Reznor Door Air Heater Option User Manual

OPTION BX1,
OVERHEAD DOOR
SWITCH
®
Applies to: "Door Air Heater" Application
Installation Form RZ-NA-I-OPT -DS
Obsoletes Form RGM 400-DS
Although this overhead door is referred to as an option, it is a require­ment for Reznor application (A.G.A. certified to ANSI Z83.17 or C.G.A. approved to CAN 1-3.12).
The switch is a Honeywell Micro-Switch precision limit switch (P/N
124253). The function of the switch is to energize and interlock the heat­ing unit when an outside overhead door reaches approximately 80% of full open travel. The switch will de-energize the furnace when the over­head door closes approximately 20%. The complete door switch includes a limit switch electrically wired to the heater and a roller yoke for me­chanical activation by a field-supplied trigger on the overhead door.
Installation should be done by a qualified agency in accordance with the instructions that follow and in compliance with all codes and require­ments of authorities having jurisdiction. The agency performing this work assumes responsibility for this installation.
All electrical wiring and connections, including electrical grounding MUST be in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in Canada, with the Canadian Electrical Code, Part 1-C.S.A. Standard C22.1. In addition, the installation must comply with local ordinances and applicable gas company requirements.
®
makeup air systems installed in a "door air heater"
Option BX1, Overhead Door Switch (P/N 124253)
REQUIRED FOR ALL DIRECT-FIRED "DOOR AIR HEATER" APPLICATIONS
Switch Models and Specifications, Honeywell
Micro-switch #LSNIA-3P Dimensions 4.2" H x 2.4" W x 1.9" D Electrical Rating 10 Amp continuous at
230, 240, 480 or 600 VAC
60 Amp make and 6 Amp break at 120 VAC
Contacts SPDT maintained, 1 set
normally open and 1 set
normally closed. Ambient Rating 30oF to 240oF Actuation Twin yoke roller lever
(rollers are at a 90o angle) Operating Force 4 lbs NEMA Enclosure 3, 4, 6P and 13
Installation Instructions
Before beginning installation, read both the switch manufacturer's instructions and the "LEFT" and "RIGHT" instructions below. Follow all instruc­tions carefully. In all cases, disconnect both the electrical power and the gas supply from the heater during installation of the door switch.
The switch is tapped for a 1/2" threaded (field-supplied) conduit connection. The electrical connection must be sealed and the switch positioned
so that moisture will not enter through the connection. See switch specifications and heater wiring diagram for electrical information.
For installation indoors on the LEFT side of an automatic overhead door:
WITH DOOR IN CLOSED POSITION. . .
1. Mount the switch and the field-supplied activation trigger in loca-
tions so that mechanical contact will be made when the overhead door is approximately 80% open. Secure the switch through the front using two #10 x 2" long sheetmetal screws or through the back using two #10 x 32 x 2" long studs. Attach field-supplied conduit connec­tion.
2. Loosen the two screws on the front of the switch that retain the termi-
nal access cover. Remove the cover exposing four wire terminals. Pull the appropriate gauge (no smaller than 18 gauge and no larger then 12 gauge) protected control wire through the conduit connection. Attach the conduit. Connect the wires
to pressure terminals #3 and #4. Connect the
ground wire.
3. Using a 9/64" allen
wrench, attach the roller yoke in the position illus­trated in Figure 1. The field-supplied door activa­tion trigger must mechani­cally activate the rollers during both the opening and closing of the over­head door.
©2014 Reznor, LLC. All rights reserved. Printed In the U.S.A. Trademark Note: Reznor 0514 POD OG Form I-OPT-DS (Version 0.1)
®
is registered in the United States and other countries.
Figure 1 - Roller Yoke Position for "Left" Side Installation (Door Closed)
For installation overhead door:
indoors on the RIGHT side of an automatic
WITH DOOR IN CLOSED POSITION. . .
1. Mount the switch and the field-supplied activation trigger in loca-
tions os that mechanical contact twill be made when the overhead door is approximately 80% open. Secure the switch through the front using two #10 x 2" long sheetmetal screws or through the back using two #10 x 32 x 2" long studs. Attach field-supplied conduit connec­tion.
2. Loosen the two screws on the front of the switch that retain the termi-
nal access cover. Remove the cover exposing four wire terminals. Pull the appropriate gauge (no smaller than 18 gauge and no larger then 12 gauge) protected control wire through the conduit connection. Attach the conduit. Connect the wires
to pressure terminals #1 and #2. Connect the
ground wire.
3. Using a 9/64" allen
wrench, attach the roller yoke in the position illus­trated in Figure 2. The field-supplied door activa­tion trigger must mechani­cally activate the rollers during both the opening and closing of the overhead door.
Figure 2 - Roller Yoke Position
for "Right" Side Installation
(Door Closed)
Mfg P/N 124765
Loading...