Use copper pipe ONLY. Plastic pipe MUST NOT be used.
It is a requirement of a solar water heater installation that all pipe work be in copper
and not plastic, due to the effects of high water temperatures and pressures.
Owner’s Guide
and
Installation Instructions
Solar 511161 Storage Tank
This water heater must be installed and serviced by a qualified person.
Please leave this guide with the householder.
Page 2
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the solar collectors MUST BE
of copper. All compression fittings must use brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating application and capable of
withstanding the temperature of the water generated by the solar collectors under stagnation
conditions
The specification of the chosen insulation material should be checked with the insulation
manufacturer prior to installation as different materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to comply with the
requirements of AS/NZS 3500.4
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar pipe work
be fitted up to and cover the connections on both the solar storage tank and the solar collectors.
Note: Failure to observe these requirements also increases the risk of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or where it may be in contact
with a metal roof, may lead to freeze damage. The system has NO WARRANTY for freeze damage if
the solar hot and solar cold pipes are not insulated in accordance with the installation instructions.
The insulation is essential to assist in providing freeze protection, will offer protection to a metal roof
against corrosion due to water running off the copper pipes, assist in avoiding accidental contact with
the solar pipe work as very high temperature water can flow from the solar collectors to the solar
storage tank, and also reduce pipe heat losses.
The insulated copper pipe work:
should be fixed at suitable locations to prevent or reduce the possibility of noise from water
hammer and vibration from occurring
is not to be placed or installed in contact with plastic pipe work.
Likewise, plastic pipe work is not to be placed or installed in contact with the insulated copper pipe
work after the collector circuit is installed.
Plastic pipe MUST NOT be used, as it will not withstand the temperature and pressure of the water
generated by the solar collector(s) under stagnation conditions. Extremely high water temperatures of
up to 150°C for non-selective surface collector(s) and greater than 200°C for selective surface
collector(s) and high water pressures exceeding 1000 kPa can be generated under these conditions.
Plastic pipe cannot withstand these temperatures and pressures and MUST NOT be used. Failure of
plastic pipe can lead to the release of high temperature water and cause severe water damage and
flooding.
Plumber: It is important to refer to and read in full the complete
“Warning: Plumber –Be Aware” statement commencing on page 41.
This water heater may be protected by one or more patents or registered designs.
®
Registered trademark of Rheem Australia Pty Ltd.
™ Trademark of Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure accuracy in preparation of this publication.
No liability can be accepted for any consequences, which may arise as a result of its application
PATENTS
TRADE MARKS
Page 3
CONTENTS
HOUSEHOLDER – We recommend you read pages 4 to 21.
The other pages are intended for the installer but may be of interest.
About Your Water Heater ............................................................................................................ 4
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable
water. Its use in an application other than this may shorten its life.
MODEL TYPE
Your Rheem® solar Loline water heater is designed for the solar collector(s) to be roof mounted and the
vitreous enamel lined solar storage tank to be installed at ground or floor level, remotely from the solar
collector(s). The solar storage tank is suitable for installation either outdoor or indoor and with 1 x CSA2612 or
1 or 2 x LCS or 1 or 2 x NPT200 solar collector(s). If an in-series gas booster is mounted to the solar storage
tank, then it is suitable for outdoor installation only.
The system is not suitable for installation above 400 metres altitude.
The system has a level of freeze protection designed to guard the system against
damage from freeze conditions (refer to “Freeze Protection” on page 8). The system must
be installed with the full length of the solar hot and solar cold pipes insulated and power
must be available at the solar control unit to offer protection against freeze damage (refer
to “Warning: Plumber – Be Aware” on page 41). Freeze conditions occur below 6°C.
Note: The Rheem warranty against freeze damage applies only to systems installed in
Australia.
The system has NO WARRANTY for freeze damage when installed above 400 metres
altitude or if the solar hot and solar cold pipes are not insulated in accordance with the
installation instructions or if power is not available at the solar control unit (refer to “Terms
of the Rheem Warranty” on page 58).
This solar water heater is designed to be installed with a Rheem continuous flow
874 series 20 or 26 litre in-series gas booster either mounted onto the storage tank or
installed remotely, or a Rheem 874 series 27 litre in-series gas booster installed remotely.
The solar water heater may be installed with another suitable type of remotely installed
in-series continuous flow or storage booster. If the in-series water heater is other than a
Rheem continuous flow 874 series 20 or 26 or 27 litre in-series gas booster, then the
references to the in-series gas booster in this guide may not be applicable to the
installation.
For information relating to the function and operation of the in-series water heater, refer
to the Owner’s Guide and Installation Instructions supplied with the water heater.
MAINS PRESSURE
The water heater is designed to operate at mains pressure by connecting directly to the mains water supply.
If the mains supply pressure in your area exceeds that shown on page 25, a pressure limiting valve must be
fitted. The supply pressure should be greater than 350 kPa for true mains pressure operation to be achieved.
A minimum water supply pressure of 200 kPa is required to enable the solar circulator and solar circuit system
to operate effectively.
SOLAR OPERATION
The operation of the circulator is controlled by the combination of:
the hot sensor located at the outlet of the solar collectors.
The hot sensor measures the water temperature at the outlet of the solar collectors.
the cold sensor located at the solar cold outlet at the base of the solar storage tank
The cold sensor measures the water temperature at the bottom of the solar storage tank.
the differential controller located in the solar control unit.
4
Page 5
ABOUT YOUR WATER HEATER
Normal operation
As the sun heats the water in the solar collectors, the increase in temperature activates the circulator. The
circulator switches on whenever the water in the solar collectors is hotter than the water in the solar storage
tank. The circulator moves the hotter water from the solar collectors through the solar hot pipe to the solar
storage tank and the cooler water from the solar storage tank is circulated to the solar collectors via the solar
cold pipe to be heated by the sun’s energy.
This process continues whilst solar energy is available and the water in the solar storage tank requires heating.
The circulator will deactivate when the water temperature in the solar storage tank is around 65°C to 75°C.
The water heater will then enter Over-temperature operation.
During normal operation if the amount of solar energy available reduces, such as when the sky becomes very
cloudy or the sun becomes lower in the sky in the late afternoon, and the water no longer gains useable heat
from the solar collectors, the circulator will deactivate. The water heater will then enter standby mode.
Over-temperature operation
The purpose of the Over-temperature operation is to reduce the amount of overheating or ‘stagnation’ of water
in the solar collectors. When the water in the solar storage tank has reached 65°C to 75°C and the circulator
has deactivated, the solar collectors will continue to gain heat while solar energy is still available.
If the water in the solar collectors stagnates and its temperature becomes very high, the circulator will activate
for a short period to transfer this extra energy to the solar storage tank. The circulator will deactivate when the
water temperature in the solar collectors decreases. This process will either repeat for a maximum of six cycles
or until the water temperature in the solar storage tank reaches around 75°C to 80°C or the hot sensor does
not sense another increase in water temperature to a stagnation level after a cycle is completed, i.e. the solar
energy available reduces.
Night Time Cooling operation
The purpose of Night Time Cooling operation is to rid the solar storage tank of excess solar energy gained by
Over-temperature operation during that day. The desired water temperature in the solar storage tank is to be
between 60°C to 70°C.
If the solar control unit has entered Over-temperature operation during the day, then after the water
temperature in the solar collectors reduces later in the day or early evening, the circulator will activate. Water
from the solar storage tank will circulate through the solar collectors and excess heat in the water will radiate
from the solar collectors reducing the temperature of the water. The water will circulate for a period of time and
until the water temperature in the solar storage tank is around 60°C to 70°C. The water heater will then enter
standby mode.
Freeze Protection operation
The purpose of Freeze Protection operation is to prevent freezing of water in the solar collectors and solar
pipe work in very cold conditions. The water in the solar collectors will cool during periods of no solar gain. In
very cold conditions, such as overnight and very early in the morning before sunrise, the water temperature
can approach freezing point.
If the hot sensor measures that the water temperature in the solar collectors is approaching freezing, the
circulator will activate. Water from the solar storage tank, containing more energy than the water in the solar
collectors, will circulate through the solar collectors keeping the water temperature above freezing point. The
circulator will remain on for some minutes and until the hot sensor measures a water temperature at a safe
level above freezing. When both of these conditions are met, the circulator will deactivate. The water heater
will then enter standby mode.
This process will repeat whenever the hot sensor measures that the water temperature in the solar collectors
is approaching freezing.
The anti-freeze heating unit in a frost element model will turn on when the circulator activates and the cold
sensor measures a very low water temperature at the bottom of the solar storage tank. The purpose of the
anti-freeze heating unit is to provide additional energy to the water to assist in the prevention of freezing in the
solar pipe work and solar collectors. The anti-freeze heating unit will turn off when either the water temperature
has risen by a few degrees or the circulator deactivates. The water heater will then enter standby mode.
Refer to “Freeze Protection” on page 8 and “Warning: Plumber – Be Aware” on page 41.
5
Page 6
ABOUT YOUR WATER HEATER
Mode
Green LED
Red LED
power on* > 48 hours
power on* < 48 hours
Normal operation
rapid pulse
3 flashes
off **
Over-temperature operation
rapid pulse
3 flashes
off, or solid then off
Night Time Cooling operation
rapid pulse
3 flashes
off
Freeze Protection operation
rapid pulse
3 flashes
off
Standby mode
solid
slow pulse
off
Notes
* Power from the GPO to the solar control unit.
** In Normal Operation the red LED may emit a rapid pulse for a short period of time under certain
circumstances (refer to “Rapid Pulsing” on page 20).
typical maximum
temperature from solar gain
maximum recommended
supply temperature to
bathrooms and ensuites
Standby mode
The water heater will be in Standby mode whenever conditions are not favourable for solar heating in Normal
operation, and Over-temperature operation and Night Time Cooling are not required or have been completed,
and conditions are not cold enough for or in-between Freeze Protection operation.
Solar Monitor LED operation
The LEDs on the Solar Monitor, located on the side of the solar control unit, operate to show the operational
mode of the water heater. Refer also to “Solar Monitor” on page 9.
HOW HOT SHOULD THE WATER BE?
The solar control unit will circulate water through the solar collector(s)
until a temperature of 70°C to 80°C is reached in the solar storage
tank.
During periods of low solar energy gain, the continuous flow in-series
gas booster will boost the water temperature automatically to its
preset outlet temperature setting, or to the temperature setting of
another type of in-series booster water heater.
The factory preset outlet temperature setting of the in-series gas
booster is:
874 series 20 litre, 26 litre, 27 litre models 60°C
Note: The preset outlet temperature setting of a continuous flow inseries gas booster cannot be adjusted by the householder. The
setting can only be adjusted by the installer, Rheem Service or their
nearest Accredited Service Agent.
Note: AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in
potable water. If this water heater is installed with an in-series continuous flow gas booster, then this
requirement of AS 3498 can be satisfied provided the booster is energised, its preset outlet temperature setting
is 70°C or higher and a remote temperature controller or an EZiSET kit is not used.
If this water heater is installed with an in-series storage booster, then this requirement of AS 3498 can be
satisfied provided the storage booster is energised and its thermostat setting is 60°C or higher.
Warning: Temperature controllers or an EZiSET kit must not be fitted to the in-series water heater as part
of a solar water heater system because water at a temperature much higher than the controller or EZiSET
setting can be delivered.
6
Page 7
ABOUT YOUR WATER HEATER
HOTTER WATER INCREASES THE RISK OF SCALD INJURY
This water heater can deliver water at temperatures which can cause scalding. Check the water temperature
before use, such as when entering a shower or filling a bath or basin, to ensure it is suitable for the application
and will not cause scald injury.
We recommend and it may also be required by regulations that an approved temperature limiting device be
fitted into the hot water pipe work to the bathroom and ensuite when this water heater is installed. This will
keep the water temperature below 50°C at the bathroom and ensuite. The risk of scald injury will be reduced
and still allow hotter water to the kitchen and laundry.
SAFETY
This water heater is supplied with a thermostat, an over-temperature energy cut-out, temperature sensors and
a combination temperature pressure relief valve. These devices must not be tampered with or removed. The
water heater must not be operated unless each of these devices is fitted and is in working order.
The operation of the over-temperature cut-out on the thermostat indicates a possibly dangerous situation. If
the over-temperature cut-out operates, it must not be reset and the water heater must be serviced by a qualified
person.
If the power supply cord or plug to the solar control unit or the electrical conduit to the solar storage tank is
damaged, it must be replaced by a qualified person in order to avoid a hazard. The power supply cord and
plug must be replaced with a genuine replacement part available from Rheem. Phone Rheem Service or their
nearest Accredited Service Agent to arrange for an inspection.
The Rheem warranty may not cover faults if relief valves or other safety devices are tampered with or
if the installation is not in accordance with these instructions.
WARNINGS
This water heater is only intended to be operated by persons who have the experience or the knowledge
and the capabilities to do so.
This water heater is not intended to be operated by persons with reduced physical, sensory or mental
capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere
with the water heater.
This water heater uses 240 V AC electrical power for operation of the control systems and the electrically
operated components. The removal of the front cover or solar control unit cover will expose 240 V AC
wiring. It must only be removed by a qualified person.
The power lead from the solar controller must be plugged into a weatherproof electrical outlet if installed
outdoors. Take care not to touch the power plug with wet hands.
Do not touch any exposed pipe work or fittings connecting the solar storage tank and the solar collector(s),
as this may result in a burn injury. Very high temperature hot water and in some circumstances high
temperature steam can be generated by the solar collector(s) under certain conditions and this flows
through the pipe work from the solar collector(s) to the solar storage tank.
Note: Any exposed pipe work or fittings in the collector circuit should be attended to and covered with
insulation. Phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
For continued safety of this water heater it must be installed, operated and maintained in accordance with
the Owner’s Guide and Installation Instructions.
Do not modify this water heater.
7
Page 8
ABOUT YOUR WATER HEATER
PRECAUTIONS
Where damage to property can occur in the event of the water heater leaking, the water heater must be
installed in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4
and all local codes and regulatory authority requirements.
The water heater must be maintained in accordance with the Owner’s Guide and Installation Instructions. Refer
to “Maintenance Requirements” on page 12 and to “Anode Inspection and Replacement” on page 16.
If this water heater is to be used where an uninterrupted hot water supply is necessary for your application or
business you should ensure that you have back-up redundancy within the hot water system design. This should
ensure the continuity of hot water supply in the event that this water heater were to become inoperable for any
reason. We recommend you seek advice from a plumber or specifier about your needs and building back-up
redundancy into your hot water supply system.
FREEZE PROTECTION
The system has a level of freeze protection designed to guard the system against damage from freeze
conditions. The system must be installed with the full length of the solar hot and solar cold pipes insulated and
power must be available at the solar control unit to offer protection against freeze damage (refer to “Warning:
Plumber – Be Aware” on page 41). Freeze conditions occur below 6°C.
Note: The Rheem warranty against freeze damage applies only to systems installed in Australia.
The system has NO WARRANTY for freeze damage when installed above 400 metres altitude or if the solar
hot and solar cold pipes are not insulated in accordance with the installation instructions or if power is not
available at the solar control unit (refer to “Terms of the Rheem Warranty” on page 58).
The anti-freeze control is designed to recirculate a small amount of water from the solar storage tank through
the solar pipe work and solar collector(s) during periods of low temperatures. This is to prevent the water inside
the pipe work and solar collector(s) from freezing. It is essential the electrical circuit to the solar control unit is
continually turned on if there is a risk of freezing. The Rheem warranty does not cover damage caused by
freeze conditions when the electrical circuit to the solar control unit is turned off or interrupted.
Additional freeze protection is provided by the anti-freeze heating unit. The anti-freeze heating unit is for
heating the water at the bottom of the solar storage tank at times of low cold water temperature. The antifreeze heating unit provides additional energy to the water to assist in the prevention of freezing in the solar
pipe work and solar collector(s). The anti-freeze heating unit is controlled by the solar controller and will only
be energised when the water temperature is very low and the circulator activates in the Freeze Protection
operation mode. The water temperature is monitored by the cold sensor.
If the water temperature at the bottom of the solar storage tank is very low when the circulator activates in the
Freeze Protection operation mode, the anti-freeze heating unit will be energised and will heat the water by a
few degrees. The anti-freeze heating unit will be de-energised when either the frost mode is shut down or the
water temperature has risen by a few degrees.
The anti-freeze heating unit is supplied with power from the solar control unit. The power outlet to the solar
control unit must be switched on for the anti-freeze heating unit to operate and offer additional freeze
protection.
An over-temperature energy cut-out is incorporated in a thermostat which is mounted on the solar storage tank
behind the front cover.
Notes:
The system is not covered for freeze damage above 400 metres altitude.
The freeze protection system will be rendered inoperable if electrical power is not available at the solar
control unit. Damage caused by freezing due to no power at the solar control unit, is not covered by the
Rheem warranty.
If it is necessary to switch the power off to the solar control unit and there is a risk of freezing, then it is
necessary to have a plumber drain the solar collector(s) and solar hot and solar cold pipes.
Refer to “Terms of the Rheem Warranty” on page 58.
8
Page 9
ABOUT YOUR WATER HEATER
Flashes
Operational Modes
Flashes
Indicator or Fault Modes
solid green
(remains on)
Standby mode
solid red
(remains on)
Hot sensor temperature
greater than 130°C
green
slow pulse
Standby mode
(power on for less than 48 hours)
red
rapid pulse
Temperature rise across collector
greater than 45°C
(circulator at full speed)
green
rapid pulse
Circulating water through collectors
3 x red
Hot sensor in collector – short circuit
3 x green
Circulating water through collectors
(power on for less than 48 hours)
4 x red
Hot sensor in collector – open circuit
no green
(remains off)
Power outage or call for service
5 x red
Cold sensor –short circuit
6 x red
Cold sensor – open circuit
SOLAR MONITOR
A solar monitor is located on the side of the solar control unit and houses a green and a red LED.
The green LED, marked “Solar”, indicates the current operational mode of the solar water heater and the red
LED, marked “Attention”, may indicate a potential fault mode.
The green LED will emit either a constant glow, a constant
pulsing or a series of flashes, with a two (2) second interval
between each series.
The red LED will emit either a constant glow, a constant
pulsing or a series of flashes with a two (2) second interval
between each series. A constant glow or pulsing does not
necessarily mean there is a fault with the system. A series of
flashes indicates there may be a particular fault condition with
the system.
The modes are:
If the power supply to the solar control unit is on and the green LED is off or the red LED is flashing, this
indicates there may be a fault with the water heater. The red LED may emit from three (3) to six (6) flashes in
each series of flashes. A constant glow or pulsing of the red LED does not necessarily mean there is a fault
with the system.
Notes:If the system is in standby mode with the green LED emitting either a constant glow or slow pulsing flashes
(circulator is off) and the solar storage tank is full of hot water, the red LED may simultaneously emit a
constant glow if solar radiation is still being received by the solar collectors. This does not indicate a fault.
The red LED will go out when the temperature in the solar collectors decreases.
During periods of high solar radiation and the circulator activates after having been off (the green LED will
emit either a rapid pulse or a series of three flashes), it is possible the red LED may simultaneously emit
a rapid pulse for a period of up to ten (10) minutes. This does not indicate a fault.
If the red LED continues to emit a rapid pulse for longer than ten (10) minutes, or emits a series of flashes,
then count the number of flashes and phone Rheem Service or their nearest Accredited Service Agent to
arrange for an inspection.
9
Page 10
ABOUT YOUR WATER HEATER
TO TURN OFF THE WATER HEATER
If you plan to be away from home for a few nights, we suggest you leave the water heater switched on.
If it is necessary to turn off the water heater:
Switch off the electrical supply to the solar control unit at the power outlet (refer to the notes below).
Close the cold water isolation valve at the inlet to the water heater.
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series water heater for the
procedure to turn off the in-series water heater.
Notes:
The freeze protection system will be rendered inoperable if electrical power is not available at the solar
control unit. Damage caused by freezing due to no power at the solar control unit is not covered by the
Rheem warranty. Refer to “Terms of the Rheem Warranty” on page 58.
If there is a risk of freezing, the electrical supply to the solar control unit should not be switched off unless
the solar collector(s) and solar hot and solar cold pipes are drained, otherwise damage could result (refer
to “Freeze Protection” on page 8).
TO TURN ON THE WATER HEATER
Open the cold water isolation valve fully at the inlet to the water heater.
If the solar collector(s) and solar hot and solar cold pipes have been drained, it will be necessary to have
a plumber purge the collector circuit of air.
If the electrical supply to the water heater has been switched off:
Switch on the electrical supply to the solar control unit at the power outlet.
The power outlet must be switched on for the solar control unit to operate and solar gain to be achieved
and for the anti-freeze heating unit to operate and offer additional freeze protection.
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series water heater for the
procedure to turn on the in-series water heater.
GOING ON HOLIDAYS
It is not necessary to switch off the electrical supply at the power outlet to the solar control unit. Refer to “To
Turn Off The Water Heater” on page 10. Also if the system is not used for a period in excess of four (4) weeks
it is recommended the solar collector(s) be covered.
HOW DO I KNOW IF THE WATER HEATER IS INSTALLED CORRECTLY?
Installation requirements are shown on pages 25 to 32. The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with Standards AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3 (for a Class 1a or
Class 10 building) as applicable under the Plumbing Code of Australia, AS/NZS 3000, and either AS 5601
or AS/NZS 5601.1 as applicable under local regulations, and all local codes and regulatory authority
requirements.
Warning: Temperature controllers or an EZiSET kit must not be fitted to the in-series water heater as part
of a solar water heater system because water at a temperature much higher than the controller or EZiSET
setting can be delivered.
Refer also to “Warning: Plumber – Be Aware” on page 41.
10
Page 11
ABOUT YOUR WATER HEATER
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Plumbing Industry Commission. This water heater must be
installed by a licensed person as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that the work complies with all the
relevant Standards. Only a licensed person will have insurance protecting their workmanship for 6 years. Make
sure you use a licensed person to install this water heater and ask for your Compliance Certificate.
DOES THE WATER CHEMISTRY AFFECT THE WATER HEATER?
The water heater is suitable for most public water supplies, however some water chemistries may have
detrimental effects on the water heater, the solar collectors, components and fittings. Refer to “Water Supplies”
on page 15.
If you are in a known harsh water area or you are not sure of your water chemistry, have your water checked
against the conditions described on pages 15 to 17.
HOW LONG WILL THE WATER HEATER LAST?
The water heater is supported by a manufacturer’s warranty (refer to page 58). There are a number of factors
that will affect the length of service the water heater will provide. These include but are not limited to the water
chemistry, the water pressure, the water temperature (inlet and outlet) and the water usage pattern. Refer to
“Precautions” on page 8.
11
Page 12
MAINTENANCE REQUIREMENTS
MINOR MAINTENANCE EVERY SIX MONTHS
It is recommended minor maintenance be performed every six (6) months. Minor maintenance can be
performed by the dwelling occupant.
The minor maintenance includes:
Operate the easing lever on the temperature pressure relief valve. It is very important you raise and lower
the lever gently. Refer to “Temperature Pressure Relief Valve” on page 13.
Warning: Exercise care to avoid any splashing of water, as water discharged from the drain line will
be hot. Stand clear of the drain line’s point of discharge when operating the valve’s lever.
Operate the easing lever on the expansion control valve (if fitted). It is very important you raise and lower
the lever gently. Refer to “Expansion Control Valve” on page 14.
Check the drain line from the safe tray (if one is installed) is not blocked.
Check the status of the LEDs. The green LED should be illuminated (either solid, pulsing or flashing). The
red LED should be off. Refer to “Solar Monitor” on page 9 and “Household Maintenance Around the Solar
Storage Tank” on page 14.
It is important to ensure the solar controller and circulator are operating correctly, particularly at the onset
of the colder winter season. Solar gain will not be achieved and the freeze protection system will be
rendered inoperative if the solar controller or circulator are not operating.
If this solar storage tank is installed with an integrated or remotely installed Rheem in-series continuous flow
gas booster, it is recommended minor maintenance be performed every six months on the gas booster by the
dwelling occupant. Another type of in-series booster may have its own recommended minor maintenance
schedule. Refer to the Owner’s Guide and Installation Instructions supplied with the booster water heater for
information regarding its recommended maintenance.
MAJOR SERVICE EVERY FIVE YEARS
It is recommended a major service be conducted on the water heater every five (5) years. If an anode
replacement is conducted sooner than a major service, then the major service should coincide with the
replacement.
Warning: Servicing of a water heater must only be carried out by qualified personnel. Phone Rheem
Service or their nearest Accredited Service Agent.
Note: The major service and routine replacement of any components, such as the anode and relief valve(s),
are not included in the Rheem warranty. A charge will be made for this work. Only genuine replacement parts
should be used on this water heater.
The major service includes the following actions:
Replace the temperature pressure relief valve.
Inspect and flush the expansion control valve (if fitted). If required, replace the valve.
Inspect and if required, replace the anode.
If the anode is not replaced, it should be replaced within three years of this service (refer to “Anode
Inspection and Replacement” on page 16).
Check the electric heating unit for excessive calcium build-up or corrosion and replace if necessary.
Check the solar control unit for correct operation.
Flush and bleed the solar collectors.
Clean the collector glass.
12
Page 13
MAINTENANCE REQUIREMENTS
water
heater
drain
line
lift until water
flows from the
drain line –
lower gently
Check the insulation on the solar hot and solar cold pipes. If required, insulate exposed pipe work and
repair or replace degraded insulation.
Visually check the unit for any potential problems.
Inspect all connections.
Check the drain line from the safe tray (if one is installed) is not blocked.
Note: The solar storage tank may need to be drained during this service. After the completion of the service,
the solar storage tank will take some time to reheat the water by solar gain.
If this solar storage tank is installed with an integrated or remotely installed Rheem in-series continuous flow
gas booster, then for the booster’s safe and efficient operation, it is recommended a major service be
conducted on the gas booster every five (5) years. Another type of in-series booster may have its own
recommended service schedule. Refer to the Owner’s Guide and Installation Instructions supplied with the
booster water heater.
TEMPERATURE PRESSURE RELIEF VALVE
This valve is near the top of the water heater and is essential
for its safe operation. It is possible for the valve to release a
little water through the drain line during each heating period.
This occurs as the water is heated and expands by
approximately 1/50 of its volume.
Continuous leakage of water from the valve and its drain
line may indicate a problem with the water heater (refer to
“Temperature Pressure Relief Valve Running” on page 19).
Warning: Never block the outlet of this valve or its drain
line for any reason.
Operate the easing lever on the temperature pressure relief
valve once every six (6) months. Refer to “Minor
Maintenance Every Six Months” on page 12. It is very
important the lever is raised and lowered gently.
DANGER: Failure to do this may result in the water
heater cylinder failing, or under certain circumstances,
exploding.
Warning: Exercise care to avoid any splashing of water,
as water discharged from the drain line will be hot. Stand
clear of the drain line’s point of discharge when operating
the valve’s lever.
If water does not flow freely from the drain line when the
lever is lifted, then the water heater must be checked.
Phone Rheem Service or their nearest Accredited Service
Agent to arrange for an inspection.
The temperature pressure relief valve should be replaced at
intervals not exceeding five (5) years, or more frequently in
areas where there is a high incidence of water deposits
(refer to “Water Supplies” on page 15).
13
Page 14
MAINTENANCE REQUIREMENTS
EXPANSION CONTROL VALVE
In many areas, including South Australia, Western Australia and scaling water areas, it is mandatory an
expansion control valve is fitted to the cold water line to the water heater. The expansion control valve may
discharge a small quantity of water from its drain line during the heating period instead of the temperature
pressure relief valve on the water heater.
Operate the easing lever on the expansion control valve once every six (6) months. Refer to “Minor
Maintenance Every Six Months” on page 12. It is very important the lever is raised and lowered gently. If
water does not flow freely from the drain line when the lever is lifted, then the water heater should be checked
by Rheem Service or their nearest Accredited Service Agent. The expansion control valve should be checked
for performance or replaced at intervals not exceeding five (5) years, or more frequently in areas where there
is a high incidence of water deposits.
COLLECTOR GLASS
Ensure the glass on your solar collector(s) is free of dust, salt spray or any other matter which may reduce the
effectiveness of the solar collector(s). Rainfall should keep the collector adequately clean. It is recommended
the collector glass be washed clean at least every three months should adequate rain not have fallen in this
period.
Collector glass can be hosed down or if the solar collector(s) is accessible such as on a trafficable roof, wash
the collector glass with water and a soft brush when the solar collector(s) is cool, such as early in the morning.
In extremely dusty areas extra attention may need to be given to keeping the collector glass clean.
Have any trees trimmed which may shade the solar collector(s).
Rheem solar collectors have passed the AS/NZS 2712 requirements for resistance to hailstone damage, so it
is not normally necessary to fit a guard to a collector. Stone Guards are available for the LCS and NPT200
solar collectors to provide a level of protection to the collectors against vandalism or accidental damage.
Contact Rheem or your local Rheem Solar Water Heater Distributor for details.
HOUSEHOLD MAINTENANCE AROUND THE SOLAR STORAGE TANK
Care should be taken when conducting general household maintenance, such as lawn mowing and grass
cutting, around the solar storage tank. Careless use of devices such as a whipper snipper could damage or
cut a sensor lead, or electrical cable or conduit.
If a sensor lead, or electrical cable or conduit is damaged or cut, solar contribution may not be achieved and
the freeze protection system may be rendered inoperative. In addition, if the electrical cable or conduit has
been damaged or cut, wiring may be exposed leading to a dangerous situation.
On a regular basis, inspect around the water heater for insect infestations, such as ants. Insects may look for
a warm place to nest, particularly in wet weather. Insects encroaching into or nesting in the water heater and
the solar control unit can interfere with the operation of the water heater and also damage components. Spray
insecticide around the water heater if necessary to rid the area of insects.
14
Page 15
Total Dissolved Solids
Anode colour code
0 – 40 mg/L
Green
40 – 150 mg/L
Green or Black
150 – 400 mg/L
Black
400 – 600 mg/L
Black or Blue
600 – 2500 mg/L
Blue
2500 mg/L +
Blue (no cylinder warranty)
(3570)
Green
150
2500
600
400
TOTAL DISSOLVED SOLIDS (TDS) mg/L
(CONDUCTIVITY - μS/cm)
(215)
(570)
(860)
Black
40
(60)
Blue
Blue
ANODE SELECTION
above
2500 mg/L (3570 μS/cm),
no warranty applies to a
vitreous enamel lined
water heater cylinder
warranty applies to a vitreous enamel lined
water heater cylinder if the correct coloured anode
is used for the TDS / conductivity level of the water
WATER SUPPLIES
This water heater must be installed in accordance with this advice to be covered by the Rheem
warranty.
This water heater is manufactured to suit the water conditions of most public reticulated water supplies.
However, there are some known water chemistries which can have detrimental effects on the water heater
and its operation and / or life expectancy. If you are unsure of your water chemistry, you may be able to obtain
information from your local water supply authority. This water heater should only be connected to a water
supply which complies with these guidelines for the Rheem warranty to apply.
CHANGE OF WATER SUPPLY
The changing or alternating from one water supply to another can have a detrimental effect on the operation
and / or life expectation of a water heater cylinder, a temperature pressure relief valve, a heating unit and a
solar collector in an open circuit solar water heater system.
Where there is a changeover from one water supply to another, e.g. a rainwater tank supply, bore water supply,
desalinated water supply, public reticulated water supply or water brought in from another supply, then water
chemistry information should be sought from the supplier or it should be tested to ensure the water supply
meets the requirements given in these guidelines for the Rheem warranty to apply.
ANODE
The vitreous enamel lined cylinder of the water heater is only covered by the Rheem warranty when the total
dissolved solids (TDS) content in the water is less than 2500 mg/L and when the correct colour coded anode
is used. If an incorrect colour coded anode is used in the water heater, any resultant faults will not be covered
by the Rheem warranty. In addition, the use of an incorrect colour coded anode may shorten the life of the
water heater cylinder.
The correct colour coded anode must be selected and fitted to the water heater in accordance with the following
advice and the Anode Selection chart on page 15 for the Rheem warranty to apply to the water heater cylinder.
The changing of an anode must be carried out by a qualified person.
Note: Some water analysis reports may state the conductivity of the water rather than the level of total
dissolved solids. Conductivity, measured in microsiemens per centimetre (µS / cm), is directly proportional to
the TDS content of the water. TDS, in mg / L, is approximately 70% of the conductivity in µS / cm.
15
Page 16
WATER SUPPLIES
ANODE INSPECTION AND REPLACEMENT
The anode installed in this water heater will slowly dissipate whilst protecting the cylinder. The life of the
cylinder may be extended by replacing the anode.
For water supplies which are either softened or desalinated, or where the water supply may alternate between
a water tank and a reticulated public supply or another supply, or where there is a variable supply (e.g. from a
bore or public reticulated supply from various water sources), the anode must be inspected (and replaced if
there is any sign of depletion) within five (5) years of its installation.
For all water supplies, if the anode is not replaced during a major service (refer to “Major Service Every Five
Years” on page 12) then the maximum time after installation when the anode should be replaced for this water
heater is eight (8) years.
CAUTION
If the water supply has a TDS greater than 150 mg/L and a green anode has not been changed to a black
anode, or if the TDS is greater than 600 mg/L and the anode has not been changed to a blue anode, there is
the possibility the anode may become overactive and hydrogen gas could accumulate in the top of the water
heater during long periods of no use.
If, under these conditions, the water heater has not been used for two or more weeks the following procedure
should be carried out before using any electrical appliances (automatic washing machines and dishwashers)
which are connected to the hot water supply.
The hydrogen, which is highly flammable, should be vented safely by opening a hot tap and allowing the water
to flow. There should be no smoking or naked flame near the tap whilst it is turned on. Any hydrogen gas will
be dissipated. This is indicated by an unusual spurting of the water from the tap. Once the water runs freely,
any hydrogen in the system will have been released.
SATURATION INDEX
The saturation index is used as a measure of the water’s corrosive or scaling properties. The saturation index
figures stated are calculated using a water temperature of 80°C.
In a corrosive water supply, the water can attack copper parts and cause them to fail.
Where the saturation index is less than –1.0, the water is very corrosive and the Rheem warranty does not
apply to a copper sheathed heating unit or to a solar collector in an open circuit solar water heater system. A
corrosion resistant heating unit must be used for the Rheem warranty to apply to the heating unit.
In a scaling water supply calcium carbonate is deposited out of the water onto any hot metallic surface.
Where the saturation index exceeds +0.40, the water is very scaling. An expansion control valve must be fitted
on the cold water line after the non-return valve to protect and for the Rheem warranty to apply to the
temperature pressure relief valve and water heater cylinder. Solar collectors in an open circuit solar water
heater system should be covered when the water heater is not intended to be used for more than four (4)
weeks.
Where the saturation index exceeds +0.80, the Rheem warranty does not apply to a standard watts density
heating unit or to a solar collector in an open circuit solar water heater system. A low watts density heating unit
must be used for the Rheem warranty to apply to the heating unit.
Water which is scaling may be treated with a water softening device to reduce the saturation index of the water.
Refer to the Saturation Index chart on page 17.
Contact Rheem Service or their nearest Accredited Service Agent if a replacement heating unit is required.
Refer to the cold water connection detail on page 43 for the position of the expansion control valve.
16
Page 17
WATER SUPPLIES
Water Chemistry
Component
Total Dissolved Solids (TDS) > 2500 mg/L
water heater cylinder
Total Dissolved Solids (TDS) not suitable for anode type
water heater cylinder
Saturation Index (SI) < -1.0
solar collector
copper sheathed heating unit
Saturation Index (SI) > +0.4
(if an expansion control valve is not fitted)
water heater cylinder
temperature pressure relief valve
Saturation Index (SI) > +0.8
solar collector
standard watts density heating unit
very corrosivevery scalingscaling
corrosive
+0.4+0.80-1.0
no warranty applies
to a:
temperature pressure relief valve
or a water heater cylinder unless
an expansion control valve is fitted.
no warranty applies
to a:
-copper sheathed heating unit
-direct (open circuit) solar collector
SATURATION INDEX (SI)
SOLAR WATER HEATERS WITH ELECTRIC HEATING UNIT
WITHIN WARRANTY
SPECIFICATION
SATURATION INDEX
(calculated @ 80°C water temperature)
no warranty applies
to a:
-standard watts density heating unit
-direct (open circuit) solar collector
SUMMARY OF WATER CHEMISTRY ADVICE AFFECTING WARRANTY
The water heater, solar collectors and their components are not suitable for certain water chemistries. Those
chemistries are listed below. If the water heater is connected at any time to a water supply with the following
water chemistry, the Rheem warranty will not cover any resultant faults on the components listed below:
17
Page 18
SAVE A SERVICE CALL
Check the items below before making a service call. You will be charged for attending to any condition or fault
that is not related to manufacture or failure of a part.
NOT ENOUGH HOT WATER (OR NO HOT WATER)
Insufficient sunlight
Insufficient sunlight due to cloudy weather during hotter months or low solar energy contribution in colder
months may mean the in-series water heater operates more often.
Solar Control Unit
Check the power supply cord is plugged in and the power outlet switched on.
Is power available in the house? Try using another electrical appliance.
Green LED is off or red LED is flashing on Solar Monitor
If the green LED is off or the red LED is flashing on the Solar Monitor
label, there may be a problem with the solar water heater operation and
solar gain is not being achieved. This will result in the in-series gas
booster operating to provide all of the hot water required.
Switch off the electrical supply at the power outlet to the solar control
unit for a few seconds, then switch on again.
If the green LED remains off or the red LED recommences to flash, then
count the number of flashes and phone Rheem Service or their nearest
Accredited Service Agent to arrange for an inspection.
Collector(s) shaded
If trees or other objects shade the solar collector(s) or if the glass is dirty, the effectiveness of the solar
collector(s) will be greatly reduced.
Have the trees trimmed or the solar collector(s) relocated if the obstruction is permanent or clean the
collector glass.
Refer to “Collector Glass” on page 14.
Collector area is too small
For most installations, the number of solar collector(s) recommended in Rheem literature has been proven
to provide the required solar energy to meet the average family needs. However, in some circumstances,
it may be possible to install a second LCS or NPT200 solar collector.
Air in collector(s) (no solar gain)
It is possible under certain conditions, such as when the pipe work has been opened, that air may become
trapped in the solar collector(s). This will prevent the circulator from moving water around the collector
circuit. Have a plumber purge the collector circuit of air.
Are you using more hot water than you think?
Is one outlet (especially the shower) using more hot water than you think?
Very often it is not realised the amount of hot water used, particularly when showering. Carefully review
the family’s hot water usage. As you have installed an energy saving appliance, energy saving should
also be practised in the home. Adjust your water usage pattern to take advantage of maximum solar gains.
Have a plumber install a flow control valve to each shower outlet to reduce water usage.
Temperature pressure relief valve running
Is the relief valve discharging too much water?
Refer to “Temperature Pressure Relief Valve Running” on page 19.
18
Page 19
SAVE A SERVICE CALL
TEMPERATURE PRESSURE RELIEF VALVE RUNNING
Normal Operation
It is normal and desirable this valve allows a small quantity of water to escape
during the heating cycle. However, if it discharges more than a bucket full of water
in 24 hours, there may be another problem.
Continuous dribble
Try gently raising the easing lever on the relief valve for a few seconds (refer to
“Temperature Pressure Relief Valve” on page 13). This may dislodge a small
particle of foreign matter and clear the fault. Release the lever gently.
Steady flows for long period (often at night)
This may indicate the mains water pressure sometimes rises above the designed
pressure of the water heater. Ask your installing plumber to fit a pressure limiting
valve.
Warning: Never replace the relief valve with one of a higher pressure rating.
Heavy flows of hot water until the water heater is cold - then stops until
water reheats
The water heater must be switched off at the isolating switch or switchboard.
Phone Rheem Service or their nearest Accredited Service Agent to arrange for
an inspection.
EXPANSION CONTROL VALVE RUNNING
If an expansion control valve is fitted in the cold water line to the water heater (refer
to the cold water connection diagram on page 43) it may discharge a small quantity of
water instead of the temperature pressure relief valve on the water heater. The benefit
is that energy is conserved as the discharged water is cooler.
IN-SERIES WATER HEATER OPERATING TOO FREQUENTLY
You may find that the in-series water heater operates more frequently than expected. This will occur when the
solar heated water temperature is lower than the temperature setting of the in-series water heater. This may
be experienced during periods of low solar energy gain or if there has been heavy hot water usage. A Rheem
continuous flow solar gas booster will operate if the solar heated water temperature is lower than 58°C.
Fan Continues To Run After Water Heater Operation Stops
It is the normal operation of the Rheem solar gas booster for the fan to continue running after heating of the
water is finished. The fan may run for up to two minutes after the burners extinguish, to prepare for the next
ignition.
COLLECTOR GLASS
The Rheem warranty DOES NOT cover breakage of solar collector glass. Check your household insurance
policy covers collector glass breakage.
Warning: No attempt should be made to remove or replace broken collector glass.
The collector glass is not offered as a replacement part. Should the solar collector require replacement, contact
Rheem Service or their nearest Accredited Service Agent.
NOISE FROM THE SOLAR COLLECTORS
This water heater is installed with higher performing selective surface solar collector(s). During periods of
higher solar radiation or lower hot water usage and the solar storage tank is full of hot water, the water heater
may undergo Over-temperature operation (refer to “Over-temperature operation” on page 5). If this mode of
operation has occurred and the circulator has deactivated, the water in the solar collector(s) will continue to
gain heat and increase in pressure when solar radiation is still available. This increase in heat and pressure is
greater when higher performing selective surface solar collector(s) are installed compared to non-selective
surface collector(s).
When a hot tap is opened, this pressure is released and the high temperature water may turn to steam creating
a sudden and loud rumbling noise and even a rattling or banging noise of the solar collector(s) against the roof
cladding material. This results from the higher level of solar radiation and the water in the solar storage tank
being at its maximum temperature and is not caused by a fault with the solar water heater.
19
Page 20
SAVE A SERVICE CALL
GREEN LED IS NOT ILLUMINATED ON SOLAR MONITOR
Check the power outlet for the solar control unit is switched on.
If the power outlet for the solar control unit is switched on, switch off for a few seconds and then switch on
again. If the green LED remains off there may be a fault with the water heater. Phone Rheem Service or their
nearest Accredited Service Agent to arrange for an inspection.
RED LED ILLUMINATED ON SOLAR MONITOR
The illumination of the red LED does not necessarily mean there is a fault with the system. A constant glow or
rapid pulsing of the red LED indicates an operational mode of the water heater.
Constant Glow
When the water heater has entered Over-temperature operation, the water in the solar collector(s) will continue
to gain heat whilst solar energy is still available. The red LED will commence to emit a constant glow when
sufficient solar energy has been received to activate the circulator. This indicates a build-up in temperature of
the water in the solar collector(s) and does not represent a fault. The red LED will stop glowing when the
circulator has moved the excess energy from the solar collector(s) to the solar storage tank.
When six Over-temperature cycles have been completed and if solar energy is still available, the red LED will
emit a constant glow until either a reasonable quantity of hot water is drawn from a tap or the water in the solar
collector(s) looses energy and cools as the available solar energy is reduced, such as when the sun becomes
lower in the sky in the late afternoon / early evening or the sky becomes very cloudy.
Refer to “Over-temperature operation” on page 5.
Rapid Pulsing
During Normal operation the red LED will rapid pulse if the temperature difference between the hot sensor and
cold sensor is high due to excess heat in the solar collector(s). This may not represent a fault. The rapid pulsing
of the red LED will cease as the water circulates transferring the excess heat from the solar collector(s) to the
solar storage tank and the temperature difference between the hot sensor and cold sensor reduces. This
should be within four (4) to five (5) minutes, but may take up to ten (10) minutes.
If the red LED continues to emit a rapid pulse for longer than ten (10) minutes, switch off the electrical supply
at the power outlet to the solar control unit for a few seconds, then switch on again. If the red LED continues
to emit a rapid pulse for longer than ten (10) minutes, phone Rheem Service or their nearest Accredited Service
Agent to arrange for an inspection.
Series of Flashes
If the red LED is flashing this indicates there may be a fault with the water heater. The red LED may emit from
three to six flashes in each series of flashes with a 2 second interval between each series.
If the red LED emits a series of flashes, switch off the electrical supply at the power outlet to the solar control
unit for a few seconds, then switch on again. If the red LED illuminates again, then count the number of flashes
and phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
CIRCULATOR OPERATES AT NIGHT
The circulator can operate during periods of no solar energy, usually at night, under two operational modes of
the water heater. This is by design and does not indicate a fault.
Freeze Protection operation: The circulator will activate (green LED rapid pulse or 3 flashes) if the water
temperature in the solar collector(s) approaches freezing point. This occurs in very cold conditions, such as
overnight and very early in the morning before sunrise. The purpose of the Freeze Protection operation is to
prevent freezing of water in the solar collector(s) and solar pipe work. The circulator will remain on for some
minutes and until the hot sensor measures a water temperature at a safe level above freezing from the storage
tank. This process will repeat whenever the water temperature in the solar collector(s) approaches freezing
point. Refer to “Freeze Protection operation” on page 5.
Night Time Cooling operation: The circulator will activate (green LED rapid pulse or 3 flashes) if the water
heater has entered Over-temperature operation during that day. This can occur during periods of higher solar
energy or lower hot water usage. Excess solar energy gained will be dissipated through the solar collector(s)
until the water temperature in the solar storage tank decreases to a desired 60°C to 70°C. The circulator may
remain on for some time. Refer to “Night Time Cooling operation” on page 5.
20
Page 21
SAVE A SERVICE CALL
HIGHER THAN EXPECTED GAS BILLS
With the installation of your new solar hot water system, maximum energy savings can be achieved with careful
planning of hot water usage. Should you at any time feel your energy bill is higher than expected, we suggest
you check the following points:
Is the relief valve running excessively?
Refer to “Temperature Pressure Relief Valve Running” on page 19).
Is one outlet (especially the shower) using more hot water than you
think?
Refer to “Not Enough Hot Water” on page 18.
Is there a leaking hot water pipe, dripping hot water tap, etc?
Even a small leak will waste a surprising quantity of hot water and
energy. Replace faulty tap washers, and have a plumber rectify any
leaking pipe work.
Is the in-series water heater operating too frequently?
Refer to “In-Series Water Heater Operating Too Frequently” on page 19.
Has there been an increase in hot water usage?
An increase in hot water usage may result in an increase in booster operation.
Has your water heating tariff rate been increased by your energy retailer since your previous bill?
IF YOU HAVE CHECKED ALL THE FOREGOING AND STILL BELIEVE YOU NEED ASSISTANCE, PHONE
RHEEM SERVICE OR THEIR NEAREST ACCREDITED SERVICE AGENT.
21
Page 22
INSTALLATION – SYSTEM
THIS WATER HEATER IS FOR OUTDOOR INSTALLATION ONLY, IF AN IN-SERIES GAS BOOSTER IS
MOUNTED ON THE STORAGE TANK.
THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
The system is suitable for installation with 1 x CSA2612 or 1 or 2 x LCS or 1 or 2 x NPT200 solar collector(s).
The system is not suitable for installation above 400 metres altitude.
A CSA2612 or LCS or NPT200 solar collector(s) may be installed up to 90° from the optimum orientation when
installed as part of this system.
In Victoria, an approved 161 tank system with 1 x CSA2612 solar collector installed within the Regulation
Compliance Zone achieves compliance to new home legislation for water heating. Outside of the compliance
zone 2 x LCS solar collectors should be used to achieve compliance.
In areas other than Victoria, 2 x LCS solar collectors should not be installed with this system.
IMPORTANT NOTES
Working on roofs is and should always be considered a hazardous activity, particularly early in the
morning, late in the evening, when the roof is wet and during and after periods of rain.
All work must be carried out in accordance with Local, State and Federal Occupational Safety, Health and
Welfare Regulations. In particular, the requirements for safety whilst manual lifting, working at heights and
on roofs.
Installers must be competently trained in:
Height Hazard Assessment
Working at Height Procedures
Assessment / Use / Wearing of correct height safety equipment (harnesses etc.)
All other relevant safety factors specific to the installation and maintenance work to be compliant with
suitable Occupational, Health and Safety Regulations / Codes.
All relevant permits shall be obtained from the regulatory authorities before commencing work to install
the solar hot water system.
All work carried out must be performed by appropriately qualified tradespeople or be suitably supervised
for trades assistant duties.
Every care must be taken to protect and warn occupants of the building and the public from personal injury
which may occur from falling tools, roof materials, fittings or any other hazards of a general nature.
Advise the occupants of any inconvenience which may occur due to disconnection of existing water and
electrical supplies.
The connection, attachment, integration or general association of other equipment or parts which either
directly or indirectly affect the operation or performance of this equipment could void the Rheem warranty.
All packaging materials must be removed from the solar storage tank prior to its installation. This includes
the removal of the cardboard base of the carton from the underside of the solar storage tank.
22
Page 23
INSTALLATION – SYSTEM
FREEZE PROTECTION
The system has a level of freeze protection designed to guard the system against damage from freeze
conditions. The system must be installed with the full length of the solar hot and solar cold pipes insulated and
power must be available at the solar control unit to offer protection against freeze damage (refer to “Warning:
Plumber Be Aware” on page 41). Freeze conditions occur below 6°C.
Note: The Rheem warranty against freeze damage applies only to systems installed in Australia.
The system has NO WARRANTY for freeze damage when installed above 400 metres altitude or if the solar
hot and solar cold pipes are not insulated in accordance with the installation instructions or if power is not
available at the solar control unit (refer to “Terms of the Rheem Warranty” on page 58).
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with Standards AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3 (for a Class 1a or
Class 10 building) as applicable under the Plumbing Code of Australia, AS/NZS 3000, and either AS 5601
or AS/NZS 5601.1 as applicable under local regulations, and all local codes and regulatory authority
requirements.
Warning: Temperature controllers or an EZiSET kit must not be fitted to the in-series water heater as part
of a solar water heater system because water at a temperature much higher than the controller or EZiSET
setting can be delivered.
Victorian Installers
Notice to Victorian Installers from the Victorian Plumbing Industry Commission if this solar water heater is
installed in a new Class 1 dwelling in the State of Victoria. The system model number is to be recorded on the
Certificate of Compliance. It is also a requirement to provide the householder with permanent documentation
recording the system model number exactly as it is shown in the ‘VEET Product Register’ published by the
Essential Services Commission in Victoria (see www.veet.vic.gov.au). This documentation may be in the form
of an indelible label adhered to the solar storage tank, or other suitable form placed in an accessible location,
such as the meter box, for later inspection.
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable
water. Its use in an application other than this may shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or
business, then there should be back-up redundancy within the hot water system design. This should ensure
the continuity of hot water supply in the event that this water heater was to become inoperable for any reason.
We recommend you provide advice to the system owner about their needs and building back-up redundancy
into the hot water supply system.
This solar water heater is designed to be installed with a Rheem continuous flow 874 series 20 or 26 litre inseries gas booster either mounted onto the storage tank or installed remotely, or a Rheem 874 series 27 litre
in-series gas booster installed remotely.
Warning: A model in-series gas booster greater than 26 litre capacity cannot be mounted on the solar
storage tank and may only be installed remotely. The size and weight of the gas booster may cause the solar
storage tank to topple over.
The solar water heater may be installed with another suitable type of remotely installed in-series continuous
flow or storage booster. If the in-series water heater is other than a Rheem continuous flow 874 series 20 or
26 or 27 litre in-series gas booster, then the references to the in-series gas booster in this guide may not be
applicable to the installation.
For information relating to the function and operation of the in-series water heater, refer to the Owner’s Guide
and Installation Instructions supplied with the water heater.
23
Page 24
INSTALLATION – SYSTEM
Note: AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in
potable water. If this water heater is installed with an in-series continuous flow gas booster, then this
requirement of AS 3498 can be satisfied provided the booster is energised, its preset outlet temperature setting
is 70°C or higher and a remote temperature controller or an EZiSET kit is not used.
If this water heater is installed with an in-series storage booster, then this requirement of AS 3498 can be
satisfied provided the storage booster is energised and its thermostat setting is 60°C or higher.
Installing the Water Heater as a Pre-Heater
This water heater can be used as a pre-heater to a new or existing in-series booster water heater provided:
The in-series booster water heater is;
thermostatically-controlled, and
suitable to be used as an in-series booster water heater for a solar water heater.
The operating pressures of the two water heaters are compatible or reduced to the lower rated of the two
water heaters.
The in-series booster water heater has sufficient thermal capacity to supply the hot water requirements of
the application during periods of low or no solar gain.
A temperature-operated bypass valve is installed prior to the in-series water heater if this water heater
has either an over temperature energy cut-out which can be permanently disabled by high temperature
hot water or a maximum recommended inlet supply temperature less than the temperature of water which
can be supplied by this solar water heater.
It will be necessary to check with the manufacturer of the in-series water heater as to its suitability for use as
an in-series booster to this solar water heater.
24
Page 25
Model
161
Relief valve setting
1000 kPa
Expansion control valve setting *
850 kPa
Max. mains supply pressure
With expansion control valve
680 kPa
Without expansion control valve
800 kPa
Min. mains supply pressure
200 kPa
* Expansion control valve not supplied with the water heater.
INSTALLATION – SOLAR STORAGE TANK
SOLAR WATER HEATER STORAGE TANK LOCATION
The solar storage tank is suitable for either outdoor or indoor installation. If an in-series gas booster is mounted
to the solar storage tank, then the installation must be outdoors. Whether located outdoor or indoor, the solar
storage tank should be installed close to the most frequently used outlet and its position chosen with safety
and service in mind.
Consideration must also be given to the position of the solar storage tank in relation to the solar collector(s).
There are limitations on the maximum length of the solar hot and solar cold pipes between the solar storage
tank and the solar collector(s). Refer to “Solar Collector Location” on page 37, to “Pipe Lengths” on page 39
and to “Maximum height to collectors” on page 40.
Clearance must be allowed for servicing of the solar storage tank and solar
control unit. The solar storage tank must be accessible without the use of
a ladder or scaffold. Make sure the temperature pressure relief valve lever
is accessible and the front cover, thermostat, anti-freeze heating unit,
controller cover, PCB and circulator can be removed for service.
You must be able to read the information on the rating plate. If possible
leave headroom of one water heater height so the anode can be inspected
or replaced. Remember you may have to remove the entire solar storage
tank later for servicing.
The solar storage tank is to be installed at ground or floor level and must
stand vertically upright on a stable base as acceptable to local authorities.
The base of the water heater is made of corrosion resistant material, and it
may be placed directly in contact with the supporting surface. It is not
necessary to allow for free air circulation under the base of the water
heater.
Note: The water heater should not be placed in direct contact with a
concrete surface that is less than two months old and not fully cured as this
may attack the metal coating of the water heater base. A moisture barrier
should be used between the two surfaces in this instance. The barrier
should extend at least 100 mm from the water heater and may be trimmed
after two months.
Remember all local authorities have regulations about putting water heaters into roof spaces.
SAFE TRAY
Where damage to property can occur in the event of the water heater
leaking, the water heater must be installed in a safe tray. Construction,
installation and draining of a safe tray must comply with AS/NZS 3500.4
and all local codes and regulatory authority requirements. AS/NZS 3500.4
also has particular requirements when a safe tray must be installed.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below, an approved pressure limiting
valve is required and should be fitted as shown in the installation diagram (refer to the cold water connection
diagram on page 43).
25
Page 26
INSTALLATION – SOLAR STORAGE TANK
TANK WATER SUPPLY
If the water heater is supplied with water from a tank supply and a minimum water supply pressure of 200 kPa
at the water heater cannot be achieved, then a pressure pump system must be installed to allow the solar
circuit system to operate. Care must be taken to avoid air locks. The cold water line from the supply tank should
be adequately sized and fitted with a full flow gate valve or ball valve. Consideration must be given to any
minimum water supply pressure requirements of an in-series water heater.
WALL BRACKET
It is a requirement to secure the solar storage tank to the wall. Fit
the wall bracket and secure the solar storage tank to the wall prior
to the mounting of an in-series gas booster to the solar storage tank.
The top of the unit is to be secured to the wall with the wall bracket,
wall plugs and screws provided. If the wall plugs and screws
provided are not suitable for the wall construction, then other
suitable fasteners are to be used. Refer to the fastener
manufacturer’s information and recommendations for the type of
fastener to use for the wall type and load bearing requirements.
To fit the wall bracket:
Position the bracket against the wall, ensuring the bracket is
centred at the rear of the storage tank top, and mark the fixing
points on the wall where the bracket is to be secured.
Drill holes in the wall to receive the wall plugs supplied or other
suitable fasteners for the wall bracket.
Fix the wall bracket to the wall using the screws provided or other suitable fasteners.
Secure the bracket to the top of the water heater using the self-tapping screws provided.
HOT WATER DELIVERY
This water heater can deliver water at temperatures which can cause scalding.
It is necessary and we recommend that a temperature limiting device be fitted between the water heater and
the hot water outlets in any ablution and public areas such as a bathroom, ensuite or public amenities, to
reduce the risk of scalding. The installing plumber may have a legal obligation to ensure the installation of this
water heater meets the delivery water temperature requirements of AS/NZS 3500.4 so that scalding water
temperatures are not delivered to a bathroom, ensuite or other ablution or public area.
The temperature limiting device must be of a type suitable for use with a solar water heater and should have:
a specified ‘minimum temperature differential’ between the hot water inlet and the tempered water outlet
of no greater than 10°C, when used with a solar water heater and continuous flow water heater
a specified ‘maximum permitted pressure variation’ in either supply between the hot water inlet and the
cold water inlet of no less than 15% when used with a continuous flow water heater.
Refer to the specifications of the temperature limiting device.
Warning: Temperature controllers or an EZiSET kit must not be fitted to the in-series water heater as part
of a solar water heater system because water at a temperature much higher than the controller or EZiSET
setting can be delivered.
Where a temperature limiting device is installed adjacent to the in-series water heater, the cold water line to
the temperature limiting device can be branched off the cold water line either before or after the isolation valve
and pressure limiting valve to the solar storage tank, but it MUST BE before a non-return valve. If an expansion
control valve is required, it must always be installed after the non-return valve and be the last valve prior to the
solar storage tank.
Solar control unit, PN 052294 (introduced to 511161 solar storage tanks manufactured from August 2018),
contains a non-return valve at the inlet to the circulator. For a water heater fitted with this solar control unit, a
non-return valve installed on the cold water line to the tank, and after the cold water branch to a temperature
limiting device, is not required to be a dual check valve type.
26
Page 27
INSTALLATION – SOLAR STORAGE TANK
If a combination isolation valve and non-return valve (duo or trio valve) is installed on the cold water line to the
solar water heater and the cold water line to the temperature limiting device branches off after this valve, then
a second non-return valve must be installed between the cold water branch and the solar storage tank.
If a pressure limiting valve is installed on the cold water line to the solar water heater and the cold water line
to a temperature limiting device branches off before this valve or from another cold water line in the premises,
then a pressure limiting valve of an equal pressure setting may be required prior to the temperature limiting
device.
Integrated In-series Gas Booster as part of an Open Circuit Solar Loline Water Heater Installation
Two Temperature Zones Using a Temperature Limiting Device
Remote In-series Gas Booster as part of an Open Circuit Solar Loline Water Heater Installation
Two Temperature Zones Using a Temperature Limiting Device
27
Page 28
INSTALLATION – SOLAR STORAGE TANK
CIRCULATED HOT WATER FLOW AND RETURN SYSTEM
The solar storage tank of a solar water heater should not be installed as part of a circulated hot water flow and
return system in a building. The benefits of solar gain will be significantly reduced.
If a circulated flow and return system is required, it is necessary to connect the circulation return line to the inseries booster and not to the solar storage tank.
A Rheem 874 model in-series gas booster can be installed as part of a circulated hot water flow and return
system in a building. If the in-series gas booster is mounted on the solar storage tank, then a suitable Tee
must be installed at the inlet to the gas booster, after the flexible hose from the solar hot outlet on the tank.
The circulated return line is to be connected to the Tee.
Refer to the Circulated Hot Water Flow and Return System diagram on page 29.
If the in-series booster is a continuous flow water heater, then the circulator must be:
sized and set to provide a minimum flow rate of 3.0 L/min through the circulated hot water flow and return
system, and
either thermostatically and / or timer controlled.
The circulator must not be set to operate continuously, i.e. 24 hours per day.
Temperature Settings
AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in
potable water.
If the in-series water heater is a continuous flow water heater, to meet this requirement of AS 3498, its
preset outlet temperature setting must be set to 70°C or higher.
If the in-series water heater is a storage water heater, to meet this requirement of AS 3498, its thermostat
must always be set to at least 60°C.
Water should not be circulated from a water heater with a temperature setting of less than 60°C.
The return water temperature to the water heater must not be less than 55°C.
If the water temperature decreases by more than 5°C due to heat loss from the ring main, the preset outlet
temperature setting or thermostat setting of the in-series water heater must be set to above 60°C to ensure
the return water temperature is not less than 55°C.
Temperature Limiting Device
A temperature limiting device cannot be installed in circulated hot water flow and return pipe work. The
tempered water supplied from the temperature limiting device cannot be circulated.
Where a circulated hot water flow and return system is required in a building, a temperature limiting device
can only be installed on a dead leg, branching off the circulated hot water flow and return pipe.
If circulated tempered water were to be returned back to the booster water heater, then when the hot taps are
closed no water will be supplied to the cold water inlet of the temperature limiting device whilst hot water will
continue to be supplied to the hot water inlet of the temperature limiting device.
This condition may result in either water at a temperature exceeding the requirements of AS/NZS 3500.4 being
delivered to the hot water outlets in the ablution areas, or the device closing completely and not delivering
water at all, or the device failing. Under this condition, the operation and performance of the device cannot be
guaranteed.
28
Page 29
INSTALLATION – SOLAR STORAGE TANK
Total Dissolved Solids
Anode colour code
0 – 40 mg/L
Green
40 – 150 mg/L
Green or Black
150 – 400 mg/L
Black
400 – 600 mg/L
Black or Blue
600 – 2500 mg/L
Blue
2500 mg/L +
Blue (no cylinder warranty)
Remote In-series Gas Booster as part of an Open Circuit Solar Loline Water Heater Installation
Circulated Hot Water Flow and Return System
REDUCING HEAT LOSSES
The cold water line to and the hot water line from the water heater must be insulated in accordance with the
requirements of AS/NZS 3500.4. The insulation must be weatherproof and UV resistant if exposed.
The full length of the solar hot and solar cold pipes between the solar storage tank and the solar collector(s)
MUST BE insulated. Refer to “Warning: Plumber Be Aware” on page 41.
ANODE
The vitreous enamel lined cylinder of the water heater is only covered by the Rheem warranty when the total
dissolved solids (TDS) content in the water is less than 2500 mg/L and when the correct colour coded anode
is used. If an incorrect colour coded anode is used in the water heater, any resultant faults will not be covered
by the Rheem warranty. In addition, the use of an incorrect colour coded anode may shorten the life of the
water heater cylinder.
The correct colour coded anode for the water supply being used must be selected and fitted to the water heater
for the Rheem warranty to apply to the water heater cylinder (refer to “Water Supplies” on page 15 and the
Anode Selection chart on page 15). The black anode is typically fitted as standard.
If the water supply has a TDS greater than 150 mg/L and a green anode has not been changed to a black
anode, or if the TDS is greater than 600 mg/L and the anode has not been changed to a blue anode, there is
the possibility the anode may become overactive and hydrogen gas could accumulate in the top of the water
heater during long periods of no use. In areas where this is likely to occur, the installer should instruct the
householder on how to dissipate the gas safely (refer to “Caution” on page 16).
SADDLING - PIPE WORK
To prevent damage to the cylinder when attaching pipe clips or saddles to the water heater jacket, we
recommend the use of self-drilling screws with a maximum length of 13 mm. Should pre drilling be required,
extreme caution must be observed when penetrating the jacket of the water heater.
Note: If the cylinder is damaged as a result of attaching pipe clips or saddles to the jacket, any resultant
faults will not be covered by the Rheem warranty.
29
Page 30
INSTALLATION – SOLAR STORAGE TANK
8748 series gas booster mounting
ANTI-FREEZE HEATING UNIT
Additional freeze protection is provided by the anti-freeze heating unit. The anti-freeze heating unit is for
heating the water at the bottom of the solar storage tank at times of very low cold water temperature. The antifreeze heating unit provides additional energy to the water to assist in the prevention of freezing in the solar
pipe work and solar collector(s). The anti-freeze heating unit is controlled by the solar controller and will only
be energised when the water temperature is very low and the circulator activates in the frost mode. The water
temperature is monitored by the cold sensor.
If the water temperature at the bottom of the solar storage tank is very low when the circulator activates in
Freeze Protection operation mode, the anti-freeze heating unit will be energised and will heat the water by a
few degrees. The anti-freeze heating unit will be de-energised when either the frost mode is shut down or the
water temperature has risen by a few degrees.
The anti-freeze heating unit is supplied with power from the solar control unit. The power outlet to the solar
control unit must be switched on for the anti-freeze heating unit to operate and offer additional freeze
protection.
MOUNTING THE GAS BOOSTER
Fit the wall bracket and secure the solar storage tank to the wall prior to the mounting of an in-series gas
booster to the solar storage tank. Refer to “Wall Bracket” on page 26.
It is recommended to install the fittings associated with the solar control unit prior to mounting the in-series gas
booster. Refer to “Installation – Solar Control Unit” on page 34. The service 3-way valve assembly must be
fitted prior to mounting the in-series gas booster. Refer to step 12 on page 36.
Two brackets are supplied to mount the gas booster to the solar storage tank. The top bracket is secured to
the tank, then the gas booster is hung from this bracket, prior to locating the lower bracket and securing it to
the tank to hold the gas booster in position.
To fit the top bracket:
Locate one of the mounting brackets horizontally, with the two prongs pointing upwards, and the two
holes of the bracket over the dimples marked on the side of the solar storage tank.
Secure the mounting bracket using two of the
screws supplied, with the screws penetrating
through the dimples.
To mount the 8748 series gas booster:
Hang the solar gas booster water heater onto
the mounting bracket, by placing the two
horizontal slots in the top hanging bracket
over the two prongs.
To fit the bottom bracket:
Position the second mounting bracket behind
the bottom hanging bracket of the solar gas
booster water heater, ensuring:
The two prongs on the bracket are
pointing downwards, and
The prongs are inserted through the two
horizontal slots of the solar gas booster
hanging bracket.
The bracket is to be fully engaged, seating firmly onto the bottom of the slots.
Check the bracket is fully engaged and firmly seated onto the bottom of the slots of the gas booster
hanging bracket prior to securing the mounting.
This is to ensure there is no movement of the solar gas booster after the installation is complete.
Secure the mounting bracket using the remaining two screws supplied.
30
Page 31
DIMENSIONS AND TECHNICAL DATA
Model
Capacity
Tank Mass (kg)
(without booster)
Tank Mass (kg)
(with booster)
Empty
Full
Empty
Full
511 161
165 litres
62
227
81
246
INSTALLATION – SOLAR STORAGE TANK
storage tank only (remote boost) storage tank with integrated boost
Valve service 3-way solar assembly, consisting of:
1 x service valve 3-way solar
2 x nut compression ½”
2 x olive compression copper ½”
1
331658
Union body R 3/4 M x DN15 olive
1
331655
Nut compression DN15
1
331656
Olive compression copper DN15
1
070897
Pipe cold 160L loline preformed tube ½” x 350 mm long
1
180073
Insulation pipe 13 mm ID x 13 mm wall 280 mm long
1
090281
Insulation pipe 35 mm ID x 80 mm long slit
2
080228
Cable tie black 250 – 300 mm x 4.8 mm
6
088065
Fitting union male ½” C x ½” C Rye 4930, consisting of:
1 x hex nipple brass ½” x ½”
2 x nut compression ½”
2 x olive compression copper ½”
1
Part No
Supplied for Bracket Connection (Tank to Wall)
106117
Wall bracket – L shape
1
080229
Wall plug plastic red 25 mm long (6 mm drill bit required)
2
080117
Screw button head 8G x 15 x 25
2
088031
Screw phillips pan head no 8 x 13
2
Part No
Supplied for Mounting In-series Gas Booster
140129
Mounting bracket gas booster
2
080031
Screw phillips pan head no 8 x 13
4
Part No
Supplied for Connection to In-series Gas Booster
088172
Braided hose insulated 750 mm x 12 mm diam, consisting of,
1 x 088219 hose 750 mm x 12 mm diam, 1/2” female cone,
1 x 090280 insulation pipe 25 mm ID
1
088143
Fitting hex nipple brass ¾” x ½”
1
088150
Elbow brass ½”F x ½” M Rye 2503
1
088161
Adaptor reducing brass ¾” F x ½” M
1
Part No
Supplied for Solar Storage Tank
220641
Valve TPR ½” x 1000 kPa HTE523/507
1
INSTALLATION – SOLAR CONTROL UNIT
The solar control unit is supplied mounted on the side of the solar storage tank. A kit (PN 299292) containing
components to enable the connection of the solar pipe work to the tank is supplied with the tank. Solar control
unit, PN 052294 (introduced to 511161 solar storage tanks manufactured from August 2018), contains a nonreturn valve at the inlet to the circulator.
The solar control unit, supplied with a 1.8 metre power cord, requires a 240 V 50 Hz general purpose outlet
(GPO) located within 1.2 metres of its installation. The GPO must have a continuous power supply. The GPO
is required to be weatherproof if installed outdoors (refer to “Connections – Electrical” on page 47).
Note: The solar control unit automatically controls the flow rate through the collector circuit. This is achieved
via the hot and cold sensors and differential controller programming providing control over the operation of the
circulator. There is no provision for nor is adjustment to the solar control unit required.
34
Page 35
INSTALLATION – SOLAR CONTROL UNIT
Notes:
All pipe work must be purged and cleared of foreign matter before connection and before attempting to
operate the water heater.
It is important to connect the solar hot and solar cold pipes to the correct connections at the solar collector
and at the solar storage tank.
Connect the solar hot and solar cold pipes to the solar storage tank using only the fittings supplied.
All olive compression fittings must use brass or copper olives.
Use an approved thread sealant such as Teflon tape on all threaded joints. Conetite or O-ring fittings do
not require a thread sealant.
Note: The solar control unit automatically controls the flow rate through the collector circuit. This is achieved
via the hot and cold sensors and differential controller programming providing control over the operation of the
circulator. There is no provision for nor is adjustment to the solar control unit required.
SUPPLIED WITH 511161 SOLAR STORAGE TANK
1. Hex nipple ½” X ½”
2. Union R 3/4 M x DN15 olive
3. Preformed pipe DN15
4. Compression nut
5. Olive
6. Solar control unit
7. Screws
8. Cold sensor and clip
9. Service 3-way valve assembly
10. Insulation 280 mm long x 13 mm ID
11. Insulation 80 mm long x 35 mm ID
12. Cable tie
35
Page 36
INSTALLATION – SOLAR CONTROL UNIT
SOLAR STORAGE TANK WITH RAISED SOLAR HOT INLET
Numbers in parentheses refer to items on diagram on page 35.
To connect the solar cold pipe to the solar control unit on a solar Loline storage tank:
1. Fit the union R 3/4 M x DN15 (2) to the solar cold water outlet of the solar storage tank.
2. Undo the compression nut and olive from the underside of the solar control unit (6) and put aside.
3. Loosen, but do not remove, the four screws (7) which attach the solar control unit (6) to the solar storage
tank and slide the control unit upwards to the stops in the bracket slots.
4. Place a compression nut (4) and olive (5) over each end of the DN15 preformed pipe (3), pre-insulated
with the 280 mm long x 13 mm ID insulation (10), and locate the pipe in the union (2) at the solar cold
outlet and in the union at the inlet of the circulator on the underside of the solar control unit (6), ensuring
the straight end is orientated upwards.
5. Return the solar control unit (6) to its original position, ensuring the DN15 preformed pipe (3) is well seated
in the union (2) and in the inlet of the circulator. Connect the preformed pipe using the compression nuts (5)
and olives (6) provided.
6. Tighten the four screws (7) attaching the solar control unit (6) to the solar storage tank.
7. Disassemble the fitting union, and place a compression nut (4) and olive (5) over the end of the copper
pipe protruding from the side of the solar control unit (6), and over the end of the solar cold pipe (to the
collector).
8. Connect the solar cold pipe (to the collector) to the pipe from the solar control unit (6) using the nipple (1)
from the fitting union and the compression nuts (4) and olives (5).
9. Clip the cold sensor (10) over the end of the preformed pipe adjacent to the union (2) at the solar cold
outlet connection.
10. Insulate the lower end of the preformed pipe (3), cold sensor and union (2), with an 80 mm long x 35 mm ID
piece of insulation (11) and secure with two cable ties (12).
11. Connect the hot sensor lead (from the solar collector installation) to the hot sensor cable connector at the
side of the solar control unit (6).
Note: Ensure the hot sensor lead is not in direct contact with the solar pipe work at any point of the
collector circuit, otherwise damage to the sensor lead can occur due to the high temperatures which can
be experienced within the pipe work. Damage to the hot sensor lead can result in solar gain not being
achieved and the freeze protection system being rendered inoperative. The hot sensor lead may be cable
tied to the outside of the insulation on the solar pipe work.
To connect the solar hot pipe to the solar storage tank:
12. Fit the service 3-way valve assembly (9) to the solar hot water inlet of the solar storage tank. Ensure the
service valve inlet is pointing vertically upwards.
13. Connect the solar hot pipe (from the collector) to the inlet of the service valve assembly (9) using the
compression nut (4) and olive (5) provided with the valve.
14. Connect a DN15 copper drain line to the service valve to carry the discharge clear of the water heater and
solar control unit (refer to “Service Valve Drain” on page 46), using the compression nut (4) and olive (5)
provided with the valve.
15. Insulate the drain line from the service valve (9) with closed cell type insulation or similar (minimum
thickness 13 mm). The insulation must be weatherproof and UV resistant if exposed.
16. After the collector circuit has been purged of air (refer to “Bleeding The Solar Collector(s)” on page 50,
insulate the service valve assembly (9), from the solar tank to the drain line of the service valve, with an
80 mm long x 35 mm ID piece of insulation (11) and secure with two cable ties (12).
36
Page 37
INSTALLATION – SOLAR COLLECTOR(S)
SOLAR COLLECTOR LOCATION
Consideration must be given to the position of the solar collector(s) in relation to the solar storage tank. There
are limitations on the maximum length of the solar hot and solar cold pipes between the solar storage tank and
the solar collector(s). Refer to “Solar Storage Tank Location” on page 25, to “Pipe Lengths” on page 39 and to
“Maximum height to collectors” on page 40.
The solar collector(s) must be installed in a shade free position. The surrounds should be checked for higher
buildings or trees which may cause shade at other times of the year and for small trees which may grow and
shade the solar collector(s) in the future.
The installation must comply with the requirements of either AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3
(for a Class 1a or Class 10 building) as applicable under the Plumbing Code of Australia, and all local codes
and regulatory authority requirements. Refer to the installation instructions supplied with the collector kit for
details on the installation of the solar collector(s).
ROOF STRENGTH
The installer must ensure the structural integrity of the building is not compromised by the solar water heater
installation and the roof structure is suitable to carry the full weight of the solar collector(s) and frame (if one is
installed). If in any doubt of the construction or the condition of the roof, the roof should be suitably
strengthened. Consult a structural engineer. Each solar collector and its fittings weigh approximately
36 kg (LCS – 2.0 m2 collector) or 41 kg (NPT200 – 2.0 m2 collector) or 55 kg (CSA2612 – 2.6 m2 collector)
when full of water.
ROOF AREA FOR INSTALLATION
Roof area required for 2.0m2 solar collectors:
2 solar collectors – 2.3 m wide x 2.0 m deep Weight (full) 72 to 82 kg approx.
1 solar collector – 1.2 m wide x 2.0 m deep Weight (full) 36 to 41 kg approx.
Roof area required for 2.6m2 solar collectors:
1 solar collector – 1.4 m wide x 2.3 m deep. Weight (full) 55 kg approx.
In addition to this area, a minimum one (1) metre clearance is recommended on all four sides of the solar
collectors for safe service access.
Maximum Number of Collectors
The maximum number of solar collectors as part of an open circuit system is:
Selective Surface LCS 2.0m2 Collectors
161 tank – 2 x collectors (Victoria only if installed greater than 50° off solar north)
– 1 x collector (other areas)
Non-Selective Surface NPT200 2.0m2 Collectors
161 tank – 2 x collectors
Selective Surface CSA2612 2.6m2 Collectors
161 tank – 1 x collector
ORIENTATION OF SOLAR COLLECTORS
The optimum orientation of solar collectors, to maximise system performance, is facing true north (in the
southern hemisphere) or true south (in the northern hemisphere).
However, the optimum orientation of solar collectors is not always practical or achievable. If it is not possible
to achieve the optimum orientation, then it is recommended to install the solar collectors as close to the
optimum orientation as possible.
37
Page 38
INSTALLATION – SOLAR COLLECTOR(S)
A CSA2612 or LCS or NPT200 solar collector(s) may be installed up to 90° from the optimum orientation when
installed as part of this system, however solar system performance will be reduced. The system owner needs
to be made aware of, understand and accept that solar system performance will be reduced and increased
boosting may be required to meet their hot water requirements.
The total solar radiation received by solar collectors will reduce by approximately 4% to 5% when facing 45°
from the optimum orientation and approximately 10% to 15% when facing 90° from the optimum orientation.
Where the collectors can be installed at a similar angle either east or west of the optimal orientation, then the
hot water load and usage pattern may need to be considered. If the majority of hot water usage is before
2:00 PM favour an easterly bias. If the majority of hot water usage is after 2:00 PM favour a westerly bias.
Note: Always check for true north or true south using a compass or other suitable device.
In Victoria, an approved 511161 tank system with 1 x CSA2612 solar collector installed within the Regulation
Compliance Zone achieves compliance to new home legislation for water heating. Outside of the compliance
zone 2 x LCS solar collectors should be used to achieve compliance.
In areas other than Victoria, 2 x LCS solar collectors should not be installed with this system.
INCLINATION OF SOLAR COLLECTOR
To help maximise system performance, the solar collector should be installed with an optimum inclination. This
is equal to 90% to 100% of the local latitude angle when the collector is oriented within 60° of true north or true
south, and generally between 10° and 20° when the collector is oriented between 60° and 90° from the
optimum orientation.
Generally, improved summer performance is obtained from an angle of inclination less than the optimum angle
and improved winter performance is obtained by an angle of inclination greater than the optimum angle. If the
angle of inclination varies by 20° from the optimum angle, the solar collector will receive about 10% less total
annual solar radiation. The latitude of some Australian cities are listed on page 39.
AS/NZS 3500.4 states that solar collectors shall be installed at an angle within 20° of the local latitude angle.
However, the optimum inclination of the solar collector is not always practical or achievable. The solar collector
may be installed at the roof angle for simplicity of installation and appearance, but must never be flat for a
pumped solar water heater installation. Although the solar collectors can be installed with an inclination of less
than 10° from the horizontal, this is not advised.
The risks include:
the collector glass not 'self-cleaning', leading to dirty collector glass reducing solar performance, and
condensation on the underside of the glass taking longer to clear, and
condensation droplets falling onto the absorber plate potentially causing discolouration.
The collector kit is suitable for installations with an inclination of up to 45°.
A Variable Pitch frame can be installed to increase the angle of inclination of the collector used in a pumped
solar water heater installation. This type of frame should be used if the roof pitch either varies by more than
20° from the optimum angle or if the roof pitch is less than 10°.
The use of a Variable Pitch frame should be discussed with the system owner. If this option is neither possible
nor acceptable to the system owner, it may be possible for an additional solar collector to be installed or to
install selective surface collectors in lieu of non-selective surface collectors to help make up for the reduction
in solar performance compared to the optimum inclination. Each option should be discussed with the system
owner.
If these options are neither possible nor acceptable to the system owner, then the system owner needs to be
made aware of, understand and accept that solar system performance will be reduced and increased boosting
may be required to meet their hot water requirements.
38
Page 39
INSTALLATION – SOLAR COLLECTOR(S)
Adelaide
35°S
Cairns
17°S
Hobart
42°S
Port Hedland
20°S
Alice Springs
24°S
Canberra
35°S
Mildura
34°S
Rockhampton
24°S
Brisbane
27°S
Darwin
12°S
Melbourne
38°S
Sydney
34°S
Broken Hill
31°S
Geraldton
28°S
Perth
32°S
Townsville
19°S
Maximum recommended total combined pipe length (solar hot + solar cold)
and number of 90° bends
Pipe Size
1 or 2 Collector(s)
Pipe Length
90° Bends
DN15
40 metres
20
DN20
NR
NR
For each additional 90° bend, reduce the maximum total pipe length by 0.5 metres.
For each additional metre of pipe length, reduce the number of 90° bends by two.
Note: One 90° elbow is equal to two 90° bends. NR – not recommended.
CYCLONIC OR HIGH WIND AREAS
For an installation of solar collectors on a pitched roof in a cyclonic or high wind area, a suitable With Pitch
frame (available for 2.0m2 collector only) is required. Contact Rheem or your local Rheem Solar Water Heater
Distributor for details.
The installation of the solar collectors on a suitable frame, subject to the frame’s design criteria not being
exceeded:
may be suitable for installation in geographic locations up to and within Wind Region D (With-Pitch frame
for 2.0m2 collectors only) or up to and within Wind Region C (Variable-Pitch frame), as defined in Volume 2
of the National Construction Code, AS 4055 and AS/NZS 1170.2, or equivalent locations, and
may provide an acceptable method of installation where it is necessary to satisfy the requirements of the
National Construction Code for high wind areas, or equivalent requirements.
LATITUDE OF SOME AUSTRALIAN CITIES
PIPE LENGTHS
The solar hot and solar cold pipes between the solar storage tank and the solar collectors shall:
be of bendable grade or hard drawn copper tube, or annealed copper tube.
Annealed copper tubing shall not be joined using olive compression fittings.
Note: When annealed copper pipe is used in the collector circuit, then a suitable length of bendable grade
or hard drawn copper pipe is to be brazed to the end of the collector circuit pipe work at the connection
points where a copper or brass olive and compression nut is used. This requirement is to ensure there is
minimum risk of pipe movement where the copper or brass olive and compression nut seal the connection
at the fitting, so leaks will not occur.
have a continuous fall from the solar collectors to the solar storage tank. Horizontal runs of pipe work are
acceptable and may be installed as part of an open circuit system.
Care must be taken to ensure the pipe work maintains a continuous fall or horizontal runs over the life of
the installation. Pipe work should be fixed at regular intervals to assist in maintaining this requirement.
Particular care is to be taken when annealed copper tube is used to ensure this requirement is met.
not exceed the maximum recommended combined lengths as specified in the table.
It is essential for these requirements to be followed for the system to operate correctly and efficiently. Solar
pipe work which is oversized, or is too long, or does not have a continuous fall can result in a reduction in
performance or the system not operating effectively.
39
Page 40
INSTALLATION – SOLAR COLLECTOR(S)
=
Notes:
It is important to connect the solar hot and solar cold pipes to the correct connections at the solar collector
and at the solar storage tank.
The solar cold pipe connects to the bottom of the solar collector array and may connect to either the left
or right hand side. The solar hot pipe must connect to the top of the solar collector array diagonally
opposite to the solar cold pipe connection. The solar hot outlet and hot sensor connection is to be the
highest point of the system.
The hot sensor connection is at the solar hot outlet where the solar hot pipe connects to the solar collector
for this open circuit system.
Refer to “Warning: Plumber – Be Aware” on page 41.
Maximum height to collector(s)
The maximum height of a solar Loline installation, from the solar controller (circulator) to the top of the solar
collector(s), is determined by the maximum recommended total pipe length for the system and the water supply
pressure. Refer to “Pipe Lengths” on page 39.
The maximum recommended total pipe length of the collector circuit should not be exceeded and a minimum
water supply pressure of 200 kPa should be available at the inlet to the system, otherwise the system
performance may be reduced or the collector circuit may not be purged of air during the commissioning of the
system.
Open Circuit System – Pipe Work Installation Requirements
40
Page 41
INSTALLATION – SOLAR COLLECTOR(S)
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the solar collector(s) MUST BE
of copper. All compression fittings must use brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating application and capable
of withstanding the temperature of the water generated by the solar collector(s) under stagnation
conditions
The specification of the chosen insulation material should be checked with the insulation
manufacturer prior to installation as different materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to comply with the
requirements of AS/NZS 3500.4
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar pipe work
be fitted up to and cover the connections on both the solar storage tank and the solar collector(s).
Note: Failure to observe these requirements also increases the risk of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or where it may be in contact
with a metal roof, may lead to freeze damage. The system has NO WARRANTY for freeze damage if
the solar hot and solar cold pipes are not insulated in accordance with the installation instructions.
The insulation is essential to assist in providing freeze protection, will offer protection to a metal roof
against corrosion due to water running off the copper pipes, assist in avoiding accidental contact with
the solar pipe work as very high temperature water can flow from the solar collectors to the solar
storage tank, and also reduce pipe heat losses.
The insulated copper pipe work:
should be fixed at suitable locations to prevent or reduce the possibility of noise from water
hammer and vibration from occurring
is not to be placed or installed in contact with plastic pipe work.
Likewise, plastic pipe work is not to be placed or installed in contact with the insulated copper
pipe work after the collector circuit is installed.
Plastic pipe MUST NOT be used, as it will not withstand the temperature and pressure of the water
generated by the solar collector(s) under stagnation conditions. Extremely high water temperatures of
up to 150°C for non-selective surface collector(s) and greater than 200°C for selective surface
collector(s) and high water pressures exceeding 1000 kPa can be generated under these conditions.
Plastic pipe cannot withstand these temperatures and pressures and MUST NOT be used. Failure of
plastic pipe can lead to the release of high temperature water and cause severe water damage and
flooding.
The solar hot outlet and hot sensor connection is to be the highest point of the system. The highest
point of the solar hot and solar cold pipes must be where they connect to the solar collector(s), to
avoid the possibility of air locks occurring in the system. There MUST BE a continuous fall in the
pipe work from the solar collector(s) to the solar storage tank. Horizontal runs of pipe work are
acceptable and may be installed as part of an open circuit system.
A non-return valve MUST BE installed on the cold water line to the solar storage tank AFTER the cold
water branch to a temperature limiting device.
The pressure applied to the collector circuit and solar collector(s) during a pressure test of an open
circuit system MUST NOT exceed 1000 kPa, otherwise damage may result. Refer to “Pressure
Testing” on page 42.
41
Page 42
INSTALLATION – SOLAR COLLECTOR(S)
Pressure Testing
The solar water heater, including the collector circuit, is to be isolated during the testing and commissioning of
the heated water reticulation system in a building in accordance with Clause 9.3 (a) of AS/NZS 3500.4:2015
and 2018 or Clause 3.34.2 (a) of AS/NZS 3500.5:2012 for a Class 1a or Class 10 building as applicable under
the Plumbing Code of Australia. The collector circuit includes the solar hot and solar cold pipes and solar
collectors.
It may be necessary to pressure test the collector circuit to comply with codes and regulatory authority
requirements or on other occasions where the solar collector(s) and solar hot and solar cold pipes are installed
prior to the solar storage tank, such as on a building site.
Collector Circuit
Warning: The pressure applied to the collector circuit during a pressure test of an open circuit system
MUST NOT exceed 1000 kPa where a CSA2612 or LCS or NPT200 solar collector(s) is installed, otherwise
damage may result.
Open Circuit System
If the solar collector(s), solar pipe work and solar storage tank are installed and commissioned together, then
the flooding of the collector circuit with water under mains pressure for an open circuit system and checking
the pipe work for leaks during the commissioning procedure can be substituted for the pressure testing of the
collector circuit.
42
Page 43
OR
CONNECTIONS – PLUMBING
All plumbing work must be carried out by a qualified person and in accordance with the requirements of either
AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as applicable under
the Plumbing Code of Australia, and all local codes and regulatory authority requirements.
Warning: Certain types of plastic pipe, such as polybutylene pipe, are not suitable to be used as a hot
water pipe between:
this water heater and a temperature limiting device, and
this water heater and a hot water outlet if a temperature limiting device is not installed.
This water heater can produce water at a temperature and pressure which can exceed the performance limits
of these types of pipe. This may result in pipe failure leading to severe water damage to the property. If one of
these types of plastic pipe is used as a hot water pipe in the property, then a temperature limiting device must
be installed between the water heater and this pipe work.
Note: The solar storage tank of a solar water heater should not be installed as part of a circulated hot water
flow and return system in a building. The benefits of solar gain will be significantly reduced. If a circulated flow
and return system is required, refer to “Circulated Hot Water Flow and Return System” on page 28.
CONNECTION SIZES
Hot water connection: Rp 3/4.
Cold water connection: Rp 3/4.
Solar hot (from collector) connection:
DN15 compression fitting to Service valve – (solar hot inlet to tank: Rp 3/4).
Solar cold (to collector) connection:
DN15 compression fitting to pipe at circulator outlet – (solar cold outlet from tank: Rp 3/4).
Relief valve connection: Rp 1/2.
Service valve drain connection: DN15 compression fitting.
WATER INLET AND OUTLET
All pipe work must be cleared of foreign matter before connection and purged before attempting to operate the
water heater. All olive compression fittings must use brass or copper olives. Use an approved thread sealant
such as Teflon tape on all sealing threads. Conetite or O-ring fittings do not require a thread sealant.
An isolation valve and non-return valve must be installed on the cold water line to the water heater. An
acceptable arrangement is shown in the diagram on page 43. Refer also to “Hot Water Delivery” on page 26
and to “Mains Water Supply” on page 25. The plumbing arrangements for the cold water inlet and solar hot
and solar cold pipes are shown on page 35.
43
Page 44
CONNECTIONS – PLUMBING
INSULATED
HOSE
3
4
1
WALL
BRACKET
2
A disconnection union must always be provided at the cold water inlet, solar
cold water outlet, solar hot water inlet and hot water outlet on the water
heater to allow for disconnection of the water heater.
This water heater has either a plastic dip tube or fitting liner in the inlet and
outlet fittings (see diagram). These must be in place for the water heater to
function properly. Do not remove or damage them by using heat nearby.
They will be pushed into the correct position as the fitting is screwed in.
This water heater is intended to be permanently connected to the water mains and not connected by a hoseset. A braided flexible hose or semi-flexible connector may be used for connection to the water heater, where
permitted by AS/NZS 3500.4.
IN-SERIES BOOSTER – INTEGRATED
A braided hose, 750 mm long 12 mm diameter, is supplied for connecting between the solar storage tank and
a Rheem 8748 series 20 litre or 26 litre model in-series gas booster mounted onto the storage tank.
It is recommended to install the fittings associated with the solar control unit prior to mounting the in-series gas
booster. Refer to “Installation – Solar Control Unit” on page 34. The service 3-way valve assembly must be
fitted prior to mounting the in-series gas booster. Refer to step 12 on page 36.
Fit the wall bracket and secure the solar storage tank to the wall prior to the mounting of an in-series gas
booster to the solar storage tank. Refer to “Wall Bracket” on page 26. To integrate the in-series gas booster
onto the solar storage tank, refer to “Mounting the Gas Booster” on page 30.
Warning: A model in-series gas booster greater than 26 litre capacity cannot be mounted on the solar
storage tank and may only be installed remotely. The size and weight of the gas booster may cause the solar
storage tank to topple over.
Notes
Numbers in parentheses refer to items on diagram on
page 44.
The braided hose has compression fitting connections.
Use thread sealing tape or an approved thread sealant
To connect the braided hose to the solar storage tank and
in-series gas booster:
Fit the ¾” x ½” hex nipple (1) to the hot water outlet of
Fit the ½”x ½” elbow (2) to the hex nipple (1),
Fit the ¾” x ½” reducing adaptor (3) to the water inlet of
on all fittings.
the solar storage tank.
orientating the elbow downwards.
the in-series gas booster.
Connect one end of the insulated braided hose (4) to
the elbow (2) at the hot water outlet of the solar storage
tank and the other end to the adaptor (3) at the water
inlet to the in-series gas booster.
SUPPLIED WITH 511161 SOLAR STORAGE TANK
1. Hex nipple ¾” x ½”
2. Elbow ½” x ½”
3. Adaptor – ¾” x ½”
4. Insulated braided hose
44
Page 45
CONNECTIONS – PLUMBING
IN-SERIES BOOSTER – REMOTE LOCATION
The in-series booster water heater may be installed remotely from the solar storage tank.
If the in-series water heater is a continuous flow gas water heater, this may be located adjacent to the right
hand side of the solar storage tank and subject to the location of the flue terminal complying with the
requirements of AS 5601 or AS/NZS 5601.1, connected using the fittings and braided hose supplied and
following the procedure outlined under “In-Series Booster – Integrated” on page 44. A full flow isolation valve
need not be installed.
Otherwise, the pipe work between the solar storage tank and an in-series water heater has a minimum
recommended pipe size of DN20, MUST BE of copper and be fully insulated with a closed cell type insulation
or equivalent in accordance with the requirements of AS/NZS 3500.4. In Victoria, insulation with a minimum
R-value of 0.6 (usually 25 mm thick) must be used to achieve compliance to local regulatory requirements.
The insulation must be weatherproof and UV resistant if exposed. The insulation must be fitted up to the
connections on both the solar storage tank and the in-series water heater. A full flow isolation valve must be
installed on the water line to the in-series water heater.
PIPE SIZES
To achieve true mains pressure operation, the cold water line to the water heater should be the same size or
bigger than the hot water line from the water heater.
The pipe sizing for hot water supply systems should be carried out by persons competent to do so, choosing
the most suitable pipe size for each individual application. Reference to the technical specifications of the water
heater and local regulatory authority requirements must be made.
TEMPERATURE PRESSURE RELIEF VALVE
The temperature pressure relief valve is supplied in the plastic bag with the solar control unit ground kit
components. The temperature pressure relief valve must be fitted before the water heater is operated. Before
fitting the relief valve, make sure the probe has not been bent. Seal the thread with an approved thread sealant
such as Teflon tape - never hemp. Make sure the tape does not hang over the end of the thread.
Screw the valve into the opening labelled “Relief Valve”(refer to the installation diagram on page 33) leaving
the valve outlet pointing downwards. Do not use a wrench on the valve body - use the spanner flats provided.
A copper drain line must be fitted to the temperature pressure relief valve (refer to "Relief Valve Drain" on
page 46).
The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the
insulation installed so as not to impede the operation of the valve. The insulation must be weatherproof and
UV resistant if exposed.
EXPANSION CONTROL VALVE
Local regulations may make it mandatory to install an expansion control valve (ECV) in the cold water line to
the water heater. In other areas, an ECV is required if the saturation index is greater than +0.4 (refer to “Water
Supplies” on page 15).
The expansion control valve must always be installed after the non-return valve and be the last valve installed
prior to the water heater (refer to diagrams on page 43). A copper drain line must be fitted to the expansion
control valve (refer to "Relief Valve Drain" on page 46).
The valve, if installed within 500 mm of the water heater, must be insulated with closed cell polymer insulation
or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve.
The insulation must be weatherproof and UV resistant if exposed.
45
Page 46
CONNECTIONS – PLUMBING
RELIEF VALVE DRAIN
DN15 copper drain lines must be fitted to the temperature pressure relief valve and expansion control valve (if
one is installed) to carry the discharge clear of the water heater. Connect the drain lines to the valves using
disconnection unions. The drain line from the valve to the point of discharge should be as short as possible,
have a continuous fall all the way from the water heater to the discharge outlet and have no tap, valves or
other restrictions in the pipe work.
A drain line from a relief valve must comply with the requirements of AS/NZS 3500.4.
A drain line must be no longer than nine (9) metres with no more than three bends greater than 45° before
discharging at an outlet or air break. The maximum length of nine (9) metres for a drain line is reduced by
one (1) metre for each additional bend required of greater than 45°, up to a maximum of three additional bends.
Where the distance to the point of final discharge exceeds this length, the drain line can discharge into a
tundish.
Subject to local regulatory authority approval, the drain lines from the temperature pressure relief valve and
expansion control valve from an individual water heater may be interconnected.
The outlet of a drain line must be in such a position that flow out of the pipe can be easily seen, but arranged
so discharge will not cause injury, damage or nuisance. The termination point of a drain line must comply with
the requirements of AS/NZS 3500.4. Drain lines must not discharge into a safe tray.
In locations where water pipes are prone to freezing, drain lines must be insulated, must not exceed 300 mm
in length and are to discharge into a tundish through an air gap of between 75 mm and 150 mm.
If a drain line discharges into a tundish, the drain line from the tundish must be not less than DN20. The drain
line from a tundish must meet the same requirements as for a drain line from a relief valve.
Warning: As the function of the temperature pressure relief valve on this water heater is to discharge high
temperature water under certain conditions, it is strongly recommended the pipe work downstream of the relief
valve be capable of carrying water exceeding 93°C. Failure to observe this precaution may result in damage
to pipe work and property.
SERVICE VALVE DRAIN
A copper drain line must be fitted to the service valve to carry the discharge clear of the water heater and solar
control unit. Connect the drain line to the service valve using the compression nut and olive provided. The pipe
work from the service valve to the drain should be as short as possible and fall all the way from the valve with
no restrictions. It should have no more than three right angle bends in it. Use DN15 pipe.
The outlet of the drain line must be in such a position that flow out of the pipe can be easily seen (refer to
AS/NZS 3500.4) - but arranged so water discharge will not cause injury, damage, nuisance or splashing. The
water discharged may be of a high temperature and even very high temperature steam can be generated
under certain conditions. The drain line must be fully insulated with closed cell polymer insulation or similar
(minimum thickness 13 mm). The insulation must be weatherproof and UV resistant if exposed.
Warning: The solar collector(s) can generate very high temperature water and even very high temperature
steam can be generated under certain conditions when the service valve is opened. It is strongly recommended
pipe work downstream of the service valve be capable of carrying water exceeding 93°C. Failure to observe
this precaution may result in damage to pipe work and property.
46
Page 47
Component
Power
consumption
Comments
Solar controls
4 Watts
Constant load - differential controller
Solar circulator
36 Watts
Maximum circulator load at solar heating cycle or
anti-freeze cycle start-up
30 Watts
Average circulator load during the solar heating cycle
or anti-freeze cycle
Heating unit
1200 Watts
Heating unit load when operating
Total
1240 Watts
Maximum load during anti-freeze cycle
1234 Watts
Average load during anti-freeze cycle
CONNECTIONS – ELECTRICAL
The power supply to the water heater must not be switched on until the water heater is filled with water.
All electrical work and permanent wiring must be carried out by a qualified person and in accordance with the
edition of the Wiring Rules AS/NZS 3000 in force in the state or territory at the time of installation, and all local
codes and regulatory authority requirements.
The power consumption of the water heater is:
The water heater will only operate on a sine wave at 50 Hz. Devices generating a square wave cannot be used
to supply power to the water heater.
SOLAR CONTROL UNIT
The solar control unit, supplied with a 1.8 metre power cord, requires a switched 240 V AC 50 Hz general
purpose outlet (GPO) to be located within 1.2 metres of the installation. The GPO must have a continuous
power supply. The GPO is required to be weatherproof if installed outdoors.
The anti-freeze heating unit is supplied with power from the power outlet via the solar control unit. A flexible
20 mm conduit is provided for the electrical cable from the solar control unit to the solar storage tank. The
conduit is connected to the solar control unit and the solar storage tank with 20 mm terminators.
The power outlet to the solar storage tank must be switched on for the solar control unit to operate and solar
gain to be achieved and for the anti-freeze heating unit to operate and offer additional freeze protection.
The anti-freeze heating unit is rated at 1200 watts.
Warning: If at any stage the heating unit requires replacement, the replacement heating unit’s rating must
not exceed 1200 watts. Fitting a heating unit with a power rating greater than 1200 watts will damage the
differential controller in the solar control unit.
The solar control unit automatically controls the flow rate through the collector circuit. This is achieved via the
hot and cold sensors and differential controller programming providing control over the operation of the
circulator. There is no provision for nor is adjustment to the solar control unit required.
THERMOSTAT SETTING
The temperature setting on the thermostat connected to the anti-freeze heating unit does not need to be
adjusted as this thermostat does not provide temperature control. Its primary function is to provide an energy
cut-out in the event the solar controller fails to turn off power to the anti-freeze heating unit. Temperature
control for the freeze protection function is provided by the differential controller in the solar control unit.
47
Page 48
CONNECTIONS – ELECTRICAL
A1
N
31
4
2
Main 240AC
Booster Heating Unit
A1
N
3 1
4
2
Hot sensor
connection
Cold sensor
WIRING DIAGRAM – SOLAR STORAGE TANK
Solar Control Unit Anti-Freeze Heating Unit
48
Page 49
COMMISSIONING
TO FILL AND TURN ON THE WATER HEATER
The power supply to the solar control unit must not be switched on until the water heater is filled with
water.
Open all of the hot water taps in the house (don’t forget the shower).
Open the service valve fitted at the solar hot water inlet (from collector) of the solar storage tank, using a
pair of pliers or other appropriate tool. Refer to the Service 3-Way Valve diagram on page 50.
Open the cold water isolation valve fully on the cold water line to the water heater.
Air will be forced out of the taps and the service valve drain line.
Close each tap as water flows freely from it.
Close the service valve when water runs freely from the drain line.
The solar collectors and collector circuit should now be purged of air.
Check the pipe work for leaks.
Plug in the solar control unit at the power outlet and switch on the electrical supply.
The power outlet must be switched on for the solar control unit to operate and solar gain to be achieved
and for the anti-freeze heating unit to operate and offer additional freeze protection.
Refer to “Solar Controller Operation at Start-Up” on page 51.
Note: The solar control unit automatically controls the flow rate through the collector circuit. This is
achieved via the hot and cold sensors and differential controller programming providing control over the
operation of the circulator. There is no provision for nor is adjustment to the solar control unit required.
Remove the packaging / covers from the solar collector(s). Note: If the service 3-way valve was not opened during the tank filling procedure above, then the collector
circuit will need to be purged of air. Refer to “Bleeding the Solar Collector(s)” on page 50.
Explain to the householder or a responsible officer the functions and operation of the solar water heater. Upon
completion of the installation and commissioning of the water heater, leave this guide with the householder or
a responsible officer.
TO TURN OFF THE WATER HEATER
If it is necessary to turn off the water heater on completion of the installation, such as on a building site or
where the premises is vacant, then:
Switch off the electrical supply to the solar control unit at the power outlet (refer to note below).
Close the cold water isolation valve at the inlet to the water heater.
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series water heater for the
procedure to turn off the in-series water heater.
Notes:
The freeze protection system will be rendered inoperable if electrical power is not available at the solar
control unit. Damage caused by freezing due to no power at the solar control unit is not covered by the
Rheem warranty.
If there is a risk of freezing, then it is necessary to drain the solar collector(s) and solar hot and solar cold
pipes (refer to “Draining the Solar Collector(s)” on page 53).
Refer to “Terms of the Rheem Warranty” on page 58.
49
Page 50
COMMISSIONING
Service 3-Way Valve
IN-SERIES BOOSTER
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series water heater for the
commissioning procedure of the in-series water heater.
If a continuous flow gas water heater has been installed as an in-series gas booster to the solar water heater,
then to complete the installation, it is necessary to check the gas supply pressure at the inlet to the in-series
gas booster, and also the minimum test point pressure and the maximum test point pressure of the in-series
gas booster. Refer to “Gas Inlet Pressure” and to “Burner Gas Pressure” in the Owner’s Guide and Installation
Instructions supplied with the in-series gas booster.
PRESET OUTLET TEMPERATURE
Note: AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in
potable water. If this water heater is installed with an in-series continuous flow gas booster, then this
requirement of AS 3498 can be satisfied provided the booster is energised, its preset outlet temperature setting
is 70°C or higher and a remote temperature controller or an EZiSET kit is not used.
If this water heater is installed with an in-series storage booster, then this requirement of AS 3498 can be
satisfied provided the storage booster is energised and its thermostat setting is 60°C or higher.
It will be necessary to check and if required to adjust the preset outlet temperature setting of the continuous
flow water heater or the thermostat setting of a storage water heater when it is installed as an in-series booster
to a solar water heater or if it is an existing water heater and a solar water heater is then installed.
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series continuous flow gas booster
for the procedure to check and adjust the preset outlet temperature if required.
Refer to the Owner’s Guide and Installation Instructions supplied with the in-series storage booster for the
procedure to check and adjust the thermostat setting if required.
Note: Consideration must be given to the delivery temperature to any ablution and public areas such as a
bathroom, ensuite or public amenities. Refer to “Hot Water Delivery” on page 26 and to the schematics of “Two
Temperature Zones Using A Temperature Limiting Device” on page 27.
BLEEDING THE SOLAR COLLECTOR(S)
Upon completion of the installation, if the service 3way valve was not opened during the tank filling
procedure, then it is necessary to purge the air from
the collector circuit.
To purge air from the collector circuit:
Ensure the water heater is full of water and all of
the hot taps are turned off.
Using a pair of pliers or other appropriate tool,
open the service 3-way valve fitted at the solar hot
water inlet (from collector) of the solar storage
tank (see diagram).
Warning: Stand well aside of the service valve
drain pipe discharge point and exercise care to
avoid any splashing of water, as water or in some
circumstances steam discharged from the solar
collector(s) may be of a very high temperature.
The mains pressure will force water to flow from the tank and through the pipe work, forcing air from the
collector circuit through the service valve. This is evidenced by spurting of water from the drain line
connected to the service valve.
Note: Allow water to flow from the drain line for a few minutes before closing the service valve. Water
already in the solar hot pipe will drain out prior to air in the top of the collector circuit being purged by the
mains pressure water rising in the solar cold pipe.
Close the service valve when water runs freely under mains pressure from the drain line.
50
Page 51
COMMISSIONING
SOLAR CONTROLLER OPERATION AT START-UP
When the electrical supply is switched on to the solar control unit at start-up:
If there is no solar gain, the circulator will not activate and the green LED will emit a slow pulse.
The slow pulse indicates the circulator is not activated and the power to the solar control unit has been on
for less than 48 hours.
If there is solar gain, the circulator activates and the green LED will emit a series of three (3) flashes.
The three (3) flashes indicate the circulator is operating and power to the solar control unit has been on
for less than 48 hours.
The circulator will operate at full speed for approximately fifteen (15) seconds.
After fifteen (15) seconds, the solar controller will commence to pulse the circulator to reduce the flow
rate through the collector circuit. This will increase the temperature rise across the solar collector(s)
and assist in maximising the system efficiency for the available solar energy. It is normal operation
for the circulator to experience a pulsing effect.
The red LED may emit a rapid pulse for a short period (whilst the green LED is emitting a series of three (3)
flashes), particularly if the solar collector(s) were left uncovered during the final stages of the installation
and commissioning procedure.
This indicates a temperature difference between the hot sensor and cold sensor of greater than 45°C and
does not represent a fault code. This is the result of a build-up of heat and increase in water temperature
in the solar collector(s) prior to the switching on of the electrical supply to the solar control unit.
The rapid pulsing of the red LED will cease as the water circulates and the heat is dissipated from the
solar collector(s). This should be within four (4) to five (5) minutes of start-up, but may take up to ten (10)
minutes.
Whilst the red LED is emitting a rapid pulse, the circulator will operate at full speed. After the red LED has
extinguished, the solar controller will commence to pulse the circulator to reduce the flow rate through the
collector circuit.
If the red LED does continue to emit a rapid pulse for longer than ten (10) minutes, this may indicate water
is not circulating through the solar collector(s) and collector circuit:
switch off the electrical supply at the power outlet to the solar control unit
repeat the procedure to bleed the solar collector(s)
switch on the electrical supply at the power outlet to the solar control unit.
51
Page 52
COMMISSIONING
Flashes
Operational Modes
Flashes
Indicator or Fault Modes
solid green
(remains on)
Standby mode
solid red
(remains on)
Hot sensor temperature
greater than 130°C
green
slow pulse
Standby mode
(power on for less than 48 hours)
red
rapid pulse
Temperature rise across collector
greater than 45°C
(circulator at full speed)
green
rapid pulse
Circulating water through collector(s)
3 x red
Hot sensor in collector – short circuit
3 x green
Circulating water through collector(s)
(power on for less than 48 hours)
4 x red
Hot sensor in collector – open circuit
no green
(remains off)
Power outage or call for service
5 x red
Cold sensor –short circuit
6 x red
Cold sensor – open circuit
DIAGNOSTIC FEATURES OF THE SOLAR CONTROLLER
A solar monitor is located on the side of the solar control unit and houses both a green and a red LED.
The green LED, marked “Solar”, indicates the current operational mode of the solar water heater and the red
LED, marked “Attention”, may indicate a potential fault mode.
The green LED will emit either a constant glow, a constant
pulsing or a series of flashes, with a two (2) second interval
between each series.
The red LED will emit either a constant glow, a constant
pulsing or a series of flashes with a two (2) second interval
between each series. A constant glow or pulsing does not
necessarily mean there is a fault with the system. A series of
flashes indicates there may be a particular fault condition with
the system.
The modes are:
If the power supply to the solar control unit is on and the green LED is off or the red LED is flashing, this
indicates there may be a fault with the water heater. The red LED may emit from three (3) to six (6) flashes in
each series of flashes. A constant glow or pulsing of the red LED does not necessarily mean there is a fault
with the system.
Note: During periods of high solar radiation and if the circulator activates after having been off, such as during
start-up if the solar collector(s) have not been covered, it is possible the red LED may emit a rapid pulse for a
period of up to ten (10) minutes. This does not indicate a fault. Refer to “Solar Controller Operation at Start-
Up” on page 51 for the possible green and red LED pulsing sequence during start-up procedure.
If the red LED continues to emit a rapid pulse for longer than ten (10) minutes, or emits a series of flashes,
then count the number of flashes and phone Rheem Service or their nearest Accredited Service Agent to
arrange for an inspection.
52
Page 53
DRAINING THE WATER HEATER
To drain the water heater:
Cover the solar collector(s) with an opaque material.
Open a hot water tap and allow the water to run for five minutes immediately prior to draining the solar
storage tank.
This will assist in the transfer of any high temperature water in the solar collector(s) to the solar storage
tank.
Close the hot water tap.
Turn off the water heater (refer to “To Turn Off The Water Heater” on page 49).
Warning: Exercise care, as water discharged from the solar storage tank may be of a very high
temperature.
Operate the relief valve release lever - do not let the lever snap back or you will damage the valve seat.
Operating the lever will release the pressure in the water heater.
Undo the union at the cold water inlet and attach a hose.
Let the other end of the hose go to a drain.
Operate the relief valve again.
This will let air into the water heater and allow the water to drain through the hose.
DRAINING THE SOLAR COLLECTOR(S)
To drain the solar collector(s) and the solar hot and solar cold pipes:
Cover the solar collector(s) with an opaque material.
Open a hot water tap and allow the water to run for five minutes immediately prior to draining the solar
collector(s).
This will assist in the transfer of any high temperature water in the solar collector(s) to the solar storage
tank.
Close the hot water tap.
Turn off the water heater (refer to “To Turn Off The Water Heater” on page 49).
Warning: Exercise care, as water discharged from the solar collector(s) may be of a very high
temperature.
Using a pair of pliers or other appropriate tool, open the service valve fitted at the solar hot water inlet of
the solar storage tank (refer to diagram on page 50).
Undo the compression fitting on the union located to the right of the solar control unit, and disconnect the
solar cold pipe.
Water will now drain from the solar collector(s) and the solar hot and solar cold pipes.
When water stops flowing from the solar hot and solar cold pipes, reconnect the solar cold pipe at the
union and tighten the compression fitting.
Close the service valve.
53
Page 54
PURGING AND FLUSHING THE SOLAR COLLECTOR(S)
Upon completion of the installation, if the service 3-way valve was not opened during the tank filling procedure,
then it is necessary to purge the air from the collector circuit.
Other than at the time of the water heater’s installation, it will be necessary to purge air from the collector
circuit:
When the water heater is to be turned on and the solar collector(s) and solar hot and solar cold pipes have
been drained.
After maintenance has been conducted on the pipe work and air has entered the system.
If the circulator appears not to be circulating water around the system.
It is recommended to flush the solar collector(s) every five (5) years. This will assist in keeping the solar
collector(s), and solar hot and solar cold pipes clear of sediment.
It may also be necessary to flush the solar collector(s) if there is sediment in the water supply.
Warning: Other than at the time of the water heater’s installation, it is recommended purging air from the
collector circuit or flushing of the solar collector(s) be conducted early in the morning, within three (3) hours of
sunrise, when the sun is low in the sky. The water temperature inside the solar collector(s) is lower as the solar
collector(s) would not have had a chance to gain as much heat as later in the day. Purging air from the collector
circuit or flushing the solar collector(s) at a time later than this can result in the discharge of high temperature
water and in some circumstances, high temperature steam.
To purge air from the collector circuit or flush the solar collector(s):
Open a hot water tap and allow the water to run for five (5) minutes.
Close the hot tap.
Wait a further five (5) minutes before attempting to purge air from the collector circuit or flush the solar
collector(s).
This will assist in the transfer of any high temperature water in the solar collector(s) to the solar storage
tank.
Warning: Exercise care, as water discharged from the solar collector(s) may be of a very high
temperature.
Follow the procedure “Bleeding the Solar Collector(s)” on page 50, allowing the water to flow from the
service valve drain line for a few minutes before closing the service valve.
54
Page 55
This page is intentionally blank.
55
Page 56
This page is intentionally blank.
56
Page 57
This page is intentionally blank.
57
Page 58
RHEEM SOLAR LOLINE WATER HEATER WARRANTY
– AUSTRALIA ONLY –
SOLAR WATER HEATER MODEL 511161
1. THE RHEEM WARRANTY – GENERAL
1.1 This warranty is given by Rheem Australia Pty Limited ABN 21 098 823 511 of 1 Alan Street, Rydalmere
New South Wales.
1.2 Rheem offer a trained and qualified national service network who will repair or replace components at the
address of the water heater subject to the terms of the Rheem warranty. Rheem Service, in addition can
provide preventative maintenance and advice on the operation of your water heater. The Rheem Service
contact number is 131031, with Contact Centre personnel available 24 hours, 7 days a week to take your
call and if necessary to arrange a service call for during normal working hours Monday to Friday (hours
subject to change).
1.3 For details about this warranty, you can contact us on 131031 or by email at
warrantyenquiry@rheem.com.au (not for service bookings).
1.4 The terms of this warranty and what is covered by it are set out in sections 2 and 3 and apply to water
heaters manufactured after 1st July 2013.
1.5 If a subsequent version of this warranty is published, the terms of that warranty and what is covered by it
will apply to water heaters manufactured after the date specified in the subsequent version.
2. TERMS OF THE RHEEM WARRANTY AND EXCLUSIONS TO IT
2.1 The decision of whether to repair or replace a faulty component is at Rheem’s sole discretion.
2.2 If you require a call out and we find that the fault is not covered by the Rheem warranty, you are
responsible for our standard call out charge. If you wish to have the relevant component repaired or
replaced by Rheem, that service will be at your cost.
2.3 Where a failed component or cylinder is replaced under this warranty, the balance of the original warranty
period will remain effective. The replacement does not carry a new Rheem warranty.
2.4 Where the water heater is installed outside the boundaries of a metropolitan area as defined by Rheem
or further than 25 km from either a regional Rheem branch office or an Accredited Rheem Service Agent's
office, the cost of transport, insurance and travelling between the nearest branch office or Rheem
Accredited Service Agent’s office and the installed site shall be the owner’s responsibility.
2.5 Where the water heater is installed in a position that does not allow safe or ready access, the cost of that
access, including the cost of additional materials handling and/or safety equipment, shall be the owner’s
responsibility. In other words, the cost of dismantling or removing cupboards, doors or walls and the cost
of any special equipment to bring the water heater to floor or ground level or to a serviceable position is
not covered by this warranty.
2.6 This warranty only applies to the original and genuine Rheem water heater in its original installed location
and any genuine Rheem replacement parts.
2.7 The Rheem warranty does not cover faults that are a result of:
a) Accidental damage to the water heater or any component (for example: (i) Acts of God such as
floods, storms, fires, lightning strikes and the like; and (ii) third party acts or omissions).
b) Misuse or abnormal use of the water heater.
c) Installation not in accordance with the Owner’s Guide and Installation Instructions or with relevant
statutory and local requirements in the State or Territory in which the water heater is installed.
d) Connection at any time to a water supply that does not comply with the water supply guidelines as
outlined in the Owner’s Guide and Installation Instructions.
e) Repairs, attempts to repair or modifications to the water heater by a person other than Rheem
Service or a Rheem Accredited Service Agent.
f) Faulty plumbing or faulty power supply.
58
Page 59
RHEEM SOLAR LOLINE WATER HEATER WARRANTY
What components are
covered
The period from the date of
installation in which the
fault must appear in order to
be covered
What coverage you receive
511 series 160 model
All components
Year 1
Repair and/or replacement of the faulty
component, free of charge, including labour.
The cylinder
(if the water heater is installed
in a single-family
domestic dwelling)
Years 2 & 3
Repair and / or replacement of the cylinder,
free of charge, including labour.
Years 4 & 5
Replacement cylinder, free of charge.
Installation and repair labour costs are the
responsibility of the owner.
The cylinder
(if the water heater is not
installed in a single-family
domestic dwelling)
Years 2 & 3
Replacement cylinder, free of charge.
Installation and repair labour costs are the
responsibility of the owner.
The solar collector
(all installations)
Years 2 to 5
Replacement solar collector, free of charge.
Installation and repair labour costs are the
responsibility of the owner.
– AUSTRALIA ONLY –
SOLAR WATER HEATER MODEL 511161
g) Failure to maintain the water heater in accordance with the Owner's Guide and Installation
Instructions.
h) Transport damage.
i) Fair wear and tear from adverse conditions (for example, corrosion).
j) Cosmetic defects.
k) Breakage of collector glass for any reason including hail damage (we suggest that the collector
glass be covered by your home insurance policy).
l) Ice formation in the waterways of a water heater system incorporating a freeze protection system
where the electricity supply has been switched off or has failed or where it is installed at an altitude
more than 400 metres above sea level.
2.8 Subject to any statutory provisions to the contrary, this warranty excludes any and all claims for damage
to furniture, carpet, walls, foundations or any other consequential loss either directly or indirectly due to
leakage from the water heater, or due to leakage from fittings and/ or pipe work of metal, plastic or other
materials caused by water temperature, workmanship or other modes of failure.
2.9 If the water heater is not sized to supply the hot water demand in accordance with the guidelines in the
Rheem water heater literature, any resultant fault will not be covered by the Rheem warranty.
3. WHAT IS COVERED BY THE RHEEM WARRANTY
FOR THE WATER HEATERS DETAILED IN THIS DOCUMENT
3.1 Rheem will repair or replace a faulty component of your water heater if it fails to operate in accordance
with its specifications as follows:
59
Page 60
RHEEM SOLAR LOLINE WATER HEATER WARRANTY
RHEEM AUSTRALIA PTY LTD, A.B.N. 21 098 823 511, www.rheem.com.au
For Service Telephone 131 031 AUSTRALIA
– AUSTRALIA ONLY –
SOLAR WATER HEATER MODEL 511161
4. ENTITLEMENT TO MAKE A CLAIM UNDER THIS WARRANTY
4.1 To be entitled to make a claim under this warranty you need to:
a) Be the owner of the water heater or have consent of the owner to act on their behalf
b) Contact Rheem Service without undue delay after detection of the defect and, in any event, within
the applicable warranty period.
4.2 You are not entitled to make a claim under this warranty if your water heater:
a) Does not have its original serial numbers or rating labels.
b) Is not installed in Australia.
5. HOW TO MAKE A CLAIM UNDER THIS WARRANTY
5.1 If you wish to make a claim under this warranty, you need to:
a) Contact Rheem on 131031 and provide owner’s details, address of the water heater, a contact
number and date of installation of the water heater or if that’s unavailable, the date of manufacture
and serial number (from the rating label on the water heater)
b) Rheem will arrange for the water heater to be tested and assessed on-site.
c) If Rheem determines that you have a valid warranty claim, Rheem will repair or replace the water
heater in accordance with this warranty
5.2 Any expenses incurred in the making of a claim under this warranty will be borne by you.
6. THE AUSTRALIAN CONSUMER LAW
6.1 Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are
entitled to a replacement or refund for a major failure and for compensation for any other reasonably
foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods
fail to be of acceptable quality and the failure does not amount to a major failure.
6.2 The Rheem warranty (set out above) is in addition to any rights and remedies that you may have under
the Australian Consumer Law.
Revision Date: 2018 November 122491E
60
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.