Rheem 031JAZ, 036CAZ, 036DAZ, 036JAZ, 037CAZ Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
ANT SAFETY INFORMA
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLAT I ON, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE AT TEMPTING INSTALLATION OR OPERATION. FA ILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLAT I ON, ADJUSTMENT,SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
efrigerant
ISO 9001:2000
AIR-COOLED CONDENSING UNITS
(-)ANL-*AZ MODEL SERIES – 13 SEER (-)APL-JAZ MODEL SERIES – 14 SEER (-)APM-JAZ MODEL SERIES – 14.5 SEER
[ ] INDICATES METRIC CONVERSIONS
(14.5 SEER MODELS
& 14 OR 13 SEER MODELS IN CERTAIN MARKED SYSTEMS)
SUPERSEDES 92-21354-51-07
92-21354-51-08
TABLE OF CONTENTS
Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Electrical & Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Corrosive Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Locating Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Factory-Preferred Tie-Down Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Refrigerant Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Tools Required for Installing & Servicing R-410A Models . . . . . . . . . . . . . . .8
Specification of R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Quick Reference for R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Replacement Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Interconnecting Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-13
Evacuation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Start-Up and Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Checking Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Checking Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
High and Low Pressure Controls (HPC or LPC) . . . . . . . . . . . . . . . . . . . . .18
Field Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-22
Trouble Shooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-26
CHECKING PRODUCT RECEIVED
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. Check condensing unit model number, electrical characteristics and accessories to determine if they are correct. Check system components (evaporator coil, condens­ing unit, evaporator blower, etc.) to make sure they are properly matched.
2
FIGURE 1
A-00002
BOTTOM VIEW SHOWING DRAIN OPENINGS (\\\\\ SHADED AREAS).
A
-
0
0
0
0
1
ALLOW 24” [610 mm] SERVICE ACCESS C
LEARANCE
AIR INLETS (LOUVERS)
M
IN. CLEARANCE
3
SIDES
ACCESS PANEL
A
IR DISCHARGE
A
LLOW 60” [1524 mm] CLEARANCE
ALLOW 6” [153 mm]
A
-
00003
DIMENSIONS AND INSTALLATION CLEARANCES
UNIT MODEL NUMBER EXPLANATION
(-) ANL
– 024 JAZ
TU/HR x 1000 (COOLING CAPACITY)
B 018 = 18,000 BTU/HR
024 = 24,000 BTU/HR 030/031 = 30,000 BTU/HR 036/037 = 36,000 BTU/HR 042/043 = 42,000 BTU/HR 048/049 = 48,000 BTU/HR 060 = 60,000 BTU/HR
N = STANDARD EFFICIENCY P = HIGH EFFICIENCY
REMOTE CONDENSING UNIT
RADE NAME
T
COOLING CONNECTION FITTING
- SCROLL COMPRESSOR
Z
VARIATIONS
- Series = FULL FEATURED
A
LECTRICAL DESIGNATION
E J = 208/230V-1-60
= 208/230V-3-60
C D = 460V-3-60
= 575V-3-60
Y
DESIGN SERIES L=R-410A
M=R410 2NDDESIGN SERIES
Available only on
[
-)ANL- Models]
(
}
DIMENSIONAL DATA
CONDENSING UNIT MODEL
CONDENSING UNIT MODEL
CONDENSING UNIT MODEL
(-)ANL
LENGTH “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH “W” (INCHES)
(-)APL
LENGTH “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH “W” (INCHES)
(-)APM
LENGTH “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH “W” (INCHES)
018
024/031 030 036/042 049 043/037 048/060
19" 19" 19" 25" 29" 23" 33" 351⁄2" 401⁄2" 443⁄8" 443⁄8" 443⁄8" 443⁄8" 443⁄8" 243⁄4"
27
018JAZ/024JAZ
5
8"
1
31
2" 311⁄2" 311⁄2" 311⁄2" 311⁄2"
030JAZ
036JAZ/042JAZ 048JAZ/060JAZ
19" 29" 33"
401⁄2" 443⁄8" 443⁄8"
1
31
2" 311⁄2"
024JAZ 030JAZ
036JAZ/042JAZ 048JAZ/060JAZ
275⁄8"
018JAZ
19" 29" 33"
401⁄2" 443⁄8" 443⁄8"
1
2" 311⁄2"
31
27
5
8"
3
TABLE 1
(-)ANL ELECTRICAL AND PHYSICAL DATA
PHYSICALELECTRICAL
Model
Number
(-)ANL-
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated
Load
Amperes
(RLA)
Locked
Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
018JAZ 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 9.07 [0.84] 1 1775 [838] 70 [1984] 130 [59] 140 [63.5] 024JAZ 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 11 [1.02] 1 1920 [906] 72 [2041] 140 [63.5] 150 [68] 030JAZ 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 12.94 [1.2] 1 2470 [1166] 94 [2665] 160 [72.6] 170 [77.1]
031JAZ 1-60-208/230 14.1/14.1 73 0.6 19/19 25/25 30/30 11.1 [1.02] 1 1920 [906] 83 [2353] 142 [54] 152 [70] 036CAZ 3-60-208-230 13.2/13.2 88 0.8 18/18 25/25 30/30 17.26 [1.6] 1 2570 [1213] 113 [3204] 205 [93] 215 [97.5] 036DAZ 3-60-460 6.0 44 0.4 8 15 15 17.26 [1.6] 1 2570 [1213] 113 [3204] 205 [93] 215 [97.5] 036JAZ 1-60-208/230 17.9/17.9 112 0.8 24/24 30/30 40/40 17.26 [1.6] 1 2570 [1213] 113 [3204] 205 [93] 215 [97.5] 037CAZ 3-60-208-230 13.2/13.2 88 1.2 18/18 25/25 30/30 16.1 [1.5] 1 2300 [1085] 106 [3005] 160 [72] 170 [77] 037DAZ 3-60-460 6.0 44 0.6 9 15 15 16.1 [1.5] 1 2300 [1085] 106 [3005] 160 [72] 170 [77] 037JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 16.1 [1.5] 1 2300 [1085] 106 [3005] 160 [72] 170 [77] 042CAZ 3-60-208-230 13.5/13.5 88 1.2 19/19 25/25 30/30 17.26 [1.6] 1 3290 [1553] 130 [3686] 205 [93] 215 [97.5] 042DAZ 3-60-460 6.0 44 0.6 9 15 15 17.26 [1.6] 1 3290 [1553] 130 [3686] 205 [93] 215 [97.5] 042JAZ 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 17.26 [1.6] 1 3290 [1553] 130 [3686] 205 [93] 215 [97.5] 043CAZ 3-60-208-230 13.5/13.5 83.1 1.2 19/19 25/25 30/30 17.26 [1.6] 1 3200 [1510] 115 [3260] 205 [93] 215 [97] 043DAZ 3-60-460 6.0 44 0.6 9 15 15 17.26 [1.6] 1 3200 [1510] 115 [3260] 205 [93] 215 [97] 043JAZ 1-60-208/230 19.9/19.9 109 1.2 27/27 35/35 45/45 17.26 [1.6] 1 3200 [1510] 115 [3260] 205 [93] 215 [97] 048CAZ 3-60-208-230 13.7/13.7 83.1 1.2 19/19 25/25 30/30 23.01 [2.14] 1 3500 [1652] 145 [4111] 230 [104.3] 240 [108.9] 048DAZ 3-60-460 6.2 41 0.6 9 15 15 23.01 [2.14] 1 3500 [1652] 145 [4111] 230 [104.3] 240 [108.9] 048JAZ 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3500 [1652] 145 [4111] 230 [104.3] 240 [108.9] 048YAZ 3-60-575 4.8 33 0.5 7 15 15 23.01 [2.14] 1 3500 [1652] 145 [4111] 230 [104.3] 240 [108.9] 049CAZ 3-60-208-230 13.7/13.7 83.1 1.2 19/19 25/25 30/30 20.1 [1.8] 1 3200 [1510] 132 [3742] 235 [106] 245 [111] 049DAZ 3-60-460 6.2 41 0.6 9 15 15 20.1 [1.8] 1 3200 [1510] 132 [3742] 235 [106] 245 [111] 049JAZ 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 20.1 [1.8] 1 3200 [1510] 132 [3742] 235 [106] 245 [111] 049YAZ 3-60-575 4.8 33 0.5 7 15 15 20.1 [1.8] 1 3200 [1510] 132 [3742] 235 [106] 245 [111] 060CAZ 3-60-208-230 15.6/15.6 110 1.2 21/21 25/25 35/35 23.01 [2.14] 1 3500 [1652] 180 [5103] 250 [113.4] 260 [117.9] 060DAZ 3-60-460 7.8 52 0.6 11 15 15 23.01 [2.14] 1 3500 [1652] 180 [5103] 250 [113.4] 260 [117.9] 060JAZ 1-60-208/230 26.3/26.3 134 1.2 35/35 45/45 60/60 23.01 [2.14] 1 3500 [1652] 180 [5103] 250 [113.4] 260 [117.9] 060YAZ 3-60-575 5.8 38.9 0.5 8 15 15 23.01 [2.14] 1 3500 [1652] 180 [5103] 250 [113.4] 260 [117.9]
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m2]
Outdoor Coil Weight
Refrig.
Per
No.
Rows
CFM [L/s]
Circuit Oz. [g]
Net
Lbs. [kg]
Shipping Lbs. [kg]
TABLE 2
(-)APL ELECTRICAL AND PHYSICAL DATA
ELECTRICAL
Model
Number
(-)APL-
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
{RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
Outdoor Coil Weight
No.
2
]
Rows
018J*Z 1-60-208/230 9/9 48 0.8 13/13 15/15 20/20 11 [1.02] 1 1900 [897] 79 [2240] 140 [63.5] 155 [70.3] 024J*Z 1-60-208/230 13.5/13.5 58.3 0.8 18/18 25/25 30/30 11 [1.02] 1 2300 [1085] 105 [2977] 140 [63.5] 187 [84.8] 030J*Z 1-60-208/230 12.8/12.8 64 1.2 18/18 25/25 30/30 20 [1.86] 1 3200 [1510] 135 [3827] 200 [90.7] 213 [96.6] 036J*Z 1-60-208/230 16.7/16.7 79 1.2 23/23 30/30 35/35 23.01 [2.14] 1 3200 [1510] 141 [3997] 230 [104.3] 228 [103.4] 042J*Z 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 23.01 [2.14] 1 3200 [1510] 152 [4309] 230 [104.3] 252 [114.3] 048J*Z 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 23.01 [2.14] 1 3300 [1557] 152 [4309] 230 [104.3] 253 [114.8] 060J*Z 1-60-208/230 26.4/26.4 134 1.2 35/35 45/45 60/60 44 [4.09] 2 3100 [1463] 286 [8108] 280 [127] 305 [138.3]
CFM [L/s]
PHYSICAL
Refrig.
Per
Circuit
Oz. [g]
Net
Lbs. [kg]
Shipping Lbs. [kg]
4
TABLE 3
-)APM ELECTRICAL AND PHYSICAL DATA
(
ELECTRICAL
Model Number (-)APM-
018JAZ 1-60-208/230 9/9 48 0.8 13/13 15/15 20/20 11 [1.02] 1 2300 [1085] 82 [2325] 137[62.1] 152 [68.9] 024JAZ 1-60-208/230 13.5/13.5 58.3 1.1 18/18 25/25 30/30 20 [1.86] 1 3300 [1557] 128 [3629] 190 [86.2] 205 [93] 030JAZ 1-60-208/230 12.8/12.8 64 0.8 17/17 25/25 25/25 20 [1.86] 1 3300 [1557] 129 [3657] 200 [90.7] 213 [96.6] 036JAZ 1-60-208/230 16/16 79 0.8 21/21 25/25 35/35 23.01 [2.14] 1 3300 [1557] 146 [4139] 201 [91.2] 223 [101.2] 042JAZ 1-60-208/230 17.9/17.9 112 2.8 26/26 30/30 40/40 23.01 [2.14] 1 3300 [1557] 152 [4309] 224 [101.6] 246 [111.6] 048JAZ 1-60-208/230 21.8/21.8 117 2.8 31/31 40/40 50/50 23.01 [2.14] 2 3300 [1557] 203 [5755] 265 [120.2] 290 [131.5] 060JAZ 1-60-208/230 26.4/26.4 134 2.8 36/36 45/45 60/60 23 [2.14] 2 3300 [1557] 262 [7428] 274 [124.3] 299 [135.6]
Phase Frequency (Hz) Voltage (Volts)
Compressor
Rated Load
Amperes
{RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
Outdoor Coil Weight
No.
2
]
Rows
CFM
[L/s]
PHYSICAL
Refrig.
Per Circuit Oz. [g]
Net
Lbs. [kg]
Shipping Lbs. [kg]
WARNING
!
THE MANUFACTURER’S WARRAN­TY DOES NOT COVER ANY DAM­AGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS. ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFAC­TURER) INTO, ONTO OR IN CON­JUNCTION WITH THE AIR CONDI­TIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CON­DITIONER AND MAY ALSO ENDAN­GER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
GENERAL
The information contained in this manual has been prepared to assist in the proper installation, operation and maintenance of the air conditioning system. Improper installation, or installation not made in accordance with these instructions, can result in unsatisfactory operation and/or dangerous conditions, and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the con­densing unit specification sheet should be used.
APPLICATION
Before installing any air conditioning equipment, a duct analysis of the structure and a heat gain calculation must be made. A heat gain calculation begins by measuring all external surfaces and openings that gain heat from the surrounding air and quantifying that heat gain. A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal.
There are several factors that the installers must consider:
• Outdoor unit location • Proper equipment evacuation
• System refrigerant charge • Indoor unit airflow
• Indoor unit blower speed • Supply and return air duct design and sizing
• System air balancing • Diffuser and return air grille location and sizing
CORROSIVE ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment. This oxidation could shorten the equipment’s useful life. Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical conta­minants from industries such as paper mills and petroleum refineries.
If the unit is to be installed in an area where contaminants are likely to be a prob­lem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet.
In coastal areas, locate the unit on the side of the building away from the water­front.
Shielding provided by a fence or shrubs may give some protection, but cannot violate minimum airflow and service access clearances.
Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan.
Regular maintenance will reduce the build-up of contaminants and help to protect the unit’s finish.
5
WARNING
!
DISCONNECT ALL POWER TO UNIT BEFORE STARTING MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH.
Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
Regular cleaning and waxing of the cabinet with an automobile polish will pro­vide some protection.
A liquid cleaner may be used several times a year to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
LOCATING UNIT
CONDENSER LOCATION
Consult local and national building codes and ordinances for special installation requirements. Following location information will provide longer life and simplified servicing of the outdoor condenser.
NOTE: These units must be installed outdoors. No ductwork can be attached, or other modifications made, to the discharge grille. Modifications will affect perform­ance or operation.
OPERATIONAL ISSUES
IMPORTANT: Locate the condenser in a manner that will not prevent, impair or compromise the performance of other equipment horizontally installed in prox­imity to the unit. Maintain all required minimum distances to gas and electric meters, dryer vents, exhaust and inlet openings. In the absence of National Codes, or manaufacturers’ recommendations, local code recommendations and requirements will take presidence.
Refrigerant piping and wiring should be properly sized and kept as short as pos­sible to avoid capacity losses and increased operating costs.
Locate the condenser where water run off will not create a problem with the equipment. Position the unit away from the drip edge of the roof whenever pos­sible. Units are weatherized, but can be affected by the following:
o Water pouring into the unit from the junction of rooflines, without protective
guttering. Large volumes of water entering the condenser while in operation can impact fan blade or motor life, and coil damage may occur to a heat pump if moisture cannot drain from the unit under freezing conditions.
Closely follow clearance recommendations on Page 3. o 24” to the service panel access
o 60” above condenser fan discharge (unit top) to prevent recirculation
o 6” to condenser coil grille air inlets (per condenser).
FOR CONDENSERS WITH SPACE LIMITATIONS
In the event that a space limitation exists, we will permit the following clearances:
Single Unit Applications: Clearances below 6 inches will reduce unit capacity and efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.
Multiple Unit Applications: When multiple condenser grille sides are aligned, a 6­inch per unit clearance is recommended, for a total of 12" between two units. Two combined clearances below 12 inches will reduce capacity and efficiency. Do not reduce the 60-inch discharge, or 24-inch service, clearances.
Do not obstruct the bottom drain opening in the condenser base pan. It is essential to provide defrost condensate drainage to prevent possible refreezing of the condensation. Provide a base pad for mounting the unit, which is slightly pitched away from the structure. Route condensate off the base pad to an area which will not become slippery and result in personal injury.
6
STEP 4: Drill four pilot holes in pad, ensuring that the hole is at least 1/4” deeper
than the concrete screw being used.
STEP 5: Center basepan over pre-drilled holes and insert concrete screws.
STEP 6: Tighten concrete screws.
NOTE: Do not over-tighten the concrete screws. Doing so can weaken the integrity of the concrete screw and cause it to break.
STEP 7: Finish unit assembly per unit’s installation instructions.
UNIT MOUNTING
If elevating the condensing unit, either on a flat roof or on a slab, observe the following guidelines.
The base pan provided elevates the condenser coil 3/4” above the base pad.
If elevating a unit on a flat roof, use 4” x 4” (or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration.
NOTE: Do not block drain openings shown in Figure 1.
FACTORY-PREFERRED TIE-DOWN METHOD
FOR CONDENSING UNITS
IMPORTANT: These instructions are intended as a guide to securing equipment for wind-load ratings of “120 MPH sustained wind load” and “3-second, 150 MPH gust.” While this procedure is not mandatory, the Manufacturer does recommend that equipment be properly secured in areas where high wind damage may occur.
STEP 1: Before installing, clear pad of any dirt or debris.
IMPORTANT: The pad must be constructed of industry-approved materials, and must be thick enough to accommodate the concrete fastener.
STEP 2: Center base pan on pad, ensuring it is level.
STEP 3: Using basepad as a guide, mark spots on concrete where 4 holes will be
drilled (see Figure 2).
CUSTOMER SATISFACTION ISSUES
The condenser should be located away from the living, sleeping and recation­al spaces of the owner and those spaces on adjoining property.
To prevent noise transmissionm, the mounting pad for the outdoor unit should not be connected to the structure, and should be located sufficient distance above grade to prevent ground water from enteriing the unit.
PROPER INSTALLATION
roper sizing and installation of equipment is critical to achieve optimal perform-
P ance. Use the information in this Installation Instruction Manual and reference the applicable Engineering Specification Sheet when installing this product.
IMPORTANT: This product has been designed and manufactured to meet ENERGY
®
STAR nents. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufac­turer’s refrigerant charging and air flow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
criteria for energy efficiency when matched with appropriate coil compo-
TABLE 4
DIMENSIONS
MODEL NUMBER LWAB CD
(-)ANL-018/024/030, (-)APL-018/024, (-)ANL-031, (-)APM-018 375⁄8" 2515⁄16" 15" 34" 31⁄2" 221⁄2"
(-)ANL-037/043/049, (-)ANL-036/042/048/060, (-)APL-030/036/042/048/060, (-)APM-024/030/036/042/048/060 411⁄2" 2913⁄16" 15" 38" 31⁄2" 261⁄2"
7
REFRIGERANT CONNECTIONS
All units are factory charged with Refrigerant 410A. All models are supplied with service valves. Keep tube ends sealed until connection is to be made to prevent system contamination.
TOOLS REQUIRED FOR INSTALLING & SERVICING R-410A MODELS
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
SPECIFICATION OF R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must accommodate its higher pressures. It cannot be retrofitted into R-22 condens­ing units.
FIGURE 2
S
CREW LOCATIONS
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
8
Physical Properties: R-410A has an atmospheric boiling point of -62.9°F and its saturation pressure at 77°F is 224.5 psig.
Composition: R-410A is an azeotropic mixture of 50% by weight difluoromethane (HFC-32) and 50% by weight pentafluoroethane (HFC-125).
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R-22. Recovery and recycle equipment, pumps, hoses and the like need to
h
ave design pressure ratings appropriate for R-410A. Manifold sets need to range
up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can b
ecome combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be per-
formed safely with nitrogen or a mixture of R-410A and nitrogen.
QUICK REFERENCE GUIDE FOR R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times)
than R-22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in color.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999,
R-410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for equipment charging. Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit. Only manufacturer approved liq-
uid line filter driers can be used. These are Sporlan (CW083S) and Alco (80K083S) driers. These filter driers are rated for minimum working pressure of 600 psig.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
REPLACEMENT UNITS
To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized. Test the oil for acid. If positive, a suction line filter drier is mandatory.
IMPORTANT: WHEN REPLACING AN R-22 UNIT WITH AN R-410A UNIT, EITHER REPLACE THE LINE SET OR ENSURE THAT THE EXISTING LINE SET IS THOROUGHLY CLEANED OF ANY OLD OIL OR DEBRIS.
EVAPORATOR COIL
REFER TO EVAPORATOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not responsible for the performance and opera-
tion of a mismatched system, or for a match listed with another manufacturer’s coil.
!
CAUTION
Only use evaporators approved for use on R-410A systems. Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant forming two differ­ent liquids and decreasing oil return to the compressor. This can result in com­pressor failure.
9
Loading...
+ 19 hidden pages