Rheem 441 Series, 761 Series, 771 Series, 791 Series, 451 Series Service Instructions Manual

...
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
Rheem Australia Pty Ltd ABN 21 098 823 511
SERVICE INSTRUCTIONS
Lazer 441, 451, 741, 751, 761,
771, 781 & 791 Series
Revision: AD
Issued: Jan 14
Lazer 1 & 2
Silhouette
(Designer Series)
Classic
(Modular Series)
Silhouette
(Modular Series)
441 Series
761 Series
771 Series
791 Series
451 Series
781 Series
741 Series
751 Series
First Issued: May 1987
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
2
CONTENTS
INTRODUCTION ..................................................................................................................... 3
SAFETY WARNING................................................................................................................. 3
MODEL IDENTIFICATION ....................................................................................................... 3
SPECIFICATIONS ................................................................................................................... 4
PREVENTATIVE MAINTENANCE .......................................................................................... 5
OPERATION ............................................................................................................................ 6
Electronic Controller Operating Modes ................................................................................. 6
COMPONENTS AND THEIR FUNCTIONS ............................................................................. 7
INSTALLATION NOTES .......................................................................................................... 8
WIRING DIAGRAMS ............................................................................................................... 9
741/751 (2.5L - 40L) ............................................................................................................. 9
761, 791 & 771/781 (2.5L – 40L) ........................................................................................ 10
FAULT FINDING .................................................................................................................... 11
General Fault Finding Chart ................................................................................................ 11
Mode 1 Fault Finding .......................................................................................................... 12
Component Tests 1 - 4 .................................................................................................... 13
Mode 2 Fault Finding .......................................................................................................... 14
Component Tests 5 - 8 ....................................................................................................... 15
Mode 3 & 4 Fault Finding .................................................................................................... 16
LAZER BOILING WATER UNITS AT HIGH ALTITUDES ...................................................... 17
How to Adjust the Temperature Setting of the Controller (ECB) ................................ ......... 17
ELECTRICAL IN-SERVICE TESTING ................................................................................... 18
ACCESSING COMPONENTS ............................................................................................... 19
COMPONENT REPLACEMENT ............................................................................................ 20
Water Temperature Sensor (Thermistor) ............................................................................ 20
DOCUMENT REVISION HISTORY ....................................................................................... 27
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
3
INTRODUCTION
The information provided in these instructions is based on the Rheem Lazer Boiling Water Unit being installed in accordance with the installation instructions provided with each unit.
Should you require further technical advice on the Rheem Lazer Boiling Water Unit, contact your nearest Rheem Australia Service Office where all genuine replacement parts are also available.
SAFETY WARNING
The purpose of this Service Manual is to provide sufficient information to allow a person with the skills as required by the controlling Regulatory Authorities to carry out effective repairs in the minimum of time.
Safety precautions or areas where extra care should be observed when conducting tests outlined in this service manual are printed in bold italics. Take care to observe the recommended procedure.
Certain diagnostic procedures outlined in these Service Instructions require
“live” testing of certain components. An RCD should be installed between the
power point and 3-pin cord of the water heater whilst conducting the tests.
MODEL IDENTIFICATION
The identification (model) number is designed to convey detailed information about the heater to which it is attached. Lazer Boiling Water Units are interpreted thus:
7 7 1
015
7 - Automatic Operation
4 & 7 - White enamel jacket 5 & 8 - S/Steel jacket 6 & 9 - Plastic Jacket, Silhouette
1 - Single heating unit 2 - Double heating unit
025 = 2.5 litre capacity 045 = 4.5 litre capacity 050 = 5.0 litre capacity 075 = 7.5 litre capacity 150 = 15 litre capacity 250 = 25 litre capacity 400 = 40 litre capacity
SERIAL NUMBER 741/751 Series
The serial number incorporates the date of manufacture as thus:
02
87
125
Month of Manufacture
Year of Manufacture
Serial Number
SERIAL NUMBER 771/781, 761 & 791 Series
The serial number indicates the country code AU for Australia and a sequential build number. The date of manufacture is listed on the rating plate inside the jacket by the month and year i.e. SEP 1999
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
4
SPECIFICATIONS
Capacity
Litres
Model
Heating Element
Input (kW)
Load & Wiring
Type
Electrical Supply
Inlet Water
Pressure (kPa)
Inlet & Outlet
Connection
Min
Max
2.5
741025
1 x 2.4
10 amp
3-pin plug
230/240 VAC
50Hz
55
1000
R½/15
771025
50
761025
20
791025
50
4.5
741045
1 x 2.4
10 amp
3-pin plug
230/240 VAC
50Hz
55
1000
R½/15
5.0
771050
1 x 2.4
10 amp
3-pin plug
230/240 VAC
50Hz
50
1000
R½/15
761050
20
791050
50
7.5
741075 751075
1 x 2.4
10 amp
3-pin plug
230/240 VAC
50Hz
55
1000
R½/15
771075 781075
50
761075
20
791075
50
15
741150 751150
1 x 2.4
10 amp
3-pin plug
230/240 VAC
50Hz
55
1000
R½/15
771150 781150
75
25
741250 751250
1 x 3.6
15 amp
circuit
230/240 VAC
50Hz
200
1000
R½/15
771250 781250
75
40
741400 751400
1 x 4.6
20 amp
circuit
230/240 VAC
50Hz
200
1000
R½/15
771400 781400
100
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
5
PREVENTATIVE MAINTENANCE It is suggested for peak performance that the Boiling Water Unit be serviced every six
months.
Servicing must be performed by suitably qualified persons.
Hot surface or liquid. Personal Protective Clothing (PPE) shall be worn to reduce the risk of burns or scalding.
1. Check the inlet strainer located inside the water inlet connection to ensure it is clean and not blocked with foreign matter. If an additional auxiliary filter is fitted, such as in areas of poor water quality check to ensure it is also clean and not blocked with foreign matter.
2. Check for signs of excessive corrosion on jacket and internal panels. Corrosion can be indicative that a leak is present.
3. Check for leaks at all BWU fittings.
4. Check the vent line to ensure it is not blocked with foreign matter. It is imperative that
the vent line does not become blocked as the BWU is not designed to be pressurised.
5. Isolate power and check all electrical connections for signs of overheating due to poor connection.
6. Conduct an electrical in-service test. (Refer to page 18).
7. Check tap for signs of leaking & excessive dripping after operation (clean or replace if required.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
6
OPERATION IMPORTANT: High altitude will affect the Lazer Boiling Water Unit operation. Refer to
page 17 for more details To commission water heater from empty:
Turn on water supply first Turn on 240V supply, solenoid will open and filling will commence. Filling will continue until the water reaches the WLS low-level probe. Filling will stop and heating will commence until water reaches 97ºC. Heating continues and filling re-commences and continues until water temperature
drops to 93ºC. Each time the solenoid valve closes the WLS high level is checked.
This process repeats itself until the water level reaches the WLS high-level probe, at
which time the solenoid closes and the heating unit is switched off when water temperature reaches 97ºC.
From there on the heating unit will cycle to maintain water temperature between 93
and 97ºC.
The drawing off of boiling water will cause the solenoid to open and deliver cold water
on to the WTS which will in turn cause heating to commence.
The continuous drawing of water will cause the solenoid to close after 25 seconds;
ensuring water temperature is not continually reduced.
Electronic Controller Operating Modes Mode 1. Empty
When water level is below the WLS low-level probe the heating unit will turn OFF, and the solenoid valve will open to allow water to enter. When water level reaches the WLS low-level probe, a delay of 2 seconds will elapse before the solenoid closes and heating commences.
Mode 2. Not Full
Continuing from Mode 1, the heating unit will have power on throughout Mode 2. While it is heating, small quantities of water (approx. 100mL per cycle) are admitted through the solenoid each time the water temperature is sensed at 97ºC.
The solenoid will:
Open to fill at 97ºC Close at 93ºC
The solenoid cycle time will depend on the delay between cold-water entry and the sensing of 93ºC, which is directly related to:
Temperature of inlet water. Pressure of inlet water. Capacity of the Lazer Boiling Water Unit. Water level in the Lazer Boiling Water Unit
Water temperature should not drop below 93ºC throughout the fill cycle. Each time the solenoid closes, the WLS high- level probe is activated and, if found to be covered with water the ECB will change to Mode 3.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
7
Mode 3. Full
When water has covered the WLS high-level probe the solenoid will close and heating will continue until a temperature of 97ºC is attained. The solenoid will open again for a split second at this time.
Thereafter the solenoid opens only when the water level falls below the WLS high- level
probe.
Heating will continue to cycle ON and OFF between 93 and 97ºC.
The drawing of water from the tap will return the ECB to Mode 2. During continuous drawing of water the solenoid will close after being open for 25
seconds.
Draining of all water will return the ECB to Mode 1.
Mode 4. Over temperature Cut Out (OTC)
The OTC mode will activate when the solenoid remains open for longer than 25 seconds in Mode 2.
Once activated the OTC will switch OFF power to the solenoid and heating unit and remain in this state until the water temperature drops below 93ºC. At this temperature the ECB will switch back to Mode 2.
The OTC mode is not temperature activated and will not prevent continuous boiling of the Lazer.
COMPONENTS AND THEIR FUNCTIONS ELECTRONIC CONTROL BOX (ECB): A box containing a transformer, relay and electronic
PC board which provides the logic to monitor and control water level and temperature. An over temperature function is incorporated to prevent the unit boiling dry. The wiring
terminals are 240 volt and 0 to 24 volt; therefore it is essential to connect all wires to the correct positions.
WATER LEVEL SENSOR (WLS): An insulated stainless steel probe that monitors:
Low water level to ensure the heating element cannot operate unless covered by
water
High water level to ensure the maximum water level is not exceeded.
Damage to the probe insulation will cause the heater to malfunction. SOLENOID VALVE / INLET FILTER: A 12-volt solenoid for 741/751 series with an inline
filter attached is located in front of the inner tank at the top of the water heater. A 24-volt solenoid for 761,771/781, 791 series with an inline filter attached is located on the
lower left hand side of the water heater. The operation is ON or OFF, but because of its small orifice size water hammer is not a
problem. HEATING UNIT / SENSOR PROBE: A square flanged heating unit, bent at 90º on some
units to suit the width of the tank, incorporating a sensor probe centrally located between the element loop.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
8
TEMPERATURE SENSOR (WTS): A thermistor is inserted inside the probe of the heating unit and monitors water temperature to maintain water at near boiling point.
OVERFLOW / VENT: The outlet of this pipe must be to atmosphere for the following reasons:
To allow air to escape while filling To allow excess water to escape To allow steam to escape while heating To prevent inner tank collapse when draining
INSTALLATION NOTES
The Lazer boiling water unit is not weatherproof. External locations must be protected from the weather and freezing conditions.
MOUNTING POSITION: Minimum clearances required for servicing are 350mm clear above the top and to the right for 741/751 series and 150mm clear above the top and to the right for 761, 771/781 and 791 series. Refer to installer to correct if clearances are less than required.
OVERFLOW/VENT: A drain line discharging to the atmosphere with a continuous fall, not exceeding 1 metre and with not more than 3 bends is required. The point of discharge should be where the user can see it, but not cause annoyance or injury if water or steam is discharged. A drain line not meeting these requirements must be installed with an air-break (tundish).
WATER SUPPLY: The Lazer Boiling Water Unit is not a pressurized appliance. An AIR­BREAK is incorporated into the internal filler pipe. Connect only to a cold water supply with a constant pressure above the minimum supply pressure as specified in the SPECIFICATION TABLE on page 4.
The maximum supply pressure shall not exceed 1000kPa for all models. An approved stopcock is required for servicing purposes in the cold water supply line before the Lazer Boiling Water Unit.
IMPORTANT:
Non-return valves or stopcocks incorporating a non-return valve MUST NOT BE
INSTALLED in the water supply connection for 741, 751and 761 series. 771, 781 and 791 series have a non-return valve fitted within the water heater. DO NOT CONNECT TO A HOT WATER SUPPLY.
HOT WATER TAP: The tap is supplied with a chrome plated brass extension piece on 741/751 and 771/781 series. A 29mm A/F nut allows the tap to be aligned to a vertical position.
On 761 and 791 series the tap is a “Rocker” type and is already installed for use. The tap will drain all the contents of the Lazer Boiling Water Unit on some 741/751 series, and therefore expose the heating unit to the air.
DO NOT:
Over-tighten tap into tank. Remove the tap to service heating unit.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
9
ELECTRICAL CONNECTION: All Lazer Boiling Water Units are designed for 220/240 volt 50 Hertz electrical supply. Installations that cannot achieve the specified supply current, i.e. private generators should be avoided. The internal wiring is designed to suit the load rating of the heating unit stated on the RATING LABEL found inside the jacket.
DO NOT FIT A HEATING UNIT OF HIGHER RATING THAN SPECIFIED ON THE
RATING LABEL.
Lazer Boiling Water Units with 10amp load are supplied with a 3-pin plug. A licensed electrician must wire units of 15amp capacity to a suitable supply.
WIRING DIAGRAMS 741/751 (2.5L - 40L)
2.5L -15L
25L - 40L
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
10
761, 791 & 771/781 (2.5L – 40L)
ECB
2.4kW Element
Solenoid
761- 791 - 771/781 Series
2.5L - 15L
Phase
Element
Neutral
Earth
Ready
Ground
Vp
Low
High
Solenoid-
Solenoid+
Sensor-
Sensor+
LED Board
P E N
Terminal Block
Note: ECO not fitted on 15L models
WLS
R B
BL
R
R
761 & 791 models only
G
R
W
BL
W
B/W
BL
R
BR
G
BL
ECB
3.6kW - 25L
4.6kW - 40L Element
Solenoid
771/781 Series 25 - 40L
Phase
Element
Neutral
Earth
Ready
Ground
Vp
Low
High
Solenoid-
Solenoid+
Sensor-
Sensor+
P E N
Terminal Block
WLS
R
R
G
W
BL
W
B/W
BL
R
BR
G
BL
BR
BR
Relay
BL
B=Black BL=Blue BR=Brown G=Green W=White R=Red B/W=Black/White
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
11
FAULT FINDING
It is possible to independently test individual components of the Lazer Boiling Water Unit, however it is strongly recommended that this Test Procedure be followed irrespective of a suspected malfunctioning component.
A failed or malfunctioning component may be the result of incorrect installation, faulty or intermittent services, i.e. large voltage or water pressure fluctuations, water filtration units or non-return valves in the water supply line or, incorrectly installed overflow/vent pipes.
Prior to commencing this Procedure ensure that the water pressure and electrical supply meet the required specification for the Lazer boiling water unit outlined on page 4.
General Fault Finding Chart
Disconnect power and
isolate water supply
Remove the jacket front or
access covers
Drain tank completely via drain
plug or tap
Water at elevated temperatures may be present when
draining, care should be taken to prevent scalding
Refit drain plug,
reconnect power and
restore water supply
Mode 1 diagnosis
NO
YES
NO
YES
Mode 2 diagnosis
NO
YES
NO
NO
Over temperature
mode diagnosis
YES
YES
NO
YES
Mode 3 diagnosis
NO
Normal OperationYES
Is the water
solenoid open?
1
Water solenoid closes
after a period?
Element
commences heating?
2
Solenoid alternates
operation until upper
water level reached,
element remains on
continuously?
Was the solenoid
open for longer than 25
seconds?
4
2
Mode 2 diagnosis
Element de-energized
after a period?
3
Element cycles to
maintain water
temperature?
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
12
Mode 1 Fault Finding
YES YES
NO
Repair broken strap or wiringNO
Disconnect the plug from the water level
probe
NO
YES
YES
Isolate power before checking
the water level probe connection
Clean connection or replace
wiring.
Retest operation
NO
YES
Replace ECB
Retest operation
NO
Clean or replace water level
probe
Restest operation
YES
NO
NO
YES
Replace ECB
Retest operation
YES
Replace ECB and solenoid
valve
Retest operation
NO
YES
Replace solenoid valve
Retest operation
NO
1
Is the solenoid open? Does the solenoid close?
2
Mode 2 Diagnosis
Is there continuity of the
earth strap from the tank
to the ECB?
TEST 1
2.1
Does the solenoid open?
Is the connection to the water level probe clean
and tight?
Is scale built up on probe
wires or body?
TEST 2
Is the supply voltage from
the ECB correct?
TEST 3
Is the resistance of the
solenoid valve correct?
TEST 4
2
Mode 2 Diagnosis
Is the resistance of the solenoid valve correct?
TEST 4
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
13
Component Tests 1 - 4
Test 1
Test 2
Normal resistance between the tank and the earth point on the ECB is 0 ohms (dead short) when measured with a multimeter on the x1 resistance scale.
Normal resistance between the high level probe wire and low level probe wire should be infinity (open circuit) when measured with a multimeter on the x10M resistance scale.
Test 3
Test 4
Install RCD and exercise caution when
conducting live tests
741/751 series
Normal voltage at the solenoid under load should be between 6 and 12 volts when measured with a multimeter on the DC voltage scale.
761, 771/781 and 791 series
Normal voltage at the solenoid under load should be between 8 and 24 volts when measured with a multimeter on the DC voltage scale.
741/751 series
Normal resistance of the solenoid coil should be 23 ohms +/- 5% when measured with a multimeter on the x1 resistance scale.
761, 771/781 and 791 series
Normal resistance of the solenoid coil should be 55 ohms +/- 5% when measured with a multimeter on the x1 resistance scale.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
14
Mode 2 Fault Finding
YES
YES
YES
NO
NO
YES
Replace solenoid
Retest operation
NO
Replace element Retest operation
NO
YES
Replace thermistor
Retest operation
NO
YES
Refit the thermistor in the
correct position
Retest operation
NO
Adjust the temperature setting by following the potentiometer
procedure in this manual.
Retest operation if fault
persists replace the ECB
YES
NO
Replace ECB
Retest operation
2.5, 5 & 7.5 litre models
NO
Replace relay
Retest operation
YES
15, 25 & 40 litre models
2
Is voltage present
at the element?
TEST 5
Capacity of Lazer?
Is voltage
present at relay?
TEST 6
Has the
Solenoid closed?
Is the resistance
of the element correct?
TEST 7
2.2
Does the unit
boil continuously?
2.1 3
Does the solenoid close
when upper water level
reached?
Is the resistance of
the thermistor correct?
TEST 8
Is the thermistor fully
inserted into the well?
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
15
Component Tests 5 - 8
Test 5
Test 6
Install RCD and exercise caution when
conducting live tests
Normal voltage at the element is 240v when measured with a multimeter on the AC voltage scale
Install RCD and exercise caution when
conducting live tests
Normal voltage to the relay coil is 240v when measured with a multimeter on the AC voltage scale.
Test 7
Test 8
Normal resistance of the element and ECO when measured with a multimeter on the x1 resistance scale is:
2.4kW - 23.7 ohms +/- 5%
3.6kW - 15.7 ohms +/- 5%
4.6kW - 12.3 ohms +/- 5%
Normal resistance of the water temperature sensor (Thermistor) is 950 ohms - 1000 ohms at 20ºC. The Thermistor should be replaced if the reading is less than 850 ohms or greater then 1250 ohms. When measured with a multimeter on the x1K scale a normal reading will be between .95 and 1.00.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
16
Mode 3 & 4 Fault Finding
NO
Any time the solenoid is open
for a period exceeding 25
seconds before a shift in
temperature is detected the
unit will enter the over
temperature mode (OTC)
YES
Check for low supply flow due
to water filters etc
Advise customer to draw
smaller quantities of water at
one time
NO
Replace solenoid
Retest operation
YES
YES
Check the water level probe
sensor wires for correct length
NO
Siphoning may be occurring.
Advise user to have a tundish
installed as per the installation
instructions.
Unit may enter over temperature (OTC) mode during this condition if the
solenoid opens for periods
exceeding 25 seconds
YES
NO
NO
OTC MODE
Draw a quantity of water from
the unit through the tap
NO
Normal OperationYES
3
Are large quantities of hot
water being discharged
from the vent pipe?
Is the vent pipe
longer than 3 metres?
1
Does the unit discharge
large quantities of hot
water intermittently?
Does the unit maintain
water temperature during
periods of non use?
Did the unit
Refill and heat?
2.2
4
Are large amounts
of hot water being drawn
through the tap?
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
17
LAZER BOILING WATER UNITS AT HIGH ALTITUDES
An increase in altitude will reduce the boiling temperature of water. Therefore it is necessary to provide an adjustment on the Lazer Control System for installations over 300 metres above sea level.
All controllers supplied as a component of the finished product are factory adjusted to deliver water at a temperature of 92ºC.
Why should temperature adjustment be necessary?
Replacement of the Electronic Controller Replacement of the Thermistor or a Heating Unit and Thermistor. Altitude compensation
Where is the Adjustment Potentiometer and what does it look like?
Relative to the controller terminals, the Potentiometer (Trim Pot) for temperature adjustment is located at the right rear of the control box. Access is provided by means of a 10mm diameter hole in the controller cover (refer to figure below). Some controllers have no covers fitted, so the Trim Pot is visible on the PCB at the described location.
The Trim Pot can be identified as being a white or blue disc, approximately 6mm in diameter and having a screw driver slot in its top face.
The dotted lines of the TRIM POT arc
represent “HOURS”.
Each hour represents approx 1ºC
How to Adjust the Temperature Setting of the Controller (ECB)
Components adjacent to the trim pot will be live, take care while making adjustments not to touch other components.
1. Isolate the electrical supply and drain the Lazer Boiling Water Unit to a low level.
2. Using a 3mm wide screw driver, rotate the Trim Pot ANTICLOCKWISE to its MINIMUM SETTING.
3. Switch the power back ON and allow it to operate automatically for 5 MINUTES (the element should switch on and the solenoid valve should operate at least once).
4. Using a 3mm wide screw driver, rotate the Trim Pot CLOCKWISE to its MAXIMUM SETTNG. The unit will now boil and not take water.
5. Allow the unit to boil for approx. 1 minute before rotating the Trim Pot ANTICLOCKWISE until such time as the solenoid opens, allowing water to flow into the tank.
6. Rotate the Trim Pot ANTICLOCKWISE a further turn (approx. 45 degrees). This will prevent the unit from boiling should atmospheric pressure decrease.
7. Before re-fitting the jacket cover wait at least one solenoid operation to ensure that the unit has been correctly adjusted.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
18
ELECTRICAL IN-SERVICE TESTING
Wear Personal Protective Equipment when conducting step 1 of these procedures to reduce the risk of electric shock. Refer to Rheem safety procedure on electrical testing.
1. For 3 – 15L models: Isolate power by switching off at power point and unplugging
BWU 3 pin plug from power point. For 25 & 40L models: Isolate power by turning isolation switch off and then
removing fuse (or switching off circuit breaker). Disconnect Active, Neutral and Earth wires from BWU terminal block.
Procedure 1: To check insulation resistance of the BWU Neutral Circuit (reading not to be below 1 mega-ohm).
2. For 3 – 15L models: Connect megger leads to the neutral and earth pins on the 3-pin
plug. For 25 & 40L models: Connect megger leads to the Neutral conductor and the Earth
terminal of the BWU terminal block.
3. Operate insulation resistance tester. A reading above 1 mega ohm should be obtained.
4. If a reading below 1 mega ohm is indicated, all component parts will need to be
individually tested to locate the fault.
Procedure 2: To check insulation resistance of the BWU Active Circuit (reading not to be below 1 mega-ohm).
5. For 3 – 15L models: Connect megger leads to the active and earth pins on the 3-pin plug.
For 25 & 40L models: Connect megger leads to the active conductor and the earth terminal of the BWU terminal block.
6. Operate insulation resistance tester. A reading above 1 mega ohm should be obtained.
7. If a reading below 1 mega ohm is indicated, all component parts will need to be
individually tested to locate the fault.
Procedure 3: To check “Earth Continuity” of the water heater.
8. Set the multimeter to x1 Ω (ohms) resistance scale.
9. (3 – 15L Models) Measure between the earth pin on the 3 pin plug and the water heater
jacket. The reading should be less than 0.5Ω. (25-40L models) Measure between the earth terminal and the water heater jacket. The
reading should be less than 0.5Ω.
10. If a reading greater than this value is obtained the earthing connection should be checked
for corrosion/tightness and the power lead earth wire tested, if necessary replace the power lead.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
19
ACCESSING COMPONENTS
Ensure that the unit is unplugged or isolated from the electrical supply.
Removing & Replacing Jacket Lid and Name Plate
(741/751 Series)
Removing the Lid (Figure 1)
1. Remove the four retaining screws.
2. Remove the LID by lifting from the jacket.
Figure 1
Removing the Nameplate (Figure 2)
1. Remove the two retaining screws.
2. Slide the Nameplate forward on the Tap Stem and rotate through 90 degrees to obtain access to components.
Note: The Tap does not need to be removed to service or replace components housed behind the Nameplate.
Figure 2
Removing & Replacing Jacket Front
(761 and 791 Series)
Removing the Jacket Front (Figures 3&4)
1. Remove the two retaining screws. (Figure 3)
2. Remove the spout by pulling down and gently pushing toward the back.
Figure 3
3. Insert fingertips between the Jacket Front and Jacket Back in the vicinity of the Jacket Retaining Clips and gently pull the Jacket Front forward until free of tap. (Figure 4)
4. Lift the Jacket Front until free of the Retaining Clips.
Warning: The LED Display lead (item 1, figure 4) must now be disconnected from the ECB. The Jacket Front is then free to be removed.
Figure 4
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
20
COMPONENT REPLACEMENT
Water Temperature Sensor (Thermistor)
Ensure that the unit is unplugged or isolated from the electrical supply.
741/751 Series
1. Remove the nameplate. (Refer to page 19)
2. Disconnect the wiring to the water temperature sensor.
3. Withdraw the water temperature sensor from the element.
4. Coat the thermistor with “heat sink compound”
5. Slide the replacement water level sensor into the element ensuring it seats at the end of the tube.
6. Reconnect the wiring and refit the nameplate.
7. Restore power and test operation of boiling water unit.
Figure 5
761, 771/781 & 791 series 2.5L – 7.5L
1. Remove the jacket front.
2. Disconnect the wiring to the water temperature sensor.
3. Withdraw the water temperature sensor from the element.
4. Coat the thermistor with “heat sink compound”
5. Slide the replacement water level sensor into the element ensuring it seats at the end of the tube.
6. Reconnect the wiring and refit the nameplate.
7. Restore power and test operation of boiling water unit.
771/781 series 15L – 40L
1. Remove the left hand side panel. (Refer to figure 9 page 22)
2. Disconnect the wiring to the water temperature sensor.
3. Withdraw the water temperature sensor from the element.
4. Coat the thermistor with “heat sink compound”
5. Slide the replacement water level sensor into the element ensuring it seats at the end of the tube.
6. Reconnect the wiring and refit the nameplate.
7. Restore power and test operation of boiling water unit.
Figure 6
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
21
Electronic Control Box
Ensure that the unit is unplugged or isolated from the electrical supply.
741/751 Series
1. Remove the Jacket Top (Refer to page
19)
2. Gently disconnect the push-on spade terminals
3. Slide the ECB upwards to disengage from the metal tabs in the back panel and lift the ECB clear.
4. Replace the ECB repeating the above steps in the reverse. Ensure that the wiring loom terminals are correctly replaced. Check the terminal block connector to ensure that no wires were accidentally dislodged during the service repair.
5. Restore the power supply and test the unit for normal operation.
6. Refit the Jacket Top.
Figure 7
761, 771/781 and 791 Series
1. Remove the Jacket Front, 2.5L – 7.5L (Refer to page 19) or Left hand side panel, 15L – 40L (Refer to figure 9 page 22).
2. Gently disconnect the push-on spade terminals and the multi-pin connector from the ECB.
3. With the aid of fingertips, gently unclip the ECB Mounting Clips (3) clear of the controller board and lift the ECB (4) through 40 degrees as shown in figure 6.
4. Remove the ECB from the rear Mounting Clips by pulling forward.
5. Replace the ECB repeating the above steps in the reverse. Ensure that the wiring loom terminals are correctly replaced. Check the terminal block connector to ensure that no wires were accidentally dislodged during the service repair.
6. Restore the power supply and test the unit for normal operation.
7. Refit the Jacket Front or Top.
Figure 8
NOTE: ALWAYS check product EARTHING before replacing the Jacket Front or Top
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
22
Solenoid Valve
Ensure that the unit is unplugged or isolated from the electrical supply and the stopcock is closed.
761, 771/781 and 791 Series
1. Remove the Jacket Front (2.5L - 7.5L models, refer to page 19) or Side Panel (15 - 40L models, refer to figure 9)
2. Disconnect the push-on spade terminals from the solenoid
3. Disconnect the inlet supply pipe to the unit.
4. Disconnect the silicone tube
5. Hold the inlet fitting with the aid of a 24mm AF spanner and, using a 27mm AF spanner remove the retaining nut.
6. Remove the Nylon Washer
7. Remove the valve and inlet assembly from the tank.
8. Unscrew the valve assembly from the inlet fitting.
9. Reassemble the inlet fitting, nylon washer and replacement valve assembly.
10. Refit the assembly in reverse order of above.
11. Restore water supply and check for water leaks.
12. Refit panels, restore power supply and test unit for normal operation.
Figure 9
741/751 Series
1. Remove the jacket top (Refer to page 19)
2. Disconnect the solenoid lead spade connectors from the ECB.
3. Place absorbent cloth below and around solenoid to protect ECB and wiring from water spillage.
4. Hold the solenoid securely and undo the compression nuts on either side of the valve assembly.
5. Remove the solenoid valve assembly.
6. Fit the replacement solenoid valve assembly ensuring the water flow is in the direction of the arrow on the brass body.
7. Complete assembly in reverse order of above.
8. Restore water supply and check for water leaks.
9. Refit panels, restore power supply and test unit for normal operation.
Figure 10
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
23
Water Level Probe
Ensure that the unit is unplugged or isolated from the electrical supply and the stopcock is closed.
A common Water Level Probe is supplied as a replacement part. Prior to fitting the probe it may be necessary to cut the long and short sensor wires to suit the model. Refer to the table on page 24 for correct cutting lengths.
741/751 and 771/781 Series Removing the Water Level Probe
1. Remove the jacket top, all 741/751series and 771/781 series 15l –40L, or jacket front, 771/781 series 2.5L – 7.5L. (Refer to page 12)
2. Disconnect the wiring connector from the Water Level Probe.
3. Remove the Water Level Probe by pulling vertically out of the tank (Exercise care not to distort the tank top).
Replacing the Water Level Probe
1. Bend the high level probe wire (item 3, figure 11) away from the low level probe wire (item 4, figure 11) to an angle of 15º, or such that slight pressure is needed to squeeze the probe wires together when inserting the Water Level Probe into the tank sleeve.
2. Insert the replacement Water Level Probe into the tank sleeve and press until seated. (Exercise care not to distort the tank top.)
3. Refit the wiring connector to the Water Level Probe
4. Restore water and power supplies, check for water leaks and test boiling water unit for correct operation.
5. Refit the jacket top or front.
Figure 11
761 and 791 Series Removing the Water Level Probe
1. Remove the jacket front. (Refer to page 19)
2. Disconnect the wiring connector from the Water Level Probe
3. Remove the Water Level Probe by pulling vertically out of the tank. (Exercise care not to distort the tank top.)
5. Bend the high level probe wire (item 3, figure 12) away from the low level probe wire (item 4, figure 12) to an angle of 15º, or such that slight pressure is needed to squeeze the probe wires together when inserting the Water Level Probe into the tank sleeve.
6. Insert the replacement Water Level Probe into the tank sleeve and press until seated. (Exercise care not to distort the tank top.)
7. Refit the wiring connector to the Water Level Probe
8. Restore water and power supplies, check for water leaks and test boiling water unit for correct operation.
9. Refit the jacket front.
Figure 12
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
24
Water Level Probe Lengths
Cut each leg of the Water Level Probe to the length shown in the table below
Model
Short Probe Length in mm
(Length X)
Long Probe Length in mm
(Length Y)
741025
112
137.5
741045
112
262.5
741075 / 751075 741150 / 751150 741250 / 751250
112
367.5
741400 / 751400
112
582
761025
112
200
761050
112
273
761075
112
390
771025
100
205
771050
100
290
771075 / 781075
100
390
771150 / 781150 771250 / 781250 771400 / 781400
100
465
791025
100
205
791050
100
290
791075
100
390
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
25
Element
Ensure that the unit is unplugged or isolated from the electrical supply and the stopcock is closed. Water at elevated temperatures may be present when draining, care should be taken to prevent scalding.
741/751 Series
1. Drain the Lazer boiling water unit
2. Remove the Nameplate. (Refer to page 19)
3. Disconnect the 2 wires from the element terminals.
4. Disconnect the wiring to the water temperature sensor.
5. Undo the 2 retaining nuts from the element flange and remove the element.
6. Replace element gasket if required.
7. Reassemble in the reverse order of above.
8. Restore water and power supplies and allow unit to fill and heat.
9. Check for water leaks
10. Refit nameplate. Disconnect power during this step.
761, 771/781 and 791 series
2.5L – 7.5L
1. Drain the Lazer boiling water unit.
2. Remove the Jacket Front. (Refer to page 19)
3. Disconnect wire from element terminal and ECO.
4. Disconnect the wiring to the water temperature sensor.
5. Undo the 2 retaining nuts from the element flange and remove the element.
6. Replace element gasket if required.
7. Reassemble in reverse order of above.
8. Restore water and power supplies and allow unit to fill and heat.
9. Check for water leaks.
10. Refit the Jacket Front. Disconnect power during this step.
15L – 40L
Follow the procedure outlined above, removing the left hand side panel (Refer to figure 9 page 22) not the jacket front at step 2.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
26
Tap
Ensure that the unit is unplugged or isolated from the electrical supply and the stopcock is closed. Water at elevated temperatures may be present when draining, care should be taken to prevent scalding.
741/751 & 771/781 Series
1. Drain the Lazer boiling water unit.
Tap head only
2. Using a spanner undo the lock nut at the tap head.
3. Remove the tap head.
4. Fit the replacement tap, ensuring it is vertical when retightening the lock nut
5. Restore water and power supplies and test boiling water unit operation
Complete Tap Assembly
2. Grip the tap extension with multigrips (or similar) and unscrew the tap assembly from the tank. Care should be taken not to damage or distort the tank.
3. Apply Teflon thread tape to the replacement tap extension and screw into the tank. Care should be taken not to damage or distort the tank. (A barrier such as a piece of cloth should be wrapped around the replacement tap extension to prevent damage to the finish of the shaft by tools)
4. Ensure the tap head is vertical; loosening the tap head lock nut will allow adjustment of the tap head position.
5. Restore water and power supplies and boiling water unit operation.
Figure 13
761/791Series
1. Drain the Lazer boiling water unit
2. Remove the jacket front. (Refer to page 19)
3. Unscrew the lock nut (anti-clockwise) and gently pull the tap assembly from the tap body.
4. Carefully insert the replacement tap assembly into the tap body and tighten the lock nut (clockwise). Note: Do not over tighten, as this will cause the tap to drip.
To replace the spring, lightly compress the spring by pressing on the front of the diaphragm. This will facilitate the removal of the tap cap pin to allow the tap to be disassembled.
Figure 14
Note: The tap seal and spring are replaceable as separate items. Refer to Spare Parts Manual SPM-BW for part numbers.
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Service Instructions REV AD. Issue 02/01/14
This document is stored and maintained electronically by Service. All printed copies are deemed “uncontrolled”
27
DOCUMENT REVISION HISTORY
Title:
Lazer 441, 451, 741, 751, 761, 771, 781 & 791 Series Service Instructions
Document No:
TM001
Rev
Details of change
D.O.I.
A
Service Instructions issued for 441/451 series Lazer
05/87
B
Service Instructions updated to cover 741, 751, 771, 781, 761 & 791 series Lazer
27/04/01
C
Reference to Southcorp replaced by Rheem Australia
28/03/03
AD
Format updated; Warranty Statement removed; Exploded views & Replacement Parts Lists removed, now form part of Boiling Water Spare Parts Manual SPM-BW
02/01/14
NOTE: Every care has been taken to ensure accuracy in preparation of this publication. No liability can be
accepted for any consequences which may arise as a result of its application.
Loading...