Use copper pipe ONLY. Plastic pipe MUST NOT be used.
It is a requirement of a solar water heater installation that all
pipe work be in copper and not plastic, due to the effects of
high water temperatures.
Installation Instructions
Collector Kits
Collectors with Copper Waterways, Conetite Connections
for use in Open Circuit Systems
using uncoated DR Brass Conetite fittings
LCS, TBT200
SOLAR COLLECTORS
This collector kit must be installed and serviced by a qualified person.
Please leave this guide with the householder.
Page 2
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the
solar collectors MUST BE of copper. All compression fittings must use
brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating
application and capable of withstanding temperatures of up to 150°C,
which may be generated by the solar collectors under stagnation
conditions.
The specification of the chosen insulation material should be checked
with the insulation manufacturer prior to installation as different
materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to
comply with the requirements of either AS/NZS 3500.4 or
AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as
applicable under the Plumbing Code of Australia.
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar pipe work
be fitted up to and cover the connections on both the solar storage tank
and the solar collectors.
Note: Failure to observe these requirements also increases the risk
of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or
where it may be in contact with a metal roof, may lead to freeze damage.
The system has NO WARRANTY for freeze damage if the solar hot and
solar cold pipes are not insulated in accordance with the installation
instructions.
The insulation is essential to assist in providing freeze protection, will offer
protection to a metal roof against corrosion due to water running off the
copper pipes, assist in avoiding accidental contact with the solar pipe work
as very high temperature water can flow from the solar collectors to the
solar storage tank, and also reduce pipe heat losses.
Plumber: It is important to refer to and read in full the complete
“Warning: Plumber –Be Aware” statement commencing on page 14.
2
Page 3
CONTENTS
HOUSEHOLDER - This installation instruction booklet is
intended for the installer but you may find it of interest.
Notice to Victorian Customers from the
Victorian Plumbing Industry Commission.
This water heater must be installed by a licensed person
as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that
the work complies with all the relevant Standards. Only a licensed person will
have insurance protecting their workmanship for 6 years. Make sure you use
a licensed person to install this water heater and ask for your Compliance
Certificate.
Components And Kit Contents .................................................. 4
System Installation ...................................................................... 6
Installation – Solar Storage Tank ............................................... 8
Installation – Solar Collectors .................................................... 9
Roof Assembly Of Solar Collectors ......................................... 18
For installation with a pumped open circuit solar water heater.
Your solar water heater is designed for the solar collectors to be roof mounted and
the solar storage tank to be installed at ground or floor level. The collector kits are
suitable for:
12104795 LCS, TBT200 solar collectors
Note: One Additional Collector Kit is required for a third solar collector.
COMPONENTS AND KIT CONTENTS
WARNINGS
Warning: Only use components with cones of uncoated DR Brass as part of
an open circuit system. Coated brass cones must not be used.
Warning: This parts kit shall not be used with a solar collector with a steel
absorber plate. Use only with collectors which have copper waterways and
conetite style connections.
4
Page 5
COMPONENTS AND KIT CONTENTS
Part No
Kit Components and Description
12104793
one
collector
12104794
two
collectors
12104795
collector
add on
347229
Installation instructions roof kit
1 1 1
347587
Warning Sheet – DR Brass conetite kits
1 1 1
331847
Collector rail (1020 mm)
2 - 2
331846
Collector rail (1650 mm)
- 2 -
204600
Collector straps
4 4 2
331844
Drive cleat
- - 2
331928
Collector clamps
4 8 4
209130
209124
209118
Hex screw set M8 x 20, and
Washer M8 SS flat, and
Nut SS M8 x 1.25 mm
1 x 344267 fitting conetite -15BSP
1 x 337116 gland nut
1 1
331656
Olive ½” brass
2 2 -
331655
Nut compression G½
2 2 -
346025
or
056029
Hot sensor assembly immersion
including 2 x 087025 O-ring 5/32” ID x 1/16”
1 1 -
346026
Hot sensor adaptor
1 1 -
123204
Label hot pipe / cold pipe
1 1 -
348071
Cable ties 150 mm long
10
10
-
5
Page 6
SYSTEM INSTALLATION
THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
The system is suitable for installation with LCS or TBT200 selective surface solar
collectors as part of an open circuit system installation.
The system is not suitable for installation above 400 metres altitude.
IMPORTANT NOTES
Working on roofs is and should always be considered a hazardous activity,
particularly early in the morning, late in the evening, when the roof is wet and
during and after periods of rain.
All work must be carried out in accordance with Local, State and Federal
Occupational Safety, Health and Welfare Regulations. In particular, the
requirements for safety whilst manual lifting, working at heights and on roofs.
Installers must be competently trained in:
Height Hazard Assessment
Working at Height Procedures
Assessment / Use / Wearing of correct height safety equipment
(harnesses etc.)
All other relevant safety factors specific to the installation and
maintenance work to be compliant with suitable Occupational, Health and
Safety Regulations / Codes.
All relevant permits shall be obtained from the regulatory authorities before
commencing work to install the solar hot water system.
All work carried out must be performed by appropriately qualified
tradespeople or be suitably supervised for trades assistant duties.
Every care must be taken to protect and warn occupants of the building and
the public from personal injury which may occur from falling tools, roof
materials, fittings or any other hazards of a general nature.
Advise the occupants of any inconvenience which may occur due to
disconnection of existing water and electrical supplies.
The connection, attachment, integration or general association of other
equipment or parts which either directly or indirectly affect the operation or
performance of this equipment could void the manufacturer’s warranty.
6
Page 7
SYSTEM INSTALLATION
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with Standards AS/NZS 3500.4 or AS/NZS 3500.5:2012
Section 3 (for a Class 1a or Class 10 building) as applicable under the
Plumbing Code of Australia, AS/NZS 3000 and all local codes and regulatory
authority requirements.
In New Zealand, the installation must also conform to Clause G12 of the New
Zealand Building Code.
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the
purpose of heating potable water. Its use in an application other than this may
shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is
necessary for the application or business, then there should be back-up
redundancy within the hot water system design. This should ensure the continuity
of hot water supply in the event that this water heater was to become inoperable
for any reason. We recommend you provide advice to the system owner about
their needs and building back-up redundancy into the hot water supply system.
OPEN CIRCUIT SYSTEM INSTALLATION
An open circuit system has a collector circuit which is directly connected to the
potable water in the solar storage tank. Potable water from the solar storage tank
circulates through and collects heat gained by the solar collectors and then
circulates back into the solar storage tank.
Warning: Only use components with cones of uncoated DR Brass as part of
an open circuit system. Coated brass cones must not be used.
Freeze Protection
The system has a level of freeze protection designed to guard the system against
damage from freeze conditions. The system must be installed with the full length
of the solar hot and solar cold pipes insulated to offer protection against freeze
damage (refer to “Warning: Plumber Be Aware” on page 14). Freeze conditions
occur below 6°C.
The system has NO WARRANTY for freeze damage when installed above
400 metres altitude or if the solar hot and solar cold pipes are not insulated in
accordance with the installation instructions (refer to “Warranty Note” on
page 39).Note: The manufacturer’s warranty against freeze damage applies only
to systems installed in Australia.
7
Page 8
INSTALLATION – SOLAR STORAGE TANK
SOLAR WATER HEATER STORAGE TANK LOCATION
The solar storage tank should be installed close to the most frequently used
outlet and its position chosen with safety and service in mind.
Consideration must also be given to the position of the solar storage tank in
relation to the solar collectors. There are limitations on both the maximum length
of the solar hot and solar cold pipes and the maximum height between the solar
storage tank and the solar collectors. Refer to “Solar Collector Location” on
page 9, to “Pipe Lengths” on page 13 and to “Maximum Height to Collectors” on
page 16.
Refer to the installation instructions supplied with the solar storage tank for
installation details of the solar storage tank.
8
Page 9
INSTALLATION – SOLAR COLLECTORS
SOLAR COLLECTOR LOCATION
Consideration must be given to the position of the solar collectors in relation to
the solar storage tank. There are limitations on both the maximum length of the
solar hot and solar cold pipes and the maximum height between the solar storage
tank and the solar collectors. Refer to “Solar Storage Tank Location” on page 8,
to “Pipe Lengths” on page 13 and to “Maximum Height to Collectors” on page 16.
The solar collectors must be installed in a shade free position. The surrounds
should be checked for higher buildings or trees which may cause shade at other
times of the year and for small trees which may grow and shade the solar
collectors in the future.
The installation must comply with the requirements of either AS/NZS 3500.4 or
AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as
applicable under the Plumbing Code of Australia, and all local codes and
regulatory authority requirements.
ROOF STRENGTH
The installer must ensure the structural integrity of the building is not
compromised by the solar water heater installation and the roof structure is
suitable to carry the full weight of the solar collectors and frame (if one is
installed). If in any doubt of the construction or the condition of the roof, the roof
should be suitably strengthened. Consult a structural engineer. Each solar
collector and its fittings weighs approximately 41 kg when full of water.
ROOF AREA FOR INSTALLATION
Roof area required for solar collectors:
3 solar collectors – 3.4 m wide x 2.0 m deep. Weight (full) 123 kg approx.
2 solar collectors – 2.3 m wide x 2.0 m deep. Weight (full) 82 kg approx.
1 solar collector – 1.2 m wide x 2.0 m deep. Weight (full) 41 kg approx.
In addition to this area, a minimum of one (1) metre clearance is recommended
to be left around the solar collectors on all four sides of the solar collectors for
safe service access.
Maximum Number of Collectors
The maximum number of these selective surface collectors for each tank size as
part of an open circuit system is:
410 tank – 3 x collectors
270, 320, 325 tanks – 2 x collectors
160 tank – 1 x collector (2 in Victoria only)
9
Page 10
INSTALLATION – SOLAR COLLECTORS
ORIENTATION OF SOLAR COLLECTORS
To help maximise system performance, solar collectors should be installed with
an optimum orientation facing true north (in the southern hemisphere) or true
south (in the northern hemisphere). Always check for true north or true south
using a compass or other suitable device.
The solar performance of a system reduces as the orientation of the collectors
moves away from the optimum orientation, resulting in the need for increased
boosting to supply the same hot water load. Solar collectors facing up to 45° from
the optimum orientation will receive about 4% to 5% less total solar radiation.
However, the optimum orientation of solar collectors is not always practical or
achievable. Solar collectors may be installed up to 90° from the optimum
orientation. Where the orientation is greater than 60° from the optimum, it may
be possible for an additional solar collector to be installed to help make up for
the reduction in solar performance compared to the optimum orientation. This
option should be discussed with the system owner.
If this option is neither possible nor acceptable to the system owner, then the
system owner needs to be made aware of, understand and accept that increased
boosting may be required to meet their hot water requirements.
In Australia for climate zones 1, 2,
and 3 there is a risk that systems
with selective surface LCS or
TBT200 solar collectors may over
perform.
In these zones, systems with 2 or
more LCS or TBT200 solar
collectors should be installed at
orientations between 60° and 90°
from true north only.
In climate zone 4, systems with selective surface LCS or TBT200 solar collectors
provide optimum performance compared with non-selective surface collectors,
particularly in the months of lower solar radiation.
In Victoria where a system with a 160 litre tank is installed, 2 x LCS solar
collectors should only be installed outside of the Regulation Compliance Zone in
order to achieve compliance. In areas other than Victoria, a 160 litre tank should
not be installed with more than one selective surface collector.
10
Page 11
INSTALLATION – SOLAR COLLECTORS
INCLINATION OF SOLAR COLLECTORS
To help maximise system performance, solar collectors should be installed with
an optimum inclination. This is equal to 90% to 100% of the local latitude angle
when collectors are oriented within 60° of true north or true south, and between
10° and 20° when the collectors are oriented between 60° and 90° from the
optimum orientation.
Generally, improved summer performance is obtained from an angle of
inclination less than the optimum angle and improved winter performance is
obtained by an angle of inclination greater than the optimum angle. If the angle
of inclination varies by 20° from the optimum angle, the solar collectors will
receive about 10% less total annual solar radiation. The latitude of some
Australian cities are listed on page 12.
However, the optimum inclination of solar collectors is not always practical or
achievable. Solar collectors may be installed at the roof angle for simplicity of
installation and appearance, but must never be flat for a pumped solar open
circuit water heater installation. Although the solar collectors can be installed with
an inclination of less than 10°, this is not advised. The risks include:
the collector glass not 'self-cleaning', leading to dirty collector glass reducing
solar performance, and
condensation on the underside of the glass taking longer to clear, and
condensation droplets falling onto the absorber plate potentially causing
discolouration.
The collector kit is suitable for installations with an inclination of up to 45°. Where
the solar collectors are installed at inclinations greater than 45°, a With Pitch
frame is necessary. Refer to your local Solar Distributor for details.
A Variable Pitch frame can be installed to increase the angle of inclination of the
collectors used in a pumped solar water heater installation. This type of frame
should be used if the roof pitch either varies by more than 20° from the optimum
angle or is less than 10°.
The use of a Variable Pitch frame should be discussed with the system owner. If
this option is neither possible nor acceptable to the system owner, it may be
possible for an additional solar collector to be installed to help make up for the
reduction in solar performance compared to the optimum inclination. This option
should be discussed with the system owner.
If these options are neither possible nor acceptable to the system owner, then
the system owner needs to be made aware of, understand and accept that
increased boosting may be required to meet their hot water requirements.
11
Page 12
INSTALLATION – SOLAR COLLECTORS
Adelaide
35°S
Cairns
17°S
Hobart
42°S
Port Hedland
20°S
Alice Springs
24°S
Canberra
35°S
Mildura
34°S
Rockhampton
24°S
Brisbane
27°S
Darwin
12°S
Melbourne
38°S
Sydney
34°S
Broken Hill
31°S
Geraldton
28°S
Perth
32°S
Townsville
19°S
CYCLONIC OR HIGH WIND AREAS
For an installation of solar collectors on a pitched roof in a cyclonic or high wind
area, a suitable With Pitch frame is required. Refer to your local Solar Distributor
for details.
The installation of these solar collectors on a suitable frame, subject to the
frame’s design criteria not being exceeded:
may be suitable for installation in geographic locations up to and within Wind
Region D (With Pitch frame) or up to and within Wind Region C (Variable
Pitch frame), as defined in the Building Code of Australia, Australian
Standard AS 4055 and the Australian / New Zealand Standard
AS/NZS 1170.2, or equivalent locations, and
may provide an acceptable method of installation where it is necessary to
satisfy the requirements of the Building Code of Australia for high wind
areas, or equivalent requirements.
LATITUDE OF SOME AUSTRALIAN CITIES
12
Page 13
INSTALLATION – SOLAR COLLECTORS
Maximum recommended total combined pipe length (solar hot + solar cold)
and number of 90° bends
Pipe Size
1 or 2 Collectors
3 Collectors
Pipe Length
90° Bends
Pipe Length
90° Bends
DN15
40 metres
20
30 metres
20
DN20
NR
NR
40 metres
20
For each additional 90° bend, reduce the maximum total pipe length by 0.5 m.
For each additional metre of pipe length, reduce the number of 90° bends by two.
Note: One 90° elbow is equal to two 90° bends.
NR – not recommended, NA – not available
PIPE LENGTHS
The solar hot and solar cold pipes between the solar storage tank and the solar
collectors shall:
be of bendable grade or hard drawn copper tube.
Annealed or soft copper shall not be used.
have a continuous fall from the solar collectors to the solar storage tank.
Horizontal runs of pipe work are acceptable and may be installed as part of
an open circuit system.
Care must be taken to ensure the pipe work maintains a continuous fall or
horizontal runs over the life of the installation. Pipe work should be fixed at
regular intervals to assist in maintaining this requirement.
not exceed the maximum recommended combined lengths as specified in
the table.
Notes:
It is important to connect the solar hot and solar cold pipes to the correct
connections at the solar collectors and at the solar storage tank.
The solar cold pipe connects to the bottom of the solar collector array and
may connect to either the left or right hand side. The solar hot pipe must
connect to the top of the solar collector array diagonally opposite to the solar
cold pipe connection. The solar hot outlet connection is to be the highest
point of the system.
The hot sensor connection is at the solar hot outlet where the solar hot pipe
connects to the solar collector for this open circuit system.
Refer to “Warning: Plumber – Be Aware” on page 14.
It is essential for these requirements to be followed for the system to operate
correctly and efficiently. Solar pipe work which is oversized, or is too long, or
does not have a continuous fall can result in a reduction in performance or the
system not operating effectively.
13
Page 14
INSTALLATION – SOLAR COLLECTORS
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the
solar collectors MUST BE of copper. All compression fittings must use
brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating
application and capable of withstanding temperatures of up to 150°C,
which may be generated by the solar collectors under stagnation
conditions
The specification of the chosen insulation material should be checked
with the insulation manufacturer prior to installation as different
materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to
comply with the requirements of either AS/NZS 3500.4 or
AS/NZS 3500.5:2012 Section 3 (for a Class 1a or Class 10 building) as
applicable under the Plumbing Code of Australia
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar pipe work
be fitted up to and cover the connections on both the solar storage tank
and the solar collectors.
Note: Failure to observe these requirements also increases the risk
of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or
where it may be in contact with a metal roof, may lead to freeze damage.
The system has NO WARRANTY for freeze damage if the solar hot and
solar cold pipes are not insulated in accordance with the installation
instructions.
The insulation is essential to assist in providing freeze protection, will offer
protection to a metal roof against corrosion due to water running off the
copper pipes, assist in avoiding accidental contact with the solar pipe work
as very high temperature water can flow from the solar collectors to the
solar storage tank, and also reduce pipe heat losses.
14
Page 15
INSTALLATION – SOLAR COLLECTORS
WARNING: Plumber – Be Aware
The insulated copper pipe work:
should be fixed at suitable locations to prevent or reduce the possibility
of noise from water hammer and vibration from occurring
is not to be placed or installed in contact with plastic pipe work.
Likewise, plastic pipe work is not to be placed or installed in contact
with the insulated copper pipe work after the solar circuit is installed.
The solar hot outlet and hot sensor connection is to be the highest point of
the system. The highest point of the solar hot and solar cold pipes must be
where they connect to the solar collectors, to avoid the possibility of air
locks occurring in the system. There MUST BE a continuous fall in the
pipe work from the solar collectors to the solar storage tank. Horizontal
runs of pipe work are acceptable and may be installed as part of an open
circuit system.
Plastic pipe MUST NOT be used, as it will not withstand the temperature
and pressure of the water generated by the solar collectors under
stagnation conditions. Extremely high water temperatures up to 150°C for
non-selective surface collectors and greater than 200°C for selective
surface collectors and extremely high water pressures can be generated
under these conditions. Plastic pipe cannot withstand these temperatures
and pressures and MUST NOT be used. Failure of plastic pipe can lead to
the release of high temperature water and cause severe water damage
and flooding.
The pressure applied to the solar circuit and solar collectors during a
pressure test of an open circuit system MUST NOT exceed 1000 kPa,
otherwise damage may result.
Refer to “Pressure Testing” on page 17.
Upon completion of the installation of the solar collectors with conetite
fittings, the packaging material may be removed whether or not the solar
circuit is connected to the solar storage tank and / or the solar water heater
is commissioned, without damage to the solar collectors.
15
Page 16
INSTALLATION – SOLAR COLLECTORS
Maximum Height to Collectors
The maximum height of a pumped open circuit solar installation, from the solar
controller (circulator) to the top of the solar collectors, is determined by the
maximum recommended total pipe length for the system and the water supply
pressure.
The maximum recommended total pipe length of the solar circuit should not be
exceeded and a minimum water supply pressure of 200 kPa should be available
at the inlet to the system, otherwise the system performance may be reduced or
the solar circuit may not be purged of air during the commissioning of the system.
Open Circuit Solar
Pipe Work Installation Requirements
16
Page 17
INSTALLATION – SOLAR COLLECTORS
Pressure Testing
The solar water heater, including the collector circuit, is to be isolated during the
testing and commissioning of the heated water reticulation system in a building
in accordance with Clause 9.3 (a) of AS/NZS 3500.4:2015 or Clause 3.34.2 (a)
of AS/NZS 3500.5:2012 for a Class 1a or Class 10 building as applicable under
the Plumbing Code of Australia. The collector circuit includes the solar hot and
solar cold pipes and solar collectors.
It may be necessary to pressure test the collector circuit to comply with codes
and regulatory authority requirements or on other occasions where the solar
collectors and solar hot and solar cold pipes are installed prior to the solar
storage tank, such as on a building site.
Collector Circuit
Warning: The pressure applied to the collector circuit during a pressure test
of an open circuit system MUST NOT exceed 1000 kPa where LCS or TBT200
collectors are installed, otherwise damage may result to the solar collectors.
Open Circuit System
If the solar collectors, solar pipe work and solar storage tank are installed and
commissioned together, then the flooding of the collector circuit with water under
mains pressure for an open circuit system and checking the pipe work for leaks
during the commissioning procedure can be substituted for the pressure testing
of the collector circuit.
17
Page 18
ROOF ASSEMBLY OF SOLAR COLLECTORS
Notes:
Warning: This parts kit shall not be used with J, KF or T200 steel
collectors. Use only with collectors which have copper waterways and
conetite style connections.
These solar collectors have passed the AS/NZS 2712 requirements for
resistance to hailstone damage, so it is not normally necessary to fit a guard
to a collector. Stone Guards are available to provide a level of protection to
the collectors against vandalism or accidental damage. Refer to your local
Solar Distributor for details.
The manufacturer’s warranty DOES NOT cover breakage of solar collector
glass. Check your insurance policy covers collector glass breakage.
Warning: No attempt should be made to remove or replace broken
collector glass.
The collector glass is not offered as a replacement part. Should the solar
collector require replacement, contact your local Solar Distributor for details.
Warning: Do not remove the solar collector packaging completely, prior
to the installation as the solar collector surface can become very hot. Remove
only sufficient packaging material to enable the installation of the solar
collectors.
Upon completion of the installation of the solar collectors with conetite fittings,
such as on a building site, the packaging material may be removed whether
or not the solar circuit is connected to the solar storage tank and / or the solar
water heater is commissioned, without damage to the solar collectors.
The solar collector packaging must be removed completely prior to the
permanent operation of the water heater.
All connectors, unions, end plugs, brass fittings, collector straps and collector
rails required for the installation are included with the collector kit. Suitable
screws or anchors will be required to fix the collector straps to the rafters for
a pitched roof installation.
Clamps, screws, washers and nuts to secure the solar collector(s) to the
collector rails are included with the collector kit.
All olive compression fittings must use brass or copper olives. Use an
approved thread sealant such as Teflon tape on all other threaded joints.
Conetite fittings do not require a thread sealant.
Roof Condition: Check the condition of the roof and advise the client of any
broken tiles or damaged roof sheeting before commencing the installation.
18
Page 19
ROOF ASSEMBLY OF SOLAR COLLECTORS
Numbers in parentheses refer to items in the diagrams on page 36 (one solar
collector installation), page 37 (two solar collector installation) and page 38 (three
solar collector installation).
DO NOT MODIFY THESE PARTS IN ANY WAY
1. Solar Frame: If a solar frame is to be installed, determine the location of the
frame(s). Refer to “Solar Collector Location” on page 9 and the installation
instructions provided with the frame(s).
Assemble and fix the frame(s) to the roof in accordance with the installation
instructions provided with the frame.
Depending upon the positioning of the frame on the roof and any minor fall
the roof may have, ensure the collector rail is either horizontal or is higher
on the hot outlet side of the solar collectors. If in doubt use a spirit level.
Proceed to step 4.
2. Solar Collector Location: If a solar frame is not installed, select a suitable
position for the solar collectors. Refer to “Solar Collector Location” on
page 9.
3. Collector Rail (bottom) – Pitched Roof Installation: Determine the
location of the bottom collector rail(s) (1). If more than two solar
collectors (17) are installed, locate the collector rail (1) from the Additional
Collector kit adjacent to the first collector rail (1) and join together using the
drive cleat (8) supplied in the Additional Collector kit.
Note: The collector straps (2) are to be fitted to the collector rail(s) (1) before
fixing the straps to the rafters.
Determine which slots in the bottom collector rail (1) will be used for the
collector straps (2) after locating the rafters and taking note of the rafter
spacing. Hook two collector straps (2) to the first bottom collector rail
(long) (1) and one collector strap (2) to the additional bottom single collector
rail (short) (1) (if used).
Refer to “Hooking Collector Strap to Collector Rail” on page 26 and Detail A
on page 27.
When positioned, the collector rail is to be either horizontal or have a rise
across the solar collectors from the solar cold connection side up to the solar
hot connection side for an open circuit system. The solar hot outlet and hot
sensor connection is to be the highest point of the system.
Note:Refer also to “Tile Roof with a flat tile profile” on page 20 if the
installation is on a tile roof where the tile has a flat profile. Additional
requirements for the positioning of the collector rail and installation of the
solar collectors apply.
19
Page 20
Horizontal
Horizontal
Solar Hot
Outlet
Position top
of collector
as low as
practical
on roof tile
ENVELOPE COLLECTORS
EXTRUDED RAIL
30-40mm
from
horizontal
Solar Hot
Outlet
15-20mm
from horizontal
Solar Cold Inlet
15-20mm
from horizontal
Solar Cold Inlet
30-40mm
from
horizontal
Position topof collectoras low aspracticalon roof tile
ROOF ASSEMBLY OF SOLAR COLLECTORS
Tile Roof with a flat tile profile: If the installation is on a tile roof with a flat
tile profile, the solar collectors (17) must be installed at an angle from the
horizontal to assist in rainwater runoff. The solar hot outlet side must be on
the left hand side and the solar cold inlet must be on the right hand side of
the collector array.
The top end of the solar collector on the solar cold inlet side must sit atop
the lower end of a tile lap. Measure down the roof approximately 1940 mm
from this point to determine the position of the bottom collector rail.
Ensure the end of the collector rail (1) at the outlet side (left hand side) of
the solar collectors is higher up the roof than the end of the collector rail at
the inlet side (right hand side) of the solar collectors by:
15 – 20 mm for one solar collector, or
30 – 40 mm for two solar collectors, or
45 – 60 mm for three solar collectors.
This is to provide a downward angle along the top end of the collectors to
assist in rainwater runoff in order to prevent pooling.
Flat Tile Profile – Collector Angle From Horizontal
Failure to adhere to this requirement may result in pooling of rainwater at
the top of the collectors. If the top end of the collector array is too close to
the lap of the tiles, there is a risk of pooling water seeping up and under the
tile lap. The rainwater runoff is to flow from left to right to reduce the risk of
water working through the joints between tiles.
20
Page 21
ROOF ASSEMBLY OF SOLAR COLLECTORS
Tile Roof: Remove the tiles on the next row above the position of the
collector rail (1) to expose the rafters. Position the collector rail (1) and fix
the collector straps (2) directly to the rafters, using suitable screws or
anchors. Replace the tiles.
Metal Roof: Position the collector rail (1) and fix the collector straps (2) to
the rafters, through the metal roofing material, using suitable screws or
anchors. Care should be taken not to mark Colorbond or other metal roof
sheet with a marking pen and to remove all swarf from the metal roof as
these can cause deterioration of the metal roofing material.
Note: Fixings are to penetrate through the high point in the roof material
profile. AS/NZS 3500.4 states a minimum of three (3) screws 40 mm long
be used per fixing strap. Longer screws or anchors may be required to
achieve a 40 mm minimum embedment into rafters for a metal roof.
Additional screws or anchors may be required.
4. Solar Collectors: Using a lifting device, lift the first solar collector (17) onto
the roof and place it carefully with the lower end seated in the collector
rail (1) and prior to positioning the next solar collector, firmly clamp (two
clamps per collector) to the collector rail using the clamps, hex screws,
washers and nuts provided.
Repeat this procedure for additional collectors (17), firmly clamping each
collector to the collector rail (1) with two clamps (13) prior to positioning a
subsequent collector.
Refer to “Clamping Collector to Collector Rail” on page 29.
Note: Firmly clamping each solar collector to the collector rail as it is placed
in position reduces the possibly of the collector(s) accidently moving or
sliding off the collector rail.
Remove the red transit plugs from the collector sockets.
5. Collector Unions: Couple the solar collectors (17) together using the
collector unions (3) supplied in the collector kit.
Refer to “Coupling Collector to Collector – Conetite Fittings” on page 28.
Note: It will be necessary to loosen the clamps on a collector prior to it being
coupled to its adjacent collector. Secure the clamps again on each collector
after it is coupled to the adjacent collector.
6. Fixing Collector (Bottom): Ensure the solar collectors (17) are correctly
positioned, centred and well seated in the collector rail(s) (1).
Tighten the clamps (13) on each solar collector (17).
Refer to “Clamping Collector to Collector Rail” on page 29.
21
Page 22
ROOF ASSEMBLY OF SOLAR COLLECTORS
7. Collector Rail (top) – Pitched Roof Installation: If more than two solar
collectors (17) are installed, at the top end of the solar collectors (17) locate
the second collector rail (1) from the Additional Collector kit adjacent to the
first collector rail (1) and join together using the driver cleat (8) supplied in
the Additional Collector kit.
Note: The collector straps (2) are to be fitted to the collector rail(s) (1) before
fixing the straps to the rafters.
Determine which slots in the top collector rail (1) will be used for the collector
straps (2) after locating the rafters and taking note of the rafter spacing.
Hook two collector straps (2) to the first top collector rail (long) (1) and one
collector strap (2) to the additional top single collector rail (short) (1) (if
used).
Refer to “Hooking Collector Strap to Collector Rail” on page 26 and Detail B
on page 27.
Locate the top collector rail(s) (1) against and underneath the top end of the
solar collectors.
8. Fixing Collector (Top): Ensure the solar collectors (17) are correctly
positioned, centred and well seated in the collector rail (1).
Clamp the solar collectors (17) (two clamps per collector) to the collector
rail (1), using the clamps (13), hex screws, washers and nuts provided.
Refer to “Clamping Collector to Collector Rail” on page 29.
straps (2) to the rafters.
Tile Roof: Remove the tiles on the next row above the position of the top
collector rail (1) to expose the rafters. Once the collector rail (1) is in position,
fix the collector straps (2) directly to the rafters, using suitable screws or
anchors. Replace the tiles.
Metal Roof: Once the collector rail (1) is in position, fix the collector straps (2)
to the rafters, through the metal roofing material, using suitable screws or
anchors. The collector straps (2) may be cut to a length of approximately
100 mm to retain the aesthetics of the installation.
Note: Fixings are to penetrate through the high point in the roof material
profile. AS/NZS 3500.4 states a minimum of three (3) screws 40 mm long
be used per fixing strap. Longer screws or anchors may be required to
achieve a 40 mm minimum embedment into rafters for a metal roof.
Additional screws or anchors may be required.
10. Connector: Fit a connector (10) to the inlet of the solar collector array.
Refer to “Coupling Cold and Hot Pipes to Collector – Conetite Fittings” on
page 31.
22
Page 23
ROOF ASSEMBLY OF SOLAR COLLECTORS
11. Sensor Connector: Fit a sensor connector (4) (with hot sensor port) to the
outlet of the solar collector array.
Note: If the installation is on a tiled roof, the orientation of the hot sensor
port and hot sensor probe (when installed) must be angled between the
perpendicular (90°) to the roof to a maximum 30° off perpendicular down the
roof. Refer to Detail J on page 32.
Refer to “Coupling Cold and Hot Pipes to Collector – Conetite Fittings” on
page 31.
12. End Plug (Collector Bung): Fit the end plugs (5) (collector bung)
assemblies to the two remaining solar collector connections.
Refer to “End Plug (Collector Bung) Assembly – Conetite Fittings” on
page 29.
13. Solar Hot and Solar Cold Pipes: Install the solar cold pipe from the solar
storage tank to the solar collectors (17) and the solar hot pipe from the solar
collectors (17) to the solar storage tank.
The solar hot and solar cold pipes should be a minimum DN15, but sized to
suit the installation for an open circuit system. Refer to “Pipe Lengths” on
page 13.
The solar hot and solar cold pipes must have a continuous fall from the solar
collectors to the solar storage tank. Horizontal runs of pipe work are
acceptable and may be installed for an open circuit system.
The full length of the solar hot and solar cold pipes must be insulated. The
insulation must be capable of withstanding the temperatures generated by
the solar collectors under stagnation conditions.
Warning: Plumber – Be Aware: It is important you refer to “Warning:
Plumber – Be Aware” on page 14 for further and important information
relating to the installation of the solar hot and solar cold pipes.
Refer also to installation diagrams on pages 36, 37 and 38 and to “Pipe
Work Roughing In Dimensions” on page 33.
Notes:
Penetrations through the roofing material must be:
■ at the high point of the roof tile or metal sheet
■ made neatly and kept as small as practicable
■ waterproofed upon installation of the solar hot and solar cold
pipes.
Exposed insulated pipe work between the solar collectors and the
penetration through the roofing material should be kept to a minimum
to maintain the aesthetics of the installation.
23
Page 24
ROOF ASSEMBLY OF SOLAR COLLECTORS
14. Connecting the Solar Hot and Solar Cold Pipes to Collectors: Connect
the solar cold pipe to the connector (10) at the inlet of the solar
collectors (17) and the solar hot pipe to the sensor connector (4) at the outlet
of the solar collectors (17) using the compression nuts (11) and olives (12)
provided.
Refer to “Coupling Cold and Hot Pipes to Collector – Conetite Fittings” on
page 31 and the installation diagrams on pages 37 and 38.
15. Hot Sensor Lead – Collector Connection: Insert the sensor probe of the
hot sensor lead assembly (9) into the sensor connector (4), ensuring the
‘O’ ring is in position on the probe. Lock it into position with the locking
washer and clip provided.
Hot Sensor Lead – Solar Storage Tank Connection: Run the hot sensor
lead down to the solar storage tank. An extension sensor lead is available if
the hot sensor lead is not long enough to reach the solar storage tank.
Refer to the Owner’s Guide and Installation Instructions supplied with the
solar storage tank for the connection detail.
Tank with side solar connections and side mounted solar control unit:
Connect the hot sensor lead to the hot sensor cable connecting socket
located at the underside of the solar control unit screwed to the side of the
solar storage tank. If a short sensor lead adaptor is supplied taped to the
outside of the plastic bag containing the hot sensor lead assembly, it will be
necessary to use this to enable the mating of the connections. If the short
sensor lead adaptor is not required it can be discarded.
16. Cable Ties: Secure the hot sensor lead at appropriate locations with the
cable ties (14) provided.
Notes:
The hot sensor lead may be cable tied to the outside of the insulation
on the solar pipe work.
Ensure the hot sensor lead is not in direct contact with the solar pipe
work at any point of the collector circuit, otherwise damage to the
sensor lead can occur due to the high temperatures which can be
experienced within the pipe work.
Damage to the hot sensor lead can result in solar gain not being
achieved and the freeze protection system being rendered inoperative.
24
Page 25
ROOF ASSEMBLY OF SOLAR COLLECTORS
17. Labels: At ground or floor level, above the location of the solar storage tank,
attach the ‘Solar Cold Pipe’ label (16) to the insulation on the solar cold pipe
to the solar collectors and the ‘Solar Hot Pipe’ label (15) to the insulation on
the solar hot pipe from the solar collectors.
Ensure the arrows on the labels are pointing in the correct direction of closed
circuit fluid flow.
18. Pressure Testing the Collector Circuit: Upon completion of the solar
collector and solar hot and solar cold pipe installation, it may be required to
pressure test the collector circuit. Refer to “Pressure Testing” on page 17.
19. Connecting the Solar Hot and Solar Cold Pipes to the Solar Storage Tank:Refer to “Connections –Plumbing” in the Owner’s Guide and
Installation Instructions supplied with the solar storage tank for details on
the solar hot and solar cold pipe connections to the solar storage tank.
20. Commissioning: Upon completion of the installation, refer to the Owners
Guide and Installation instructions supplied with the solar storage tank for
the commissioning procedure of the solar water heater.
INSTALLATION CHECK LIST
Once the installation is complete, it is important to check the following:
Maximum recommended total combined solar hot and solar cold pipe length
is not exceeded.
Solar hot and solar cold pipes are insulated in accordance with the
installation instructions.
The solar hot and solar cold pipes have a continuous fall from the solar
collectors to the solar storage tank. Horizontal runs of pipe work are
acceptable.
Ensure the collector rail is either horizontal or is higher on the hot outlet side
of the solar collectors. If in doubt use a spirit level.
Or if the installation is on a tile roof with a flat profile tile, then the end of the
collector rail at the outlet side (left hand side) of the solar collectors is higher
up the roof than the end of the collector rail at the inlet side (right hand side)
of the solar collectors by:
15 – 20 mm for one solar collector, or
30 – 40 mm for two solar collectors, or
45 – 60 mm for three solar collectors.
25
Page 26
Recommended slots
Rafter spacing
One collector
(1 x one collector rail)
Two collectors
(1 x two collector rail)
300 mm (12”)
1 & 4 or 2 & 3
1 & 6 or 2 & 5
400 mm (16”)
1 & 3 or 2 & 4
1 & 5 or 2 & 6
450 mm (18”)
1 & 4
2 & 5
500 mm (20”)
1 & 4
1 & 6 or 2 & 5
600 mm (24”)
2 & 3
1 & 5 or 2 & 6
900 mm (36”)
1 & 4
2 & 5
Recommended slots – Three collectors
Rafter spacing
(1 x two and 1 x one collector rails)
300 mm (12”)
1 & 5 (long) & 9 (short)
400 mm (16”)
1 & 5 (long) & 9 (short)
450 mm (18”)
2 & 5 (long) & 10 (short)
500 mm (20”)
1 & 6 (long) & 10 (short)
600 mm (24”)
1 & 5 (long) & 9 (short)
900 mm (36”)
1 & 4 (long) & 10 (short)
1
2
3 4 5 6 7 8 9
101 2 3 4 5 6
1 2 3
4
CONNECTION DETAILS
HOOKING COLLECTOR STRAP TO COLLECTOR RAIL
Refer to installation diagrams on pages 36 to 38 for position and Detail A on
page 27 and Detail Bon page 27.
1. Determine which slots in the collector rail(s) (1) will be used for the collector
straps (2) after locating the rafters and taking note of the rafter spacing.
2. Note: The collector straps are to be fitted to the collector rail(s) before fixing
the straps to the rafters.
collector rail – one collector
collector rail – two collectors
collector rails – three collectors
26
Page 27
CONNECTION DETAILS
3. Noting the orientation of the collector strap’s folded end:
Bottom collector rail – slide the long straight end of the collector strap
through the appropriate slot from the underside of the collector rail (refer to
Detail A).
Top collector rail – slide the long straight end of the collector strap through
the appropriate slot from the top side of the collector rail (refer to Detail B).
Pull the collector strap through until the first bend in the strap slips into the
slot in the collector rail. The strap will engage with the collector rail.
COUPLING COLLECTOR TO COLLECTOR – CONETITE FITTING
Refer to installation diagrams on pages 37 and 38 for position and Detail C on
page 28.
1. Fit a collector union (3) to each collector connection of the first solar
collector (17) to receive the second solar collector and screw in the unions
until they seat firmly against the collector connection. Hand tighten only so
the solar collectors can be shifted and centred.
2. Place the collector unions (3) into the collector connections on the second
solar collector and screw in the unions until they seat firmly against the
collector connection. Hand tighten only so the solar collectors can be shifted
and centred.
3. Repeat steps 1 and 2 for a third solar collector (if installed).
4. After the solar collectors are centred on the collector rail(s), tighten each
collector union (3) with a spanner applying medium pressure.
DETAIL C – COLLECTOR UNION ASSEMBLY – CONETITE FITTING
28
Page 29
CONNECTION DETAILS
END PLUG (COLLECTOR BUNG) ASSEMBLY – CONETITE FITTING
Refer to installation diagrams on pages 36 to 38 for position and Detail D on
page 29.
1. Place the collector bung of the end plug (5) assembly into the collector
connection and screw in the gland nut until it seats firmly against the
collector connection, applying medium pressure with a spanner to tighten.
DETAIL D – END PLUG (COLLECTOR BUNG) ASSEMBLY
CONETITE FITTING
CLAMPING COLLECTOR TO COLLECTOR RAIL
Refer to installation diagrams on pages 36 to 38 for position and Detail E on
page 30 and Detail Fon page 30.
1. Centre the solar collectors on the collector rails (1).
2. Position the collector clamp (13) over the hole in the collector rail (1) with
the top lip of the clamp over the collector trim.
3. Insert the hex screw through the hole in the collector clamp and collector
rail (1), place the washer and nut on the screw and screw the nut until it
seats firmly against the lip of the collector rail, applying medium pressure
with a spanner to tighten.
29
Page 30
CONNECTION DETAILS
DETAIL E – CLAMPING COLLECTOR TO COLLECTOR RAIL – BOTTOM
DETAIL F – CLAMPING COLLECTOR TO COLLECTOR RAIL – TOP
30
Page 31
CONNECTION DETAILS
COUPLING COLD AND HOT PIPES TO COLLECTOR – CONETITE FITTING
Refer to installation diagrams on pages 36 to 38 for position and Detail G on
page 31, Detail H on page 32 and Detail Jon page 32.
1. Place the conetite connector of the connector (10) assembly into the solar
cold collector connection and screw in the gland nut until it seats firmly
against the collector connection, applying medium pressure with a spanner
to tighten.
2. Place the compression nut (11) and olive (12) over the end of the solar cold
pipe. Position the cold pipe into the connector (10) assembly, seat the
olive (12) and tighten the compression nut (11).
3. Repeat this procedure with the sensor connector (4) assembly to couple the
solar hot pipe to the solar collector (17).
Note: If the installation is on a tiled roof, the orientation of the hot sensor
port and hot sensor probe (when installed) must be angled between the
perpendicular (90°) to the roof to a maximum 30° off perpendicular down the
roof. Refer to Detail J on page 32.
DETAIL G – CONNECTOR ASSEMBLY – CONETITE FITTING
(SOLAR COLD CONNECTION TO SOLAR COLLECTOR)
31
Page 32
CONNECTION DETAILS
Tiled roof
30°
Down roof
Hot sensor & connector
assembly range is from
perpendicular to maximum
30° off perpendicular
"down" roof
Perpendicular
to roof
30°
DETAIL H – SENSOR CONNECTOR ASSEMBLY – CONETITE FITTING
Refer to the diagrams for roughing in dimensions for pipe work to the solar
collectors and to the solar storage tank.
remote boost integrated boost
Note: * the roughing in dimensions for B and C are 200 mm above fitting to allow room
for bends and valve installation.
Integrated Gas Boost and Remote Boost
Solar Storage Tanks 160 Litre (Open Circuit)
33
Page 34
PIPE WORK ROUGHING IN DIMENSIONS
A B C D
Pipe Work to
Solar Storage Tank
Capacity
(litres)
Hot Outlet
Solar Hot
Flow *
Solar Cold
Return *
Cold Inlet
270 tank
270
1190
685
635
73
320, 325 tanks
325
1430
754
635
73
410 tank
410
1600
820
643
81
Note: * the roughing in dimensions for B and C are 200 mm above fitting to allow room for
bends and valve installation.
Electric Boost
Solar Storage Tanks (Open Circuit)
34
Page 35
PIPE WORK ROUGHING IN DIMENSIONS
Pipe Work to Solar Collectors
E
F
1 Collector
1200
1875
2 Collectors
2260
1875
3 Collectors
3320
1875
Solar Pipe Work Roughing In Dimensions
35
Page 36
Solar Cold Pipe
(to collectors)
Solar Hot Pipe
(from collectors)
(apply to solar hot pipe
at storage tank level)
(apply to solar cold pipe
at storage tank level)
2000
5
17
14
1
2
13
1
16
13
2
5
11
12
9
4
13
11
12
10
15
1220
Insulated solar cold
pipe from storage tank.
Insulated solar hot
pipe to storage tank
EXPLODED VIEWS – SOLAR COLLECTORS
Note: Although the drawings illustrate the solar cold pipe connecting the bottom
left hand corner of the solar collector array, the solar cold pipe may be connected
to either the bottom right or the bottom left hand corner. The solar hot pipe must
connect to the top of the solar collector array diagonally opposite to the solar cold
pipe connection.
INSTALLATION ONE COLLECTOR WITH CONETITE FITTINGS
SUPPLIED IN ONE COLLECTOR KIT (CONETITE FITTINGS) (12104793)
1. Collector rail
2. Collector strap
4. Sensor connector
5. End plug (collector bung)
assembly
9. Hot sensor lead assembly
10. Connector
11. Compression nut
12. Compression olive
13. Clamp, hex screw, washer, nut
14. Cable tie
15. Label – solar hot pipe
16. Label – solar cold pipe
(Supplied separately)
17. Solar collector
36
Page 37
EXPLODED VIEWS – SOLAR COLLECTORS
Solar Cold Pipe
(to collectors)
Solar Hot Pipe
(from collectors)
(apply to solar hot pipe
at storage tank level)
(apply to solar cold pipe
at storage tank level)
2280
2000
5
3
3
17
1
13
2
2
13
1
14
13
5
15
16
11
12
4
9
Insulated solar hot
pipe to storage tank
Insulated solar cold
pipe from storage tank
10
12
11
INSTALLATION TWO COLLECTORS WITH CONETITE FITTINGS
SUPPLIED IN TWO COLLECTOR KIT (CONETITE FITTINGS) (12104794)
1. Collector rail
2. Collector strap
3. Collector union
(connector assembly)
4. Sensor connector
5. End plug (collector bung)
assembly
9. Hot sensor lead assembly
10. Connector
12. Compression olive
13. Clamp, hex screw, washer, nut
14. Cable tie
15. Label – solar hot pipe
16. Label – solar cold pipe
(Supplied separately)
17. Solar collector
11. Compression nut
37
Page 38
EXPLODED VIEWS – SOLAR COLLECTORS
SK7115-6 REV BD3/13
13
cable tie
SUPPLIED IN COLLECTOR
ADDON KIT
(1ADDITIONAL COLLECTOR)
1. Collectorrail
2. Collectorstrap
3. Collectorunion
8. Driver cleat
13. Clamp, hex screw, washer,nut
SUPPLIED SEPARATELY
17. Solar Collector
SOLAR DIRECT COLLECTOR INSTALLATION - ADDITIONAL COLLECTOR (EXPLODED VIEW)
WITH UNCOATED BRASS CONETITE FITTING SOLAR COLLECTORS.
2000
3340 (3 COLLECTORS)
8
17
3
3
13
1
2
13
8
2
Solar Hot Pipe
(from collectors)
Solar Cold Pipe
(to collectors)
(apply to solar hot pipe
at storage tankd level)
(apply to solar hot pipe
at storage tank level)
Insulated solar cold pipe
from storage tank
Insulated solar hot pipe
to storage tank
INSTALLATION – ADDITIONAL SOLAR COLLECTOR – CONETITE FITTINGS
SUPPLIED IN COLLECTOR ADD ON KIT (CONETITE FITTINGS) (12104795)
The solar water heater and its components are covered by a manufacturer’s
warranty. For full details, refer to the Owners Guide and Installation Instructions
supplied with the solar storage tank.
The part extracts from the “Terms Of TheWarranty And The Exclusions To It” of
the water heater Warranty should be noted before commencing the installation
of the solar collectors.
TERMS OF THE WARRANTY AND EXCLUSIONS TO IT
2.5 Where the water heater is installed in a position that does not allow safe or ready access,
the cost of that access, including the cost of additional materials handling and/or safety
equipment, shall be the owner’s responsibility. In other words, the cost of dismantling or
removing cupboards, doors or walls and the cost of any special equipment to bring the water
heater to floor or ground level or to a serviceable position is not covered by this warranty.
2.7 The warranty does not cover faults that are a result of:
c) Installation not in accordance with the Owner’s Guide and Installation Instructions or with
relevant statutory and local requirements in the State or Territory in which the water
heater is installed.
d) Connection at any time to a water supply that does not comply with the water supply
guidelines as outlined in the Owner’s Guide and Installation Instructions.
k) Breakage of collector glass for any reason including hail damage (we suggest that the
collector glass be covered by the home insurance policy).
l) Ice formation in the waterways of a water heater system incorporating a freeze protection
system where the electricity supply has been switched off or has failed or where it is
installed at an altitude more than 400 metres above sea level.
2.8 Subject to any statutory provisions to the contrary, this warranty excludes any and all claims
for damage to furniture, carpet, walls, foundations or any other consequential loss either
directly or indirectly due to leakage from the water heater, or due to leakage from fittings and/
or pipe work of metal, plastic or other materials caused by water temperature, workmanship
or other modes of failure.
39
Page 40
Revision Date: 2016 August 347229E
RHEEM AUSTRALIA PTY LTD - ABN 21 098 823 511
SOLAHART INDUSTRIES PTY LTD - ABN 45 064 945 848
1 Alan Street Rydalmere NSW 2116 Australia
(PO Box 7508 Silverwater NSW 2128 Australia)
PATENTS
This water heater may be protected by one or more patents or registered designs
in the name of Rheem Australia Pty Ltd or Solahart Industries Pty Ltd.
®
Registered trademark of Rheem Australia Pty Ltd or Solahart Industries Pty Ltd.
TM
Trademark of Rheem Australia Pty Ltd or Solahart Industries Pty Ltd.
TRADEMARKS
Note: Every care has been taken to ensure the accuracy in preparation of this
publication. No liability can be accepted for any consequences,
which may arise as a result of its application.
40
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.