THE DRAFT INDUCER COLLAR TO PREVENT DAMAGING THE INDUCER. DRILL 1/8” DIAMETER HOLES
THROUGH THE VENT PIPE AND COLLAR AND USE #8
SCREWS TO ATTACH. SEE FIGURE 16. FAILURE TO FOLLOW THIS WARNING CAN CAUSE RECIRCULATION OF
FLUE PRODUCTS CAUSING CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH.
FURNACE CATEGORY INFORMATION
This furnace is shipped as a Category I type induced draft furnace. A Category I furnace operates with a nonpositive vent pressure and has a vent gas temperature at least 140°F above the
dew point of the vent gases. A Category I type may be a draft
hood equipped furnace or have a fan assisted combustion system (induced draft). The inducer is used to pull flue products
through the combustion chamber and as they leave the furnace,
most of the energy has been dissipated. The buoyant effect of the
flue gases provides venting to the outdoors.
During the off cycle, the inducer is off and there is very little flow
through the vent, cooling the vent. During the on cycle there is no
dilution airflow, as with a draft hood type furnace. Although the
vent heats up rapidly without dilution air, the flue products contain
more water vapor, which results in a higher dew point temperature. It is most important that you follow the guidelines in these
instructions to prevent the possible formation of condensation in
the venting system.
As a Category I furnace it may be vented vertically with type B-1
vent pipe and also may be common vented, as described in
these instructions.
IMPORTANT APPLICATION NOTES
hen the furnace is used as a replacement, the existing vent
W
system should be inspected to assure that there are no obstructions, blockage, or any signs of corrosion and is properly sized for
use with this furnace.
NOTE: When the vent table permits more than one diameter of
pipe for a connector or vent, the smallest permitted diameter
must be used.
Vent pipe may be type “B-1,” either rigid or suitable flexible construction that carries a U.L. listing.
Common venting is allowed with vertical B-1 vent systems, and
lined masonry chimneys. Follow the National Fuel Gas Code,
ANSI Z223.1 and/or the Natural Gas Installation Code, CSAB149.1 & .2 for proper installation practices.
NOTE: Follow combustion air instructions as outlined in this manual.
Single wall vent connectors to “B-1 vent or masonry chimneys”
may be used under the guidelines of the National Fuel Gas Code,
ANSI Z223.1 and/or the Natural Gas Installation Code, CSAB149.1 & .2.
The entire length of the vent connector shall be readily accessible for inspection, cleaning and replacement.
“B-1” VERTICAL VENTING
NOTE: Refer to the National Fuel Gas Code, ANSI Z223.1 and/or
the Natural Gas Installation Code,
CSA-B149.1 & .2.
Type “B-1” vents must be installed in accordance with the terms
of their listings and the vent manufacturer’s instructions.
“B-1” vents must be supported and spaced in accordance with
their listings and the manufacturer’s instructions. All vents must
be supported to maintain their minimum clearances from combustible material.
VERTICAL VENTING
Categorized
Furnace Vent
Input Size Recommended
(See NFGC)
50K 3”
75K *4”
100K *4”
125K *5”
150K *5”
*NOTE: All furnaces have a 3” vent connection as shipped from the factory. A 3” to 4”, 3” to 5”, or 4” to 5” vent transition may be required when
vertically vented or common vented with metal vent pipes. THE VENT
TRANSITION CONNECTION MUST BE MADE AT THE FURNACE
VENT EXIT. It must originate with an adapter if required, at the furnace
flue collar and terminate either in a listed cap or roof assembly. When
common venting, the vent connector size may differ from the above diameters depending on application. See National Fuel Gas Code ANSI
Z223.1 or latest edition tables.
Combustion Air
19
COMBUSTION AND VENTILATION AIR (cont.)
LISTED CAP
LISTED GAS VENT
ROOF PITCH = X/12
12
X
- MINIMUM ALLOWABLE HEIGHT
F
ROOF PITCH“H” (MIN.) FT.
FLAT TO 6/12 1.0
OVER 6/12 TO 7/12 1.25
OVER 7/12 TO 8/12 1.5
OVER 8/12 TO 9/12 2.0
OVER 9/12 TO 10/12 2.5
OVER 10/12 TO 11/12 3.25
OVER 11/12 TO 12/12 4.0
OVER 12/12 TO 14/12 5.0
OVER 14/12 TO 16/12 6.0
OVER 16/12 TO 18/12 7.0
OVER 18/12 TO 20/12 7.5
OVER 20/12 TO 21/12 8.0
ST-A1220-24
VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed
cap or listed roof assembly. Gas vents 12 inches in size or
smaller with listed caps shall be permitted to be terminated in
accordance with Figure 15, provided they are at least 8 feet
rom a vertical wall or similar obstruction. All other gas vents
f
Combustion Air
shall terminate not less than 2 feet above the highest point
where they pass through the roof and at least 2 feet higher
than any portion of a building within 10 feet.
2. A type B-1 gas vent shall terminate at least 5 feet in vertical
height above the highest connected equipment draft hood or
flue collar.
1
3. Must rise
/4” per foot away from the furnace on horizontal runs
and be supported with straps or hangers so it has no sags or
dips. Supports at 4 foot intervals and at all elbows are recommended.
4. The vent connector must be mechanically fastened to the outlet collar of the furnace with at least (2) sheet metal screws except vent connectors that are B-1 material. These shall be
assembled in accordance with the manufacturer’s instructions.
See Figures 16 and 17.
5. Any angle greater than 45 degrees from the vertical is considered horizontal. The total horizontal distance of a vent plus the
horizontal vent connector serving draft-hood equipped appliances shall not be greater than 75 percent of the vertical
height of the vent.
Single appliance venting of a fan assisted furnace into a tile-lined
masonry chimney is prohibited. The chimney must be lined with
either Type B vent or with a listed, single wall, metal lining system. Reference National Fuel Gas Code, ANSI Z223.1 and/or the
Natural Gas Installation Code, CSA-B149.1 & .2. See Figure 18
or typical B-1 vent chase.
f
OTE: A chimney adapter is available as an accessory (see ac-
N
cessory section of this manual). Follow manufacturer’s instructions.
WARNING
!
DO NOT CONNECT THIS FURNACE TO A CHIMNEY USED
TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).
VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD TO
IMPROPER FUNCTIONING OF THE UNIT, AND DUE TO
SOOTING, THE POSSIBILITY OF FIRE RESULTING IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SPECIAL VENT SYSTEMS (SVS)
IMPORTANT: It is THE FURNACE MANUFACTURER’s position
now that new
III vent application, including Selkirk’s Selvent™ II HTPV product, should cease immediately.
installations of any HTPV pipe used in a category
FIGURE 15
TYPICAL VENTING WITH “B-1” VENT
ST-A1220-24
20
FIGURE 16
ATTACHING TO DRAFT INDUCER COLLAR
A0991-01
COMBUSTION AND VENTILATION AIR (cont.)
FR ESH AIR INLE T
ST-A1220-09-01
1. STANDARD 3” FLUE CONNECTION.
2. 4” ADAPTER - OPTIONAL
SEE NATIONAL FUEL GAS CODE FOR SIZING OPTIONS
1.
2.
FIGURE 17
Combustion Air
FIGURE 18
DEDICATED VENTING THROUGH
CHIMNEY WITH “B-1” VENT
ST-A1220-09
21
COMBUSTION AND VENTILATION AIR (cont.)
POWER VENT SYSTEMS
When vertical venting is not possible, the only acceptable method
for horizontal venting is with the use of Tjernlund model GPAK1TR or Field Controls models SWG-4R power venter. Type B
vent pipe and fittings must be used. Common venting is not per-
Combustion Air
mitted
All application and installation instructions supplied with the
power venter must be followed.
Please address all questions regarding power venter installation,
agency listings and furnace model compatibility to:
Tjernlund Products, Inc.
(800) 255-4208 or (612) 426-2993
Field Controls L.L.C.
(800) 742-8368 or (919) 522-0214
EXISTING VENT SYSTEMS
IMPORTANT RETROFIT
VENTING INSTRUCTIONS
If this furnace is a replacement installation, ALWAYS INSPECT
the existing vent system to be sure there are no obstructions,
blockages, or signs of corrosion.
When the existing furnace is removed from a venting system
serving other appliances, the venting is likely to be too large to
properly vent the remaining attached appliances.
The following steps shall be followed with each appliance that remains connected to the common venting system, while the other
appliances that remain connected to the common venting systems are not in operation.
NOTE: When the vent table permits more than one diameter
of pipe for a connector or vent, the smallest permitted diameter must be used.1. Seal any unused openings in the common venting system.
NOTE: Ensure existing venting system complies with latest addi-
tion of National Fuel Gas Code ANSI Z223.1 and all local
codes/regulations.
1. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage, restriction, leakage, corrosion or other deficiencies which could
cause an unsafe condition.
. Insofar as is practical, close all building doors, windows and all
2
doors between the space where the appliances remaining connected to the common venting system are located. Turn on
clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
3. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance
will operate continuously.
4. Test for spillage at the draft hood relief opening after 5 minutes
of main burner operation. Use the flame of a match or candle,
or smoke from a cigarette, cigar, or pipe.
5. After it has been determined that each appliance that remains
connected to the common venting system properly vents
(when tested as outlined above) return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
6. If improper venting is observed during any of the above tests,
the common venting system must be resized. Refer to National
Fuel Gas Code, ANSI Z223.1 and/or the Natural Gas Installation Code, CSA-B149.1 & .2.
22
GAS SUPPLY AND PIPING
GAS SUPPLY
IMPORTANT SAFETY INFORMATION
NATURAL GAS AND PROPANE
(LIQUEFIED PETROLEUM GAS / LPG)
SAFETY
GAS SUPPLY
ARNI
W
!
• FURNACES USING PROPANE GAS ARE DIFFERENT FROM NATURAL GAS MODELS. A NATURAL
GAS HEATER WILL NOT FUNCTION SAFELY ON
PROPANE AND VICE VERSA. CONVERSIONS OF
HEATER GAS TYPE SHOULD ONLY BE MADE BY
QUALIFIED INSTALLERS USING FACTORY SUPPLIED COMPONENTS. THE FURNACE SHOULD
ONLY USE THE FUEL TYPE IN ACCORDANCE
WITH LISTING ON RATING PLATE. ANY OTHER
FUEL USAGE WILL RESULT IN DEATH OR SERIOUS PERSONAL INJURY FROM FIRE AND/OR EXPLOSION.
• BOTH NATURAL GAS AND PROPANE HAVE AN
ODORANT ADDED TO AID IN DETECTING A GAS
LEAK. SOME PEOPLE MAY NOT PHYSICALLY BE
ABLE TO SMELL OR RECOGNIZE THIS ODORANT.
IF YOU ARE UNSURE OR UNFAMILIAR WITH THE
SMELL OF NATURAL GAS OR PROPANE, ASK
YOUR LOCAL GAS SUPPLIER. OTHER CONDITIONS, SUCH AS “ODORANT FADE,” WHICH
CAUSES THE ODORANT TO DIMINISH IN INTENSITY, CAN ALSO HIDE, CAMOUFLAGE, OR OTHERWISE MAKE DETECTING A GAS LEAK BY
SMELL MORE DIFFICULT.
• UL OR CSA RECOGNIZED FUEL GAS DETECTORS
ARE RECOMMENDED IN ALL ENCLOSED
PROPANE AND NATURAL GAS APPLICATIONS
WHEREIN THERE IS A POTENTIAL FOR AN EXPLOSIVE MIXTURE OF FUEL GAS TO ACCUMULATE.
FUEL DETECTOR INSTALLATION SHOULD BE IN
ACCORDANCE WITH THE DETECTOR MANUFACTURER’S RECOMMENDATIONS AND/OR LOCAL
LAWS, RULES, REGULATIONS, OR CUSTOMS.
• BEFORE ATTEMPTING TO LIGHT THE FURNACE,
MAKE SURE TO LOOK AND SMELL FOR GAS
LEAKS. USE A SOAPY SOLUTION TO CHECK ALL
GAS FITTINGS AND CONNECTIONS.
BUBBLING AT A CONNECTION INDICATES A LEAK
THAT MUST BE CORRECTED. WHEN SMELLING TO
DETECT A GAS LEAK, BE SURE TO ALSO SNIFF
NEAR THE FLOOR. PROPANE GAS IS HEAVIER
THAN AIR AND TENDS TO COLLECT AT LOWER
LEVELS MAKING IT MORE DIFFICULT TO SMELL AT
NOSE LEVEL. NATURAL GAS IS LIGHTER THAN AIR
NG
(Continued on next column)
AND WILL RISE, POSSIBLY ACCUMULATING IN
HIGHER PORTIONS OF THE STRUCTURE.
• IF A GAS LEAK IS PRESENT OR SUSPECTED:
- DO NOT ATTEMPT TO FIND THE CAUSE YOURSELF.
- NEVER
LEAKS. THE GAS CAN IGNITE RESULTING IN
DEATH, PERSONAL INJURY, OR PROPERTY
DAMAGE.
- DO NOTTRY TO LIGHT ANY APPLIANCE.
- DO NOTTOUCH AND ELECTRICAL SWITCH.
- DO NOT USE ANY PHONE IN YOUR BUILDING.
- LEAVE THE BUILDING IMMEDIATELY AND CALL
THE GAS SUPPLIER FROM A NEIGHBOR’S
PHONE. FOLLOW THE GAS SUPPLIER’S INTRUCTIONS.
- IF YOU CANNOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.
- DO NOT RETURN TO THE BUILDING UNTIL AUTHORIZED BY THE GAS SUPPLIER OR FIRE DEPARTMENT.
• SHOULD OVERHEATING OCCUR OR THE GAS
SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE FURNACE.
• CONSULT WITH THE LOCAL BUILDING DEPARTMENT AND FUEL GAS SUPPLIER BEFORE INSTALLING THE HEATER:
- THE INSTALLATION AND PURGING OF GAS PIPING MUST CONFORM TO LOCAL CODES, UTILITY COMPANY REQUIREMENTS, AND THE
LATEST EDITION OF NATIONAL FUEL GAS
CODE (NFGC) - ANSI Z223.1/NFPA 54, OR CSA
B149.1, NATURAL GAS AND PROPANE INSTALLATION CODE.
- LP FURNACES SHOULD NOT BE INSTALLED
BELOW GRADE (IN A BASEMENT FOR EXAMPLE) IF SUCH INSTALLATION IS PROHIBITED BY
FEDERAL, STATE, PROVINCIAL, AND/OR LOCAL
LAWS, RULES, REGULATIONS, OR CUSTOMS.
- INSTALLATION OF A GAS PRESSURE REGULATOR MAY BE REQUIRED IN THE GAS SUPPLY
LINE. THE REGULATOR SHOULD NOT EXCEED
THE MAXIMUM SUPPLY PRESSURE LISTED ON
THE FURNACE RATING PLATE. DO NOT USE AN
INDUSTRIAL-TYPE GAS REGULATOR.
- FOLLOW ALL LOCAL CODES AND SECTION 8.3
OF NFGC WITH REGARD TO PURGING OF GAS
PIPING TO ENSURE THAT THE AIR AND/OR FUEL
GAS IN THE GAS PIPING IS PROPERLY VENTED
TO A LOCATION WHERE AN EXPLOSIVE MIXTURE CANNOT ACCUMULATE.
USE AN OPEN FLAME TO TEST FOR GAS
Gas Supply
23
GAS SUPPLY
GAS PIPING
ARNI
W
!
NG
THIS FURNACE IS EQUIPPED AT THE FACTORY
FOR USE ON NATURAL GAS ONLY. CONVERSION
TO LP GAS REQUIRES A SPECIAL KIT IS AVAILABLE AT THE DISTRIBUTOR. FAILURE TO USE THE
PROPER CONVERSION KIT CAN CAUSE FIRE,
CARBON MONOXIDE POISONING, EXPLOSION,
PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH. SEE THE CONVERSION KIT INDEX SUPPLIED WITH THE FURNACE. THIS INDEX IDENTIFIES THE PROPER LP GAS CONVERSION KIT
REQUIRED FOR EACH PARTICULAR FURNACE.
IMPORTANT: Any additions, changes or conversions required for
the furnace to satisfactorily meet the application should be made
by a qualified installer, service agency or the gas supplier, using
Gas Supply
factory-specified or approved parts.
IMPORTANT: Connect this furnace only to gas supplied by a
commercial utility or commercial fuel provider.
IMPORTANT: A U.L. or CSA recognized fuel gas and CO detec-
tor(s) are recommended in all applications, and their installation
should be in accordance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
Install the gas piping according to all local codes, state codes and
regulations of the utility company, whichever holds jurisdiction.
If possible, run a separate gas supply line directly from the meter
to the furnace. Consult the local gas company for the location of
the manual main shut-off valve. The gas line and manual gas
valve must be adequate in size to prevent undue pressure
drop and never smaller than the pipe size to the combination
gas valve on the furnace. Refer to Table 6 for the recom mended
pipe size for natural gas and Table 7 for LP gas pipe sizes.
IMPORTANT: It is permissible to run flexible gas connector inside
the unit to a piece of black pipe. If local codes allow the use of a
flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another
gas appliance. Massachusetts law limits flexible gas connectors to
a maximum of 36”.
Install a ground joint union outside the cabinet and within 3
feet to easily remove the control valve assembly. Install a
manual shut-off valve in the gas line outside the furnace casing. The valve should be readily accessible to turn the gas supply
on or off. Install a drip leg in the gas supply line as close to the furnace as possible. Always use a pipe compound resistant to the
action of liquefied petroleum gases on all threaded connections.
IMPORTANT: When making gas pipe connections, use a back-up
wrench to prevent any twisting of the control assembly and gas
valve. Do not overtighten the connection.
Any strains on the gas valve can change the position of the gas
orifices in the burners. This can cause erratic furnace operation.
MPORTANT: ENSURE that the furnace gas control valve not be
I
subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual shut-off valve from
the gas supply piping during any pressure testing that exceeds
1/2 PSIG (3.48 kPa).
FIGURE 19
AS PIPING INSTALLATION
G
GAS PIPE INSTALLATION
ANUAL GAS VALVE
M
IN CLOSED
(
OSITION)
P
4 TO 5 FEET
ABOVE FLOOR
REQ'D BY SOME
UTILITIES
DRIP LEG
ABOVE FLOOR
REQ'D BY SOME
DRIP LEG
4 TO 5 FEET
UTILITIES
FLAME SENSOR
UNION
BURNERS
DIRECT
SPARK
IGNITOR
UPFLOW
BURNERS
FLAME SENSOR
HORIZONTAL
MANUAL GAS VALVE
(IN CLOSED POSITION)
DUCT
UNION
MANIFOLD
GAS VALVE
MANIFOLD
DIRECT SPARK
IGNITOR
GAS VALVE
24
GAS PRESSURE
GAS SUPPLY (cont.)
IMPORTANT: ENSURE that the furnace gas valve is not to be
subjected to high gas line supply pressures.
DISCONNECT the furnace and its individual manual gas stop
from the gas supply piping during any pressure testing that ex-
ceeds 1/2 PSIG. (3.48 kPa).
atural gas supply pressure must be 5" to 10.5" w.c. LP gas
N
upply pressure must be 11" to 13" w.c. This pressure must
s
be maintained with all other gas-fired appliances in operation.
The minimum gas supply pressure to the gas valve for proper furnace input adjustments is 5" w.c. for natural gas, however 6" to 7"
is recommended. The minimum gas supply pressure is 11" w.c.
for LP gas.
CAUTION
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE
FURNACE INPUT RATING BE ADJUSTED AND THAT
THE SIZE OF THE BURNER ORIFICES BE RECALCULATED BASED ON ELEVATION AND GAS HEATING VALUE. THE BURNER ORIFICES MAY (OR MAY
NOT) NEED TO BE CHANGED. SEE THE SECTION
TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS
BOOK FOR INSTRUCTIONS.
FIGURE 20
YPICAL GAS VALVE (WHITE RODGERS)
T
I
NLET
PRESSURE TAP
WARNING
!
LI
GAS
A
URGE
P
R
E
V
NE
ON
TI
OR
GE
A
US
CA
ROP
P
ATH.
DE
TO
ROV
P
LUTI
CHAMBE
ANY
FAI
.
A
E
RTY
E
CK
CHE
D
E
ON,
TI
GNI
I
LURE
RE
FI
AMA
D
FOR
CHLORI
OTHE
OR
R.
ON
TO
OR
GAS
V
NE
OURCE
S
ADHE
X
E
GE
-FRE
DE
AP
R
,
LE
E
P
P
R
RE
LOS
E
P
NE
US
RS
AKA
S
E
ROV
O
UTLET PRESSURE TAP
O
NT
I
MATCHE
E
FOR
THI
TO
RE
ON
I
ONAL
,
GE
OAP
ME
D
E
THE
CHE
W
S
ULTI
S
NJ
I
E
US
AND W
THOD.
LOW-FIRE
M
PRESSURE
ADJUSTMENT
COMBUS
FLAME
,
S
NG
CKI
NG
ARNI
UR
AN
NG
OR
Y
AP
I
-
ATE
HIGH-FIRE
MANIFOLD
P
RESSURE
ADJUSTMENT
ANIFOLD
-
AK
LE
CAN
N
-
O
S
R
Gas Supply
-
GAS VALVE
This furnace has a 24-volt gas valve. It has ports for measuring
supply and manifold gas pressure. The valve body contains a
pressure regulator to maintain proper manifold gas pressure.
A control switch is on the valve body. It can be set to only the
“ON” or “OFF” positions. The gas valve is a slow-opening valve.
See Figure 20.
When energized, it takes 2 to 3 seconds to fully open.
TABLE 6
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
gravity of 0.60 (natural gas).
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the furnace. By formula:
Cu. Ft. Per Hr. Required=
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT
termined by consulting the local natural gas utility or the LP gas supplier.
Gas Input of Furnace (BTU/HR)
Heating Value of Gas (BTU/FT
3
)
3
) may be de-
25
GAS SUPPLY (cont.)
GAS PRESSURE
SETTING GAS PRESSURE
The maximum gas supply pressure to the furnace
must not exceed 10.5" w.c. natural gas, or 13" w.c. LP
gas. The minimum supply gas pressure to the gas valve
should be 5⬙ w.c. natural gas or 11⬙ w.c. LP gas. A properly
calibrated manometer is required for accurate gas pressure measurements.
SUPPLY GAS PRESSURE
MEASUREMENT
An inlet pressure tap is on the input side of the gas valve.
1. With gas shut off to the furnace at the manual gas
valve outside the unit.
Gas Supply
2. Loosen (do NOT remove) the inlet pressure tap using
a 3/32⬙ allen-head wrench (see Figure 20).
3. Connect a manometer to the pressure tap. The pressure tap requires a 5/16⬙ I.D. hose.
A kit is available from Prostock Replacement Parts
which includes the following:
A. 3/32⬙ allen-head wrench
B. 5/16⬙ to 1/4⬙ hose reducer fitting
C. Short piece of 5/16⬙ I.D. hose
Kit part number is: F0092-100300S1
4. Turn on the gas supply and operate the furnace and all
other gas-fired units on the same gas line as the furnace.
5. Note or adjust the line gas pressure to give:
A. 5⬙ - 10.5⬙ w.c. for natural gas.
B. 11⬙ - 13⬙ w.c. for LP gas.
6. Shut off the gas at the manual gas valve and remove
the manometer and hose.
7. Tighten the allen-head screw in the inlet pressure tap
using a 3/32⬙ allen-head wrench (see Figure 20).
8. Turn on the gas supply and check for gas leaks using
an approved leak detector. Do NOT use a flame of any
kind to check for leaks. Repair any leaks and repeat.
If the supply gas line pressure is above these ranges, install an in-line gas regulator to the furnace for natural gas
units. With LP gas, have the LP supplier reduce the line
pressure at the regulator.
If supply gas line pressure is below these ranges, either remove any restrictions in the gas supply piping or enlarge
the gas pipe. See Tables 6 and 7. With LP gas, have the
LP supplier adjust the line pressure at the regulator.
ON
UTI
A
C
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE
FURNACE INPUT RATING BE ADJUSTED AND THAT
THE SIZE OF THE BURNER ORIFICES BE RECALCULATED BASED ON ELEVATION AND GAS HEATING VALUE. THE BURNER ORIFICES MAY (OR MAY
NOT) NEED TO BE CHANGED. SEE THE SECTION
TITLED “HIGH ALTITUDE INSTALLATIONS” OF THIS
BOOK FOR INSTRUCTIONS.
Manifold Gas Pressure Measurement. Natural gas
manifold pressure should be 3.5" w.c. for high fire and
1.8" w.c. for low fire. LP gas manifold pressure should
be 10.0" w.c. for high fire and 4.9" w.c. for low fire. Only
small variations in gas pressure should be made by adjusting the pressure regulator.
1. With the gas to the unit shut off at the manual gas
valve, remove the outlet pressure tap plug.
2. Loosen (do NOT remove) the outlet pressure tap plug
using a 3/32⬙ allen-head wrench (see Figure 20).
3. Connect a manometer to this pressure tap. The pressure tap requires a 5/16⬙ I.D. hose.
A kit is available from Prostock Replacement Parts
which includes the following:
A. 3/32⬙ allen-head wrench
B. 5/16⬙ to 1/4⬙ hose reducer fitting
C. Short piece of 5/16⬙ I.D. hose
Kit part number is: F0092-100300S1
4. Turn on the gas supply and operate the furnace (apply
a heat call).
5. Note or adjust the manifold gas pressure to give:
A. 3.5⬙ w.c. high fire/1.8⬙ w.c. low fire natural gas.
B. 10.0⬙ w.c. high fire/1.9⬙ w.c. low fire L.P. gas.
6. To adjust the pressure regulators, remove the regulator
caps. (See Figure 20.)
7. Turn the adjustment screw clockwise to increase pressure, or counterclockwise to decrease pressure.
8. Securely replace the regulator caps.
9. Shut off gas at the manual gas valve and remove the
manometer and hose.
10. Tighten the allen-head screw in the inlet pressure tap
using a 3/32⬙ allen-head wrench (see Figure 20).
11. Turn on the gas supply and apply a heat call to the furnace then check for gas leaks using an approved leak
detector. Do NOT use a flame of any kind to check for
leaks. Repair any leaks and repeat.
26
N
(
c
t
F
N
m
f
s
N
W
r
b
N
LP CONVERSION
O
T
E
:
T
h
e
v
a
l
v
e
c
a
n
b
e
c
o
n
v
e
r
t
e
d
t
o
u
s
e
l
i
q
u
i
f
i
e
d
p
e
t
r
o
l
e
u
m
4
.
T
u
r
n
t
h
e
g
a
s
s
u
p
p
l
y
b
a
c
k
o
n
a
n
d
c
h
e
c
k
f
o
r
p
r
o
p
e
r
o
p
e
r
L
P
)
g
a
s
b
y
r
e
p
l
a
c
i
n
g
t
h
e
p
r
e
s
s
u
r
e
r
e
g
u
l
a
t
o
r
s
p
r
i
n
g
w
i
t
h
t
h
o
e
n
v
e
r
s
i
o
n
k
i
t
s
p
r
i
n
g
.
T
h
i
s
L
P
k
i
t
s
p
r
i
n
g
a
l
l
o
w
s
t
h
e
r
e
g
u
l
a
t
o
o
m
a
i
n
t
a
i
n
t
h
e
p
r
o
p
e
r
m
a
n
i
f
o
l
d
p
r
e
s
s
u
r
e
f
o
r
L
P
g
a
i
g
u
r
e
2
1
.
O
T
E
:
O
r
d
e
r
t
h
e
c
o
r
r
e
c
t
L
P
c
o
n
v
e
r
s
i
o
n
k
i
a
n
u
f
a
c
t
u
r
e
r
.
F
u
r
n
a
c
e
c
o
n
v
e
r
s
i
o
n
o
r
m
e
d
b
y
a
q
u
a
l
i
f
i
e
d
i
n
s
t
a
l
l
u
p
p
l
i
e
r
.
O
x
M
O
D
E
L
S
h
e
n
c
o
n
v
e
r
t
i
n
g
f
u
r
n
e
m
o
v
e
t
h
e
N
e
l
o
w
1
.
T
u
2
.
R
3
.
R
4
.
R
b
r
5
.
P
6
.
R
7
.
R
8
.
T
u
O
T
E
O
:
r
n
o
f
f
a
e
m
o
v
e
t
e
m
o
v
e
t
e
m
o
v
e
t
a
c
k
e
t
t
o
u
t
t
h
e
t
w
e
-
i
n
s
t
a
l
l
e
p
l
a
c
e
b
r
n
o
n
e
:
S
o
m
e
a
x
i
n
s
e
r
t
l
l
e
l
e
c
t
r
i
c
h
e
b
u
r
n
e
h
e
b
u
r
n
e
h
e
t
w
o
s
t
h
e
c
e
n
t
o
s
c
r
e
w
s
t
h
e
b
u
r
n
u
r
n
e
r
d
o
l
e
c
t
r
i
c
a
l
p
N
O
x
m
o
d
e
c
e
s
e
q
u
a
s
s
e
m
b
a
l
p
o
w
e
r
d
o
o
r
f
r
r
a
s
s
e
m
c
r
e
w
s
a
t
e
r
p
a
n
e
b
a
c
k
i
n
e
r
a
s
s
e
m
o
r
.
o
w
e
r
a
n
e
l
s
m
a
y
r
,
s
e
r
v
i
i
p
p
e
d
w
i
l
i
e
s
.
S
t
e
r
a
n
d
t
h
e
o
m
t
h
e
f
b
l
y
–
h
a
t
a
c
h
i
n
g
l
a
n
d
r
e
m
t
o
t
h
e
h
b
l
y
.
d
g
a
s
s
h
a
v
e
o
t
t
o
L
P
g
a
c
e
a
g
e
n
t
h
N
O
x
i
p
s
f
o
r
r
e
g
a
s
s
u
p
u
r
n
a
c
e
.
n
d
l
e
w
i
t
t
h
e
N
O
x
o
v
e
N
O
o
l
e
s
i
n
t
h
u
p
p
l
y
t
o
n
e
l
e
s
s
N
s
f
r
o
m
t
h
e
s
m
u
s
t
c
y
o
r
t
h
n
s
e
r
t
s
t
o
m
o
v
a
l
a
r
p
l
y
t
o
t
h
h
c
a
r
e
.
i
n
s
e
r
t
r
e
x
i
n
s
e
r
t
s
e
c
e
n
t
e
r
t
h
e
u
n
i
t
.
O
x
i
n
s
e
r
.
S
e
e
f
u
r
n
a
c
b
e
L
e
e
t
a
.
p
r
t
e
e
p
e
r
-
g
a
s
P
g
a
s
,
l
i
s
t
e
d
f
u
r
n
a
c
e
.
i
n
e
r
a
n
e
l
.
.
a
t
i
o
n
a
n
d
m
a
n
i
f
o
l
d
p
r
e
s
s
u
r
e
.
5
.
A
t
t
a
c
h
t
h
e
n
o
t
i
c
e
l
a
b
e
l
a
l
e
r
t
i
n
g
t
h
e
n
e
x
t
s
e
r
v
i
c
e
t
e
c
i
a
n
t
h
a
t
t
h
e
f
u
r
n
a
c
e
h
a
s
b
e
e
n
c
o
n
v
e
r
t
e
d
t
o
L
P
g
ARNI
W
!
NG
LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FERTILIZER) EXCEPT LP GAS. THIS INCLUDES ALL DELIVERY VESSELS (LP TRUCKS). IF MATERIAL OTHER
THAN LP GAS IS USED IN THE SAME
VESSELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE FURNACE. THIS WILL VOID THE MANUFACTURER’S
WARRANTY. CONTACT THE SUPPLIER TO MAKE
SURE FERTILIZER IS NOT USED IN THE SAME
TANKS USED TO STORE AND DELIVER LP GAS.
FIGURE 21
TYPICAL LP KIT CONTENTS
-
c
h
n
i
-
a
s
.
LP Conversion
O
L
v
T
t
h
t
h
S
T
e
R
I
F
I
C
E
I
N
S
T
A
L
L
A
T
I
O
N
P
G
a
s
i
s
a
m
a
n
u
f
a
c
t
u
r
e
d
g
a
s
t
h
a
t
h
a
s
c
o
n
s
i
s
t
e
n
t
h
e
a
t
i
n
a
l
u
e
a
c
r
o
s
s
m
o
s
t
r
e
g
i
o
n
s
.
h
e
S
e
a
L
e
v
e
l
i
n
p
u
t
s
h
o
u
l
d
s
t
i
l
l
b
e
r
e
d
u
c
e
d
b
y
4
o
u
s
a
n
d
f
t
.
a
n
d
t
h
e
o
r
i
f
i
c
e
s
i
z
e
m
u
s
t
b
e
e
r
e
d
u
c
e
d
i
n
p
u
t
s
e
l
e
c
t
i
o
n
c
h
a
r
t
e
c
t
i
o
n
.
o
c
h
a
n
g
e
o
r
i
f
i
c
e
s
p
u
d
s
f
o
v
a
t
i
o
n
:
1
.
S
h
u
t
o
f
f
t
h
e
m
a
g
a
s
m
a
n
i
f
o
l
d
.
2
.
R
e
p
l
a
c
e
t
h
e
o
r
i
3
.
R
e
a
s
s
e
m
b
l
e
i
n
r
n
u
a
l
m
a
f
i
c
e
s
p
u
r
e
v
e
r
s
e
TABLE 7
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
27
LOCKING
TABS
ELECTRICAL WIRING
ELECTRICAL WIRING
ARNI
W
!
TURN OFF ELECTRIC POWER AT FUSE BOX OR
SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS. FAILURE TO DO SO CAN
CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
ARNI
W
!
THE CABINET MUST HAVE AN UNINTERRUPTED
GROUND ACCORDING TO THE LATEST EDITION OF
THE NATIONAL ELECTRICAL CODE, ANSI/NFPA70OR IN CANADA, THE CANADIAN ELECTRICAL
CODE, CSA-C221 OR LOCAL CODES THAT APPLY.
DO NOT USE GAS PIPING AS AN ELECTRICAL
GROUND. A GROUND SCREW IS PROVIDED IN THE
JUNCTION BOX. FAILURE TO DO SO CAN CAUSE
ELECTRICAL SHOCK RESULTING IN PERSONAL
INJURY OR DEATH.
WARNING
!
THIS FURNACE IS EQUIPPED WITH A BLOWER
DOOR SAFETY SWITCH. DO NOT DISABLE THIS
SWITCH. FAILURE TO FOLLOW THIS WARNING
CAN RESULT IN ELECTRICAL SHOCK, PERSONAL
INJURY OR DEATH.
NG
NG
These may be obtained from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
FIGURE 22
ST-A1220-05
ELECTRICAL CONNECTIONS
Before proceeding with the electrical connections, be certain that
the voltage, frequency and phase corresponds to that specified
on the furnace rating plate. For single furnace application, maximum over-current protection is 15 amperes.
Use a separate fused branch electrical circuit containing a properly sized fuse or circuit breaker. Run this circuit directly from the
main switch box to an electrical disconnect that is readily accessible and located near the furnace (as required by code). Connect
from the electrical disconnect to the junction box on the left side
of the furnace, inside the blower compartment. For the proper
connection, refer to the appropriate wiring diagram located on the
inside cover of the furnace control box and in these instructions.
NOTE: The electrical junction box may be moved to the right side
if necessary. A knockout is provided. Seal the opposite hole with
plug provided.
NOTE: L1 (hot) and L2 (neutral) polarity must be observed when
making field connections to the furnace. The ignition control may
not sense flame if L1 and L2 are reversed. Make all electrical
connections in accordance with the latest edition of the National
Electrical Code ANSI/NFPA70.
Electrical Wiring
28
REVERSING THE ELECTRICAL
CONNECTION (JUNCTION BOX)
If the line voltage electrical needs to be moved to the opposite
side of the furnace, the following steps should be taken:
1. The furnace must NOT be electrically connected to line voltage prior to reversing the electrical connection.
2. Disconnect the wires from the door switch.
3. Remove the junction box from the furnace cabinet wall by removing the two screws that hold it to the cabinet. Leave the
wires connected to the junction box.
4. Remove 7/8” plug from hole opposite j-box location. Drill 2 @
3/16” Ø holes in the jacket. NOTE: Dimples/marks are provided in the sheet metal for correct drilling location.
5. Move the junction box to the opposite side of the cabinet. Install using the two screws removed in step 3 above. Note
that all screws penetrating the junction box must be blunt –
no sharp tipped screws can be used.
6. Replace the plug from the opposite of the furnace (the new jbox location) to the old j-box location and install qty=2 1/4”
plugs from parts bag in empty screw holes in old location of
j-box into the mounting screw holes in the old junction box location.
ELECTRICAL WIRING
2
2
2
HEAT COOL
LOW
HT/FAN
M2 M1 H/C
EAC
L1B XFMRHUM
SPARK
IGNITION
TOWER
NEUTRALS
LINE
P2
REVERSING ELECTRICAL CONNECTION & THERMOSTAT
7. Using a flat screwdriver, squeeze the retaining arms on the
door switch and gently pry the door switch from it’s opening.
8. Install the door switch in the same opening on the opposite
of the furnace and reconnect the electrical connectors (re-
oved in Step 2) to the door switch.
m
THERMOSTAT
See Field Selections – Dipswitchs for heating “auto staging” options. The room thermostat must be compatible with the furnace.
See manufacturer’s thermostat spec sheet for compatability concerns. Generally, all thermostats that are not of the “current robbing” type are compatible with the integrated furnace control. The
low voltage wiring should be sized as shown.
FIGURE 23
TYPICAL THERMOSTAT WIRING
NOTE: Do not use 24 volt control wiring smaller than No. 18
AWG.
Install the room thermostat in accordance with the instruction
sheet packed in the box with the thermostat. Run the thermostat
ead wires inside the blower compartment and connect to low
l
voltage terminals as shown on the wiring diagram. Never install
the thermostat on an outside wall or where it will be influenced by
drafts, concealed hot or cold water pipes or ducts, lighting fixtures, radiation from fireplace, sun rays, lamps, televisions, radios
or air streams from registers.
FIGURE 24
SOLATION RELAY
I
FIGURE 25
LINE VOLTAGE CONNECTIONS
ST-A1227-06
ST-A1205-08A-X0
Electrical Wiring
ST-A1227-07
29
ACCESSORIES
FI
E
LD
I
N
S
T
A
LLE
D
OP
TI
ON
AC
C
E
S
S
OR
I
E
S
ELECTRONIC AIR CLEANER
Line voltage power can be supplied from the terminal labeled
“EAC” and a line voltage neutral terminal on the control board.
This will power the electronic air cleaner whenever the circulating
Accessories
air blower is in operation.
HUMIDIFIER
Line voltage power is supplied from the terminal labeled “HUM” to
a line voltage neutral terminal on the control board. This will
power the humidifier whenever the induced draft motor is energized.
NOTE: Maximum current – 1.0 amps for each option (humidifier
or electronic air cleaner).
RXGW-C01 4-INCH FLUE ADAPTER
(See Figure 26)
Refer to “Venting” section of this manual for more information. See
National Fuel Gas Code for sizing options.
FILTERS (See Figure 26)
eep filters clean at all times. A filter is not provided with the
K
furnace, but one must be field-supplied and installed.
It is recommended to replace the furnace filter periodically to
maintain optimum furnace performance.
RXGW-B01 CHIMNEY ADAPTER
IMPORTANT: CHIMNEY ADAPTER IS CERTIFIED FOR USE
ON (-)802P MODELS.
This appliance is CSA certified for use with RXGW-B01 Chimney
Adapter. Refer to Kit Installation Instructions 92-101682-01.
30
ST-A1220-07-X0
RXGF-CD
ACCESSORY FILTER RACK
FIELD SUPPLIED FILTER
FLANGE WRAPS
AROUND BACK AND
S
CREWS TO T HE
R
EAR OF THE
FUR NCE, AT THE
L
OCATIONS
PROVIDED
CUT OUT USING
E
MBO SSED ANGL ES
AS A GUID E
FOR PROPER SIZE
23” X 14”
RXGF-CB
$&&(6625<),/7(55$&.
FIELD SUPPLIED FILTER
ST-A1220-06-X0
F
I
E
L
D
FIGURE 26
ILTER LOCATIONS
F
ACCE
I
N
S
T
A
L
L
E
D
O
P
T
I
O
N
A
C
C
E
S
S
O
R
I
E
S
(
c
o
n
S
S
ORIE
t
.
)
S
Accessories
FIELD SUPPLIED FILTER
BOTTOM RETURN
SIDE RETURN
RXGF-CB ACCESSORY
FILTER RACK
ST-A1220-07-00
ST-A1220-06-00
HORIZONTAL RETURN
31
TWINNING
FU
R
N
AC
E
TW
I
N
N
I
N
G
I
N
S
T
A
LLA
TI
ON
S
Twinning operation of two furnaces, installed side-by-side,
connected by a common duct system with main power
supplied by the same source, and controlled by a common
thermostat can be done with the UT Electronic Controls
1095-300 integrated control boards.
IMPORTANT: Only twin furnaces with identical control boards.
IMPORTANT: Only bottom returns can be used. No more than
two furnaces can share the same supply and return. Furnaces
must have same heating and blower capacity. Twinning furnaces
must operate off the same phase of power.
It should be noted that both blowers will run simultaneously when
there is a call for heating, cooling or fan.
NOTE: Duct system must be adequate to provide correct airflow
Twinning
to each furnace for supply and return.
UT ELECTRONIC CONTROLS
1095-300 CONTROL BOARD
(62-104059-01)
1. Single Stage Operation
a. Control board “ONE” is on furnace connected to the
thermostat.
b. The 24 VAC supply to both control boards must be
in phase with each other.
c. Connect the “C,” “W”, “W2” and “TWIN” terminals to
counterparts on each control.
d. Twinning is automatically detected when wire is con-
nected to the twin terminal on both controls. If twinning is detected and then lost in the same power
cycle, the furnace control will declare and display
fault code 20 at the seven-segment display.
➀ See Figure 27 for twinning wire diagram for 1-stage
thermostat.
➁ See Figure 28 for twinning wire diagram for 1-stage
thermostat and times staging.
➂ See Figure 29 for twinning wire diagram for a 2-stage
thermostat.
32
C
ON
TR
OL
B
OA
R
D
TWINNING
S
ST-A1205-05-X0
Twinning
FIGURE 27
UT ELECTRONIC CONTROLS 1095-300 CONTROL BOARD, TWINNING CONNECTION – SINGLE STAGE OPERATION
33
TWINNING
C
ON
TR
OL
Twinning
B
OA
R
D
S
(
cont
.
)
ST-A1205-06-X0
FIGURE 28
UT ELECTRONIC CONTROLS 1095-300 CONTROL BOARD, TWINNING CONNECTION – ONE STAGE THERMOSTAT & TIMED STAGING GAS HEAT OPERATION
34
C
ON
TR
OL
B
OA
R
D
S
(
cont
TWINNING
.
)
ST-A1205-07-X0
FIGURE 29
UT ELECTRONIC CONTROLS 1095-300 CONTROL BOARD, TWINNING CONNECTION –TWO-STAGE OPERATION
Accessories
35
HIGH ALTITUDE
NATURAL GAS AT HIGH ALTITUDES
From Table F.1 of National Fuel Gas Code Handbook, 2002 (3.5ⴖ
WARNING
!
INSTALLATION OF THIS FURNACE AT ALTITUDES ABOVE
2000 FT (610 m) SHALL BE IN ACCORDANCE WITH
LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES,
HE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54
T
OR NATIONAL STANDARD OF CANADA, NATURAL GAS
AND PROPANE INSTALLATION CODE, CAN B149.1.
ON
UTI
A
C
!
ELEVATIONS ABOVE 2000 FT. REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE
OF THE BURNER ORIFICES BE RE-CALCULATED BASED
ON ELEVATION AND GAS HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT) NEED TO BE CHANGED.
THE FOLLOWING EXAMPLES SHOW HOW TO DETERMINE IF AN ORIFICE CHANGE WILL BE NECESSARY
AND HOW TO DETERMINE THE NEW ORIFICE SIZE.
34" 80 Plus furnaces installed above 2,000 ft. require the furnace
to be de-rated 4% per thousand feet.
IMPORTANT: Factory installed orifices are calculated and sized
based on a sea level Natural Gas heating value of 1050 BTU per
cubic ft.
NOTE: Orifices are available through your local distributor.
Reference Table 8 for approximate orifice sizing.
The following are examples of orifice sizing using the National
Fuel Gas Code Appendix F:
For a simplified estimation of orifice size based on gas heating
value and elevation, Table 8 may be used. However, calculations
are the best method.
Example: 900 BTU/ft
I/H = Q
25000 / 900 = 27.78 ft
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 900
Q = 27.78 ft3Natural Gas per hour.
3
Regional Natural Gas Heating Value
3
w.c. column).
Orifice required at Sea Level: #40
From Table F.4 of National Fuel Gas Code Handbook, Orifice re-
quired at 5000 ft. elevation (4% de-rate per thousand ft): #42
Orifice required at 8000 ft. elevation (4% de-rate per thousand ft.):
#44
Example: 1050 BTU/ft3 Regional Natural Gas Heating Value
I / H = Q
25000 / 1050 = 23.81ft
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 1050
Q = 23.81 ft3Natural Gas per hour.
From Table F.1 of Natural Fuel Gas Code Handbook, 2002 (3.5⬙
w.c. column).
Orifice required at Sea Level: #43
From Table F.4 of National Fuel Gas Code Handbook, 2002
Orifice required at 5000 ft. elevation (4% de-rate per
thousand ft.): #45
Orifice required at 8000 ft elevation (4% de-rate per
thousand ft): #47
ORIFICE ORDERING INFORMATION
Orifice sizes are selected by adding the 2-digit drill size required in
the orifice part number. Drill sizes available are 39 through 64;
metric sizes available 1.10mm (-90) and 1.15mm (-91):
Orifice Part Number 62-22175-(drill size)
Example 1:
# 60 drill size orifice required
Part # 62-22175-60
Example 2:
1.15mm drill size orifice required
Part # 62-22175-91
3
High Altitude
36
Notes:
3. This chart is based on the National Fuel Gas Code (NFGC) Annex F based on natural gas with a secific gravity of 0.60
Sea Level
to 1,999'
2,000' to
2,999'
3,000' to
3,999'
4,000' to
4,999'
5,000' to
5,999'
6,000' to
6,999'
7,000' to
7,999'
8,000' to
8,999'
9,000' to
9,999'10,000'
43444444454546474748
42424343434444454647
42
424343434444454647
41
424242434344444546
40
41
42
42424343444445
39
404141424243434444
38
394041414242434344
37
383939404142424343
37
383939404142424343
36
373838394041414243
35
363637373839404142
5. Furnace operation is optimized when operating at design rate. Installer is responsible to verify rate.
6. This table applies to 80+ models only with 25,000BTU/Burner. DO NOT
USE THIS CHART FOR ANY 90+ FURNACE MODEL.
NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE & ELEVATION*
*Table is derived from Appendix of the National Fuel Gas Code . To determine the correct orifice for your installation consult the National
Fuel Gas Code tables F.1 and F.4
2. Local utilities adjust the sea level heating value of gasses used at higher elevations to compensate for appliance operation at altitude.
Installer must be aware of the local heating value (sea level standard) to use the chart below.
4. The recommended orifices below allow the furnace to operate within 10% of design rate. However, NFGC calculations are the best
method.
1. All(-)80+ units are factory equiped with orifices sized for 1050 sea level heating value gas.
ELEVATION
Grey Cells Indicate Factory
Orifice Size
Gas Heating
Value
(BTU's/ft
3
)
@ Sea
Level**
1,000-1,100
900-999
800-899
700-799
**Be sure to use sea level heating value. When requesting the heating value from a local utility, it must be converted to sea level equivalent
in order to use this table.
N
ATU
TABLE 8
SUPPLEMENTAL ORIFICE SIZE CHART
R
A
L
GA
S
AT
H
I
GH
HIGH ALTITUDE
A
L
TI
TU
D
E
S
(
cont
.
)
High Altitude
37
HIGH ALTITUDE
LP
GA
S
AT
H
I
GH
A
L
TI
TU
D
E
S
LP GAS (TABLE 9)
NOTE: Keep any parts removed during LP conversion procedure
tored with the product literature for future use.
s
LP Gas is a manufactured gas that has consistent heating value
across most regions.
The NFGC guidelines are used with the following exception:
The recommended LP Gas high altitude orifice selections differ
slightly in that the NFGC LP orifice chart, as they are not accurate
for these products. The National Fuel Gas Code LP orifices are
based on an 11" of water column pressure at the orifice, which differs from products that use 10" of water column at the orifice. This
difference requires a deviation from the NFGC orifice size recommendations. The Sea Level input should still be reduced by 4%
per thousand ft. and the orifice size must be selected based on
the reduced input in Table 9.
38
S
E
QU
E
N
C
E
OF
OP
E
R
A
TI
ON
START-UP PROCEDURES
S
This furnace is equipped with a direct ignition control. Each time
the room thermostat calls for heat, the ignitor lights the main
burners directly. See the lighting instructions on the furnace.
TO START THE FURNACE
1. Remove the burner compartment control access door.
2. IMPORTANT: Be sure that the manual gas control has been
in the “OFF” position for at least five minutes. Do not attempt
to manually light the main burners.
3. Turn off the furnace electrical power and set the room thermostat to its lowest setting.
4. Turn the gas control to the “ON” position or move the gas
control lever to the “On” position.
5. Replace the burner compartment control access door.
6. Turn on the furnace electrical power.
7. Set the room thermostat to a point above room temperature
to light the main burners.
8. After the burners are lit, set the room thermostat to a desired
temperature.
9. Operate gas heat for a minimum period of 15 minutes and adjust input rate (page 44) and observe condensate system for
leaks. Correct leaks and set rate, shutdown furnace and repeat until no leaks in condensate system can be detected.
TO SHUT DOWN THE FURNACE
1. Set the room thermostat to its lowest setting and wait for furnace to shut down.
2. Remove the burner compartment control access door.
3. Shut off the gas to the main burners by turning the gas control
to the “OFF” position.
WARNING
!
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY
FAIL TO SHUT OFF, CLOSE THE MANUAL GAS VALVE
FOR THE APPLIANCE BEFORE SHUTTING OFF THE
ELECTRICAL SUPPLY. FAILURE TO DO SO CAN CAUSE
AN EXPLOSION OR FIRE RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
SEQUENCE OF OPERATION
UT ELECTRONIC CONTROLS
Integrated Controls with Direct Spark Ignition.
1. Each time the thermostat “W” (Heating) contacts close, the
furnace control checks to make sure the pressure switch is
open. Next the induced draft blower (inducer) begins a prepurge cycle. Inducer starts on high.
2. After proving high and low pressure switches have closed, inducer slows to low speed.
3. After the 30-second pre-purge, the gas valve opens on low
fire for an 8-second trial for ignition.
4. The spark igniter is energized to light the gas burners and
stays energized for the up to 7 seconds after the gas
valve opens.
5. 8 seconds after the gas valve opens the remote flame sensor must prove flame ignition for one second using the
process of flame rectification. If the burners don’t light, the
system goes through another ignition sequence. It does this
up to four times before entering a 1-hour lockout.
6. The main blower starts approximately 20 seconds after the
burners ignite.
7. After blower starts unit will shift to either low or high heat as
determined by thermostat.
8. When the thermostat “W” (Heat Call) ends, the gas valve
closes, flame is extinguished, the induced draft blower stops
after a 10-second post-purge, and the negative pressure
switches opens.
9. The main blower continues until timed off by the setting on
the integrated furnace control board.
Sequence if the system doesn’t light or doesn’t sense flame:
1. On a call for heat, the furnace control checks to make sure
the pressure switch is open. Next the control runs the inducer
for 30 seconds to prepurge.
2. After the 30-second pre-purge, the gas valve opens for an 8second trial for ignition. The inducer continues and the igniter
stays energized.
3. If flame is not sensed during the 8th second after the gas
valve opens, the gas valve closes, and the igniter de-energizes.
4. The inducer stops (may take up to 20 seconds for inducer fan
to stop rotating) and the control verifies that the pressure
switch has opened. Once the open pressure switch is confirmed, the control begins the next ignition cycle by energizing
the inducer for a pre-purge of 30 seconds. After a 30-second
pre-purge period, the gas valve is energized and the control
looks for a flame signal for up to 8 seconds. If no flame is
sensed, the cycle is repeated up to 4 times before entering a
1-hour lockout.
All furnace controls come standard with a 7-segment diagnostic
display. During standby mode with no fault codes present, the
display will read “0” (zero). During normal thermostat heating,
cooling or continuous fan operation, a letter will be displayed to
describe the mode of operation as follows:
C = Cooling or Heat-Pump Heat Operation
F = Continuous Fan Operation
H = Gas Heating Operation
When the control senses a fault present, it will display a code to
help in diagnoses. A list of normal operating codes and potential
fault codes follows:
The method for displaying a two-digit fault is to display the first
(most significant) digit for one second immediately followed by
the second digit – which is also displayed for a duration of one
second. A ½ second pause is then displayed. Cycle repeats until
the fault is cleared. Each fault is flashed (displayed) a minimum
of two times even if the fault condition has cleared before the
fault can be displayed twice.
Sequence of display:
A. The first two-digit fault will be displayed once as described
above.
B. The upper-most horizontal segment of the seven-segment
display is energized for ½ second.
C. The second two-digit fault is displayed once as described
above.
D. The upper-most horizontal segment of the seven-segment
display is energized for ½ again.
This cycle repeats until one fault is gone (in which case the remaining fault will be displayed as described above) or both faults
are gone or otherwise as noted below:
1. When a failed ignition has occurred four times in a row, the
control enters one-hour lockout and fault codes “10” and
“11” will be displayed alternately as described above.
2. When flame is lost five times in a row, the control enters onehour lockout and fault codes “10” and “13” will be displayed
alternately as described above (A-D).
3. While the control is in one-hour lockout due to an unexpected
flame, the fault codes “14” (unexpected flame) and “10” (soft
lockout) will be displayed alternately at the seven-segment
display as described above (A-D).
4. While the control has entered a one-hour lockout after declaring a dead blower after the main limit control has been open
for more than 150 seconds, the fault codes “61” (Non-operational blower) and “10” (soft lockout) will be displayed alternately as described above (A-D). Note: the dead blower fault
and associated one-hour lockout will occur up to four times in
one heat call. Upon declaring this fault for the fourth time in
one heat call, the control will enter hard lockout.
5. When the main limit has been open during a gas heat call for
more than 150 seconds and has not yet re-closed, the fault
codes “61” (Non-operational blower) and “22” (open limit)
will be displayed alternately as described above (A-D) until
the limit re-closes.
The higher priority fault code will be displayed until the condition
is corrected then the lower priority fault code will display (provided the fault condition is still present).
DUAL FAULTS DISPLAYED
In some cases when two faults are present simultaneously, both
faults are displayed. These exceptions for dual faults are noted
below.
Fault Codes
40
L
O
C
K
O
U
T
1-S
TAGE
LOCK
OUT
All lockout conditions can be cleared immediately provided that
he original fault causing the lockout is cleared and power to the
t
unit is cycled off and then back on again or (soft lockout only) if a
heat call is cycled off for greater than 2 seconds but less than 20
seconds.
The furnace control will not initiate a heat cycle during any lockout condition. A call for compressor or continuous fan will generally be responded to but control will display the lockout error fault
code instead of the “C” (for compressor) or “F” (for Continuous
fan).
FIVE-MINUTE LOCKOUT
A five minute “soft” lockout will be initiated if the low pressure
switch fails to close after 60 seconds of continuous inducer operation at the beginning of a normal heat cycle (pressure switch
proving period). The seven-segment display will display the appropriate fault. Lockout will automatically be reset after five minutes.
ONE-HOUR LOCKOUT
A one hour “soft” lock out will be initiated when:
- Flame has not been detected after four ignition trials.
- Flame has been lost for five times in one heat call.
- Undesired flame has been detected. The one-hour period will
commence after flame is no longer detected.
- Dead Blower has been detected (main limit circuit open for
more than 150 seconds)
- When voltage has unexpectedly been detected on the gas
valve circuit and voltage goes away when inducer is shut off.
The seven-segment display will alternately display “10” and the
code number for the fault causing the lockout. Lockout will automatically be reset after one hour
HARD LOCKOUT
Three conditions shall cause a hard lockout:
1. The control senses an unspecified internal fault. Fault code
“93” is set and displayed. This lockout condition cannot be
reset by cycling the heat call.
2. Voltage is detected unexpectedly on the gas valve contacts
(welded relay) and will not clear by cycling the inducer. Fault
code “93” is set and displayed. This lockout condition cannot
be reset by cycling the heat call.
3. The furnace control will declare that the blower motor is inoperable (dead) if the main limit control has been open for more
than 150 seconds. Gas heating is terminated. However, the
control continues to try to operate heating for up to four attempts in case the blower motor starts working again. If a
dead blower has been declared four times in one heat call,
the furnace control enters a hard-lockout. Fault code “61” is
set and displayed. This lockout condition CAN
cling the heat call.
be reset by cy-
Lockout
41
FI
E
LD
FIE
S
E
LE
C
LD S
TI
ON
S
E
–– D
LE
I
P
CTIONS
S
W
I
TC
H
E
& ADJUS
S
TM
E
NTS
A dipswitch bank; SW1 is provided for some field adjustments. Heating blower off delay, cooling (and heat-pump)
blower off delay, display (7-Segment) orientation and fault
clear are the adjustments and functions that can be handled using the dipswitches.
Seven-Segment Display Orientation; SW1
As the control will be applied in a multi-position furnace a
means of changing the orientation of the seven segment
display is required. This dipswitch is to be labeled SW1.
Factory setting of the SW1 dipswitch is OFF. The factory
setting display orientation is with the control placed in a
vertical orientation and the low voltage terminal block T2 is
on the left.
Cool Blower-Off Delay; SW2 & SW3
A means of selecting the cooling speed blower “off” delay
time is provided. In legacy mode, dipswitches are required
to select the delay time. These dipswitches are to be la-
Field Selections
beled SW2 and SW3. The following table defines the settings:
There are applications where a single stage thermostat is
used with the two stage furnace. With this application the
furnace will initially operate in the low heat stage. Based
upon a user selected time, the furnace will automatically
stage to high heat stage mode. auto staging will take place
with a 24VAC signal on “W1” when autostaging is turned
on. “W2” will be recognized as a call for stage 2 heat even
when autostaging is active. The following dipswitches are
available to accommodate this requirement:
Faults will automatically be cleared from the fault buffer after one
week. The fault buffer can also be manually cleared if this is desired. For the first 30 seconds after a change in state of dipswitch SW8, the furnace control will wait to determine if the
ADJUS
I
T
C
H
E
S
(
c
o
n
t
i
n
u
e
C
DONONAutoStage, 20 minutes on
Manual Fault Clear; SW8
For the first 30 seconds after a change in state of dipswitch
SW8, the furnace control will wait to determine if the switch
becomes on/off/on/off/on/off or off/on/off/on/off/on within
30 seconds. When this action is detected within 30 seconds, the fault code memory buffer shall be cleared.
switch becomes on/off/on/off/on/off or off/on/off/on/off/on
within 30 seconds. When this action is detected within 30 seconds, the fault code memory buffer shall be cleared. Be sure to
return the dipswitch to the original state (on or off) or is in the desired position after clearing the fault buffer using this method.
OFFONAutoStage, 15 minutes on
TM
d
)
low, then to high with call
on “W1”
low, then to high with call
on W1” *(ref only)
E
NTS
Field Selections
FAULT RECALL
Upon power reset, the three most recent faults which are
less than one week old will be flashed in succession from
the most recent to the oldest. This will be done as a diag-
FLAME STATUS L.E.D. (AMBER)
A yellow or amber L.E.D. is provided to indicate flame status. When normal flame is sensed, the flame L.E.D. is continuously on. The flame L.E.D. will flash at a rate of one to
four flashes per second if a weak flame is detected. If an
unexpected flame is detected, the L.E.D. will flash rapidly.
TIMING DIAGRAM
On the next page is a timing diagram for normal heat sequence. This diagram assumes no faults are present during the heat call.
nostic aid to the field technician. After one week, a fault will
be removed from the fault buffer.
The L.E.D. is off when there is no flame detected.
For more diagnostics information, consult the wiring diagram and troubleshooting chart at the end of this book.
43
TIM
ING DIAGRAM
, FIE
LD S
E
LE
CTIONS
&
ADJUS
TABLE 10
IMING DIAGRAM
T
Field Selections
TM
E
NTS
ST-A1205-10-X0
ADJUSTING OR CHECKING FURNACE INPUT
The maximum gas supply pressure to the furnace should
be 10.5" w.c. for natural gas and 13.0" w.c. for L.P. The
minimum gas supply pressure for purposes of input adjustment to the furnace should be 5" w.c for natural gas and
11.0" w.c. for L.P.
A calibrated manometer is required for accurate gas pres-
sure readings.
The manifold pressure should be set at 3.5" w.c. high fire,
1.8" low fire, for natural gas and 10.0" w.c. high fire and
4.9" w.c. low fire for L.P. Only small variations in the gas
flow should be made by means of the pressure regulator
adjustment. In no case should the final manifold pressure
vary more than plus or minus 0.3" w.c. from the abovespecified pressures. To adjust the pressure regulator, remove the regulator cap and turn the adjustment screw
clockwise to increase pressure or counterclockwise to decrease pressure. Then replace the regulator cap securely.
Any necessary major changes in the gas flow rate should
be made by changing the size of the burner orifices.
To change orifice spuds, shut off the manual gas valve and
remove the gas manifold. On LP gas furnaces, the LP gas
supply pressure must be set between 11" and 13" w.c. by
means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10" w.c. at the gas
control valve. For elevations up to 2,000 feet, rating plate
input ratings apply. For high altitudes (elevations over
2,000 ft.), see conversion kit index for derating and orifice
spud sizes.
Checking furnace input is important to prevent over firing
beyond its design-rated input. NEVER SET INPUT ABOVE
THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate. Start the furnace and measure the time required to burn one cubic foot
of gas. Prior to checking the furnace input, make certain
that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace
in operation.
The furnace is shipped from the factory with #42 orifices.
They are sized for natural gas having a heating value of
1050 BTU/cu. ft. and a specific gravity of .60.
Since heating values vary geo-graphically, the manifold
pressure and/or gas orifice size may need to be changed
to adjust the furnace to its nameplate input. Consult the
local gas utility to obtain the yearly average heating value
and orifice size required to fire each individual burner at
25,000 BTU/HR.
NOTE: Refer to the High Altitude Section of this manual
and the National Fuel Gas Code for high altitude rate adjustment above 2,000 ft.
45
AIRFLOW
E
NERGY
PERFORMANCE
VERIFIED
802PA075417MSA
XXXXXX
HIGH FIRE
AIR TEMPERATURE RISE
LOW FIRE FIRE
25 TO 55 °F (°C)
20 TO 50 °F (°C)
91-22176-09
ASSEMBLED IN THE USA
The importance of proper air flow over the heat exchanger cannot
be over emphasized.
CAUTION
!
IT IS IMPORTANT THAT EACH DUCT SYSTEM BE SIZED
AND INSTALLED FOR THE SPECIFIC APPLICATION BY
PROPERLY APPLYING THE APPROPRIATE INDUSTRY ACCEPTED STANDARD. IF LESS THAN MINIMUM STANDARDS ARE APPLIED, THE EQUIPMENT USER COULD
EXPECT TO EXPERIENCE HIGHER UTILITY BILLS, MAJOR
COMPONENT FAILURE, VARYING DEGREES OF AIR
NOISE OR OTHER UNSATISFACTORY ISSUES, OVER
WHICH THE MANUFACTURER HAS NO CONTROL.
One of the most common causes of heat exchanger failure is overheating due to low air flow. An air flow table is located inside the
blower door and on the following pages.
TEMPERATURE RISE CHECK
To determine if the air flow is correct, make a temperature rise
check.
1. Insert a thermometer in the supply air duct as close to the furnace as possible yet out of a direct line from the heat exchanger. See Figure 31.
2. Insert a thermometer in the return air duct as close to the furnace as possible.
3. Operate the furnace.
4. When the thermometer in the supply air duct stops rising (approximately five minutes), subtract the return air temperature
from the supply air temperature. The difference is the temperature rise.
Airflow
5. Compare the measured temperature rise to the approved temperature rise range listed on the furnace name plate. See Figure 32.
If the measured temperature rise is above the approved range, either the air flow is too low or the manifold pressure needs to be adjusted. More air must be moved by speeding up the blower, by
removing restrictions in the duct system, or by adding more supply
or return air duct. If the measured temperature rise is below the approved range, either the air flow is too much or the manifold pressure needs to be adjusted. Use lower speed tap on the multi-speed
blower.
IMPORTANT: The measured temperature rise should be in the
middle of the range.
IMPORTANT: Some high-efficiency filters have a greater than normal resistance to airflow. This can adversely affect furnace operation. BE SURE TO CHECK AIRFLOW if using any filter other than
factory-provided filter.
FIGURE 31
EMPERATURE RISE MEASUREMENT
T
FIGURE 32
TYPICAL FURNACE NAME PLATE
WARNING
!
THE MEASURED TEMPERATURE RISE SHOULD BE AS
CLOSE TO THE MIDDLE OF THE STATED RANGE AS POSSIBLE. FOR EXAMPLE, IF THE RISE RANGE IS 40 TO 70°F
(4.5°-21°C), THE MIDDLE OF THE RISE RANGE IS 55°F
(12.8°C). IN ALL APPLICATIONS, THE INSTALLER MUST ADJUST THE TEMPERATURE RISE TO THIS “MIDDLE” POINT
AS CLOSELY AS POSSIBLE. ALSO, THE TEMPERATURE
RISE SHOULD NEVER BE ABOVE OR FALL BELOW THE
STATED RANGE. DOING SO COULD CAUSE DAMAGE TO
THE HEAT EXCHANGER OR INTERMITTENT OPERATION.
THIS COULD CAUSE INJURY OR DEATH AND WILL VOID
THE MANUFACTURER’S WARRANTY FOR THIS PRODUCT.
46
TABLE 12
AIR FLOW PERFORMANCE – (-)802P/(-)(-)80MDP SERIES MODELS
The furnace controls have four active quick connect terminals for connecting the motor speed leads. These are:
1. LO HEAT/FAN — motor runs on this speed when the
thermostat is in the “FAN ON” position or when low
stage heat (W) is energized.
2. COOL — connect desired cooling speed.
3. HI HEAT — connect desired high heating speed.
4. H/C (for heat/cool) — connect desired speed when
high heating and cooling speed are the same.
In addition to the active motor terminals, there are two
motor parking terminals (labeled M1 and M2) available for
placing any unused motor taps. All unused motor taps
should be connected to either M1 or M2. These terminals
(M1 and M2) will not be energized under any condition.
Airflow
IMPORTANT: Do not connect any motor speeds to “HI
HEAT” and/or “COOL” if you use the “HEAT/COOL” terminal.
If cooling speed and fan speed are desired to be the same,
this may be accomplished by not connecting “Y” to the integrated furnace control.
See selection titled “Field Selections – Dipswitches” for
setting the heating and cooling blower off delay times.
47
SAFETY FEATURES
LIMIT CONTROL
The high limit cut-off temperature is set at the factory and cannot
be adjusted. The temperature setting prevents the air temperature leaving the furnace from exceeding the maximum outlet air
temperature, which, if exceeded, will shut the furnace down.
There are several reasons for a limit switch to open and almost
always involve low airflow through the furnace.
1. A dirty or restricted air filter.
2. A dirty or restricted cooling coil.
3. Undersized or restricted return air system.
4. Undersized or restricted supply air system.
5. A problem affecting the main blower:
A. A wrong speed tap selection.
B. Failing motor bearings.
C. Low voltage to the motor.
D. Dirty blower wheel.
E. Wrong motor rotation.
F. Blower wheel slipping on the
F. motor shaft.
G. Bad run capacitor.
6. Overfiring the furnace with too much gas pressure.
7. Ventilation problems.
FLAME ROLL-OUT SAFETY SWITCHES
Furnaces are equipped with safety switches to protect against
flame roll-out conditions in the burner compartment, which, if
tripped, will terminate the heating cycle. In the event of a flame
roll-out condition, the switch will shut the furnace down. Switches
for the furnaces are located on either side of the burner cover
plate and just above the burners on the blower divider panel. If a
switch is tripped, it must be manually reset. DO NOT jumper or
reset this switch. If this switch should trip, a qualified installer,
service agency or the gas supplier should be called to diagnose
and/or correct the source of tripping. If this unit is mounted in a
closet, the door must be closed when making this check.
PRESSURE SWITCH
This furnace is equipped with a normally-open pressure switches
that monitors pressure conditions within the furnace vent system
during the heating cycle.
There are several reasons for the pressure switch not to close.
1. An inoperative induced draft blower.
2. A loose or leaky pressure switch hose.
3. A blockage in the vent.
4. Severe downdrafts canceling the draft from the inducer fan.
5. A leaky gasket at the induced draft blower.
6. Improperly sized or installed vent.
The pressure switch contacts must open before the unit can go
through another heating cycle.
See diagnostic chart in this book for diagnostic recommendations.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY
SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A
SAFETY SWITCH CAUSES THE FURNACE TO SHUT
DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICATION OF A POTENTIAL SAFETY HAZARD THAT MUST BE
ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE
AGENCY OR THE GAS SUPPLIER. DO NOT RESET
SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
AND/OR VERIFICATION OF PROPER SAFE OPERATION
BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE
GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY
WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN A
NEW SAFETY SWITCH IS INSTALLED, IT MUST BE
TESTED FOR A MINIMUM OF 15 MINUTES WITH THE
FURNACE OPERATING AT MAXIMUM INPUT RATE AND
WITH BOTH BLOWER AND BURNER DOOR INSTALLED.
IF THE FURNACE IS INSTALLED IN A CLOSET, THE
CLOSET DOOR MUST ALSO BE CLOSED FOR THIS
TEST. REPEAT THE TEST AT THE MINIMUM INPUT RATE
IF THE FURNACE IS A MULTI-STAGE FURNACE.
Safety Features
48
MAINTENANCE
MAINTENANCE
ARNI
W
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT,
SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN
NG
FILTERS
CAUTION
!
DO NOT OPERATE THE SYSTEM FOR EXTENDED PERIODS WITHOUT FILTERS. A PORTION OF THE DUST
ENTRAINED IN THE AIR MAY TEMPORARILY LODGE
IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY RECIRCULATED DUST PARTICLES WILL
LUBRICATION
FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
DISCONNECT MAIN ELECTRICAL POWER TO THE
UNIT BEFORE ATTEMPTING ANY MAINTENANCE.
FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR
DEATH.
BE HEATED AND CHARRED BY CONTACT WITH THE
FURNACE HEAT EXCHANGER. THIS RESIDUE WILL
SOIL CEILINGS, WALLS, DRAPES, CARPETS AND
OTHER HOUSEHOLD ARTICLES.
IMPORTANT: DO NOT attempt to lubricate the bearings on
the blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the
warranty.
The blower motor and induced draft blower motor are permanently lubricated by the manufacturer and do not require further attention.
It is recommended that the blower motor and induced draft
blower motor be cleaned periodically by a qualified installer, service agency, or the gas supplier to prevent the
possibility of overheating due to an accumulation of dust
and dirt on the windings or on the motor exterior. And, as
suggested elsewhere in these instructions, the air filters
should be kept clean. Dirty filters can restrict airflow. The
motor depends upon sufficient air flowing across and
through it to keep from overheating.
Maintenance
49
M
AINTE
S
Y
S
TE
M
NANCE
OP
E
R
ATI
ON
I
N
FOR
MA
TI
ON
ADVISE THE CUSTOMER
1. Keep the air filters clean. The heating system will oper-
ate better, more efficiently and more economically.
2. Arrange the furniture and drapes so that the supply air
registers and the return air grilles are unobstructed.
3. Close doors and windows. This will reduce the heating
load on the system.
4. Avoid excessive use of kitchen exhaust fans.
5. Do not permit the heat generated by television, lamps
ANNUAL INSPECTIO
• The furnace should operate for many years without excessive scale build-up in the flue passageways. However,
it is recommended that a qualified installer, service
agency, or the gas supplier annually inspect the flue passageways, the vent system and the main burners for continued safe operation. Pay particular attention to
deterioration from corrosion or other sources.
• IMPORTANT: It is recommended that at the beginning
and at approximately half way through the heating season, a visual inspection be made of the main burner
flames for the desired flame appearance by a qualified installer, service agency or the gas supplier. If the flames
are distorted and/or there is evidence of back pressure,
check the combustion and ventilation air system for blockage. If there is carbon and scale in the heat exchanger
tubes, the heat exchanger assembly should be replaced.
N
or radios to influence the thermostat operation.
6. Except for the mounting platform, keep all combustible
articles 3 feet from the furnace and vent system.
7. IMPORTANT: Replace all blower doors and compart-
ment covers after servicing the furnace. Do not operate the unit without all panels and doors securely in
place.
8. Explain the advantages of continuous fan operation to
the customer.
• IMPORTANT: It is recommended that at the beginning of
the heating season, the flame sensor be cleaned with
fine steel wool or Scotch Bright Pad by a qualified installer, service agency or the gas supplier.
• IMPORTANT: It is recommended that an annual inspection and cleaning of all furnace markings be made to assure legibility. Attach a replacement marking, which can
be obtained through the distributor, if any are found to be
illegible or missing.
WARNING
!
HOLES IN THE VENT PIPE OR HEAT EXCHANGER
CAN CAUSE TOXIC FUMES TO ENTER THE HOME,
RESULTING IN CARBON MONOXIDE POISONING
OR DEATH. THE VENT PIPE OR HEAT EXCHANGER
MUST BE REPLACED IF THEY LEAK.
REPLACEMENT PARTS
Please visit www.myrheem.com/myruud.com for replacement parts information.
DIAGNOSTICS
Refer to Figure 33 for determining cause of unit problems.
WIRING DIAGRAM
Maintenance
Figure 34 is a complete wiring diagram for the furnace.
A wiring diagram is also available on the unit.
50
FIGURE 33
GO TO
E
NOTE: Always verify gas valve inlet and outlet gas pressure.
KEY TO ABBREVIATIONS
I
BM = Indoor Blower Motor
IDM = Induced Draft Motor
IFC = Integrated Furnace Control
PS = Pressure Switch(es)
SE = Spark Electrode
DSI = Direct-Spark Ignition
FLAME (AMBER) LED CODES
OF F = N o F l am e P r es e n t
RAPID BLINK = Unexpected Flame
SLOW BLINK = Marginal Flame Sense
S
TEADY ON = Normal Flame Sense
Does the IDM Energize?
IDM Runs for 30 sec. pre-purge?
Spark Ignitor Sparking?
D
oes Main Burner Light and stay lit?
I
s the gas valve energized?
PS dropping out?
Check IFC*
Does IBM start on heat speed 20 seconds
after burners light ?
Does main burner remain lit until
heat call ends?
Does thermostat maintain reasonable room
temperature near setpoint?
Set thermostat to off position (W to C = ØV)
Does gas valve shut off immediately?
Does IDM shut off after ten second post-purge?
Does IBM shut off after a max. of 3 min?
END
Heat-mode troubleshootin g
“FAULT DISPLAYED ?”
24V on W to IFC?
C
heck IFC*.
Does IDM run
indefinately .
Does IDM Run for 60 sec. and then off for Five minutes
- Check thermostat in “heat” mode,
battery, wire, and connections.
-
Check PS contacts
- Check wires for short.
-
Check IFC*.
- Check switches and hoses for
water or moisture
- Check PS, PS Hoses, and wires.
- Check for blocked vent, excessive vent length or elbows, or
blocked heat exchanger.
- Check IDM wired correctly.
-
Ensure against excessive wind, which can open pressure switch.
- Check for intermittent P.S. operation.
- Check switches and hoses for water or moisture.
- Check gas supply and manifold pressure.
-
Ensure L1 and Neutral not swapped on IFC and junction box.
- Check igniter alignment .
- Check orifice or other restrictions to gas flow.
- Check flame sense rod (clean with scotch brite pad).
- Check flame carry over.
- Check wires, continuity , and connection between IFC and gas valve.
-
Ensure 24 V between appropriate pins on connector of IFC.
- Ensure manual switch on valve is in the “ON” position.
- 90+ check aux. limit open? Should be closed
-90+ upflow models – check drain pressure switch between IFC and
gas valve – should be closed – replace drain pressure switch if drain
is not blocked or clear drain if blocked.
- Did a pressure switch open during ignition trial? If yes, go to F
- Did a limit open during ignition trial? If yes, go to D
- Check line voltage between “HEAT” and “NEUTRAL” on IFC.
-
Check wires, connections, and continuity between IFC and IBM.
- Check IBM capacitor.
- Check IBM.
CHECK:
-grounding on IFC and unit.
- check for proper polarity between L1 & neutral.
-flame sense rod (clean if necessary).
- wire continually between flame sense rod and appropriate pin of
connector on IFC
-flame carries across all burners, and all burners stay lit.
CHECK:
AIRFLOW
- ensure no restrictions, such as dirty filter,dampers, closed registers, etc.
LIMITS
- ensure good wire and connections between IFC and all limits. Make sure
limits are not open when circulating air temperature is within a specified range.
ROLLOUTS
- ensure rollouts or overtemperature limits do not need to be reset. Make
sure no flame rollout in burner compartment due to blocked flu or heat exchanger.
OVERFIRE
- ensure furnace is not overtemperature (temp rise is above stated range).
Check gas valve, proper orifice size, gas pressure, etc.
Is Limit circuit open
or
opening and closing?
Note: IFC Status LED should be blinking a Fault Code.
Is the IFC sensing agood flame: NOTE:
Flame sen se light sho uld b e steady-o n
whenburnersare lit. If flameLED blinking,
or off, flame sense is low or absent.
Ensure thermostat is properly placed and not improperly affected by
registers, fans, sunlight, heat through walls, pipes, or wires in walls.
- Check heat anticipator setting. Furnace may need an isolation relay.
- Check installation instructions under section titled “Isolation Relay” for
details .
-Verify correct furnace sizing.
N
OTE: If IFC goes into lockout (“STATUS LED will blink code “1”), shut
off main power to unit, wait 30 seconds and then reset power.
PROBLEM
STILL
PRESENT
Fault Code Present
“FLAME” LED BLINKING
OR STEADY ON
If “E” did not
resolve issue
Double check - Is W off at IFC?
(W to C = ØV?)
Voltage present at gas valve?
- Check gas valve.
SEE F AULT C ODES
- Check IFC*.
Check IFC*.
*Most failures are not due to the IFC. Double
check all other possibilities, including the
ground connection or wire connections, before
replacing the IFC.
Ensure TSTATis not in “FAN” position.
Is disply flashing a fault code
Is “FLAME” LED blinking or steady-on?
**System will attempt to light 4 times. Voltage
is present at gas valve for only 7 seconds during each trial for ignition. The entire system will
go into a 1 hour lockout after 4 attempts.
-
Check line voltage at IDM.
- Check wires and connections between IDM and IFC.
-
Ensure line voltage on IDM pins of IFC connector.
- Check IDM capacitor (90+ only).
CHE CK BL INK C ODES
-Check for open limit or limit circuit.
FOR DIRECT SPARK IGNITION
- Check ignitor connected .
- Check ignitor wires.
- Check ignitor for fractures or cracking
- Check ignitor placement .
- If problem persists, check IFC*.
REPEAT THIS PROCEDURE UNTIL TROUBLE-FREE OPERATION IS OBTAINED.
1
) Set FAN switch to “AUTO”
2) Set thermostat to call for low HT ( “W” terminal)
START
YES
NO
NO
If “
I
” did not
resolve issue.
NO
NO
NO
N
O
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
Y
ES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
I
D
F
E
G
YES
NO
YES
PREPURGE
IGNITION TRIAL
IBM “ON” DELAY
STEADY STATE LOW HT
END HEAT CALL
POST-PURGE
IBM “OFF” DELAY
STEADY OFF
NO
**
ST-A1227-08-00
GO TO
F
GO TO
I
WARNING
HAZARDOUS VOLTAGE
LINE VOLTAGE
CONNECTIONS
DISCONNECT POWER BEFORE SERVICING.
SERVICE MUST BE BY A TRAINED, QUALIFIED
SERVICE TECHNICIAN.
NOTE:
Always verify gas valve inlet and outlet
gas
pressure.
INTEGRATED FURNACE CONTROL (IFC)
DIAGNOSTICS GUIDE
NOTE: Most failures are not due to the IFC. Double check all othe r
possibilities, including the ground connection, before replacing the IFC.
BLOCKED DRAIN - (fault “59” should be present)
Set T-stat to High Heat - Energize W2 + W
Fault
Priority
24
22
21
19
23
13
15
14
16
2
20
4
17
3
6
9
8
7
11
18
1
CODE
DESCRIPTION
O
C
H
h
F
10
11
12
13
14
20
22
26
33
44
4
6
4
5
5
5
57
61
93
Standby
Compressor on (cooling or heat pump heat)
High Gas heat on
Low gas heat on
Continuous fan on
1 Hour lockout
Failed ignition
Low flame sense
Flame lost
Unexpected flame
Twinning fault
Main limit open
Line and Neutral reversed
MRLC(Man. Reset limit cont.)(aka roll-out) open
Low Pres. Switch Closed
L
ow Pres. Switch Open, Indcr on low Speed
L
ow Pres. Switch Open, Indcr on High Speed
H
igh Pres. Switch Closed
High Pres. Switch Open
Blower Fault - blower unable to run
Internal control fault
“ATTEND TO FAULT”
- For Twinned units, check that both IFCs are set for “TWIN” and wires
are connected between “TWIN” terminals .
- Check IFC*.
- For twinned units, ensure transformers are in phase.
(if out of phase, flame LED will be dim).
- For non-twinned units, ensure “TWIN” is in the single (OFF) position.
- For Twinned units – ensure both IFC‘s have same part number.
H
Check for high gas valve relay
on IFC stuck closed. Replace
IFC, if neccessary
Do IDM, IBM & Gas Valve Shift to High Heat?
STEADY HIGH HEAT
CHECK:
-IDM
-IDM Capacitor
-Low Pres. Sw. wiring
-Hoses to Low Pres. Sw.
CHECK:
-IBM
-IBM Capacitor
-Wiring
-Flame Sense Rod
Low Pressure
Switch Open?
High Gas Valve
Energized?
24 VAC on
W2?
Check
T- STAT
NO
NO
NO
NO
YES
YESYES
YES
YES
Restore thermostat to
normal operation.
DIAGNOSTICS FLOWCHART
Diagnostics
51
Wiring Diagram
FIGURE 34
FOR MODELS WITH UT ELECTRONIC CONTROLS 1028-928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION
52
CM 0814
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.