Rheem 12104793, 12104794, 12104795 Installation Instructions Manual

WARNING: Plumber – Be Aware
Use copper pipe ONLY. Plastic pipe MUST NOT be used.
It is a requirement of a solar water heater installation that all
pipe work be in copper and not plastic, due to the effects of
high water temperatures.
Installation Instructions
Collector Kits
Collectors with Copper Waterways, Conetite Connections
for use in Open Circuit Systems
LCS, TBT200
SOLAR COLLECTORS
This collector kit must be installed and serviced by a qualified person.
Please leave this guide with the householder.
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the
solar collectors MUST BE of copper. All compression fittings must use brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating
application and capable of withstanding temperatures of up to 150°C, which may be generated by the solar collectors under stagnation conditions.
The specification of the chosen insulation material should be checked with the insulation manufacturer prior to installation as different materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to
comply with the requirements of either AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as applicable under the Plumbing Code of Australia.
be weatherproof and UV resistant if exposed extend through any penetrations in the eaves, ceiling and roof cover valves and fittings in the solar pipe work be fitted up to and cover the connections on both the solar storage tank
and the solar collectors.
Note: Failure to observe these requirements also increases the risk of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or where it may be in contact with a metal roof, may lead to freeze damage. The system has NO WARRANTY for freeze damage if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions.
The insulation is essential to assist in providing freeze protection, will offer protection to a metal roof against corrosion due to water running off the copper pipes, assist in avoiding accidental contact with the solar pipe work as very high temperature water can flow from the solar collectors to the solar storage tank, and also reduce pipe heat losses.
Plumber: It is important to refer to and read in full the complete
“Warning: Plumber – Be Aware” statement commencing on page 14.
2

CONTENTS

HOUSEHOLDER - This installation instruction booklet is
intended for the installer but you may find it of interest.
Notice to Victorian Customers from the
Victorian Plumbing Industry Commission.
This water heater must be installed by a licensed person
as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that the work complies with all the relevant Standards. Only a licensed person will have insurance protecting their workmanship for 6 years. Make sure you use a licensed person to install this water heater and ask for your Compliance Certificate.
Components And Kit Contents .................................................. 4
System Installation ...................................................................... 6
Installation – Solar Storage Tank ............................................... 8
Installation – Solar Collectors .................................................... 9
Roof Assembly Of Solar Collectors ......................................... 18
Connection Details .................................................................... 26
Pipe Work Roughing In Dimensions ........................................ 33
Exploded Views – Solar Collectors .......................................... 36
Warranty Note ............................................................................ 39
3
SOLAR COLLECTOR KITS – CONETITE FITTINGS
For installation with a pumped open circuit solar water heater.
Your solar water heater is designed for the solar collectors to be roof mounted and the solar storage tank to be installed at ground or floor level. The collector kits are suitable for:
Collector Kit – Conetite Fittings 1 Collector (uncoated brass conetites)
12104793 LCS, TBT200 solar collectors
Collector Kit – Conetite Fittings 2 Collectors (uncoated brass conetites)
12104794 LCS, TBT200 solar collectors
Collector Kit –Conetite Fittings Additional Collector (uncoated brass conetites)
12104795 LCS, TBT200 solar collectors Note: One Additional Collector Kit is required for a third solar collector.

COMPONENTS AND KIT CONTENTS

WARNINGS
Warning: Only use components with cones of uncoated DR Brass as part of
an open circuit system. Coated brass cones must not be used.
Warning: This parts kit shall not be used with a solar collector with a steel absorber plate. Use only with collectors which have copper waterways and conetite style connections.
4
COMPONENTS AND KIT CONTENTS
Part No
Kit Components and Description
12104793
one
collector
12104794
two
collectors
12104795
collector
add on
347229
Installation instructions roof kit
1 1 1
347587
Warning Sheet – DR Brass conetite kits
1 1 1
331847
Collector rail (1020 mm)
2 - 2
331846
Collector rail (1650 mm)
- 2 -
204600
Collector straps
4 4 2
331844
Drive cleat
- - 2
331928
Collector clamps
4 8 4
209130 209124 209118
Hex screw set M8 x 20, and Washer M8 SS flat, and Nut SS M8 x 1.25 mm
4 4 4
8 8 8
4 4 4
341390
Collector connector (collector union) assembly conetite brass
- 2 2
341391
Collector bung (end plug) assembly conetite brass - consisting of:
1 x 344236 collector bung uncoated 1 x 337116 gland nut
2 2 -
344269
Sensor connector fitting conetite brass – 15BSP temp assbly direct - consisting of:
1 x 344268 fitting conetite -15BSP temp
sensor 1 x 337116 gland nut 1 x 088062 sensor nipple solar loline 1 x 087026 O ring 5/16” ID x 1/16 BS011
silicone
1 1 -
344278
Connector fitting conetite brass – 15BSP assbly direct - consisting of:
1 x 344267 fitting conetite -15BSP 1 x 337116 gland nut
1 1
331656
Olive ½” brass
2 2 -
331655
Nut compression G½
2 2 -
346025
or
056029
Hot sensor assembly immersion including 2 x 087025 O-ring 5/32” ID x 1/16”
1 1 -
346026
Hot sensor adaptor
1 1 -
123204
Label hot pipe / cold pipe
1 1 -
348071
Cable ties 150 mm long
10
10
-
5

SYSTEM INSTALLATION

THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
The system is suitable for installation with LCS or TBT200 selective surface solar collectors as part of an open circuit system installation.
The system is not suitable for installation above 400 metres altitude.

IMPORTANT NOTES

Working on roofs is and should always be considered a hazardous activity,
particularly early in the morning, late in the evening, when the roof is wet and during and after periods of rain.
All work must be carried out in accordance with Local, State and Federal
Occupational Safety, Health and Welfare Regulations. In particular, the requirements for safety whilst manual lifting, working at heights and on roofs.
Installers must be competently trained in:
Height Hazard Assessment Working at Height Procedures Assessment / Use / Wearing of correct height safety equipment
(harnesses etc.)
All other relevant safety factors specific to the installation and
maintenance work to be compliant with suitable Occupational, Health and Safety Regulations / Codes.
All relevant permits shall be obtained from the regulatory authorities before
commencing work to install the solar hot water system.
All work carried out must be performed by appropriately qualified
tradespeople or be suitably supervised for trades assistant duties.
Every care must be taken to protect and warn occupants of the building and
the public from personal injury which may occur from falling tools, roof materials, fittings or any other hazards of a general nature.
Advise the occupants of any inconvenience which may occur due to
disconnection of existing water and electrical supplies.
The connection, attachment, integration or general association of other
equipment or parts which either directly or indirectly affect the operation or performance of this equipment could void the manufacturer’s warranty.
6
SYSTEM INSTALLATION

INSTALLATION STANDARDS

The water heater must be installed:
by a qualified person, and in accordance with the installation instructions, and in compliance with Standards AS/NZS 3500.4 or AS/NZS 3500.5:2012
Section 3 (for a Class 1a or Class 10 building) as applicable under the Plumbing Code of Australia, AS/NZS 3000 and all local codes and regulatory authority requirements.
In New Zealand, the installation must also conform to Clause G12 of the New Zealand Building Code.

WATER HEATER APPLICATION

This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable water. Its use in an application other than this may shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or business, then there should be back-up redundancy within the hot water system design. This should ensure the continuity of hot water supply in the event that this water heater was to become inoperable for any reason. We recommend you provide advice to the system owner about their needs and building back-up redundancy into the hot water supply system.

OPEN CIRCUIT SYSTEM INSTALLATION

An open circuit system has a collector circuit which is directly connected to the potable water in the solar storage tank. Potable water from the solar storage tank circulates through and collects heat gained by the solar collectors and then circulates back into the solar storage tank.
Warning: Only use components with cones of uncoated DR Brass as part of
an open circuit system. Coated brass cones must not be used.

Freeze Protection

The system has a level of freeze protection designed to guard the system against damage from freeze conditions. The system must be installed with the full length of the solar hot and solar cold pipes insulated to offer protection against freeze damage (refer to “Warning: Plumber Be Aware” on page 14). Freeze conditions occur below 6°C.
The system has NO WARRANTY for freeze damage when installed above 400 metres altitude or if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions (refer to “Warranty Note” on page 39).Note: The manufacturer’s warranty against freeze damage applies only to systems installed in Australia.
7

INSTALLATION – SOLAR STORAGE TANK

SOLAR WATER HEATER STORAGE TANK LOCATION

The solar storage tank should be installed close to the most frequently used outlet and its position chosen with safety and service in mind.
Consideration must also be given to the position of the solar storage tank in relation to the solar collectors. There are limitations on both the maximum length of the solar hot and solar cold pipes and the maximum height between the solar storage tank and the solar collectors. Refer to “Solar Collector Location” on page 9, to “Pipe Lengths” on page 13 and to “Maximum Height to Collectors” on page 16.
Refer to the installation instructions supplied with the solar storage tank for installation details of the solar storage tank.
8

INSTALLATION – SOLAR COLLECTORS

SOLAR COLLECTOR LOCATION

Consideration must be given to the position of the solar collectors in relation to the solar storage tank. There are limitations on both the maximum length of the solar hot and solar cold pipes and the maximum height between the solar storage tank and the solar collectors. Refer to “Solar Storage Tank Location” on page 8, to “Pipe Lengths” on page 13 and to “Maximum Height to Collectors” on page 16.
The solar collectors must be installed in a shade free position. The surrounds should be checked for higher buildings or trees which may cause shade at other times of the year and for small trees which may grow and shade the solar collectors in the future.
The installation must comply with the requirements of either AS/NZS 3500.4 or AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as applicable under the Plumbing Code of Australia, and all local codes and regulatory authority requirements.

ROOF STRENGTH

The installer must ensure the structural integrity of the building is not compromised by the solar water heater installation and the roof structure is suitable to carry the full weight of the solar collectors and frame (if one is installed). If in any doubt of the construction or the condition of the roof, the roof should be suitably strengthened. Consult a structural engineer. Each solar collector and its fittings weighs approximately 41 kg when full of water.

ROOF AREA FOR INSTALLATION

Roof area required for solar collectors: 3 solar collectors – 3.4 m wide x 2.0 m deep. Weight (full) 123 kg approx. 2 solar collectors – 2.3 m wide x 2.0 m deep. Weight (full) 82 kg approx. 1 solar collector – 1.2 m wide x 2.0 m deep. Weight (full) 41 kg approx. In addition to this area, a minimum of one (1) metre clearance is recommended
to be left around the solar collectors on all four sides of the solar collectors for safe service access.

Maximum Number of Collectors

The maximum number of these selective surface collectors for each tank size as part of an open circuit system is:
410 tank – 3 x collectors 270, 320, 325 tanks – 2 x collectors 160 tank – 1 x collector (2 in Victoria only)
9
INSTALLATION – SOLAR COLLECTORS

ORIENTATION OF SOLAR COLLECTORS

To help maximise system performance, solar collectors should be installed with an optimum orientation facing true north (in the southern hemisphere) or true south (in the northern hemisphere). Always check for true north or true south using a compass or other suitable device.
The solar performance of a system reduces as the orientation of the collectors moves away from the optimum orientation, resulting in the need for increased boosting to supply the same hot water load. Solar collectors facing up to 45° from the optimum orientation will receive about 4% to 5% less total solar radiation.
However, the optimum orientation of solar collectors is not always practical or achievable. Solar collectors may be installed up to 90° from the optimum orientation. Where the orientation is greater than 60° from the optimum, it may be possible for an additional solar collector to be installed to help make up for the reduction in solar performance compared to the optimum orientation. This option should be discussed with the system owner.
If this option is neither possible nor acceptable to the system owner, then the system owner needs to be made aware of, understand and accept that increased boosting may be required to meet their hot water requirements.
In Australia for climate zones 1, 2, and 3 there is a risk that systems with selective surface LCS or TBT200 solar collectors may over perform.
In these zones, systems with 2 or more LCS or TBT200 solar collectors should be installed at orientations between 60° and 90° from true north only.
In climate zone 4, systems with selective surface LCS or TBT200 solar collectors provide optimum performance compared with non-selective surface collectors, particularly in the months of lower solar radiation.
In Victoria where a system with a 160 litre tank is installed, 2 x LCS solar collectors should only be installed outside of the Regulation Compliance Zone in order to achieve compliance. In areas other than Victoria, a 160 litre tank should not be installed with more than one selective surface collector.
10
INSTALLATION – SOLAR COLLECTORS

INCLINATION OF SOLAR COLLECTORS

To help maximise system performance, solar collectors should be installed with an optimum inclination. This is equal to 90% to 100% of the local latitude angle when collectors are oriented within 60° of true north or true south, and between 10° and 20° when the collectors are oriented between 60° and 90° from the optimum orientation.
Generally, improved summer performance is obtained from an angle of inclination less than the optimum angle and improved winter performance is obtained by an angle of inclination greater than the optimum angle. If the angle of inclination varies by 20° from the optimum angle, the solar collectors will receive about 10% less total annual solar radiation. The latitude of some
Australian cities are listed on page 12.
However, the optimum inclination of solar collectors is not always practical or achievable. Solar collectors may be installed at the roof angle for simplicity of installation and appearance, but must never be flat for a pumped solar open circuit water heater installation. Although the solar collectors can be installed with an inclination of less than 10°, this is not advised. The risks include:
the collector glass not 'self-cleaning', leading to dirty collector glass reducing
solar performance, and
condensation on the underside of the glass taking longer to clear, and condensation droplets falling onto the absorber plate potentially causing
discolouration.
The collector kit is suitable for installations with an inclination of up to 45°. Where the solar collectors are installed at inclinations greater than 45°, a With Pitch frame is necessary. Refer to your local Solar Distributor for details.
A Variable Pitch frame can be installed to increase the angle of inclination of the collectors used in a pumped solar water heater installation. This type of frame should be used if the roof pitch either varies by more than 20° from the optimum angle or is less than 10°.
The use of a Variable Pitch frame should be discussed with the system owner. If this option is neither possible nor acceptable to the system owner, it may be possible for an additional solar collector to be installed to help make up for the reduction in solar performance compared to the optimum inclination. This option should be discussed with the system owner.
If these options are neither possible nor acceptable to the system owner, then the system owner needs to be made aware of, understand and accept that increased boosting may be required to meet their hot water requirements.
11
INSTALLATION – SOLAR COLLECTORS
Adelaide
35°S
Cairns
17°S
Hobart
42°S
Port Hedland
20°S
Alice Springs
24°S
Canberra
35°S
Mildura
34°S
Rockhampton
24°S
Brisbane
27°S
Darwin
12°S
Melbourne
38°S
Sydney
34°S
Broken Hill
31°S
Geraldton
28°S
Perth
32°S
Townsville
19°S

CYCLONIC OR HIGH WIND AREAS

For an installation of solar collectors on a pitched roof in a cyclonic or high wind area, a suitable With Pitch frame is required. Refer to your local Solar Distributor for details.
The installation of these solar collectors on a suitable frame, subject to the frame’s design criteria not being exceeded:
may be suitable for installation in geographic locations up to and within Wind
Region D (With Pitch frame) or up to and within Wind Region C (Variable Pitch frame), as defined in the Building Code of Australia, Australian Standard AS 4055 and the Australian / New Zealand Standard AS/NZS 1170.2, or equivalent locations, and
may provide an acceptable method of installation where it is necessary to
satisfy the requirements of the Building Code of Australia for high wind areas, or equivalent requirements.

LATITUDE OF SOME AUSTRALIAN CITIES

12
Loading...
+ 28 hidden pages