Rheem 310 Series, 551310 Service Instructions Manual

Page 1
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
RRhheeeem
m AAuussttrraalliiaa PPttyy LLttdd
AABBNN 2211 009988 882233 551111
SERVICE INSTRUCTIONS
310 Series Heat Pump
TM025
R
R
R
e
e
e
v
v
v
i
i
i
s
s
s
i
i
i
o
o
o
n
n
n
:
:
:
B
B
B
P
P
P
u
u
u
b
b
b
l
l
l
i
i
i
s
s
s
h
h
h
e
e
e
d
d
d
:
:
:
0
0
0
8
8
8
/
/
/
0
0
0
7
7
7
551310
Page 2
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
1
Contents
Safety Warning....................................................................................................................2
Introduction..........................................................................................................................2
Specifications.......................................................................................................................3
Preventative Maintenance ...................................................................................................3
Operation.............................................................................................................................4
Electronic Controller ............................................................................................................5
Operating Sequence Flow Charts:.......................................................................................6
Refrigeration Terms and their Meaning................................................................................8
Components and their Function...........................................................................................8
Common Faults ...................................................................................................................9
Wiring Diagram..................................................................................................................11
Refrigeration Sealed System Diagram...............................................................................12
LED Indication ...................................................................................................................12
Fault Finding......................................................................................................................14
Refrigerant Charge ............................................................................................................45
Electrical Insulation Testing...............................................................................................46
Component Replacement Procedures – Water Heater......................................................47
Component Replacement Procedures – Refrigeration Plant .............................................52
Component Replacement Procedures – Sealed Refrigeration System .............................57
Exploded View - Refrigeration Plant ..................................................................................62
Replacement Parts List – Refrigeration Plant.................................................................63
Exploded View - Water Heater...........................................................................................64
Replacement Parts List – Water Heater.........................................................................65
Rheem Electric Water Heater Warranty - (Australia Only).................................................66
Document Revision History................................................................................................67
Page 3
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
2
Safety Warning
The purpose of this Service Manual is to provide sufficient information to allow a person with the skills as required by the controlling Regulatory Authorities to carry out effective repairs to a Rheem 310 series Heat Pump Water Heater in the minimum of time.
Safety precautions or areas where extra care should be observed when conducting tests outlined in this manual are indicated by print in bold italics and/or a warning symbol. Take care to observe the recommended procedure.
Certain diagnostic procedures outlined in these service instructions require “live” testing to be conducted. Wear Personal Protective Equipment (PPE) when conducting these tests to prevent the risk of electric shock. (Refer to the Rheem Safety Procedure on electrical testing)
R134A is a controlled substance under the fair trading act. Personnel qualified and licensed to work with refrigerants may only carry out service and repair to the sealed refrigeration system. During repair the refrigerant
must be recovered, not vented to atmosphere.
Environmental
At the end of the service life of a Rheem heat pump the refrigerant must be recovered by personnel qualified and licensed to work with refrigerants prior to the unit being disposed of. Refrigerants must not be vented to
atmosphere.
Introduction
The information provided in these instructions is based on the water heater being installed in accordance with the Installation Instructions provided with each water heater.
Should you require further technical advice on a Rheem 310 Series Heat Pump Water Heater, contact your nearest Rheem Service Department where all genuine replacement parts are also available.
Heater Model Identification
All identification numbers are designed to convey detailed information about the water heater to which it is attached. The model number consists of 8 digits.
5 X X 310 0 X 5 – Renewable Energy Model
5 – Air Sourced 9 – Solar Sourced
0 – No Heating Units 1 – Booster Element
Storage Capacity in Litres No Reference – System Requirement 0 – Element Not fitted
5 – 2400 watts 7 – 3600 watts
Note: Model number, serial number and date of manufacture should be quoted in all correspondence.
Page 4
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
3
Specifications
Water Heater
Model 551310
Capacity - Litres 310 Boost Capacity - Litres 220 Booster element rating - kW 2.4 or 3.6 T&PR valve Rating - kPa 1000
With ECV 680
Maximum inlet pressure - kPa
Without ECV 800 Inlet / Outlet RP¾/20
Water Connections
T&PR RP½/15 Quantity 1
Anode
Length 1153 Control board thermostat setting (fixed) 60ºC Limp mode mechanical thermostat setting 70ºC Mechanical thermostat ECO setting 88ºC
Refrigeration System
Parameter 551310
Sound rating 51 dBA @1.5m Superheat setting (Factory) +6ºC at 10ºC Evaporator temp. Refrigerant charge R134A 1050 grams Compressor internal OTC Open 150ºC. Close 90ºC (automatic reset)
Compressor winding resistance
Run winding - Red & Blue: 2.2 ohms at 20ºC
Start winding - Red & Black: 3.27 ohms at 20ºC
Compressor Capacitor 35µF 240 VAC 50HZ Fan winding resistance
Run winding – Black & Brown: 184 ohms at 20ºC
Start winding – Black & Blue: 238 ohms at 20ºC Fan Capacitor 2µF 240 VAC 50HZ Circulator winding resistance 75.3 ohms @ 20ºC
Preventative Maintenance
It is suggested for peak performance that the water heater be serviced annually.
1. Check for discharge from the T&PR valve. When the element or heat pump is
operating a small discharge of water may be evident. Operate the valve-easing lever to ensure the valve opens and resets properly. Always open and close the valve gently. The T&PR valve should be replaced at 5 yearly intervals.
2. Check for leaks at all cylinder fittings.
3. Check for signs of excessive corrosion on the water heater jacket.
4. Isolate power to the water heater and check all electrical connections for signs of
overheating due to poor connection.
5. Conduct an 'Electrical insulation test' on the water heater (refer to page 46).
6. Check evaporator fins and fan blade for build up of dust or debris.
7. Check for sludge build up and if necessary drain and flush tank.
Page 5
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
4
Operation
Operation – Water System:
The heat pump utilises a form of heating called ‘top down’ heating. The circulator (1) draws cooler water from the bottom of the cylinder via the long dropper tube (2). The water passes through the heat exchanger (condenser) (3) where it is heated by the refrigerant and is then returned to the top of the cylinder via a short dropper tube (4).
Operation – Heat Pump Mode:
During normal operation in ‘heat pump’ mode the electronic controller (control board) holds a control relay in the energised state and power for the compressor is passed to an electronic switch (called a triac) via the normally open relay contact.
The operation of the compressor causes a pressure difference within the sealed refrigeration system. This pressure difference causes the refrigerant to move around the sealed system. The refrigerant enters the evaporator (5) as a liquid, as the refrigerant absorbs heat from the atmosphere it changes state, at low pressure, from a sub cooled liquid to a super heated vapour or gas (evaporates). The vapour then enters the compressor (6) and obtains more heat, known as heat of compression, and passes into the heat exchanger as a super heated vapour at high pressure.
As the refrigerant passes through the heat exchanger it gives off heat which is absorbed by the water flowing through a separate chamber inside the heat exchanger. As the refrigerant gives off heat it cools and changes state back into a liquid (condenses). The refrigerant then enters the evaporator again and the cycle is repeated.
Operation – Boost Mode:
The controller will enter ‘boost’ mode when atmospheric conditions are unsuitable for heat pump operation or a possible failure of the refrigeration or water circuits has been detected. The following error conditions will initiate boost mode:
1. The temperature sensed by the ambient air sensor is below 0°C.
2. The water leaving the heat exchanger is greater than 80°C.
3. The compressor discharge temperature is greater than 110°C.
4. The evaporator temperature is less than -3°C.
5. The failure of sensors S3, S4 or S5.
6. The compressor is not running based on either of the following conditions:
a. After 2 minutes in controller sequence 3 the compressor discharge temperature has
not risen 15°C above ambient.
b. In controller sequence 4 the water temperature rise across the heat exchanger
(condenser) is less than 8°C.
In boost mode the electronic controller continues to control the temperature of the water in the cylinder and the circulator however the control relay is de-energised switching the power supply from the compressor triac to the element.
Page 6
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
5
Boost mode allows 220 litres of 60ºC hot water to be provided by electric boosting. During this mode the circulator will cycle on and off periodically allowing for the 220 litre boost capacity rather than just the amount of water above the element as is the case with a conventional electric boost system.
Once a heating cycle is completed the error is cleared and normal operation is resumed on the next call for heat.
Note: If sensor S4 fails the system will operate on boost mode however the temperature will in this case be controlled by the mechanical thermostat and 220 litres of 70ºC water will be available.
Operation – Limp Mode:
Limp mode will only occur due to the failure of both sensors S1 and S4. In limp mode the electronic controller no longer controls the operation of the heat pump
and both ‘heat pump’ mode and ‘boost’ mode are rendered inoperable. The control relay is de-energised switching the power supply from the compressor triac to the element.
Limp mode allows 111 litres of hot water to be provided by electric boosting and the water temperature is controlled by the mechanical thermostat which is set to 70°C; in this condition only the water in the zone above the element is heated as the circulator does not operate.
It should be noted that if sensor S1 fails and sensor S4 is operational the system operates in boost mode however the circulator cannot operate. In this case the end result is an operation similar to limp mode in which 111 litres of water is heated by the booster and the temperature controlled to 70ºC by the Robertshaw thermostat.
Electronic Controller
The main features of the electronic controller (control board) are shown on the diagram opposite. The inputs to the software are shown in blue and the outputs that control the heat pump are shown in red.
The connection marked “relay element” energises or de-energises a relay that switches from heat pump heating to electric element heating when the system operates in “boost” or “limp” mode.
The “Compressor TRIAC” switches the power to the compressor on and off.
The “Communication port” can be used in conjunction with a computer to read the inputs and outputs from the software. This information may be logged using specially designed logging software (Contact Rheem Service for more information regarding this software).
The “Software loading port” is only used for loading software on to the control board.
The green and red LED’s indicate the condition of the heat pump (refer to the section titled “LED Indication” on page 12).
Page 7
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
6
Operating Sequence Flow Charts:
Page 1 of 2:
Power to controller
Tank
sensors S3-S5
ok?
NO
YES
YES
NO
Heat
pump sensors
T0-T4 ok?
Sequence 0
S4< 44.5°C
or S3 < 50°C
YES
Call for heat
Green LED solid
System in stand by mode
NO
Set paramaters
Seq 1
Circulator on
Seq 2
Compressor on
Evaporator fan on
30 seconds later
Circulator to minimum flow rate
Sequence 3
T0
= or > than
57°C?
Cylinder sensors
Heat exchanger
outlet sensor
NO
Sequence 4
Circulator to variable speed
YES
Use value of T4 and T1 to set circulator flow
rate to achieve 62°C at heat exchanger outlet
T0
= 60°C?
Fault
detected?
S4 > 53°C
or S5 > 50°C?
T4
<0°C?
YES
Green LED flashing
At maximum flow rate
Circulator off
Compressor off
Evaporator off
NO
Refrigeration
Heating cycle
ends
Adjust pump
flow rate
NO
T4 < 0°CT0 > 80°C T2 < -3°C
Water
discharge temp
too hot
T0 - T1
<8°C
Refrigerant
circuit not
operational
NO
Temperature rise across heat
exchanger smaller than 8°C
Ambient air
temp too
low
Evaporator
frozen
Sensor T0 - T4
Open or
short circuit
T3 >
T4 +15°C?
After 2 minutes
YES
NO
Compressor discharge
temperature 15°C above ambient
Condenser inlet
temp higher than
pick up temp
T1 > S4 +7°C
T3 > 110°C
High ambient
temp or running
too long
Check every
11 minutes
NO
Compressor recently on -
delay start
S3 - S5
H
Y
Z
Open or
short circuit
Thermostat
contacts closed?
NO
T2
<-3°C?
T0
>80°C?
NO
YES
Ambient conditions too cold
for heat pump operation
Circulator
fault
Controller de-energised
no operation
NO
Error condition reset
Relay energised
NO
YES
H
T3
>60°C?
YES
YES
A
H
T3 >
T4 +15°C?
YES
NO
Compressor discharge
temperature 15°C above ambient
YES
Software
version
HPV 4.0 or higher
HPV 3.1, HPV
3.2 or no HPV identification
Relay de-
energised &
element on
S0 & S1 > 62°C?
YES
YES
NO
S0 & S1 < 62°C?
YES
Relay
energised &
element off
S4< 44.5°C
or S3 < 50°C
NO
B
NO
YES
B
YES
NO
YES
Page 8
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
7
Page 2 of 2:
NO
Boost Mode
220L heated to
approx. 60°C
H
Relay de-energised
Red LED Flashing
Element On
S1
>62°C?
S4
>53°C?
YES
NO
Element Off
YES
Z
Circulator On
NO
S1
<61°C?
NO
S4
>53°C?
YES
Circulator Off
YES
NO
Sequence 0
YES
S4
Sensor
ok?
Temp at
thermostat =
70°C?
Controller can no longer detect
lower cylinder temperature.
Water temperature will be
controlled by mechanical
thermostat to 70°C
S1
Sensor
ok?
NO
YES
Controller can no longer detect
upper cylinder temperature.
The circulator will not operate
preventing water below the
element level from heating
Temperature at sensor S4 will
not achieve 53°C
NO
Heating Cycle
complete
Element On
Limp Mode
111L heated to
approx. 70°C
NO
Element Off
YES
Power to controller off
Y
S1
Sensor
ok?
S1
>62°C?
YES
Boost Mode
220L heated to
approx. 70°C
Circulator On
Temp at
thermostat =
70°C?
YES
S1
<61°C?
NO
Circulator Off
YES
NO
YES
Element On
NO
T2
> 2°C?
T4
> 2°C?
A
YES
NO
NO
Ambient temperature high enough
to resume heat pump operation
YES
Page 9
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
8
Refrigeration Terms and their Meaning
Sub Cooled Liquid – A substance below its saturation temperature at a given pressure. Super Heated Vapour – A substance above its boiling point at a given pressure. Saturated Vapour – A substance at its boiling point at a given pressure. Latent Heat – Hidden (invisible) heat removed or added to a substance that results in a
change of state (i.e. liquid to a vapour) without an increase or decrease in temperature. Heat of Compression – The additional heat added to a substance by the act of
compressing it. Low Side – Components and pipe work of a refrigeration system operating at low
pressure, generally considered to be the evaporator, suction line and accumulator. High Side – Components and pipe work of a refrigeration system operating at high
pressure, generally considered to be the condenser, discharge line, liquid receiver/filter drier and compressor case where a rotary compressor is utilized.
Boil Off – The action of a substance as it absorbs heat and changes state (evaporates) from a liquid to a vapour (gas).
Give Up Heat – The action of a substance as it releases heat and changes state (condenses) from a vapour (gas) to a liquid.
Components and their Function
Temperature and Pressure Relief Valve - A valve designed to provide automatic relief by
discharging water in case of excessive temperature, pressure or both.
Never fit a T&PR Valve with a pressure rating greater than that indicated on
the product-rating label.
Pressure Limiting Valve (P.L.V.) - A valve that controls its outlet pressure to a predetermined limit.
Outlet Delivery Tube (Dip Tube) - A plastic tube installed in the hot water outlet of the water heater cylinder to conduct water from the highest point to the outlet connection. It also acts as a fitting liner.
Diffuser - A plastic device installed in the cold water inlet of the water heater cylinder to assist with stratification. It also acts as a fitting liner.
Fitting Liner - A plastic tube installed in the cold-water inlet of the water heater to provide protection against corrosion through the life of the water heater.
Anode (Sacrificial) - A metal alloy electrode installed in the water heater cylinder that by galvanic action protects the cylinder from corrosion.
Thermostat - A device responsive to temperature that controls the supply of electrical energy to the compressor, which results in the stored water being maintained at the required temperature.
Evaporator Thermistor - A device responsive to temperature that controls the active supply between the compressor circuit and the booster element circuit.
Page 10
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
9
Compressor - An electro-mechanical device that adds heats to the refrigerant by compressing it, known as “heat of compression” the resulting increase in refrigerant temperature increases its pressure and causes the refrigerant to circulate through the system.
Evaporator - A finned copper coil mounted on top of the water heater. The refrigerant enters as a liquid, as it passes through the coil it absorbs heat from the surrounding atmosphere and “boils off” (evaporates) to a gas.
Condenser - An insulated housing containing stainless steel chambers where heat transfer occurs. The condenser (or heat exchanger) contains three chambers, one for refrigerant, one for water and a third separating chamber containing air. The refrigerant enters as a gas, as it passes through the condenser it transfers (“gives up”) the heat absorbed via the evaporator to the water flowing through the condenser in a separate chamber, during this process the refrigerant cools and changes state (condenses) back to a liquid.
Receiver Filter Drier - This device, fitted between the condenser and thermal expansion (TX) valve, receives and stores liquid refrigerant from the condenser for delivery to the evaporator. The receiver also incorporates a filter and drier to trap impurities and remove moisture from the sealed refrigeration system
Accumulator - This device, fitted in the suction line prior to the compressor, is designed to accumulate and prevent liquid refrigerant from entering and damaging the compressor. Any liquid refrigerant is evaporated or “boiled off” and converted to a vapour by the accumulator.
Thermal Expansion (TX) Valve - A valve, installed between the condenser and evaporator that controls (meters) the amount of refrigerant delivered to the evaporator. The TX valve has an external temperature sensor fitted to the suction line and increases or decreases the refrigerant flow to the evaporator depending on the detected suction line temperature.
Thermal Cut Out (Overload) - A manual reset temperature sensitive device that automatically cuts off the supply of electrical energy to the control board and/or boost element.
Heating Unit (Element) - A tubular device containing an electric resistance element that converts electrical energy to heat. Standard element ratings are 2.4 and 3.6kW.
Common Faults
When a complaint is lodged about the performance of a hot water system there are a number of causes that should be checked and eliminated. In an attempt to pinpoint the most likely cause it is important to discuss with the customer their reasons for the complaint, the duration of the problem, any change in circumstances or usage and recent weather conditions. This information in conjunction with the following listed common complaints will assist you in locating the most likely cause. All procedures assume there is water flowing through the water heater.
Discoloured water - This may be the result of discoloured water entering from the cold water mains. Check if the cold water is also discoloured.
Excessive hot water usage - The complaints of insufficient hot water and no hot water can on many occasions be attributed to hot water usage exceeding the capacity of the water heater to provide hot water.
Page 11
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
10
When first attending a call of this nature it is essential to establish the probable hot water usage by querying the usage habits of the household and compare this with the potential delivery of the model water heater installed. It can then be established if the usage is within or outside the capacity of the model. The areas to look at for excessive usage are:
1. Automatic washing machines.
2. Showers exceeding 12 litres/minute for mixed water and 5 minutes in duration.
3. Two or more showers operating at the same time.
4. Change of occupancy or number of persons increased.
5. High water pressure area. (Excessive pressure relief valve discharge)
6. Plumbing leaks.
7. Crossed connection. Water hammer - A water heater will not cause water hammer, however valves associated
with the water heater may be the source of the problem i.e. cold-water stopcock, non­return valve or relief valve.
Most water hammer problems are associated with plumbing, hot and cold or appliances i.e. solenoid valves, ballcocks, loose pipes, sharp angles in pipe work, faulty or worn valve parts, loose tap washers or neighbouring equipment.
High water pressure areas will have more complaints of this nature and the use of a pressure-limiting valve (PLV) to reduce the household cold-water pressure will usually solve most problems.
Hot water plumbing leaks - If hot water has not been used for a period of time, feeling the temperature of the hot water line may give an indication of water flow if the pipe is warm. The method of checking for plumbing leaks is:
1. Turn off the stopcock on the cold water supply to the water heater.
2. Open a hot tap to ensure the flow of water stops. This will confirm the stopcock is
operating correctly.
3. Turn off the hot tap.
4. Turn on the stopcock to make up the water pressure in the cylinder, and then turn the
stopcock off again.
5. Wait approximately 5 minutes then do either of the following:
a. With your ear close to the stopcock turn it on slightly and listen for any water
passing. If there are no leaks, water should not pass.
b. Open a hot tap while listening for any pressure release. If there is a pressure
release there will be no leaks in the plumbing system.
Mixing or crossed connections - If an automatic dishwasher, washing machine, flick mixer tap, tempering valve or thermostatic mixing valve is installed there is always the possibility that the cold water could mix with the hot water through a faulty or incorrectly installed valve. This is referred to as a cross connection. The complaints of insufficient hot water, water too cold or excessive discharge from the pressure relief valve may be attributed to a cross connection. The method of checking for a cross connection is:
1. Turn off the stopcock on the cold water supply to the water heater.
2. Open a hot tap. If water flow is persistent and cold a cross connection exists.
Page 12
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
11
Wiring Diagram
Page 13
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
12
Refrigeration Sealed System Diagram
LED Indication
All 310 series Heat Pumps have LED indication. There are two variations of LED indication depending upon the version of the controllers software; however all versions utilise a red and green LED to display the operational status and/or fault condition of the appliance. Note: The software version is printed on a label on the control board.
Controller Software Version HPV 3.1, HPV 3.2 or no HPV identification
310 Series Heat Pumps with controller version HPV3.1, HPV 3.2 or no HPV identification have a green and red LED located internally on the control board in the heat pump (refrigeration) module and utilise the following LED indication:
LED Indication
LED Status Condition Details
Green Solid S4 > 53ºC or S5 > 50ºC
Standby mode (end of heating cycle, cylinder water at required temperature).
Green Flashing S4 < 44.5ºC or S3 < 50ºC Call for heat initiated. Red Flashing
Various (refer to operating sequence flow chart on page 6 for more details).
Component fault or ambient conditions too cold for heat pump operation.
No indication
Fault or system operating in limp mode.
Fault or system in limp mode with call for heat satisfied (water in cylinder @ 70ºC determined by mechanical thermostat).
Note: Refer to diagram on page 5 for control board LED location.
Page 14
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
13
Controller Software Version HPV 4.0 or higher
310 series Heat Pumps with controller version HPV 4.0 or higher have a red and green LED located externally on the front of the heat pump module or internally on the control board in the heat pump (refrigeration) module depending upon date of manufacture.
LED Flashing Frequency: Different combinations of flashing red and/or green LED’s are utilised to indicate the operational status or fault condition of the Heat Pump. Each flash in a series will last 0.5 seconds and is separated by 0.5 seconds between flashes. Each series of flashes is separated by 2 sec.
Example: LED provides 2 flashes: 1) LED on for 0.5 sec.
2) LED off for 0.5 sec.
3) LED on for 0.5 sec.
4) LED off for 2 sec.
5) Return to Step 1). Operational LED Indication: If no fault is present the green LED will flash as shown
below to indicate the operational sequence number the Heat Pump is currently operating in (refer to operating sequence flow chart on page 6 for more details).
Operational LED Indication
Sequence Green LED Red LED
0 Solid 0 2 2 flashes 0 3 3 flashes 0 4 4 flashes 0
Fault Indication: If a fault is present the green and/or red LED’s will indicate the fault
condition according to the table below.
Fault Indication
Fault Error Green LED Red LED
Faulty power supply or system in limp mode
with call for heat satisfied (1)
N/A 0 0
T3 (comp dis) > 60°C in sequence 0 (2)
SerrNo 4 1 Flash 0
T4 (ambient air) < 0°C (3)
SerrNo 1 0 Solid
Any Sensor Strip Sensor Fault Any Sflag 0 1 Flash
Water circ fault T0 (water outlet) > 80°C
SerrNo 2 0 2 Flashes
T2 (evaporator) < -3°C
SerrNo 8 0 3 Flashes
Comp/refrig fault T3 > T4 + 15°C (in seq3)
SerrNo 32 0 4 Flashes
Comp/refrig fault T0 - T1 < 8°C (in seq4)
SerrNo 32 0 5 Flashes
Water circ fault T1 > S4 + 7°C
SerrNo 64 0 6 Flashes
TRIAC/refrig fault T3 > 110°C
SerrNo 128 0 7 Flashes Thermistor T0 Fault Tflag 1 1 Flash* 1 Flash* Thermistor T1 Fault Tflag 2 2 Flashes* 2 Flashes* Thermistor T2 Fault Tflag 4 3 Flashes* 3 Flashes* Thermistor T3 Fault Tflag 8 4 Flashes* 4 Flashes* Thermistor T4 Fault Tflag 16 5 Flashes* 5 Flashes*
Notes: * The green and red LED’s flash simultaneously in these cases.
(1) System may be in limp mode with call for heat satisfied (water in cylinder @ 70ºC
determined by mechanical thermostat).
(2) This condition creates a delay start for the compressor. This is not considered a fault. (3) Ambient temperature too cold for heat pump operation. This is not considered a fault.
Page 15
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
14
Fault Finding
Fault Chart
Number
Page
1 16
1.1 17
1.2 21
No Hot Water
7 43
Insufficient hot water 2 23
3 24
3.1 25
3.2 25
3.3 26
3.4 27
3.5 29
3.6 30
3.7 30
8.1 44
Software version
HPV 3.1, HPV 3.2
or no HPV
identification
8.3 44 4 32
4.1 33
4.2 33
4.3 34
4.4 35
4.5 36
4.6 37
4.7 38
4.8 39
4.9 – 4.13 40
4.14 40 8 44
System in boost or limp mode
Software version
HPV 4.0 or higher
8.2 44 Leaking water heater 5 41 Noisy water heater 6 42 Blowing fuse/circuit breaker 7 43
Page 16
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
15
General Fault Finding Chart
Fault Diagnosis
No
hot water?
YES
1
Insufficient
hot water?
NO
2
YES
System
in boost or limp
mode?
NO
3
YES
NO
5
YES
6
NO
Leaking
water heater?
Noisy
water heater?
7
YES
NO
Blowing fuse/circuit breaker
Boost or limp mode will be indicated by any of the following LED conditions: Red solid or flashing. Red & green flashing together. No LEDs (Limp mode with Robertshaw thermostat open)
4
HPV 3.1, HPV 3.2 or no HPV identification
HPV 4.0 or higher
What is the
controller
software version?
Note: For more information on LED indication refer to pages 12 and 13.
Page 17
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
16
Fault Finding Chart 1
1
Warning: Terminals may be ‘live’.
Wear Personal Protective
Equipment to prevent risk of
electric shock.
Is 240
volts present at
the terminal
block?
Test 1
1.1
YES
Is
the heater
connected to an
off peak
tariff?
NO
Off peak connection is unsuitable for Heat
Pump models. Connect to continuous tariff or
‘off peak 2’ if available
YES
Is the
isolating switch
or time clock
turned off?
NO
Restore power and advise customerYES
Is the
fuse blown at the
switchboard?
NO
Fault in household electrical wiringNO
Reset circuit breaker
or rewire fuse
YES
Did
the fuse or
circuit breaker blow
again?
7
YES
1. Heat pump connected to mix ed circuit, possible excessi ve current draw or another appliance with a fault
2. Faulty circuit breaker or fatigued fuse wire
3. Unit may be short cycling due to faulty thermostat
NO
No Hot Water
Page 18
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
17
Fault Finding Chart 1.1
Note: Ensure you
wait the full five
minutes before
progressing from
this point.
1.1
Are the
thermostat contacts
closed?
NO Replace thermostat.
Test 2
No Hot Water
Is there
240V at the
control board &
relay?
Test 3
Wiring incorrect. Check control board wiring loom plug (lower thermostat to control
board wiring loom).
NO
Test 4
What is the
status of the
control boards
LED’s five
minutes after
resetting?
Replace control board.
Red solid or Red and Green LED’s indicating simultaneously
Green flashing
Green solid
No indication
1.2
Replace sensor strip.
Replace control board (system should have been operating in
boost mode after five minutes
from resetting) then check
system operation as a second
fault may be present.
YES
Note: To reset heat
pump switch power off,
wait for 30 seconds
then switch back on.
Reset heat pump &
wait five minutes
before progressing
from this point.
Is the
compressor
running?
Is the
sensor strip
working?
NO
YES
Is the
refrigeration
system
heating?
YES
NO
YES
NO
To check if the refrigeration system is heating feel the braided flexible hose from the heat exchanger water out l et.
What is the
controller
software version?
HPV 3.1, HPV 3.2 or no HPV identification
HPV 4.0 or higher
Is
sensor T3
working?
YES
Replace sensor T3.NO
Test 5
System working ok. The element ci rc u i t s h ould be checked as a temporary condition may have caused the appliance to enter boost mode. If in boost mode and the
element circuit is not operational the cylinder water will
be cold and the system cannot reset itself automatically.
Replace control board.
YES
Is the
evaporator fan
operating?
YES
3.6
NO
1.2
Red flashing
Is
the air flow
obstructed?
NO
Remove obstruction or clean
evaporator.
YES
Note: For more information on LED indication refer to pages 12 and13.
Page 19
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
18
Component Tests 1, 2, 3 & 6
Tests 1 Test 2
240
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the terminals of the terminal block located behind the element access cover. The following measurements should be obtained:
Active & Neutral – 240 volts. Active & Earth – 240 volts. Neutral & Earth – 0 volts.
Warning - Ensure power is isolated before conducting this test.
Using a multimeter on the ohms scale, measure between the terminals of the mechanical thermostat. The following results should be obtained:
1L & 2T – 0 ohms. 3L & 4L – 0 ohms.
Test 3 Test 6
240
240
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the top 2 terminals of the heat pump module terminal block.
Normal voltage is 240 volts.
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the A return and Neutral terminals of the terminal block located behind the element access cover.
Normal voltage is 240 volts.
Note: Refer to page 19 for component test 4 and page 20 for component test 5.
Page 20
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
19
8.49
Component Test 4
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Sensor Strip Testing: Unplug the sensor strip plug from the control board and using a multimeter on the kilo-ohms scale, measure between the pins of the sensor strip plug*. There are six individual tests to be performed as there are six individual sensors contained along the length of the sensor strip (sensors S0 – S5). As the resistance of each sensor will change according to its temperature, the resistance measurements for each sensor will need to be checked against the Temperature/Resistance Table shown below. For this reason it is best to empty the tank of hot water and then measure the cold water temperature at the T&PR so a known temperature datum can then be applied to all sensors which should then in turn all have similar resistance value when tested.
Sensor Test Points
S0 – Between Pins 1 and 9 S1 – Between Pins 2 and 9 S2 – Between Pins 4 and 9 S3 – Between Pins 6 and 9 S4 – Between Pins 3 and 8 S5 – Between Pins 3 and 10
*Note: The sensor strip plug socket test points are quite small, Fine Probe Adapters (part number WH0020082) can be utilised as probe extensions. Alternatively small pins may be used however ensure good contact is made when testing.
Sensor Strip Temperature / Resistance Table
T (°C) R (k) T (°C) R (k) T (°C) R (k) T (°C) R (k) T (°C) R (kΩ)
-10 37.45 10 15.45 30 7.037 50 3.485 70 1.853
-9 35.73 11 14.82 31 6.782 51 3.371 71 1.799
-8 34.11 12 14.22 32 6.537 52 3.262 72 1.743
-7 32.56 13 13.65 33 6.302 53 3.157 73 1.695
-6 31.10 14 13.10 34 6.076 54 3.055 74 1.646
-5 29.71 15 12.58 35 5.86 55 2.957 75 1.589
-4 28.39 16 12.09 36 5.653 56 2.863 76 1.552
-3 27.13 17 11.61 37 5.454 57 2.773 77 1.508
-2 25.94 18 11.16 38 5.264 58 2.686 78 1.465
-1 24.81 19 10.72 39 5.081 59 2.602 79 1.424 0 23.73 20 10.31 40 4.905 60 2.521 80 1.384 1 22.71 21 9.913 41 4.736 61 2.442 81 1.345 2 21.73 22 9.535 42 4.574 62 2.367 82 1.307 3 20.81 23 9.173 43 4.418 63 2.295 83 1.271 4 19.92 24 8.826 44 4.269 64 2.225 84 1.236 5 19.09 25 8.495 45 4.125 65 2.157 85 1.202 6 18.29 26 8.177 46 3.987 66 2.092 86 1.169 7 17.52 27 7.873 47 3.854 67 2.029 87 1.137 8 16.80 28 7.583 48 3.726 68 1.968 88 1.107 9 16.11 29 7.304 49 3.603 69 1.91 89 1.077
Sensor strip plug
pin configuration
Testing the
sensor strip
Page 21
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
20
Component test 5
T Sensor Testing: 310 Series Heat Pumps have five independent thermistors which are
utilised to monitor temperatures at various locations around the system. These thermistors connect to and are monitored by the control board and are known as ‘T sensors’.
All five T sensors are identical and each can be tested as follows:
Warning - Ensure power is isolated before conducting this test.
Unplug the relevant T sensor from the control board and remove the T sensor from its location so its temperature will be the same as the ambient air temperature (As sensor T4 detects the ambient air temperature it may remain in position for this test). Using a multimeter on the kilo­ohms scale, measure between the two pins of the T sensor plug*. As the resistance of each sensor will change according to its temperature, the resistance measurements for each sensor will need to be checked against the Temperature/Resistance Table shown below and the value then compared to the ambient air temperature.
*Note: The sensor strip plug socket test points are quite small, Fine Probe Adapters (part number WH0020082) can be utilised as probe extensions. Alternatively small pins may be used however ensure good contact is made when testing.
Sensor Monitors Part Number
T0 Water temperature leaving the condenser T1 Water temperature entering the condenser T2 Evaporator temperature T3 Compressor discharge temperature T4 Ambient air temperature
056006
T Sensor Temperature / Resistance Table
The table below sets out the resistance of the T sensors for a given water or air temperature.
Temperature
Degrees C
Resistance (All T Sensors)
Kilo-ohms
0 23.73 10 15.45 20 10.31 30 7.037 40 4.905 50 3.485 60 2.521 70 1.853 80 1.384
Page 22
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
21
Fault Finding - Chart 1.2
1.2
Is there
240V at the
element?
NO
Test 6
No Hot Water
Test 8
YES
YES
Is there
240V at the N/C
relay contact?
YES
Is there
6VDC at the relay
coil?
NO
YES
NO
Is the
element resistance
correct?
NO
Test 7
Test 9
Repair faulty wiring.
Appliance operation should then
be checked to determine why the
system entered boost or limp
mode as a second fault may be
present.
Replace element.
Appliance operation should then
be checked to determine why the
system entered boost or limp
mode as a second fault may be
present.
Replace relay.
Appliance operation should then
be checked to determine why the
system entered boost or limp
mode as a second fault may be
present.
Replace control board.
Appliance operation should then
be checked to determine why the
system entered boost or limp
mode as a second fault may be
present.
Repair faulty wiring between heat
pump module electrical
connection plug and element.
Appliance operation should then
be checked to determine why the
system entered boost or limp
mode as a second fault may be
present.
Note: all faults in this chart are in the ‘boost’ or ‘limp mode’ (element) circuit. After determining the fault in the element circuit the appliance
operation should then be checked to determine why the system
entered boost or limp mode as a second fault may be present.
Page 23
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
22
Component Tests 7, 8 & 9
Tests 7 Test 8
240
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the white wire on the heat pump module electrical connection plug and the top terminal of the heat pump module terminal block (Neutral).
Normal voltage is 240 volts.
Warning - Ensure power is isolated before conducting this test.
Disconnect the element wires from the thermostat and terminal block, and using a multimeter on the ohms scale, measure between the two element wires. The following results should be obtained:
2.4kW element: 22 – 26 ohms.
3.6kW element: 15 – 17 ohms.
Test 9
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the DC voltage scale, measure between the two wires on the control board relay plug.
Normal voltage is 6 Volts DC.
Page 24
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
23
Fault Finding - Chart 2
2
YES
Recommend a water heater of
sufficient capacity to meet the
customers needs.
Insufficient Hot Water
NO
Has the
supply of hot water
recently been
depleted?
Boost or limp mode may be indicated by any of the following LED conditions: Red solid or flashing. Red & green flashing together. No LED indication.
Has the
usage pattern
changed
recently?
i.e. additional applianc es or people using hot water
Depending on the ambient
temperature the water heater may
take 3 to 5 hours to recover.
Is the
heater of sufficient
size?
NO
Recommend a hot water usage
pattern that will suit the water
heater and the custom ers needs.
YES
Is the
water supply pressure
more than 80% of the
T&PR rating?
Fit pressure limiting valve if not
already installed.
Existing pressure limiting valve
faulty - replace.
YESYES
Is the
correct T&PR
valve fitted?
NO
NO
YES
Check for crossed water
connection.
Replace T&PR valve.
Replace T&PR valve with one of
correct pressure rating.
Do not use reconditioned T&PR
valves.
Are there
any plumbing leaks,
crossed connections or
dripping taps?
NO
Repair any leaks.
Isolate crossed conne c t i ons .
YES
Is the
heater operating
in boost or limp
mode?
NO
What is the
controller
software version?
YES
3
4
HPV 3.1, HPV 3.2 or no HPV identification
HPV 4.0 or higher
Is the
T&PR valve
continuously
discharging
water?
YES
NO
Is the
heater outlet water
temperature
> 58°C
Is a
tempering valve
fitted?
Are the filters blocked?
NO
Clean or replace filtersYES YES
Is the
tempering valve outlet
water temperature
approx 48°C?
NO
NO
Replace tempering valveNO
YES
System workingYES
NO
Is the
sensor strip
working?
NO
YES
Replace sensor strip
Test 4
The heater outlet water temperature can be measured at the T&PR.
Is the heater
connected to an
off peak tariff?
NO
Off peak connection is unsuitable
for Heat Pump models. Connect
to continuous tariff or off peak 2 if
available.
YES
Note: This assumes that
the hot water to the
tempering valve is above
52°C.
Note: For more information on LED indication refer to pages 12 and 13.
Page 25
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
24
Fault Finding - Chart 3
3
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
What is the
status of the
control boards
LED’s?
Replace control board.
Red solid or Red and Green LED’s indicating simultaneously
Red flashing
Green solid
Green flashing
Test 4
System working. Check operation.
No LED Indication
3.1
NO
YES NO
Are the
relay, circulator,
fan, sensor strip & T
sensors all firmly plugged
into the correct
sockets?
YES
Ensure plugs are firmly plugged
into correct sockets on control
board and that plug pins on
control board are clean and free
from conformal coating.
NO
Test 5
Is the
sensor strip
working?
Replace sensor strip.
Are all
T sensors
working?
Replace faulty T sensor(s).
Ensure water in heat
pump is below 60ºC &
reset heat pump. To reset heat pump switch off, wait for 30 seconds
then switch back on.
Does
compressor
successfully start
after delay?
Note: The compressor
starts 30 seconds after
the circulator.
NO
NO
Is
circulator
operating?
Does
compressor try
to start after
delay?
NO
3.3
3.4
Circulator operation can be checked by feeling circulator brass body for vibration.
Let heat pump
run for ten
minutes or until
red LED flashes.
Does
red LED
flash?
YES
Red LED will flash if system enters boost
mode.
8.3
Has
compressor
recently been
operating?
YES
Compressor internal OTC
may have opened.
Switch off power to heat
pump, wait for ten
minutes then switch
power back on.
YES
NO
3.5
YES
System working. Ambient air
temperature may have been too high or
low for normal operation. Heat pump
may have been too hot after operating
for an extended period due to large
volumes and/or frequent water usage.
NO
YES
YES
LED
Status
after 5
seconds
Green - flashing
Red solid or flashing / Red and Green indicating simultaneously / Green solid
Replace control board.
3.2
Red - flashing
3.8
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 26
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
25
Fault Finding – Chart 3.1
3.1
Are the
thermostat contacts
closed?
YES
Repair faulty wiring.
Replace control board.
Test 2
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
NO
System has operated in limp mode due to a faulty sensor strip (S1 & S4 faults) and has completed a heating
cycle. Water was heated by the
electric element and controlled by
the Robertshaw thermostat to 70ºC.
Replace sensor strip.
Is the
sensor strip
working?
NO
Replace control board.
YES
Test 4
Are the
sensor strip plug
pins clean?
Ensure sensor strip plug pins and
control board socket are clean
and free from conformal coating.
NO
YES
Fault Finding – Chart 3.2
3.2
T0 is monitoring water out of the heat exchanger
Switch off heat pump & allow sensor T0 to cool
below 80ºC. When
sufficiently cool switch
heat pump back on.
Is red
LED flashing after
5 seconds?
Replace control board
YES
Is
Green LED
flashing?
NO
YES
Circulator operation can be checked by feeling circulator brass body for vibration.
NO
Has
sensor T0 cooled
to below
80ºC?
YES
NO
Is circulator
operating?
3.3
NO
3.8
YES
Replace control board
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
Page 27
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
26
Fault Finding – Chart 3.3
3.3
Ensure circulator is firmly plugged
into correct socket on control
board and that plug pins on
control board are clean and free
from conformal coating.
NO
YES
Is the
circulator motor
resistance
correct?
Is 240V
present at the
circulator?
Test 10
Is the
circulator plug firmly
plugged into correct
socket?
NO
Check circulator impellor for
restriction or siezure.
YES
Replace circulator
YES
NO
Test 11
Replace control board
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
Component Tests 10 & 11
Test 10 Test 11
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the circulator plug terminals at the control board.
Normal voltage is 240 volts. Note: As the control board controls the
speed of the circulator by pulsing the electrical supply to the circulator an analogue multimeter may indicate between 180 – 240V.
Warning - Ensure power is isolated before conducting this test.
Unplug the circulator connection plug from the control board and using a multimeter on the ohms scale, measure between the two circulator connection plug terminals.
A reading of approximately 75.3 ohms should be obtained.
Page 28
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
27
Fault Finding – Chart 3.4
3.4
Is 240V
present at the
compressor
terminals?
NO Faulty compressor wiring.
YES
Are
the compressor
winding resistances
correct?
Test 12
Replace compressor
NO
Faulty compressor and/or
compressor capacitor wiring.
YES
Note: Tests 12 & 13 must be performed after waiting for the 30 second delay after starting of the
circulator and cannot be performed
whilst the red LED is flashing.
Test 14
Is the
compressor
capacitor working?
Replace compressor capacitorNO
YES
Is 240V
present at the control
board compressor
terminals?
YES
Test 15
Test 13
Replace control boardNO
Is there
6VDC at the relay
coil?
Is the
relay plug plugged
into the control
board?
NO
YES
Plug in relay plug at control board.NO
Ensure plug pins are clean of
conformal coating and are making
contact. If plug & pins are ok
replace the control board.
YES
Test 9
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
Are
the compressor
winding resistances
correct?
Compressor internal ECO
may have tripped open
circuiting the compressor
windings. Wait ten
minutes for ECO to cool
and auto reset.
NO
Is the
compressor
temperature 150ºC
or hotter?
Reset heat pump and run
system until compressor
ECO trips again.
YES
Test 14
8.3
YES
NO
Note: To reset heat
pump switch power off,
wait for 30 seconds
then switch back on.
Note: Compressor internal
ECO is auto trip & auto
reset & is not a replaceable
component.
ECO Opens @ 150ºC
ECO Closes @ 90ºC
Page 29
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
28
Component Tests 12 – 15
Tests 12 Test 13
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Remove the compressor electrical access cover and using a multimeter on the AC voltage scale, measure between the red and blue wires.
Normal voltage is 240 volts.
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the control board compressor output terminal and the top terminal of the heat pump module terminal block (Neutral).
Normal voltage is 240 volts.
Test 14 Test 15
Warning - Ensure power is isolated before conducting this test.
Remove the compressor electrical access cover and mark and disconnect terminal wiring. Using a multimeter on the ohms scale, measure between the compressor terminals. The following run and start winding results should be obtained.
(Run) Red & Blue terminals – 2.2 ohms (Start) Red & Black terminals – 3.2 ohms
Warning - Ensure power is isolated before conducting this test.
Disconnect the wiring to the compressor capacitor and using a multimeter on the capacitance (µF) scale measure between the two capacitor terminals.
Normal capacitance is 35 micro Farads (35µF).
Page 30
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
29
Fault Finding – Chart 3.5
3.5
Is the
temperature at
sensor T4
< 2ºC?
System functioning correctly and
should operate in boost mode
until temperature at T4 rises
above 2ºC at which time the heat
pump will reset and start back at
sequence 0.
YES
T4 is ambient
air sensor
Is the
temperature at
sensor T2
< 2ºC?
NO
3.6
YES
T2 is evaporator
sensor
Is the
ambient air
temperature <
5
ºC?
NO
System functioning correctly and
should operate in boost mode
until evaporator temperature rises
above 2ºC at which time the heat
pump will reset and start back at
sequence 0.
YES
Is
the ambient air
temperature above
50ºC?
System working ok. Ambient air
temperature too hot for normal
heat pump operation.
YES
NO
NO
T2 temperature can
be measured by
inserting thermometer
probe into evaporator
fins next to sensor T2.
Is the
circulator water
flow direction
correct?
Reinstall circulator so flow is
directed towards heat exchanger.
NO
YESYES
Is the
water system
blocked?
NO
YES
Clear blockage in water system at
circulator, heat exchanger,
dropper tubes or flexible hoses.
YES
NO
Are the
refrigeration
system pressures
correct?
YES
YES
8.1
NO NO
Tests 19 & 20
Is the
circulator impellor
functioning?
Has the
cold water dropper
tube fallen off?
Replace cold water dropper tube.
Is there
an air lock in the
water system
Repair or replace circulator
impellor.
NO
Bleed air from water outlet at
flexible hose union.
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
Warning! Ensure water escaping from flexible hose is caught in a container and does not escape or sensor strip damage may occur.
3.7
Page 31
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
30
Fault Finding – Chart 3.6
3.6
Did the
evaporator fan
come on with the
compressor?
YES
Ensure evaporator fan is firmly
plugged into correct soc ket on
control board and that pl ug p i ns
on control board are clean and
free from conformal coating.
Are the
fan motor winding
resistances
correct?
Is 240V
present at the fan
terminals?
NO
YES
Is the
evaporator fan firmly
plugged into correct
socket?
NO NO
Replace control board.YES
Replace evaporator fan motor.NO
Is the
fan capacitor
working?
Replace capacitor.
Replace faulty contro l board.
YES NO
YES
Test 17
Test 18
Test 16
Is
the air flow
obstructed?
NO
Remove obstruction.YES
Clean dirty evaporator.
Appliance installe d i n enclosed
room contrary to installation
instructions.
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification. Also HPV 4.0 or higher from fault finding chart 1.1 only
Is the
fan wiring faulty
or incorrect?
NO
Repair or replace faulty wiring.YES
Fault Finding – Chart 3.7
Note: To reset heat pump switch power off,
wait for 30 seconds then switch back on.
Note: Compressor internal
ECO is auto trip & auto
reset & is not a replaceable
component.
Opens @ 150ºC
Closes @ 90ºC
3.7
Replace compressor
NO
Test 15
Replace faulty control board.
System in boost or limp mode - Software version HPV 3.1, HPV 3.2 or no HPV
identification
Are
the compressor
winding resistances
correct?
Replace compressor capacitor.
Compressor internal ECO may have
tripped open circuiting the compressor
windings. Wait ten minutes for ECO
to cool and auto reset.
NO
Is the
compressor
temperature 150ºC
or hotter?
Reset heat pump and run
system until compressor
ECO trips again.
YES
Test 14
8.3
YES
NO
YES
Is the
compressor
capacitor working?
Are
the compressor
winding resistances
correct?
Test 14
NO
Replace compressor capacitorYES
Page 32
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
31
Component Tests 16, 17 & 18
Tests 16 Test 17
240
Warning – ‘Live’ equipment wear Personal Protective Equipment when conducting this test.
Using a multimeter on the AC voltage scale, measure between the third and fourth terminals down from the top on the heat pump module terminal block.
Normal voltage is 240 volts.
Warning - Ensure power is isolated before conducting this test.
Mark and disconnect fan wiring at the heat pump module terminal block and using a multimeter on ohms scale, measure between the disconnected fan wires. The following run and start winding results should be obtained.
(Run) Black & Brown wires – 184 ohms (Start) Black & Blue wires – 238 ohms
Test 18
Warning - Ensure power is isolated before conducting this test.
Mark and disconnect the fan capacitor wiring at the heap pump module terminal block and using a multimeter on the capacitance (µF) scale measure between the two capacitor wires.
Normal capacitance is 2 micro Farads (2µF).
Note: Refer to page 45 for component tests 19 & 20.
Page 33
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
32
Fault Finding – Chart 4
System in boost or limp mode - Software version 4.0 or higher
Boost or limp mode will be indicated by any of the following LED conditions:
4.3
What is the
status of the
control boards
LEDs?
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.2
Red 1 flash
Red 2 flash
Red 3 flash
Red 4 flash
Red 5 flash
Red 6 flash
Red 7 flash
Red & Green 1 flash
Red & Green 2 flash
Red & Green 3 flash
Red & Green 4 flash
Red & Green 5 flash
No LED indication
4
Flashing frequency: Different combinations of flashing LED’s (one Red & one Green) will indicate the status of the heat pump. Each flash in a series will last for 0.5 seconds and is separated by 0.5 seconds between flashes . Each series of flashes is separated by 2 seconds.
Notes:
Green solid - Heat pump operating in sequ enc e 0 (standb y ) Green 1 flash - Compressor delay start (T3 > 60ºC in seq 0) Green 2 flash - Heat pump operating in sequence 2
Green 3 flash - Heat pump operating in sequence 3 Green 4 flash - Heat pump operating in sequence 4
Other LED indication: If no fault is present the Green LED will flash to indicate the following:
4.1
Red solid
Red solid or flashing. Red & Green flashing simultaneously . No LED indication.
For other LED indication refer to notes below.
For more information on LED indication refer to pages 12 and13.
Page 34
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
33
Fault Finding – Chart 4.1
4.1
Is
sensor T4
firmly plugged
into correct
socket?
NO
Ensure sensor T4 is firmly
plugged into correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Red solid
T4 < 0
ºC
YES
Is the
temperature at
sensor T4
< 2ºC?
NO
YES
Is
sensor T4
working?
Test 5
Replace sensor T4NO
Replace control boardYES
T4 is ambient
air sensor
Note: When T4 < -0ºC the system will enter boost mode. When in boost mode due
to this operation the system will reset and start at sequence 0 when T4 > 2ºC
System functioning correctly and
should operate in boost mode
until temperature at T4 rises
above 2ºC at which time the heat
pump will reset and start back at
sequence 0.
Note: Refer to page 5 for T sensor plug socket location on control board.
Fault Finding – Chart 4.2
4.2
Is the
sensor strip
working?
NO
Red 1 flash
sensor strip fault
Is the
sensor strip
firmly plugged
into the correct
socket?
YES
NO
Test 4
Replace control boardYES
Ensure sensor strip is firmly
plugged into correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Replace sensor strip
Page 35
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
34
Fault Finding – Chart 4.3
4.3
NO
Red 2 flash
T0 >80ºC
YES
YES
NO
Test 5
T0 is monitoring
water out of the heat exchanger
Is
sensor T0
firmly plugged
into correct
socket?
Is
sensor T0
working?
Replace sensor T0
Switch off heat pump & allow sensor T0 to cool
below 80ºC. When
sufficiently cool switch
heat pump back on.
Does red
LED immediately
go to 2 flash?
Replace control board
YES
Is circulator
operating?
NO
Blockage of water system at
circulator, heat exchanger,
dropper tubes or flexible hoses.
Loose, damaged or jammed
circulator impellor.
YES
Circulator operation can be checked by feeling circulator brass body for vibration.
NO
Ensure circulator is firmly plugged
into correct socket on control
board and that plug pins on
control board are clean and free
from conformal coating.
NO
YES
Is the
circulator motor
resistance
correct?
Is 240V
present at the
circulator?
Test 10
Is the circulator plug firmly plugged into correct
socket?
NO
Check for loose, damaged or
jammed circulator impellor.
YES
Replace circulator
YES
NO
Test 11
Has
sensor T0 cooled
to below
80ºC?
YES
NO
Replace control board
Ensure sensor T0 is firmly
plugged into correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Is there
an air lock in the
water system?
NO
Bleed air from water outlet at
flexible hose union.
YES
Warning! Ensure water escaping from flexible hose is caught in a container and does not escape or sensor strip damage may occur.
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 36
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
35
Fault Finding – Chart 4.4
4.4
Is
sensor T2
firmly plugged
into correct
socket?
NO
Ensure sensor T2 is firmly
plugged into correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Red 3 flash
T2 < -3ºC
Is the
temperature at
sensor T2
< 2ºC?
NO
Is
sensor T2
working?
Test 5
Replace sensor T2NO
Replace control boardYES
T2 is evaporator
sensor
System functioning correctly and
should operate in boost mode
until evaporator temperature rises
above 2ºC at which time the heat
pump will reset and start back at
sequence 0.
Did the
system reset &
operate in normal
heat pump
mode?
Is the
ambient air
temperature <
5
ºC?
YES
YES
Is the
evaporator fan
running?
NO
YES
Note: Compresor
will not start until 30 seconds after
the circulator
YES
Ensure evaporator fan is firmly
plugged into correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Are the
fan motor winding
resistances
correct?
Is 240V
present at the fan
terminals?
YES
Is the
evaporator fan firmly
plugged into correct
socket?
NO NO
NO
Replace control boardYES
Replace evaporator fan motorNO
Is the
fan capacitor
working?
Replace capacitor
Repair faulty wiring
NO
NO
YES
YES
Test 17
Test 18
T2 temperature can
be measured by
inserting thermometer
probe into evaporator
fins next to sensor T2.
Test 16
Note: When T2 < -3ºC the system will enter boost mode. When in boost mode due
to this operation the system will reset and start at sequence 0 when T2 > 2ºC
Is
the air flow
obstructed?
NO
Remove obstruction.YES
YES
Clean dirty evaporator.
Appliance installed in enclosed
room contrary to installation
instructions. Appliance is suitable
for outdoor installation only.
Raise temperature of sensor T2 to
above 2ºC by removing from
evaporator and holding probe between
thumb & fingers. Heat pump should
auto reset to sequence 0 when T2
raises above 2ºC. Ensure sensor
probe is reinserted into evaporator on
completion of testing procedure.
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 37
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
36
Fault Finding – Chart 4.5
4.5
Is 240V
present at the
compressor
terminals?
NO Faulty compressor wiring.
Red 4 flash
T3 is not > T4 +
15
ºC in sequence 3
YES
Does
compressor start
or try to start after
delay?
YES
Are
the compressor
winding resistances
correct?
Test 12
Replace compressorNO
Faulty compressor and/or
compressor capacitor wiring.
YES
Note: T3 is compressor discharge se ns or. T4 is ambient air sensor. This check is performed in sequence 3 to
ensure that the sealed refrigerant system is operating (heating).
8
Are
sensors T3 & T4
firmly plugged into
the correct
sockets?
Ensure sensors T3 & T4 are firmly
plugged into correct sockets on
control board and that plug pins
on control board are clean and
free from conformal coating.
NO
Note: Tests 12 & 13 must be
performed after waiting for the 30
second delay after starting of the
circulator and cannot be perf ormed
whilst the red LED is flashing.
Test 14
NO
Is the
compressor
capacitor working?
Replace compressor capacitorNO
Note: The compressor starts 30
seconds after the circulator.
YES
Are
sensors T3 & T4
working?
Replace faulty sensor(s)NO
Ensure water in heat pump is below 60ºC & reset heat pump. To reset heat pump switch off, wait for 30 seconds then switch back on.
YES
Does red
LED immediately
go to 4 flash?
NO
YES
Is 240V
present at the control
board compressor
terminals?
YES
Test 15
Test 13
Test 5
Replace control boardNO
Replace control board
Is there
6VDC at the relay
coil?
Is the
relay plug plugged
in to the control
board?
NO
YES
Plug in relay plug at control board.NO
Ensure plug pins are clean of
conformal coating and are making
contact. If plug & pins are ok
replace the control board.
YES
Test 9
YES
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 38
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
37
Fault Finding – Chart 4.6
4.6
Is 240V
present at the
compressor
terminals?
NO Faulty compressor wiring.
YES
Does
compressor start
or try to start after
delay?
NO
YES
Are
the compressor
winding resistance s
correct?
Test 12
Replace compressorNO
Faulty compressor and/or
compressor capacitor wiring.
YES
8
Are
sensors T0 & T1
firmly plugged into
the correct
sockets?
Ensure sensors T0 & T1 are
plugged into correct sockets on
control board and that plug pins
on control board are clean and
free from conformal coating.
NO
Note: Tests 12 & 13 must be
performed after waiting for the 30
second delay after s t a rting of the
circulator and cannot be performed
whilst the red LED is flashing.
Test 14
Is the
compressor
capacitor
working?
Replace compressor capacitorNO
Note: The
compressor starts 30
seconds after the
circulator.
YES
Are
sensors T0 & T1
working?
YES
Replace faulty sensor(s)NO
Ensure water in heat pump is below 60ºC & reset heat pump. To reset heat pump switch off, wait for 30 seconds then switch back on.
YES
Does red
LED immediately
go to 5 flash?
NO
YES
Is 240V
present at the control
board compressor
terminals?
YES
Test 15
Test 13
Test 5
Replace control boardNO
Replace control board
Red 5 flash
T0 - T1 < 8ºC in
sequence 4
Note: T0 is heat exchanger water outlet sensor. T1
is heat exchanger water inlet sensor. This check is performed in sequence 4 to ensure that the sealed
refrigerant system is operating (heating).
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 39
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
38
Fault Finding – Chart 4.7
4.7
Is the sensor strip & sensor T1 firmly plugged into
the correct
sockets?
Ensure sensor strip & sensor T1
are both firmly plugged into the
correct sockets on control board
and that plug pins on control
board are clean and free from
conformal coating.
NO
YES
Is
sensor T1
working?
Replace sensor T1NO
YES
Test 5
Replace cold water dropper tube.
Red 6 flash
T1 > S4 + 7ºC in sequence 3 or 4
Note: T1 is heat exchanger water inlet sensor. S4 is thermistor sensor strip sensor.
This check is performed in sequence 3 or 4 to ensure that the circulator is operating.
Is
sensor strip
working?
YES
Replace sensor stripNO
Is the
circulator water
flow direction
correct?
YES
NO
Reinstall circulator so as flow is
directed towards heat exchanger.
Has the
cold water dropper
tube fallen off?
YES
Replace control board.NO
Test 4
Is there
an air lock
in the water
system?
Bleed air from water system at
water outlet flexible hose union.
YES
NO
Warning! Ensure water escaping from flexible hose is caught in a container and does not escape or sensor strip damage may occur.
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 40
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
39
Fault Finding – Chart 4.8
4.8
NO
YES
System working ok. Ambie nt air
temperature too hot for normal
heat pump operation.
YES
Test 5
Appliance may have been
operating for an extended period
due to large volume and/or
frequent water usage.
Red 7 flash
T3 > 110ºC in
sequence 3 or 4
Note: T3 is compressor
discharge sensor.
NO
YES
Is
sensor T3
firmly plugged
into correct
socket?
YES
NO
NO
Test 19
Ensure sensor T3 is firmly
plugged into the correct socket on
control board and that plug pins
on control board are clean and
free from conformal coating.
Replace sensor T3
Is
sensor T3
working?
Is
the ambient air
temperature above
50ºC?
8.2
Fit pressure gauge to
high side of
refrigerant system
Is the
head pressure
excessive?
Has
sensor T3 cooled
to below
60ºC?
Switch off heat pump & allow sensor T3 to cool
below 60ºC. When
sufficiently cool switch
heat pump back on.
NO
YES
Note: Refer to page 5 for T sensor plug socket location on control board.
Page 41
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
40
Fault Finding – Charts 4.9 to 4.13
4.9
NO
T sensor fault
YES
NO
Test 5
Is
T sensor
firmly plugged
into correct
socket?
Replace T sensor.
Ensure T sensor is firmly plugged
into correct socket on control
board and that plug pins on
control board are clean and free
from conformal coa ti n g.
4.10 4.11 4.12 4.13
Replace control board.
Is T sensor working?
T0 fault.
T0 is monitoring
water out of the
heat exchanger.
T1 fault.
T1 is monitoring
water into the
heat exchanger.
T2 fault.
T2 is monitoring
the evaporator
temperature.
T3 fault.
T3 is monitoring
the compressor
discharge temp.
T4 fault.
T4 is monitoring
the ambient air
temperature.
YES
Note: Refer to page 5 for T sensor plug socket location on control board.
Fault Finding – Chart 4.14
4.14
Are the
thermostat contacts
closed?
YES
Repair faulty wiring.
Replace control board.
Test 2
System in boost or limp mode - Software version 4.0 or higher
NO
System has operated in limp mode
due to a faulty sensor strip (S1 & S4
faults) and has completed a heating
cycle. Water was heated by the
electric element and controlled by
the Robertshaw thermostat to 70ºC.
Replace sensor strip.
Is the
sensor strip
working?
NO
Replace control board.
YES
Test 4
Are the
sensor strip plug
pins clean?
Ensure sensor strip plug pins and
control board socket are clean
and free from conformal coating.
NO
YES
Is there
240V at the
control board &
relay?
YES
Wiring incorrect. Check control board wiring loom plug (lower thermostat to control
board wiring loom).
NO
Test 3
Page 42
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
41
Fault Finding – Chart 5
5
Is
the T&PR
valve continuously
discharging
water?
Existing pressure limiting valve
faulty.
Fit pressure limiting valve if not
already fitted.
Replace T&PR valve if required.
Is the
leak from the
electrical access
cover?
NO
YES
NO
Is the
leak from
the element barrel
fitting?
YES
Check for loose element bolts.
Remove element and replace
gasket.
YES
NO
Remove anode and repair leak
using Teflon thread tape.
YES
Is the
correct T&PR valve
fitted?
Replace T&PR valve with one of
the correct pressure rating.
Do NOT use reconditioned
T&PR valves.
NO
Check for crossed water
connection.
Replace T&PR valve.
YES
Is the
water supply
pressure above
800kPa?
YES
NO
Is
the water leak
intermittent?
NO
Leak is probably condensate draining from the evaporator
condensate tray.
Normal Operation.
YES
Are
the anode/s
leaking?
Inner Cylinder leaking
Check for hot spots on the jacket
Replace water heater.
NO
Is the leak from the heat pump water
system?
NO
Tighten or remake flexible hose
connection(s).
Repair or replace leaking heat
exchanger.
Replace leaking circulator.
Remake or replace dropper tube
connections.
YES
Leaking water heater
Page 43
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
42
Fault Finding – Chart 6
6
Fan loose on motor shaft, remove
assembly and tighten.
Fan motor faulty - Replace.
Is the
noise water
hammer?
NO
NO
Is the
noise only evident
when water is flowing
through the
heater?
YES
Cylinder contracting due to pressure
release when hot tap opened.
This can also be accompanied by a
creaking or cracking sound.
Normal Operation.
NO
Check for restrictions in pipe work, faulty
valves, loose plumbing or other
appliances i.e. washing machine or
dishwasher.
Fit 600kPa pressure limiting valve.
YES
Is
the noise
mechanical or air
related?
Normal noise level during operation is
approximately 52dB at 1.5 metres.
If this level is affecting neighbors a timer
should be fitted to prevent operation
during the affected hours or to comply
with local council regulations
AIR
Is the
noise from the
evaporator
fan?
Is the noise only evident during the heating
cycle?
Check for loose fittings or pipe work in
the refrigeration system.
Check for possible mechanical failure in
compressor
YES
Is the
water pressure
more than 80% of the
T&PR valve
rating?
Check all other appliances or valves that
can generate noise i.e. washing
machines, dishwashers, ball valves etc.
NO
YES
Mechanical
Refer to water hammer causes in the
‘Common Complaints’ section.
Check for a faulty stop cock, non-return
valve or T&PR valve.
NO
Is the
noise a
metallic popping
sound?
YES
NO
YES
Noisy water heater
Page 44
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
43
Fault Finding – Chart 7
7
Is the
reading below 1
Megaohm?
Replace compressor.
NO
YES
Is the
reading below 1
Megaohm?
Replace fan motor.YES
Replace element.
Replace thermostat.
Replace circulator.
Replace control board.
Check for pinched or
damaged wiring touching
the heater jacket.
YES
NO
YES
NO
NO
YES
NO
YES
Is the
reading below 0.66
Megaohms?
Is the
reading below 1
Megaohm?
Is the
reading below 1
Megaohm?
Is the
reading below 1
Megaohm?
NO
Disconnect the power supply
wiring to the control board at
the terminal block and
megger between each control
board wire and earth.
Disconnect the wiring to the
compressor and megger
between each compressor
terminal and earth.
Disconnect the wiring to the
fan motor at the terminal
block and megger between
each fan wire and earth.
Disconnect the wiring to the
element at the thermostat
and megger between each
element wire and earth.
Disconnect the remaining
wiring from the thermostat
and megger between each
thermostat terminal and
earth.
Disconnect the wiring plug to
the circulator at the control
board and megger between
each circulator wire and
earth.
Blowing fuse/circuit breaker
Note: The control board has an internal resistor that will prov ide a Megaohm reading of
0.66 Megaohms when an insulation test is conducted on the con trol boa rd or the appliance with control board connected.
Page 45
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
44
Fault Finding – Chart 8 - 8.3
8.3
Replace compressor.
Test 19
Refrigeration system fault finding
Is the
head pressure
excessive?
Test 21
NO
Fit pressure gauge
to high side of
refrigerant system.
Allow time for the
system to equalise.
Did
the system
equalise?
Is the system
taking too long to
equalise?
Possible restriction in system,
Locate and repair.
Possible system overcharge,
adjust refrigerant charge.
TX valve metering incorrectly ,
adjust or replace TX valve.
NO
YES
Is the
TX valve
operating?
NO
Locate blockage in refrigerant
system and repair.
YES
Adjust TX valve (refer to
component replacement
procedure 23 “TX valve
adjustment”) or replace if faulty.
NO
System overcharged, adjust
refrigerant charge.
YES
YES
8.28
Fit pressure gauges to high and low side
of refrigerant system.
Is the
Suction pressure
low/vacuum or
excessively
high?
Test 20
Locate and repair leak in
refrigerant system.
High side head pressure excessive (Test 18)
YES
High
Low
NO
8.1
Page 46
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
45
Component Test 19
Warning – “Live” equipment. Wear Personal Protective Equipment when conducting this test.
1800 kPa
Fit gauges to the high side access pipe and observe the discharge pressure.
Typical high pressure range is 1400­2100 kPa depending on cylinder water temperature. The high pressure range should be within 1700-1800 kPa when heating from cold.
Component Test 20
Warning – “Live” equipment. Wear Personal Protective Equipment when conducting this test.
400 kPa
Check for persistent air bubbles through sight glass of receiver/filter drier. Fit gauges to the low side access pipe and observe the suction pressure.
The suction (low side) pressure is very dependent on ambient conditions however the low pressure range is typically between 200-600 kPa.
200 kPa @ 10°C ambient. 600 kPa @ 45°C ambient.
A suction pressure of less than 200kPa may indicate a refrigerant leak or a malfunctioning TX valve.
Note: Refer to the following section for more information on refrigerant charge and refrigerant charge fault indications.
Refrigerant Charge
Indication of correct refrigerant charge
The receiver/filter dryer sight glass should show clear liquid, a few small bubbles might be visible during initial start up of the system or when the TX valve opens quickly, however clear liquid should return shortly after. Compressor current draw should be between 5 – 6 Amps and system pressures should be within normal ranges (refer to component test 19 (above) and component test 20 (above) for typical system pressures).
Page 47
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
46
Indication of undercharged system
Bubbles persist for a significant amount of time or repeat often. Compressor current draw is low (<5 Amps) together with low system pressures. If sight glass indicates clear gas, not liquid, and current draw is very low combined with low discharge line temperature then the system is totally empty. Note: Unusual current draw or low suction pres sure can be a sign of other problems such as a blockage or malfunctioning TX valve.
Indication of overcharged system
Continuous liquid through sight glass, evaporator tends to flood, head pressure high, compressor current draw high (>6 Amps) and compressor noisy. Note: Unusual current draw or high head pressure can be a sign of other problems such as a blockage or malfunctioning TX valve.
Component Test 21
Warning – “Live” equipment. Wear Personal Protective Equipment when conducting this test.
Fit gauges to low side access pipe. Remove the insulation from the TX valve sensor on the suction line.
Hold the sensor by hand to increase the heat detected by the sensor. The TX valve should open with the following results:
1. Flow of refrigerant through sight glass of receiver/filter dryer should increase.
2. Evaporator pressure should increase.
3. Suction line should become cooler.
Remove hand and replace insulation, the TX valve should close, resulting in the reversal of the above results.
Electrical Insulation Testing
There are three basic test procedures that should be carried out when the operation and function of a heat pump water heater’s electrical system is in doubt.
Wear Personal Protective Equipment when conducting step 1 of this procedure to reduce the risk of electric shock. Refer to Rheem safety procedure on electrical testing.
Insulation resistance of the water heater Neutral Circuit. (Reading not to be below
0.66 Mega ohm).
1. Isolate power to the water heater at the isolation switch. Confirm with multi-
meter across terminal block Active and Neutral, then Active and Earth, then Neutral and Earth that voltage is not present.
2. Once satisfied, disc onnect the Active and Neutral wires from the water heater terminal block.
3. Connect megger leads to the Neutral of the water heater wiring and Earth.
4. Operate megger. A reading above 0.66 Mega ohm should be obtained.
5. If a reading below 0.66 Mega ohm is indicated, all component parts will need to be individually tested to locate the fault. Refer to Fault Finding Chart 7 on page 43.
Page 48
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
47
Insulation resistance of the water heater Active Circuit (reading not to be below 0.66 mega-ohm).
6. Connect megger leads to the Active of the water heater wiring and Earth.
7. Operate megger. A reading above 0.66 Mega ohm should be obtained.
8. If a reading below 0.66 Mega ohm is indicated, all component parts will need to be individually tested to locate the fault. Refer to Fault Finding Chart 7 on page 43.
To check “Continuity” of the Heat Pump electrical circuit.
9. Set megger to resistance scale or multimeter to x1 resistance scale.
10. Measure between the Active and Neutral terminals on the power supply terminal block located behind the electrical/element access cover. The resistance should be approximately 24 ohms. If a reading outside this resistance is measured all electrical component parts will need to be individually tested to locate the fault. Refer to Specifications table on page 3 for indicative resistance values of components.
11. Reconnect active cable to ‘A’ terminal and neutral cable to ‘N’ terminal at heater terminal block.
12. Replace fuse. Note: If continuing with any diagnostic procedures do not replace
the fuse.
Component Replacement Procedures – Water Heater
Draining the Water Heater (Procedure 1)
Elevated temperatures may be present during the draining process. Wear Personal Protective Equipment to prevent scalds or burns.
Wear Personal Protective Equipment when conducting step 3 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power and water supplies to the water heater.
2. Relieve pressure from the water heater through the T & PR valve or a hot tap.
3. Remove the lower electrical/element access cover and confirm with a multi-
meter between the Active and Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
4. Disconnect the cold water supply pipe
5. Fit a drain hose to the cold-water connection and run the other end to a drain or safe
location.
6. Open the temperature and pressure relief valve to allow air into the system.
Page 49
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
48
Temperature and Pressure Relief Valve (Procedure 2)
Never fit a T&PR valve with a rating higher than that indicated on the water heater rating plate. Do not use reconditioned T&PR valves.
1. Isolate the power and water supplies to the water heater.
2. Relieve pressure from the water heater through the T & PR valve or a hot tap.
3. Remove the drain line from the T&PR valve.
4. Unscrew the T&PR valve and remove.
A quantity of hot water will discharge from the tank during this process. Wear Personal Protective Equipment to prevent scalds or burns.
5. Confirm the replacement T&PR valve is the correct rating and refit using thread tape.
6. Refit the drain line.
7. Close the hot tap and restore water supply.
8. Check T&PR valve thread for leaks.
9. Operate the T&PR valve lever to reset relief drain.
10. Purge air from the system through hot taps.
11. Restore the power supply to the water heater.
Dip Tube (Procedure 3)
1. Isolate the power and water supplies to the water heater.
2. Relieve pressure from the water heater through the T & PR valve or a hot tap.
3. Disconnect the hot water line from the outlet of the water heater.
A quantity of hot water will discharge from the outlet during this process. Wear Personal Protective Equipment to prevent scalds or burns.
4. Using a flat blade screwdriver gently split the outer rim at the top and bottom of the dip
tube face and prise the dip tube out of the cylinder fitting.
5. Fit the replacement dip tube into the cylinder fitting ensuring the flat lines up with the
fitting (dip tube facing up) and gently drive the dip tube into the fitting a short distance.
6. Reconnect the plumbing; this will push the dip tube into the correct location.
7. Restore the water supply and purge air from the system through hot taps.
8. Restore the power supply.
Mechanical Thermostat (Procedure 4)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater and remove access cover.
2. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Disconnect the wiring to the thermostat.
4. Slide the thermostat out from under the retaining clamp.
5. Remove any scale from the cylinder surface.
6. Fit the replacement thermostat under the clamp.
7. Reconnect the wiring as per the circuit wiring diagram on page 11.
8. Conduct an electrical insulation test. Refer to page 46.
9. Refit the access cover and restore the power supply.
Page 50
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
49
Anode (Procedure 5)
Elevated temperatures may be present during anode removal process. Wear Personal Protective Equipment to prevent scalds or burns.
1. Isolate the power and water supplies to the water heater.
2. Relieve pressure from the water heater and drain approximately 10 litres of water
from the cylinder through the T & PR valve.
3. Remove the air inlet louver (Refer to Procedure 10).
4. Remove the refrigeration section jacket top.
5. Remove the anode cap(s). Access is provided through the refrigeration plant chassis.
6. Using a 27mm tube or socket spanner remove the anode(s).
7. Apply thread seal tape to replacement anode, refit and tighten. Note: It may be
necessary to cut the anode to length prior to fitting. Refer to page 3 for the correct anode length.
8. Restore water supply and check for leaks.
9. Refit the anode cap(s), jacket, air inlet louver and jacket top and restore power.
Heating Unit (Procedure 6)
Wear Personal Protective Equipment when conducting step 1 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Drain the water heater. Refer to procedure 1.
2. Remove the access cover and disconnect the wiring from the terminal block. Disconnect the wiring to the heating unit from the thermostat. Unclip the terminal block from the jacket and remove thermostat and terminal block.
3. Remove the two screws retaining the thermostat clamp.
4. Loosen the two lower screws slightly. When water is below the heating unit level, refit the cold water supply pipe.
5. Remove the two lower screws and withdraw the heating unit carefully making sure the loop does not catch and open up inside the cylinder.
6. Clean around the cylinder fitting, fit gasket to replacement heating unit and insert into water heater. Note: Ensure the element is installed in the same orientation.
7. Replace screws and thermostat clamp, and then tighten.
8. Close T&PR valv e, and open all hot taps. Restore the cold water supply and purge air through hot taps, close each hot tap as water runs freely.
9. Check heating unit for leaks.
10. Refit thermostat and terminal block and reconnect the wiring as per the circuit wiring diagram on page 11.
11. Refit the access cover.
12. Restore power supply to the water heater.
Page 51
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
50
Dropper Tube(s) (Procedure 7)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
In order to replace the dropper tube(s) the heat pump (refrigeration) module must be removed and refitted. Due to the weight of the unit (approx 45kgs) this is a two man job.
A quantity of hot water may discharge from the flexible hose(s) during this procedure. Wear Personal Protective Equipment to prevent scalds or burns and ensure all escaping water is caught in a container to prevent the sensor
strip from becoming water damaged.
1. Isolate the power and water supplies to the water heater.
2. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Relieve pressure from the water heater and drain approximately 10 litres of water
from the cylinder through the T & PR valve.
4. Remove the refrigeration module (refer to procedure 9 steps 4 - 9).
5. Remove the sensor strip wiring grommet from the jacket top.
6. Loosen the main power wiring cable clamp screw.
7. Carefully remove the jacket top. Note: During the foaming process the foam adheres to
the jacket top which can make it difficult to remove.
8. Clear foam from around the dropper tube(s) ¾” to ½”brass fitting(s).
9. Using an extra deep 35mm socket unscrew the dropper tube(s) brass fitting(s) in an
anticlockwise direction. Note: the 35mm socket must have a minimum internal nut clearance depth of 40mm.
10. Withdraw brass adapter(s) and dropper tube(s) from cylinder. Note: dropper tube is a
push fit into the tapered section of the brass adapter, simply pull dropper tube to remove.
11. Complete reassembly in reverse order of above using thread tape on dropper tube(s)
brass adapter(s) threaded section.
Page 52
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
51
Sensor Strip (Procedure 8)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
In order to replace the sensor strip the heat pump (refrigeration) module must be removed and refitted. Due to the weight of the unit (approx 45kgs) this is a two man job.
1. Isolate the power and water supplies to the water heater.
2. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the refrigeration module (refer to procedure 9).
4. Remove the sensor strip wiring grommet from the jacket top.
5. Loosen the main power wiring cable clamp screw.
6. Carefully remove the jacket top. Note: During the foaming process the foam adheres to
the jacket top which can make it difficult to remove.
7. Carefully remove the foam insulation from around the sensor strip wiring until the
sensor strip pocket can be seen (approx 150 – 200mm down), adjacent to the cylinder top. Note: Save the foam insulation for repacking in step 14 of this procedure.
8. Carefully grip the sensor strip and slide the sensor strip out, ensure that the sensor
strip pocket has also not been gripped. Note: The fitment between the sensor strip
and the pocket is quite firm, do not pull on the wires only as they will break away from the strip.
9. Carefully insert the replacement sensor strip into the pocket. Note: When reinserting
the replacement sensor strip ensure the plastic backing is facing AWAY from the
cylinder. The strip will need to be supported by hand to prevent it bending as it is inserted into the pocket and it must be fully inserted to operate correctly. Lubricants
of any kind must NOT be used.
10. Re-pack the foam removed in step 11 into the hole.
11. Complete reassembly in reverse order of above.
12. Restore water and electricity supplies and check heat pump operation.
Page 53
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
52
Component Replacement Procedures – Refrigeration Plant
Refrigeration Module (Procedure 9)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
Due to the weight of the refrigeration unit (approx 45kgs) this is a two man job.
A quantity of hot water may discharge from the flexible hose(s) during this procedure. Wear Personal Protective Equipment to prevent scalds or burns and ensure all escaping water is caught in a container to prevent the sensor
strip from becoming water damaged.
1. Isolate the power and water supplies to the water heater.
2. Confirm with a multi-meter between Active and Neutral, then Active and Earth,
then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Relieve pressure from the water heater and drain approximately 10 litres of water
from the cylinder through the T & PR valve.
4. Remove the front and rear air louvres.
5. Undo the controller cover retaining screw, remove the c ontroller cover and disconnect
the sensor strip and power supply wiring loom plugs from the electronic controller.
6. If fitted, disconnect the condensate drain.
7. Disconnect the hot and cold flexible hoses connecting the heat pump module to the
cylinder at the cylinder fittings (refer to owners guide for location). Note: Ensure all
escaping water is caught in a container to prevent the sensor strip from becoming water damaged.
8. Remove the 3 x 6mm bolts retaining the heat pump module to the cylinder (refer to
owners guide for location).
9. Slide lifting bars (part number 080151) through the slots provided in the chassis (refer
to owners guide for location) and lift the heat pump module clear of the cylinder.
10. Complete reassembly in reverse order of above.
Air Inlet Louver (Procedure 10)
1. Isolate the power to the water heater.
2. Remove the refrigeration section jacket top.
3. Remove the 2 screws from the left and right hand sides of the air inlet louver.
4. Remove the 3 screws from the Colorbond trim directly below the air inlet louver.
5. Lift the louver clear of the jacket.
6. Complete reassembly in reverse order of above.
Page 54
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
53
Refrigeration Section Jacket (Procedure 11)
The fan motor may commence operation without warning. Failure to isolate the power may result in serious injury if the fan commences operation during the removal process.
1. Remove the air inlet louver (refer to Procedure 10).
2. Remove the air outlet cover.
3. Remove the handle.
4. Remove the screws retaining the jacket to the water heater and lift the jacket clear. Note: The refrigeration section jacket is quite flexible, care should be taken to ensure it does not kink during removal or replacement.
5. Complete reassembly in reverse order of above.
Evaporator Fan Motor (Procedure 12)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
The fan motor may commence operation without warning. Failure to isolate the power may result in serious injury if the fan commences operation during the removal process.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the refrigeration section jacket (refer to Procedure 11).
4. Undo the controller cover retaining screw, remove the controller cover and disconnect the wiring to the fan motor from the terminal block. Cut wiring loom cable ties and remove fan wiring.
5. Remove the 2 screws retaining the fan shroud to the evaporator.
6. Slide the shroud up to disengage the locating tabs and lift clear.
7. Undo the nut retaining the fan blade to the motor shaft and remove the blade.
8. Undo the 3 nuts retaining the motor to the shroud and remove the motor.
9. Complete reassembly in reverse order of above.
Page 55
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
54
Control Board (Procedure 13)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Undo the controller cover retaining screw, remove the controller cover and unplug power supply wiring loom, T sensors, circulator, fan and sensor strip plugs from control board.
5. Mark and disconnect compressor wiring from control board.
6. Remove two screws retaining control board bracket to refrigeration base and remove control board.
7. Complete reassembly in reverse order of above.
Relay (Procedure 14)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Undo the controller cover retaining screw, remove the controller cover and disconnect wiring to compressor capacitor.
5. Remove cable tie retaining compressor capacitor and remove compressor capacitor.
6. Mark and disconnect wiring to relay, remove two relay retaining screws and remove relay.
7. Complete reassembly in reverse order of above.
Compressor Capacitor (Procedure 15)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Undo the controller cover retaining screw, remove the controller cover and disconnect wiring to compressor capacitor.
5. Remove cable tie retaining compressor capacitor and remove compressor capacitor.
6. Complete reassembly in reverse order of above.
Page 56
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
55
Fan Capacitor (Procedure 16)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Undo the controller cover retaining screw, remove the controller cover and disconnect wiring to compressor capacitor
5. Remove cable tie retaining compressor capacitor and remove compressor capacitor.
6. Disconnect wiring to fan capacitor, remove two fan capacitor retaining screws and remove fan capacitor.
7. Complete reassembly in reverse order of above.
Circulator (Procedure 17)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
A quantity of hot water may discharge from the circulator flexible hoses during this procedure. Wear Personal Protective Equipment to prevent scalds or burns and ensure all escaping water is caught in a container to prevent the
sensor strip from becoming water damaged.
1. Isolate the power and water supplies to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Relieve pressure from the water heater and drain approximately 10 litres of water from the cylinder through the T & PR valve.
4. Remove the air inlet louver (refer to Procedure 10).
5. Remove circulator electrical cover, disconnect wiring and remove wiring from circulator compression gland.
6. Unscrew circulator flexible hose unions. Note: Ensure all escaping water is caught
in a container to prevent the sensor strip from becoming water damaged.
7. Unscrew circulator inlet adapter and remove circulator from supporting bracket.
8. Complete reassembly in reverse order of above.
Page 57
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
56
T sensor(s) (Procedure 18)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power supply to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Undo the controller cover retaining screw and remove the controller cover.
5. Unplug the T sensor plug from the control board.
6. Remove insulation surrounding T sensor (if applicable).
7. Remove sensor retaining clip and withdraw sensor. Note: Ambient air sensor is held in place by a locking nut and evaporator sensor is held in place by a cable tie. Ambient air sensor retainer can be manoeuvred out of cable tie. Do not cut cable tie as it is difficult to replace.
8. Cut wiring loom cable ties and remove T sensor and wiring.
9. Complete reassembly in reverse order of above.
Page 58
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
57
Component Replacement Procedures – Sealed Refrigeration System
Personnel qualified and licensed to work with refrigerants may only carry out the following repair procedures to the sealed refrigeration system.
The following procedures assume that all work conducted conforms to the refrigeration code of good practice. During repair the refrigerant must be recovered, not vented to atmosphere.
Evaporator (Procedure 19)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the evaporator shroud and fan assembly (refer to Procedure 12 Steps 3 - 6).
4. Remove the evaporator T sensor clip from the cable tie and remove the T sensor from the evaporator finning.
5. Recover refrigerant from sealed refrigeration system.
6. Remove the pipe insulation to expose pipe work at the evaporator. Un-braze the pipe­work to the evaporator.
7. Remove the 4 screws retaining the evaporator to the chassis and lift evaporator clear.
8. Fit and secure the replacement evaporator and braze pipe work.
9. Replace the receiver/filter drier. (Refer to Procedure 20 – steps 4 to 7)
10. Pressurise system to 3000kPa and conduct a leak test. Refit and secure pipe work insulation.
11. Evacuate system to 100 microbar (30”) for a period of at least 30 minutes.
12. Recharge system with the correct refrigerant. Refer to specifications table on page 3.
13. Refit the evaporator shroud and fan motor assembly and refrigeration section jacket.
14. Refit air inlet louver and jacket top.
15. Restore power. The refrigeration plant should commence operation.
Page 59
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
58
Receiver/Filter Drier (Procedure 20)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the air inlet louver (refer to Procedure 10).
4. Recover refrigerant from sealed refrigeration system.
5. Undo the compression nuts on the inlet and outlet of the receiver/filter drier.
6. Cut the cable tie and remove the receiver/filter drier.
7. Fit the replacement receiver/filter drier, secure using a cable tie and retighten the compression fittings.
8. Pressurise system to 3000kPa and conduct a leak test.
9. Evacuate system to 100 microbar (30”) for a period of at least 30 minutes.
10. Recharge system with the correct refrigerant. Refer to “Specifications – Refrigeration System” table on page 3.
11. Refit air inlet louver and jacket top.
12. Restore power. The refrigeration plant should commence operation after a 30 second delay.
Page 60
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
59
Compressor and Accumulator (Procedure 21)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the refrigeration section jacket (refer to Procedure 11).
4. Remove the evaporator shroud and fan motor assembly (refer to Procedure 12 Steps 3
- 6).
5. Recover refrigerant from sealed refrigeration system.
6. Disconnect the wiring to the compressor and unclip and remove the compressor T sensor from the compressor discharge pipe work.
7. Remove the pipe insulation to expose pipe work at the compressor and accumulator. Un-braze the discharge pipe-work from the compressor and the suction line from the accumulator.
8. Remove the 3 nuts retaining the compressor to the chassis and lift the compressor and accumulator clear.
9. Fit and secure the replacement compressor and accumulator, braze pipe work, reconnect wiring to the compressor and refit the discharge T sensor and retaining clip.
16. Replace the receiver/filter drier (Refer to Procedure 20 – steps 4 to 7).
10. Pressurise system to 3000kPa and conduct a leak test. Refit and secure pipe work insulation.
11. Evacuate system to 100 microbar (30”) for a period of at least 30 minutes.
12. Recharge system with the correct refrigerant. Refer to “Specifications – Refrigeration System” table on page 3.
13. Refit the evaporator shroud and fan motor assembly and refrigeration section jacket.
14. Refit air inlet louver and jacket top.
15. Restore power. The refrigeration plant should commence operation after a 30 second delay.
Page 61
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
60
TX Valve Replacement (Procedure 22)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
1. Isolate the power to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Remove the refrigeration section jacket (refer to Procedure 11).
4. Recover refrigerant from sealed refrigeration system.
5. Remove the pipe insulation to expose pipe- work at the TX valve assembly and the TX valve sensor.
6. Separate the TX valve sensor and capillary from the suction line.
7. Un-braze the pipe-work and remove the TX valve.
8. Braze the replacement TX valve into place and attach the sensor to the suction line. Note: Ensure the sensor bulb is in good contact with the suction line.
9. Replace the receiver/filter drier (Refer to Procedure 20 – steps 4 to 7).
10. Pressurise system to 3000kPa and conduct a leak test. Refit and secure the pipe work insulation.
11. Evacuate system to 100 microbar (30”) for a period of at least 30 minutes.
12. Recharge system with the correct refrigerant. Refer to “Specifications – Refrigeration System” table on page 3.
13. Restore power. The refrigeration plant should commence operation after a 30 second delay.
14. Refit air inlet louver and jacket top.
15. Adjust TX valve if required (Refer to Procedure 23).
TX Valve Adjustment (Procedure 23)
Components within the refrigeration plant section will be “live” during the adjustment process. Wear Personal Protective Equipment to reduce the risk of electric shock.
The TX valve is supplied preset and should be installed with the factory setting (6ºC) unaltered. This setting is calibrated for the lowest superheating and optimum evaporator utilization. However, should it be necessary to adjust the superheat, turn the adjusting spindle as follows: Clockwise = Reduced refrigerant flow, increase of superheat. Anticlockwise = Increased refrigerant flow, decrease in superheat.
1. Remove the air inlet louver (refer to Component Replacement - Procedure 10).
2. Remove the TX valve sealing cap (see diagram opposite).
3. Using a 4mm Allen key back the TX valve adjuster screw anticlockwise all the way out. Note: The adjuster screw is recessed approximately 8mm.
4. Screw the adjuster screw in three full turns to achieve the required superheat setting of +6ºC. Note: 1 full 360º turn of the adjuster screw = 2ºC.
5. Refit and tighten the TX valve cap to a torque of 4Nm.
Page 62
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
61
Heat Exchanger (Procedure 24)
Wear Personal Protective Equipment when conducting step 2 of this procedure to reduce the risk of electric shock. Refer to Rheem Safety Procedure on electrical testing.
A quantity of hot water may discharge from the flexible hose(s) during this procedure. Wear Personal Protective Equipment to prevent scalds or burns and ensure all escaping water is caught in a container to prevent the sensor
strip from becoming water damaged.
1. Isolate the power and water supplies to the water heater.
2. Remove the access cover and confirm with a multi-meter between Active and
Neutral, then Active and Earth, then Neutral and Earth terminals of the terminal block that voltage is not present.
3. Relieve pressure from the water heater and drain approximately 10 litres of water
from the cylinder through the T & PR valve.
4. Remove the refrigeration section jacket (refer to Procedure 11).
5. Recover refrigerant from sealed refrigeration system.
6. Undo flexible hose unions at heat exchanger. Note: Ensure all escaping water is
caught in a container to prevent the sensor strip from becoming water damaged.
7. Remove insulation from refrigeration pipe work to and from the heat exchanger and remove inlet and outlet water sensors.
8. Cut cable ties and remove heat exchanger styrene insulation.
9. Un-braze refrigeration pipe work from heat exchanger and remove heat exchanger.
10. Un-braze water system inlet and outlet pipe work from old heat exchanger and braze these components on to the new heat exchanger.
11. Braze the replacement heat exchanger (refrigeration pipe work) into place.
12. Refit inlet and outlet water sensors and replace pipe work and heat exchanger insulation.
13. Remake flexible hose connections to heat exchanger.
17. Replace the receiver/filter drier (Refer to Procedure 20 – steps 4 to 7).
14. Pressurise system to 3000kPa and conduct a leak test. Refit and secure the pipe work insulation.
15. Evacuate system to 100 microbar (30”) for a period of at least 30 minutes.
16. Recharge system with the correct refrigerant. Refer to “Specifications – Refrigeration System” table on page 3.
17. Restore water supply and bleed air from the heat exchanger water outlet union. Note:
Ensure all escaping water is caught in a container to prevent the sensor strip from becoming water damaged.
18. Restore power. The refrigeration plant should commence operation after a 30 second delay.
19. Adjust TX valve (Refer to Procedure 23).
20. Refit refrigeration jacket (reverse procedure 11).
21. Restore water and power supplies. The refrigeration plant should commence operation after a 30 second delay.
Page 63
TM025 Rheem Heat Pump Service Instructions REV: A 62
Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
Exploded View - Refrigeration Plant
Page 64
TM025 Rheem Heat Pump Service Instructions REV: A 63
Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
Replacement Parts List – Refrigeration Plant
Item Description Part Number
1 Air Grille 104798 2 Fan Motor Assy 180027 3 Air Shield 108374 4 Fan Shroud 180026 5 Jacket Top 100659 6 Evaporator Coil 180025 7 Condenser 180032 8 Hose – Braided 088086
9 Circulator 051575 10 Capacitor – Fan Motor 890374 11 Relay 052123 12 Controller Assy 051577 13 Control Cover 051659 14 Sensor Clip 890263 15 Sensor 056006 16 Capacitor - Compressor 890373 17 Compressor 180029 18 Chassis Assy 140114 19 Receiver/Filter Drier 180021 20 TX Valve 180024 21 Drip Tray 104797 22 Side Cover 108372 23 Side Cover - Drip tray outlet 108373 24 Label – Air Grille 120513 25 Condenser Insulation 090249 26 Condenser Insulation Cover 090250 27 Pipe – Refrigerant, Low Pressure 181526 28 Pipe – Refrigerant, High Pressure 181527 29 Pipe – Refrigerant, Drier to Heat Exchanger 181528 30 Pipe – Refrigerant, Drier to TX 181529 31 Pipe – Refrigerant, TX to Evaporator 181530 32 Pipe – Condenser, Upper Water with Thermistor Holder Fitting 088096 33 Pipe – Condenser, Lower Water with Thermistor Holder Fitting 088098
NS Heat Pump Module to Water Heater Mounting Screws (pkt of 3) 080156
NS = Not shown
Page 65
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
64
Exploded View - Water Heater
Page 66
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
65
Replacement Parts List – Water Heater
Item Description Part Number
1 Jacket Bottom 100633
2 Pipe Seal – Inlet/Outlet (¾” x 38) 221418
3 Inlet Diffuser 220516
4 Name Band 120512
5 Dip Tube (Outlet) 225601
6 Wiring loom assembly N/A
Anode – Black 221904 Anode – Blue 221924
7
Anode – Green 222024 8 Anode Cover 221720-1 9 Dropper Tube Seal 087027
10 Dropper Tube – Short 220558 11 O-ring – Dropper Tubes 087023 12 Fitting ¾” to ½” Brass 088040 13 Pipe Seal – Dropper Tubes (30 x 16) 221233 14 Dropper Tube – Long 220559 15 Grommet - Sensor Strip 080149 16 Foam Cover 221735 17 Sensor Strip 053053 18 Jacket Top 108375 19 Pipe Seal – T & PR (½” x 38) 221420 20 Element Gasket 050704 21 Thermostat – EWT 1L2-561 051571 22 Thermostat Clamp 102501 23 Access Cover 100703-1 24 Element Bolts 051404
Element 2.4kW 050324
25
Element 3.6kW 050323
26 Terminal Block 051521 27 T & PR Valve HTE523/507 220641
Page 67
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
66
Rheem Electric Water Heater Warranty - (Australia Only)
WARRANTY CONDITIONS
1. This warranty is applicable only to water heaters
manufactured from 1
st
September 2006.
2. The water heater must be installed in accordance
with the Rheem water heater installation instructions, supplied with the water heater, and in accordance with all relevant statutory and local requirements of the State in which the water heater is installed.
3. Where a failed component or water heater is
replaced under warranty, the balance of the original warranty period will remain effective. The replaced part or water heater does not carry a new warranty.
4. Where the water heater is installed outside the
boundaries of a metropolitan area as defined by Rheem or further than 25 km from a regional Rheem branch office, or an Accredited Service Agent, the cost of transport, insurance and travelling costs between the nearest Rheem
Accredited Service Agent’s premises and the installed site shall be the owner’s responsibility.
5. Where the water heater is installed in a position
that does not allow safe, ready access, the cost of accessing the site safely, including the cost of additional materials handling and / or safety equipment, shall be the owner’s responsibility.
6. The warranty only applies to the water heater and
original or genuine (company) component replacement parts and therefore does not cover any plumbing or electrical parts supplied by the installer and not an integral part of the water heater, e.g. pressure limiting valve; isolation valves; non-return valves; electrical switches; pumps or fuse.
7. The water heater must be sized to supply the hot
water demand in accordance with the guidelines in the Rheem water heater literature.
WARRANTY EXCLUSIONS
REPAIR AND REPLACEMENT WORK WILL BE CARRIED OUT AS SET OUT IN THE RHEEM WATER HEATER WARRANTY ABOVE HOWEVER THE FOLLOWING EXCLUSIONS MAY CAUSE THE WATER HEATER WARRANTY TO BECOME VOID AND MAY INCUR A SERVICE CHARGE AND / OR COST OF PARTS.
a) Accidental damage to the water heater or any
component, including: Acts of God; failure due to misuse; incorrect installation; attempts to repair the water heater other than by a Rheem Accredited Service Agent or the Rheem Service Department.
b) Where it is found there is nothing wrong with the
water heater; where the complaint is related to excessive discharge from the temperature and / or pressure relief valve due to high water pressure; where there is no flow of hot water due to faulty plumbing; where water leaks are related to plumbing and not the water heater or water heater components; where there is a failure of gas, electricity or water supplies; where the supply of gas, electricity or water does not comply with relevant codes or acts.
c) Where the water heater or water heater
component has failed directly or indirectly as a result of: excessive water pressure; excessive temperature and / or thermal input; blocked overflow / vent drain; corrosive
from the water heater.
d) Where the water heater is located in a position
that does not comply with the Rheem water heater installation instructions or relevant statutory requirements, causing the need for major dismantling or removal of cupboards, doors or walls, or use of special equipment to bring the water heater to floor or ground level or to a serviceable position.
e) Repair and / or replacement of the water heater
due to scale formation in the waterways or the effects of either corrosive water or water with a high chloride or low pH level when the water heater has been connected to a scaling or corrosive water supply or a water supply with a high chloride or low pH level as outlined in the Owner’s Guide and Installation Instructions booklet.
f) Breakage of collector glass for any reason
including hail damage. (We suggest that the collector glass be covered by your home insurance policy).
SUBJECT TO ANY STATUTORY PROVISIONS TO THE CONTRARY, THIS WARRANTY EXCLUDES ANY AND ALL CLAIMS FOR DAMAGE TO FURNITURE, CARPETS, WALLS, FOUNDATIONS OR ANY OTHER CONSEQUENTIAL LOSS EITHER DIRECTLY OR INDIRECTLY DUE TO LEAKAGE FROM THE WATER HEATER, OR DUE TO LEAKAGE FROM FITTINGS AND / OR PIPE WORK OF METAL, PLASTIC OR OTHER MATERIALS CAUSED BY WATER TEMPERATURE, WORKMANSHIP OR OTHER MODES OF FAILURE.
Rheem Australia Pty Ltd A.B.N 21 098 823 511
FOR SERVICE TELEPHONE
131 031 AUSTRALIA
or refer local Yellow Pages
NOTE: Every care has been taken to ensure accuracy in preparation of this publication. No liability can be accepted for any
consequences, which may arise as a result of its application.
Page 68
TM025 Rheem Heat Pump Service Instructions REV: B Date of Issue: 02/08/07
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
67
Document Revision History
Title
Service Instructions for Rheem Heat Pump
Document Number
TM025
Revision Details of change D.O.I.
A Service Instructions issued for 310 Series Heat Pump 03/07 B Addition to flow diagram 08/07
Loading...