Rheem 130, 000 BTU, 100 User Manual

Adv anta gePlus Sealed-Combustion Gas-Fired Commercial Water Heaters
Available in Sizes Ranging From 45 - 119 Gallon Models
100,000 BTU/Hr.thru 199,000 BTU/Hr.
Rheem-Ruud AdvantagePlus
TM
Gas Commercial Water Heaters are specifically designed to provide customers with maximum savings on operation, space and installation. Designed with the most advanced technology available, these products optimize efficiency and operating reliability.
Construction Features:
316L stainless steel tank
construction (requires no anode rods).
No chimney required; direct
vent using plastic pipe.
Ther mal efficiency of 95%
dramatically reduces operating costs.
85 equivalent feet of vent length.
Low NOx emissions. Meets
SCAQMD Rule 1146.2.
High impact plastic jacket
eliminates dents.
2” of non-CFC, polyurethane
foam insulation.
Less than 1/2 degree per
hour heat loss (R17).
Corrosion resistant, high
efficiency 90/10 cupronickel heat exchanger.
Self-diagnostic electronic
control with digital readout for water temperature, set point and differential.
Removable front cover allows
easy access to equipment (24" service clearance recommended).
Temperature range from 70°F to 160°F (maximum temperature setting of 180°F available on HE45-160 and HE45-199 booster models only).
Zero clearance to all combustible surfaces.
Factory installed AGA/ASME rated T&P relief valve.
Booster installation kit provided with HE45-160 and HE45-199 booster models.
No Chimney Required
Vents Up To 40 Feet
Using 3" Schedule 40
PVC, CPVC or ABS Pipe
100,000 BTU and
130,000 BTU Models
Are Certified To
Vent With 2"
Schedule 40 PVC,
CPVC or ABS Pipe
Certifications and Ratings:
The water heaters are UL/ULC listed and meet or exceed thermal efficiency and standby loss requirements of current ASHRAE standards.All water heaters are supplied with an AGA/ASME rated temperature and pressure relief valve.The control panel is an integrated solid state temperature and igni­tion control device with integral diagnostics, LED fault display capability and a digital display of temperature settings.All models are North Carolina Code compliant. Meet all safety and construction requirements of ANSI Z21.10.3.
CERTIFIED FOR A 150 PSI MAXIMUM WORKING PRESSURE.
®
Continued next page.
Heat Exchanger/ Combustion Chamber
Control Well and E.C.O. Air Inlet Connector Gas Valve Combustion Blower Gas Burner Gas Inlet Nipple 1/2 Hot Surface Ignitor Flame Probe Exhaust Outlet Connector Control Board Vent Over-Temp
Reset Switch Exhaust Elbow and Drain Pressure Switch Transformer Condensate Connector
Hose Condensate Connector
DIMENSIONAL INFORMATION
All dimensions shown in English and Metric
MODEL
WATER CONNECTIONS APPROX
NUMBER UNITS
ABCDEFGH
VENT
INLET OUTLET
SHIPPING WT.
inches 42 23 1/2 32 35 5 25 1/4 27 9/16 5 7/8 2 1 1 175 lbs.
mm 1067 597 813 889 127 641 700 149 51 25 25 79 kgs
inches 42 23 1/2 32 35 5 25 1/4 27 9/16 5 7/8 3 1 1 175 lbs.
mm 1067 597 813 889 127 641 700 149 76 25 25 79 kgs
inches 72 23 1/2 32 65 5 25 1/4 20 1/4 7 3/4 3* 1-1/2 1-1/2 235 lbs.
mm 1854 597 813 1651 127 641 514 197 76 38 38 106 kgs
inches 73 27 36 66 3/4 6 3/4 28 7/8 22 9 1/2 3* 1-1/2 1-1/2 405 lbs.
mm 1854 686 914 1695 171 733 559 241 76 38 38 184 kgs
* 130,000 BTU models are certified to be installed with 2" venting. All models require a 120V power source. See use and care manual for venting details.
HE45-100 HE45-130
HE45-160 HE45-199
HE80-130 HE80-160 HE80-199
HE119-130 HE119-160 HE119-199
0" CLEARANCE TO COMBUSTIBLES ON ALL ADVANTAGE PLUS UNITS, HOWEVER, A 24" CONTROL PANEL SERVICE CLEARANCE IS RECOMMENDED.
MODELS WITH INPUTS OF 100,000 BTU AND 130,000 BTU ARE CERTIFIED TO VENT WITH 2" SCHEDULE 40 PVC, CPVC OR ABS PIPE
HE45-100 HE45-130
HE80-130 HE119-130
HE80-160 HE119-160
HE80-199 HE119-199
HE45-160
HE45-199
MAXIMUM DELIVERY
In U.S. Gallons and Liters
(Includes useable storage and recovery for indicated times)
MODEL INPUT (BTU/HR) TEMP. 5 10 15 20 30 45 1 2 3 MIN.TO RECOVER NUMBER
GALLONS LITERS NAT.& LP
RISE UNITS MIN. MIN. MIN. MIN. MIN. MIN. HR. HR. HR. CONTENTS
HE45-100 45 170 100,000
100°F GAL. 41 51 60 70 89 118 147 262 377
23
37.7°C LTR. 156 192 228 265 337 446 555 991 1427
HE45-130 45 170 130,000
100°F GAL. 44 56 69 81 106 144 181 331 481
18
37.7°C LTR. 166 214 261 308 403 544 686 1253 1819
HE80-130 80 303 130,000
100°F GAL. 68 81 93 106 131 168 206 355 505
32
37.7°C LTR. 259 306 354 401 495 637 779 1345 1912
HE119-130 119 450 130,000
100°F GAL. 96 108 121 133 158 196 233 383 532
48
37.7°C LTR. 363 410 457 504 599 750 882 1449 2015
HE45-160 45 170 160,000
100°F GAL. 47 62 78 93 124 170 216 400 584
15
37.7°C LTR. 177 235 294 352 468 642 817 1514 2211
HE80-160 80 303 160,000
100°F GAL. 71 87 102 117 148 194 240 424 609
26
37.7°C LTR. 270 328 386 444 561 735 909 1607 2304
HE119-160 119 450 160,000
100°F GAL. 99 114 129 145 175 221 268 452 636
39
37.7°C LTR. 373 432 490 548 664 838 1013 1710 2408
HE45-199 45 170 199,000
100°F GAL. 51 70 89 108 146 203 261 490 719
12
37.7°C LTR. 192 264 336 408 553 770 987 1854 2721
HE80-199 80 303 199,000
100°F GAL. 75 94 113 132 171 228 285 514 743
21
37.7°C LTR. 284 357 429 501 646 863 1079 1947 2814
HE119-199 119 450 199,000
100°F GAL. 102 121 141 160 198 255 312 542 771
31
37.7°C LTR. 338 460 532 604 749 966 1183 2050 2918
All models have a maximum setpoint of 160°F with the exception of the HE45-160 and HE45-199 booster models. The HE45-160 and HE45-199 have a maximum setpoint of 180°F.
RECOVERY CAPACITIES
Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises
MODEL INPUT (BTU/HR) THERMAL
40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
NUMBER NAT. & LP EFFICIENCY UNITS
(22°C) (28°C) (33°C) (39°C) (45°C) (50°C) (56°C) (61°C) (67°C) (72°C) (78°C)
100,000 95%
GPH 288 230 192 165 144 128 115 105 96 N/A N/A
LPH 1090 872 726 623 545 484 436 396 363 N/A N/A
130,000 95%
GPH 374 299 249 214 187 166 150 136 125 N/A N/A
LPH 1417 1133 944 809 708 630 567 515 472 N/A N/A
160,000 95%
GPH 461 368 307 263 230 205 184 167 154 N/A N/A
LPH 1744 1395 1162 996 872 775 697 634 581 N/A N/A
199,000 95%
GPH 573 458 382 327 286 255 229 208 191 N/A N/A
LPH 2169 1735 1446 1239 1084 964 867 789 723 N/A N/A
BOOSTER MODELS
160,000 95%
GPH 461 368 307 263 230 205 184 167 154 142 132
LPH 1744 1395 1162 996 872 775 697 634 581 536 498
199,000 95%
GPH 573 458 382 327 286 255 229 208 191 176 164
LPH 2169 1735 1446 1239 1084 964 867 789 723 667 620
Recovery rating is based on thermal efficiencies obtained in an UL certified laboratory.