Rheem 14AJM Installation Manual

Page 1
RECOGNIZETHIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
DO NOT DESTROYTHIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL­LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
13 & 14.5 SEER SERIES
CONDENSING UNITS
11⁄2 - 5 TONS FEATURING
EARTH-FRIENDLY R-410A REFRIGERANT R-410
NOTE: Appearance of unit may vary.
(13 & 14.5 SEER MODELS IN CERTAIN MATCHED SYSTEMS)
SUPERSEDES 92-21354-78-00
92-21354-78-01
Page 2
TABLE OF CONTENTS
1.0 SAFETY INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Checking Product Received. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Electrical and Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 LOCATING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Condenser Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Operational Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 For Condensers With Space Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Customer Satisfaction Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.7 Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.8 Factory-Preferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.0 TOOLS REQUIRED FOR INSTALLING & SERVICING R-410A MODELS . . . . . 8
5.1 Specifications of R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Quick Reference Guide for R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.0 REPLACEMENT UNITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.0 EVAPORATOR COIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8.0 REPLACEMENT UNITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.0 INTERCONNECTING TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.1 Vapor and Liquid Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.2 Maximum Length of Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.3 Outdoor Unit Installed Above Indoor Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.4 Outdoor Unit Below Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.5 Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.6 Tubing Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9.7 Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10.0 EVACUATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11.0 START UP AND PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
12.0 CHECKING AIRFLOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
13.0 CHECKING REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
13.1 Charging Using Charging Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
13.2 Charging By Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
13.3 Final Leak Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14.0 ELECTRICAL WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14.1 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14.2 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14.3 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15.0 FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15.1 Compressor Crankcase Heat (CCH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15.2 Time Delay Control (TDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15.3 Low Ambient Control (LAC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
15.4 High and Low Pressure Controls (HPC & LPC). . . . . . . . . . . . . . . . . . . . . . 18
16.0 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
16.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
16.2 Single-Pole Compressor Contactor (CC). . . . . . . . . . . . . . . . . . . . . . . . . . . 18
17.0 TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
17.1 Electrical Checks Flow Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
17.2 Mechanical Checks Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
17.3 Superheat Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
17.4 Subcooling Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
17.5 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
18.0 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
18.1 PSC Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
18.2 ECM Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2
Page 3
1.0 SAFETY INFORMATION
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL­LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE HEAT PUMP CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS. ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE HEAT PUMP. YOU SHOULD BE AWARE THAT THE USE OF UNAU­THORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE HEAT PUMP AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBIL­ITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
WARNING
!
TURN OFF ELECTRIC POWER AT THE FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNECTION MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS. FAILURE TO DO SO CAN RESULT IN ELEC­TRICAL SHOCK, SEVERE PERSONAL INJURY OR DEATH.
CAUTION
!
The filter drier is located inside the control box. The filter drier must be installed externally in the liquid line or the Warranty will be VOID!
3
Page 4
WARNING
!
THE MANUFACTURER’S WAR­RANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS. ACCES­SORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFAC­TURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
2.0 GENERAL
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the air conditioning system. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions, and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the condensing unit specification sheet should be used.
IMPORTANT: We recommend replacement of any HVAC equipment that has been subjected to flooding in order to avoid any risk of injury or harm.
IMPORTANT: Use all available safety precautions during the installation and servic­ing of any HVAC equipment.
2.1 CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check condensing unit model number, electrical characteristics and accessories to determine if they are correct and match the original order from the local distributor. Check system components (evaporator coil, condensing unit, evaporator blower, etc.) to make sure they are properly matched.
2.2 APPLICATION
Before installing any air conditioning equipment, a duct analysis of the structure and a heat gain calculation must be made. A heat gain calculation begins by measuring all external surfaces and openings that gain heat from the surrounding air and quantifying that heat gain. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal.
There are several factors that the installers must consider:
• Outdoor unit location • Proper equipment evacuation
• System refrigerant charge • Indoor unit airflow
• Indoor unit blower speed • Supply and return air duct design and sizing
• System air balancing • Diffuser and return air grille location and sizing
4
Page 5
L
H
SEE DETAIL A
w
A-00008
2.3 (SEE FIGURE 1)
FIGURE 1
DIMENSIONS
AIR DISCHARGE: ALLOW
60” MINIMUM CLEARANCE.
AIR INLETS
(LOUVERED PANELS) ALLOW 6” MINIMUM CLEARANCE
SERVICE ACCESS
ALLOW 24” CLEARANCE
NOTE: GRILLE APPEARANCE MAY VARY.
DIMENSIONAL DATA
13 Seer Model Size
14.5 Seer Model Size
Height “H” (in.) [mm]
Length “L” (in.) [mm]
Width “W” (in.) [mm]
18, 24
241/4 [616] 235/8[600] 235/8 [600]
30 36, 42 48, 60
18, 24, 30 36, 42, 48, 60
1
/4 [616]
24 275/8[702]
5
27
/8 [702]
27 31 31
3
/8 [710]
5
/8[803]
5
/8 [803]
35 31 31
3
/8 [913]
5
/8[803]
5
/8 [803]
5
Page 6
2.4 ELECTRICAL & PHYSICAL DATA (SEE TABLE 1)
TABLE 1
ELECTRICAL AND PHYSICAL DATA – 13 SEER
Electrical Physical
Model
Number
Rev. 6/2/2009
18 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 8.43 1 1675 75.2 120 128
24 1-60-208/230 13.5/13.5 58.3 0.6 18/18 25/25 30/30 8.43 1 1665 73.8 121 129
30 1-60-208/230 12.8/12.8 73 0.6 17/17 20/20 25/25 10.29 1 2075 86.08 135 143
36 1-60-208/230 16.7/16.7 79 0.8 22/22 30/30 35/35 12.43 1 2690 96 159 167
42 1-60-208/230 17.9/17.9 112 0.8 24/24 30/30 40/40 16.39 1 2980 126.4 218 230
48 1-60-208/230 21.8/21.8 117 0.8 29/29 35/35 45/45 21.85 1 3175 144 225 237
60 1-60-208/230 26.4/26.4 134 1.2 35/35 45/45 60/60 21.85 1 3570 176 223 234
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load Amperes
(FLA)
Minimum
Circuit Ampacity Amperes
ELECTRICAL AND PHYSICAL DATA – 14.5 SEER
Electrical Physical
Model
Number
14AJM
Rev. 4/28/2009
18 1-60-208/230 9/9 48 0.8 12/12 15/15 20/20 16.39 1 2805 112 154 171
24 1-60-208/230 13.5/13.5 58.3 0.8 18/18 25/25 30/30 16.39 1 2805 105.6 154 171
30 1-60-208/230 12.8/12.8 64 0.8 17/17 25/25 25/25 16.39 1 3000 112 157 175
36 1-60-208/230 16.7/16.7 79 0.8 22/22 30/30 35/35 21.85 1 3570 130.4 181 201
42 1-60-208/230 17.9/17.9 112 2.8 26/26 30/30 40/40 21.85 1 3060 145.12 205 225
48 1-60-208/230 21.8/21.8 117 2.8 31/31 40/40 50/50 21.85 2 4105 216 246 269
60 1-60-208/230 26.4/26.4 134 2.8 36/36 45/45 60/60 21.85 2 4105 240 254 274
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load Amperes
(FLA)
Minimum
Circuit Ampacity Amperes
Fuse or HACR
Circuit Breaker
Minimum Amperes
Fuse or HACR
Circuit Breaker
Minimum Amperes
Maximum
Amperes
Maximum
Amperes
Outdoor Coil Weight
Face Area
Sq. Ft. [m
[0.78] [790] [2132] [54.4] [58.1]
[0.78] [786] [2092] [54.9] [58.5]
[0.96] [979] [2440] [61.2] [64.9]
[1.15] [1269] [2722] [72.1] [75.8]
[1.52] [1406] [3583] [98.9] [104.3]
[2.03] [1498] [4082] [102.1] [107.5]
[2.03] [1685] [4990] [101.2] [106.1]
Face Area
Sq. Ft. [m
[1.52] [1324] [3175] [69.8] [77.6]
[1.52] [1324] [2994] [69.8] [77.6]
[1.52] [1416] [3175] [71.2] [79.4]
[2.03] [1685] [3697] [82.1] [91.2]
[2.03] [1444] [4114] [92.9] [102.1]
[2.03] [1937] [6124] [112.9] [122]
[2.03] [1937] [6804] [115.2] [124.3]
No.
2
]
Rows
Outdoor Coil Weight
No.
2
]
Rows
CFM [L/s]
CFM [L/s]
Refrig.
Per Circuit Oz. [g]
Refrig.
Per Circuit Oz. [g]
Net
Lbs. [kg]
Net
Lbs. [kg]
Shipping Lbs. [kg]
Shipping Lbs. [kg]
NOTE: Factory Refrigerant Charge includes refrigerant for 15 feet of standard line set.
3.0 LOCATING UNIT
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
6
3.1 CORROSIVE ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
Page 7
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with an automobile polish will pro-
vide some protection.
A liquid cleaner may be used several times a year to remove matter that will not
wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
3.2 CONDENSER LOCATION
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor condenser.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perfor­mance or operation.
3.3 OPERATIONAL ISSUES
IMPORTANT: Locate the condenser in a manner that will not prevent, impair or
compromise the performance of other equipment horizontally installed in prox­imity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or manaufacturers’ recommendations, local code recommendations and requirements will take presidence.
Refrigerant piping and wiring should be properly sized and kept as short as
possible to avoid capacity losses and increased operating costs.
Locate the condenser where water run off will not create a problem with the
equipment. Position the unit away from the drip edge of the roof whenever pos­sible. Units are weatherized, but can be affected by water pouring into the unit from the junction of rooflines, without protective guttering.
3.4 FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances: Single Unit Applications: One condenser inlet air grille side may be reduced to no
less than a 6-inch clearance. Clearances below 6 inches will reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clear­ances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6­inch per unit clearance is recommended, for a total of 12 inches between two units. Two combined clearances below 12 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service, clearances.
3.5 CUSTOMER SATISFACTION ISSUES
The condenser should be located away from the living, sleeping and recreation-
al spaces of the owner and those spaces on adjoining property.
To prevent noise transmission, the mounting pad for the outdoor unit should
not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from entering the unit.
3.6 PROPER INSTALLATION
Proper sizing and installation of equipment is critical to achieve optimal perfor­mance. Use the information in this Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENER­GY STAR nents. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufac­turer’s refrigerant charging and air flow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
®
criteria for energy efficiency when matched with appropriate coil compo-
7
Page 8
3.7 UNIT MOUNTING
If elevating the condensing unit, either on a flat roof or on a slab, observe the following guidelines.
The base pan provided elevates the condenser coil 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration.
3.8 FACTORY-PREFERRED TIE-DOWN METHOD
INSTRUCTIONS:
IMPORTANT: These instructions are intended as a guide to securingequipment for wind­load ratings of “120 MPH sustained wind load”and “3-second, 150 MPH gust.”While this procedure is not mandatory, the Manufacturer doesrecommendthat equipment be prop­erly secured in areas where high wind damagemay occur.
STEP 1: Before installing, clear pad of any dirtor debris.
STEP 2: Center basepan on pad, ensuring it is level. STEP 3: Remove unittop panel by removingscrews around the perimeter of top panel.
STEP 4: Drill4 or 6 holes (1/4” diameter) in the unit basepan only STEP 5: Select and obtain appropriate concrete or lag screws and flatwashers per
STEP 6: Drillpilot holes in padthrough the basepan clearance holes drilledin Step 4,
STEP 7: Driveconcretescrews or lag screwsthrough
STEP 8: Re-connect fan motor wire leads to contactorper the unit wiringdiagram and
STEP 9: Finish unit installation per Sections 4 – 16 in this manual.
IMPORTANT: The pad mustbe constructed of industry-approved materials, and must be thickenough to accommodate the concrete fastener.
Disconnect fan motor leads from contactor and lay top panel aside taking care not to damagethe fan.
per figure 2.
figure 2.
1
ensuring that the holesare at least used. Use the concretescrew or lag screw manufacturer’srecommended hole diameter for the pilotholes.
and into the pad. Use flat washersunder the head of the screws. Snug screws to basepan.
NOTE: Do not over-tighten theconcrete or lag screws.Doing so can weakenor strip
the fastener and causeit to breakor pull out.
lower unit top onto the unit. Takecare to place the fan motor wire conduitin the slot in thetop of thecontrol box as the top is lowered ontothe unit. Re-install screws that attach unittop to the unit.
4” deeper than the concrete fastener being
1
4” clearance holes in unit basepan
4.0 REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
5.0 TOOLS REQUIRED FOR INSTALLING &
5.0 SERVICING R-410A MODELS
Manifold Sets:
-Up to 800 PSIG High Side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Ratiing of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
CAUTION
!
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
8
Page 9
FIGURE 2
TIE-DOWN KIT ASSEMBLY
(6) 1-1/2” x 1/4” CONCRETE SCREWS SNUG TO BASE PAN. LENGTH TO PENETRATE CONCRETE 1.5” MINIMUM. OR (6) 1-1/2” x 1/4” LAG SCREWS SNUG TO BASE PAN. LENGTH TO PENETRATE WOOD 1.5” MINIMUM SCREWS HAVE TO BE PLACED ON THE BASE PAN AS SHOWN UNLESS OTHERWISE SPECIFIED.
CONCRETE PAD SPECIFICATIONS:
GREATER THAN OR EQUAL TO 2-1/2” THICK SOLID CONCRETE DENSITY GREATER THAN OR EQUAL TO 144 LBS/FT PAD LENGTH GREATER THAN OR EQUAL TO (UNIT LENGTH +2”) PAD WIDTH GREATER THAN OR EQUAL TO (UNIT WIDTH +2)
(6) 1-1/2” x 1/4” CONCRETE SCREWS SNUG TO BASE PAN. LENGTH TO PENETRATE CONCRETE 1.5” MINIMUM. OR (6) 1-1/2” x 1/4” LAG SCREWS SNUG TO BASE PAN. LENGTH TO PENETRATE WOOD 1.5” MINIMUM SCREWS HAVE TO BE PLACED ON THE BASE PAN AS SHOWN UNLESS OTHERWISE SPECIFIED.
VIEW B
3
OR EQUIVALENT
VIEW A
13 SEER MODELS
18/24
30 B
36/42/48/60
14.5 SEER MODELS
18/24/30/36/
42/48/60
TIE DOWN
ASSEMBLY
VIEW
A 23.63” 23.63” 2.49” 19.77” 2.41” 19.63”
B
LWABCD E F
27.63” 27.63” 3.5”
31.63” 31.63” 5.63”
TIE DOWN ASSEMBLY DIMENSIONS
22.63”
24.50”
3.5” 22.63”
5.63” 24.50”
5.1 SPECIFICATION OF R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 condens­ing units.
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its saturaton pressure at 77°F is 224.5 psig.
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane (HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
have design pressure ratings appropriate for R-410A. Manifold sets need to range
IF ANY ACCUMULATOR IS UTILIZED, ADD 3.5” TO THE “A” DIMENSION AND 2” TO THE “C” DIMENSION FOR THIS HOLE LOCATION ONLY.
CENTER LINE
OF UNIT
CENTER LINE
OF UNIT
CENTER LINE
OF UNIT
CENTER LINE
OF UNIT
CENTER LINE
OF UNIT
CENTER LINE
OF UNIT
9
Page 10
up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
5.2 QUICK REFERENCE GUIDE FOR R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit. Only manufacturer approved liq­uid line filter driers can be used. These are Sporlan (CW083S) and Alco (80K083S) driers. These filter driers are rated for minimum working pressure of 600 psig.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
6.0 REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, liquid line filter drier sould be installed and refrigerant tubing should be properly sized. Test the oil for acid. If positive, a suction line filter drier is mandatory.
IMPORTANT: WHEN REPLACING AN R-22 UNIT WITH AN R-410A UNIT, EITHER REPLACE THE LINE SET OR ENSURE THAT THE EXISTING LINE SET IS THOROUGHLY CLEANED OF ANY OLD OIL OR DEBRIS.
7.0 EVAPORATOR COIL
REFER TO EVAPORATOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
CAUTION
!
Only use evaporators approved for use on R-410A systems. Use of existing R-22 evaporators can introduce mineral oil into the R-410Arefrigerant forming two differ­ent liquids and decreasing oil return to the compressor. This can result in com­pressorvfailure.
NOTE: All units must be installed with a TEV Evaporator.
The thermostat expansion valve is specifically designed to operate with R-410A.
DO NOT use an R-22 TEV or evaporator. The existing evaporator must be replaced with the factory specified TEV evaporator specifically designed for R-410A.
10
LOCATION
Do not install the indoor evaporator coil in the return duct system of a gas or oil fur­nace. Provide a service inlet to the coil for inspection and cleaning. Keep the coil pitched toward the drain connection.
Page 11
CAUTION
!
When coil is installed over a finished ceiling and/or living area, it is recommended that a secondary sheet metal condensate pan be constructed and installed under entire unit. Failure to do so can result in property damage.
8.0 REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. Test the oil for acid. If positive, a suction line filter drier is mandatory. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized.
9.0 INTERCONNECTING TUBING
9.1 VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made. Refer to Line Size Information in Tables 2 through 4 for correct size and multipliers to
be used to determine capacity for various vapor line diameters and lengths of run. The losses due to thelines being exposed to outdoor conditions are not included.
The factory refrigeration charge in the outdoor unit is sufficient for 15 feet of inter­connecting lines. The factory refrigeration charge in the outdoor unit is sufficient for the unit and 15 feet of standard size interconnecting liquid and vapor lines. For dif­ferent lengths, adjust the charge as indicated below.
1/4” ±0.2 oz. per foot 5/16” ±0.3 oz. per foot 3/8” ±0.5 oz. per foot 1/2” ±1.0 oz. per foot
9.2 MAXIMUM LENGTH OF LINES
The maximum length of interconnecting line is 150 feet. Always use the shortest length possible with a minimum number of bends. Additional compressor oil is not required for any length up to 150 feet.
NOTE: Excessively long refrigerant lines cause loss of equipment capacity.
9.3 OUTDOOR UNIT INSTALLED ABOVE INDOOR COIL
Keep the vertical separation between coils to a minimum. However, the vertical dis­tance can be as great as 120 feet with the condensing unit ABOVE the indoor coil. Use the following guidelines when installing the unit:
1. DO NOT exceed 120 feet maximum vertical separation.
2. Expansion Valve Coil: a. The vertical separation can be greater than the value in Table 3, but no
more than 120 feet.
b. No changes are required for expansion valve coils.
3. Always use the smallest liquid line size permitted to minimize the system charge.
4. Table 3 may be used for sizing horizontal runs.
9.4 OUTDOOR UNIT BELOW INDOOR COIL
Keep the vertical separation to a minimum. Use the following guidelines when installing the unit:
1. DO NOT exceed the vertical separations as indicated on Table 4.
2. Always use the smallest liquid line size permitted to minimize system charge.
3. Table 4 may be used for sizing horizontal runs.
9.5 TUBING INSTALLATION
Observe the following when installing correctly sized type “L” refrigerant tubing between the condensing unit and evaporator coil:
11
Page 12
If a portion of the liquid line passes through a hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required.
Use clean, dehydrated, sealed refrigeration grade tubing.
Always keep tubing sealed until tubing is in place and connections are to be made.
Blow out the liquid and vapor lines with dry nitrogen before connecting to the outdoor unit and indoor coil. For an air conditioning system, any debris in the line set could end up plugging the expansion device.
CAUTION
!
The filter drier is located inside the control box. The filter drier must be installed externally in the liquid line or the Warranty will be VOID!
If tubing has been cut, make sure ends are deburred while holding in a position to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes.
For best operation, keep tubing run as short as possible with a minimum num­ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a tubing bender on the vapor line to prevent kinking.
The vapor line must be insulated to prevent dripping (sweating) and prevent performance losses. Armaflex and Rubatex are satisfactory insulations for this purpose. Use 1/2” minimum insulation thickness, additional insulation may be required for long runs.
Check Table 2 for the correct vapor line size. Check Tables 4 and 5 for the cor­rect liquid line size.
9.6 TUBING CONNECTIONS
Indoor evaporator coils have only a holding charge of dry nitrogen. Keep all tube ends sealed until connections are to be made.
Use type “L” copper refrigeration tubing. Braze the connections with accepted industry practices.
Be certain both refrigerant service valves at the outdoor unit are closed.
TABLE 2
SUCTION LINE LENGTH/SIZE VS. CAPACITY MULTIPLIER (R-410A)
Unit Size
Suction Line
Connection Size
Suction Line
Run - Feet
Optional
Standard
25’
Optional Optional
Standard
50’
Optional Optional
100’
150’
NOTES:
*Standard Line Size Using suction line larger than shown in chart will result in poor oil return and is not recommended.
Standard
Optional Optional
Standard
Optional
1
2 Ton 2 Ton 21⁄2 Ton 3 Ton 31⁄2 Ton 4 Ton 5 Ton
1
3/4" I.D. 3/4" I.D. 3/4" I.D. 7/8" I.D. 7/8" I.D. 7/8" I.D. 7/8" I.D.
5/8
3/4*
---
1.00 1.00 1.00 1.00 1.00 1.00 1.00
1.00 1.00 1.00 1.00 1.00 1.00 1.00
--- --- 1.00 --- --- --- ---
0.98 0.98 0.96 0.98 0.99 0.99 0.99
0.99 0.99 0.98 0.99 0.99 0.99 0.99
--- --- 0.99 --- --- --- ---
0.95 0.95 0.94 0.96 0.96 0.96 0.97
0.96 0.96 0.96 0.97 0.98 0.98 0.98
--- --- 0.97 --- --- --- ---
0.92 0.92 0.91 0.94 0.94 0.95 0.94
0.93 0.94 0.93 0.95 0.96 0.96 0.97
--- ---
5/8
3/4* 3/4*
--- 7/8
5/8 3/4*
0.95
7/8
---
--- --- --- ---
3/4
7/8*
---
7/8*
1 1/8
---
7/8*
1 1/8
---
12
Page 13
TABLE 3
LIQUID LINE SIZE – OUTDOOR UNIT ABOVE INDOOR COIL
Outdoor Unit Above Indoor Coil
Liquid Line Size
System
Capacity
LineSize
Connection Size
(InchI.D.)
LineSize
(InchO.D.)
25 50 75 100 125 150
(Cooling Only - Does not apply to Heat Pumps)
Total Equivalent Length - Feet
Minimum Vertical Separation - Feet
1/4 0000824
1
1
2 Ton 3/8” 5/16 0 00000
3/8* 0 00000
1/4 0329 55 81 108
2 Ton 3/8” 5/16 0 00000
3/8* 0 00000
1/4 0 14 56 98 N/A N/A
1
2
2 Ton 3/8” 5/16 0 00000
3/8* 0 00000
3 Ton 3/8”
31⁄2 Ton 3/8”
4 Ton 3/8”
5 Ton 3/8”
NOTES:
*Standard Line Size N/A - Application not recommended.
5/16 0 00009 3/8* 0 00000 5/16 00016 35 54 3/8* 0 00000 3/8* 0 00000
1/2 0 00000
3/8* 0 00000
1/2 0 00000
TABLE 4
LIQUID LINE SIZE – OUTDOOR UNIT BELOW INDOOR COIL
Liquid Line Size
System
Capacity
LineSize
Connection Size
(InchI.D.)
LineSize
(InchOD)
25 50 75 100 125 150
Outdoor Unit Below Indoor Coil
Total Equivalent Length - Feet
Maximum Vertical Separation - Feet
1/4 25 40 25 9 N/A N/A
1
1
2 Ton 3/8” 5/16 25 50 62 58 53 49
3/8* 25 50 75 72 70 68
1/4 23 N/A N/A N/A N/A N/A
2 Ton 3/8” 5/16 25 36 29 23 16 9
3/8* 25 50 72 70 68 65
1/4 25 N/A N/A N/A N/A N/A
1
2
2 Ton 3/8” 5/16 25 49 38 27 17 6
3/8* 25 50 68 65 62 58
3 Ton 3/8”
31⁄2 Ton 3/8”
4 Ton 3/8”
5 Ton 3/8”
NOTES:
*Standard Line Size N/A - Application not recommended.
5/16 25 50 37 22 7 N/A
3/8* 25 50 68 63 58 53
5/16 25 23 4 N/A N/A N/A
3/8* 25 50 43 36 30 24 3/8* 25 46 38 30 22 15
1/2 25 50 56 55 53 52
3/8* 25 50 56 44 32 20
1/2 25 50 75 81 79 76
13
Page 14
Clean the fittings before brazing.
Remove the cap and schrader core from service port to protect seals from heat damage.
Use an appropriate heatsink material around the copper stub and the service valves before applying heat.
IMPORTANT: Do not braze any fitting with the TEV sensing bulb attached.
Braze the tubing between the outdoor unit and indoor coil. Flow dry nitrogen into a service port and through the tubing while brazing.
After brazing – use an appropriate heatsink material to cool the joint and remove any flux residue.
9.7 LEAK TESTING
Pressurize line set and coil through service fittings with dry nitrogen to 150 psig maximum. Leak test all joints using liquid detergent. If a leak is found, repair and repeat leak test procedures.
WARNING
!
DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY WITH OIL, WHICH CAN CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
10.0 EVACUATION PROCEDURE
Evacuation is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the line set and indoor coil.
Air in the system causes high condensing temperatures and pressure, resulting in increased power input and non-verifiable performance.
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric and hydrochloric acids. These attack motor windings and parts, causing breakdown.
After the system has been leak checked and proven sealed, connect the vacuum pump and evacuate system to 500 microns. The vacuum pump must be connected to both the high and low sides of the system through adequate connections. Use the largest size connections available since restrictive service connections may lead to false readings because of pressure drop through the fittings.
IMPORTANT: Compressors (especially scroll type) should never be used to evacu­ate the air conditioning system because internal electrical arcing may result in a damaged or failed compressor.
14
11.0 START UP AND PERFORMANCE
Even though the unit is factory charged with R410A, the charge must be checked to the charge table attached to the service panel and adjusted, if required. Allow a minimum of 5 minutes running. Before analyzing charge, see the instructions on the unit service panel rating plate for marking the total charge.
The service valves are not backseating valves. To open the valves, remove the valve cap with an adjustable wrench. Insert a 3/16” or 5/16” hex wrench into the stem. Backoutcounterclockwiseuntil it stops.
Replace the valve cap finger tight then tighten an additional 1/8 of a turn for a metal-to-metal seal.
12.0 CHECKING AIRFLOW
The air distribution system has the greatest effect. The duct system is totally con­trolled by the contractor. For this reason, the contractor should use only industry­recognized procedures.
The correct air quantity is critical to air conditioning systems. Proper operation, effi­ciency, compressor life, and humidity control depend on the correct balance between indoor load and outdoor unit capacity. Excessive indoor airflow increases the possibility of high humidity problems. Low indoor airflow reduces total capacity, and causes coil icing. Serious harm can be done to the compressor by low airflow, such as that caused by refrigerant flooding.
Page 15
Air conditioning systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet air­flow to all rooms in the home. This ensures a comfortable living space.
These simple mathematical formulas can be used to determine the CFM in a resi­dential or light commercial system.
Electric resistance heaters can use
CFM =
Gas furnaces can use
CFM =
An air velocity meter or airflow hood can give a more accurate reading of the sys­tem CFM.
volts x amps x 3.414
1.08 x temp rise
BTUH
T x 1.08
13.0 CHECKING REFRIGERANT CHARGE
Charge for all systems should be checked against the Charging Chart inside the access panel cover. Before using the chart, the indoor conditions must be within 2°F of desired comfort conditions and system must be run until operating conditions stabilize (15 min. to 30 min.)
CAUTION
!
THE TOP OF THE SCROLL COMPRESSOR SHELL IS HOT. TOUCHING THE COMPRESSOR TOP MAY RESULT IN SERIOUS PERSONAL INJURY.
IMPORTANT: Do not operate the compressor without charge in system.
Addition of R-410A will raise pressures (vapor, liquid and discharge) and lower vapor temperature.
If adding R-410A raises both vapor pressure and temperature, the unit is over­charged.
IMPORTANT: Use industry-approved charging methods to ensure proper system charge.
13.1 CHARGING USING CHARGING CHART
NOTE: THIS UNIT CONTAINS R-410A REFRIGERANT.
DO NOT CHARGE WITH R-22 REFRIGERANT.
The liquid pressure method is used for charging systems in the cooling mode. The service port on the liquid (small valve) and suction (large valve) is used for this pur­pose.
Verify that the outdoor unit is running in the cooling mode and the indoor air mover is delivering the maximum airflow for this system size. Read and record the outdoor ambient temperature. Read and record the liquid and suction pressures at the ports on the liquid and suction valves.
If refrigerant lines are sized using the nameplate charge, the correct liquid pressure is found at the intersection of the suction pressure and the outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
CAUTION
!
R-410A PRESSURES ARE APPROXIMATELY 60% HIGHER THAN R-22 PRESSURES. USE APPROPRIATE CARE WHEN USING THIS REFRIGER­ANT. FAILURE TO EXERCISE CARE MAY RESULT IN EQUIPMENT DAM­AGE, OR PERSONAL INJURY.
15
Page 16
If the refrigerant lines utilize extended lengths, add 4 psi to the liquid pressure val­ues shown in the chart.
1. Remove refrigerant charge if the refrigerant liquid pressure is above the cor­rected chart value.
2. Add refrigerant charge if the liquid pressure is below the corrected chart value.
13.2 CHARGING BY WEIGHT
For a new installation, evacuation of interconnecting tubing and evaporator coil is adequate; otherwise, evacuate the entire system. Use the factory charge shown in Table 1 of these instructions or unit data plate. Note that charge value includes charge required for 15 ft. of standard size interconnecting liquid line. Calculate actu­al charge required with installed liquid line size and length using:
1/4” O.D. = 0.2 oz./ft. 5/16” O.D. = 0.3 oz./ft. 3/8” O.D. = 0.5 oz./ft. 1/2” O.D. = 1.0 oz./ft.
With an accurate scale (+/– 1 oz.) or volumetric charging device, adjust charge dif­ference between that shown on the unit data plate and that calculated for the new system installation. If the entire system has been evacuated, add the total calculat­ed charge.
NOTE: When the total refrigerant charge volume exceeds the values in Table 7, the manufacturer recommends installing a crankcase heater and start kit.
13.3 FINAL LEAK TESTING
After the unit has been properly evacuated and charged, a halogen leak detector should be used to detect leaks in the system. All piping within the condensing unit, evaporator, and interconnecting tubing should be checked for leaks. If a leak is detected, the refrigerant should be recovered before repairing the leak. The Clean Air Act prohibits releasing refrigerant into the atmosphere.
WARNING
!
TURN OFF ELECTRIC POWER AT THE FUSE BOX OR SERVICE PANEL BEFORE MAKING ANY ELECTRICAL CONNECTIONS.
ALSO, THE GROUND CONNEC­TION MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS. FAILURE TO DO SO CAN RESULT IN ELECTRICAL SHOCK, SEVERE PERSONAL INJURY OR DEATH.
14.0 ELECTRICAL WIRING
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local code.
14.1 GROUNDING
A grounding lug is provided near the contactor for a ground wire.
WARNING
!
THE UNIT MUST BE PERMANENTLY GROUNDED. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
14.2 POWER WIRING
It is important that proper electrical power from a commercial utility is available at the condensing unit contactor. Voltage ranges for operation are shown in Table 5.
Power wiring must be run in a rain-tight conduit. Conduit must be run through the connector panel below the access cover (See Figure 1) and attached to the bottom of the control box.
Connect power wiring to contactor located in outdoor condensing unit electrical box. (See wiring diagram attached to unit access panel.)
Check all electrical connections, including factory wiring within the unit and make sure all connections are tight.
DO NOT connect aluminum field wire to the contactor terminals.
16
TABLE 5
VOLTAGE RANGES (60 HZ)
Operating Voltage Range at Copeland
Nameplate Voltage Maximum Load Design Conditions for
Compressors
208/230 (1 Phase) 187 - 253
Page 17
14.3 CONTROL WIRING
(See Figure 3)
If the low voltage control wiring is run in conduit with the power supply, Class I insu­lation is required. Class II insulation is required if run separate. Low voltage wiring may be run through the insulated bushing provided in the 7/8 hole in the base panel, up to and attached to the pigtails from the bottom of the control box. Conduit can be run to the base panel if desired by removing the insulated bushing.
A thermostat and a 24 volt, 40 VA minimum transformer are required for the control circuit of the condensing unit. The furnace or the air handler transformer may be used if sufficient. See the wiring diagram for reference. Use 18-gauge thermostat wire only.
15.0 FIELD INSTALLED ACCESSORIES
15.1 COMPRESSOR CRANKCASE HEAT (CCH)
While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added. Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase heater to minimize refrigerate migra­tion, and to help eliminate any start up noise or bearing “wash out.”
NOTE: The installation of a crankcase heater is recommended if the system charge exceeds the values listed in Table 6.
All heaters are located on the lower half of the compressor shell. Its purpose is to drive refrigerant from the compressor shell during long off cycles, thus preventing damage to the compressor during start-up.
At initial start-up or after extended shutdown periods, make sure the heater is ener­gized for at least 12 hours before the compressor is started. (Disconnect switch on and wall thermostat off.)
TABLE 6
MAXIMUM SYSTEM CHARGE VALUES – 13 SEER
13 SEER Compressor Charge Limit Charge Limit
Model Model Without Crankcase Without Crankcase
Size Number Heat (1 Phase) Heat (3 Phase)
18 ZP16K5E 9.6 lbs. 24 ZP20K5E 9.6 lbs. 30 ZP24K5E 9.6 lbs. 36 ZP31K5E 9.6 lbs. 8 lbs. 42 ZP36K5E 12 lbs. 10 lbs. 48 ZP42K5E 12 lbs. 10 lbs. 60 ZP51K5E 12 lbs. 10 lbs.
MAXIMUM SYSTEM CHARGE VALUES – 14.5 SEER
14.5 SEER Compressor Charge Limit Model Model Without Crankcase
Size Number Heat (1 Phase)
18 ZP16K5E 9.6 lbs. 24 ZP20K5E 9.6 lbs. 30 ZP24K5E 9.6 lbs. 36 ZP31K5E 9.6 lbs. 42 ZP34K5E 12 lbs.
NOTE: Model sizes 48 and 60 have a factory installed crankcase heater.
15.2 TIME DELAY CONTROL (TDC)
The time delay (TDC) is in the low voltage control circuit. When the compressor shuts off due to a power failure or thermostat operation, this control keeps it off at least 5 minutes which allows the system pressure to equalize, thus not damaging the compressor or blowing fuses on start-up.
17
Page 18
FIGURE 3
CONTROL WIRING FOR GAS OR ELECTRIC HEAT
FOR TYPICAL GAS OR OIL HEAT
FOR TYPICAL ELECTRIC HEAT
15.3 LOW AMBIENT CONTROL (LAC)
This component senses compressor head pressure and shuts the heat pump fan off when the head pressure drops to approximately 220 PSIG [1516.8 kPa]. This allows the unit to build a sufficient head pressure at lower ambient in order to main­tain system balance and obtain improved capacity. Low ambient control should be used on all equipment operated below 70°F [21.1°C] ambient.
15.4 HIGH AND LOW PRESSURE CONTROLS (HPC & LPC)
These controls keep the compressor from operating in pressure ranges which can cause damage to the compressor. Both controls are in the low voltage control cir­cuit.
High pressure control (HPC) is an auto-reset which opens near 610 PSIG and closes at 420 PSIG.
The low pressure control (LPC) is an automatic reset which opens near 50 PSIG and closes near 95 PSIG.
16.0 SERVICE
16.1 OPERATION
Single phase units are operated PSC (no starting components). It is important that such systems be off for a minimum of 5 minutes before restarting to allow equaliza­tion of pressure. The thermostat should not be moved to cycle unit without waiting 5 minutes. To do so may cause the compressor to go off on an automatic overload device or blow a fuse. Poor electrical service can also cause nuisance tripping on overloads, trip a breaker, or cause light dimming. This generally can be corrected by adding start components. Check with factory for recommended start compo­nents, if required. For PSC type operation, refrigerant metering must be done with fixed orifice, cap tubes or bleed type expansion valves because of low starting torque. If non-bleed expansion valve coils (supplied by factory) are used, start com­ponents are required.
18
16.2 SINGLE-POLE COMPRESSOR CONTACTOR (CC)
Single-pole contactors are used on all standard single phase units up through 5 tons. Caution must be exercised when servicing as only one leg of the power sup­ply is broken with the contactor.
Page 19
17.0 TROUBLE SHOOTING
In diagnosing common faults in the air conditioning system, it is useful to present the logical pattern of thought that is used by experienced technicians. The charts which follow are not intended to be an answer to all problems, but only to guide your thinking as you attempt to decide on your course of action. Through a series of yes and no answers, you will follow the logical path to a likely conclusion.
Use these charts as you would a road map, if you are a beginning technician. As you gain experience, you will learn where to establish the shortcuts. Remember that the chart will help clarify the logical path to the problem.
17.1 ELECTRICAL CHECKS FLOW CHART
Unit Running?
YES
Repair and Recheck
YES
Repair and Recheck
YES
Run Capacitor
Start Capacitor
Potential Relay
Compressor Internal
Overload Open
NO
Thermostat Problem?
NO
Transformer Problem?
NO
Voltage on Compressor
Side of Contactor?
NO
Circuit Breakers
or Fuses Open
YES
YES
Go to
Mechanical Checks
NO
Voltage on Line
Side of Contactor?
YES
Compressor Contactor
Hi Pressure Control
Compressor Winding Open
Unit Wiring and
Connections
Compressor Winding
Grounded
Condenser Fan
Grounded
Grounded Capacitor
Replace Fuses
or Reset Breakers and Recheck
Lo Pressure Control
Compressor Time-Delay
Unit Wiring and
Connections
19
Page 20
17.2 MECHANICAL CHECKS FLOW CHART
Unit Running?
YES
Pressure problems?
High Head Pressure
Inoperative Outdoor Fan
Overcharge Low Ambient Temperature
Recirculation of
Condenser Air
Non-condensibles
Low Head Pressure
Low on Charge Dirty FiltersDirty Condenser Coil
Open IPR Valve Dirty Evaporator
Inoperative Compressor
Valves
Restricted Filter-drier
NO
Go to Electrical
Checks Flow Chart
Low Suction Pressure
Inadequate Airflow
Broken Indoor
Blower Belt
Inoperative Indoor Blower
Higher than Ambient
Air Entering Condenser
Wrong Condenser Fan Rotation
Indoor Metering Device
Stuck Open
Restriction in System
Indoor Metering
Device Stuck
Closed
Low on Charge
Faulty Metering Device
Restriction in System
Restricted Filter-drier
Recirculation of
Evaporator Air
Wrong Evaporator
Blower Rotation
Inadequate Ducts
20
Page 21
TABLE 7
TEMPERATURE PRESSURE CHART
TEMP R-410A
(Deg. F) PSIG
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60 0.4
-50 5.1
-40 10.9
-35 14.2
-30 17.9
-25 22.0
-20 26.4
-15 31.3
-10 36.5
-5 42.2 0 48.4 5 55.1
10 62.4 15 70.2 20 78.5 25 87.5 30 97.2 35 107.5 40 118.5 45 130.2 50 142.7 55 156.0 60 170.1 65 185.1 70 201.0 75 217.8 80 235.6 85 254.5 90 274.3
95 295.3 100 317.4 105 340.6 110 365.1 115 390.9 120 418.0 125 446.5 130 476.5 135 508.0 140 541.2 145 576.0 150 612.8
17.3 SUPERHEAT CALCULATION
1. Measure the suction pressure at the suction line service valve.
2. Convert the suction pressure to saturated temperature. See Table 7.
3. Measure the temperature of the suction line at the suction line service valve.
4. Compare the temperature of the suction line to the saturated temperature.
5. The difference between saturated temperature and suctin line temperature is the superheat. Superheat normal range 12° to 15°.
17.4 SUBCOOLING CALCULATION
1. Measure the liquid pressure at the liquid line service valve.
2. Convert the liquid line pressure to saturated temperature. See Table 7.
3. Measure the liquid line temperature at the liquid line service valve.
4. Compare the liquid line temperature to the saturated temperature.
5. The difference between saturated temperature and liquid line temperature is the subcooling. Subcooling normal range 9° to 12°.
TABLE 8
AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPS
AIR CONDITIONING SYSTEM
TROUBLESHOOTING TIPS
SYSTEM PROBLEM
Overcharge High High Low High High
Undercharge Low Low High Low Low
Liquid Restriction (Drier) Low Low High High Low
Low Evaporator Airflow Low Low Low Low Low
Dirty Condenser High High Low Low High
Low Outside Ambient Temperature Low Low High High Low
Inefficient Compressor Low High High High Low
TXV Feeler Bulb Charge Lost Low Low High High Low
Poorly Insulated Sensing Bulb High High Low Low High
DISCHARGE SUCTION
PRESSURE PRESSURE AMPS
INDICATORS
SUPERHEAT SUBCOOLING
COMPRESSOR
21
Page 22
17.5 GENERAL
TROUBLE SHOOTING CHART
!
WARNING
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing unit
Outdoor fan runs, compressor • Run or start capacitor defective • Replace
doesn’t • Start relay defective • Replace
Insufficient cooling • Improperly sized unit • Recalculate load
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
Registers sweat • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component
High head-high or normal vapor • Dirty outdoor coil • Clean coil
pressure - Cooling mode • Refrigerant overcharge • Correct system charge
Low head-high vapor pressures • Flowcheck piston size too large • Change to correct size piston
Low vapor - cool compressor - • Low indoor airflow • Increase speed of blower or reduce restriction - replace air
iced indoor coil filter
High vapor pressure • Excessive load • Recheck load calculation
Fluctuating head & vapor • TXV hunting • Check TXV bulb clamp - check air distribution on coil - replace
pressures TXV
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
• Thermostat out of calibration-set too high • Reset
• Defective contactor • Check for 24 volts at contactor coil - replace if contacts are open
• Blown fuses / tripped breaker • Replace fuses / reset breaker
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) • Reset-also see high head pressure remedy-The high pressure control opens at 450 PSIG
• Loose connection • Check for correct voltage at compressor ­check & tighten all connections
• Compressor stuck, grounded or open motor winding, • Wait at least 2 hours for overload to reset.
open internal overload. If still open, replace the compressor.
• Low voltage condition • Add start kit components
• Improper indoor airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
nameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
filter
• Flowcheck piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
• Outdoor fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
• Defective Compressor valves • Replace compressor
• Incorrect capillary tubes • Replace coil assembly
• Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
• Defective compressor • Replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
22
Page 23
01-19-04
JHB
90-101229-01
01
18.0 WIRING DIAGRAMS
FIGURE 4
18.1 PSC DIAGRAM SINGLE-PHASE WIRING DIAGRAM
23
Page 24
FIGURE 5
18.2 ECM DIAGRAM
24 CM 0509
Loading...