Rheem 16AJL SERIES Specifications

Page 1
Rheem Value Series Two-Stage Air Conditioners
FORM NO. A11-210
16AJL- Series
Efficiencies up to 16 SEER/13 EER Nominal Sizes 2-5 Ton [7.03 to 17.6 kW] Cooling Capacities 25,400 to 57,000 BTU/H [7.44 to 16.70 kW]
Outdoor air conditioner designed for ground level or rooftop
installations. These units offer comfort and dependability for single, multi-family and light commercial applications.
10 easy-to-read diagnostic alert codes
Painted louvered steel cabinet
Easily accessible control box
Condenser coils constructed with copper tubing and
enhanced aluminum fins (2-4 Tons)/MicroChannel (5 Ton)
Grille/Motor mount for quiet fan operation
Filter Drier (shipped – not installed)
Air
Air Conditioners
16AJL Series
Note: Above image does not show deep drawn basepan.
16.0
Page 2
Air
Table of Contents
16AJL Series
2
TABLE OF CONTENTS
Model Number Identification ............................................................................3
Accessories....................................................................................................3
Scroll Compressor ..........................................................................................3
Performance Data ......................................................................................4-18
Electrical & Physical Data ..............................................................................19
Unit Dimensions............................................................................................20
Refrigerant Line Size Information ....................................................................21
Limited Warranty ..........................................................................................22
Page 3
Air
Model I.D./Accessories/Compressor
16AJL Series
3
Model Number Identification
16 A J L 24
NOMINAL COOLING CAPACITY
24 = 24,000 BTU/HR [7.03 kW] 36 = 36,000 BTU/HR [10.55 kW] 48 = 48,000 BTU/HR [14.07 kW] 60 = 60,000 BTU/HR [17.58 kW]
A 01
16 SEER A = AIR CONDITIONER VOLTAGE
J = 208-230
SINGLE PHASE
DESIGN SERIES
L = 1ST DESIGN
R-410A
CABINET
A = FULL METAL JACKET
RHEEM
VALUE
SERIES
Accessories
Low Pressure Control (RXAC-A07)
High Pressure Control (RXAB-A07)
Low Ambient Control (RXAD-A08)
Compressor Time Delay Control
Crankcase Heater
Sound Enclosure
* Photos are representative. Actual models may vary.
For detailed thermostat match-up information, see specification sheet form number T11-001.
300-Series *
Deluxe Programmable
400-Series *
Special Applications/ Programmable
500-Series *
Communicating/ Programmable
200-Series *
Programmable
Scroll®Compressor
The reliable scroll compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor tech­nology. The advanced scroll compressor offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The scroll compressor also has low start torque, reducing start problems in the field. And its unique design enables air conditioners to perform efficiently and quietly.
[ ] Designates Metric Conversions
Thermostats
Page 4
Air
Performance Data
16AJL Series
4
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
24
RCSL-H*2621
RHML-HM2421
1 14400 [4.2] 6800 [2.0]
25400 [7.4] 16 13
525 [248] 0
2 18100 [5.3] 7300 [2.1] 700 [330] 74
1 - dehumid 0 [0.0] 0 [0.0] 0 [0]
2 - dehumid 0 [0.0] 0 [0.0] 0 [0]
RCFL-H*2417
RGFE-06?MCK?
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RGFG-06?MCK?
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RGGE-07?MCK?
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RGJF-07?MCK?
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RGLE-07?AMK?
1 14700 [4.3] 6500 [1.9]
25000 [7.3] 15 12.5
600 [283] 0
2 18200 [5.3] 6800 [2.0] 800 [378] 74
RGPE-05?BMK?
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RGRM-04?MAE?
1 14300 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
575 [271] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
ROCA-070E03
1 14700 [4.3] 6500 [1.9]
24800 [7.3] 15 12.5
600 [283] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
ROLA-070E03
1 14500 [4.2] 6500 [1.9]
24800 [7.3] 15 12.5
600 [283] 0
2 18000 [5.3] 6800 [2.0] 800 [378] 74
RCFL-H*2417+RXMD-C04 Coil Only
1 13600 [4.0] 6600 [1.9]
23800 [7.0] 14 11.5
525 [248] 0
2 16800 [4.9] 7000 [2.1] 700 [330] 74
RCFL-H*2617
RGFE-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGFG-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGGE-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGJF-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGLE-07?AMK?
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGPE-05?BMK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGRM-04?MAE?
1 14900 [4.4] 6700 [2.0]
25600 [7.5] 16 13
575 [271] 0
2 18600 [5.4] 7000 [2.1] 800 [378] 74
ROCA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROLA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RCFL-H*2617+RXMD-C04 Coil Only
1 14000 [4.1] 6800 [2.0]
24800 [7.3] 14.5 12
525 [248] 0
2 17500 [5.1] 7300 [2.1] 700 [330] 74
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 5
Air
Performance Data
16AJL Series
5
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
024
RCFL-H*2621
RGFE-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGFG-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGGE-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGJF-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGLE-07?AMK?
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGPE-05?BMK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGRM-04?MAE?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROCA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROLA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RCFL-H*2621+RXMD-C04 Coil Only
1 14000 [4.1] 6800 [2.0]
24800 [7.3] 14.5 12
525 [248] 0
2 17500 [5.1] 7300 [2.1] 700 [330] 74
RCFN-H*2417
RGFE-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGFG-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGGE-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGJF-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGLE-07?AMK?
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGPE-05?BMK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGRM-04?MAE?
1 14900 [4.4] 6700 [2.0]
25600 [7.5] 16 13
575 [271] 0
2 18600 [5.4] 7000 [2.1] 800 [378] 74
ROCA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROLA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RCFN-H*2417+RXMD-C04 Coil Only
1 14000 [4.1] 6800 [2.0]
24800 [7.3] 14.5 12
525 [248] 0
2 17500 [5.1] 7300 [2.1] 700 [330] 74
RCFN-H*2421
RGFE-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGFG-06?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 6
Air
Performance Data
16AJL Series
6
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
24
RCFN-H*2421
RGGE-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGJF-07?MCK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGLE-07?AMK?
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGPE-05?BMK?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RGRM-04?MAE?
1 14900 [4.4] 6700 [2.0]
25800 [7.6] 16 13
575 [271] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROCA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
ROLA-070E03
1 15100 [4.4] 6700 [2.0]
25800 [7.6] 16 13
600 [283] 0
2 18800 [5.5] 7000 [2.1] 800 [378] 74
RCFN-H*2421+RXMD-C04 Coil Only
1 14000 [4.1] 6800 [2.0]
24800 [7.3] 14.5 12
525 [248] 0
2 17500 [5.1] 7300 [2.1] 700 [330] 74
RCSL-H*2621 RHPL-HM2421
1 14700 [4.3] 6500 [1.9]
25000 [7.3] 16 13
600 [283] 0
2 18200 [5.3] 6800 [2.0] 800 [378] 74
RCSN-H*2421 RHPN-HM2421
1 14900 [4.4] 6700 [2.0]
26000 [7.6] 16 13
575 [271] 0
2 19000 [5.6] 7000 [2.1] 800 [378] 74
36
RCSL-H*3821
RHML-HM3621
1 19500 [5.7] 9100 [2.7]
35400 [10.4] 16 13
800 [378] 0
2 24500 [7.2] 10900 [3.2] 1050 [495] 77
1 - dehumid 0 [0.0] 0 [0.0] 0 [0]
2 - dehumid 0 [0.0] 0 [0.0] 0 [0]
RCFL-H*3617
RGFE-06?MCK?
1 18400 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGFE-07?MCK?
1 18400 [5.4] 9000 [2.6]
34600 [10.1] 14.5 12
725 [342] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
RGFG-06?MCK?
1 18400 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGFG-07?MCK?
1 19200 [5.6] 8800 [2.6]
34200 [10.0] 14.5 12
800 [378] 0
2 23200 [6.8] 11000 [3.2] 1000 [472] 77
RGGE-06?MCK?
1 18600 [5.4] 9000 [2.6]
34800 [10.2] 14.5 12
725 [342] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGGE-07?MCK?
1 18700 [5.5] 8900 [2.6]
34800 [10.2] 14.5 12
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGJF-06?MCK?
1 18600 [5.4] 9000 [2.6]
34800 [10.2] 14.5 12
725 [342] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGJF-07?MCK?
1 18700 [5.5] 8900 [2.6]
34800 [10.2] 14.5 12
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGLE-07?AMK?
1 18900 [5.5] 8900 [2.6]
34800 [10.2] 15 12.5
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGPE-05?BMK?
1 18700 [5.5] 8900 [2.6]
34400 [10.1] 14.5 12
750 [354] 0
2 23300 [6.8] 11100 [3.3] 975 [460] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 7
Air
Performance Data
16AJL Series
7
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFL-H*3617
RGPE-07?AMK?
1 18600 [5.4] 9000 [2.6]
34400 [10.1] 15 12.5
725 [342] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGRM-04?MAE?
1 18700 [5.5] 8900 [2.6]
34600 [10.1] 14.5 12
750 [354] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
RGRM-06?MAE?
1 19200 [5.6] 8800 [2.6]
34400 [10.1] 14.5 12
775 [366] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGRM-07?MAE?
1 19000 [5.6] 8800 [2.6]
34400 [10.1] 14 11.5
800 [378] 0
2 23600 [6.9] 10800 [3.2] 1025 [484] 77
RGTM-06?MAE?
1 19900 [5.8] 8500 [2.5]
34600 [10.1] 14.5 12
900 [425] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
ROCA-070E03
1 19200 [5.6] 8800 [2.6]
34600 [10.1] 15 12.5
800 [378] 0
2 23600 [6.9] 11000 [3.2] 1000 [472] 77
ROCA-070E04
1 19200 [5.6] 8800 [2.6]
34600 [10.1] 15 12.5
800 [378] 0
2 23600 [6.9] 11000 [3.2] 1000 [472] 77
ROLA-070E03
1 18600 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23300 [6.8] 11100 [3.3] 975 [460] 77
ROLA-070E04
1 18600 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23300 [6.8] 11100 [3.3] 975 [460] 77
RCFL-H*3617+RXMD-C04 Coil Only
1 18600 [5.4] 8800 [2.6]
34400 [10.1] 13.5 11
800 [378] 0
2 23600 [6.9] 10800 [3.2] 1050 [495] 77
RCFL-H*3621
RGFE-06?MCK?
1 18600 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGFE-07?MCK?
1 18600 [5.4] 9000 [2.6]
34600 [10.1] 14.5 12
725 [342] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
RGFE-09?ZCM?
1 19800 [5.8] 8600 [2.5]
35400 [10.4] 14.5 12
875 [413] 0
2 25200 [7.4] 10200 [3.0] 1200 [566] 77
RGFG-06?MCK?
1 18600 [5.4] 9000 [2.6]
34400 [10.1] 14.5 12
725 [342] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGFG-07?MCK?
1 19200 [5.6] 8800 [2.6]
34400 [10.1] 14.5 12
800 [378] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGFG-09?ZCM?
1 19800 [5.8] 8600 [2.5]
35400 [10.4] 14.5 12
875 [413] 0
2 25200 [7.4] 10200 [3.0] 1200 [566] 77
RGFG-10?ZCM?
1 19900 [5.8] 8500 [2.5]
35400 [10.4] 14.5 12
900 [425] 0
2 25200 [7.4] 10200 [3.0] 1200 [566] 77
RGGE-06?MCK?
1 18600 [5.4] 9000 [2.6]
34800 [10.2] 14.5 12
725 [342] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGGE-07?MCK?
1 18700 [5.5] 8900 [2.6]
34800 [10.2] 14.5 12
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGGE-10?ZCM?
1 19800 [5.8] 8600 [2.5]
35400 [10.4] 14.5 12
875 [413] 0
2 25200 [7.4] 10200 [3.0] 1200 [566] 77
RGJF-06?MCK?
1 18600 [5.4] 9000 [2.6]
34800 [10.2] 14.5 12
725 [342] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGJF-07?MCK?
1 18700 [5.5] 8900 [2.6]
34800 [10.2] 14.5 12
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 8
Air
Performance Data
16AJL Series
8
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFL-H*3621
RGJF-10?ZCM?
1 19800 [5.8] 8600 [2.5]
35400 [10.4] 14.5 12
875 [413] 0
2 25200 [7.4] 10200 [3.0] 1200 [566] 77
RGLE-07?AMK?
1 18900 [5.5] 8900 [2.6]
34800 [10.2] 15 12
750 [354] 0
2 24000 [7.0] 10800 [3.2] 1025 [484] 77
RGLE-07?BRQ?
1 19200 [5.6] 8800 [2.6]
35000 [10.3] 15 12
775 [366] 0
2 24200 [7.1] 10800 [3.2] 1025 [484] 77
RGLE-10?BRM?
1 19800 [5.8] 8600 [2.5]
35600 [10.4] 15 12
875 [413] 0
2 25400 [7.4] 10200 [3.0] 1200 [566] 77
RGPE-05?BMK?
1 18700 [5.5] 8900 [2.6]
34400 [10.1] 14.5 12
750 [354] 0
2 23300 [6.8] 11100 [3.3] 975 [460] 77
RGPE-07?AMK?
1 18600 [5.4] 9000 [2.6]
34600 [10.1] 15 12
725 [342] 0
2 23600 [6.9] 11000 [3.2] 1000 [472] 77
RGPE-07?BRQ?
1 18600 [5.4] 9000 [2.6]
35000 [10.3] 15 12
725 [342] 0
2 24200 [7.1] 10800 [3.2] 1025 [484] 77
RGRM-04?MAE?
1 18700 [5.5] 8900 [2.6]
34600 [10.1] 14.5 12
750 [354] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
RGRM-06?MAE?
1 19200 [5.6] 8800 [2.6]
34400 [10.1] 14.5 12
775 [366] 0
2 23400 [6.9] 11000 [3.2] 1000 [472] 77
RGRM-07?MAE?
1 19000 [5.6] 8800 [2.6]
34400 [10.1] 14 11.5
800 [378] 0
2 23600 [6.9] 10800 [3.2] 1025 [484] 77
RGRM-07?YBG?
1 18400 [5.4] 9000 [2.6]
34000 [10.0] 14.5 12
700 [330] 0
2 22900 [6.7] 11100 [3.3] 975 [460] 77
RGRM-10?ZAJ?
1 19800 [5.8] 8600 [2.5]
35000 [10.3] 14.5 12
875 [413] 0
2 24600 [7.2] 10400 [3.0] 1150 [543] 77
RGTM-06?MAE?
1 19900 [5.8] 8500 [2.5]
34600 [10.1] 14.5 12
900 [425] 0
2 23800 [7.0] 10800 [3.2] 1025 [484] 77
RGTM-07?RBG?
1 19200 [5.6] 8800 [2.6]
34800 [10.2] 15 12.5
800 [378] 0
2 24000 [7.0] 10800 [3.2] 1050 [495] 77
ROCA-070E03
1 19200 [5.6] 8800 [2.6]
34600 [10.1] 15 12.5
800 [378] 0
2 23600 [6.9] 11000 [3.2] 1000 [472] 77
ROCA-070E04
1 19200 [5.6] 8800 [2.6]
34600 [10.1] 15 12.5
800 [378] 0
2 23600 [6.9] 11000 [3.2] 1000 [472] 77
ROLA-070E03
1 20100 [5.9] 8500 [2.5]
35400 [10.4] 15 12.5
900 [425] 0
2 25100 [7.4] 10300 [3.0] 1175 [554] 77
ROLA-070E04
1 20100 [5.9] 8500 [2.5]
35400 [10.4] 15 12.5
900 [425] 0
2 25100 [7.4] 10300 [3.0] 1175 [554] 77
ROLA-115E05
1 20100 [5.9] 8500 [2.5]
35600 [10.4] 15 12.5
900 [425] 0
2 25400 [7.4] 10200 [3.0] 1200 [566] 77
RCFL-H*3621+RXMD-C04 Coil Only
1 18600 [5.4] 8800 [2.6]
34400 [10.1] 13.5 11.5
800 [378] 0
2 23600 [6.9] 10800 [3.2] 1050 [495] 77
RCFL-H*3821
RGFE-06?MCK?
1 18700 [5.5] 9300 [2.7]
34800 [10.2] 15 12
725 [342] 0
2 23700 [6.9] 11100 [3.3] 1000 [472] 77
RGFE-07?MCK?
1 18700 [5.5] 9300 [2.7]
35000 [10.3] 15.5 12.5
725 [342] 0
2 24100 [7.1] 10900 [3.2] 1025 [484] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 9
Air
Performance Data
16AJL Series
9
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36 RCFL-H*3821
RGFE-09?ZCM?
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGFG-06?MCK?
1 18700 [5.5] 9300 [2.7]
34800 [10.2] 15 12
725 [342] 0
2 23700 [6.9] 11100 [3.3] 1000 [472] 77
RGFG-07?MCK?
1 19300 [5.7] 9100 [2.7]
34600 [10.1] 15 12
800 [378] 0
2 23500 [6.9] 11100 [3.3] 1000 [472] 77
RGFG-09?ZCM?
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGFG-10?ZCM?
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15 12
900 [425] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGGE-06?MCK?
1 18700 [5.5] 9300 [2.7]
35200 [10.3] 15.5 12.5
725 [342] 0
2 24300 [7.1] 10900 [3.2] 1025 [484] 77
RGGE-07?MCK?
1 18900 [5.5] 9300 [2.7]
35000 [10.3] 15.5 12.5
750 [354] 0
2 24100 [7.1] 10900 [3.2] 1025 [484] 77
RGGE-10?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGJF-06?MCK?
1 18700 [5.5] 9300 [2.7]
35200 [10.3] 15.5 12.5
725 [342] 0
2 24300 [7.1] 10900 [3.2] 1025 [484] 77
RGJF-07?MCK?
1 18900 [5.5] 9300 [2.7]
35000 [10.3] 15.5 12.5
750 [354] 0
2 24100 [7.1] 10900 [3.2] 1025 [484] 77
RGJF-10?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGLE-07?AMK?
1 18900 [5.5] 9300 [2.7]
35200 [10.3] 16 12.5
750 [354] 0
2 24300 [7.1] 10900 [3.2] 1025 [484] 77
RGLE-07?BRQ?
1 19500 [5.7] 9100 [2.7]
35400 [10.4] 16 13
775 [366] 0
2 24500 [7.2] 10900 [3.2] 1025 [484] 77
RGLE-10?BRM?
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
875 [413] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RGPE-05?BMK?
1 18900 [5.5] 9300 [2.7]
34600 [10.1] 15.5 12.5
750 [354] 0
2 23400 [6.9] 11200 [3.3] 975 [460] 77
RGPE-07?AMK?
1 18700 [5.5] 9300 [2.7]
34800 [10.2] 15.5 12.5
725 [342] 0
2 23700 [6.9] 11100 [3.3] 1000 [472] 77
RGPE-07?BRQ?
1 18700 [5.5] 9300 [2.7]
35400 [10.4] 16 13
725 [342] 0
2 24500 [7.2] 10900 [3.2] 1025 [484] 77
RGRM-04?MAE?
1 18900 [5.5] 9300 [2.7]
34800 [10.2] 15 12
750 [354] 0
2 23900 [7.0] 10900 [3.2] 1025 [484] 77
RGRM-06?MAE?
1 19300 [5.7] 9100 [2.7]
34600 [10.1] 15 12
775 [366] 0
2 23500 [6.9] 11100 [3.3] 1000 [472] 77
RGRM-07?MAE?
1 19300 [5.7] 9100 [2.7]
34800 [10.2] 15 12
800 [378] 0
2 23900 [7.0] 10900 [3.2] 1025 [484] 77
RGRM-07?YBG?
1 19600 [5.7] 9000 [2.6]
35200 [10.3] 14.5 11
850 [401] 0
2 24900 [7.3] 10300 [3.0] 1200 [566] 77
RGRM-10?ZAJ?
1 19900 [5.8] 8900 [2.6]
35400 [10.4] 15 12
875 [413] 0
2 24900 [7.3] 10500 [3.1] 1150 [543] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 10
Air
Performance Data
16AJL Series
10
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFL-H*3821
RGTM-06?MAE?
1 20100 [5.9] 8900 [2.6]
35000 [10.3] 15.5 12.5
900 [425] 0
2 24100 [7.1] 10900 [3.2] 1025 [484] 77
RGTM-07?RBG?
1 19300 [5.7] 9100 [2.7]
35200 [10.3] 16 12.5
800 [378] 0
2 24300 [7.1] 10900 [3.2] 1050 [495] 77
ROCA-070E03
1 19300 [5.7] 9100 [2.7]
35000 [10.3] 16 12.5
800 [378] 0
2 23900 [7.0] 11100 [3.3] 1000 [472] 77
ROCA-070E04
1 19300 [5.7] 9100 [2.7]
35000 [10.3] 16 12.5
800 [378] 0
2 23900 [7.0] 11100 [3.3] 1000 [472] 77
ROLA-070E03
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 16 12.5
900 [425] 0
2 25400 [7.4] 10400 [3.0] 1175 [554] 77
ROLA-070E04
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 16 12.5
900 [425] 0
2 25400 [7.4] 10400 [3.0] 1175 [554] 77
ROLA-115E05
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
900 [425] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RCFL-H*3821+RXMD-C04 Coil Only
1 18700 [5.5] 9100 [2.7]
34600 [10.1] 14 11.5
800 [378] 0
2 23700 [6.9] 10900 [3.2] 1050 [495] 77
RCFL-H*3824
RGFE-09?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15 12
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGFG-09?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15 12
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGFG-10?ZCM?
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15 12
900 [425] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGGE-10?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGGE-12?RCM?
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
875 [413] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RGJF-10?ZCM?
1 19900 [5.8] 8900 [2.6]
35800 [10.5] 15.5 12.5
875 [413] 0
2 25500 [7.5] 10300 [3.0] 1200 [566] 77
RGJF-12?RCM?
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
875 [413] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RGLE-07?BRQ?
1 19500 [5.7] 9100 [2.7]
35400 [10.4] 16 13
775 [366] 0
2 24500 [7.2] 10900 [3.2] 1025 [484] 77
RGLE-10?BRM?
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
875 [413] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RGPE-07?BRQ?
1 18700 [5.5] 9300 [2.7]
35400 [10.4] 16 13
725 [342] 0
2 24500 [7.2] 10900 [3.2] 1025 [484] 77
RGPE-12?ARM?
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
875 [413] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RGRM-07?YBG?
1 19600 [5.7] 9000 [2.6]
35200 [10.3] 14.5 11
850 [401] 0
2 24900 [7.3] 10300 [3.0] 1200 [566] 77
RGRM-10?ZAJ?
1 19900 [5.8] 8900 [2.6]
35400 [10.4] 15 12
875 [413] 0
2 24900 [7.3] 10500 [3.1] 1150 [543] 77
RGTM-07?RBG?
1 19300 [5.7] 9100 [2.7]
35200 [10.3] 16 12.5
800 [378] 0
2 24300 [7.1] 10900 [3.2] 1050 [495] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 11
Air
Performance Data
16AJL Series
11
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFL-H*3824
ROCA-070E03
1 19300 [5.7] 9100 [2.7]
34800 [10.2] 16 12.5
800 [378] 0
2 23700 [6.9] 11100 [3.3] 1000 [472] 77
ROCA-070E04
1 19300 [5.7] 9100 [2.7]
34800 [10.2] 16 12.5
800 [378] 0
2 23700 [6.9] 11100 [3.3] 1000 [472] 77
ROLA-070E03
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15.5 12.5
900 [425] 0
2 25400 [7.4] 10400 [3.0] 1175 [554] 77
ROLA-070E04
1 20100 [5.9] 8900 [2.6]
35800 [10.5] 15.5 12.5
900 [425] 0
2 25400 [7.4] 10400 [3.0] 1175 [554] 77
ROLA-115E05
1 20100 [5.9] 8900 [2.6]
36000 [10.5] 16 12.5
900 [425] 0
2 25700 [7.5] 10300 [3.0] 1200 [566] 77
RCFL-H*3824+RXMD-C04 Coil Only
1 18700 [5.5] 9100 [2.7]
34600 [10.1] 14 11.5
800 [378] 0
2 23700 [6.9] 10900 [3.2] 1050 [495] 77
RCFN-H*3624
RGFE-09?ZCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGFG-09?ZCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGFG-10?ZCM?
1 22300 [6.5] 8300 [2.4]
38500 [11.3] 16 13
900 [425] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGGE-10?ZCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGGE-12?RCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGJF-10?ZCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGJF-12?RCM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGLE-10?BRM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGPE-12?ARM?
1 22200 [6.5] 8400 [2.5]
38500 [11.3] 16 13
875 [413] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RGRM-07?YBG?
1 21700 [6.4] 8500 [2.5]
37800 [11.1] 15 12
850 [401] 0
2 28300 [8.3] 9500 [2.8] 1200 [566] 77
RGRM-10?ZAJ?
1 22000 [6.4] 8400 [2.5]
38000 [11.1] 16 13
875 [413] 0
2 28300 [8.3] 9700 [2.8] 1150 [543] 77
RGTM-07?RBG?
1 21400 [6.3] 8600 [2.5]
37800 [11.1] 16 13
800 [378] 0
2 27600 [8.1] 10200 [3.0] 1050 [495] 77
ROCA-070E03
1 23200 [6.8] 8000 [2.3]
38500 [11.3] 16 13
1000 [472] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
ROCA-070E04
1 23200 [6.8] 8000 [2.3]
38500 [11.3] 16 13
1000 [472] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
ROLA-070E03
1 22300 [6.5] 8300 [2.4]
38500 [11.3] 16 13
900 [425] 0
2 28900 [8.5] 9600 [2.8] 1175 [554] 77
ROLA-070E04
1 22300 [6.5] 8300 [2.4]
38500 [11.3] 16 13
900 [425] 0
2 28900 [8.5] 9600 [2.8] 1175 [554] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 12
Air
Performance Data
16AJL Series
12
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFN-H*3624 ROLA-115E05
1 22300 [6.5] 8300 [2.4]
38500 [11.3] 16 13
900 [425] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RCFN-H*3624+RXMD-C04 Coil Only
1 20800 [6.1] 8600 [2.5]
37200 [10.9] 14.5 12
800 [378] 0
2 27000 [7.9] 10200 [3.0] 1050 [495] 77
RCSL-H*3821 RHPL-HM3821
1 20700 [6.1] 8700 [2.5]
35800 [10.5] 16 12.5
950 [448] 0
2 25300 [7.4] 10500 [3.1] 1150 [543] 77
RCSN-H*3624 RHPN-HM3624
1 20900 [6.1] 8900 [2.6]
38500 [11.3] 16 13
725 [342] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
48
RCSL-H*4824
RHML-HM4824
1 26900 [7.9] 12100 [3.5]
48500 [14.2] 16 13
1050 [495] 0
2 34700 [10.2] 13800 [4.0] 1400 [661] 77
1 - dehumid 0 [0.0] 0 [0.0] 0 [0]
2 - dehumid 0 [0.0] 0 [0.0] 0 [0]
RCFL-H*4821
RGFE-10?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1425 [672] 77
RGFG-09?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGFG-10?ZCM?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1050 [495] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGGE-09?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGGE-10?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1050 [495] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGJF-09?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGJF-10?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGLE-07?BRQ?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGLE-10?BRM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15.5 12
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGPE-07?BRQ?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 12
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGPE-10?BRM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 12
1075 [507] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGRM-07?YBG?
1 23600 [6.9] 12600 [3.7]
45000 [13.2] 14 10.5
1050 [495] 0
2 30100 [8.8] 14900 [4.4] 1400 [661] 77
RGRM-09?ZAJ?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 14.5 11.5
1075 [507] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGRM-10?ZAJ?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 14.5 11
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1425 [672] 77
RGTM-07?RBG?
1 24700 [7.2] 12300 [3.6]
46000 [13.5] 15 11.5
1125 [531] 0
2 31600 [9.3] 14400 [4.2] 1475 [696] 77
RGTM-09?ZAJ?
1 24400 [7.1] 12400 [3.6]
46000 [13.5] 15 11.5
1100 [519] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 13
Air
Performance Data
16AJL Series
13
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
48
RCFL-H*4821
ROCA-070E04
1 25100 [7.4] 11900 [3.5]
45500 [13.3] 14.5 11
1200 [566] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
ROLA-070E04
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1375 [649] 77
ROLA-115E05
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RCFL-H*4821+RXMD-C04 Coil Only
1 23200 [6.8] 12600 [3.7]
45500 [13.3] 13.5 11.5
1050 [495] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RCFL-H*4824
RGFE-09?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGFE-10?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1425 [672] 77
RGFE-12?RCM?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15 11.5
1025 [484] 0
2 31900 [9.3] 14600 [4.3] 1450 [684] 77
RGFG-09?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGFG-10?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGFG-12?RCM?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15 11.5
1025 [484] 0
2 31900 [9.3] 14600 [4.3] 1450 [684] 77
RGGE-09?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGGE-10?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGGE-12?RCM?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1050 [495] 0
2 31600 [9.3] 14900 [4.4] 1375 [649] 77
RGJF-09?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGJF-10?ZCM?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGJF-12?RCM?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1050 [495] 0
2 31600 [9.3] 14900 [4.4] 1375 [649] 77
RGLE-07?BRQ?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15.5 12
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGLE-10?BRM?
1 24700 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1050 [495] 0
2 31600 [9.3] 14900 [4.4] 1400 [661] 77
RGLE-12?ARM?
1 24700 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1075 [507] 0
2 31600 [9.3] 14900 [4.4] 1425 [672] 77
RGPE-07?BRQ?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1050 [495] 0
2 31600 [9.3] 14900 [4.4] 1400 [661] 77
RGPE-10?BRM?
1 24500 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1075 [507] 0
2 31600 [9.3] 14900 [4.4] 1400 [661] 77
RGPE-12?ARM?
1 24700 [7.2] 12700 [3.7]
46500 [13.6] 15.5 12
1075 [507] 0
2 31600 [9.3] 14900 [4.4] 1425 [672] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 14
Air
Performance Data
16AJL Series
14
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
48
RCFL-H*4824
RGRM-07?YBG?
1 24100 [7.1] 12700 [3.7]
45000 [13.2] 14 10.5
1050 [495] 0
2 30100 [8.8] 14900 [4.4] 1400 [661] 77
RGRM-09?ZAJ?
1 24300 [7.1] 12700 [3.7]
46000 [13.5] 14.5 11.5
1075 [507] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGRM-10?ZAJ?
1 24300 [7.1] 12700 [3.7]
45500 [13.3] 15 11
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1425 [672] 77
RGRM-12?RAJ?
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1075 [507] 0
2 31100 [9.1] 14900 [4.4] 1425 [672] 77
RGTM-07?RBG?
1 25200 [7.4] 12400 [3.6]
46500 [13.6] 15 11.5
1125 [531] 0
2 32100 [9.4] 14400 [4.2] 1475 [696] 77
RGTM-09?ZAJ?
1 24900 [7.3] 12500 [3.7]
46000 [13.5] 15 11.5
1100 [519] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGTM-10?RBJ?
1 25200 [7.4] 12400 [3.6]
46000 [13.5] 15 11.5
1125 [531] 0
2 31100 [9.1] 14900 [4.4] 1425 [672] 77
ROCA-070E04
1 25800 [7.6] 12000 [3.5]
46000 [13.5] 14.5 11.5
1200 [566] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
ROLA-070E04
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1375 [649] 77
ROLA-115E05
1 24500 [7.2] 12700 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RCFL-H*4824+RXMD-C04 Coil Only
1 23900 [7.0] 12700 [3.7]
46000 [13.5] 14 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RCFN-H*4824
RGFE-09?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGFE-10?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1425 [672] 77
RGFE-12?RCM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12
1025 [484] 0
2 35000 [10.3] 13500 [4.0] 1450 [684] 77
RGFG-09?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGFG-10?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1050 [495] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGFG-12?RCM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12
1025 [484] 0
2 35000 [10.3] 13500 [4.0] 1450 [684] 77
RGGE-09?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGGE-10?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1050 [495] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGGE-12?RCM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12.5
1050 [495] 0
2 34700 [10.2] 13800 [4.0] 1375 [649] 77
RGJF-09?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGJF-10?ZCM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1050 [495] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 15
Air
Performance Data
16AJL Series
15
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
48
RCFN-H*4824
RGJF-12?RCM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12.5
1050 [495] 0
2 34700 [10.2] 13800 [4.0] 1375 [649] 77
RGLE-07?BRQ?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12.5
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGLE-10?BRM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12.5
1050 [495] 0
2 34700 [10.2] 13800 [4.0] 1400 [661] 77
RGLE-12?ARM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12.5
1075 [507] 0
2 34700 [10.2] 13800 [4.0] 1425 [672] 77
RGPE-07?BRQ?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12.5
1050 [495] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGPE-10?BRM?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12.5
1075 [507] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGPE-12?ARM?
1 26400 [7.7] 12100 [3.5]
48500 [14.2] 16 12.5
1075 [507] 0
2 34700 [10.2] 13800 [4.0] 1425 [672] 77
RGRM-07?YBG?
1 25900 [7.6] 12100 [3.5]
47000 [13.8] 15 11
1050 [495] 0
2 33200 [9.7] 13800 [4.0] 1400 [661] 77
RGRM-09?ZAJ?
1 26400 [7.7] 12100 [3.5]
47500 [13.9] 15.5 12
1075 [507] 0
2 33700 [9.9] 13800 [4.0] 1400 [661] 77
RGRM-10?ZAJ?
1 26400 [7.7] 12100 [3.5]
47500 [13.9] 15.5 11.5
1025 [484] 0
2 33700 [9.9] 13800 [4.0] 1425 [672] 77
RGRM-12?RAJ?
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 15.5 12
1075 [507] 0
2 34200 [10.0] 13800 [4.0] 1425 [672] 77
RGTM-07?RBG?
1 27200 [8.0] 11800 [3.5]
48500 [14.2] 15.5 12
1125 [531] 0
2 35200 [10.3] 13300 [3.9] 1475 [696] 77
RGTM-09?ZAJ?
1 27100 [7.9] 11900 [3.5]
48000 [14.1] 15.5 12
1100 [519] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RGTM-10?RBJ?
1 27200 [8.0] 11800 [3.5]
48000 [14.1] 16 12.5
1125 [531] 0
2 34200 [10.0] 13800 [4.0] 1425 [672] 77
ROCA-070E04
1 27600 [8.1] 11400 [3.3]
47500 [13.9] 15 12
1200 [566] 0
2 33700 [9.9] 13800 [4.0] 1400 [661] 77
ROLA-070E04
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12.5
1025 [484] 0
2 34200 [10.0] 13800 [4.0] 1375 [649] 77
ROLA-115E05
1 26400 [7.7] 12100 [3.5]
48000 [14.1] 16 12
1050 [495] 0
2 34200 [10.0] 13800 [4.0] 1400 [661] 77
RCFN-H*4824+RXMD-C04 Coil Only
1 25700 [7.5] 12100 [3.5]
47500 [13.9] 14.5 12
1050 [495] 0
2 33700 [9.9] 13800 [4.0] 1400 [661] 77
RCSN-H*4824 RHPN-HM4824
1 26200 [7.7] 12300 [3.6]
49500 [14.5] 16 12.5
1000 [472] 0
2 37000 [10.8] 12500 [3.7] 1600 [755] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 16
Air
Performance Data
16AJL Series
16
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
60
RCSL-H*6024
RHML-HM6024
1 30900 [9.1] 14600 [4.3]
57000 [16.7] 16 12.4
1200 [566] 0
2 40200 [11.8] 16800 [4.9] 1600 [755] 77
1 - dehumid 0 [0.0] 0 [0.0] 0 [0]
2 - dehumid 0 [0.0] 0 [0.0] 0 [0]
RCFL-H*6024
RGFE-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFE-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFE-12?RCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGFG-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFG-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15 11
1200 [566] 0
2 40100 [11.7] 16400 [4.8] 1650 [779] 77
RGFG-12?RCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGGE-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGGE-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGGE-12?RCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1575 [743] 77
RGJF-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGJF-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGJF-12?RCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1575 [743] 77
RGLE-07?BRQ?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGLE-10?BRM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGLE-12?ARM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGPE-07?BRQ?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGPE-10?BRM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1625 [767] 77
RGPE-12?ARM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1625 [767] 77
RGRM-09?ZAJ?
1 30400 [8.9] 14600 [4.3]
55500 [16.3] 15 11
1225 [578] 0
2 38700 [11.3] 16800 [4.9] 1625 [767] 77
RGRM-10?ZAJ?
1 29600 [8.7] 14900 [4.4]
56000 [16.4] 15 11
1150 [543] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 17
Air
Performance Data
16AJL Series
17
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
60
RCFL-H*6024
RGRM-12?RAJ?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGTM-07?RBG?
1 31600 [9.3] 13900 [4.1]
56500 [16.6] 15 11.5
1325 [625] 0
2 40300 [11.8] 16200 [4.7] 1675 [790] 77
RGTM-09?ZAJ?
1 31200 [9.1] 14300 [4.2]
56000 [16.4] 15.5 11.5
1250 [590] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGTM-10?RBJ?
1 31300 [9.2] 14200 [4.2]
56500 [16.6] 15.5 11.5
1275 [602] 0
2 40300 [11.8] 16200 [4.7] 1675 [790] 77
ROLA-070E04
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1175 [554] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
ROLA-115E05
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RCFL-H*6024+RXMD-C04 Coil Only
1 29900 [8.8] 14600 [4.3]
56500 [16.6] 14 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RCFN-H*6024
RGFE-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFE-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFE-12?RCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGFG-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15 11
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGFG-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15 11
1200 [566] 0
2 40100 [11.7] 16400 [4.8] 1650 [779] 77
RGFG-12?RCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGGE-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGGE-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGGE-12?RCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1575 [743] 77
RGJF-09?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGJF-10?ZCM?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1200 [566] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGJF-12?RCM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1575 [743] 77
RGLE-07?BRQ?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGLE-10?BRM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGLE-12?ARM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 18
Air
Performance Data
16AJL Series
18
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
60
RCFN-H*6024
RGPE-07?BRQ?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RGPE-10?BRM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1225 [578] 0
2 39700 [11.6] 16800 [4.9] 1625 [767] 77
RGPE-12?ARM?
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 16 12
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1625 [767] 77
RGRM-09?ZAJ?
1 30400 [8.9] 14600 [4.3]
55500 [16.3] 15 11
1225 [578] 0
2 38700 [11.3] 16800 [4.9] 1625 [767] 77
RGRM-10?ZAJ?
1 29600 [8.7] 14900 [4.4]
56000 [16.4] 15 11
1150 [543] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGRM-12?RAJ?
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1225 [578] 0
2 39200 [11.5] 16800 [4.9] 1625 [767] 77
RGTM-07?RBG?
1 31600 [9.3] 13900 [4.1]
56500 [16.6] 15 11.5
1325 [625] 0
2 40300 [11.8] 16200 [4.7] 1675 [790] 77
RGTM-09?ZAJ?
1 31200 [9.1] 14300 [4.2]
56000 [16.4] 15.5 11.5
1250 [590] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
RGTM-10?RBJ?
1 31300 [9.2] 14200 [4.2]
56500 [16.6] 15.5 11.5
1275 [602] 0
2 40300 [11.8] 16200 [4.7] 1675 [790] 77
ROLA-070E04
1 30400 [8.9] 14600 [4.3]
56000 [16.4] 15.5 11.5
1175 [554] 0
2 39200 [11.5] 16800 [4.9] 1600 [755] 77
ROLA-115E05
1 30400 [8.9] 14600 [4.3]
56500 [16.6] 15.5 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RCFN-H*6024+RXMD-C04 Coil Only
1 29900 [8.8] 14600 [4.3]
56500 [16.6] 14 11.5
1200 [566] 0
2 39700 [11.6] 16800 [4.9] 1600 [755] 77
RCSL-H*6024 RHPL-HM6024
1 33000 [9.7] 13500 [4.0]
57500 [16.8] 16 12
1400 [661] 0
2 41500 [12.2] 16000 [4.7] 1700 [802] 77
RCSN-H*6024 RHPN-HM6024
1 28300 [8.3] 15700 [4.6]
57500 [16.8] 16 12
1000 [472] 0
2 41700 [12.2] 15800 [4.6] 1725 [814] 77
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling
Page 19
Air
Electrical and Physical Data
16AJL Series
19
Model
Number
16AJL
ELECTRICAL PHYSICAL
Phase Frequency (Hz) Voltage (Volts)
Compressor
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per Circuit Oz. [g]
Weight
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping Lbs. [kg]
Rev. 2/29/2012
24 1-60-208/230 13/13 58.3 0.8 14/14 20/20 20/20 16.39 [1.52] 1 2805[1324] 105.4 [2988] 154 [69.9] 171 [69.9]
36 1-60-208/230 17/17 83 1.9 22/22 30/30 35/35 21.85 [2.03] 1 3435[1621] 147 [4167] 181 [82.1] 201 [82.1]
48 1-60-208/230 23.6/23.6 104 1 28/28 35/35 45/45 21.85 [2.03] 1 3615[1706] 171 [4847] 249 [112.9] 269 [112.9]
60 1-60-208/230 28.8/28.8 152.9 2.8 35/35 45/45 60/60 21.85 [2.03] 1 3500[1652] 131.3 [3722] 254 [115.2] 274 [115.2]
NOTE: Factory Refrigerant Charge includes refrigerant for 15 feet of standard line set.
[ ] Designates Metric Conversions
Electrical and Physical Data
Page 20
Air
Unit Dimensions
16AJL Series
20
Unit Dimensions
Model No.
16AJL
Unit Dimensions
36, 48, 60 315/8 [803] 315/8 [803]
Width “W”
Inches [mm]
Length “L”
Inches [mm]
Height “H”
Inches [mm]
24 315/8 [803] 315/8 [803] 273/8 [695]
353/8 [899]
[ ] Designates Metric Conversions
Page 21
Air
Refrigerant Line Size Information
16AJL Series
21
Suction Line Length/Size versus Capacity Multiplier (R-410A)
Unit Size 2 Ton 3 Ton 4 Ton 5 Ton
Suction Line Connection Size 3/4" [19.05] I.D. 7/8" [22.23] I.D.
Suction Line Run—Feet [m]
5
/8" [15.88 mm] O.D. Optional
3
/4" [19.05 mm] O.D. Standard*
3
/4" [19.05 mm] O.D. Optional
7
/8" [22.23 mm] O.D. Standard*
7
/8" [22.23 mm] O.D. Optional
1
1
/8" [28.58 mm] O.D. Standard*
25' [7.62]
Optional Standard Optional
1.00
1.00 —
1.00
1.00 —
1.00
1.00 —
1.00
1.00 —
50' [15.24]
Optional Standard Optional
0.98
0.99 —
0.98
0.99 —
0.99
0.99 —
0.99
0.99 —
100' [30.48]
Optional Standard Optional
0.95
0.96 —
0.96
0.97 —
0.96
0.98 —
0.97
0.98 —
150' [45.72]
Optional Standard Optional
0.92
0.94 —
0.94
0.95 —
0.95
0.96 —
0.94
0.97 —
System
Capacity
Line Size
(Inch O.D.)
[mm]
Liquid Line Size – Outdoor Unit Above Indoor Coil
(Cooling Only—Does not apply to Heat Pumps)
Liquid Line Size – Outdoor Unit Below Indoor Coil
Minimum Vertical Separation—Feet [m] Maximum Vertical Separation—Feet [m]
25
[7.62]50[15.24]75[22.86]
100
[30.48]
125
[38.10]
150
[45.72]25[7.62]50[15.24]75[22.86]
100
[30.48]
125
[38.10]
150
[45.72]
Total Equivalent Length—Feet [m] Total Equivalent Length—Feet [m]
3 Ton
5/16 [7.94] 0 0 0 0 0 9 [2.74] 25 [7.62] 50 [15.24] 37 [11.28] 22 [6.71] 7 [2.13] N/A
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 68 [20.73] 63 [19.20] 58 [17.68] 53 [16.15]
4 Ton
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 46 [14.02] 38 [11.58] 30 [9.14] 22 [6.71] 15 [4.57] 1/2 [12.57] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 56 [17.07] 55 [16.76] 53 [16.15] 52 [15.85]
Liquid Line Sizing (R-410A)
5/16* [7.94] 0 0 0 0 0 0 25 [7.62] 36 [10.97] 29 [8.84] 23 [7.01] 16 [4.88] 9 [2.74]
2 Ton
1/4 [6.35] 0 3 [0.91] 29 [8.84] 55 [16.76] 81 [24.69] 108 [32.92] 23 [7.01] N/A N/A N/A N/A N/A
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 72 [21.95] 70 [21.34] 68 [20.73] 65 [19.81]
3/8
[9.53]
3/8
[9.53]
3/8
[9.53]
Liquid Line Connection
Size
(Inch I.D.)
5 Ton
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 56 [17.07] 44 [13.41] 32 [9.75] 20 [6.10] 1/2 [12.57] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 75 [22.86] 81 [24.69] 79 [24.08] 76 [23.16]
3/8
[9.53]
NOTES: *Standard line size
N/A = Application not recommended.
NOTES: *Standard line size
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
[ ] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information
Page 22
Air
Limited Warranty
16AJL Series
22
GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
*For complete details of the Limited and Conditional Warranties, including
applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
Conditional Parts
(Registration Required)...............................Ten (10) Years
Conditional Compressor
(Registration Required)...............................Ten (10) Years
Page 23
Air
Notes
16AJL Series
23
Page 24
The new degree of comfort.
Rheem Heating, Cooling & Water Heating • P.O. Box 17010
Fort Smith, Arkansas 72917 • www.rheem.com
In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
PRINTED IN U.S.A 06/12 QG FORM NO. A11-210