Rheem 54 KW, 6 KW User Manual

IMMERSION ELECTRIC TANK-TYPE WATER HEATERS
6 KW THRU 54 KW
RHEEM-RUUD Electric Commercial Water Heaters are
suitable for general commercial hot water applications and are also ideal for point-of-use installations, eliminat­ing costly temperature loss in long piping runs. A single unit can be used as a booster heater to satisfy the hot water requirements of commercial dishwashers. A single temperature storage unit, when installed with a mixing valve, will supply two temperatures in food service establishments. For larger volume hot water requirements, 2, 3 or 4 units can be parallel manifolded, using optional factory kits.
Construction Features:
SYSTEM SENTINEL – An element diagnostic
panel, utilizing light emitting diodes (L.E.D.) correspond­ing to the number and location of each heating element are energized when the electric elements are operating. An unlit L.E.D. pinpoints the exact location of a non­functioning element, making element operation diagnosis simple and positive..
R-FOAM®INSULATION – A rigid ployurethane
foam insulation provides superior insulating qualities, improves efficiency. Exceeds R-16 insulation factor. Our patented process of injecting R-Foam directly into the insulating cavity adds additional durability and toughness to the heater jacket. Fiberglass insulation guards against heat loss in the heating element compartment, and provides easy service access.
LIFEGUARD HEATING ELEMENTS – Separate
screw-in type elements feature a stainless steel outer sheath of INCO-LOY®800, surrounding a Nichrome wire filament, to resist water chemical corrosion and burn-out even in air or sediment…for long element life and long life performance. Elements are directly immersed in the water for efficient transfer of heat, and are easily changed by simply screwing new ones into the tank.
GLASS LINED STORAGE TANK – Heavy duty
steel tank protects with double coating of exclusive Rheemglas to resist the corrosive action of hot water. Designed for 150 PSI working pressure. Each tank is supplied with factory installed anode rods for cathodic protection.
Certifications and Ratings:
EFFICIENCY – These units have been tested according to procedures specified by CSA and meet or exceed the energy
efficiency requirements of ASHRAE Standard 90.1b 1992 requirements for energy conservation.
50, 85 AND 120 GALLON CAPACITIES
208, 240 AND 600 VOLTAGES
EG IMMERSION THERMOSTAT MODELS
WATER CONNECTIONS – Hot outlet and cold inlet
are 1-1/2" NPS brass nipples which prevent excessive turbulence of heating water and result in optimum tank draw.
SINGLE PANEL CONTROL BOX – With hinged
door, provides immediate access to all electrical components and elements.
TERMINAL BLOCK – All models are equipped with
CSA listed terminal blocks for simplicity of installation. This new terminal block will accept either copper or aluminum field connect wire.
RECOVERY CAPACITIES
Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises
INPUT EQUIVALENT 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
KW BTU/HR. UNITS
(22°C) (28°C) (33°C) (39°C) (45°C) (50°C) (56°C) (61°C) (67°C) (72°C) (78°C)
6 GPH
LPH
9 30,709 GPH 93 74 62 53 47 41 37 34 31 29 27
LPH 352 282 235 201 176 157 141 128 117 108 101
12 40,946 GPH 124 99 83 71 62 55 50 45 41 38 35
LPH 470 376 313 268 235 209 188 171 157 145 134
15 51,183 GPH 155 124 103 89 78 69 62 56 52 48 44
LPH 587 470 391 335 294 261 235 213 196 181 168
18 61,420 GPH 186 149 124 106 93 83 74 68 62 57 53
LPH 705 564 470 403 352 313 282 256 235 217 201
24 81,893 GPH 248 199 165 142 124 110 99 90 83 76 71
LPH 939 751 626 537 470 417 376 342 313 289 268
30 102,366 GPH 310 248 207 177 155 138 124 113 103 95 89
LPH 1174 939 783 671 587 522 470 427 391 361 335
36 122,839 GPH 372 298 248 213 186 165 149 135 124 115 106
LPH 1409 1127 939 805 705 626 564 512 470 434 403
45 153,549 GPH 465 372 310 266 233 207 186 169 155 143 133
LPH 1761 1409 1174 1006 881 783 705 640 587 542 503
54 184,259 GPH 558 447 372 319 279 248 223 203 186 172 160
LPH 2114 1691 1409 1208 1057 939 845 769 705 650 604
ELECTRICAL CHARACTERISTICS
INPUT
KW
NO.
OF
ELE-
MENTS
ELE-
MENT
WAT-
TAG E
FULL LOAD CURRENT
IN AMPERES
208V
Phase
1 3
240V
Phase
1 3
600V
Phase
3
IMMERSION THERMOSTATS
Number
of Fuses
30A Class G
208/240V 600V
Number
of
Contactors
208/240V 600V
Optional Models – Staged
Models with Suffix “F”
Number of
Thermostats
KW Step
Size
Number
of
Thermostats
IMMERSION THERMOSTATS Tank Capacity In Gallons
50 Gal. (190L) 85 Gal. (321L) 120 Gal. (454L)
EG50-C-9 EG85-C-9 EG120-C-9 EG50-C-12 EG85-C-12 EG120-C-12 EG50-C-15 EG85-C-15 EG120-C-15 EG50-C-18 EG85-C-18 EG120-C-18 EG50-C-24 EG85-C-24 EG120-C-24 EG50-C-30 EG85-C-30 EG120-C-30 EG50-C-36 EG85-C-36 EG120-C-36
EG85-C-45 EG120-C-45 EG85-C-54 EG120-C-54
INPUT
KW
6
9 12 15 18 24 30 36 45 54
N/A
ONE
THERMOSTAT
STANDARD
6 16
9 3 3000 43 25 38 22 9 6 3 2 1 1 9 12 3 4000 58 33 50 29 12 6 3 2 1 1 12 15 3 5000 72 42 63 36 15 6 3 2 1 1 15 18 3 6000 87 50 75 43 18 6 3 2 1 1 18 24 6 4000 116 67 100 58 23 12 6 4 2 1 2 12 30 6 5000 144 84 125 73 29 12 6 4 2 1 2 15 36 6 6000 173 100 150 87 35 12 6 4 2 1 2 18 45 9 5000 217 125 188 109 43 18 9 6 3 1 3 15 54 9 6000 260 150 225 130 52 18 9 6 3 1 3 18
MODEL NUMBERS
Loading...