Reznor B5SM Installation Manual

INSTALLATION INSTRUCTIONS FOR
INSTALLATION
(B4,B5)SM 090/120 SERIES AIR HANDLER
INSTRUCTION
I - Ship ping and Pack ing List
Pack age 1 of 1 con tains:
1 - Economizer As sem bly 1 - Con trols and Wir ing Har ness As sem bly 3 - Wire Nuts 14 - #10 x ½
Check contents for shipping damage. Contact the last carrier immediately if any shipping damage is found.
II - Ap pli ca tion
Economizers are used with Nordyne (B4,B5)SM Series Air Handlers for automatic sensor-controlled introduction of outdoor air into the system through an electro-mechanically controlled damper. Outdoor air is mixed with the buildings return air to economically improve indoor air quality and aide in reducing energy costs.
Economizers can be utilized in either Horizontal or Vertical air handler applications and are easily mounted over the air handler return air and filter frame assembly, The C-7150 Mixed Air Sensor is shipped inside the economizer and must be relocated downstream of the air handler refrigerant coil in accordance with these instructions.
560199
ECONOMIZER USED WITH
FORM # 572D-1210
INDOOR RETURN AIR INLET
ENTHALPY SENSOR
Economizer Sup ply / Re turn Duct Con nec tions:
39.75" Wide x 15.63" High (Outside Flange Dimensions)
Warn ing:
This kit is to be installed by a qualified service technician in accordance with these instructions and all codes having jurisdiction. Failure to follow these instructions could result in serious injury, property damage, or death. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment.
III - In stal la tion
1. DISCONNECT ALL POWER TO THE UNIT.
2. Install and secure the economizer as shown with the air handler in the Horizontal position (Figure 1) or in the Vertical position (Figure 2) using screws (12) provided in the kit.
NOTE: Economizers must be properly supported when
installed with this air handler. Support for the economizer is field supplied and the responsibility of the installer to use methods approved by State or Local mechanical building codes having jurisdiction. For Vertical installations, Nordyne Adjustable Support Leg Kit , SKU # 560258 may be used.
DRIVE MOTOR
W7212 LOGIC MODULE
ELECTRICAL KNOCKOUTS
3. Connect ductwork to the economizer using flanges provided.
Fig ure 1 - (B4,B5)SM Horizontal Application
1
INSTALLATION
(B4,B5)SM 090/120 SERIES AIR HANDLER
INSTRUCTION
4 Remove the economizer control access panel, the air
handler motor access panel, and the air handler control panel cover.
5 Remove the electrical knockout on the economizer
next to the damper motor and the plastic plug on the air handler panel above the control panel, This will allow routing of the economizer control wiring through a length of 1" conduit, or other equivalent means of wire protection based on State or Local codes which covers 24V Class 2 wiring.
6 Cut and discard wire tie securing control wiring bundle
inside the economizer. Remove the two red wires from the C-7150 Mixed Air Sensor and mount the sensor to the divider plate located left of the blower motor assembly as shown in Figure 3 using two screws provided.
Important - DO NOT cut other wires. Inspect bundle for
damaged connections or loose wires.
7. Route the nine economizer control wires from the economizer quick connect plug through the conduit and into the air handler compartment. Route all wires except for the two red Mixed Air Sensor wires into the control panel through the Low Voltage bushing.
8. Connect the two red wires to the Mixed Air Sensor and secure wires away from the blower and motor components.
9. Nordyne air handlers are designed to work with either A/C or Heat Pump outdoor units. Select the proper wiring diagram for this application on Page 5 and 6 to connect the remaining seven economizer control wires to the air handler.
INSTALLATION INSTRUCTIONS FOR
560199
ECONOMIZER USED WITH
ELECTRICAL
KNOCKOUTS
MOTOR ACCESS PANEL
Fig ure 2 - (B4,B5)SM Vertical Application*
CONTROL PANEL
Replace air handler control panel cover and motor access panel.
IV - Op er a tion
Note: These instructions are written for the economizer
to operate with a standard single stage Heat/Cool or Heat Pump thermostat. If 2nd stage mechanical (compressor) cooling is desired a 2 Stage Cool / 1 Stage Heat thermostat is required.
A. Cool ing Mode, Se quence of Op er a tion (Stan dard)
1. On a call for cooling, with ambient temperature and humidity above enthalpy control setpoint, the refrigerant system will operate normally, and damper will open to minimum vent position. See Section VI for
proper set up and adjustments.
2. On a call for cooling, with outdoor ambient temperature and humidity suitable for cooling, enthalpy control will shift stage one cooling control to outside air. The economizer damper will modulate, mixing outside air with return air, to control supply air temperature to approximately 55°F (13°C). If additional cooling is required, the compressor can be energized through second stage of an optional two stage Cooling thermostat. Refer to wiring diagrams for proper connections.
* Air handler shipped from factory for horizontal application. See air handler installation instructions for
conversion from horizontal to vertical application.
2
Fig ure 3 - Mixed Air Sensor Location
MIXED AIR SENSOR
INSTALLATION
INSTRUCTION
INSTALLATION INSTRUCTIONS FOR
560199
ECONOMIZER USED WITH
(B4,B5)SM 090/120 SERIES AIR HANDLER
B. Cool ing Mode, Sin gle Enthalpy Con trol
(Fac tory Stan dard)
The C7400A enthalpy control senses both temperature and humidity or the heat content of the outside air. It controls the amount of outdoor air brought into the system. When the heat content of the outside air is below control setpoint, the control modulates outdoor dampers to meet cooling needs of the building. When the heat content rises above control setpoint, the control closes outdoor dampers to minimum position. The recommended setpoint is “A”. If Economizer is allowing air which is too warm or too humid to enter the system, control may be changed to a lower setpoint (B, C, or D). Refer to
Figure 4 and Figure 5.
C. Heat ing Mode (Heat Pump Ap pli ca tion ONLY)
1. On a call for heat the fresh air damper will
open to the minimum vent position.
V - Economizer Set Up Pro ce dures
Notice to Installer: Proper operation of this economizer when used with an outdoor HEAT PUMP system is dependent on the type
thermostat installed with the unit. Identify which type thermostat is connected to unit before making any wiring changes if needed.
Figure 4
Fig ure 5
(B4,B5)SM air handler economizers come equipped with Honeywell W7212 logic modules which offer additional connections for Demand Control Ventilation (DCV) and Power Exhaust. Contact your local Honeywell or Tradeline representative for additional information on these controls and their specific applications
3